User’sManual
Manual Change No. 18-0028-E
Oct. 19, 2018
Please use this manual change with the user’s manuals listed below.
1. Applicable User’s Manual and Page
IM No. (Edition) Page Revised contents
IM 01C50T01-02EN(3)
YTA610 and YTA710 Temperature Transmitters (HART Protocol)
Add CAUTION.
Add *2 and *3.
3-15 3.5.3 Burnout Function
3.5.9 Burst ModeTable 4.1 List of Alarms Table 4.1 List of Alarms Table 4.2 Output Operation 4.3 Diagnostics Function
Applicable part
4-34-4
Add *2 and *3.Change Terminal Sensor Fail in Table4.2.
Add NOTE.
4-23-18
Add NOTE. Add CAUTION.
<3. Parameter Setting > 3-15
IM 01C50T01-02EN
(2) Auto Release Time
ThisparametercanbeusedtosettheautoreleasetimeofLoopTestandSimulation(See3.5.14).• ProceduretocallupthedisplayDevicesetup→Diag/Service→TestDevice→AutoReleaseTimeSelectfrom10minutes,30minutes,60minutes,3hours,6hoursor12hours.Defaultsettingis10minutes.
NOTEIfthetransmitterisequippedwiththeintegralindicator,theLCDdisplaysF.O.
3.5.3 Burnout Function
(1) Sensor burnout
Configuretheburnoutmodeinthecaseofsensorfailureordisconnection.• ProceduretocallupthedisplayDevicesetup→Basicsetup→AOBasicSetup→AOSensorBODir:SelectHigh,Low,UserConfigorOff.→AOSensorBOUnit:SelectmAor%→AOSnsBOUsrVal:Outputsusersetvaluewithin3.6to21.6(mA)or-2.5to110(%)Whenthesensorfailureisdetected,thetransmitteroutputsoneofthefollowingvalues.Low:Outputs3.6mAHigh:Outputs21.6mAUser(mA):OutputsusersetvalueinmA.
Settablewithin3.6to21.6mA.User(%):Outputsusersetvaluein%.
Settablewithin-2.5to110%.Off:TheburnoutoutputisNOTdefined
Duringsensorburnouttime,anyofAL.09,AL.10to13orAL.22alarmmessageisgenerated.(SeeChapter4fordetails.)
(2) Burnout in hardware failure
TheoutputstatusofthetransmitterinhardwarefailureissetusingaslideswitchontheMAINassembly.Thecurrentsettingcanbecheckedinparameter“PVAlrmtype”.• Proceduretocallupthe“AOAlrmtypeparameter”displayDevicesetup→Basicsetup→AOBasicSetup→AOAlrmtypHi:Morethan110%output(21.6mA)Lo:Lessthan-5%output(3.2mA)
3.5.4 Integral Indicator Display ModeWhenanintegralindicatorisspecifiedwiththetransmitter,thedisplayitemsanddisplaycyclecanbeconfigured.
(1) Process Variable Display
ProcessvariablesthatcanbedisplayedinYTAareshownintheTable3.1.Acycleofuptofourdisplays(DispOut1,DispOut2,Disp%,DispmA)canbeshownbyassigningvariablestotheparameters.Indicatevaluesofprocessvariableswiththeindicationlimits–99999to99999.
F0305.ai
P SP T F
%
Table 3.1 Process Variable Display
Process variable Disp Out1 Disp Out2Sensor1 Sensor1−Terminal Terminal Sensor2 Sensor2−Terminal Sensor1−Sensor2 Sensor2−Sensor1 Averege SensorBackup PV SV TV QV Notused ─
NOTEEven if abnormality or disconnection of the terminal block temperature sensor occurs, AL22 may not be output and AL04 may be generated.
CAUTIONThere is a time lag between sensor failure and sensor abnormality detection.Since the failed measurement value is output, the current output also becomes undefined.When an error is detected, it becomes the output set with this parameter.However, when sensor burnout is set to OFF, it may be held with indefinite measurement value, so please understanding this point.
<3. Parameter Setting > 3-18
IM 01C50T01-02EN
operation,eveniftheSensor1recovers,thetransmitterwillcontinuetouseSensor2untilthebackupoperationisresetbyparameterorpoweristurnedoff.IfSensor2failsduringbackupoperation,thetransmitterwillsend“BackupSns2Fail”totheintegralindicatorandHARTcommunicatorandoutputthe“Sensorburnout”value.
Buttwosensorsshouldbesametype.Sensorvalue:DisplayinBackup(1) ToenableSensorbackupfunctiona) Setthesensortype,wireandunitforSensor1and2.(See3.4.1)AnySensortypeexcept“Non-connection”canbeselected.
b) MaptheSensorBackupasPV.c) SetthesensorburnouttypetoHigh,Loworusersettingvalue.Ifthesensorburnouttypeissetto“off”,thesensorfailurewillnotbedetectedandthebackupfunctionwillnotact.
Table 3.2 Burst Parameters
Command Parameter Burst Command Burst Msg Trigger
ModeBurst Trigger
Source Burst Trigger Units
PV Cmd1:PV Continuous ─Window PV Dependonthe
assignedvariableto PV
RisingFallingOn-change
LoopCurrentandPercentRange
Cmd2:%range/current Continuous ─Window %range %RisingFallingOn-change
PV,SV,TV,QV Cmd3:Dynvars/current Continuous ─Window PV Dependonthe
assignedvariableto PV
RisingFallingOn-change
DeviceVariable Cmd33:Devicevars Continuous ─ ─Window TopofBurstDevice
VariableDependsonmappingRising
FallingOn-change
DeviceVariablewithstatus
Cmd9:Devicevarsw/status Continuous ─ ─Window TopofBurstDevice
VariableDependsonmappingRising
FallingOn-change
AdditionalDevicestatus
Cmd48:ReadAdditionalDeviceStatus
Continuous ─ ─On-change Allstatus ─
(2) TomakethetransmitterreturntousingSensor1inBackupOperation
b) ProceduretocallupthedisplayDevisesetup→Detailedsetup→SensorSetup→SensorBackup→recoverSensor
c) ConfirmthatSensorBackupStateis“Sensor1 Active”.
3.5.9 Burst ModeWhentheBurstmodeisenabled,thetransmittercontinuouslysendsuptothreedatalistedinTable3.2.WhentheBurstmodeissetto“ON”,transmittercontinuouslysendsalarmsignalalso.WhenchangingthesettingofBurstmode,set“Off”totheBurstmode.Defaultsettingis“Off”.
CAUTIONThere is a time lag between sensor failure and sensor abnormality detection.Since the failed measurement value is output, the current output also becomes undefined.For this reason, until failure of Sensor 1 switches to Sensor 2, or ”Output state at sensor burnout” due to failure of Sensor 2 The output becomes undefined until switching to the output.When an abnormality is detected, it is output according to the measured value of Sensor 2 or "Output state at sensor burnout".
a) ConfirmthattheSensor1isrecovered
• SpecificationsSpecifications:DualinputonlySensorType:Anytypeavailable
<4. Diagnostics > 4-2
IM 01C50T01-02EN
• ProceduretocallupthedisplayDevicesetup→Processvariables→DynamicVariable→PV→ PDQ:PVdataquality→ LS:PVlimitstatusDevicesetup→Processvariables→DeviceVariables→Sensor1→ Sns1PDQ:Sensor1dataquality→ Sns1LS:Sensor1limitstatusAboveprocedureisthesameaboutothervariables.
Table 4.1 List of Alarms
Indicator HART display Cause Output operation during alarm Action
AL.00 CPUFail MainCPUfailed. AccordingtotheBurnoutinHardwarefailureoutputCommunicationdisabled
Replacetheamplifier.
AL.01 SensorNVFail Sensornon-volatilememoryverifiesalarm.
AccordingtotheBurnoutinHardwarefailureoutputCommunicationenabledAL.02 TempNVFail Non-volatilememoryof
TEMPASSYverifiesalarm.AL.03 ADConvFail Inputcircuithardwarefailed.AL.04*2 MainRvrsCalcFail MAINASSYmemoryfailed.AL.05 TempRvrsCalcFail TEMPASSYmemoryfailed.AL.06 TempVoltageFail TEMPASSYvoltagefailed.AL.07 CommNVFail Communicationnon-volatile
memoryverifiesalarm.AL.08 TempNVWarning Non-volatilememoryofthe
TEMPASSYverifiesalarm.Continuetooperateandoutput
AL.09 IntCommFail Internalcommunicationfailed.
AccordingtotheSensorBurnoutoutputCommunicationenabled
AL.10 Sensor1Failure Sensor1failedordisconnectedfromterminalblock.
ReferTable4.2. • Checksensorfordamage.
• Checkterminalconnection.AL.11 Sensor2Failure Sensor2failedor
disconnectedfromterminalblock.
AL.12*1 Sensor1Short Sensor1short-circuited.AL.13*1 Sensor2Short Sensor2short-circuited.AL.14*1 Sensor1 Corrosion Sensor 1 corroded. Continuetooperateand
outputChecksensor,terminal,andcable.AL.15*1 Sensor2 Corrosion Sensor 2 corroded.
AL.20 Sensor1SignalError Sensor1inputisoutofmeasurablerange.
• Checksensorconnection.
• Checksensortypeselected.
AL.21 Sensor2SignalError Sensor2inputisoutofmeasurablerange.
AL.22*3 TerminalSensorFail Terminalblocktemperatureisabnormal.Orterminalblocktemperaturesensorfailed.
ReferTable4.2 Replacetheamplifier.
AL.23 BackupSensor1Fail Duringsensorbackupoperation,Sensor1fails,ithasoutputSensor2.
Operatingtothebackupside.Whenthebackupsidealsofails,outputisaccordingtoburnoutsetting.
Checksensor1fordamage.
AL.24 BackupSensor2Fail Duringsensorbackupoperation,Sensor2fails.
Continuetooperateandoutput
Checksensor2fordamage.
<4. Diagnostics > 4-3
IM 01C50T01-02EN
Indicator HART display Cause Output operation during alarm Action
AL.25 Sensor Drift Sensor drift Continuetooperateandoutput
Checksensorfordamage.
AL.26*1 Sensor1TempCycle TemperaturecyclingtimesofSensor1exceedsthethreshold
Resettempcycleofsensor1.
AL.27*1 Sensor2TempCycle TemperaturecyclingtimesofSensor2exceedsthethreshold.
Resettempcycleofsensor2.
AL.30 OutputTooLow PVvalueisbelowtherangelimitsetting.
Lowerlimit3.68mA(-2%) ChecktheLRVsettingandadjust.
AL.31 OutputTooHigh PVvalueisabovetherangelimitsetting.
Upperlimit20.8mA(105%) ChecktheURVsettingandadjust.
AL.40 Sensor1TempLow Measuredtemperatureofsensor1istolow.
Continuetooperateandoutput
Checksensortypeselected.
AL.41 Sensor1TempHigh Measuredtemperatureofsensor1istohigh.
AL.42 Sensor2TempLow Measuredtemperatureofsensor2istolow.
AL.43 Sensor2TempHigh Measuredtemperatureofsensor2istohigh.
AL.44 AmbTempLow Ambienttemperatureisbelow-40degreeC.
Useaheatertoraisetheambienttemperature,orresettoahigherlevel.
AL.45 AmbTempHigh Ambienttemperatureisabove85degreeC.
Takeenoughdistancefromthesourceofheat,orresettoalowerlevel.
AL.50 LRVTooLow LRVsettingisbelowthesensoroperatingtemperaturerange.
ChecktheLRVsetting.
AL.51 LRVTooHigh LRVsettingisabovethesensoroperatingtemperaturerange.
AL.52 URVTooLow SettingtheURVisbelowthesensoroperatingtemperaturerange.
ChecktheURVsetting.
AL.53 URVTooHigh SettingtheURVisabovethesensoroperatingtemperaturerange.
AL.54 SpanTooSmall Spanisbelowtherecommendedminimumspan.
ChecktheLRVandURVsetting.
AL.60 IllegalPVCfg ThereisasettingalarminthesensorthatismappedtothePV
HoldtheoutputofthepreviousalarmWhenitoccursatstartup,holdat4mA
CheckthePVmapping.
AL.61 IllegalSensor1Cfg Thereisafalsesettosensor1.
Continuetooperateandoutput
Checkthesensor1setting.
AL.62 IllegalSensor2Cfg Thereisafalsesettosensor2.
Checkthesensor2setting.
AL.70 OutputManualMode Underlooptestmode Settingvalueoflooptest Checklooptestmode.
*1: ApplicableonlyforYTA710.*2: AL04 may be generated even when abnormality or disconnection of the terminal block temperature sensor occurs.*3: Even if abnormality or disconnection of the terminal block temperature sensor occurs, AL22 may not be output and AL04 may be generated.
<4. Diagnostics > 4-4
IM 01C50T01-02EN
Table 4.2 Output Operation
Current output mapping Sensor1 Failure Sensor2 Failure Sensor1 Short*3 Sensor2 Short *3 Terminal
Sensor FailSENS.1 SensorBurnout *1 SensorBurnout *1 Output Hold*4
S.1-TER SensorBurnout *1 SensorBurnout *1TERM *1 *1 *1 *1SENS.2 *1 SensorBurnout *1 SensorBurnoutS.2-TER *1 SensorBurnout *1 SensorBurnoutS.1-S.2 SensorBurnout SensorBurnout SensorBurnout SensorBurnoutS.2-S.1 SensorBurnout SensorBurnout SensorBurnout SensorBurnoutAVG SensorBurnout SensorBurnout SensorBurnout SensorBurnoutBACKUP *2 *2 *2 *2
*1: Continuetooperateandoutput.*2: Whenbothsensor1andsensor2occurerror,outputisburnout.*3: ApplicableonlyforYTA710.*4: Fixed output value just before the alarm occurred.
4.2 Logging FunctionsTheYTAserieshavethecapabilitytostorethedatausefulfordiagnosisoftheproblems.
(1) Alarm log
Uptofouralarmhistoriesarestoredinthetransmittermemory,andcanbeseenusingthefollowingprocedures.Callupthedisplay:Devicesetup→Diag/Service→StatusLog
(2) Max/Min log
MinimumvalueandMaximumvalueoftheprocessvariablesarestoredinthetransmittermemoryandcanbechecked.a) Proceduretocallupthedisplay
Devicesetup→Diag/Service→SensorMax/MinLog
b) TocleartheloggeddataforProcessvariablesexceptTermvariables,selectresetSnsMax/Min.
NOTEThesevaluesmaybecomebigbydisconnectionofthesensor,etc.Pleaseresetinthiscase.
(3) Operation Time
Transmitter’soperationtimefromthefirstpower-oniscounted.Callupthe“OperationTime”displaytocheckthetime.Devicesetup→Detailedsetup→Deviceinformation→Date&Time→OperationTime
NOTEOperationTimeissavedevery15minutes.
4.3 Diagnostics FunctionTheYTAhasthefollowingdiagnosticfunctions.
(1) Hardware Failure
ThisfunctiondetectsFailuresofCPU,ADconverter,memory,etc.
(2) Sensor Failure
Thisfunctiondetectsanydisconnectionofsensors.Whenthecurrentisappliedandtheresistanceofasensorisabovethethreshold,thefunctionoutputsadisconnectionalarm.Parametersetting:NotnecessaryAlarmoutput:Whentheresistanceisabovethethreshold,thefunctionoutputsthealarmofSensor1Failure(AL.10)orSensor2Failure(AL.11).
(3) Terminal block Failure
ThisfunctiondetectsanydisconnectionatCJC.WhenitdetectsthattheresistanceofCJCisabovethethreshold,thefunctionoutputsanalarm.Parametersetting:NotnecessaryAlarmoutput:Whentheresistanceisabovethethreshold,thefunctionoutputsthealarmofTerminalSensorFail(AL.22).
NOTEEven if abnormality or disconnection of the terminal block temperature sensor occurs, AL22 may not be output and AL04 may be generated.
Output Hold*4
Output Hold*4
Output Hold*4
Output Hold*4
Output Hold*4
Output Hold*4
Output Hold*4
Output Hold*4