Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia & R. Rebeschini [email protected] [email protected] Trasfor S.A. , Customized Transformers & Inductors 6995-Molinazzo di Monteggio, Switzerland. www.trasfor.com

Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Embed Size (px)

Citation preview

Page 1: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to

Doubly-Fed Induction Generator Based Wind Turbines

D. Aguglia & R. [email protected]@trasfor.ch

Trasfor S.A. , Customized Transformers & Inductors6995-Molinazzo di Monteggio, Switzerland.

www.trasfor.com

Page 2: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Outline

• Motivations - Gearbox failures statistics• Crowbar protection system for DFIG• Worst fault conditions & gearbox mechanical

stress• Series transformer connection as a solutions for

gearbox protection• Adapted specifications for a series transformer• Conclusion

2

Page 3: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Motivations - Gearbox failures statistics

3

Failure frequency Downtime

Data from: J. Ribrant, « Reliability performance and maintenance – A survey of failures in wind power systems », M.Sc. Thesis.

6,7 %13,4 %

5,5 %

17,5 %

5,6 %13,3 %

1,2 %9,8 %

14,1 %

12,9 %

Electrical system

GeneratorBlades /

pitch

Yaw System

Hydraulics

Mechanical Brakes

Gears

Sensors

Control system

Rest

13,3 %

9,4 % 8,9 %

14,3 %

5,3 %

4,4 %1,2 %

19,4 %

5,4 %

18,3 %

Electrical system

GeneratorBlades /

pitch

Yaw system

Hydraulics

Mechanical Brakes

Gears

Sensors

Control system

Rest

• Gears failures issues (data: 2000–2004, Sweden)

Page 4: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Crowbar protection system for DFIG

4

• Main purpose : Power converter protection during grid faults

Specifications impose to remain connected to grid during faults/voltage dips.

Crowbar designed to protect rotor side power converter.This protection system impose an over dimensioning of the gearbox!

Page 5: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Worst fault conditions & gearbox mechanical stress

5

3-phase to ground short-circuit on a 1.5MW DFIG using crowbar protection system.

0 0.05 0.1-5

0

5

Time [s]

Sta

tor

curr

en

ts i s [p

.u.]

0 0.05 0.1

-5

0

5

Time [s]

Ro

tor

curr

en

ts i r [p

.u.]

0 0.05 0.10

0.5

1

1.5

2

2.5

Time [s]

To

rqu

e T

e [p.u

.]

0 0.05 0.1

-500

0

500

Time [s]

Ro

tor

Vo

ltag

e v

r' [V]

(a) (b)

(d)(c)

Worst case at full load operation !

Page 6: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Worst fault conditions & gearbox mechanical stress

6

Phase to ground short-circuit on a 1.5MW DFIG using crowbar protection system.

0 0.05 0.1-4

-2

0

2

4

Time [s]

Sta

tor

curr

en

ts i s [p

.u.]

0 0.05 0.1

-4

-2

0

2

4

Time [s]

Ro

tor

curr

en

ts i r [p

.u.]

0 0.05 0.1-1

0

1

2

Time [s]

To

rqu

e T

e [p.u

.]

0 0.05 0.1-400

-200

0

200

Time [s]

Ro

tor

volta

ge

s v r' [V

]

(a) (b)

(c) (d)

Worst case at full load operation !

Page 7: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Worst fault conditions & gearbox mechanical stress

7

Phase to phase to ground short-circuit (to 0V) on a 1.5MW DFIG using crowbar protection system.

0 0.05 0.1

-5

0

5

Time [s]

Sta

tor

curr

en

ts [p

.u.]

0 0.05 0.1

-5

0

5

Time [s]

Ro

tor

curr

en

ts [p

.u.]

0 0.05 0.1

0

1

2

Time [s]

To

rqu

e [p

.u.]

0 0.05 0.1

-500

0

500

Time [s]

Ro

tor

volta

ge

s V

r' [V]

(a) (b)

(c) (d)

Worst fault! Worst case at full load operation !

Page 8: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Worst fault conditions & gearbox mechanical stress

8

• Summary for crowbar protection system efficiency

– Designed to protect power converter.– Not suitable for gearbox/gears protection.– Implies gearbox over-dimensioning.

Faulty peak torque must be reduced!

Page 9: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Series connection

Series transformer connection as a solutions for gearbox protection

9

Classic shunt connection• Series connection to the grid

Injection of series voltage during Grid voltage dips

Voltage dip seen by DFIG

Faulty DFIG currents and torque attenuated!

Page 10: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Series transformer connection as a solutions for gearbox protection

10

…through H Bridges• Series connection to the grid

Advantages: possibility to compensate unbalances during “normal operation”.

Drawback: more switches!

Page 11: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Series transformer connection as a solutions for gearbox protection

11

• Series connection to the grid…through conventional 2-level power converterAdvantages: classic topology with less switches.

Drawback: difficult to compensate asymmetrical faults.

Page 12: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Adapted specifications for a series transformer

12

• Design specifications of series transformerThe series connection system should be designed taking into account the steady-state and fault operation.

s

P

s

PP

s

sPP

turbrs

turbr

1

1

.

.

• Steady-state analysis

Active power balance imposed

by DFIG! -0.200.20.40.60.8-0.2

0

0.2

0.4

0.6

0.8

Slip [-]

Po

we

r [p

.u.]

Pturb.

Ps

Pr

Turbine’s power is a cubic function of the wind speed

Page 13: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Adapted specifications for a series transformer

13

• Steady-state analysis

gridsturbr

s

gridseriesturbr

IVs

P

s

PP

IVs

sPP

31

31

.

.

DFIG stator current flowing through series transformer : Igrid = Is

-0.2-0.100.10.20.3

-0.5

0

0.5

1

1.5

Slip [-]

Vo

ltag

e [p

.u.]

Vs

Vseries

Vgrid• In hypo-synchronous operation

DFIG stator voltage increases! grid Grid voltage selection issues!

• In hyper-synchronous operation DFIG stator voltage decreases! Series voltage already with the right phase angle. Ready to react against faults!!!

Transformer maximal voltage ~0.5 p.u.

Page 14: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

-0.2-0.100.10.20.30

0.2

0.4

0.6

0.8

1

Slip [-]

Cur

rent

[p.

u.]

Igrid

-0.2-0.100.10.20.3

0

0.2

0.4

0.6

0.8

1

Slip [-]

Cur

rent

[p.

u.]

Is

Ir

Igrid

Adapted specifications for a series transformer

14

• Steady-state analysisTransformer & converter ratings

- Transformer maximal current 1 p.u.!!! - Max voltage 0.5 p.u.- Transformer apparent power increased!!!

Different currents seen by the GSC – losses are not the same!

Page 15: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Adapted specifications for a series transformer

15

• Fault operation analysis

-0.2-0.100.10.20.3

-0.5

0

0.5

1

1.5

Slip [-]

Vo

ltag

e [p

.u.]

Vs

Vseries

Vgrid

Series voltage already in the right polarity & ready for protection during faults.

Worst DFIG operation range for faults behavior

If series transformer rated at 0.5 p.u., possibility to provide 50% of voltage.

That means the worst voltage dip seen by DFIG is 50% only…enough to protect gearbox!

Page 16: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Conclusion

• Crowbar protection system contributes to gearbox mechanical stress – need for over-dimensioning.

• Series transformer topology very interesting for fault ride-through capabilities & decrease of gearbox dimensions.

• Steady-state specifications analysis is enough to guarantee a good series transformer design for gearbox mechanical stress reduction.

• Series transformer will have a slight apparent power increase compared to shunt topology.

Page 17: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Thank you very much!

17

Trasfor S.A. , Customized Transformers & Inductors6995-Molinazzo di Monteggio, Switzerland.

www.trasfor.com

Please refer to our paper for details and contact us:[email protected]@trasfor.ch

Page 18: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Worst fault conditions & gearbox mechanical stress

18

0 0.005 0.01 0.015 0.021

1.5

2

2.5

3

Short-circuit instant [s]

peak

torq

ue [p

.u.]

0 0.005 0.01 0.015 0.02300

350

400

450

500

550

600

650

Short-circuit instant [s]

peak

rot

or v

olta

ge V

r [V

]

• Peak torque & peak rotor voltages depends on fault time occurrence.

Page 19: Power Transformer Role for Gearbox Mechanical Stress Mitigation during Voltage Dips Applied to Doubly-Fed Induction Generator Based Wind Turbines D. Aguglia

Power transformer role & Solutions for new protection systems

19

• As WT size increases, generator’s voltages will be higher and higher.

OR:A power transformer for DFIG rotor connection to the grid will be needed!