22
HWAT ® System Installation and Operation Manual HWAT Hot Water Temperature Maintenance Systems for thermally insulated pipes H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page i

POWER & ENERGY METERS

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

Page 1: POWER & ENERGY METERS

HWAT® SystemInstallation andOperation Manual

HWAT Hot Water TemperatureMaintenance Systems forthermally insulated pipes

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page i

Page 2: POWER & ENERGY METERS

ii iii

Important Safeguards

WARNING: Fire and shock hazard.

Raychem® HWAT® Systems must be installed correctly to ensure proper operation and to preventshock and fire. Read these important warnings andcarefully follow all the installation instructions.• To minimize the danger of fire from sustained

electrical arcing if the heating cable is damaged orimproperly installed, and to comply with TycoThermal Controls requirements, agency certifica-tions, and national electrical codes, ground-faultequipment protection must be used on each heat-ing-cable branch circuit. Arcing may not bestopped by conventional circuit breakers.

• Approvals and performance of the heat-tracing systems are based on the use of Tyco ThermalControls specified parts only. Do not substituteparts or use vinyl electrical tape.

• Bus wires will short if they contact each other.Keep bus wires separated.

• Connection kits and cable ends must be kept drybefore and during installation.

• The black heating-cable core is conductive and canshort. It must be properly insulated and kept dry.

• Damaged bus wires can overheat or short. Do notbreak bus wire strands when preparing the cablefor connection.

• Damaged heating cable can cause electrical arcingor fire. Do not use metal attachments such as pipestraps or tie wire. Use only Tyco Thermal Controlsapproved tapes and cable ties to secure the cableto the pipe.

• Do not attempt to repair or energize damagedcable. Remove damaged cable at once and replacewith a new length using the Raychem RayClic-Ssplice kit. Replace damaged connection kits.

• Use only fire-resistant insulation which is compatible with the application and the maximumexposure temperature of the system to be traced.

Table of Contents

General Information 1

Heating Cable Verification 5

Heating Cable Installation 7

Heat Cable Components 13

Control and Monitoring 15

Thermal Insulation 16

Power Supply and Electrical Protection 18

Commissioning and Preventative Maintenance 20

Test Procedures 23

Troubleshooting Guide 32

Installation and Inspection Record 361110987654321

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page ii

Page 3: POWER & ENERGY METERS

1

General Information11.1 Use of the Manual

This installation and operation manual is for Raychem HWATHot Water Temperature Maintenance systems installed onthermally insulated pipes only.

This manual details how to install and operate an HWAT system. The HWAT System includes the HWAT-Y2 and HWAT-R2 heating cables, RayClic connection kits, and theHWAT-ECO controller. It is important to review this manualand the following documents with the installing contractor:

• HWAT System Product Selection & Design Guide (H57538)

• HWAT System Design Guide (H57510)

• HWAT-ECO Data Sheet (H57339)

• HWAT Heating Cable Data Sheet (H57512)

• RayClic Connection System Data Sheet (H57545)

• HWAT-ECO Installation and Operation Manual (H57340)

For additional information contact:

Tyco Thermal Controls300 Constitution DriveMenlo Park, CA 94025-1164 USATel (800) 545-6258Fax (800) [email protected]

Important: For the Tyco Thermal Controls warranty andagency approvals to apply, the instructions that are includ-ed in this manual and product packages must be followed.

1.2 Safety GuidelinesThe safety and reliability of any heat-tracing system dependson the quality of the products selected, and on properdesign, installation, and maintenance. Incorrect design, handling, installation, or maintenance of any of the systemcomponents can cause underheating or overheating of thepipe, or damage to the heating cable system, and may resultin system failure, electric shock, or fire. The guidelines andinstructions contained in this guide are important. Followthem carefully to minimize these risks and to ensure that theHWAT System performs reliably.

Pay special attention to the following:

• Instructions marked Important

• Safety warnings identified as WARNING

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page iv

Page 4: POWER & ENERGY METERS

General Information1

2 3

General Information11.3 Typical HWAT System

A typical HWAT System is shown is Figure 1 below. Theheating cable is cut to length in the field and is attached tothe pipe with glass tape. A power connection kit connectsthe heating cable bus wires to power in a junction box.RayClic tees and splices accommodate pipe branches toconnect two or three heating cables together. An end sealkit is used to terminate the end of the heating cable. A con-troller is used to set the maintain temperature and improveenergy savings.

Figure 1: Typical HWAT heating cable system

Splice To power

distribution

panel

Note: Partial pipe insulation shown here for clarity.All pipes must be fully insulated

End seal

Tee

Thermalinsulation

Heatingcable

Hot waterheatersensor

Glasstape

Powerconnection

Controller

To BMS

ETLlabel

1.4 Electrical CodesSection 427 of the National Electrical Code (NEC), and Part 1, Section 62 of the Canadian Electrical Code (CEC), inparticular, govern the installation of electrical heat-tracingsystems used on hot water pipes. All installations must bein compliance with this and any other applicable nationalor local codes.

1.5 ApprovalsHWAT-Y2 and HWAT-R2 heating cables, RayClic connec-tion kits, and the HWAT-ECO controller are UL Listed andCSA certified for use in non-hazardous locations. Refer tothe specific product data sheets for details.

1.6 WarrantyTyco Thermal Controls’ standard limited warranty appliesto all products.

An extension of the limited warranty period to ten (10)years from the date of installation is available if a properlycompleted on-line warranty form is completed within (30)days from the date of installation. The extension is validfor the HWAT-Y2 and HWAT-R2 heating cables, RayClicconnection kits and accessories, but not the HWAT-ECO.You can access the complete warranty on www.tycother-mal.com.

1.7 Trade CoordinationInstallation of an HWAT System can involve or impact thework of numerous trades. Therefore, effective and earlycoordination between trades is a critical aspect of allHWAT System Installations. The installation of the heatingcable and connections must be properly scheduled, alongwith the scheduling of the risers and insulation installation.

This guide will assist the installer throughout the installa-tion process and must be reviewed by all affected tradesbefore installation of the HWAT System begins. In a fast-track job, the HWAT System must be considered a criticalpath item: the pipe, heating cable, insulation, and wall-board must all be installed in the proper order, since theheating cable cannot be installed later. If, for example, thewalls go up before the heating cable has been meggered, itmay be necessary to remove the walls in order to repair adamaged or improperly installed system.

Ensuring that the installation of the HWAT System isincluded in the overall construction schedule will helpensure a successful and trouble-free installation.

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 2

Page 5: POWER & ENERGY METERS

Heating Cable Verification2

4 5

General Information12.1 Heating Cables

The HWAT System includes HWAT-Y2 and HWAT-R2 heat-ing cables designed to maintain the piping at specific tem-perature settings with the use of the HWAT-ECO controller.Figure 2 shows the construction of the heating cables.

Figure 2: HWAT-Y2 and HWAT-R2 heating cables

Nickel-plated copper bus wires

Self-regulating conductive core

Polymer-coated aluminum wrap

Tinned-copper braid

Modified polyolefinouter jacket

Modified polyolefin inner jacket

1.8 General Installation NotesRead and observe the instructions in this guide to insurethat the HWAT System is installed successfully.

• Accidental damage to the system can be minimizedduring construction by installing thermal insulation onthe pipe immediately after the pipe has been traced andthe heating cable has been tested.

• Read all installation documentation to familiarize your-self with the system components.

• Read and follow all warnings and recommendations. Allinvolved trades should review this entire guide andassess the recommendations applicable to their scopeof work.

• All heat-traced pipes and equipment must be thermallyinsulated. Insulation is an important part of the HWATSystem. For an effective system, the fiberglass insula-tion must be a specific thickness for each specific pipesize as detailed in Table 2, page 16.

• Do not install the HWAT System below the minimuminstallation temperature. • The minimum installation temperature for HWAT

heating cables is 0°F (–18°C) • The minimum installation temperature for HWAT-ECO

it’s 40°F (5°C).

• Ensure that your water heater temperature is set at yourdesired pipe maintain temperature.

• Do not energize cable when it is coiled or on the reel.

• Never use metal tie wire or pipe straps to secure heat-ing cables to pipes.

Note: Exceeding 150°F (65°C) for HWAT-Y2, or185°F (85°C) for HWAT-R2 will decrease the power out-put of the heating cables over time.

1.9 Tools RequiredFor installing cable and connection kits:

• Utility knife • Diagonal cutters

• Cable cutters • Tape measure

• Screwdriver • Heat gun or propane torch

For testing the heating cable:

• Megohmmeter (Megger) 2500 Vdc

• Multimeter (voltage, resistance and capacitance)

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 4

Page 6: POWER & ENERGY METERS

Heating Cable Installation3

6 7

Heating Cable Selection23.1 Heating Cable Storage

• Store the heating cable in a clean, dry location.Temperature range: –0°F (–18°C) to 140°F (60°C).

• Protect the heating cable from mechanical damage.

3.2 Pre-Installation Checks

Check materials received:

• Review the heating cable design and compare the list ofmaterials to the catalog numbers of the heating cablesand connection kits received to confirm that the propermaterials are on site. The heating cable type is printedon its jacket.

• The HWAT System is limited to 208 V or 240 V servicewhen using the HWAT-ECO controller. Ensure that theservice voltage available is correct.

• Inspect the heating cable and connection kits to ensurethere is no in-transit damage.

• Verify that the heating cable jackets are not damaged byconducting the insulation resistance test (refer toSection 9) on each reel of cable. Do not power the heat-ing cable when it’s on the reel.

Check piping to be traced:

• Make sure all mechanical pipe testing (i.e. hydrostatictesting/purging) is complete and the system has beencleared by the client for tracing.

• Walk the system and plan the routing of the heatingcable on the pipe.

• Inspect the piping and remove any burrs, rough sur-faces or sharp edges.

3.3 Installation• Pay out the heating cable, loosely stringing it along the

pipe, making sure that the cable is always next to thepipe when crossing obstacles.

• Install HWAT heating cable in straight runs along thepipe. Spiraling the heating cable is not necessary.

• If the cable is on the wrong side of an obstacle such asa crossing pipe or I-beam, you will need to reinstall it orcut and splice it.

2.2 Heating Cable SelectionConfirm that the correct HWAT heating cable is selectedbefore installing it on the pipe.

The minimum control setpoint for both HWAT-Y2 andHWAT-R2 is 105°F (40°C). The maximum control setpointfor HWAT-R2 is 140°F (60°C). The maximum control set-point for HWAT-Y2 depends on the voltage and the indoorambient temperature per the charts below.

Figure 3: Design setpoint capability

80(27)

70(21)

60(16)105

(41)110(43)

115(46)

120(49)

Maintain temperature °F (°C)

Ambi

ent t

empe

ratu

re °F

(°C)

125(52)

130(54)

135(57)

140(60)

80(27)

70(21)

60(16)105

(41)110(43)

115(46)

120(49)

Maintain temperature °F (°C)

Ambi

ent t

empe

ratu

re °F

(°C)

125(52)

130(54)

135(57)

140(60)

80(27)

70(21)

60(16)105

(41)110(43)

115(46)

120(49)

Maintain temperature °F (°C)

Ambi

ent t

empe

ratu

re °F

(°C)

125(52)

130(54)

135(57)

140(60)

HWAT-R2208 & 240V

HWAT-Y2240V

HWAT-Y2208V

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 6

Page 7: POWER & ENERGY METERS

Heating Cable Installation3

8 9

Heating Cable Installation3• When installing the heating cable, the cable must not be

compressed or pinched between two objects. Wall andfloor penetrations and pipe hangers are particular areasof concern.

Figure 4: Protecting the heating cable in floor penetrations

• Run insulation through the pipe hanger ensuring thatthe pipe is not resting on the heater.

Figure 5: Pipe hanger with heating cable

• When making floor or wall penetrations, make sure thehole is large enough to accommodate the pipe and thethermal insulation. When sealing around pipes at floorpenetrations, avoid damaging or cutting the heatingcable, or pinching it between the pipe and the concrete.

• The heating cable must not be embedded directly in thesealing material; the pipe should have thermal insulationover it (if allowed by local codes) or the heating cableshould be run through the penetration in a tube or con-duit. If the conduit must be sealed, use a pliable fire-resistant material (Dow Corning Fire Stop, 3M FireBarrier, or T&B Flame-Safe) that can be removed if nec-essary.

Figure 6: Multiple pipe floor penetration

• On vertical piping groups, run the heating cable alongthe inside of the pipe close to other pipes so it will notbe damaged if the pipe hits the side of the floor penetra-tion. Run the heating cable over the outside of the pipesupport. Do not clamp the heating cable to the pipe withthe pipe support.

• In high-rise construction it may be necessary to installthe HWAT System 10 or 12 floors at a time to fit intothe construction schedule. If so, the end of the heatingcable should be sealed with a RayClic-E end seal andplaced in an accessible location. This allows testing ofone part of the heating cable at a time, and allows splic-ing it to another section when the system is complete.

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 8

Page 8: POWER & ENERGY METERS

Heating Cable Installation3

10 11

Heating Cable Installation3Paying out the cable:

• Use a reel holder that pays out smoothly with little tension. If the heating cable snags, stop pulling.

• Keep the heating cable strung loosely but close to thepipe being traced to avoid interference with supportsand equipment.

• Meter marks on the heating cable can be used to determine cable length.

• Protect all heating cable ends from moisture, contamination and mechanical damage.

Figure 7: HWAT cable layout

When paying out the heating cable, AVOID:

• Sharp edges

• Excessive pulling force or jerking

• Kinking and crushing

• Walking on it, or running over it with equipment

WARNING: Fire and shock hazard. Do not installdamaged cable. Connection kits and cable ends mustbe kept dry before and during installation.

Positioning heating cables

If possible, position the heating cable on the lower sectionof the pipe, at the 4 or 8 o’clock positions, as shownbelow, to protect it from damage.

Figure 8: Cable positioning

Attaching the heating cable

Starting from the end opposite the reel, tape the heatingcable to the pipe every 2 feet. Work back to the reel. Leaveextra heating cable at the power connection, at all sides ofsplices and tees to allow for future servicing. See Table 1,page 14.

• Install heating cable connection kits immediately afterattaching the heating cable. If immediate installation isnot possible, protect the heating cable ends from mois-ture.

Bending the cable

When positioning the heating cable on the pipe, do notbend tighter than 1/2” radius. The heating cable does notbend easily in the flat plane. Do not force such a bend, asthe heating cable will be damaged.

Figure 9: Bending technique

1/2"

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 10

Page 9: POWER & ENERGY METERS

1312

Heating Cable Components44.1 General Connection Kit Information

Raychem RayClic connection kits must be used withHWAT heating cables. A complete circuit requires a powerconnection and an end seal. Splices and tees and otherconnection kits are used as needed. Use the HWATSystem Design Guide (H57510) to select appropriate con-nection kits. Installation instructions are included withevery connection kit. Steps for preparing the heating cableand installing connection kits must be followed. HWATconnection kit locations should be noted on “As Built”drawings. Connection kit locations should be marked onthe outside of the insulation cladding with the labels pro-vided in the kits.

Figure 11: RayClic connection system

RayClic-PT

RayClic-PC

RayClic-S

RayClic-X

RayClic-T

RayClic-PS

RayClic-E

Heating Cable Installation3Crossing the cable

HWAT heating cables are self-regulating and may be overlapped whenever necessary without overheating orburning out.

Cutting the cable

Cut the heating cable to the desired length after it isattached to the pipe. HWAT can be cut to length withoutaffecting the heat output per foot.

Attachment tapes

To ensure that the heating cable is in full contact with thepipe, use tape to attach the heating cable to the pipe every2 ft (.6 m). Use Raychem GT-66 attachment tape. One rollwill handle approximately 50 ft (15 m) of cable.

Figure 10: Attaching the heating cable

WARNING: Do not use metal attachments such aspipe straps or tie wire. Do not use vinyl-based electricalor duct tape. Use only Tyco Thermal Controls approvedtapes.

Glass tape(typical)

2 ft.

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 12

Page 10: POWER & ENERGY METERS

14 15

Heating Cable Components4 Control and Monitoring55.1 HWAT-ECO Controller

The Raychem HWAT-ECO controller is designed for useonly with HWAT-Y2 and HWAT-R2 heating cables and mustbe used to ensure proper water temperature.

Refer to the HWAT-ECO Installation and Operation Manual(H57340) for the installation and operation instructions ofthe controller.

Figure 12: HWAT-ECO controller

Connection Kit Installation

• When practical, mount the connection kits on top of thepipe. All heating cable connections must be mountedabove grade level.

• Leave excess cable to serve as a service loop at all con-nection kits (power, splice, cross or tee) for future main-tenance, as detailed in Table 1. The additional heatingcable will easily pay for itself in time savings if itbecomes necessary to check or replace a connection kitafter installation. Splices and tees should have a serviceloop on each of the heating cables entering the connec-tion kit.

Table 1: Service loops for each connection kit

• Provide access to each connection kit to simplify futuresystem modifications and maintenance.

• Locate junction boxes for easy access but not wherethey may be exposed to mechanical abuse.

• Heating cables must be installed over, not under, pipestraps used to secure components.

WARNING: The black heating-cable core is electri-cally conductive and can short. It must be properly insu-lated and kept dry. Damaged bus wires can overheat orshort.

WARNING: Fire and shock hazard. Raychem brandspecified components must be used. Do not substituteparts or use vinyl electrical tape.

RayClic-PC 1 2.0 ft (0.6 m) 2 ft (0.6 m)RayClic-S 2 1.0 ft (0.3 m) 2 ft (0.6 m)RayClic-T 3 1.0 ft (0.3 m) 3 ft (0.9 m)RayClic-X 4 1.0 ft (0.3 m) 4 ft (1.2 m)RayClic-PS 2 1.5 ft (0.5 m) 3 ft (0.9 m)RayClic-PT 3 1.3 ft (0.4 m) 4 ft (1.2 m)RayClic-E 1 NA NA

Connection # of cable Cable length/ Total cable lengthkit name connections/kit connection (Service loop)

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 14

Page 11: POWER & ENERGY METERS

17

Thermal Insulation66.1 Insulating the System

Pipes must be insulated with the correct thermal insulationto maintain the desired pipe temperatures. For pipes 1 1/4inches and smaller, use insulation that is oversized by 1/4inch to allow room for insulating over the heating cables.The thermal insulation schedule is shown in Table 2.

Table 2: Fiberglass insulation schedule

Note: For pipes 3 inches and larger, the thickness ofinsulation can be equal to the pipe diameter with one runof heating cable or 1/3 the pipe diamter with two runs ofheating cable.

6.2 Insulation Installation• Before insulating the pipe, visually inspect the heating

cable and connection kits to ensure they are properlyinstalled and there are no signs of damage. Damagedcable or connection kits must be replaced.

• Check that the insulation type and thickness complieswith the insulation schedule detailed in Table 2.

• Insulate the pipes immediately after the heating cable isinstalled and has passed all tests to minimize damage tothe cable.

• Insulate the pipe at floor and wall penetrations. Failure todo so will cause cold spots in the water system and couldlead to damage to the heating cable. If local codes do notallow this, the heating cable should be run through a con-duit or channel before the firestop is installed. Use a fire-resistant sealing compound such as Dow Corning FireStop, 3M Fire Barrier, or T&B Flame-Safe.

• Do not use staples to close the insulation. Use tape or theadhesive-lined edge of the insulation to ensure that theseam remains sealed. Staples can damage the HWATheating cable.

1/2 3/4 1/2 3/4 1 1 1 1 1/4 1 1 1/4 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 2 2 2 2 1/2 2 1/2 2 1/2 3 3 3

Copper pipe IPS insulation Insulation size (in) size (in) thickness (in)

16

Thermal Insulation6

Figure 13: Sealing the insulation seam

• Mark the location of splices, tees, and end seals on theoutside of the insulation, with labels provided in the kits,while installing the insulation. Use large diameter insula-tion or sheets to cover splices, tees, or service loops.

Figure 14: Insulation labels

• RayClic slices, tees, and end seals must be thermallyinsulated.

• Make sure that all heat-traced piping, fittings, wall pene-trations, and branch piping are insulated. Correct tem-perature maintenance requires properly installed and drythermal insulation. Uninsulated sections of pipe canresult in cold spots.

• After installing insulation, electrical codes require thatyou install “Electric Traced” labels along the piping atsuitable intervals (10-foot intervals recommended) onalternate sides.

WARNING: Use only fire-resistant insulation, suchas fiberglass.

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 16

Page 12: POWER & ENERGY METERS

18 19

Power Supply and ElectricalProtection7 Power Supply and Electrical

Protection77.1 Voltage Rating

Verify that the supply voltage is either 208 or 240 volts asspecified by the HWAT System design.

7.2 Circuit Breaker SizingCircuit breakers must be sized using the cable lengthsshown in Table 3. Do not exceed the maximum circuitlength shown for each breaker size. Use circuit breakersthat incorporate 30 mA ground-fault circuit protection, orprovide equivalent levels of ground-fault protection.

Table 3: Maximum circuit length in feet (meters)

7.3 Electrical LoadingOver-current devices are selected according to the heatingcable type, supply voltage, and circuit length to allow forstart-up. The design specifies the size and type of over-current device. Piping systems are seldom installed exactlyas the drawings show. If changes are made, make surethat all circuit lengths comply with Table 3.

7.4 Ground-Fault ProtectionIf the heating cable is improperly installed, or physicallydamaged to the point that water contacts the bus wires,sustained arcing or fire could result. If arcing does occur,the fault current may be too low to trip conventional circuitbreakers. Tyco Thermal Controls, the U.S. NationalElectrical Code, and the Canadian Electrical Code requireboth ground-fault protection of equipment and a groundedmetallic covering on all heating cables. All HWAT heatingcables meet the metallic covering requirements. Ground-fault protection must be provided by the installer.

15 Amp 350 (105) 250 (75)20 Amp 500 (150) 330 (100)30 Amp 800 (240) 500 (150)

Breaker HWAT-Y2 HWAT-R2Size @208 or 240-volt @208 or 240-volt

WARNING: To minimize the danger of fire from sus-tained electrical arcing if the heating cable is damagedor improperly installed, and to comply with TycoThermal Controls requirements, agency certifications,and national electrical codes, ground-fault equipmentprotection must be used on each heating-cable branchcircuit. Arcing may not be stopped by conventional cir-cuit breakers.

WARNING: Disconnect all power before making con-nections to the heating cable.

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 18

Page 13: POWER & ENERGY METERS

20 21

Commissioning and PreventativeMaintenance8 Commissioning and Preventative

Maintenance8Tyco Thermal Controls requires a series of commissioningtests be performed on the HWAT System. These tests arealso recommended at regular intervals for preventive main-tenance. Results must be recorded and maintained for thelife of the system, utilizing the “Installation and InspectionRecord” (refer to Section 11). Submit this manual with ini-tial commissioning test results to the owner.

Ensure that your water heater and mixing valve tempera-ture are set at your desired pipe maintain temperature.

Note: Exceeding 150°F (65°C) for HWAT-Y2, or 185°F(85°C) for HWAT-R2 will decrease the power output ofthe heating cables over time.

8.1 TestsA brief description of each test is found below. Detailedtest procedures are found in Section 9.

Visual inspection

Visually inspect the pipe, insulation, and connections to theheating cable for physical damage. Check that no moistureis present, electrical connections are tight and grounded,insulation is dry and sealed, and control and monitoringsystems are operational and properly set. Damaged heat-ing cable must be replaced. Once the heating cable isinstalled any repairs to pipes should be done very carefully.The heater must be shielded from excessive heat.Temperatures greater than 185°F will permanently damagethe affected section of heater. Damage due to excessiveexternal heat may or may not effect the operation of theentire circuit. A torch must not be used on the pipe, pipehangers, or riser clamps after the heating cable has beeninstalled on the pipe because this can cause permanentdamage to the heating cable (even if it does not appear tobe burned). Use a saw, not a torch, to cut riser clamps. Ifuse of a torch is unavoidable, cut the fiberglass tape thatholds the HWAT cable to the pipe on either side of the areato be heated, and pull the cable away from the pipe. Makesure you do not cut the HWAT cable. Shield the cable fromthe flame. Charred or damaged cable must be replaced toavoid the risk of arcing or fire.

Figure 15: Shielding the cable from the flame

Insulation Resistance

Insulation Resistance (IR) testing is used to verify theintegrity of the heating-cable inner and outer jackets. IR testing is analogous to pressure testing a pipe anddetects if a hole exists in the jacket.

Power check

The power check is used to verify that the system is gener-ating the correct power output. This test can be used incommissioning to confirm that the circuit is functioningcorrectly. For on-going maintenance, compare the poweroutput to previous readings.

The heating cable power output per foot is calculated bydividing the total wattage by the total length of a circuit.The current, voltage, operation temperature and lengthmust be known. Circuit length can be determined from “asbuilt” drawings, meter marks on the cable or with thecapacitance test. The watts per foot can be compared tothe heating cable output in section 9.4 for an indication ofheating-cable performance:

Ground-fault test

Test all ground-fault breakers per manufacturer’s instructions.

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 20

Page 14: POWER & ENERGY METERS

22 23

Commissioning and PreventativeMaintenance8 Test Procedures9

8.2 Preventative MaintenanceRecommended maintenance for HWAT Systems consistsof performing the system tests for commissioning, and ona regular basis. Procedures for these tests are described inSection 9. Systems should be checked each year. If theHWAT System fails any of the tests, refer to Section 10 fortrouble shooting assistance. Make the necessary repairsand replace any damaged cable immediately. De-energizeall circuits that may be affected by maintenance. Protectthe heating cable from mechanical or thermal damage dur-ing maintenance work.

Maintenance records

The “Installation and Inspection Record,” (refer to Section11) should be filled out during all maintenance and repair-work and kept for future reference.

Repairs

Use only HWAT heating cable, HWAT-ECO controller, andRayClic connection kits when replacing any damaged heat-ing cable system. Repair the thermal insulation to originalcondition or replace with new insulation, if damaged.Retest the system after all repairs or replacements.

WARNING: Damage to cables or components cancause sustained electrical arcing or fire. Do not attemptto repair damaged heating cable. Do not energize cablesthat have been damaged by fire. Replace damaged cableat once by removing the entire damaged section andsplicing in a new length using the appropriate RayClicsplice kits.

9.1 System TestsThe following tests must be done after installing theRayClic connection kits, but before the thermal insulationis applied to the pipe:

1. Visual inspection

2. Insulation resistance (Megger™) test

After the thermal insulation has been installed on the pipe,the following tests must be performed:

1. Visual inspection

2. Insulation resistance (Megger) test

3. Circuit length verification (Capacitance test)

4. Power test

5. Temperature test

All test procedures are described in this manual. It is theinstaller’s responsibility to perform these tests or have anelectrician perform them. Record the results in theInstallation and Inspection Record in Section 11.

1. Visual inspection test

• Check inside all power, splice and tee kits for properinstallation, overheating, corrosion, moisture, or looseconnections.

• Check the electrical connections to ensure that groundand bus wires are insulated over their full length.

• Check for damaged, missing or wet thermal insulation.

• Check that end seals, splices, and tees are properlylabeled on insulation cladding.

• Check HWAT-ECO controller for proper setpoint andoperation. Refer to the HWAT-ECO Installation andOperation Manual for details.

2. Insulation Resistance (Megger) test

Frequency

Insulation resistance testing is required during the installa-tion process, and as part of regularly scheduled mainte-nance, as follows:

• Before installing the cable

• Before installing components

• Before installing the thermal insulation

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 22

Page 15: POWER & ENERGY METERS

24 25

Test Procedures9 Test Procedures9

Figure 16: Insulation resistance test

Insulation Resistance test procedure

1. De-energize the circuit.

2. Disconnect the HWAT-ECO controller if installed.

3. Disconnect bus wires from terminal block.

Test A

L2

L1

Test B

Attach to pipe

• After installing the thermal insulation

• Prior to initial start-up (commissioning)

• As part of the regular system inspection

• After any maintenance or repair work

Procedure

Insulation resistance testing (using a megohmmeter)should be conducted at three voltages; 500, 1000, and2500 Vdc. Potential problems may not be detected if test-ing is done only at 500 and 1000 volts.First measure theresistance between the heating cable bus wires and thebraid (Test A), then measure the insulation resistancebetween the braid and the metal pipe (Test B). Do notallow test leads to touch junction box, which can causeinaccurate readings.

Note: System tests and regular maintenance proce-dures require that Megger testing be performed. Testdirectly from the HWAT-ECO or the junction box closestto the RayClic-PC.

WARNING: Fire hazard in hazardous locations.Megger test can produce sparks. Be sure there are noflammable vapors in the area before performing thistest.

Insulation resistance criteria

A clean, dry, properly installed circuit should measurethousands of megohms, regardless of the heating-cablelength or measuring voltage (500–2500 Vdc). The follow-ing criteria are provided to assist in determining theacceptability of an installation where optimum conditionsmay not apply.

• All insulation resistance values should be greater than1000 megohms. If the reading is lower, consult Section10, Troubleshooting Guide.

Note: Insulation resistance values for Test A and Bfor any particular circuit should not vary more than 25percent as a function of measuring voltage. Greatervariances may indicate a problem with your heat-trac-ing system, confirm proper installation and/or contactTyco Thermal Controls for assistance.

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 24

Page 16: POWER & ENERGY METERS

Figure 17: Capacitance test

4. Power check

The power output of Self-Regulating heating cable is tem-perature-sensitive and requires the following special proce-dure to determine its value:

1. Power the heating cable and allow it to stabilize for 2hours, then measure current and voltage at the junc-tion box. If a controller is used, refer to details below.

2. Check the pipe temperature under the thermal insula-tion at several locations.

3. Calculate the power of the heating cable by multiplyingthe current by the input voltage and dividing by theactual circuit length.

Power (w/ft or m) = Volts (Vac) x Current (Amps)

Length (ft or m)

The power calculated should be similar to the value generated by:

Rated Power (w/ft or m) = Volts (Vac) x Rated Current

Table 5: Rated Current (A/ft or m)

Refer to the HWAT-ECO Installation and Operation Manual(H57340) for controller commissioning tests and records.

HWAT-Y2 125˚F (52˚C) .017 (.056)HWAT-R2 140˚F (60˚C) .009 (.030)

Heating Pipe Rated Current Cable Temperature (A/ft or m)

26 27

Test Procedures9 Test Procedures 94. Set test voltage at 0 Vdc.

5. Connect the negative (–) lead to the heating-cablemetallic braid or RayClic green wire.

6. Connect the positive (+) lead to both heating-cable buswires or RayClic black wires.

7. Turn on the megohmmeter and set the voltage to 500Vdc; apply the voltage for 1 minute. Meter needleshould stop moving. Rapid deflection indicates a short.Record the insulation resistance value in the InspectionRecord.

8. Repeat Steps 4-7 at 1000 and 2500 Vdc.

9. Turn off the megohmmeter.

10. If the megohmmeter does not self-discharge, dischargephase connection to ground with a suitable groundingrod. Disconnect the megohmmeter.

11. Repeat this test between braid and pipe.

12. Reconnect bus wires to terminal block.

13. Reconnect the HWAT-ECO controller.

3. Circuit length verification (Capacitance test)

Connect the capacitance meter negative lead to both buswires and the positive lead to the braid wire. Set the meterto the 200nF range. Multiply this reading by theCapacitance factor for the correct heating cable shownbelow to determine the total circuit length.

Length (ft or m) = Capacitance (nF) x Capacitance factor (ft or m/nf)

Table 4: Capacitance factors

Compare the calculated circuit length to the design draw-ings and circuit breaker sizing tables.

HWAT-Y2 5.0 (1.6)HWAT-R2 5.8 (1.8)

Heating Cable Capacitance Factor ft/nF (m/nF)

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 26

Page 17: POWER & ENERGY METERS

28 29

Test Procedures9 Test Procedures 99.2 Fault Location Tests

There are three methods used for finding a fault within asection of heating cable:

1. Ratio method

2. Conductance method

3. Capacitance method

1. Ratio method

The ratio method uses resistance measurements taken ateach end of the heating cable to approximate the locationof a bus wire short. A shorted heating cable could result ina tripped circuit breaker. If the resistance can be read on astandard ohm meter this method can also be used to finda fault from a bus wire to the ground braid. This type ofshort would trip a GFPD and show a failed Megger read-ing. Measure the bus-to-bus heating-cable resistance ateach end (measurement A and measurement B) of the sus-pected section.

Figure 19: Cable resistance measurement test

The approximate location of the fault, expressed as a per-centage of the heating cable length from the front end, is:

Fault location: D = A x 100(A + B)

Example: A = 1.2 ohmsB = 1.8 ohms

Fault location: D = 1.2 / (1.2 + 1.8) x 100= 40%

The fault is located 40% into the circuit as measuredfrom the front end.

To locate a low resistance ground fault, measure betweenbus and braid.

A B

5. Temperature test

When testing an HWAT System for temperatures it isimportant to test in an appropriate sequence. The HWATSystem is only keeping the water in the pipe hot. It doesnot heat the water. When testing, do not introduce waterfrom the water heater into the system in an area that youhave not yet tested. Testing should start at the point ofuse closest to the water heater and progress out.

Testing should be done after a minimum of 4 hours of nowater usage. This will ensure that the temperatures indi-cated are not due to flow conditions. It is a good idea toturn off all cold water valves to eliminate the possibility ofintroducing cold water to the hot side via a cross connec-tion.

The following example illustrates a typical temperaturetest sequence for an HWAT System.

Figure 18: Typical temperature test sequence

2

3

1

5

4

98

7 10

611

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 28

Page 18: POWER & ENERGY METERS

Figure 20: Low resistance ground-fault test

The approximate location of the fault, expressed as a per-centage of the heating-cable length from the front end is:

Fault location: D = A x 100(A + B)

Example: A = 1.2 ohmsB = 1.8 ohms

Fault location: D = 1.2 / (1.2 + 1.8) x 100= 40%

The fault is located 40% into the circuit as measuredfrom the front end

2. Conductance method

The conductance method uses the core resistance of theheating cable to approximate the location of a fault whenthe heating cable has been severed and the bus wires havenot been shorted together. A severed cable may result in acold section of pipe and may not trip the circuit breaker.

Measure the bus-to-bus heating cable resistance at eachend (measurement A and measurement B) of the suspectsection. Since self-regulating cables are a parallel resis-tance, the ratio calculations must be made using the con-ductance of the cable.

Figure 21: Cable resistance measurement

A B

A B

Braid

30

Test Procedures9The approximate location of the fault, expressed as a per-centage of the heating cable length from the front end, is:

Fault location: D = 1/ A x 100(1/A + 1/B)

Example: A = 100 ohmsB = 25 ohms

Fault location: D = (1/100) / (1/100 + 1/25) x 100= 20%

The fault is located 20% from the front end of the circuit.

3. Capacitance method

This method uses capacitance measurement (nF) asdescribed in section 9.1.3, to approximate the location of afault where the heating cable has been severed, or a con-nection kit has not been connected.

Record the capacitance reading from one end of the heat-ing cable. The capacitance reading should be measuredbetween both bus wires twisted together (positive lead)and the braid (negative lead). Multiply the measured capac-itance with the heating cable's capacitance factor as listedin the following example:

Example: HWAT-R2 = 16.2 nF

Capacitance factor = 5.8 ft/nF

Fault location = 42.2 nF x 5.8 ft/nF = 245 ft (75 m)from reading location

As an alternative, capacitance values from each end. Theratio of one capacitance value taken from one end (A)divided by the sum of both A and B (A + B) and then multi-plied by 100 yields the distance from the first end,expressed as a percentage of the total heating cable circuitlength. See Table 4, page 26, for capacitance factors.

Fault location: C = A x 100(A + B)

31

Test Procedures9

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 30

Page 19: POWER & ENERGY METERS

3332

Troubleshooting Guide10Symptom Probable Causes Corrective Action

Low water temperature Insulation is wet, or missing.

HWAT-ECO controller lowered the pipe setpoint temperature because water heater is cold.

Ambient too low.

Improper voltage applied.

Improper insulation thickness used.

HWAT-ECO was set incorrectly.

Cold water is being introduced into the hot water system.

Tripped circuit breaker

Remove wet insulation and replace with dry insulation, and secure it with proper weatherproofing.

Verify the HWAT-ECO water heater setting, water heater temperature, and sensor placement; and correct as required.

Set the HWAT-ECO to the appropriate ambient temperature.

Refer to the HWAT-ECO Installation and Operation Manual (H57340) to set the HWAT-ECO to the correct voltage (208 or 240 Vac)

Contact your Tyco Thermal Controls representative to confirm the design and modify as recommended.

Refer to the HWAT-ECO Installation and Operation Manual (H57340) for the correct settings.

Verify that the plumbing fixtures and valves are operating properly.

See "Circuit breaker trips" section of this Troubleshooting Guide.

Symptom Probable Causes Corrective Action

Low or no power output Low or no input voltage applied.

The circuit is shorter than the design shows, due to splices or tees not being connected, or the heating cable having been severed.

Improper component connection causing a high-resistance connection.

HWAT-ECO set wrong or incorrectly wired.

The heating cable has been exposed to excessive temperature, moisture or chemicals.

Repair the electrical supply lines and equipment.

Check the routing and length of heating cable (use “as built” drawings to reference actual pipe layout). Connect all splices or tees. Locate and replace any damaged heating cables. Then recheck the power output.

Examine RayClic connection kits for proper installation. Check for loose wiring connections and rewire if necessary.

Refer to the HWAT-ECO Installation and Operation Manual (H57340) for the correct settings.

Check the pipe temperature. Verify heater selection. Check the power output of the heating cable per the design vs. actual. Reduce pipe temperature if possible or contact your Tyco Thermal Controls representative to confirm design.

Replace damaged heating cable. Check the pipe temperature. Check the power output of heating cable.

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 32

Page 20: POWER & ENERGY METERS

3534

Troubleshooting Guide10Symptom Probable Causes Corrective Action

Low or inconsistent insulation resistance

Nicks or cuts in the heating cable.

Short between the braid and heating cable core or the braid and pipe.

Arcing due to damaged heating-cable insulation.

Moisture present in the components.

Test leads touching the junction box.

If heating cable is not yet insulated, visually inspect the entire length for damage, especially at elbows and flanges and around valves. If the system is insulated, remove the connection kits one-by-one to isolate the damaged the section.

Replace damaged heating-cable sections.

If moisture is present, dry out the connections and retest. Be sure all conduit entries are sealed, and that condensate in conduit cannot enter power connection boxes. If heating-cable core or bus wires are exposed to large quantities of water, replace the heating cable. (Drying the heating cable is not sufficient, as the power output of the heating cable can be significantly reduced.)

Clear the test leads from junction box and restart.

Symptom Probable Causes Corrective Action

Circuit breaker trips Circuit breaker is undersized.

Connections and/or splices are shorting out.

Physical damage to heating cable is causing a direct short.

Bus wires are shorted at the end.

Circuit lengths too long

Nick or cut exists in heating cable or power feed wire with moisture present or moisture in connections.

GFPD is undersized (5mA used instead of 30mA) or miswired.

Recheck the design for startup temperature and current loads. Do not exceed the maximum circuit length for heating cable used. Replace the circuit breaker, if defective or improperly sized.

Visually inspect the RayClic connection systems. Replace if necessary.

Check for damage around the valves and any area where there may have been maintenance work. Replace damaged sections of heating cable.

Check the end seal to ensure that bus wires are not shorted. If a dead shoris found, the heating cable may have been permanently damaged by excessive current and may need to be replaced.

Separate the circuit into multiple circuits that do not exceed max circuit lengths.

Replace the heating cable, as necessary. Dry out and reseal the connectionand splices. Using a megohmmeter, retest insulation resistance.

Replace undersized GFPD with 30mA GFPD. Check the GFPD wiring instructions.

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 34

Page 21: POWER & ENERGY METERS

3736

Installation and Inspection Record

Tyco Thermal Controls Industrial Heat-Tracing

Installation and Inspection Record

Facility:

Test Date:

Circuit number:

Heating cable type:

HWAT-ECO setting:

Water heater/mixing valve setting:

Circuit length:Commission

Inspection date:

Visual Inspection

Confirm 30mA ground-fault device (proper rating/function)

Visual inspection inside connection boxes for overheating, corrosion, moisture, loose connections and other problems.

Proper electrical connection, ground, and bus wires insulated over full length.

Damaged or missing thermal insulation; damaged, missing,cracked lagging or weather-proofing.

Covered end seals, splices, and tees properly labeled on insulation.

Check HWAT-ECO for moisture, corrosion, setpoint, switch operation

Insulation resistance (Megger) test M-Ohms

Bus to braid (Test A) 500 Vdc

1000 Vdc

2500 Vdc

Braid to pipe (Test B) 500 Vdc

1000 Vdc

2500 Vdc

Power check

Circuit voltage

Panel (Vac)

Circuit end* (Vac)

Circuit amps after 2 hours (Amps)

Pipe temperature (°F)

Power = (volts x amps after 2 hrs) / circuit length (watts/ft)* Commissioning only

11

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 36

Page 22: POWER & ENERGY METERS

© 2

004

Tyco

The

rmal

Con

trols

LLC

P

rinte

d in

USA

P00

0000

272

H57

548

05

/05

Worldwide HeadquartersTyco Thermal Controls300 Constitution DriveMenlo Park, CA 94025-1164USATel (800) 545-6258Fax (800) [email protected]

CanadaTyco Thermal Controls250 West St.Trenton, OntarioCanada K8V 5S2Tel (800) 545-6258Fax (800) 527-5703

Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product fortheir particular application. Tyco Thermal Controls makes no warranties as to theaccuracy or completeness of the information, and disclaims any liability regardingits use. Tyco Thermal Controls' only obligations are those in the Tyco ThermalControls Standard Terms and Conditions of Sale for this product, and in no casewill Tyco Thermal Controls or its distributors be liable for any incidental, indirect,or consequential damages arising from the sale, resale, use, or misuse of theproduct. Specifications are subject to change without notice. In addition, TycoThermal Controls reserves the right to make changes—without notification toBuyer—to processing or materials that do not affect compliance with anyapplicable specification.

Tyco, Raychem, RayClic, and HWAT are trademarks or registered trademarksof Tyco Thermal Controls LLC or its affiliates.

Megger is a trademark of Megger Limited.

H57548_HWAT_I0M_0804.qxd 5/24/05 3:56 PM Page 38