Grid Automation Controller COM600Product Guide

Power Products

Page 2: Power Products Grid Automation Controller COM600 Product Guide

ABB 2

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

Disclaimer

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document.

© Copyright 2012 ABB

All rights reserved.

Trademarks

ABB is a registered trademark of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.

Contents

1. Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2. Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3. Parameter setting . . . . . . . . . . . . . . . . . . . . . . . 5

4. Event and alarm lists . . . . . . . . . . . . . . . . . . . . . 6

5. Disturbance and fault record handling . . . . . . . 6

6. Data historian . . . . . . . . . . . . . . . . . . . . . . . . . 6

7. GOOSE analyzer . . . . . . . . . . . . . . . . . . . . . . . . 8

8. Logic processor . . . . . . . . . . . . . . . . . . . . . . . . 9

9. Access control and substation security . . . . . . 9

10. Substation integration . . . . . . . . . . . . . . . . . . . 9

11. Integration of ABB IEDs . . . . . . . . . . . . . . . . 11

12. Commissioning and troubleshooting . . . . . . 11

13. Communication . . . . . . . . . . . . . . . . . . . . . . . 12

14. Communication redundancy . . . . . . . . . . . . 12

15. Smart Grid . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

16. Technical data . . . . . . . . . . . . . . . . . . . . . . . . 14

17. Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

18. Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

19. Selection and ordering . . . . . . . . . . . . . . . . . 22

20. References . . . . . . . . . . . . . . . . . . . . . . . . . . 24

21. Document revision history . . . . . . . . . . . . . . . 25

Page 3: Power Products Grid Automation Controller COM600 Product Guide

ABB 3

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

Issued: 2012-05-31 Revision: D

1. Description

COM600, the grid automation controller of ABB, is an all-in-one communication gateway, automation platform and user interface solution for utility and industrial distribution substations. The gateway functionality provides seamless connectivity between substation IEDs and network-level control and management systems. The automation platform with its logic processor makes COM600 a flexible implementation platform for substation-level automation tasks. As a user interface solution COM600 accommodates web technology based functionalities providing access to substation devices and processes via a web browser based human machine interface (HMI).

The COM600 design process has been guided by the IEC 61850 standard for com-munication and interoperability of substa-tion equipment. The communication gateway functionality of COM600 supports a variety

of commonly used communication protocols of substation devices. For even greater con-nectivity, OPC data access and OPC alarms and events are supported to enable informa-tion sharing and control with, for example, a distributed control system (DCS).

The IEC 61131-3 based logic processor can be programmed to execute automatic sequences directly via communications media. Further, the logic processor enables the creation of both simple control programs and more so-phisticated applications like load shedding or fault isolation and network restoration.

The COM600 hardware platform is based on ruggedized mechanics with no moving parts subject to wear and tear. Thus, the compact and robust design is well adapted for harsh environments. The preinstalled software and the off-line configuration performed on a separate computer contribute to a faster project execution.

OPC Server

IEC 61850

DNP3 Slave

OPC Client

Web serverHMI application

IEC 61163-3

OPC Client

REMOTECONTROL

Standard web-browser

Configuration tool on a PC

Connectivity packages for ABB IEDs

and/or device profiles

On-l

ine o

pera

tion

Co

nfig

ura

tion p

hase

, o

ff-l

ine

IEC 61850-8-1

REF615REF630

REF 543

REF611

Conf

SCL

Fig. 1 Grid Automation Controller COM600 overview

Page 4: Power Products Grid Automation Controller COM600 Product Guide

ABB 4

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

2. Application

COM600 provides gateway functions for map-ping signals between protection and control IEDs in industrial or utility substations and higher-level systems. It further includes an optional HMI that provides data and information from the substation to the users.

COM600 gathers data from protection and control IEDs and from process devices using different communication protocols. The supported protocols can be combined freely in one station computer, limited only by the number of hardware interfaces and the license. COM600 uses web technology to display data to different users in a professional and user-friendly manner. The optional slave protocols enable the transfer of information to a network control centre (NCC) or distributed control system (DCS).

COM600 benefits from the potential of the IEC 61850 standard by using the IEC 61850-6 substation configuration language (SCL)

and IEC 61850 -7 communications modeling regardless of protocol used. As the IEC 61850 data modeling is used for all communication protocols the gateway cross-reference is done in the same way regardless of the protocol, for example IEC 61850-8-1 or DNP3.

COM600 can by using the optional web HMI (requires Mozilla Firefox®, Opera, Google Chrome or Microsoft Internet Explorer (IE) with Adobe SVG viewer 3.03, if IE 9.0 or later is in use Adobe SVG viewer is not needed) be used for efficient substation visualization, monitoring and control. Measured values from process devices are displayed on the HMI. Single-line diagrams can be used to view any available measured values from the process devices.

All primary single-line diagram (SLD) devices are displayed in one screen. The SLD recognizes different voltage levels and different busbar systems such as single busbar, double busbar and duplex systems. The four-mode busbar coloring visualizes the busbar status. The coloring of the busbar is user configurable.

EMS/SCADA

DMS

Ethernet switch

M2MGateway

TCP/IP protocols(DNP3 or IEC 60870-5-104)

TCP/IP protocols(DNP3 or IEC 60870-5-104)

TCP/IP protocols(IEC 61850)

TCP/IP protocols(DNP3 or IEC 60870-5-104)

Serial protocols(DNP3 or IEC 60870-5-101)

LAN 1

REF615 RIO600REF615 RER620 RER620

RER601 RER601

REF611

Fig. 2 Overview of a utility substation using Grid Automation Controller COM600

Page 5: Power Products Grid Automation Controller COM600 Product Guide

ABB 5

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

The single line diagram can be configured to include an indication for the local/remote selection switch. Alarm symbols and generic symbols can be placed in the SLD to give an even better overview of the status. In addition, generic control buttons can be added to control objects. A separate control dialog is used for controlling the switching device. It provides information on switching device identification, reservation status and interlocking conditions. The select-before-execute logic is used to prevent unintended operation. By reserving the switching device for a single user the risk of controlling the device from two different locations is eliminated. Further, COM600 supports the tap changer function.

Connection examples: COM600 has by default four serial ports. The number of serial ports can be increased using the optional serial card. The four serial ports enable the connection and combination of different serial protocols. For example 3 SPA + 1 IEC 101 protocol or 2 SPA + 1 IEC 103 +1 IEC 101 protocol.

COM600 can be equipped with an optional Ethernet interface. The number of Ethernet interfaces can be increased by choosing the optional Ethernet extension card.

3. Parameter setting

The parameter setting tool (PST) is used for viewing and/or setting parameters in IEDs supporting transparent SPA, Modbus or IEC 61850 parameterization. The PST enables activation of the parameter setting function for the chosen IEDs. In addition, it enables that only selected parameters are shown in the web HMI of COM600 limiting the number of visible parameters to the ones that are con-sidered important for the user. Changes in the settings require that the user has engineering or administrator rights in COM600.

REF615 REF615REF615PLC PLCPLC

Ethernet switchEthernet switch

OPC Server

OPC Client / Server

LOCALHMI

ElectricalSCADA

DISTRIBUTIONCONTROLSYSTEM

Fig. 3 Overview of an industrial system using Grid Automation Controller COM600

Page 6: Power Products Grid Automation Controller COM600 Product Guide

ABB 6

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

4. Event and alarm lists

Events and alarms are identified by date, time, bay, device, object description and status. Furthermore, the events and alarms can be automatically filtered according to voltage level or bay criteria. By default 50 MB of disk space is reserved for events storage. The storage enables recording up to ca. 500 000 events. The amount of disk space reserved for the events can be configured by the user. First-in, first-out logic is used for overwriting events. The user can export an event list to a .csv file for further analysis. COM600 supports printing of events to an Event Printer for long time archiving.

5. Disturbance and fault record handling

COM600 automatically downloads distur-bance records from the connected IEDs. The disturbance records are saved in the stand-ard COMTRADE format. In-depth analysis is enabled using WaveWin ABB software or any other commercially available disturbance record analyzer supporting the COMTRADE

format. Downloading of disturbance records requires use of the IEC 61850-8-1 communi-cation protocol.

COM600 including the optional HMI functionality supports the viewing of fault records from the 611 and 615 series IEDs. The records enable the user to analyze recent power system events. Each record includes current, voltage and angle values, etc. The fault records are marked with consecutive fault numbers and time stamps indicating when the faults were detected.

6. Data historian

The COM600 data historian is a real-time database designed and optimized for process information management and extensive history recording. The data historian is based on ABB’s cpmPlus Knowledge Manager software. It combines the benefits of an easy-to-use real-time database with industrial reliability, performance, and real-time functionality to provide an excellent platform for process information management. The data historian can be used for accurate process performance monitoring

Ethernet switch

RS-232/RS-485 serial links 1 - 8

link 1 link 8

LAN 1Web HMI

LAN 2

Ethernet switch

GPS

IED IED

Fig. 4 Application example

Page 7: Power Products Grid Automation Controller COM600 Product Guide

ABB 7

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

Fig. 5 COM600 web HMI showing persisting and fleeting alarms

Fig. 6 COM600 Data historian

Page 8: Power Products Grid Automation Controller COM600 Product Guide

ABB 8

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

by following process and equipment performance calculations with real-time and history values. Better understanding of the process behaviour by joining time-based process measurements with production and maintenance events helps the user to understand the process dynamics. It further provides required information for learning how to keep the process running. High performance and reliability, together with maintenance-free operation, provide a solid platform for trending. The optional data historian functionality offers means of storing, analyzing and presenting process data.

7. GOOSE analyzer

The COM600 GOOSE Analyzer Tool (GAT) is a professional system-level tool for monitoring and analyzing GOOSE signals in an IEC 61850 station bus. Analyzing of GOOSE signals is based on used System Configuration Description file (SCD). GAT supports commissioning, operation, maintenance and upgrade phases of the system.

GAT consists of a server and a Web-based HMI (Web HMI). The server incorporates GOOSE Connection Viewer and GOOSE Test Manager functionalities. The GOOSE Connection Viewer presents graphically GOOSE signal flow from publishers to sub- scribers on a content page. The Connection Viewer enables real-time diagnosis of the GOOSE signal flow presenting the status of communication between different network devices, eg. IEDs, COM600 and the Remote I/O device RIO600. Further, the viewer provides fast and reliable approach

Fig. 7 GOOSE Connection Viewer

Page 9: Power Products Grid Automation Controller COM600 Product Guide

ABB 9

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

to establish a holistic view of all network devices utilizing GOOSE and the status of the communication between them. The viewer also provides a continuous list of latest sent values and real-time events. Query of historical events is also supported.

8. Logic processor

COM600 offers straightforward approach to the languages specified by the IEC 61131-3 standard for programmable logic controllers (PLC). The programmable logic processor in COM600 is offered as a selectable software option. The PLC programming system enables programming and execution of automation tasks. In addition, the IEC 61131-3 programming in COM600 offers on-line and off-line functionality for engineering and diagnostics.

The logic processor is suitable for post-processing of data from the IEDs and for programmable control of outputs of the IEDs. Any analog or binary data, collected from the IEDs, can be processed in the logic program. The result of the established logic can be displayed in the HMI and sent as a command to an IED or to a remote control center utilizing one of the slave protocols of COM600.

COM600 offers a framework for sequence control. The framework includes HMI functions for controlling and monitoring sequence execution and a logic processor library for creating the sequence logic. With the help of sequences the operator can run control sequences that will operate multiple switching devices, e.g. circuit breakers, sequentially to a certain state.

9. Access control and substation security

To protect COM600 from unauthorized access and to maintain information integrity, COM600 is provided with a four-level, role-based authentication system with administrator-programmable individual passwords for the viewer, operator, engineer and administrator level. Further, the security features include host-based firewalls and communication encryption using the secure HTTPS (hypertext transfer protocol secure) protocol.

10. Substation integration

COM600 provides connectivity to a range of ABB systems. The connectivity to ABB’s low voltage motor control center MNS iS is provided using an OPC server in COM600. COM600 receives data from the MNSiS devices and provides a human-machine interface (HMI) and gateway functionality for a smooth integration. Further, COM600 offers connectivity to ABB’s Automation System 800xA and MicroSCADA by means of OPC or other communication protocols.

Page 10: Power Products Grid Automation Controller COM600 Product Guide

ABB 10

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

M M M

REF615 REF615 REF615 REF615

MLink

DISTRIBUTIONCONTROLSYSTEM

Ethernet switch

Ethernet switch Ethernet switch

GPS

PLANT TCP/IP

7.2 kV

7.2/0.4 kV

0.4 kV

OPC Client/Server

FEEDER 1 FEEDER 2 FEEDER 3

LOCALHMI

Fig. 9 Substation integration

EMS/SCADA

ENGINEERING

Ethernet switch

WAN

LAN 1

ELECTRONIC SECURITY PERIMETER

Built-in firewall

REF 542plus

REF615REF615REF615REF615REF630REF611

Fig. 8 Substation security and secured Web HMI for remote access

Page 11: Power Products Grid Automation Controller COM600 Product Guide

ABB 11

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

OPC Server

IEC 61850

DNP3 Slave

OPC Client

Web serverHMI application

IEC 61131-3

OPC Client

SCADA

REF630

Web HMI

REF615

REF 543

REF611

Ethernet switch

TCP/IP protocols(IEC 61850, DNP3,

Modbus®)

• Simulation of complete IEDs• Source data monitoring• Forcing of source data• GOOSE Analyzer• ...• ...

Fig. 10 Commissioning and troubleshooting

11. Integration of ABB IEDs

COM600 supports ABB’s connectivity package concept which simplifies system configuration and integration of IEDs. A connectivity package is a collection of software and specific IED information, which enable system products and tools to connect and interact with the IED. The connectivity packages reduce the risk of errors in system integration, minimizing device configuration and set-up times. The engineering in COM600 is done by selecting the connectivity package for the IED version and configuration or by importing the configuration file from the IED.

12. Commissioning and troubleshooting

COM600 offers several tools and functions to support efficient commissioning and troubleshooting of the substation. The built-in IED simulation functionality enables testing and verifying of the correct operation of the HMI and gateway configuration of COM600 without any physical connection of IEDs. Further, communication diagnostic events can be enabled to track all messages being sent by or received from the IEDs.

Using the Station Automation Builder SAB600 provided with COM600 on-line diagnostic data, real-time process data, the communication channels and the control function of the IEDs can be analyzed without separate protocol analyzers.

Page 12: Power Products Grid Automation Controller COM600 Product Guide

ABB 12

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

13. Communication

COM600 is designed to support the IEC 61850 standard, and can thereby conveniently be integrated in IEC 61850 systems. Using the IEC 61850-8-1 GOOSE profile COM600 supports GOOSE messaging between the IEC 61850 compliant IEDs and the Station Automation device COM600. Further, COM600 supports GOOSE messaging between several COM600 devices in the system. Apart from IEC 61850, COM600 supports a wide range of master communication protocols. This enables the connection of both IEC 61850 devices and other devices which are not IEC 61850 compliant to the system. For example, native IEC 61850 protection and control IEDs can be connected to COM600 using the IEC 61850 protocol while meters can be connected to COM600 using the Modbus protocol.

Due to the vast amount of by data generated by modern IEC 61850 compliant devices it may in some cases be necessary to limit the amount of information presented to the SCADA-system (Supervisory Control And Data Acquisition) or DCS (Distributed Control System) to avoid unnecessary information overflow. This is achieved by using the cross-reference tool of COM600 when mapping information to slave protocols. Reducing information to higher-level systems not only reduces load but also increases security as it is possible to, for example, disable control to a certain system.

COM600 can be configured as an IEC 61850 proxy server enabling the connection of non IEC 61850 compliant devices to then system. COM600 converts the incoming data according to the IEC 61850 protocol. The IEC 61850 proxy server of COM600 is thereby very useful during for example extensions.

In addition, COM600 offers OPC client and server connectivity. This enables data access and data sharing between the non-electrical system and the electrical system supporting OPC.

14. Communication redundancy

To maintain and improve the reliability of the communication network and the communi-cation between the IEDs and COM600, IEC 62439/PRP (parallel redundancy protocol)-based communication is supported. PRP is based on duplicated networks, where each message is sent via both networks. The first of the received messages is accepted whereas the duplicate is discarded. Message replica-tion and discarding is done by the DuoDriver in COM600. Further, the DuoDriver hides the two networks from upper level applica-tions. IEC 62439/PRP-based communication requires that COM600 is equipped with the optional LAN card and that the IEDs used support PRP.

In addition, COM600 supports switch fault tolerance (SFT) provided that the optional LAN-card and COM600 are connected to two separate switches. SFT creates a failover relationship between the two adapters con-nected to separate switches. The manager responsibility is transferred from one agent to the other in case of a failure. The Switch Fault Tolerance feature of the Intel network adapter requires the Teaming Feature to be enabled.

Page 13: Power Products Grid Automation Controller COM600 Product Guide

ABB 13

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

15. Smart Grid

COM600 can be ordered with a fault detec-tion, fault isolation and load restoration (FDIR) function suitable for radial distri-bution networks. The FDIR function gath-ers data from protection and control IEDs installed in the radial distribution networks and substations and automatically runs a fault detection, fault isolation and load restoration (FDIR) algorithm using the Logic Processor of COM600. The FDIR function continuously updates the network status by receiving switch status and load signals from the IEDs.

When a fault occurs in the network, the FDIR function locates the fault based on switch open and trip information received from the IED of the affected feeder. Further, the FDIR analyzes the network and if the fault is found, the FDIR function isolates the fault from the network. When the fault is isolated the FDRIR function tries to restore supply to the healthy part of the network without overloading the switches or power sources. After the fault has been cleared and the return to normal com-mand has been given the FDIR function sends commands to the IEDs to restore the network to the normal pre-fault condition.

RecloserGridShield

RecloserGridShield

RecloserGridShield

RecloserGridShield

Pole mounted switchdisconnector

Pole mounted switchdisconnector

RecloserGridShield

COM600

RER620

RER620

RER620

RER620

RER620

(NC)

(NO)

(NC)

(NC)

(NC)

(NC)

Load Load

Load Load

Load

Load

(NC)

RER620

RER620

REF615

REF615

Communication

RER620RER620

Fig. 11 Fault detection, fault isolation and load restoration in radial distribution networks

(NC = normally closed, NO = normally open)

Page 14: Power Products Grid Automation Controller COM600 Product Guide

ABB 14

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

Table 2. Power supply

Description Value (Power supply “H”)

Uaux

nominal 110...220 V DC100... 240 V AC (50...60 Hz)

Uaux

variation 80...120% of Un

(88...264 V DC)90...110% of U

n

(90...264 V AC)

Power consumption Typical 32 W (with 110 V DC) ), max. 55 W (with 110 V DC)

Power consumption at start-up 220 W

Table 1. Dimensions

Description Value

Width 251.2 mm (284 mm with mounting kit)

Height 103 mm (114 mm with mounting kit)

Depth 313 mm

Weight 7.7 kg

Table 3. Hardware

Description Value

Processor Core 2 Duo 2.26 Ghz ( P8400)

System memory 4 GB RAM

Compact flash memory 16GB Industrial Compact Flash

Real Time Clock Battery Lithium battery

Table 4. Interfaces

Description Value

Serial interfaces 3 x RS-232 interfaces

Serial interface 1 x RS-232/485 serial interface

Ethernet interfaces 2 x 10BASE-T/100BASE-TX/1000BASE-T RJ-45 interfaces

USB 4 x USB 2.0 interfaces

16. Technical data

Page 15: Power Products Grid Automation Controller COM600 Product Guide

ABB 15

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

Table 5. Optional PCI extensions

Description Value

Serial interfaces 1) 8 x RS-232/485 serial interfaces

Ethernet interfaces 2) 2 x 10BASE-T/100BASE-TX/1000BASE-T RJ-45 interfaces

1) Operating temperature 0° C - +55° C2) Operating temperature 0° C - +55° C

Table 6. Inspection of mechanical structure

Description Reference

Markings and mechanical structure According to IEC 60255-1, -5

Degree of protection by enclosure According to IEC 60529

Clearance and creepage distances According to IEC 60255-5

Table 7. Power supply and module tests

Description Reference

Auxiliary voltage According to IEC 60255-1

Aux. voltage interruptions According to IEC 60255-11

Ripple in auxiliary DC voltage According to IEC 60255-11 15%, f = 2 x fn

Power consumption According to CE EN 61010

Table 8. Insulation tests

Description Reference

Dielectric test According to IEC 60255-5 2 kV, 50 Hz for 1 minute

Impulse voltage test According to IEC 60255-5 5 kV, 1.2/50 μs, 0.5 J

Insulation resistance According to IEC 60255-5>100 MΩ, 500 Vdc

Protective bonding impedance According to IEC 60255-27<0.1 Ω.

Page 16: Power Products Grid Automation Controller COM600 Product Guide

ABB 16

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

Table 9. Electromagnetic compatibility tests

The EMC immunity test level meets the requirements listed below:

Description Reference

1 MHz and 100 kHz burst disturbance test

•Commonmode•Differentialmode

According to IEC 61000-4-18 and IEC 60255-22-1 2.5 kV 1.0 kV

Electrostatic discharge test

•Contactdischarge•Airdischarge

According to IEC 61000-4-2, IEC 60255-22-2 6 kV 8 kV

Radio frequency field immunity According to IEC 61000-4-3 and IEC 60255-22-310 V/m (80% amp.mod.) f=80...2700 MHz 10 V/m (pulse mod.) f=900 MHz

Fast transient

•Powersupply•RJ-45port

According to IEC 61000-4-4 and IEC 60255-22-4 2 kV1 kV

Surge immunity

•Powersupply

According to IEC 61000-4-5 and IEC 60255-22-5 2 kV line-to-earth, 1 kV line-to-line

Conducted radio frequency disturbance According to IEC 61000-4-6 and IEC 60255-22-610 V (80% ampl. mod.) f= 150 kHz...80 MHz

Power frequency (50 Hz) magnetic field According to IEC 61000-4-8, 300 A/m, continuous

Voltage dips and short interruptions According to IEC 61000-4-11 30% reduction for 10 ms 60% reduction for 100 ms 60% reduction for 1000 ms >95% reduction for 5000 ms

Emission tests According to EN 55011, and IEC60255-25, class A

Table 10. Environmental conditions

Description Value

Operating temperature range -25...+70ºC 1) 2)

Relative humidity range, non-condensing 5...95% at +40ºC

Storage temperature -40...+70ºC1) Without any option cards2) With Ethernet option card: 0…+55°C, with Serial option card: 0…+55°C

Page 17: Power Products Grid Automation Controller COM600 Product Guide

ABB 17

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

Table 11. Environmental tests

Description Reference

Dry heat test According to IEC 60068-2-2Test values:•96hat+55ºC•4hat+70ºC

Cold test According to IEC 60068-2-1Test values:•96hat-10ºC•4hat-25ºC

Damp heat test, cyclic According to IEC 60068-2-30Test values:•6cycles(12+12h)at+25…55°C, humidity >93%

Storage test According to IEC 60068-2-48Test values:•72hat+70ºC•72hat-40ºC

Table 12. Mechanical tests

Description Reference

Vibration tests

•Vibrationresponsetest

•Vibrationendurancetest

According to IEC 60068-2-6 and IEC 60255-21-1

f = 10...150 Hz, ± 0.035 mm, 10…58 Hz, 5 m/s2 58…150 Hz

f = 10...150 Hz, ± 0.075 mm, 10…58 Hz, 10 m/s2 58…150 Hz

Shock and bump tests

•Shock response test

•Shock withstand test

•Bump test

According to IEC 60068-2-27 , IEC 60068-2-29 and IEC 60255-21-2

peak acceleration = 5 x gn, pulse duration = 11 ms, numbers of pulses in each diretion = 3

peak acceleration = 15 x gn, pulse duration = 11 ms, number of pulses in each direction = 3

peak acceleration = 10 x gn, pulse duration = 16 ms, number of pulses in each direction = 1000

Page 18: Power Products Grid Automation Controller COM600 Product Guide

ABB 18

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

Table 13. EMC compliance

Description Reference

Complies with the EMC directive 2004/108/EC

Standards EN 50263 (1999), EN 60255-26 (2008)EN 61000-6-2 (2005)EN 61000-6-4 (2007)

Table 14. Product safety

Description Reference

Complies with the LV directive 2006/95/EC

Standards EN 60255-27 (2005), EN 60255-1 (2009)

UL recognized component for USA and Canada UL-file number E 231775

Table 15. RoHS compliance

Description Reference

Complies with the RoHS directive 2002/95/EC

Seismic test

•biaxialmulti-frequencyrandomseismictest

According to IEC 60255-21-3 test method B

2 x gn in horizontal direction, 1 x gn in vertical direction

Table 16. Communication protocols

Master protocol Slave protocol

DNP3 LAN/WAN DNP3 LAN/WAN

DNP3 serial DNP3 serial

IEC 61850-8-1

IEC 60870-5-101 IEC 60870-5-101

IEC 60870-5-103

IEC 60870-5-104 IEC 60870-5-104

IEC 61850-8-1 (MMS & GOOSE) IEC 61850-8-1 (MMS & GOOSE)

MNS iS Connectivity

Modbus Serial Modbus Serial

Modbus TCP Modbus TCP

SNMP (Simple Network Management Protocol)

SNTP (Simple Network Time Protocol) SNTP

SPA SPA Router

Page 19: Power Products Grid Automation Controller COM600 Product Guide

ABB 19

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

Table 17. IEDs with connectivity packages supporting COM600 (applies for the IEC 61850 and SPA protocols)

610 series IEDs

Feeder Protection REF610

Motor Protection REM610

Voltage Protection REU610

611 series IEDs

615 series IEDs

Recloser Protection and Control RER620

Feeder Protection Relay REX 521

SPAJ 140 series relays

Combined Overcurrent and Earth-fault Relay SPAJ 140 C

Combined Overcurrent and Earth-fault Relay SPAJ 141 C

Combined Overcurrent and Earth-fault Relay SPAJ 142 C

Combined Phase and Neutral Overcurrent Relay SPAJ 144 C

Stabilized Differential Relay SPAD 346 C

SACO 16D series units

Digital Annunciator Unit SACO 16D1

Digital Annunciator Unit SACO 16D3

Digital Annunciator Unit SACO 64D4

RE 500 series terminals

Feeder Terminal REF 541 / 543 / 545

Transformer Terminal RET 541/ 543 / 545

Motor and Generator Terminal REM 543 / 545

Feeder Terminal REF 542plus

Table 18. Hardware requirements for SAB600

Hardware Minimum Recommended

Free hard disk space 1 Gb 1 .5Gb

Table 19. Supported operating systems 1)

Description

Microsoft Windows 2000, Windows XP Professional Edition SP2 or later, Windows 2003 Server, Vista, Vista Server 2008, Windows 7

1) Microsoft® .NET Framework 3.5 is required for running SAB600. The software is automatically installed during the installation of SAB600 if not already available on the PC.

Page 20: Power Products Grid Automation Controller COM600 Product Guide

ABB 20

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

Table 21. Tools

Description Version

Station Automation Builder SAB600 4.0

17. Tools

Engineering of COM600 is done offline on a separate computer using the Microsoft® .NET-based SAB600 engineering tool sup-plied with COM600. The configurability and functionality of COM600 depends on the communication protocol used for communi-cation between COM600 and the IEDs. The connectivity packages for ABB’s protection and control IEDs enable an efficient configu-ration of COM600. The connectivity packages include descriptions of the data and signals

available in the IEDs. The descriptions are used to automatically configure the master communication of COM600.

At project engineering SAB600 uses the potential of the IEC 61850 standard by sup-porting the IEC 61850 based SCL (Substation Configuration Description Language) file import, including the import of the communi-cation and graphical parts of the SCL-file. The finalized projects are updated from SAB600 to COM600 at site or remotely provided that a secure Ethernet connection is available.

Table 20. Supported web browsers (Web HMI)

Description Version

Microsoft Internet Explorer (with Adobe SVG viewer 3.03) 1)

6.0 or later

Mozilla Firefox® 3.0

Opera 9

Google Crome 17.x

1) If IE 9.0 or later is in use Adobe SVG viewer is not needed

Page 21: Power Products Grid Automation Controller COM600 Product Guide

ABB 21

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

Fig. 12 Top view Fig. 13 Side view

18. Mounting

The COM600 computer is designed for mounting into a control panel by using the included wall-mount kit. The COM600 is

fastened using the four holes on the unit and four screws.

Page 22: Power Products Grid Automation Controller COM600 Product Guide

ABB 22

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

C O M 6 0 0 H R H 3 2 P P G N N N D

# DESCRIPTION

1 Power supply

110 - 220 V DC, 100 - 240 V AC H

2 Optional communication cards (PCI)

Ethernet card (RJ-45) 10Base-T, 100Base-TX, 1000Base-T, 2 ports

R

Serial RS-232/RS-485 card, 8 ports S

None N

3 HMI

Web HMI H

FDIR (fault detection, fault isolation and load restoration) including FDIR-adapted Web HMI

F

None N

4 Master protocols

One master protocol 1

Two master protocols 2

Three master protocols 3

5 Slave protocols

One slave protocol 1

Two slave protocols 2

None N

6 Optional software

Data historian 1) T

Logic processor L

Data historian and Logic processor 1) P

None N

7 Optional IEC 61850 functionality

IEC 61850 proxy server and GOOSE send enabled 2) P

No optional IEC 61850 functionality N

8 Optional GOOSE Analyzer

GOOSE Analyzer enabled G

No GOOSE Analyzer N

9 Vacant digit

None N

10 Vacant digit

None N

11 Vacant digit

None N

12 Version

Version 4.0 D

1) Requires Web HMI and Internet Explorer 6.0 or later

2) Requires that at least one slave protocol is chosen (digit #5=’’1” or “2”)

19. Selection and ordering

The type and serial number label identifies the COM600 units. The order number consists of a string of code generated from

the hardware and software modules of the unit. Use the ordering key information in Fig. 14 to generate the order number when ordering.

Page 23: Power Products Grid Automation Controller COM600 Product Guide

ABB 23

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

C O M 6 0 0 H R H 3 2 P P G N N N D

# DESCRIPTION

1 Power supply

110 - 220 V DC, 100 - 240 V AC H

2 Optional communication cards (PCI)

Ethernet card (RJ-45) 10Base-T, 100Base-TX, 1000Base-T, 2 ports

R

Serial RS-232/RS-485 card, 8 ports S

None N

3 HMI

Web HMI H

FDIR (fault detection, fault isolation and load restoration) including FDIR-adapted Web HMI

F

None N

4 Master protocols

One master protocol 1

Two master protocols 2

Three master protocols 3

5 Slave protocols

One slave protocol 1

Two slave protocols 2

None N

6 Optional software

Data historian 1) T

Logic processor L

Data historian and Logic processor 1) P

None N

7 Optional IEC 61850 functionality

IEC 61850 proxy server and GOOSE send enabled 2) P

No optional IEC 61850 functionality N

8 Optional GOOSE Analyzer

GOOSE Analyzer enabled G

No GOOSE Analyzer N

9 Vacant digit

None N

10 Vacant digit

None N

11 Vacant digit

None N

12 Version

Version 4.0 D

1) Requires Web HMI and Internet Explorer 6.0 or later

2) Requires that at least one slave protocol is chosen (digit #5=’’1” or “2”)

Fig. 14 Ordering key for Grid Automation Controller COM600

C O M 6 0 0 H R H 3 2 P P G N N N D

# DESCRIPTION

1 Power supply

110 - 220 V DC, 100 - 240 V AC H

24 - 60 V AC L

2 Optional communication cards (PCI)

Ethernet card (RJ-45) 10Base-T, 100Base-TX, 1000Base-T, 2 ports

R

Serial RS-232/RS-485 card, 8 ports S

None N

3 HMI

Web HMI H

FDIR (fault detection, fault isolation and load restoration) including FDIR-adapted Web HMI

F

None N

4 Master protocols

One master protocol 1

Two master protocols 2

Three master protocols 3

5 Slave protocols

One slave protocol 1

Two slave protocols 2

None N

6 Optional software

Data historian 1) T

Logic processor L

Data historian and Logic processor 1) P

None N

7 Optional IEC 61850 functionality

IEC 61850 proxy server and GOOSE send enabled 2) P

No optional IEC 61850 functionality N

8 GOOSE Analyzer

GOOSE Analyzer enabled G

No GOOSE Analyzer N

9 Vacant digit

None N

10 Vacant digit

None N

11 Vacant digit

None N

12 Version

Version 4.0 D

1) Requires Web HMI

2) Requires that at leat one slave protocol is chosen (digit #5=’’1” or “2”)

Example code: C O M 6 0 0 H R H 3 2 P P G N N N D

Your ordering code:

Digit (#) 1 2 3 4 5 6 7

Code: C O M 6 0 0 8 9 10 11 12

Fig. 15 Your ordering code

Page 24: Power Products Grid Automation Controller COM600 Product Guide

ABB 24

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

Fig. 16 Product page

20. References

The www.abb.com/substationautomation portal offers you information about the distribution automation product and service range. You will find the latest relevant information on the COM600 unit on the product page. The download area on the right hand side of the web page contains

the latest product documentation, such as user’s guide, operator’s guide, etc. The Data and Optional features tabs contain product related information in a compact format.

Page 25: Power Products Grid Automation Controller COM600 Product Guide

ABB 25

Grid Automation Controller

COM600

Product version: 4.0

1MRS756764 D

21. Document revision history

Document revision/date

Product version

History

A/19. Feb. 2009 3.3 Document was created

B/26. Nov. 2009 3.4 Content updated to correspond to the product version

C/5. Sep. 2011 3.5 Content updated to correspond to the product version

D/31. May 2012 4.0 Content updated to correspond to the product version

Page 26: Power Products Grid Automation Controller COM600 Product Guide
Page 27: Power Products Grid Automation Controller COM600 Product Guide
Page 28: Power Products Grid Automation Controller COM600 Product Guide

ABB OyDistribution AutomationP.O. Box 699FI-65101 VAASA, FinlandPhone +358 10 22 11Fax +358 10 22 41094

www.abb.com/substationautomation

ABB Inc.Distribution Automation655 Century PointLake Mary, Florida, U.S.A.Phone 407-732-2000Fax 407-732-2335

www.abb.com/substationautomation

1MR

S75

6764

D ©

Cop

yrig

ht 2

012

AB

B. A

ll rig

hts

rese

rved

.

Contact us