Power Quality SolutionsSTATCOM, 100kVAr to 30MVArDynamic reactive power compensation

Page 2: Power Quality Solutions STATCOM, 100kVAr to 30MVAr Dynamic

2 ABB Power Electronics - STATCOM

Dynamic Reactive CompensationProviding stability, security, and reliability to the grid

Installing a STATCOM at one or more suitable points on the network is a powerful and cost effective method to increase grid transfer capability and enhance voltage stability.

What is a STATCOM?A STATCOM (or Static Synchronous Compensator) is a voltage regulating device. It is based on a power electronics voltage-source converter and can act as either a source or sink of reactive AC power. It is a member of the Flexible AC transmission system (FACTS) family which detects and instantly compensates for voltage fluctuations or flicker, as well as controls power factor.

As a fully controllable power electronic device, the STATCOM is capable of providing both capacitive and inductive VARs. ABB’s LV STATCOMs can be rated at up to +/-30 MVAR although larger sizes are possible.

Typical STATCOM applications:

– Utilities with weak grids or fluctuating reactive loads

– Unbalanced loads

– Arc furnaces

– Wind farms

– Wood chippers

– Welding operations

– Car crushers & shredders

– Industrial mills

– Mining shovels, hoists and mills

– Harbor cranes

STATCOM ApplicationsElectrical utilities and heavy industries face a number of challenges related to reactive power. Electrical utilities may be confronted with voltage sags, poor power factor and even voltage instability. Heavy industrial applications can cause disturbances like voltage unbalance, distortion or flicker on the electrical grid. Reactive power control can resolve these issues by improving the power factor or compensating for the voltage instability. In many cases, the traditional solutions of switching capacitors is too coarse and slow to stabilize a weak network.

The most advanced solution to compensate reactive power is to incorporate a Voltage Source Converter (VSC) as a variable source of reactive power. These systems offer advantages compared to standard reactive power compensation solutions in demanding applications, such as wind farms and arc furnaces, where normal reactive power control generated by generators or capacitor banks alone are too slow for the sudden load changes.

3 phase grid

Page 3: Power Quality Solutions STATCOM, 100kVAr to 30MVAr Dynamic

ABB Power Electronics - STATCOM 3

Benefits- Improves power quality and plant reliability- Increases network stability and transmission capacity- Delivers grid compliance when necessary for renewable energy- High availability and reliability

Features- Power factor control- Voltage regulation- Independant phase control- Flicker compensation- Active harmonic filtering (application specific)- Multiple system parallel control- High and low voltage ride through- Modular inverter blocks for simple long term maintenance- Medium voltage transformer included in footprint as option

minimizes installation costs- 200-300% overload capacity

ABB’s STATCOM SolutionEngineered for user simplicity

Page 4: Power Quality Solutions STATCOM, 100kVAr to 30MVAr Dynamic

4 ABB Power Electronics - STATCOM

STATCOM product portfolio

A - System temperature rating depends on housing selection; systems require derating for ambients over 40°C

B - OEM 625 kVar Cabinet solution control cabinet mounted in cabinet if space permits, otherwise separate mounting required

C - 20kV maximum inside enclosure, higher voltage ratings require external installation

D - Application specific overload ratings and duration

Configurations 625 kVar Cabinet 360 - 1900 kVar Rack / NEMA 20’ / 40’ / 53’ Enclosure

Protection class NEMA 1 NEMA 3R 20’ Enclosure 40’ Enclosure

Unit Continous kVar Rating (+ / - ) 80-970 350-1900 2,500-5,000 5,000-10,000

MVAr System applied All configurations can be paralleled to obtain higher ratings needed All configurations can be paralleled to obtain higher ratings needed

AC Grid

AC Grid Voltage Connection 480 V to 46 kV 480 V to 46 kV 46 kV 46 kV

Output Frequency 50 / 60 50 / 60 50 / 60 50 / 60

Harmonic Distortion, Current IEEE compliant IEEE compliant IEEE compliant IEEE compliant

Transient Overload Rating D 200% 200% 200%/250% 200%/250%

Extended overload rating (30 s) 150% 150% 150% 150%

Environmental Limits

Cooling Forced Air Forced Air Forced Air or HVAC Forced Air or HVAC

Ambient Temperature Range (nominal) A 0°C to 40°C -40°C to 50°C -40°C to 50°C -40°C to 50°C

Seismic Rating Zone 4 Zone 4 Zone 4 Zone 4

Housing Options - Dimensions & Weights

A) OEM Package, in (mm) 0°C to 40°C B 32Wx32Dx85H (809x804x2154); 88Wx32Dx97H (2241x800x2464)

128Wx32Dx97H (3241x800x2464)

N/A N/A

B) Indoor Package, in (mm) 0°C to 40°C60Wx40Dx97H (1524x1016x2464); 110Wx40Dx97H (2794x1016x2464)

149Wx40Dx97H (3785x1016x2464)

N/A N/A

C) Outdoor Package, in (mm) -30°C to 40°C60Wx60Dx97H (1524x1524x2464); 110Wx60Dx97H (2794x1524x2464)

149Wx60Dx97H (3785x1524x2464)

240Wx96Dx102H (6096x2438x2591)

480Wx96Dx102H (12192x2438x2591)

Weights, lbs (kg) 3000 (1361); 4100 (1860) 5500 (2495) 30000 (13608) 45000 (20412)

Includes grid-tie transformer in footprint No No Yes C Yes C

Communication Protocol

Ethernet connectivity, Modbus, TCP, DNP-3, SCADA, others possible Ethernet connectivity, Modbus, TCP, DN3-P, SCADA, others possible

Page 5: Power Quality Solutions STATCOM, 100kVAr to 30MVAr Dynamic

ABB Power Electronics - STATCOM 5

Configurations 625 kVar Cabinet 360 - 1900 kVar Rack / NEMA 20’ / 40’ / 53’ Enclosure

Protection class NEMA 1 NEMA 3R 20’ Enclosure 40’ Enclosure

Unit Continous kVar Rating (+ / - ) 80-970 350-1900 2,500-5,000 5,000-10,000

MVAr System applied All configurations can be paralleled to obtain higher ratings needed All configurations can be paralleled to obtain higher ratings needed

AC Grid

AC Grid Voltage Connection 480 V to 46 kV 480 V to 46 kV 46 kV 46 kV

Output Frequency 50 / 60 50 / 60 50 / 60 50 / 60

Harmonic Distortion, Current IEEE compliant IEEE compliant IEEE compliant IEEE compliant

Transient Overload Rating D 200% 200% 200%/250% 200%/250%

Extended overload rating (30 s) 150% 150% 150% 150%

Environmental Limits

Cooling Forced Air Forced Air Forced Air or HVAC Forced Air or HVAC

Ambient Temperature Range (nominal) A 0°C to 40°C -40°C to 50°C -40°C to 50°C -40°C to 50°C

Seismic Rating Zone 4 Zone 4 Zone 4 Zone 4

Housing Options - Dimensions & Weights

A) OEM Package, in (mm) 0°C to 40°C B 32Wx32Dx85H (809x804x2154); 88Wx32Dx97H (2241x800x2464)

128Wx32Dx97H (3241x800x2464)

N/A N/A

B) Indoor Package, in (mm) 0°C to 40°C60Wx40Dx97H (1524x1016x2464); 110Wx40Dx97H (2794x1016x2464)

149Wx40Dx97H (3785x1016x2464)

N/A N/A

C) Outdoor Package, in (mm) -30°C to 40°C60Wx60Dx97H (1524x1524x2464); 110Wx60Dx97H (2794x1524x2464)

149Wx60Dx97H (3785x1524x2464)

240Wx96Dx102H (6096x2438x2591)

480Wx96Dx102H (12192x2438x2591)

Weights, lbs (kg) 3000 (1361); 4100 (1860) 5500 (2495) 30000 (13608) 45000 (20412)

Includes grid-tie transformer in footprint No No Yes C Yes C

Communication Protocol

Ethernet connectivity, Modbus, TCP, DNP-3, SCADA, others possible Ethernet connectivity, Modbus, TCP, DN3-P, SCADA, others possible

Page 6: Power Quality Solutions STATCOM, 100kVAr to 30MVAr Dynamic

6 ABB Power Electronics - STATCOM

Value added solutionsStandard or engineered products

ABB’s containerized solution combines rugged construction with industry leading engineering providing a system that can operate under the harshest environments common in utility, industrial and renewable applications.

ABB’s standard and engineered systems include: – Scalable building block design – Redundant inverter design increases reliability and

availability – Inverter is used in a family of ABB products globally – Containerized solution reduces installation time and

provides mobility – Customer assistance in sizing and modeling of systems – Internal transformer design minimizes installation costs,

optimizes footprint and simplifies testing and commisioning – Modular construction provides for a simplified spare parts

package and fast exchange

Page 7: Power Quality Solutions STATCOM, 100kVAr to 30MVAr Dynamic

ABB Power Electronics - STATCOM 7

Service and supportInstallation, commisioning and life cycle management

Services for ABB‘s STATCOM product – Supervision of installation and commissioning – 24 x 365 local support line – Worldwide service network – Spare parts and logistics network – Training – Customized maintenance contracts – Engineering studies – Remote monitoring

Installation and commissioningProper installation and commissioning of the equipment, done by qualified and certified commissioning engineers, reduces start-up time, increases safety and reliability and decreases life cycle costs.In addition, operators can be given practical training by experienced specialists on site.

Life cycle managementABB’s life cycle management model maximizes the value of the equipment and maintenance investment by maintaining high availability, eliminating unplanned repair costs and extending the lifetime of the whole system. Life cycle management includes: – spare parts and expertise throughout the life cycle – efficient product support and maintenance for improved reliability

– functionality upgrades to the initial product

Global network, local presenceAfter-sales service is an integral part of providing the customer with a reliable and efficient STATCOM system. The ABB Group of companies operates in more than 100 countries and has a worldwide network of service operations.

Page 8: Power Quality Solutions STATCOM, 100kVAr to 30MVAr Dynamic

ABB Inc.Power Electronics16250 W. Glendale DriveNew Berlin, WI 53151Tel: 262-785-3200E-Mail: [email protected]

www.abb.com/powerelectronics

Contact us

Cop

yrig

ht 2

012

AB

B.

All

right

s re

serv

ed.

Sp

ecifi

catio

ns s

ubje

ct t

o ch

ange

with

out

notic

e. P

ES

TATC

OM

-PH

PB

01U

-EN

RE

V A

1