PlantSuite RDBMS to PI Interface via ODBC Driver for Windows NT (Intel, ALPHA) Version 2.08

PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Embed Size (px)

Citation preview

Page 1: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

PlantSuiteRDBMS to PI Interface

via ODBC Driver

for Windows NT (Intel, ALPHA)

Version 2.08

Page 2: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

How to Contact UsPhone (510) 297-5800 (main number)

(510) 297-5828 (technical support)

Fax (510) 357-8136

Internet [email protected]

World Wide Web

http://www.osisoft.com

Bulletin Board

(510) 895-9423Telebit WorldBlazer modem (Hayes, MNP, or PEP compatible)8 data bits, 1 stop bit, no parity, up to 14400 bps downloadprotocols: Xmodem, Ymodem, Zmodem, Kermit

Mail OSI Software, Inc.P.O. Box 727San Leandro, CA 94577-0427USA

OSI Software GmbH Hauptstrae 30 D-63674 Altenstadt 1Deutschland

OSI Software, LtdP. O. Box 8256Level One, 6-8 Nugent StreetAuckland 3, New Zealand

Unpublished -- rights reserved under the copyright laws of the United States.RESTRICTED RIGHTS LEGEND

Use, duplication, or disclosure by the Government is subject to restrictions as set forth in subparagraph (c)(1)(ii) of the Rights in Technical Data and Computer Software clause at DFARS 252.227-7013

Trademark statement—PI is a registered trademark of OSI Software, Inc. Microsoft Windows, Microsoft Windows for Workgroups, and Microsoft NT are registered trademarks of Microsoft Corporation. Solaris is a registered trademark of Sun

Microsystems. HP-UX is a registered trademark of Hewlett Packard Corp.. IBM AIX RS/6000 is a registered trademark of the IBM Corporation. DUX, DEC VAX and DEC Alpha are registered trademarks of the Digital Equipment Corporation.

document.doc

1999 OSI Software, Inc. All rights reserved777 Davis Street, Suite 250, San Leandro, CA 94577

Page 3: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Table of ContentsIntroduction........................................................................................................................1

Functionality......................................................................................................................3Input of Data from a Relational Database into PI.............................................................4

Input Query strategies.............................................................................................................4

Output of Data from PI into a Relational Database..........................................................8

SQL Statements...............................................................................................................11Language Requirements................................................................................................11

SQL Placeholders..........................................................................................................12

Mapping of Placeholder Data Types to SQL Data Types..............................................15

Timestamp Format.........................................................................................................16

Inputs to PI via the SELECT Clause..............................................................................17

Data acquisition strategies.............................................................................................20

SQL SELECT Command for Retrieving Data for Single PI Tag....................................20

SQL SELECT Command for Retrieving Data for Tag Groups.......................................22

SQL SELECT Command for Tag Distribution via Tagname Key...................................24

Event based Input..........................................................................................................27

Multistatement SQL Clause...........................................................................................28

Stored Procedures.........................................................................................................29

Outputs from PI via Update and Insert Clause..............................................................30

Data Output for DIGITAL Points....................................................................................31

Data Output for INTEGER Points..................................................................................32

Data Output for REAL and String Points........................................................................33

Global Variables.............................................................................................................33

Data Mapping between PI and RDBMS..........................................................................37Mapping of SELECT Data Types to PI Point Types – Data Input..................................37

Evaluation of STATUS Field for All PI Data Types - Input from RDBMS.......................39

Storage of PI POINT Database Changes.......................................................................41

March 15, 1997 iii

Page 4: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

PI Batch Database Output..............................................................................................47

Database specifics..........................................................................................................49Oracle 7.0.......................................................................................................................49

Oracle RDB....................................................................................................................49

Oracle 8.0.......................................................................................................................50

dBase III, dBase IV........................................................................................................50

MS Access.....................................................................................................................51

MS SQL Server 6.5........................................................................................................51

MS SQL Server 7.0........................................................................................................51

PI Point Configuration.....................................................................................................53

Performance Point...........................................................................................................59

IO Rate Tags.....................................................................................................................61

Interface Files..................................................................................................................63

Installation........................................................................................................................65

Updating the Interface.....................................................................................................67

Startup..............................................................................................................................69Command line switches for the RDBMS to PI interface.................................................69

Detailed explanation for command line parameters.......................................................70

Startup as console application.......................................................................................76

Startup as Windows NT Service....................................................................................76

PILOGIN.INI...................................................................................................................77

Shutdown.........................................................................................................................79

Error and information messages...................................................................................81

Hints for PI System Manager..........................................................................................83

Interface Test Environment............................................................................................85

More Examples................................................................................................................87Insert or Update.............................................................................................................87

Limitations and future enhancements...........................................................................89

OSI Software, Inc. iv

Page 5: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

IntroductionThe Interface allows bi-directional transfer of data between the PI System and any relational database that supports ODBC (Open Database Connectivity) drivers. The Interface runs on Windows NT (Server or Workstation) and Windows95 operating systems and is able to connect to any PI Server node, available in the network.

This version of the Interface only supports one ODBC connection per running copy (but it is possible to use multiple instances of this connection). SQL statements are generated by the end user in form of ASCII files or are defined in the Extended Descriptor of a PI Tag. SQL statements can serve as a source of data for one or more PI Tags defined in the PI database.

The Interface generates exception reports for all associated tags.

The PI Interface makes internal use of the PI-API-NT in order to keep a standard way of interfacing from a client node to the PI Server Node.

The interface runs under Windows NT Server or Workstation, Intel or ALPHA Platform. This machine runs either a PI3 Server Node or the PI-API Node and can connect to any PI Node in the network.

Databases and ODBC drivers not yet tested with our interface may require additional onsite testing which will translate to additional charges. Please refer to the section entitled “Interface Test Environment” for a list of databases and ODBC drivers that the interface is known to work with. Even if your database and/or ODBC driver is not shown, the interface still may work. However, if you experience problems, the interface will need to be enhanced to support your environment. Please contact your OSI sales representative.

Page 6: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Supported Features

Order Code PI-IN-OS-RELDB-NTPI-IN-OS-RELDB-NA

Interface Platforms supported Windows NT 4 or higher(Intel, ALPHA)

Vendor Software Required Yes

Vendor Software minimum requirements ODBC 3.x Driver Manager

Level 1 ODBC APIMINIMUM Grammar

Sign up for Updates Yes

Exception Reporting Yes

PI API Node Support Yes

UNIINT No

Input Scan based, Event Trigger

Outputs Event based

Text Transfer Yes

Configuration Data Output

Multiple Links Yes

Failover No

Number of Points Unlimited

Page 7: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

FunctionalityThe Interface runs on Windows NT operation system as a Console Application or as Service. It uses the standard PI-API-NT to connect to the PI Server node. The Interface Computer must have the related ODBC driver installed and configured to be able to connect to the specified database. A DSN (Data Source Name) must be configured via the ODBC Administrator. The DSN name is passed in the startup arguments of the Interface. In case of ODBC connection failure the Interface will try to reconnect to the RDBMS (see specific note in the Management section).

SQL queries are provided by the user in form of either ASCII files, which are read after startup of the Interface into the memory, or as definition in the Extended Descriptor of a tag. SQL statements are executed according to the scan class type (cyclic or event driven). When data is read from a relational database, the Interface will try to convert the result set of the query into a value, status or timestamp appropriate for the related PI Tag. The opposite direction - writing data out of the PI system works accordingly.

In the current version the Interface supports the following general features:

Support of Timestamp, Value, Status and String fields in RDB Tables

Support of string tags

Query data (read) for single tag, one value per scan, with or without timestamp from RDB

Query data (read) for single tag, time series per scan

Query data (read) for multiple tags (Tag Group), one value per tag per scan, with or without timestamp from RDB

Query data (read) for multiple tags (Tag Group), time series per tag per scan

Query data (read) via Tagname Key (Tag Distribution), time series per tag per scan

Scan or Event based SELECT queries

Event based UPDATE DELETE and INSERT queries

Support of multiple statements per query

Support of stored procedures

Support of ‘runtime placeholders’ Timestamp (Scan Time, Snapshot Time,...), Value, Status

Support of all classic ‘point attribute’ placeholders (except userint and userreal)

Support of placeholders for Value, Status, Timestamp of foreign Tag (Tag outside interface point source)

Support of ‘batch’ placeholders

Storage of point attribute (type classic) changes in RDB

Recovery options for output points

Plant Suite RDBMS to PI Interface 3

Page 8: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Input of Data from a Relational Database into PIThe SQL statement can be considered as a source of both, timestamp and value for the PI Point. Each SQL statement retrieves data from RDB and the Interface sends the results into the PI database - to the particular point. There can be multiple statements in one query as well as there are different strategies used for transforming the result set.The Interface can also define a group of tags, which share one SQL statement and the result set of the query will be distributed to all tags in a group (see chapter “SQL SELECT Command for Retrieving Data for Tag Groups”). It reduces the number of the ODBC calls and thereby increases performance.

Input Query strategies

Query for single tag – one value per scan

There are DCS systems that can keep current values in a relational table. Via scan based queries it is possible to emulate the same behavior like a scan based DCS interface. An example is getting data from an ABB IMS station.

The disadvantages for this kind of data retrieval are low performance and accuracy limited to scan frequency.

Example 1.1 – query single tag:

Page 9: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statement(file PI_REAL1.SQL)

SELECT PI_TIMESTAMP,PI_VALUE,PI_STATUS FROM PI_REAL1 WHERE PI_KEY_VALUE = ?;

Relevant PI Point Attributes

Extended Descriptor

Location1 Location2 Location3 Location4 Location5

P1=”Key_1234” 1 0 0 1 0

Instrumenttag Pointtype

PI_REAL1.SQL Float32

RDB Table Design

PI_TIMESTAMP PI_VALUE PI_STATUS PI_KEY_VALUE

Datetime (MS SQL Server)

Date/Time (MS Access)

Real (MS SQL Server)

Number-Single Precision (MS Access)

Smallint (MS SQL Server)

Number-Whole Number (MS Access)

Varchar(50) (MS SQL Server)

Text(50) (MS Access)

Query for single tag – multiple values per scan

A good strategy for high data throughput is to have low scanning rates (e.g. 1 minute) instead of doing one query every second.

This assumes that we are not scanning updated records (values that went into the RDB via UPDATE statements and that do overwrite the current value).

Instead we assume that we can query the RDB for a time period (e.g. 1 minute) and expect that new data (stored by INSERT statement) appear there.

In other words getting the same amount of data in one call is faster than getting it in many calls.

A typical high throughput query is given below. In this example we get all data since ‘snapshot’ time.

Example 1.2 – query data array for single tag:

Plant Suite RDBMS to PI Interface 5

Page 10: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Functionality

SQL Statement(file PI_STRING1.SQL)

SELECT PI_TIMESTAMP,PI_VALUE,0 FROM PI_STRING1 WHERE PI_TIMESTAMP > ?;

Relevant PI Point Attributes

Extended Descriptor

Location1 Location2 Location3 Location4 Location5

P1=TS 1 1 0 1 0

Instrumenttag Pointtype

PI_STRING1.SQL String

RDB Table Design

PI_TIMESTAMP PI_VALUE PI_STATUS

Datetime (MS SQL Server)

Date/Time (MS Access)

Varchar(1000) (MS SQL Server)

Text(255) (MS Access)

Smallint (MS SQL Server)

Number-Whole Number (MS Access)

A typical low throughput query is:

SELECT TIMESTAMP, VALUE, STATUS FROM DATA WHERE NAME= ?;

P1=AT.TAG, Location2=0

Here we get only the current value. The interface works very similar to an online DCS interface.

Note: SQL syntax and parameter description is given later in this manual.

Query data in Tag Groups

Another way of improving performance compared to single value read is grouping tags together. This might be possible if the data is somehow related, e.g. when transferring LAB data and all data come from the same sample and have the same timestamp or if the RDB table is structured in the way that multiple values are stored for the same record (table has multiple value fields).

Querying Tag Groups can also be combined with getting complete time series per scan. The limitation is in the fact that a timestamp field must be present and that only one timestamp is available per data record. The particular group is formed by tags, using the same Instrumenttag point attribute.

Example 1.3 – three points used are of PI data type Int32:

OSI Software, Inc. 6

Page 11: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statement(file PI_INT_GROUP1.SQL)

SELECT PI_TIMESTAMP, PI_VALUE1, PI_STATUS1 ,PI_VALUE2,PI_STATUS2, PI_VALUE3,0 FROM PI_INT_GROUP1 WHERE PI_TIMESTAMP > ?;

Relevant PI Point Attributes

Extended Descriptor

Location1

All points

Location2

All points

Location3 Location4

All points

Location5

All points

P1=TS 1 1 Target point1 2

Target point2 4

Target point3 6

1 0

Instrumenttag Pointtype

PI_INT_GROUP1.SQL

Int32

RDB Table Design

PI_TIMESTAMP PI_VALUEn PI_STATUSn

Datetime (MS SQL Server)

Date/Time (MS Access)

Smallint (MS SQL Server)

Number-Whole Number (MS Access)

Smallint (MS SQL Server)

Number-Whole Number (MS Access)

Tag Distribution

Compared to Tag Groups where grouping happens in form of columns, Tag Distribution means multiple records per query while each record can contain data for a different tag. To achieve this, a field must be provided in the query which contains the tagname or the alias tagname.

This option is very efficient for getting exception-based data from an RDB table where it is unknown how many data will arrive per single tag. We only know that there will typically be an average number of data records per scan.

Only one ‘distributor’ point carries the SQL statement. This point does not receive any actual data, instead the number of rows successfully delivered to according PI tags get stored in the distributor tag.

The target points are selected either according to Tagname (value retrieved in PI_NAME column should match the Tagname of the point) or according to /ALIAS=Some_key definition found in the Extended Descriptor of the particular point.

Plant Suite RDBMS to PI Interface 7

Page 12: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Functionality

Example 1.4 – query database for tags, matching a wildcard:

SQL Statement(file PI_REAL_DISTR1.SQL)

SELECT PI_TIMESTAMP, PI_NAME, PI_VALUE, PI_STATUS FROM PI_REAL_DISTR1 WHERE PI_NAME LIKE ‘Key_%’ ;

Relevant PI Point Attributes

Extended Descriptor

‘Distributor’

Location1

All points

Location2

All points

Location3 Location4

All points

Location5

All points

P1=TS 1 0 ‘Distributor’ -1

‘Target points’ 0

1 0

Instrumenttag

‘Distributor’

Pointtype

All points

PI_REAL_DISTR1.SQL

Float32

RDB Table Design

PI_TIMESTAMP PI_VALUE PI_STATUS PI_NAME

Datetime (MS SQL Server)

Date/Time (MS Access)

Real (MS SQL Server)

Number-Single Prec.(MS Access)

Varchar(12) (MS SQL Server)

Text(12) (MS Access)

Varchar(80) (MS SQL Server)

Text(80) (MS Access)

Output of Data from PI into a Relational DatabaseMoving data from PI to a relational database is accomplished similar to input. The relational database can receive timestamp, value and status of a PI point as well as all actual values of attributes addressable by placeholders (see chapter “SQL Placeholders” ). For copying new data to the relational database, usage of standard event based output points are supported. In this case the source tag should be provided as a source of actual data and the output point itself gets the copy of the exported data to verify output operation. If the output operation reports a failure (ODBC SQLExecute() fails), the output point gets a status of Bad Output.

Note: Besides Bach Database Output, all output tags are event based output. If scan based output is required, an equation tag can provide frequent events. Another alternative is to use a stored procedure and use a scan based input tag.

OSI Software, Inc. 8

Page 13: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Example 2.1 – insert 2 different sinusoid values into table:

SQL Statement(file PI_SIN_VALUES_OUT.SQL)

INSERT INTO PI_SIN_VALUES_OUT (PI_NAME1, PI_TIMESTAMP1, PI_VALUE1, PI_STATUS1, PI_NAME2,PI_VALUE2,PI_STATUS2) VALUES (?,?,?,?,?,?,?);

Relevant PI Point Attributes

Extended Descriptor Location1 Location2 Location3 Location4 Location5

/EXD=…path…\ pi_sin_values_out.plh

Content of the above stated file:

P1=AT.TAG P2=TS P3=VL P4=SS_I P5='SINUSOIDU'/AT.TAG P6='SINUSOIDU'/VL P7='SINUSOIDU'/SS_I

1 0 0 0 0

Instrumenttag Pointtype

All points

Sourcetag

PI_SIN_VALUES_OUT.SQL

Float16 SINUSOID

RDB Table Design

PI_TIMESTAMPn PI_VALUEn PI_STATUSn PI_NAMEn

Datetime (MS SQL Server)

Date/Time (MS Access)

Real (MS SQL Server)

Number-Single Precision (MS Access)

Smallint (MS SQL Server)

Number Whole Number (MS Access)

Varchar(80) (MS SQL Server)

Text(80) (MS Access)

Plant Suite RDBMS to PI Interface 9

Page 14: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL StatementsSQL statements can be generated out of ASCII files, placed in the directory specified by /SQL=path keyword found in the start-up file. Names of these files are arbitrary (the recommended form is ‘filename.SQL’). The name of an associated ASCII file for a particular point is stated in the Instrumenttag attribute. When the Instrumenttag field is blank, the Interface will look for the SQL statement definition in the Extended Descriptor denoted by the keyword /SQL = “valid SQL statement;“. Each file can contain a sequence of SQL commands separated by the ‘;’ separator and all these particular statements will be examined consecutively.

Here is an example of such a definition:

/SQL=“SELECT PI_TIMESTAMP,PI_VALUE,0 FROM TABLE1 WHERE PI_TIMESTAMP>?“ P1=ST

Note: The entire statement definition text has to be double-quoted (“ ”).

Note: The Extended Descriptor attribute is limited to 80 characters. Therefore only short statements can be given by this method.

Language RequirementsThe level of conformance of the used ODBC API is checked while the Interface starts-up. The Interface requires the ODBC driver to be least of Level 1 API conformance and used SQL statements should be of the MINIMUM Grammar conformance. The information of the conformance levels (both API and Grammar) are written into the log-file. If the API conformance of some ODBC driver is less then Level 1, the Interface stops.

The Interface supports the following Data Manipulation Language commands that can be used in SQL queries:

SELECT [ALL,DISTINCT] select-list

FROM table-reference-list

[WHERE search-condition]

[order-by-clause]

INSERT INTO table-name [(column-identifier[,column-identifier]...)] VALUES (insert-value[,insert-value]...)

UPDATE table-name SET column-identifier ={expression} [,column-identifier ={expression}]...[WHERE search-condition]

Page 15: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

DELETE FROM table-name [WHERE search-condition]

The check-up of SQL statements against a relational database is expected to be done by the user. If the syntax of some SQL statement is not proper, the Interface writes down an error message and the tag (and each related tag e.g. tags which share the same SQL command) is excluded from the interface list.

The Interface allows testing of a particular tag against the relational database, having the /TEST=Tagname keyword in the start-up file (See chapter “Detailed explanation for command line parameters ”).

Note: It is highly recommended to test a new query for the interface with MS Query first.The query produced by MS Query can mostly directly be stored in the query file, required by the interface. Current versions of MS Query also support placeholders (‘?’), so that even complex queries can graphically be produced and tested before used in the RDBMS interface.

SQL PlaceholdersThe concept of placeholders allows passing runtime values, timestamps of various formats and other configurable parameters (point attributes defined in PIPONT database) into the SQL statement on places marked by ‘?’. Question marks are only allowed on places in the SQL statement where they are syntactically correct e.g. in the search condition part of the SQL SELECT command, in the argument list of stored procedures, e.t.c. Placeholders are defined in the tag’s Extended Descriptor and should be separated by spaces. The assignment of runtime values (retrieved from the PI system) to the SQL statement is done according to the position of the placeholder. That means that the first definition of a runtime placeholder refers to the first question mark found in the SQL statement. If more space (more than 80 characters) is required for placeholder definition, a new keyword “/EXD=filename” was introduced. This construct allows extending the Extended Descriptor with the contents of the specified file.

The list and syntax of placeholder definitions is as follows:

Placeholder Keywords for Extended Descriptor

Meaning / Substitution in SQL query Remark

Snapshot placeholders

Pn=TS Timestamp taken from the PI Snapshot (detailed description see chapter “Timestamp Format ”)

Pn=LST Timestamp, Last Scan-Time (Scan Time = start time of this scan class)

Pn=ST Input: Timestamp = Start of a new scan for all members of this scan classOutput: Timestamp = Time of the output event

Pn=LET Timestamp, Last Execution Time, Execution Time = exact time when query finished

This time is different to LST depending on how much time passed between start of scan for

Page 16: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Placeholder Keywords for Extended Descriptor

Meaning / Substitution in SQL query Remark

the class and execution of this particular tag.Since queries can be very time consuming, this time difference should not be underestimated.

Pn=VL Current value

Pn=SS_I Current status in the form of integer representation

Pn=SS_C Current status in the form of digital code string Max. 12 characters

Pn=’tagname’/VL Current value of the tag ‘tagname’

Pn=’tagname’/SS_I

Pn=’tagname’/SS_C

Current status of the tag ‘tagname’

Max. 12 characters

Pn=’tagname’/TS Timestamp taken from the PI Snapshot of the tag ‘tagname’

PI point database placeholders

Pn=AT.TAG Tag name of the current tag Max. 80 characters

Pn=AT.DESCRIPTOR Descriptor of the current tag Max. 26 characters

Pn=AT.EXDESC Extended Descriptor of the current tag Max. 80 characters

Pn=AT.ENGUNITS Engineering units for the current tag Max. 12 characters

Pn=AT.ZERO Zero of the current tag

Pn=AT.SPAN Span of the current tag

Pn=AT.TYPICALVALUE Typical value of the current tag

Pn=AT.DIGSTARTCODE Digital start code of the current tag

Pn=AT.DIGNUMBER Number of digital states of the current tag

Pn=AT.POINTTYPE Point type of the current tag Max. 1 character

Pn=AT.POINTSOURCE Point source of the current tag Max. 1 character

Pn=AT.LOCATION1 Location1 of the current tag

Pn=AT.LOCATION2 Location2 of the current tag

Pn=AT.LOCATION3 Location3 of the current tag

Pn=AT.LOCATION4 Location4 of the current tag

Pn=AT.LOCATION5 Location5 of the current tag

Pn=AT.SQUAREROOT Square root of the current tag

Pn=AT.SCAN Scan flag of the current tag

Pn=AT.EXCDEV Exception deviation of the current tag

Pn=AT.EXCMIN Exception minimum time of the current tag

Pn=AT.EXCMAX Exception maximum time of the current tag

Pn=AT.ARCHIVING Archiving flag of the current tag

Pn=AT.COMPRESSING Compression flag of the current tag

Plant Suite RDBMS to PI Interface 13

Page 17: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statements

Placeholder Keywords for Extended Descriptor

Meaning / Substitution in SQL query Remark

Pn=AT.FILTERCODE Filter code of the current tag

Pn=AT.RES Resolution code of the current tag

Pn=AT.COMPDEV Compression deviation of the current tag

Pn=AT.COMPMIN Compression minimum time of the current tag

Pn=AT.COMPMAX Compression maximum of the current tag

Pn=AT.TOTALCODE Total code of the current tag

Pn=AT.CONVERS Conversion factor of the current tag

Pn=AT.CREATIONDATE Creation date of the current tag

Pn=AT.CHANGEDATE Change date of the current tag

Pn=AT.CREATOR Creator of the current tag Max. 12 characters

Pn=AT.CHANGER Changer of the current tag Max. 12 characters

Pn=AT.RECORDTYPE Record type of the current tag

Pn=AT.POINTNUMBER Point ID of the current tag

Pn=AT.DISPLAYDIGITS Display digits after decimal point of the current tag

Pn=AT.SOURCETAG Source tag of the current tag Max. 80 characters

Pn=AT.INSTRUMENTTAG Instrument tag of the current tag Max.32 characters

PI point change placeholders

Pn=AT.ATTRIBUTE Changed attribute Max. 32 characters

Pn=AT.NEWVALUE New value Max. 80 characters

Pn=AT.OLDVALUE Old value Max. 80 characters

PI batch database placeholders

Pn=BA.UNIT Batch unit Max. 80 characters

Pn=BA.BAID Batch identification Max. 80 characters

Pn=BA.PRID Batch product identification Max. 80 characters

Pn=BA.START Batch start time

Pn=BA.END Batch end time

Miscellaneous

Pn=”any-string” Double quoted string (without white characters)

No limit

Note: Pn denotes Placeholder number (n) and will be used as P1 P2 P3 …

Example for Extended Descriptor referring to an SQL statement using 3 placeholders:

P1=TS P2=SS_I P3=AT.TAG

OSI Software, Inc. 14

Page 18: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

If the same placeholder definition is used multiple times in a query, it is possible to shorten the definition string, using a back reference.

Example: P1=TS P2=VL P3=P1

Note: Placeholders like SS_I or SS_C can also be used in SELECT statements, e.g. to serve as index. One should know that for tags of type real or integer containing valid data (value is not in error and therefore is not a digital state), SS_C would use the Digital State at position 0 of the System Digital State Table. See chapter “Evaluation of STATUS Field for All PI Data Types - Input from RDBMS”. The default value for PI3 at position 0 is “??????????”

Mapping of Placeholder Data Types to SQL Data TypesPlaceholders also represent values, which get stored into database fields. Those fields must be of certain data types. In order to assist database administrators in setting-up correct tables, here is a list of how the interface maps Placeholders to SQL data types.When testing against different databases and ODBC drivers, we found that it is helpful to automatically support more than one data-type. For example integer fields in dBase appear as data type SQL_DOUBLE while most of the databases use SQL_INTEGER.

Placeholder and PI Data Type SQL Data Type

Snapshot placeholders

VL for real tags SQL_REALIf error SQL_FLOAT

VL for integer tags SQL_INTEGERIf error SQL_FLOAT

VL for digital tags SQL_VARCHAR

VL for string tags SQL_VARCHAR

SS_I for all PI data types points SQL_INTEGERIf error SQL_FLOAT

SS_C for all PI data types points SQL_VARCHAR

TS,ST,LET,LST for all PI data types points SQL_TIMESTAMP

PI point database placeholders

AT.TAG, AT.DESCRIPTOR, AT.EXDESC, AT.ENGUNITS, AT.POINTTYPE , AT.POINTSOURCE, AT.CREATOR , AT.CHANGER, AT.SOURCETAG, AT.INSTRUMENTTAG, AT.ATTRIBUTE, AT.NEWVALUE, AT.OLDVALUE, “any_string”

SQL_VARCHAR

AT_DIGSTARTCODE, AT_DIGNUMBER, AT_LOCATION1, AT_LOCATION2, AT_LOCATION3, AT_LOCATION4, AT_LOCATION5, AT_SQUAREROOT, AT_SCAN, AT_EXCMIN, AT_EXCMAX, AT_ARCHIVING,

SQL_INTEGER

If error SQL_FLOATIf error SQL_DOUBLE

Plant Suite RDBMS to PI Interface 15

Page 19: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statements

Placeholder and PI Data Type SQL Data Type

AT_COMPRESSING, AT_FILTERCODE, AT_RES, AT_COMPMIN, AT_COMPMAX, AT_TOTALCODE, AT_RECORDTYPE, AT_POINTNUMBER, AT_DISPLAYDIGITS,

AT_TYPICALVALUE, AT_ZERO, AT_SPAN, AT_EXCDEV, AT_COMPDEV, AT_CONVERS

SQL_REALIf error SQL_FLOAT

PI batch database placeholders

BA.UNIT

BA.BAID, BA_PRID

SQL_VARCHAR

BA.START, BA.END SQL_TIMESTAMP

If the ODBC driver used supports Level 2 Conformance (actually the ODBC driver must support SQLDescribeParam(), which is a Level 2 function), the interface can query the ODBC driver for the SQL Data Type. In this case a wider range of conversions can be supported.

Timestamp FormatThe time format used in various databases is not the same. ODBC drivers do the corresponding data type transformation and so the only mandatory rule is to use the appropriate timestamp format in the particular relational database.

Note: The interface expects the ‘full timestamp’ (date+time) to be read from the relational database.

The interface offers these time references to populate placeholders:

Keyword Time used

Input:

TS Timestamp from PI Snapshot of a particular point.

(Due to the Exception Reporting mechanism in the interface it does not always correspond to the visible PI Snapshot)

E.g. SELECT … WHERE PI_TIMESTAMP > ?; P1=TS : this allows scanning relational database only for newly arrived values (rows) independent of the scan frequency.

LST Last Scan-Time Scan Time is the time a Scan Class starts a new scanning period

This can be used to limit the amount of data.Events are skipped if older timestamped data arrive in a RDB table.

ST Time before query executions.A good example is to transfer future data from RDB. Only data before ST can be transferred to PI.

LET Time when the previous query was finished

OSI Software, Inc. 16

Page 20: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Keyword Time used

Output:

TS Timestamp from current PI Snapshot of source tag

ST At interface startup - ST=Snapshot TimeFrom that time on - ST=event time

When interacting with a relational database, some SQL commands (SELECT) may take a while when executing and some data transfer to PI can therefore be delayed. When the scan class is scheduled for a particular time and the real start time is delayed for more than 2 seconds (e.g. because of some long SQL operation preceded) the whole scan is skipped and an error message is written into the log-file.

The Interface offers ‘scheduled time’ (ST) which is used when a relational database does not have the timestamp available and the program should join some appropriate time to send to PI.

Last execution (LET) and last scheduled time (LST) would allow new data to be moved since the last scan. On Interface start-up both timestamps are preset with PI Snapshot Time.

Note: On interface startup LST and LET are preset with PI Snapshot timestamps.

Note: For Input Tags TS will be taken from the internal Interface snapshot. This is not the same as the PI Snapshot since Exception Reporting runs on the interface side. If for example the value is stable for a long time, the PI Snapshot will not be updated with scanned data as long no exception occurs.Not using the PI Server Snapshot Timestamp will avoid getting data between PI Server Snapshot time and Interface internal Snapshot time multiple times for queries of type“SELECT … WHERE Timestamp > ?” and P1=TS.

Note: All PI related timestamps are synchronized to the PI Server time.

Inputs to PI via the SELECT ClauseFor passing values in direction to PI, it is necessary to have a SELECT statement defined. Data obtained by ODBC API calls are distributed to the relevant PI points according to the specified ‘distribution strategy’ (see chapter “Data acquisition strategies ”).

The SELECT statement can return NULL values for any column. The interface uses the following algorithm to handle this:

If timestamp is NULL, the scheduled time (ST) is used instead.

If status is NULL and the returned value is not NULL then the value is valid.

When both value and status are NULL the ‘No Data’ digital state is used to convey the information that the expected value is absent.

The Interface accepts integer and string data types for digital tags and status values. When an integer is provided the interpretation is given by the PI-API:

If negative, this is an absolute state value.

Plant Suite RDBMS to PI Interface 17

Page 21: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statements

If zero or positive, this is an offset into the defined range of digital states.

Example 3.1 – query integer data for Digital PI tag:

SQL Statement(file PI_DIGITAL1.SQL)

SELECT PI_TIMESTAMP,PI_VALUE_INT,PI_STATUS_INT FROM PI_DIGITAL1 WHERE PI_KEY_VALUE = ?;

Relevant PI Point Attributes

Extended Descriptor

Location1 Location2 Location3 Location4 Location5

P1=”Key_1234” 1 0 0 1 0

Instrumenttag Pointtype

PI_DIGITAL1.SQL Digital

RDB Table Design

PI_TIMESTAMP PI_VALUE_INT PI_STATUS_INT PI_KEY_VALUE

Datetime (MS SQL Server)

Date/Time (MS Access)

Smallint (MS SQL Server)

Number-Whole Number (MS Access)

Smallint (MS SQL Server)

Number-Whole Number (MS Access)

Varchar(50) (MS SQL Server)

Text(50) (MS Access)

If the value, that should be interpreted as status or value for a digital tag, is retrieved in the string form, the interface checks the Digital State Table and performs the substitution.

OSI Software, Inc. 18

Page 22: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Example 3.2 – query string data for Digital PI tag:

SQL Statement(file PI_DIGITAL2.SQL)

SELECT PI_TIMESTAMP,PI_VALUE_STR,PI_STATUS_STR FROM PI_DIGITAL1 WHERE PI_KEY_VALUE = ?;

Relevant PI Point Attributes

Extended Descriptor

Location1 Location2 Location3 Location4 Location5

P1=”Key_1234” 1 0 0 1 1

Instrumenttag Pointtype

PI_DIGITAL2.SQL Digital

RDB Table Design

PI_TIMESTAMP PI_VALUE_STR PI_STATUS_STR PI_KEY_VALUE

Datetime (MS SQL Server)

Date/Time (MS Access)

Varchar (12) (MS SQL Server)

Text(12) (MS Access)

Varchar (12) (MS SQL Server)

Text(12) (MS Access)

Varchar(50) (MS SQL Server)

Text(50) (MS Access)

The SELECT statement usually returns a set of data records, which fulfil the desired search condition. When the relational database also provides a timestamp, then it is possible to setup a query like this:

SELECT TIMESTAMP, VALUE, STATUS FROM TABLE WHERE TIMESTAMP > ?; P1=LST

Normally we put all returned records into PI. Sometimes however, it is desirable to get only the first record from the result set and write it into PI. The distinction is made by the Location2 parameter.

Location2 Bulk option

0 Only the first record is valid

1 The interface tries to put all the returned data into PI

Note: It is important to provide records with timestamps sorted in ascending order. Only in this case the PI System can support Exception Reporting and Compression. Use SELECT … ORDER BY TIMESTAMP; if necessary.

An example for Location2=0 might be to request the maximum or minimum of a list of values with timestamps between 2 scan periods. The way to achieve this (in addition to Location2=0) is sorting the SELECT(ed) data in descending or ascending order.

Plant Suite RDBMS to PI Interface 19

Page 23: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statements

Data acquisition strategiesTo interpret records obtained by SELECT statement in a flexible way, we have defined different data acquisition strategies. The strategy can be selected by Location3 parameter of the PI tag.

Location3 Data acquisition strategy

0 SQL query populates a Single PI Tag

> 0 Selects Tag Group mode

Location3 points to the column number of a multiple field querywhere the selected column contains data for this tag

-1 Selects Tag Distribution modeThe SQL statement must return a key to denote the particular point

SQL SELECT Command for Retrieving Data for Single PI Tag

Fixed Positions of Columns Used in SELECT Statement

To get values from a relational database, which will be stored in one PI point, the following field sequence should be kept:

SELECT [Timestamp,] Value, Status FROM...

If provided, the Interface always expects the Timestamp field to be in the first position followed by the Value and Status columns. The Interface detects a Timestamp field by checking the field data type against SQL_TIMESTAMP. If a database does not support timestamps, (e.g. dBase IV, there are ways to convert other field types in the query. See also chapter Database specifics.

Valid combinations of Timestamp, Value and Status in a SELECT statement are:

SELECT Timestamp,Value,Status FROM...

SELECT Value,Status FROM...

Note: The Interface expects the Status column to be provided in form of a constant (zero) in the SELECT list when the database does not have any notion of the status code. (SQL allows using such a constant that is then interpreted as the PI status code). E.g. SELECT Value,0 FROM …

Note: The above stated rule applies to all PI data types.

Arbitrary Positions of Columns Used in SELECT Statement - Aliases

If the used ODBC driver supports aliases, e.g. if we can use the SELECT statement in the form:

SELCT SAMPLE_TIME AS PI_TIMESTAMP, SAMPLE_VALUE AS PI_VALUE …

there are following keywords defined to ‘re-name’ the columns used in the relational database:

PI_TIMESTAMP, PI_TAGNAME, PI_VALUE, PI_STATUS.

The Interface recognizes and assigns the fields appropriately. In this case there is no need to have fixed positions of column names in the SELECT statement.

OSI Software, Inc. 20

Page 24: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Note: In debug mode, the Interface prints out the information to the log file, whether the ODBC driver supports aliases or not. (Debug level 1 /deb=1)

Example 3.3 – field name keywords for single tag:

SQL Statement(file PI_STRING2.SQL)

SELECT VALIDITY AS PI_STATUS, SCAN_TIME AS PI_TIMESTAMP, DESCRIPTION AS PI_VALUE FROM PI_STRING2 WHERE KEY_VALUE = ?;

Relevant PI Point Attributes

Extended Descriptor

Location1 Location2 Location3 Location4 Location5

P1=”Key_1234” 1 0 0 1 0

Instrumenttag Pointtype

PI_STRING2.SQL String

RDB Table Design

SCAN_TIME DESCRIPTION VALIDITY KEY_VALUE

Datetime (MS SQL Server)

Date/Time (MS Access)

Varchar(1000) (MS SQL Server)

Text(255) (MS Access)

Smallint (MS SQL Server)

Number-Whole Number (MS Access)

Varchar(50) (MS SQL Server)

Text(50) (MS Access)

SQL SELECT Command for Retrieving Data for Tag GroupsThe SELECT command can serve as a source of data for multiple PI Tags (a group of tags). The filename that is stated in the Instrumenttag attribute is considered to be an unambiguous key that forms the group. This means that each member of the group points to the same SQL query file.

The tag that triggers the execution (the ‘master’ tag) should have in its Extended Descriptor corresponding placeholders defined which relate to the question marks in its SQL statement. It is not required that other group member tags contain the placeholder definitions.

The other criteria for building a group is to have Location3 <> 0.

Note: Single PI tags can also share the same SQL file, but they are not member of a group if Location3 = 0.

Fixed Positions of Columns Used in SELECT Statement

All the tags in a group should be numbered according to the sequence of field names used in the SELECT command. These numbers are expected to be in Location3 parameter of each tag in the group. Furthermore, the ‘master’ tag has to have the Location3 parameter set to either 1 or 2, depending on whether the optional timestamp field is available or not.

Plant Suite RDBMS to PI Interface 21

Page 25: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statements

When the above-described conditions are fulfilled, the result set returned after each execution is sorted into all group points. If a timestamp comes from a relational database, the ‘time’ field in the SELECT statement is expected to be in the first position. The simplest example is:

SELECT TIMESTAMP, VALUE1, STATUS1, VALUE2, 0, …

The second status value is forced to be of value zero (or possibly any constant applicable for a particular point). This is the same zero-status-rule as described in chapter “SQL SELECT Command for Retrieving Data for Single PI Tag ”. The Location3 parameter of the group member tags is as follows:

Master Tag and Group members

Tag Instrumenttag

Extended Descriptor

Location2 Location3 Comment

Master tag Filename.SQL P1=… 0first row only

1Bulk read

1 if no timestamp field used

2 if first field is timestamp

Master tag gets first value, status

Group member(s)

Filename.SQL Not evaluated Field number of value field

All tags must refer to the same SQL statement

Note: Those PI points, which have SQL statements defined in the Extended Descriptor (not in a file pointed to by Instrumenttag ) are expected to retrieve data only for themself, they do not have the ‘grouping’ feature.

Note: Since the above statement contains a timestamp field, the Location3 sequence is 2,4,6… otherwise it would be 1,3,5…

Arbitrary Positions of Columns Used in SELECT Statement - Aliases

A similar construction with ALIASES used in SELECT commands is applicable also in this strategy. The column names used in the RDB table can be re-named to the known keywords PI_TIMESTAMP, PI_TAGNAME, PI_VALUE, PI_STATUS.Because we will have more PI_VALUEs and PI_STATUSes present in the SELECT statement, these should be numbered. The regularity should be obvious from the following example.

OSI Software, Inc. 22

Page 26: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Example 3.4 – field alias names:

SQL Statement(file PI_STR_GR1.SQL)

SELECT PI_TIMESTAMP, PI_VALUE1, PI_VALUE3,PI_VALUE4, PI_STATUS1 ,PI_STATUS3,PI_STATUS4 FROM PI_STR_GROUP1 WHERE PI_TIMESTAMP > ?;

orSELECT TST AS PI_TIMESTAMP, V1 AS PI_VALUE1, V2 AS PI_VALUE3, V3 AS PI_VALUE4, S1 AS PI_STATUS1 , S2 AS PI_STATUS3, S3 AS PI_STATUS4 FROM PI_STR_GROUP1 WHERE PI_TIMESTAMP > ?;

Relevant PI Point Attributes

Extended Descriptor

Location1 Location2 Location3 Location4 Location5

P1=TS 1 1 Point1 1

Point2 3

Point3 4

1 0

Instrumenttag Pointtype

PI_STR_GR1.SQL String

RDB Table Design

PI_TIMESTAMP PI_VALUEn PI_STATUSn

Datetime (MS SQL Server)

Date/Time (MS Access)

Varchar(50) (MS SQL Server)

Text(50) (MS Access)

Varchar(50) (MS SQL Server)

Text(50) (MS Access)

Numbers used in column names (PI_VALUE1,PI_STATUS1…) correspond to the numbers stated in Location3. The main difference to the numbering scheme used in the ‘fixed position strategy’ is that Value and Status are of the same number. The ‘master tag’ (the point that actually gets executed) is still recognized by having Location3 = 1.

SQL SELECT Command for Tag Distribution via Tagname Key

Fixed Positions of Columns Used in SELECT Statement

The second possibility how to get data for multiple PI points out of one result set is to have one field configured as an unambiguous key (e.g. name of a point). The SELECT command should be of the following form:

SELECT [Time], Tagname, Value, Status FROM Table WHERE Time > ?;

P1=LST

Plant Suite RDBMS to PI Interface 23

Page 27: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statements

A result set will look like this:

[timestamp1,]tagname1, value1, status1

...

[timestampX,]tagnameX, valueX, statusX

...

Note: The corresponding sequence of columns used in the SELECT clause should be kept according to the example above. Brackets denote an optional column.

The query execution is controlled by one PI point that carries the SQL command – called distributor point. The distributor point and the target points should relate to the same Interface Location1, be of the same scan class Location4, and of the same PointSource, otherwise the Interface will drop the data.

Distributor Point and Target Point attributes

Tag Instrumenttag

Extended Descriptor

Location2 Location3 Location4

Distributor tag Filename.SQL P1=… 1 -1 n

Target tag Not evaluated Not evaluated n

… Not evaluated Not evaluated n

Note: The difference between a master tag for Tag Groups and a distributor tag for Tag Distribution is that the second one is a management tag only (does not get any data from the query) while the master tag for Tag Groups is at the same time management tag and first member of the group.

Note: The name of the Distributor Point should not be listed in the result set. He gets only the number of rows retrieved from the relational database. This is for administration purposes.

/ALIAS ! changed behavior

Since names of variables in the RDB might not be exactly the same as in PI we support an optional keyword /ALIAS=rdbms_tagname. This allows mapping of PI points to rows retrieved from the relational database.Please note that this switch is now case sensitive.

PI2 Tagname matching rules ! changed behavior

PI2 tagnames are always upper case. The Interface makes case insensitive comparison in order to reduce failure rates (user error). Experience with the previos version showed that this is a source for hidden errors.

OSI Software, Inc. 24

Page 28: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

When using PI2 short names, they are internally evaluated in their delimited form e.g. XX:YYYYYY.ZZ

Spaces will be preserved as well. E.g. 'XX:YYYY .ZZ'

PI3 Tagname matching rules ! changed behavior

PI3 tagnames preserve the case. The default tagname comparison is now case insensitive. If a case sensitive test is required, the /ALIAS option can be used to force a case sensitive test.

Note: See Example 1.4

Arbitrary Positions of Columns Used in SELECT Statement - Aliases

Using aliases in a SELECT command containing a tagname field is also possible.

The SELECT … AS PI_TIMESTAMP…construction renames the column names. This allows the interface to recognize the meaning of a column via their name.

Note: Do not mismatch field name aliases with the /ALIAS keyword.

Example 3.5 – distributor strategy and alias field names:

SQL Statement(file PI_ALL_TYPES_DISTR1.SQL)

SELECT NAME AS PI_TAGNAME, VALUE AS PI_VALUE , STATUS AS PI_STATUS, DATE_TIME AS PI_TIMESTAMP FROM PI_ALL_TYPES_DISTR1 WHERE NAME LIKE ‘Key_%’;

Relevant PI Point Attributes

Extended Descriptor

Location1

All points

Location2 Location3 Location4

All points

Location5

All points

Distributor – P1=”Key_1234”

Target points - /ALIAS=value retrieved in NAME column

1 1

Target points – Not

evaluated

-1

Target points – Not

evaluated

1 0

Plant Suite RDBMS to PI Interface 25

Page 29: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statements

Instrumenttag Pointtype

PI_ALL_TYPES_DISTR1.SQL

Point1 Int32

Point2 Digital

Point3 Int32

Point4 Float16

Point5 String

RDB Table Design

DATE_TIME NAME VALUE STATUS

Datetime (MS SQL Server)

Date/Time (MS Access)

Char(80) (MS SQL Server)

Text(80) (MS Access)

Real (MS SQL Server)

Text(255) (MS Access)

Real (MS SQL Server)

Text(12) (MS Access)

Event based InputInput points can be triggered on a time period basis as well as they can be event based (any time the PI snapshot of a trigger tag changes, an event is generated). To achieve this, the keyword /EVENT=tagname must be in the Extended Descriptor of the particular input tag. The SQL statement (usually SELECT) is executed each time the value of the ‘event tag’ changes.

The following example shows reading data from a relational database, triggered by sinusoid events.

Example 3.6 – event based input:

SQL Statement(file PI_STR_EVENT1.SQL)

SELECT PI_TIMESTAMP,PI_VALUE,PI_STATUS FROM PI_STRING_EVENT1;

Relevant PI Point Attributes

Extended Descriptor

Location1 Location2 Location3 Location4 Location5

/EVENT=sinusoid 1 0 0 Not evaluated

0

Instrumenttag Pointtype

PI_STR_EVENT1.SQL

String

OSI Software, Inc. 26

Page 30: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

RDB Table Design

PI_TIMESTAMP PI_VALUE PI_STATUS

Datetime (MS SQL Server)

Date/Time (MS Access)

Varchar(1000) (MS SQL Server)

Text(255) (MS Access)

Smallint (MS SQL Server)

Byte (MS Access)

Note: If no timestamp field is provided in the query, retrieved data will be stored in PI using the event timestamp rather than the query execution time.

Multistatement SQL ClauseThe interface can handle execution of more than one SQL statement. Semicolons must be used to separate multiple statements.

In the example below we keep the most recent value of the sinusoid point in the relational database by inserting the snapshot value and deleting the previous record. Output is event based.

Plant Suite RDBMS to PI Interface 27

Page 31: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statements

Example 3.7 – multi statement query:

SQL Statement(file PI_SIN_PER_SCAN1.SQL)

INSERT INTO PI_SIN_PER_SCAN1 (PI_TIMESTAMP,PI_VALUE,PI_STATUS) VALUES (?,?,?);

DELETE FROM PI_SIN_PER_SCAN1 WHERE PI_TIMESTAMP <=?;

Relevant PI Point Attributes

Extended Descriptor

Location1 Location2 Location3 Location4 Location5

P1=TS P2=VL P3=SS_I P4=LST

1 0 0 Not evaluated

0

Instrumenttag Pointtype Sourcetag

PI_SIN_PER_SCAN1.SQL

Int16 SINUSOUD

RDB Table Design

PI_TIMESTAMP PI_VALUE PI_STATUS

Datetime (MS SQL Server)

Date/Time (MS Access)

SmallInt (MS SQL Server)

Number-Whole Number (MS Access)

Smallint (MS SQL Server)

Number Single Precision (MS Access)

Stored ProceduresThe interface also offers the possibility of executing ‘stored procedures’. Stored procedure calls can use placeholders in their argument lists and behave the same way as standard queries do. The syntax for a procedure invocation conforms to the rules of SQL extensions defined by ODBC:

{call procedure-name[([parameter][,[parameter]]...)]}

Please consult the manual of your RDB for calling syntax. Some RDB do not require curly braces.

A procedure can have zero or more input parameters. In this version of the interface stored procedures which return values via parameters are not supported. Stored procedures can therefore be used mainly for triggering some actions in relational databases and supply parameters for these actions.

Note: Some data sources like MS SQL Server allow to define a SELECT statement inside the procedure body without having output parameters. The execution of such a procedure then returns the ‘standard’ result data set. In this case the interface is able to process the returned data in the same way the output from a SELECT clause gets evaluated. See the following example.

OSI Software, Inc. 28

Page 32: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Example 3.8 – stored procedure call:

SQL Statement

{CALL SP_1(?,?,?,?,?)};

Stored procedure definition

CREATE PROCEDURE SP_1 @pi_tstmp datetime, @pi_val real, @pi_stat smallint, @Beginning_Date DateTime, @Ending_Date DateTime AS

SELECT PI_TIMESTAMP,PI_VALUE,PI_STATUS FROM PI_SP_1 WHERE PI_TIMESTAMP BETWEEN @Beginning_Date AND @Ending_Date INSERT INTO PI_SP_1 ( PI_TIMESTAMP, PI_VALUE,PI_STATUS) VALUES (@pi_tstmp,@pi_val,@pi_stat)

Relevant PI Point Attributes

Extended Descriptor

Location1 Location2 Location3 Location4 Location5

P1=ST P2=G8 P3=G16 P4=LST P5=TS /SQL="{CALL SP_1(?,?,?,?,?)};"

1 1 0 2 0

Instrumenttag Pointtype Sourcetag

Float16

RDB Table Design

PI_TIMESTAMP PI_VALUE PI_STATUS

Datetime (MS SQL Server)

Real (MS SQL Server)

Smallint (MS SQL Server)

Outputs from PI via Update and Insert ClauseOutput of data towards a relational database is either internally handled via exceptions generated by the source tag or we can use scan-based output. Writing data from PI to a relational database is accomplished by using INSERT, UPDATE or CALL SQL commands. The following example keeps only one record in the relational database with the latest value of the sinusoid point. Output of the example point is event based.

Plant Suite RDBMS to PI Interface 29

Page 33: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statements

Example 3.9 – event based output:

SQL Statement(file PI_SIN_PER_SCAN2.SQL)

UPDATE PI_SIN_PER_SCAN2 SET PI_TIMESTAMP=?, PI_VALUE=?, PI_STATUS=?;

Relevant PI Point Attributes

Extended Descriptor

Location1 Location2 Location3 Location4 Location5

P1=’sinusoid’/TS P2=’sinusoid’/VL P3=’sinusoid’/SS_I

1 0 0 Not evaluated

0

Instrumenttag Pointtype Sourcetag

PI_SIN_PER_SCAN2.SQL

Float16 SINUSOID

RDB Table Design

PI_TIMESTAMP PI_VALUE PI_STATUS

Datetime (MS SQL Server)

Date/Time (MS Access)

Real (MS SQL Server)

Byte (MS Access)

Smallint (MS SQL Server)

Number Whole Number (MS Access)

Note: To update a row in a relational database - some record(s) (that match the WHERE condition, if there is any) should be present in the updated table.If the table is empty, the update will return success but the table will remain empty.For alternatives, please check the INSERT_UPDATE example in section “More Examples”

The output point (tag that does not contain the original data) will be copied with successfully written data. If the SQL statement fails, the output tag will receive a digital state of “BAD OUTPUT”. This mechanism allows simple verification of output operation.

Data Output for DIGITAL PointsFor output of PI data in direction of RDBMS, there is no fixed structure of output fields the query must supply. Instead any supported placeholder can be used for an output field. However, the placeholders VL, SS_I, SS_C apply to similar rules as value and status fields for input. Digital point output values are mapped only to strings, means the data type in the corresponding relational database for storing the value of a digital tag should be of type string.

OSI Software, Inc. 30

Page 34: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

PI Value VL

Field Type String

SS_I

Field Type Integer OR Float

SS_C

Field Type String

Digital State not in Error Range

<Digital State String> 0 O.K.

Digital State is in Error Range

<Digital State String> 1 Bad Value

Note: More data type conversions are supported for ODBC drivers with Level 2 Extensions.

Example 3.10 – Output tag is triggered by sinusoid, but values come from ‘x_digital2’:

SQL Statement(file PI_DIGITAL_OUT1.SQL)

UPDATE PI_DIGITAL_OUT1 SET PI_TIMESTAMP=?, PI_VALUE=?, PI_STATUS_I=?, PI_STATUS_STR=?;

Relevant PI Point Attributes

Extended Descriptor Location1 Location2 Location3 Location4 Location5

P1=’x_digital2’/TS P2=’x_digital2’/VL P3=’x_digital2’/SS_I P4=’x_digital2’/SS_C

1 0 0 Not evaluated

0

Instrumenttag Pointtype Sourcetag

PI_DIGITAL_OUT1.SQL

Float16 SINUSOID

RDB Table Design

PI_TIMESTAMP PI_VALUE PI_STATUS_I PI_STATUS_STR

Datetime (MS SQL Server)

Date/Time (MS Access)

Char(12) (MS SQL Server)

Text(12) (MS Access)

Smallint (MS SQL Server)

Number Single Precision (MS Access)

Smallint (MS SQL Server)

Text(12) (MS Access)

Data Output for INTEGER PointsPlease note that the usage of Placeholder VL also depends on the PI tag data type. Since an Integer PI Tag can only contain integer data, we only support mapping of VL to Integer (exact) or Float (approximate) RDBMS type fields.

Plant Suite RDBMS to PI Interface 31

Page 35: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statements

PI Value VL

Field Type Integer or Float

SS_I

Field Type Integer or Float

SS_C

Field Type String

Value >= 0 <Value> 0 O.K.

Digital State <Value> 1 <Digital State String>

Note: More data type conversions are supported for ODBC drivers with Level 2 Extensions. In such cases it is for example possible to write integer values as ASCII representation into a string field.

Data Output for REAL and String PointsData mapping for real tags is very similar to integer tags. Of course the preferred data type for VL is Float.

PI Value VL

Field Type Float(or Integer)

SS_I

Field Type Integer or Float

SS_C

Field TypeString

Value not in error <Value>(<(int)Value>)

0 O.K.

Digital State 0 1 <Digital State String>

Note: More data type conversions are supported for ODBC drivers with Level 2 Extensions. In such cases it is for example possible to write float values as ASCII representation into a string field.

Global VariablesThe Extended Descriptor has a 80-character length limitation (PI-API). In order to allow string parameters longer than 80 characters, global variables can be defined. A file containing definitions for all global variables is referenced as interface start-up parameter. The syntax for global variables is the same as for placeholders Pn, but starting with character ‘G ‘ (see chapter “SQL Placeholders”). The syntax used in global variable file is obvious from the next example:

OSI Software, Inc. 32

Page 36: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Example 3.11 – Global variables (referenced by keyword /global=d:\pipc\interfaces\rdbmspi_2.0\data\global.dat;

SQL Statement(file PI_SIN_VALUES_OUT2.SQL)

UPDATE PI_SIN_VALUES_OUT2 SET NAME1_TS=?,NAME2_TS=?,DSC3=?,NAME1=?,NAME1_DSC=?, NAME1_ENG_UNITS=?,DSC1=?,NAME1_VL=?,NAME1_SS_C=?, DSC4=?,DSC5=?,DSC6=?,NAME2=?,NAME2_DSC=?, NAME2_ENG_UNITS=?, DSC2=?,NAME2_VL=?,NAME2_SS_C=?;

Relevant PI Point Attributes

Extended Descriptor Location1 Location2 Location3 Location4 Location5

/EXD=…path…\ pi_sin_values_out2.plh

Content of the above stated file:

P1=G7 P2=G13 P3=G3 P4=G4 P5=G5 P6=G6 P7=G1 P8=G8 P9=G9 P10=G1 P11=G2 P12=G3 P13=G10 P14=G11 P15=G12 P16=G2 P17=G14 P18=G15

1 0 0 2 0

Instrumenttag Pointtype

PI_SIN_VALUES_OUT2.SQL

Int16

RDB Table Design

DSCn

NAMEn

NAMEn_DSC

NAMEn_ENG_UNITS

NAMEn_TS NAMEn_VL NAMEn_SS_C

Char(50) (MS SQL Server)

Text(50) (MS Access)

Datetime (MS SQL Server)

Date/Time (MS Access)

Real (MS SQL Server)

Number Single Precision (MS Access)

Char(12) (MS SQL Server)

Text(12) (MS Access)

Content of the global variables file

Plant Suite RDBMS to PI Interface 33

Page 37: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statements

G1="Actual-Value" G2="of-the" G3="PI-point:" G4='sinusoid'/AT.TAG G5='sinusoid'/AT.DESCRIPTOR G6='sinusoid'/AT.ENGUNITS G7='sinusoid'/TS G8='sinusoid'/VL G9='sinusoid'/SS_C G10='sinusoidu'/AT.TAG G11='sinusoidu'/AT.DESCRIPTOR G12='sinusoidu'/AT.ENGUNITS G13='sinusoidu'/TS G14='sinusoidu'/VL G15='sinusoidu'/SS_C

OSI Software, Inc. 34

Page 38: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Data Mapping between PI and RDBMSA single PI tag can only ‘historize’ value or status, but never both together in only one tag. Therefore we need to provide a method of mapping a given value / status pair into one type of information. PI System interfaces mostly apply the rule:

If the status of a value is “good”, store the value in PI.

If the status of a value is other than “good”, store the status instead.

Note: Any requirement that goes beyond that needs more than one tag.

In the previous chapter we have learned that we always need to select a value field and a status field in the SQL query. The following section will explain how these two fields provide data for the PI tag.

Mapping of SELECT Data Types to PI Point Types – Data InputFour types of input fields after a SELECT keyword can be validated for this interface:Timestamp, Tagname, Value and Status fields.To be able to evaluate those fields, the interface makes some considerations for their data types. The following table shows what combinations between PI point types and field data types are working. Tags that do not match those criteria are rejected by the interface. This does not mean that those tags cannot be serviced. It only means that additional explicit conversion might be required.

Page 39: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Input field SQL Data Type PI Point Type

Timestamp SQL_TIMESTAMP All PI point types

Tagname SQL_CHAR, SQL_VARCHAR, SQL_LONGVARCHAR

All PI point types

Real (R) Integer(I) Digital(D) String(S)

Value Approximate (floating points) data types

SQL_NUMERIC, SQL_DECIMAL, SQL_REAL , SQL_FLOAT, SQL_DOUBLE

Casted to the particular floating-point type.

Casted to long integer

Casted to integer and interpreted as pointer to Digital Set

Converted from floating-point to string.

Exact (integer) data types

SQL_TINYINT, SQL_SMALLINT, SQL_INTEGER, SQL_BIGINT, SQL_BIT

Casted to the particular floating-point type.

Casted to the particular integer type

Interpreted as pointer to Digital Set

Converted from integer to string.

Character data types

SQL_CHAR, SQL_VARCHAR , SQL_LONGVARCHAR

Converted from string to double. The double number is after that casted to particular floating-point PI type.

Converted from string to long integer and casted to integer PI data type.

Checked against Digital Set.

Retrieved number of bytes copied.

Status See chapter: Evaluation of STATUS Field for All PI Data Types - Input from RDBMS

Note: The full conversion of all possible data types supported in ‘relational world’ to PI data types goes beyond the ability of this Interface. To allow additional conversions, use the convert function described below.

Explicit data type conversion is specified in terms of SQL data type definitions.

The ODBC syntax for the explicit data type conversion function does not restrict conversions. The validity of specific conversions of one data type to another data type will be determined by each driver-specific implementation. The driver will, as it translates the ODBC syntax into the native syntax, reject those conversions that, although legal in the ODBC syntax, are not supported by the data source. In this case, the error message will be forwarded to the interface log file and, of course, the tag will be rejected.

The format of the CONVERT function is:

Page 40: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

CONVERT(value_exp, data_type)

The function returns the value specified by value_exp converted to the specified data_type, where data_type is one of the valid SQL data types.

Example:

{ fn CONVERT( { fn CURDATE() }, SQL_CHAR) }

converts the output of the CURDATE scalar function to a character string.

Because ODBC does not mandate a data type for return values from scalar functions as the functions are often data source–specific, applications should use the CONVERT scalar function whenever possible to force data type conversion.

Note: More information about the CONVERT function can be gained from the ODBC.HLP file which comes with Microsoft ODBC Data Manager.

Evaluation of STATUS Field for All PI Data Types - Input from RDBMSIn this version of the Interface presence of a status field is mandatory. Status field can be provided either in numeric or string format. For a numeric field, we only test against zero. For a string field evaluation is more complex and in order to verify this status we have to define 2 areas in the digital state table, one for successful states, another one for error or bad value states. The status areas in the digital state table are referenced via /succ1, /succ2, /bad1, /bad2 interface start-up parameters.

Note: In the following table the term used in the column SQL Data Type of Status Field denotes these SQL data types:

String SQL_CHAR, SQL_VARCHAR, SQL_LONGVARCHAR

Numeric SQL_NUMERIC, SQL_DECIMAL, SQL_REAL , SQL_FLOAT, SQL_DOUBLE, SQL_TINYINT, SQL_SMALLINT, SQL_INTEGER, SQL_BIGINT, SQL_BIT

Plant Suite RDBMS to PI Interface 37

Page 41: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statements

The Table shows mapping of the status into a PI point:

SQL Data Type of Status Field

Success Bad Not Found Result for Tag

String String is between /succ1 and /succ2

Go and evaluate Value Field

String is between /bad1 and /bad2

<Digital State>(the one which was found)

String was not found

Bad Input

Numeric <> 0 Bad Input

0 Go and evaluate Value Field

String NULL(Status Field contains NULL)

Go and evaluate Value Field

Numeric NULL Go and evaluate Value Field

Note: Searches in success and bad areas are case insensitive!

OSI Software, Inc. 38

Page 42: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Storage of PI POINT Database ChangesThe Interface can keep track of changes made in the PI Point Database. The concept is similar to regular output point handling. The difference is that the managing (output) point is not triggered by a change of PI snapshot data but by point attribute modification. Two methods of recording are available.

Short Form

The first one offers the following attributes to be stored in the relational database: TagName, AttributeName, ChangeDateTime, Changer, NewValue, OldValue. The following placeholders are at hand: AT.TAG, AT.ATTRIBUTE, AT.CHANGEDATE, AT.CHANGER, AT.NEWVALUE, AT.OLDVALUE to form appropriate INSERT statement.

Long Form

The second method allows any combination of point database placeholders (AT.___ see chapter SQL Placeholders ). The difference is that the first method inserts a new record into the RDBMS table for any attribute changed and that the second method is supposed to use a complex INSERT query that stores all needed information in one record. Both methods require a ‘managing’ point that carries the SQL statement (INSERT) and the definition of placeholders.

The following examples show how these ‘managing’ points have to be set.

Example 5.1 – Short Form:

SQL Statement(file PIPT_CHG_RED.SQL)

INSERT INTO PI_PT_CHG_REDUCED_FORM ( PI_CHANGEDATE, PI_TAG, PI_ATTRIBUTE, PI_CHANGER, PI_NEWVALUE,PI_OLDVALUE)VALUES (?,?,?,?,?,?);

Page 43: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Relevant PI Point Attributes

Extended Descriptor Location1 Location2 Location3 Location4 Location5

/EXD=…path…\ pipt_chg_red.plh

Content of the above stated file:

P1=AT.CHANGEDATE

P2=AT.TAG

P3=AT.ATTRIBUTE

P4=AT.CHANGER

P5=AT.NEWVALUE

P6=AT.OLDVALUE

1 0 0 -1

This is relevant and says that it is going to be the managing point for method one recording

0

Instrumenttag Pointtype

PIPT_CHG_RED.SQL Int32

RDB Table Design

PI_TAG PI_ATTRIBUTE PI_CHANGEDATE PI_CHANGER

Varchar(80) (MS SQL Server)

Text(80) (MS Access)

Varchar(32) (MS SQL Server)

Text(32) (MS Access)

Datetime (MS SQL Server)

Date/Time (MS Access)

Varchar(12) (MS SQL Server)

Text(12) (MS Access)

PI_NEWVALUE PI_OLDVALUE

Varchar(80) (MS SQL Server)

Text(80) (MS Access)

Varchar(80) (MS SQL Server)

Text(80) (MS Access)

Example 5.2 – Long Form:

Page 44: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SQL Statement(file PIPT_CHG_FULL.SQL)

INSERT INTO PIPT_FULLCHANGE (CREATIONDATE, CHANGEDATE, TAG, DESCRIPTOR, EXDESC, ENGUNITS, TYPICALVALUE, ZERO, SPAN, DIGSTARTCODE, DIGNUMBER, POINTTYPE, POINTSOURCE, LOCATION1, LOCATION2, LOCATION3, LOCATION4, LOCATION5, SQUAREROOT, SCAN, EXCDEV, EXCMIN, EXCMAX, ARCHIVING, COMPRESSING, FILTERCODE, RES, COMPDEV, COMPMIN, COMPMAX, TOTALCODE, CONVERS, CREATOR, CHANGER, RECORDTYPE, POINTNUMBER, POINTID, DISPLAYDIGITS, SOURCETAG, INSTRUMENTTAG) VALUES (?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?,?);

Plant Suite RDBMS to PI Interface 41

Page 45: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Data Mapping between PI and RDBMS

Relevant PI Point Attributes

Extended Descriptor Location1 Location2 Location3 Location4 Location5

/EXD=…path…\ pipt_chg_full.plh

Content of the above stated file:

P1=AT.CREATIONDATE P2=AT.CHANGEDATE P3=AT.TAG P4=AT.DESCRIPTOR P5=AT.EXDESC P6=AT.ENGUNITS P7=AT.TYPICALVALUE P8=AT.ZERO P9=AT.SPAN P10=AT.DIGSTARTCODE P11=AT.DIGNUMBER P12=AT.POINTTYPE P13=AT.POINTSOURCE P14=AT.LOCATION1 P15=AT.LOCATION2 P16=AT.LOCATION3 P17=AT.LOCATION4 P18=AT.LOCATION5 P19=AT.SQUAREROOT P20=AT.SCAN P21=AT.EXCDEV P22=AT.EXCMIN P23=AT.EXCMAX P24=AT.ARCHIVING P25=AT.COMPRESSING P26=AT.FILTERCODE P27=AT.RES P28=AT.COMPDEV P29=AT.COMPMAX P30=AT.COMPMIN P31=AT.TOTALCODE P32=AT.CONVERS P33=AT.CREATOR P34=AT.CHANGER P35=AT.RECORDTYPE P36=AT.POINTNUMBER P37=AT.DISPLAYDIGITS P38=AT.SOURCETAG P39=AT.INSTRUMENTTAG

1 0 0 -2

This is relevant and says that it is going to be the managing point for method two recording

0

OSI Software, Inc. 42

Page 46: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Instrumenttag Pointtype

PIPT_CHG_FULL.SQL Int32

RDB Table Design

PI_TAG PI_DESCRIPTOR PI_EXDESC PI_POINTTYPE PI_POINTSOURCE PI_SOURCETAG PI_INSTRUMENTTAG PI_ENGUNITS PI_CREATOR PI_CHANGER

PI_CREATIONDATE PI_CHANGEDATE

PI_ZERO PI_SPAN PI_TYPICALVALUE PI_EXCDEV PI_COMPDEV

PI_DIGSTARTCODEPI_DIGNUMBER PI_LOCATION1-5 PI_SQAREROOT PI_SCAN PI_ARCHIVING PI_COMPRESSING PI_FILTERCODE PI_RES PI_COMPMIN PI_COMPMAX PI_TOTALCODE PI_CONVERS PI_SCAN PI_SQAREROOT PI_RECORDTYPE PI_POINTNUMBER PI_DISPLAYDIGITS

Varchar(80) (MS SQL Server)

Text(80) (MS Access)

Datetime (MS SQL Server)

Date/Time (MS Access)

Real (MS SQL Server)

Single Precision (MS Access)

Varchar(12) (MS SQL Server)

Text(12) (MS Access)

Plant Suite RDBMS to PI Interface 43

Page 47: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

PI Batch Database OutputThe Interface keeps track of PI Batch database new events and stores this data in the relational database. The ‘managing’ point that carries the SQL statement (INSERT) is recognized by the presence of any of the ‘PI batch database placeholders’ (see chapter SQL Placeholders). The PI Batch database is scanned on a time basis (‘managing’ point should be input point) and newly arrived data is inserted into the relational database. The ‘managing’ point itself gets the number of new batches exported since last scan.

Example 6.0 – Batch Export:

SQL Statement(file PI_BATCH1.SQL)

INSERT INTO PI_BATCH1 (PI_BATCH_START,PI_BATCH_END, PI_BATCH_UNIT, PI_BATCH_ID, PI_BATCH_PRODUCT_ID) VALUES (?,?,?,?,?);

Relevant PI Point Attributes

Extended Descriptor

Location1 Location2 Location3 Location4 Location5

P1=BA.START P2=BA.END P3=BA.UNIT P4=BA.BAID P5=BA.PRID

1 0 0 1 0

Instrumenttag Pointtype

PI_BATCH1.SQL Float32

RDB Table Design

PI_BATCH_UNIT PI_BATCH_ID PI_BATCH_PRODUCT_ID

PI_BATCH_START PI_BATCH_END

Varchar(80) (MS SQL Server)

Text(80) (MS Access)

Datetime (MS SQL Server)

Date/Time (MS Access)

Page 48: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Database specificsAlthough ODBC is a standard, there are implementation differences of ODBC drivers compared to each other. Also the databases which are behind ODBC have differences in functionality, supported data-types, limits, SQL syntax and so on.The following section will describe some of the differences, which are important for this Interface, but this list is by far not complete.However, many of the ODBC driver specifics are handled automatically via the Interface itself.

Oracle 7.0

Statement Limitation

We have found that there is a limitation in the number of statements, which can be open at the same time. Although it is possible to increase this limit via the keyword OPEN_CURSORS configured in the file INIT.ORA, we could not get more than 100 statements to work. INIT.ORA is located at the server side of the ORACLE database.

Since this Interface normally uses one SQL statement per tag, not more than 100 tags per Interface process can be serviced. Exceptions are grouping and multiple statements per tag.The only way we found to support more than 100 tags was to use Tag Groups or Tag Distribution.

ODBC drivers used:Oracle72 1.13.0500Visegenic 32-bit Oracle driver 2.00.0000

We did not see this problem in higher versions of ORACLE.

Oracle RDB

TOP 10

If it is required to limit the number of returned rows, e.g. in order to reduce CPU load, there is a possibility to formulate the SQL query accordingly. Unfortunately this option is database specific.

RDB allows the following statement which returns up to 10 records:

SELECT * FROM test LIMIT TO 10 ROWS;

In the form

SELECT * FROM test LIMIT TO 10 ROWS WHERE timestamp > ?;

And having P1=TS, this query allows smooth history recovery when the Interface was down for a longer time.

Note: Number 10 is of course only an example value.

Page 49: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Oracle 8.0

TOP 10

Similar to the example for RDB (see above), the statement to select a maximum of 10 records looks as follows:

SELECT * FROM test WHERE ROWNUM=10;

dBase III, dBase IV

Timestamps

dBase does not support the datatype TIMESTAMP. There is a workaround to at least output data with timestamps. The target field for the timestamps must be of type TEXT(20). The Interface and the ODBC driver will automatically convert the Placeholder from type SQL_TIMESTAMP into SQL_VARCHAR.

The other way around is not that simple. Actually it is not possible to read a timestamp from a TEXT field because the required ODBC function CONVERT does not support SQL_VARCHAR into SQL_TIMESTAMP.However a workaround is possible:Use the dBase database as linked table from within MS Access. Now we can use the MS Access ODBC driver which unfortunately also does not support CONVERT from SQL_VARCHAR into SQL_TIMESTAMP. But there is a function available called CDATE.The input query looks like below and works for timestamps in dBase TEXT fields of the format “DD-MMM-YY hh:mm:ss” :

SELECT cdate(CTIMESTAMP), RVALUE, ISTATUS FROM RECEIVE WHERE cdate(CTIMESTAMP) > ?;

ODBC drivers used:Microsoft dBase Driver 3.50.360200Microsoft Access Driver 3.50.360200

Login

dBase works without Username and Password. In order to get access from the Interface a dummy username and password must be used in the startup line.

/user_odbc=dummy /pass_odbc=dummy

Multi-User Access

The Microsoft dBase ODBC driver seems to lock the dBase table. That means no other application can access the table at the same time.We did not look for workarounds, other than the MS Access linked table.

Page 50: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

MS Access

Login

MS Access can also be configured not to use (by default) Username and Password. In order to get access from the Interface a dummy username and password must be used in the startup line.

/user_odbc=dummy /pass_odbc=dummy

TOP 10

Similar to the example for RDB (see above), the statement to select a maximum of 10 records looks as follows:

SELECT TOP 10 * FROM test;

MS SQL Server 6.5

TIMESTAMP

There are 2 data types for timestamps available in SQL Server, TIMESTAMP and DATETIME. For this Interface only DATETIME works in combination with Placeholders of type SQL_TIMESTAMP.

MS SQL Server 7.0

TOP 10

Similar to the example for RDB (see above), the statement to select a maximum of 10 records looks as follows:

SELECT TOP 10 * FROM test;

Plant Suite RDBMS to PI Interface 49

Page 51: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

PI Point ConfigurationA PI point corresponds to a single parameter in the ‘interfaced system’. For example, a counter, a set point, a process variable, and the high and low control limits would each serve as a separate point in the PI System database. Each of these points must be defined and configured individually using the PIDIFF or PICONFIG utilities. For more information regarding point configuration, see the Data Archive (DA) section of the PI System Manuals.

The following point attributes are relevant to configure tags used with the RDBMS to PI Interface.

Point Name

The point name is free, according to the normal PI point naming conventions.

Extended Descriptor

The Extended Descriptor is mainly used to define placeholders (See chapter “SQL Placeholders ”).

Possible keywords used in the Extended Descriptor are described in the following table:

Keyword Example Remark

/ALIAS /ALIAS=Level321_in Used when DISTRIBUTOR strategy takes place. This allows having different point names in RDB and in PI.

/EXD /EXD=D:\PIPC\DATA\PLACEHOLDER1.DEF Allows getting over the 80-character limit of the Extended Descriptor. (Suitable for tags with more placeholders.)

/SQL /SQL=”SELECT PI_VALUE,PI_STATUS FROM PI_TABLE WHERE PI_TIMESTAMP >?;” P1=TS

Suitable for shorter SQL statements. Allows the on-line statement changes (sign-up-for-updates). The actual statement should be double-quoted and the ending semicolon is mandatory.

/TRIG

/EVENT

/EVENT=sinusoid Used for event driven input points. Each time the particular (in our case sinusoid) point changes, the actual point is processed.

Note: Each keyword has to be in uppercase.

Page 52: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Point Source

All points defined in the PI Point Database for use with this interface must share a common point source. That means that the interface is able to write retrieved data from a relational database only to tags of this point source.

The point source is a single character, for example R (Relational Database). The point source must be defined in the point source library before point configuration (PI 2.x only).

Note: See in addition Location1 parameter!

Point Type

The Interface supports the following PI point types:

Point Type How It Is Used

Digital Used for points whose value can only be one of several discrete states. These states are predefined in a particular state set (PI 3.x).

Int16 15-bit unsigned integers (0-32767)

Int32 32-bit signed integers (-2147450880 – 2147483647)

Float16 Scaled floating-point values. The accuracy is one part in 32767

Float64 Double-precision floating point values.

String Stores string data of up to 1000 characters.

Blob Binary large object – stores any type of binary data up to 1000 bytes.

Scan flag

This is usually ON for all points of this interface. If you edit this Point Attribute to OFF, then the tag is OFFLINE (no values are exchanged for this tag). In this case and if the interface is running while editing, the tag will automatically get Shutdown event.

Instrument Tag

This is the filename containing the SQL statement(s). The file location is defined in startup parameters using /SQL= directory path.

The SQL file is only evaluated on startup and on tag change events. This is to avoid getting a new SQL statement but having wrong placeholders left in the tag configuration. If a SQL statement needs to be changed during interface operation, we recommend to provide a new SQL file and edit the Instrument Tag field (and may be the Extended Descriptor if required) to point to the new SQL file. The point edit will cause the Interface to reevaluate this tag, including the new SQL statement.

Page 53: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

SourceTag

This attribute is used only for output points. The Interface decides if it is an output tag when this attribute is not empty. The source tag is the PI tag from which the output gets the values for sending to the RDBMS. The interface tag will receive a copy of all data sent to the relational database. In case of an ODBC call failure the Interface tag will receive the status BAD OUTPUT.

Location 1

This is the number of the Interface process that shall collect data for this tag. The interface can run multiple times and so distribute CPU power to groups of tags. E.g. it is possible to give a number of tags, to be scanned with high frequency, a separate process.

The parameter required here should match the parameter /IN in the startup file.

Note: It is even possible to start multiple Interface processes on different PI Nodes. But then a separate Software License for the Interface is required per PI Node.

Location 2

The second location parameter specifies if all rows of data returned by ODBC API calls in form of a result set should be written into the PI database or if only the first row is valid.

For Tag Groups the master tag will define this option for all tags related. It is not possible to read only the first record for one tag and all records for another tag.

Note: For Tagname Distribution Strategy the Interface tries to get all retrieved rows to the PI database regardless of the location2 value.

Location2 Data acquisition strategy

0 Only the first record is valid (except the Tagname Distribution Strategy)

1 The interface tries to put all the returned data into PI

Note: It is recommended to provide a timestamp field when trying to send all retrieved rows from RDB to PI.

Location 3

The third location parameter specifies the ‘Distribution Strategy’ - how retrieved data from the relational database should be interpreted and written into PI:

Location3 Data acquisition strategy

0 SQL query populates a single tag

> 0 Location3 represents the column number of a multiple field query

< 0 SQL statement returns the tagname

Plant Suite RDBMS to PI Interface 53

Page 54: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Database Specifics

Location 4

Specifies the scan class used.

The startup command procedure has parameters like/f=00:00:30

This parameter specifies cycle time for scan groups. The first /f= relates to scan group 1 etc.

This parameter should be set to zero if event controlled reading is configured (see Extended Descriptor – keyword /EVENT or /TRIG).

The Interface has the facility to keep track of PI Point Database changes. There are two approaches of recording the PIPOINT changes in RDB.

The first one (short form) requires a table in RDB which contains fields to store PI Tag Attribute changes. The interface then records the following information:

TAG_NAME, ATTRIBUTE_NAME, CHANGE_DATE, CHANGER, OLD_VALUE and NEW_VALUE

The ‘managing ‘ tag that holds the appropriate SQL (INSERT) query must have Location4=-1

The second approach (long form) of storing PI Point Database changes is designed in a way that whenever a PI Tag is modified, the complete Tag configuration after the change is recorded. This method can make use of all possible PI Point Database related placeholders (see chapter SQL Placeholders). The corresponding ‘managing’ tag must have Location4=-2

Location4 Kind of evaluation

Positive number Index to the position of /f= startup parameter keyword (scan class number)

0 Event based output and event based input

-1 Specifies the ‘managing’ tag for recording PIPOINT changes in the ‘reduced’ form

-2 Specifies the ‘managing’ tag for recording PIPOINT changes in the ‘full’ form.

Location 5

Decides about Exception Reporting feature.

Location5 Behavior

0 The Interface does the Exception Reporting in the standard way. For PI points of type String and Blob data transfer as follows:

Exception Deviation=0 means sending each value to PI. Exception Deviation<>0 means sending only changes to PI.

1 The Interface gives up the Exception Reporting. Each retrieved value is sent to PI (pisn_putsnapshotx()).

OSI Software, Inc. 54

Page 55: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

The Interface was developed using PI-API 1.2.3.x. Therefore millisecond timestamps cannot be used in conjunction with Exception Reporting. For millisecond PI3 data types Location5 must be set to 1. As a result, PI Compression will do all the work (data reduction) but also CPU load on the PI Server will be increased.

See also chapter “Limitations and future enhancements”

Exception Reporting

Standard PI usage (if Location5=0), see PI System Manual I.Not used if Location5=1.

Zero, Span

Standard PI usage, see PI System Manual I.

The Interface does not use the following tag attributes

Square root code

Totalization code

Conversion factor

Plant Suite RDBMS to PI Interface 55

Page 56: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Performance PointYou can configure a performance point to monitor the data transfer rate.

The performance point measurement is a number, which specifies the time (in seconds) that is required to update the scan list. The scan list is specified using the interface startup script and the point attributes Location4 and Location1.

To configure a performance point, create a tag with the point source specified for the interface. The point type should be float or integer. The extended descriptor should say

PERFORMANCE_POINT

all in uppercase. Location4 specifies the scan class of interest. Location1 determines the instance of the interface.

Page 57: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

IO Rate TagsAn IO Rate Tag can be configured to receive 10 minute averages of the total number of post-exception events that are sent to PI every minute by the interface (events/minute). The IO Rate will appear to be zero for the first 10 minutes that the interface is running. The “post-exception” restriction means that a new value that is received by the interface does not count toward increasing the IO Rate unless the value passes exception (i.e. ExcDev or ExcMax is exceeded).

To implement an IO Rate Tag, perform the following steps:

1. Create an IO Rate Tag. To create an IO Rate tag called “sy:mod001”, for example, create a file called iorates.dif similar to:

iorates.dif@table pipoint@ptclas classic@stype keyword@mode create,ttag, sy:mod001Descriptor, "TI505 Rate Tag #1"zero, 0span, 100TypicalValue, 50PointType, float32PointSource, LCompressing, 0 @ends

Adjust the Zero, Span, and TypicalValue as appropriate and then type the command:

C:\pi\adm\piconfig < iorates.dif

to create the IO Rate Tag.

2. Create a file called iorates.dat in the PIHOME\dat directory. The PIHOME directory is defined either by the PIPCSHARE entry or the PHOME entry in the pipc.ini file, which is located in the \Winnt directory. If both are specified, the PIPCSHARE entry takes precedence.

Since the PIHOME directory is typically C:\PROGRAM FILES\PIPC, the full name of the iorates.dat file will typically be C:\Program Files\PIPC\dat\iorates.dat.

Add a line in the iorates.dat file of the form:

sy:mod001, x

where x corresponds to the event counter specified by the /ec=x flag in the startup command file of the interface. x can be any number between 1 and 34 or between 51 and 200, inclusive.

Page 58: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

To specify additional rate counters for additional copies of the interface, create additional tags and additional entries in the iorates.dat file as appropriate. The event counter, /ec=x, should be unique for each copy of the interface.

3. Set the /ec=x flag on the startup command file of the interface to match the event counter in the iorates.dat file.

4. The interface must be stopped and restarted in order for the IO Rate tag to take effect. IORates will not be written to the tag until 10 minutes after the interface is started.

The 10-minute rate averages (in events/minute) can be monitored, for example, on a ProcessBook trend.

Page 59: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Interface FilesThe startup files for the interface reside in the PI/interfaces/RDBMSPI directory. Listed below are the files required for starting up the interface.

Directory PI\interfaces\RDBMSPIRDBMSPI.BAT Start interface as console applicationRDBMSPI.EXE InterfaceGLOBAL.DAT Example file for globale variables

Directory PI\interfaces\RDBMSPI\EXAMPLES\…Filename.SQL Example SQL Query filesFilename.dif Example piconfig fileFilename.xls Example PI-SMT fileFilename.mdb Example DatabaseReadme_dbname.doc Example Description

Example of a start-up script:

rdbmspi.exe /in=2 /ps=x /ec=21 /f=00:01:10,00:00:10 /f=00:10:20,00:01:00 /SQL=d:\pi\interfaces\rdbmspi\SQL /global=d:\pi\interfaces\rdbmspi\data\global.dat /host=localhost:5450 /output=d:\pi\interfaces\rdbmspi\logs\rdbmspi.out /dsn=MS_ACCESS /succ1=200 /succ2=211 /bad1=212 /bad2=220 /deb=1 /USER_PI=pi_user /USER_ODBC=odbc_user /tf=x_tf1 /tf=x_tf2 /stopstat=shutdown

Page 60: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

InstallationBefore installing the interface, PI-API 1.2.3.4 or PI-API 1.3.x.x must be installed.

To install the interface, you must define a point source code and modify the PI startup and shutdown command files on that node. You can optionally specify one performance monitoring tag as shown in section "Performance Point".

In the PI2 System Point Source Editor, set up the following values:Point Source Code: RPoint Source Descriptor: RDBMS via ODBC

Location Minimum 1 0 -100 0 0

Location Maximum 10 1 100 10 0

For PI3 Systems no Location Parameter Limits need to be specified.

Insert the installation disk

For Intel based Windows NT: Run the file PSrdbms_2.08i.exe.

For ALPHA based Windows NT: Run the file PSrdbms_2.08a.exe.

The Interface Setup files will be extracted to a temporary directory, e.g c:\temp\disk1

Run the setup.exe file from the temporary directory.

Example:

c:> a:PSrdbms_2.08i.exe

c:\temp\disk1\setup.exe

Configure the Startup file RDBMSPI.BAT to your needs and follow instructions in the following sections.

Plant Suite RDBMS to PI Interface 63

Page 61: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Updating the InterfaceFor an update of the RDBMS to PI Interface make a backup of all interface files at PI/interfaces/RDBMSPI directory.

For example:

c:> md /PI/interfaces/RDBMSPI/RDBMSPI_old

c:> copy /PI/interfaces/RDBMSPI/*.* /PI/interfaces/RDBMSPI/ RDBMSPI _old/*.*

If the interface was installed as service, also remove the service using rdbmspi –remove.

Now insert the RDBMS to PI interface diskette in the floppy disk drive and

For Intel based Windows NT: Run the file PSrdbms_2.08i.exe.

For ALPHA based Windows NT: Run the file PSrdbms_2.08a.exe.

The Interface Setup files will be extracted to a temporary directory, e.g c:\temp\disk1

Run the setup.exe file from the temporary directory.

Example:

c:> a:PSrdbms_2.08i.exe

c:\temp\disk1\setup.exe

Page 62: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

StartupCommand line switches for the RDBMS to PI interface

Parameter Meaning

/ps=R Point Source

/in=1 Interface number (Location1)

/ec=21 Event counter.

/f=00:00:01

or

/f=00:01:00,00:00:05

Scan Class frequency, optional use of multiple /f=…

/tf=tagname I/O rate tag per scan

/stopstator/stopatat=digstate

Optionaldefault: see right

If the /stopstat flag is present on the startup command line, then the digital state I/O Timeout will be written to each PI Point when the interface is stopped.

If /stopstat=digstate is present on the command line, then the digital state digstate will be written to each PI Point when the interface is stopped.

/host= localhost:5450 PI Home Node

/global=c:\…\global.dat Name and location of the global variable file

/sql=c:\…\dat Location of the SQL statement files

/output=c:\…\rdbmspi.log Interface specific log file name and location

/dsn=dsn_name Data Source Name

/user_pi=username(PI) Account for PI access (case sensitive evaluation)

/pass_pi=password(PI) Password for PI Server access (case sensitive evaluation)

/user_odbc=username(odbc) Username for RDBMS access (case sensitive evaluation)

/pass_odbc=password(odbc) Password for RDBMS access (case sensitive evaluation)

/test=tagname Test mode for tag=tagname

/deb=0 Debug level

/succ1=100 Begin of range in (system) digital state table which contains “successful” status strings

/succ2=120 End of range in (system) digital state table which contains “successful” status strings

/bad1=121 Begin of range in (system) digital state table which contains “Bad Input” status strings

/bad2=130 End of range in (system) digital state table which contains “Bad Input” status strings

Page 63: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Parameter Meaning

/recovery=shutdown Recovery flag. Possibilities are SHUTDOWN and TS

/recovery_time=”*-8 hours” In conjunction with the recovery flag determines the maximum amount of time for going back into the archive. The ‘time’ syntax is in PI Time Format.

(See the Data Archive Manual for more information on the time string format.)

/sr=20 Sign-Up-For-Updates rate in seconds.

/skip_time=10 Maximum delay time in seconds for scan class. Default value=2

Detailed explanation for command line parameters

/ps = R

Specifies the point source of the tags the Interface will operate on.

/in = 1

The Interface number is specified here. It corresponds to the Location 1 of a tag.

/ec = 21

For additional configuration information regarding IORates, see the section entitled “IO Rate Tags.”

/f = HH:MM:SS,hh:mm:ss

The scan frequency for different scan classes. There is no set limit on the number of scan classes .

Example: You can specify 3 scan frequencies by inserting:

. . . /f=00:00:03 /f=00:00:05 /f=00:00:30

which defines 3 scan classes 1, 2 and 3. The tag having the value of 1 in location 4 will belong to scan class 1, being scanned every 3 seconds.

Each instance of the /f flag on the command line defines a scan class for the interface. Each scan class is, in turn, associated with a scanning frequency.

The time between scans for a class is given in terms of hours (HH), minutes (MM), and seconds (SS). The scans can be scheduled to occur at a particular offset with respect to the hour in terms of hours (hh), minutes (mm), and seconds (ss). The first occurrence of the /f flag on the command line defines the first scan class of the interface, the second occurrence defines the second scan class, and so on. All PI Points that have location4 set to 1 will receive values at the frequency defined by the first scan class. Similarly, all points that have location4 set to 2 will receive values at the frequency specified by the second scan class, and so on.

Two scan classes are defined in the following example:/f=00:01:00,00:00:05 /f=00:00:07The first scan class has a scanning frequency of 1 minute with an offset of 5 seconds with respect

Page 64: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

to the minute. This means that if the interface is started at 12:03:06, the first scan will be at 12:03:10, the second scan will be at 12:03:15, and so on. The second scan class has a scanning frequency of 7 seconds. Since there is no offset given, the absolute times at which the scans are made is not defined.

The definition of a scan class does not guarantee that the associated points will be scanned at the given frequency. If the interface is under a large load, some scans may occur late or be skipped entirely.

If a scan is skipped, the interface will print out an error message.

Note : To specify an offset of 0, use the frequency instead.E.g. /f=01:00:00,01:00:00 defines a scan at every full hour.

/f=01:00:00,00:00:00 is the same as /f=01:00:00 and starts the scan without offset

/deb=0

The interface is able to print additional information into the interface specific logfile, depending on the debug level used. The amount of log information increases with the debug number as follows:

Debug level

Output

0 Normal interface operation, Print out error messages causing data loss.

Examples: connection loss, tag rejected due to wrong configuration,…

1 Additional information about interface operation

Examples: tag information, startup parameter defaults, ODBC related info

2 Information about errors which will be handled by the interface and will not cause data loss but points out problems

examples: protocol errors which were recovered by retry function

3 display original data and data types (raw values received by ODBC fetch calls) per tag per scan; this helps to trace data type conversion

4 prints out the actual values before sending to PI (values used in pisn_putsnapshotx and pisn_sendexceptions functions) per tag per scan

5 prints out each subroutine the program runs through;

(only for onsite test purposes)

/dsn=DSNname

Data source name created via ODBC administrator utility, found on the Windows NT Control Panel. We do only support Machine Data-sources and preferably System Data-sources. When the Interface is installed as Service, only System Data-sources will work!

For more information on how to setup a DSN, please see your 32bit ODBC Administrator Help file (Control Panel) or the documentation of your ODBC driver.

Plant Suite RDBMS to PI Interface 69

Page 65: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

IO Rate Tags

/global = c:\pi\sql\globals.dat

Points to the filename that contains the definition of global variables. (See chapter “Global Variables”)

/host = computer_name

This is the hostname of the computer running the PI Server.

/output = c:\pi\sql\rdbmspi.log

The Interface generates output messages into the given log-file. In order to not overwrite a previous log-file after interface restart, the interface renames the previous log-file to log-file.log;n, where n is a continuos number.

The System Manager is responsible to purge old log-files.

/user_pi

User name for the PI connection. PI Interfaces usually logs in as piadmin. This switch allows logging in as different PI user.

/pass_pi

The password for piadmin account (default) or for the account set by /user_pi parameter.As an alternative, you can wait for the logon prompt and enter the password when it runs in console mode. This will avoid the situation to have a password stored in a startup BAT file, readable for every user on this machine. The password has to be entered only once. On all future startups the interface will remember the password from an encrypted file. This encrypted file has the name of the output file (defined by /output= startup parameter) and the file extension is PI_PWD. The file gets stored in the same directory.

Example: …/in=2… /output=d:\pi\interfaces\rdbmspi\data\rdbmspi.log …

The encrypted password is stored in: d:\pi\interfaces\rdbmspi\data\rdbmspi.PI_PWD

When running the interface as service, the interface must be called at least one time in interactive mode, in order to specify the password after the prompt and let the interface create the encrypted file. The file can be deleted any time and the interface will prompt for a new password after next interactive startup.

Note: The interface will fail when started as service and not having a valid passwordfile (or having /pass_pi=password).

Note: In order to achieve a connection with the PI Server, the file PILOGIN.INI must contain a reference to that PI Server. This can be done in the easiest way via ProcessBook Connection Dialog. If ProcessBook is not installed, please see section PILOGIN.INI at the end of this chapter.

/user_odbc

User name for the ODBC connection. This parameter is required. Databases like MS Access or dBase may not always have usernames set up. In this case a dummy username must be used, e.g /user_odbc=dummy.

/pass_odbc

Password for the ODBC connection. If this parameter is omitted, the standard ODBC connect dialogue prompts the user for the user name and password. This will avoid the situation to have a

OSI Software, Inc. 70

Page 66: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

password stored in a startup BAT file (readable for every user on this machine). The password has to be entered only once. On all future startups the interface will remember the password from an encrypted file. This encrypted file has the name of the output file (defined by /output= startup parameter) and the file extension is ODBC_PWD. The file gets stored in the same directory.

Example: …/in=2… /output=d:\pi\interfaces\rdbmspi\data\rdbmspi.log …

Encrypted password is stored in: d:\pi\interfaces\rdbmspi\data\rdbmspi.ODBC_PWD

When running the interface as service, the interface must be called at least one time in interactive mode, in order to specify the password after the prompt and let the interface create the encrypted file. The file can be deleted any time and the interface will prompt for a new password after next interactive startup.

Note: The interface will fail when started as service and not having a valid passwordfile (or having /pass_odbc=password).

Databases like MS Access or dBase may not always have security set up. In this case a dummy username and password must be used, e.g /pass_odbc=dummy.

/recovery

This start-up flag determines how to handle output points after Shutdown or I/O Timeout digital states. After start-up, the Interface checks these two digital states and goes into the archive for events of the sourcetag. The SQL statement is then executed for each event retrieved from the PI archive.

/recovery_time

Used in conjunction with the /recovery flag and sets the maximum time to go back into the archive.

Following table describes the behavior.

/recovery= Behavior

SHUTDOWN If Shutdown or I/O Timeout digital states are encountered, the Interface goes back into the PI archive either starting at /recovery_time (when Shutdown or I/O Timeout timestamp is older than /recovery_time ) or starts the recovery at the time of the last event (Shutdown or I/O Timeout).Note: If no Shutdown or I/O Timeout event is encountered, no recovery takes place.

TS Starts the recovery from /recovery_time= time or from the last snapshot of the output point if this is later.

NO_REC Default value. No recovery takes place. The /recovery_time keyword is ignored.

Note: Remember, the output point contains a copy of all data successfully downloaded from the source point. The current snapshot of the output point therefore marks the last downloaded value. See also section “Limitations and future enhancements

/sql = c:\pi\sql

Points to the destination where ASCII files with SQL statements reside.

Plant Suite RDBMS to PI Interface 71

Page 67: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

IO Rate Tags

/sr

Sets the Sign-for-Updates scan period in seconds. The Interface checks each defined period of time if some changes in point database were made. Default value is 35 sec.

/stopstat

If the /stopstat flag is present on the startup command line, then the digital state I/O Timeout will be written to each PI Point when the interface is stopped.

If /stopstat=digstate is present on the command line, then the digital state digstate will be written to each PI Point when the interface is stopped. digstate can be any digital state that is defined in the PI 2 digital state table or the PI 3 system digital state table, depending upon whether the home node is a PI 2 or PI 3 system.

If neither /stopstat nor /stopstat=digstate is specified on the command line, then the default is not to write digital states to each input point when the interface is stopped.

Note: digstate can contain spaces but then the string must be embedded in double quotes.

Example:/stopstat=”I/O Timeout”

The /stopstat=shutdown option is the recommended flag.

/skip_time

Timeout in seconds for scan class. If the actual execution time for a scan class gets over the predicted scheduled time of more than skip_time seconds the scan execution is skipped. Default value is two seconds.

/succ1

Defines the start of successful area filled with strings representing a positive status.

/succ2

Defines the end of successful area filled with strings representing a positive status.

/bad1

Defines the start of bad value area filled with strings representing a negative status.

/bad2

Defines the end of bad value area filled with strings representing a negative status.

/test = “tagname”

The “/test” mode allows to test only one query at a time. For example, “/test=tag1”means connect, run the configuration for “tag1”, print results and then exit. No data is stored in RDB and PI.

/tf=tagname

Each scan class can get its own I/O rate tag. The order in the startup line will lay down the tagname to the related scan class.

After finalized scan of a certain scan class the number of successfully executed queries will be stored into the related I/O rate tag.

Example: You can specify 2 scan frequencies by inserting:

OSI Software, Inc. 72

Page 68: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

. . . /f=00:00:03 /f=00:00:05 /tf=tagname1 /tf=tagname2

Scan class 1 will have I/O rate tag tagname1 and scan class 2 will own tagname2.

Note: In the current version we only support tagnames without spaces related to their occurrence in the startup line.

Startup as console applicationTo start the interface, run the rdbmspi.bat batch file from the Interface directory.

To stop the interface type Ctrl^C or Ctrl^Break in the Interface’s standard output window.

To automate startup, you may add rdbmspi.bat to c:\pi\adm\pisitetsart.bat.

Startup as Windows NT Service

NT Service Installation

Rdbmspi Interface is installed as NT service by running the command rdbmspi -install from the Interface directory. To remove the service from the Windows NT Registry Database type

rdbmspi –remove.

Note: The service is created to start in manual mode without any dependency!

NT Service Start and Stop

The Interface’s directory should contain two files with the same name but different file extensions: rdbmspi .exe and rdbmspi.bat. (The batch file contains all the startup parameters used when the executable starts.) Once the service is created (via rdbmspi –install command) it can be started, stopped, paused and resumed from the Services dialog box in the Control Panel or directly by typing rdbmspi –start or rdbmspi –stop.

To determine if the Interface is running as a service, look at the Control Panel - Services dialog box. The status says “Started” if the Interface is running; the status is blank if it is not running. Alternatively you can list all of the NT services that are currently running by typing net start at the command prompt and see if rdbmspi is listed there.

Note: Services are automatically stopped on system shutdown but are not stopped when a user logs off from an NT console. To manually stop all running PI services, run the pisrvstop.bat command file from the pi\adm directory. This command file calls pisrvsitestop.bat, which stops the interfaces and other site-specific programs that have been configured to run as NT services.

Any site-specific services that are expected to be associated with PI should have startup and shutdown commands added to the pisrvsitestart.bat and the pisrvsitestop.bat command files.

By default the PI services are set in manual mode. This means that the services must be told to start and stop using the pisrvstart.bat and pisrvstop.bat commands. To allow the PI System to start automatically on reboot, services can be set to automatic from the Services dialog box in the Control Panel.

Plant Suite RDBMS to PI Interface 73

Page 69: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

IO Rate Tags

Optional Switches

rdbmspi –install –depend “tcpip pinetmgr” -auto

-dependStarts the interface after activation of specified services. Possibilities are:

-depend “tcpip pinetmgr”

-depend “bufserv tcpip”

-depend tcpip

-autoAutomatically starts the service after reboot of the operating.

PILOGIN.INIThe PILOGIN.INI file contains configuration and preference settings for the PI Server connections with PI-Client Software (e.g. ProcessBook or Interface). The file generally resides in the PIPC\DAT directory. ProcessBook SETUP.EXE creates this file with default settings. As you use PI-ProcessBook and the Connections feature, this file is modified.

Withot having ProcessBook installed, the file must be manually modified using any ASCII text editor.

The settings used in the examples are samples and not necessarily the default values.The Services section of the PILOGIN.INI identifies the server type:

PI1=PI

The Defaults section specifies the default server and user ID:

PIServer=tomato

PI1USER=DLeod

The PINodeIdentifiers section of PILogin.ini maps the PI Server names to codes which are stored in the ProcessBook files. ProcessBook uses these codes instead of the actual node names in order to save space and facilitate changing server names. You usually make changes to this section through the Connections command under the PI-ProcessBook File menu. Here is an example of this section:

[PINodeIdentifiers]

;PI#=Servername, NodeID, Port#

PI1=casaba,11111,545

PI2=orange,85776,545

PI3=localhost,62085,5450

PI4=olive,2153,5450

PI5=206.79.198.232,41369,5450

OSI Software, Inc. 74

Page 70: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

The first parameter after the equal sign is the PI Server name. This is usually a TCP/IP node name, but it can also be a TCP/IP address as shown on the last line.

The second parameter is the node identifier, which is stored with each tag name used in a ProcessBook file. This parameter is relevant for ProcessBook but not for the RDBMSPI Interface.

The third parameter is the TCP port number. Port 545 is used for PI Servers on OpenVMS. Port 5450 is used for PI Servers on Windows NT and UNIX.

Example (minimum) PILOGIN.INI File:

[Services]PI1=PI

[PINODEIDENTIFIERS]PI1=alpha22,48872,5450

[DEFAULTS]PIServer=alpha1PI1USER=piadmin

Plant Suite RDBMS to PI Interface 75

Page 71: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

ShutdownYou can manually stop the interface by pressing Ctrl^C or Ctrl^Break, when used in interactive mode. When the interface runs as service, you can stop it via the Control Panel or by entering the command: rdbmspi -stop

On a Windows NT PI3 Home Node, include the interface stop procedure in pisrvsitestop.bat. It should look like this:

echo Stopping Site Specific PI System Services.....\interfaces\rmp_sk\rmp_sk –stop..\interfaces\random\random –stop..\interfaces\enraf\rdbmspi –stop:theend

Page 72: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Error and information messagesYou can find messages from the interface in two places:

1. The standard PI message log called PIPC.LOG (located in \PIPC\DAT directory) accepts general information end error messages like used point source, number of points handled,...

2. The second file is interface-specific (/output=filename) and has all important information printed out by the interface. The amount of information is dependent on the debug level used (/deb=1-5).

Note: Errors related to tag values will also be reported in giving the tag a BAD INPUT state. This happens, if the status of a value derived from the RDB is BAD. Points can also get a status of I/O Timeout if the Interface detects connection problems.

Plant Suite RDBMS to PI Interface 79

Page 73: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Hints for PI System Manager

When using the option to query a complete time series for a tag, the query must solve the problem that the value/timestamp pairs arrive ordered by timestamp.Otherwise the interface cannot perform exception reporting and the piserver cannot do compression.

Reconnect attempts are modified to be more general. In the past we have learned that only a few ODBC drivers report detailed error codes for networking problems. This was required for RDBMSPI Version 1.28 to reconnect (codes 08xxx (network problems) and xxTxx (timeout) were required). As a result the interface reported an error (typically S1000) but did not reconnect (because is a general error).Now, on any serious error we test connection with the RDB and do a reconnect if necessary. This new behavior was tested with Oracle and SQL Server.

If the field size is less than required for the current value to be passed, the interface prints an error message into the log file but continues to try on the next event with the value valid at that time.E.g. if the field length of a character field is 2 and the interface tries to store “ON” and “OFF” values, “ON” will work, “OFF” will generate an error.

If the query contains a constant in the select range and the constant is a string, the ODBC driver transforms this string to capital letters.E.g. SELECT timestamp,0,’No Sample’ WHERE …the “NO SAMPLE” arrives in the PI part of the interface. Searches in the Bad and Good area are now case insensitive to address this problem.

Error messages in the logfile are only displayed on first occurance. To avoid logfiles with many same messages, we report only when the error is resolved.

The minimum field size for digital state output is 12 characters. Some ODBC drivers also require one additional character for the string termination byte (NULL). In this case we need a minimum field size of 13 characters.

SELECT statements using LST or LET may not get any data if the clocks of PI System computer and RDBMS System are not synchronised. That is because LST and LET are filled from the Interface but compared to RDBMS timestamps.

Plant Suite RDBMS to PI Interface 81

Page 74: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Interface Test EnvironmentThe Interface Version 1.28 was tested using the following software versions:

Operating System Windows NT 4.0 Workstation and Server, SP1 and SP3

C-Compiler MS Visual C/C++ 5.0

PI 3.1 on NT (Intel), Build 2.71 and 2.81

PI-ODBC-PC 1.1.0.0 (12/27/96)

UNIINT 2.23, 2.25, 2.31

Oracle - RDB Database 6.1 (Alpha)

Oracle ODBC Driver for RDB 2.10.1100

MS SQL Server 6.5

MS SQL Server ODBC Driver 2.65.0240

Oracle 7

MS Oracle ODBC Driver 2.00.00.6325

Oracle72 1.13.05.00

Visegenic 32-bit Oracle driver 2.00.00.00

dBase III, dBase IV

Microsoft dBase Driver 3.50.360200

MS Access 95, MS Access 97

Microsoft Access Driver 3.50.360200

Plant Suite RDBMS to PI Interface 83

Page 75: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Startup

The Interface Version 2.08 was tested using the following software versions:

Intel platform only

Operating System Windows NT 4.0 Workstation SP4

C-Compiler MS Visual C/C++ 6.0 SP2

PI 3.2 - SR1 Build 357.8

PI-API 1.2.3.4 and PI-API 1.3.0.0

RDBMS ODBC driver

MS SQL 6.50.201 (ROBUSTNESS tests only)

3.60.03.19

MS SQL 7.00.623 3.70.06.23

ORACLE 7.1 1.13.05.00 (Oracle72)

2.00.00.00 (Visigenic 32-bit Oracle driver)

2.00.00.6325 (Microsoft ODBC Driver for Oracle)

ORACLE 8.0 8.0.5.0.0 8.00.06.00

OSI Software, Inc. 84

Page 76: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

More Examples

Insert or UpdateA usual request is to keep a copy of current snapshot values in a relational table. The problem is that the query must decide between INSERT and UPDATE. If the PI tag already has a record in that table, UPDATE is required. If there is no record for this tag yet, INSERT has to be used. Unfortunately SQL language does not provide if…then mechanisms. The usual solution is to write a stored procedure to get this flexibility. Luckily we also support stored procedures.

But there is also a SQL solution to this problem:

Use a second table with the same fields defined as the target table. This “dummy” table has to have exactly one record with “dymmy” data. To do an INSERT or UPDATE, use a RIGHT JOIN between the two tables as in the example below:

Table1 has 2 fields, V1 and P1

Table2 has 2 fields, V1 and P1

Table2 has exactly one record with data.

Query INSERT_UPDATE:

UPDATE Tbl1 RIGHT JOIN Tbl2 ON Tbl1.P1 = Tbl2.P1 SET Tbl1.P1 = Tbl2.P1, Tbl1.V1 = tbl2.V1;

How does it work?

The trick itself lies in the RIGHT JOIN. RIGHT JOIN means, include all records (exactly one) from the table on the right and those fields from the lefthand table where the fields are equal.

If we would only do a SELECT then we would either see one record with data in all fields (the UPDATE situation) or we see only data from the dummy table and no data BUT EMPTY FIELDS from the target table (INSERT situation).

If we now do an UPDATE on this RIGHT JOIN, in the case of empty fields, the RIGHT JOIN writes back a new record.

In the other case the RIGHT JOIN just generates an UPDATE.

For use with our RDBMS Interface, we need to split the problem into more than one query

UPDATE of dummy table;

UPDATE .... RIGHT JOIN...;

This is no problem because the RDBMS Interface supports multiple statements in one SQL file.

Plant Suite RDBMS to PI Interface 85

Page 77: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Limitations and future enhancementsDue to the wide range of RDB’s and the complexity of this Interface, functionality is not fixed. Also ODBC is still improved from Microsoft which can be seen looking at frequent updates of ODBC Driver Manager, ODBC API and ODBC library. During development we found a number of limitations which could not be solved in this version:

The Interface requires ODBC Driver Manager 3.x since we had to use more enhanced functions for error detection and robustness (RDB reconnect). The ODBC Driver Manager update comes free with a number Microsoft products or can be downloaded from the Microsoft Web Page.Version 1.28 of the RDBMSPI Interface (available on request from TechSupport) can still be used for ODBC 2.x Driver Manager.

The Interface supports PI3 data types and millisecond timestamps but does not support the new PI-API 1.3 functions for Exception Reporting. That means for millisecond timestamps, Exception Reporting cannot be performed (pisn_putsnapshotx). The advantage is that this interface version works with PI-API 1.2.3.4.

The next Interface Release will use new PI-API 1.3 functions.

Event based output signs up for exceptions. Exceptions are queued but only contain information about classic datatypes. For extended datatypes that means that the value itself must be retrieved from the snapshot once the exception is recognized. Now if 2 or more exceptions for the same tag appear in the exception queue, the snapshot value of that tag would only represent the last event. Previous events either went into the archive or were filtered out by compression. As a result, events for a tag of type INT32, FLOAT64, STRING and BLOB, coming into PI with a short timedifference, will appear in the RDB with the same value.

Writing IO Timeout values to all interface tags on RDB connection problems is not optional. As a result a query like “SELECT …. WHERE timestamp > ?; P1=TS” will miss data for the period between last retrieved value and the connection problem time.The reason is that TS gets filled with the timestamp of the IO Timeout value rather than the previous retrievd “real” value.

PI point changes will only be recorded during interface operation. Information about a PI point, which is modified during interface down-time, will get lost.

Although the interface is able to write out of order data, the ability to store older data is limited to the behavior of PI-API calls used (pisn_sendexceptions and pisn_putsnapshotx). E.g: – An existing value in the PI archive cannot be replaced.– A second value in the archive cannot be created (unless it is the current snapshot value).

The next Interface Release will support optional replacement of archive data.

Page 78: PlantSuite RDBMS to PI - OSIsoftcdn.osisoft.com/interfaces/2037/PI_RDBMSPI_2.15.doc · Web viewThe execution of such a procedure then returns the ‘standard’ result data set. In

Revision HistoryDate Author Comments

24-Jan-97 BB, MF 50 % draft

20-Mar-97 BB, MF Preliminary Manual

10-Dec-97 BB Release Manual Version 1.21

18-Sep-98 BB More details addedrelated to RDBMS Interface Version 1.27

06-Nov-98 BB Release Manual Version 1.28

29-Nov-98 MF 50 % draft of Version 2

01-Feb-99 BB, MF

25-Feb-99 MH,MF Examples tested and corrected

04-Jun-99 BB Release Version 2.08