Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Piemēri enerģijas patēriņa samazināšanā
ēkās
Enerģijas forums
Cēsis
2016. gada 28.septembris
Gatis Žogla
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs 2
ESOŠĀS ĒKAS PATĒRĒ MAZ SILTUMENERĢIJAS
0
20
40
60
80
100
120
140
160
180
200
Esošās ēkas Renovētās ēkas Zema enerģijas patēriņaēkas
Pasīvās ēkas
Ap
ku
re,
kW
h/m
2 g
ad
ā
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs 3
ESOŠĀS SIENAS IR PIETIEKAMI BIEZAS
Silikāta / māla ķieģeļi
Keramzītbetona paneļi
Gāzbetona paneļi
Minerālvate / putu polistirols
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs 4
ĒKU ATJAUNOŠANAS MĒRĶIS
Samazināt kopējo maksājumu par ēkas enerģijas
patēriņu un uzturēšanu / ekspluatāciju
Vidējais esošo ēku enerģijas patēriņš apkurei ir ap
180 kWh/m2 gadā jeb 11,5 EUR/m2 gadā
Veicot pilnu ēku renovāciju ēkas apkures patēriņš
samazinās līdz aptuveni 70 kWh/m2 gadā jeb 4,5
EUR/m2 gadā
Ietaupījums ir 7 EUR/m2 gadā
Renovācijas izmaksas ir ap 80 – 100 EUR /m2
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
ĒKAS PILNA
ATJAUNOŠANA
• Reālu enerģijas ietaupījumu dod
pilna ēkas renovācija
• Ēkas renovācija jāveic ievērojot
Latvijas būvnormatīvu prasības
• Latvijas būvnormatīvs LBN 002-
15 norobežojošo konstrukciju
siltumtehnika
• No būvdarbu veicējiem jāprasa
pagarināti garantijas termiņi
• Vidēji ēkas apkures enerģijas
patēriņš tiek samazināts par
~60%
• Drīzumā būs pieejams līdz 50%
līdzfinansējums daudzdzīvokļu
ēku renovācijai
Norobežojošā
konstrukcija
Sasniedzamā
siltuma
caurlaidības
koeficienta
vērtība
publiskām
ēkām, W/(m2K)
Minimālais
siltumizolācijas
biezums
renovējot esošu
tipveida ēku, cm
Sienas 0,187 17,5
Bēniņi un
jumti
0,187 16,0
Pagrabi 0,187 15,0
Logi 1,31 Divstiklu
pakešu logs
Durvis 1,872 Divstiklu
pakešu
durvis vai
siltinātas
metāla durvis
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs 6
ĒKAS ATJAUNOŠANAS PAPILDU IEGUVUMI
Samazinātas remontu un uzturēšanas izmaksas
Pieaug ēkas mūžs
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs 7
ĒKAS ATJAUNOŠANAS PAPILDU IEGUVUMI
Ēkas izskata uzlabojums un vērtības pieaugums
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
ĒKAS ATJAUNOŠANA KĀ NEVAJADZĒTU DARĪT
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
19
http://aculiecinieks.delfi.lv/
news/novados/veja-
postijumi-
olaine.d?id=37892509
2011.gada 8.aprīlis
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
IEGŪTO REZULTĀTU
UZRAUDZĪBA DAUDZDZĪVOKĻU ĒKU
RENOVĀCIJA RUMĀNIJĀ
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
21
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
22
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
BET...
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
24
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
25
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
26
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
IEKŠTELPU KLIMATS
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
• Cilvēku faktori
• VIELMAIŅAS ĀTRUMS
• APĢĒRBS
• Iekštelpu vides faktori
• TEMPERATŪRA
• MITRUMS
• GAISA KUSTĪBAS ĀTRUMS
• GAISA PIESĀRŅOJUMS
TERMĀLĀ KOMFORTA NOTEICOŠIE FAKTORI
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
VAI 21 OC IR SILTI?
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Ēka/ telpa Kategorija
Operatīvā temperatūra, °C
Minimālā
(ziemas
apkures
periodā) – 1,0
clo
Maksimālā
(vasaras
dzesēšanas
periodā) – 0,5
clo
Dzīvojamā ēka: telpas
(guļamistaba, virtuve
utt.)
Mazkustīgs stāvoklis –
1,2 met
I 21,0 25,5
II 20,0 26,0
III 18,0 27,0
Dzīvojamā ēka: citas
telpas (noliktava, halle
utt.)
Stāvēšana, staigāšana –
1,6 met
I 18,0
II 16,0
III 14,0
Ofisa kabinets1
Mazkustīgs stāvoklis –
1,2 met
I 21,0 25,5
II 20,0 26,0
III 19,0 27,0
Atvērtais birojs2
Mazkustīgs stāvoklis –
1,2 met
I 21,0 25,5
II 20,0 26,0
III 19,0 27,0
Konferenču zāle
Mazkustīgs stāvoklis –
1,2 met
I 21,0 25,5
II 20,0 26,0
III 19,0 27,0
Auditorija
Mazkustīgs stāvoklis –
1,2 met
I 21,0 25,5
II 20,0 26,0
III 19,0 27,0
Kafejnīca, restorāns
Mazkustīgs stāvoklis –
1,2 met
I 21,0 25,5
II 20,0 26,0
III 19,0 27,0
Klase
Mazkustīgs stāvoklis –
1,2 met
I 21,0 25,0
II 20,0 26,0
III 19,0 27,0
Bērnudārzs
Stāvēšana/ staigāšana –
1,4 met
I 19,0 24,5
II 17,5 25,5
III 16,5 26,0
Universālveikals
Stāvēšana/ staigāšana –
1,6 met
I 17,5 24,0
II 16,0 25,0
III 15,0 26,0
1 Slēgts kabinets ar logu un durvīm. 2 Atvērtais birojs līdzīgs klasei, kur galdi ir sakārtoti rindās vai savādāk un
atdalīti ar sienām vai bez.
LVS EN 15251:2007 – Telpu mikroklimata (gaisa kvalitātes, temperatūras režīma, apgaismojuma un
akustikas) parametri ēku projektēšanai un to energoefektivitātes novērtēšanai
TEMPERATŪRAS PRASĪBAS
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Aktivitāte W met
Guļus stāvoklis 83 0,8
Sēdēšana 104 1,0
Stāvēšana 126 1,2
Braukšana mašīnā 144 1,4
Staigāšana, 5 km/h 360 3,4
Dejošana, basketbols,
peldēšana
624 6,0
Hokejs, futbols 835 8,0
Skriešana ar 15 km/h 990 9,5
• Vielmaiņas ātrums
tiek mērīts ar
mērvienību “met”
• 1 met atbilst sēdoša,
neaktīva cilvēka
vielmaiņas ātrumam
http://thumbs.dreamst
ime.com/thumblarge_
283/1214326572x9yH
hw.jpg
http://www.chumpysclipart.com/im
ages/illustrations/xsmall2/4547_pic
ture_of_an_overheated_man.jpg
VIELMAIŅAS ĀTRUMS
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Apģērbs
Siltuma
pretestība,
m2K/W
clo
Bez apģērba 0 0
Šorti 0,016 0,1
Viegls vasaras apģērbs – īss krekls,
īsas bikses, zeķes, sandales 0,078 0,5
Ielas apģērbs – krekls, vējjaka, garās
bikses, zeķes, sandales 0,155 1,0
Ielas apģērbs ar mēteli 0,233 1,5
Apģērbs mitram, aukstam laikam –
krekls, silta vējjaka un bikses,
džemperis, vilnas mētelis un zeķes,
apavi
0,233 – 0,310 1,5 – 2,0
Arktikas apģērbs no 0,465 no 3,0
• Apģērba termiskā
pretestība tiek
noteikta ar
mērvienības “clo”
palīdzību
• 1 clo atbilst sēdoša
neaktīva cilvēka
apģērbam
APĢĒRBS
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Zemas norobežojošo konstrukcijas virsmas temperatūras izraisa nesabalansētu siltuma starojumu
- 10°C
Āra Gaisa
temperatūra
22°C
Telpas gaisa
temperatūra
Visas norobežojošo konstrukciju virsmas ir siltas, kā rezultātā nerodas siltuma starojuma diskomforts
9.5
16.2 18.5
18.2
Operatīvā
temperatūra
22 Gaisa temperatūra
14.5
19.1
21.4 21.6
21.2 Operatīvā
temperatūra
22 Gaisa temperatūra
17.8
Avots: PassNet (Intelligent Energy Europe)
Nesiltināta ēka Pasīvā ēka
OPERATĪVĀ TEMPERATŪRA UN STAROJUMA TEMPERATŪRA
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
SILTUMENERĢIJAS
PATĒRIŅA
REGULĒŠANA
• Siltummezgls
• Termostatiskie ventiļi
• Temperatūras grafiki
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
SILTUMMEZGLS
• Siltummezglā tiek veikta
siltumenerģijas patēriņa
uzskaite
• Siltummezglā tiek
noteikts ēkai padodamais
siltumenerģijas
daudzums
• Siltummezglā tiek
sagatavots ēkas
siltumnesējs un karstais
ūdens
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
KAD JĀVEIC
SILTUMMEZGLA
IEREGULĒŠANA
Visās telpās novērojamas līdzīgas gaisa temperatūras
Telpu gaisa temperatūra visu apkures sezonu ir par zemu vai par
augstu
Telpu gaisa temperatūra apkures
sezonā mainās atkarībā no āra
gaisa temperatūras
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
TELPU GAISA TEMPERATŪRA
VISU APKURES SEZONU IR PAR
ZEMU VAI PAR AUGSTU
10
12
14
16
18
20
22
24
26
oC
Vēlamā temperatūra
Temperatūra par zemu
Temperatūra par augstu
Jāmaina uzstādītā telpu
gaisa temperatūra
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
TELPU GAISA TEMPERATŪRA
APKURES SEZONĀ MAINĀS
ATKARĪBĀ NO ĀRA GAISA
TEMPERATŪRAS
10
12
14
16
18
20
22
24
26
oC
Vēlamā temperatūra
Reālā temperatūra
Reālā temperatūra
Jāmaina uzstādītā
temperatūras
līkne
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
TERMOSTATISKIE
VENTIĻI
Termostatiskie ventiļi
nodrošina nemainīgu telpas
gaisa temperatūru
Dažādās telpās termostatiskā
ventiļa darbība var atšķirties
(ventilis darbojas atkarībā no
termostatiskā sensora
temperatūras nevis telpa
gaisa temperatūras)
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
DARBĪBAS
PRINCIPS
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
TELPAS GAISA TEMPERATŪRA
IZMANTOJOT
TERMOSTATISKOS VENTIĻUS
• Siltuma inerces
dēļ telpas gaisa
temperatūra
svārstās nelielās
robežās
18
18,5
19
19,5
20
20,5
21
21,5
22
1
11
2
22
3
33
4
44
5
55
6
66
7
77
8
88
9
10
00
11
11
12
22
13
33
14
44
15
55
16
66
17
77
18
88
19
99
21
10
22
21
23
32
24
43
25
54
26
65
27
76
oC
Attēlā redzams 2 diennakšu mērījumu rezultāts
Šajā gadījumā diennakts laikā termostatiskais
ventilis atveras 15 reizes
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
PROGRAMMĒJAMIE
TERMOSTATISKIE
VENTIĻI
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
TEMPERATŪRAS
GRAFIKI
• Temperatūras grafikus
iespējams uzstādīt gan
siltummezglā, gan ar
programmējamo
termostatisko ventiļu
palīdzību
• Lietojot programmējamos
termostatiskos ventiļus
iespējams panākt lielāku
siltumenerģijas patēriņa
ietaupījumu
10
12
14
16
18
20
22
1:0
0
2:0
0
3:0
0
4:0
0
5:0
0
6:0
0
7:0
0
8:0
0
9:0
0
10
:00
11
:00
12
:00
13
:00
14
:00
15
:00
16
:00
17
:00
18
:00
19
:00
20
:00
21
:00
22
:00
23
:00
0:0
0
oC
Vienmērīgs temperatūras grafiks
Mainīgs temperatūras grafiks
Nedēļas nogales temperatūras grafiks
• Samazinot telpas gaisa vidējo
temperatūru par 1 oC iespējams
ietaupīt līdz 7% siltumenerģijas
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
• Ieteicamais telpas
gaisa relatīvā
mitruma līmenis ir
35 līdz 65 %
Relatīvā mitruma saturs, %100
90
80
70
60
50
40
30
20
10
0
Pārāk sauss
Telpas gaisa temperatūra, oC
12 14 16 18 20 22 24 26 28
Pārāk mitrs
Komfortabls
Apmierinošs
Nekomfortabli auksts
Iekštelpas temperatūra, oC12 14 16 18 20 22 24 26 28
Sien
as v
irsm
as t
emp
erat
ūra
, oC
26
24
22
20
18
16
14
12
Nekomfortabli silts
Vēl joprojām komfortabli
Komfortabli
1
2
MITRUMS
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
-10
-5
0
5
10
15
20
25
30
Jan
vāri
s
Feb
ruār
is
Mar
ts
Ap
rīlis
Mai
js
Jūn
ijs
Jūlij
s
Au
gust
s
Sep
tem
bri
s
Okt
ob
ris
No
vem
bri
s
De
cem
bri
s
Tem
pe
ratū
ra, o
C
Vidējā āra gaisa temperatūra, oC Vidējā telpas gaisa temperatūra, oC0
10
20
30
40
50
60
70
80
90
100
Jan
vāri
s
Feb
ruār
is
Mar
ts
Ap
rīlis
Mai
js
Jūn
ijs
Jūlij
s
Au
gust
s
Sep
tem
bri
s
Okt
ob
ris
No
vem
bri
s
De
cem
bri
s
Re
latī
vais
mit
rum
s, %
Diennakts vidējais āra gaisa relatīvais mitrums, %
Telpas gaisa relatīvais mitrums, %
TELPU VĒDINĀŠANA
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
GAISA KVALITĀTE
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
GAISA KVALITĀTES PROBLĒMA
Jo lielāka gaisa
apmaiņa, jo
augstākas
kvalitātes gaiss
Jo lielāka gaisa
apmaiņa, jo
dārgāk jāmaksā
par gaisa
uzsildīšanu
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
5.04.03.0
0.50.40.3
Svaigā gaisa pieplūde uz cilvēku, m2 /h
CO
2 k
on
cen
trāc
ija,
% 1.0
0.2
0.1
0.03
Grūts darbs, 400 W
Viegls darbs, 200 W
Sēdēšana, 100 W
0.5 1 2 3 4 5 10 20 30 4050 100
2.0
Tilpums % gaisā
- 1 %
- 3 %
- 5 %
- 8%
MiegainumsViegla narkoze
ReibonisApjukums
GalvassāpesBezsamaņa
Aizmiglots skatiens
Dzirdes traucējumi
Apgrūtināta elpošana
Paaugstināta sirds darbība
un asins spiediens
Muskuļu trīce
Svīšana
Kā oglekļa dioksīds ietekmē cilvēka ķermeni?
Ogl
ekļa
dio
ksīd
a k
on
cen
trāc
ija (
pp
m u
n %
)
Bezsamaņa un nāve dažās sekundēs
Krampji un bezsamaņa dažās minūtēs
Grūti elpot
Paātrinās pulss, galvas sāpes, reiboņi
Veselības ierobežojums
Palielinās elpošanas ātrums, miegainums
Komfortabla gaisa kvalitātes ierobežojums
Svaigs āra gaiss
200 000 – 20 %
80 000 – 8 %
30 000 – 3 %
10 000 – 1.0 %
5 000 – 0.5 %
2 000 – 0.2 %
1 000 – 0.1 %
400 – 0.04 %
PAAUGSTINĀTAS CO2 KONCENTRĀCIJAS IETEKME UZ CILVĒKA VESELĪBU
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
CO2
koncentrācija,
ppm
Svaigā gaisa
daudzums,
m3/cilv./h
Izmaksas,
EUR/cilv./
apkures
sezonā
18400 1 2.2
4000 5 10.9
2200 10 21.8
1600 15 32.7
1300 20 43.6
1120 25 54.5
1000 30 65.4
915 35 76.3
850 40 87.3
800 45 98.2
760 50 109.1
Aprēķins veikts pie siltumenerģijas tarifa 65 EUR/MWh
CIK MAKSĀ SVAIGS GAISS?
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Telpu gaisa temperatūras mērījumi
Relatīvā gaisa mitruma mērījumi
CO2 koncentrācijas mērījumi, ēkas gaisa apmaiņas noteikšanai
GAISA KVALITĀTES MĒRĪJUMI
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
AR DABĪGO
VENTILĀCIJU
GAISA KVALITĀTE BĒRNUDĀRZOS
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
AR MEHĀNISKO
VENTILĀCIJU
GAISA KVALITĀTE BĒRNUDĀRZOS
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
GAISA KVALITĀTE SKOLĀS
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
23 minūtes 35 minūtes
GAISA KVALITĀTE SKOLĀS
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
11 minūtes 28 minūtes
GAISA KVALITĀTE SKOLĀS
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
• Telpu vēdināšanas mērķis ir izvadīt no ēkas piesārņojošās vielas nevis siltumenerģiju
• Nepareiza (parasti – pārāk ilga) vēdināšana atdzesē ēkas konstrukcijas, kurām ir liela siltumietilpība
TELPU VĒDINĀŠANA
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
izslēgts režīms – ierīce ir pievienota strāvas avotam,
bet gaidīšanas vai darba režīma funkcijas netiek
nodrošinātas. Elektroenerģijas netiek patērēta
gaidīšanas jeb “stand-by” režīms – ierīce ir pievienota
strāvas avotam, bet tiek piedāvāta iespēja ieslēgt ierīci
darba režīmā, kā arī tiek nodrošināta cita informācija
(pulkstenis, u.c.)
darba režīms – iekārta ir pievienota strāvas avotam un
tiek nodrošinātas iekārtas galvenās funkcijas
IEKĀRTU DARBĪBAS REŽĪMI
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
ENERĢIJAS PATĒRIŅŠ
GAIDĪŠANAS REŽĪMĀ
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
PIEMĒRS: GAIDĪŠANAS
REŽĪMS
0,36 EUR/ gadā
4,16 EUR/ gadā
Kādās ir gaidīšanas režīma izmaksas gadā, ja enerģijas patēriņš ir:
• gaidīšanas režīmā – 3 W
• darba režīmā – 25 W
Ierīces darbināšanas laiks ir 15 minūtes katru dienu
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
PIEMĒRS: LEDUSSKAPJA IZVIETOJUMS
0 %
0 kWh / gadā
0 EUR / gadā
12 %
36 kWh / gadā
5,4 EUR / gadā
100 %
292 kWh / gadā
43,8 EUR / gadā
156 %
456 kWh / gadā
68,48 EUR / gadā
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
LEDUSSKAPJA TERMOGRĀFIJA
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Datu vizuāla attēlošana
Ikgadējo datu analīze
No laika atkarīgo datu analīze
Regresijas un korelācijas analīze
Datu apstrādes metodes
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
No laika atkarīgo datu analīze
0
1000
2000
3000
4000
5000
6000
7000
janvāris
febru
āri
s
ma
rts
ap
rīlis
ma
ijs
jūnijs
jūlij
s
au
gusts
septe
mb
ris
okto
bris
no
ve
mbri
s
de
ce
mbri
s
2013
2014
2015
2016
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Enerģijas patēriņa izmaiņu analīze
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
Enerģijas patēriņa izmaiņu analīze (noviržu kumulatīvo summu metode)
gads mēnesis
skaitītāja
rādījums,
kWh patēriņš, kWh
2013
janvāris 63770 6197
februāris 67711 3941
marts 72303 4592
aprīlis 74864 2561
maijs 76195 1331
jūnijs 77143 948
jūlijs 78115 972
augusts 79060 945
septembris 80469 1409
oktobris 82835 2366
novembris 86025 3190
decembris 89081 3056
2014
janvāris 95172 6091
februāris 99083 3911
marts 101918 2835
aprīlis 103921 2003
maijs 105338 1417
jūnijs 106300 962
jūlijs 107228 928
augusts 108166 938
septembris 109312 1146
oktobris 111608 2296
novembris 114779 3171
decembris 118204 3425
2015
janvāris 122534 4330
februāris 125617 3083
marts 128142 2525
aprīlis 130212 2070
maijs 131470 1258
jūnijs 132221 751
jūlijs 133020 799
augusts 133764 744
septembris 134575 811
oktobris 136290 1715
novembris 138050 1760
decembris 140110 2060
2016
janvāris 142740 2630
februāris 144730 1990
Supporting Local Authoritites in the Development and Integration of SEAPs with
Energy management SystemsAccording to ISO 500001 www.500001seaps.eu
@500001SEAPs
ATSITIENA EFEKTS
(REBOUND EFFECT)
• Pieaugot energoefektivitātei, pieaug patēriņš
• Iemesli
• TEHNISKI – NOVECO MATERIĀLI, RODAS DEFEKTI
• UZVEDĪBAS – PAAUGSTINĀTAS TELPU GAISA
TEMPERATŪRAS, PĀRĀK BIEŽI VĒDINĀTAS TELPAS
Par atsitiena efektu - http://en.wikipedia.org/wiki/Rebound_effect_%28conservation%29