    General Handling & Storage1. I Heating PEX or Heating PEX-AL-PEX connections must be made in

    temperatures lower than 30.0F (1.1C), caution must be taken to allowthe tubing to orm a proper seal against the barb. Apply the connectionslowly to ensure the tubing material conorms to the barb.

    2. Do not allow the luid temperature to exceed:

    200.0F (93.3C) at 80 psi (5.5 bar) or Heating PEX. 200.0F (93.3C) at 100 psi (6.9 bar) or Heating PEX-AL-PEX.

    3. Do not allow the tubing to be exposed to sunlight, or direct UVexposure or more than 30 days maximum. I stored outside,tubing must remain covered by a UV resistant material.

    4. Do not allow the tubing to come in contact with any o the ollowing:

    Petroleum based products Pipesealants. Firewallsealants,exceptthoseratedforusewithHeating

    PEX or Heating PEX-AL-PEX. Kerosene. Gasoline. Fueloils. Cuttingoils. Asphalt.

    Contaminated soils or building materials.

    5. Do not use i the tubing has visible gouges, cuts, cracks, abrasions,signs o physical damage, or other deects.

    6. Do not use in swimming pools or other systems that use high levels ochlorine.

    7. Use bend supports when necessary (Heating PEX only).

    8. Do not kink. I kinking occurs, use a repair coupling.

    9. Do not expose tubing to rough terrain that may cause punctures, cuts,or other damage.

    10. Do not use tubing to transer natural gas or any otherunapproved substance.

    Contents

    GeneralHandling&Storage 3

    GeneralInstallationCautions 3

    StandardsandListings 4

    Slab-on-gradeApplications 5

    SitePreparation 5

    Insulation Requirements 5

    Type o Insulation 5

    Post Concrete Pour 5

    ControlJointsandSawCuts 5

    TubeSpacing 6

    Fasteners 6

    SlabProleandGeneralDetails 6

    InstallationSteps 6

    ThinSlaboverFrameFloorApplications 10

    TubeSpacing 10

    Fasteners 10

    ThinSlabProle 10

    InstallationSteps 10

    Insulation Requirements 13

    ThinSlabwithSleepers 13

    ThinSlabLayoutExample 13

    Under Floor Applications 14

    TubeSpacing 14

    Method o Installation 14

    BendSupports 14

    Pulling Tubing 14

    InstallationSteps 14

    Insulation Requirements 16

    Under Floor Layout Example 16

    Warranty 17

    ! WARNINGYou are required to thoroughly read all installation instructionsand product saety inormation beore beginning the installationo this product. FAILURE TO COMPLY WITH PROPERINSTALLATION INSTRUCTIONS COULD RESULT IN PROPERTYDAMAGE and/or PERSONAL INJURY.Local building or plumbing codes may require modifcations tothe inormation provided. You are required to consult the localbuilding and plumbing codes prior to installation. I thisinormation is not consistent with local building or plumbingcodes, the local codes should be ollowed.Watts is not responsible or damages resulting rom improperinstallation and/or maintenance.Contact Watts at 855.699.2887 with any questions concerningthe installation, operation, or maintenance o Watts Heating PEXor Heating PEX-AL-PEX.

    ! CAUTION

    1. Do not install within 6 (152.4 mm) horizontally or 12 (304.8 mm)vertically to a heat source such as: recessed light ixtures combustible lue vents general heating appliances

    2. Do not install directly to a heat source. A metallic adapter, minimum18 (457.2 mm) in length, must be used between the heat source

    and tubing.3. Do not support ixtures directly rom the tubing, such as hose bibs or

    shut-o valves.

    4. Protect the tubing via sleeves where it transitions through aconcrete slab, concrete wall, or other raming material.

    5. Not to be used with Insulated Barrier Heating PEX products.

    NOT FOR

    PO

    TA E USE

    Note: Heating PEX and Heating PEX-AL-PEX arenot approved or intended or use in potablewater applications.

    Note: Local building or plumbing codes may

    require modiications to the inormationprovided. You are required to consult the

    local building and plumbing codes prior

    to installation. I this inormation is not

    consistent with local building or plumbing

    codes, the local codes should be ollowed.

  • 7/28/2019 PEX-AL-PEX Installation Manual

    4/20

    4

    Standards and Listings

    Heating PEX:

    HeatingPEXismanufacturedtoASTMInternational(ASTMF876andF877)andtoSDR9dimensions.Thesestandardsinclude

    requirements and testing methods or materials, workmanship, dimensions, environmental stress cracking, sustained hydro-

    static pressure strength, bend strength, and degree o cross-linking. Heating PEX meets or

    exceeds these standards.

    HeatingPEXistestedandlistedbytheNSFInternationaltoNSF-14(rfh).

    HeatingPEXistestedandlistedbyIntertektoASTME84(StandardTestMethodforSurfaceBurningCharacteristicsofBuilding

    Materials) and meet the requirements o NFPA 90A.

    Heating PEX is tested and listed to UL 263 (Fire Tests o Building Construction and Materials) by Intertek.

    HeatingPEXislistedbytheInternationalCodeCouncilEvaluationService(ICC)toReport#ESR-1155,andPMG-1008which

    give compliance to IPC/IMC, and UPC/UMC.

    HeatingPEXiscertiedtoCSAStandardB137.5.

    Expansion Rate: 1.1"/100'/10F.

    Allow 1/8" slack or every oot o installed tubing.

    The bend radius for Heating PEX may require somebends to be light bulb in shape. This method

    allows for tighter on center spacing without

    compromising the tubing.

    Description ID (OD)

    Minimum

    Bend Radius

    Fluid Capacity

    gal/100'

    Min. Support

    Vertical

    Distance

    Min. Support

    Horizontal

    Distance

    1/2" Heating PEX 0.485" (5/8") 5" 0.92 48" 32"

    3/4" Heating PEX 0.681" (7/8") 7" 1.84 60" 32"

    1" Heating PEX 0.875" (1-1/8") 9" 3.04 60" 32"

    Temperature Pressure

    73.4F (23C) 160 psi (1.10 MPa)

    180F ( 82.2C) 100 psi (0.69 MPa)

    200F (93.3C) 80 psi (0.55 MPa)

    Heating PEX-AL-PEX:

    ManufacturedtoASTMF1281

    TestedandlistedbytheNSFInternational(NSF-14rfh).

    CarriestheUPCcerticationmark,asapprovedbytheInternationalAssociationofPlumbingandMechanicalOfcials(IAPMO).

    Expansion Rate: 0.156/100/10F.

    Note: No special considerations required to account for thermal expansion.

    The bend radius for Heating PEX-AL-PEX is slightly

    tighter than Heating PEX but may still require some

    bends to be light bulb in shape. It is important,

    however, to ensure the minimum bend radius is not

    exceeded, as this will cause the tubing to kink. This

    method allows for tighter on center spacing without

    compromising the tubing.

    Description ID (OD)

    Minimum

    Bend Radius

    Fluid Capacity

    gal/100'

    Min. Support

    Vertical

    Distance

    Min. Support

    Horizontal

    Distance

    1/2" Heating PEX-AL-PEX 0.500" (0.630") 3.2" 0.91 48" 32"

    3/4" Heating PEX-AL-PEX 0.806" (0.984") 5.5" 2.53 60" 32"1" Heating PEX-AL-PEX 1.032" (1.260") 6.5" 3.95 60" 32"

    Temperature Pressure

    73.4F (23C) 200 psi (1.38 MPa)

    180F ( 82.2C) 125 psi (0.86 MPa)

    200F (93.3C) 100 psi (0.69 MPa)

    R3"R4" R5"

    8"6" 10"

    R4" R4" R5"

    8"6" 10"

  • 7/28/2019 PEX-AL-PEX Installation Manual

    5/20

    5

    Slab-on-grade Applications

    A common application consisting o any material or mass that

    encapsulates the radiant tubing, such as concrete, sand, or soil.

    Can be on or below grade.

    Site Preparation

    A radiant slab should always:

    Be placed on well drained base rock material.

    Be placed above an ample amount o crushed rock or gravel.

    A radiant slab should never: Be placed directly on top o clay or organic subsoil.

    Be placed directly on top o solid bedrock.

    Insulation Requirements

    Two main areas to insulate:

    Vertically around the perimeter o the slab (required).

    Horizontally underneath the slab.

    Bothaidintheslabsresponseandefficiency.Ofthetwo,verticaledge

    insulation is the most important or preventing heat loss directly to the

    outside environment. Horizontal insulation helps decrease the slabs

    required start up time by isolating the slab rom the ground below.

    Type o Insulation

    Recommended insulation:

    Extruded polystyrene insulation board or equivalent.

    Not recommended:

    Beaded insulation boards.

    Foil-aced batt or board insulation.

    Bubble-type insulation.

    A 1" (25.4 mm) insulation board (R-5 or better) is recommended.

    Thicker board may be used in cold, aggressive climates. Always check

    with an architect or structural engineer to ensure the appropriate

    insulation is used.

    Watts does not recommend bubble-type insulation under a slab

    application. Most insulations o this type do not oer proper structuralsupport. Consult a structural engineer beore using this or

    similar product.

    Post Concrete Pour

    Ater the slab has been poured, interior walls and other support

    structures still have to be installed, typically secured directly to the slab.

    Take some preliminary precautions to protect the tubing

    during construction. Avoid wall locations, place tubing deeper in the

    areas to be below any anchor that will penetrate the slab.

    Control Joints and Saw Cuts

    Concrete slabs will expand and contract due to thermal changes. To

    prevent damage to the slab, expansion joints are used to control

    expansion and contraction due to thermal changes. In some cases,saw cuts are used to control where cracking occurs. Make sure the

    tubing is protected according to the requirements o the control joint.

    Slab-On-Grade Cross Section

    Slab

    Rewireor Rebar

    Heating PEX or

    HeatingPEX-AL-PEX

    Base Rock

    3

    Slab Insulation Detail

    Minimum 1" (25.4 mm)Extruded Polystyrene Insulation

    Slab:Minimum2"(50.8mm)covering above tubing

    Control Joint Options

    Heating PEX

    HeatingPEX-AL-PEX

    SubGrade

    Slab

    12" min.(304.8 mm)

    Rewireor Rebar

    ProtectiveSleeve Joint

    Pass Through

    Pass Under

    Heating PEX

    HeatingPEX-AL-PEX

    Slab

    Rewire

    or Rebar

    Joint

    SubGradeDo not exceedminimum bendradius o tubing

    3" min

  • 7/28/2019 PEX-AL-PEX Installation Manual

    6/20

    6

    12(304.8 mm)

    9(228.6 mm)

    6(152.4 mm)

    Tube Spacing

    Residential slabs will use 6" (152.4 mm), 9" (228.6 mm), or 12"

    (304.8 mm) tube spacing with some perimeter banding. Banding is

    any area where the tubing is installed with a tighter on center spacing.

    Usually seen along exterior walls with higher than normal heat loss.

    Spacingwiderthan12"(304.8 mm) may produce unacceptable foor

    temperature variations (striping). Tube spacing wider than 12" on

    center is not recommended.

    FastenersTubing can be attached to either the rewire, rebar or below slab

    insulation. The ollowing can be used, depending on

    installation requirements:

    Nylon CableTiesused to secure tubing to either rewire or rebar

    12"-18" (304.8 mm - 425.2 mm) on center.

    FoamBoardStaplescanbeusedtosecuretubingdirectlytothe

    horizontal board insulation below the slab.

    Slab Profle and General Details

    InSlab-on-Gradeapplications,aminimumof2"-3"(50.8mm-76.2

    mm) o concrete covering must be maintained above the tubing. More

    coverage may be necessary depending on the structural requirements

    o the slab.

    Installation Steps

    Maniold locations, inal concrete

    thickness and zoning details can

    aect how a concrete application

    is installed. The ollowing

    guidelines cover the most

    common installation conditions.

    I a given situation is not covered

    here, or i unexpected

    circumstances arise, please

    contact Watts or aheating proessional.

    1. Pre-Pour Conditions

    Veriy all subgrade conditions

    are properly prepared.

    Rewire or rebar are in place

    and installed according to

    design conditions.

    With orange spray paint, locate all interior walls and other obstacles

    to be avoided, such as toilet areas, sewer drains, and any structural

    supports that may penetrate the slab.

    2. Install ManioldsLocate where the maniolds are to be installed.

    Drive two pieces o rebar vertically into the ground. They may be

    removed ater the slab is poured and made ready or raming.

    Securethemanifoldswiththeuseofcabletiesorelectricaltape.

    Keepmanifoldshighenoughtoallowforthethicknessofthe

    concrete, the interior wall base plate and other structural items

    which may be installed ater the pour.

    Tube Spacing

    Insulation Layer and/orVapor Barrier

    CompactedSubgrade

    Typical Rewire Mesh

    Slab Subgrade Detail

    Manifold Pair

    TemporaryRebar

    Supports

    Slab - Maniold Installation Detail

  • 7/28/2019 PEX-AL-PEX Installation Manual

    7/20

    7

    3. Determine Zone Boundaries

    Beore tubing is installed, visually inspect the area to determine the

    zone boundaries. This helps determine where the irst circuit is to be

    placed, while identiying any obstacles.

    4. Confrm Tubing Requirements

    Measure the distance rom the

    maniolds to the arthest point in

    the zone via right angles.

    Make sure the minimum circuitlength is at least twice this distance.

    I not, the tubing will not be long

    enough to reach the arthest point

    o the zone and return.

    5. Install Tubing

    Pull one end o tubing o the

    unwinderandattachittotherst

    barb o one o the maniolds.

    Install using a single serpentine

    pattern, keeping the tubing 6"-8"

    (152.4 mm - 203.2 mm)

    rom the edge o the slab.

    Pay attention to the ootage marking

    on the tubing and cut at the

    correct length.

    At expansion/control joints, the

    tubing may be passed under the

    area or must be sleeved with

    Armafex or PVC to pass through

    expansion/control joints (see

    Expansion Joints or details).

    Use 1/2" (12.7 mm) tubing or the

    radiant foor.

    Use 3/4" (19.1 mm) or

    1" (25.4 mm) Heating PEX or

    Heating PEX-AL-PEX or supply

    and return lines to the zone.

    Supply Manifold

    Return Manifold

    Maniold

    Location

    ManioldLocation

  • 7/28/2019 PEX-AL-PEX Installation Manual

    8/20

    8

    6. Secure the Tubing

    SecureallbendsandcornerstopreventHeatingPEXfromcurling,

    creating an unwanted high point in the circuit.

    Leave 5' (1.52 m) slack on each circuit to allow adjustment o

    the maniold position rom its temporary location.

    Trim all tails o the cable ties to prevent any unwanted

    surace protrusions.

    Keepallcircuitswithin10%ofthesamelength.

    8. Inspection

    Visually inspect each circuit o tubing or possible damage caused

    during installation. I damage is ound, repair it using an approved

    Watts repair kit. Wrap the repair with electrical tape (do not use duct

    tape) to protect the connection rom the concrete.

    9. Pressure Test

    Pressure test the system with 50 - 100 psi (3.4 - 6.9 bar) water or air or

    24 hours. Do not use water i exterior temperatures are near or below

    reezing (32.0F (0.0C)) conditions.

    Attach the pressure test kit to the maniold pair making certain

    the rubber o-rings are properly seated beore threading the

    unions together. UsingtheSchraedervalveforairorthewaterllvalvesforliquid,

    llthesystem(airorwater,butnotboth).

    Closethevalveandll.Pressuretestthesystemwith50-100psi

    (3.4 - 6.9 bar) water or air or 24 hours.

    Note: I the exterior temperatures are near or below

    reezing (32.0F (0.0C )) use air to pressure test. I a

    luid must be used, use a 50-50 water/glycol

    solution. Failure to use glycol may result in rozen

    circuits. The cool night air will usually cause less

    than a 10 psi drop in pressure as the water or air

    contracts rom the cold.

    Do not test over 100 psi, (6.9 bar) as this will damagethe gauge on the test kit.

    Some minor pressure changes will occur due to

    the increased internal temperatures o the concrete

    as it begins the curing process. Fluctuations in air

    temperature may also cause a slight change in the

    test pressure. In most cases, a 10-15 psi (0.7 - 1.0

    bar) drop in pressure over a twenty our hour period

    is not uncommon.

    10. The Concrete Pour

    To help detect possible damage caused during the concrete pour, keep

    the system under pressure. I damage is apparent, locate the area inquestion and repair.

    Minor pressure changes will occur during the concrete curing process.

    Fluctuations in air temperature may cause slight changes in the test

    pressure. In most cases, a 10-15 psi (0.7 - 1.0 bar) drop in pressure

    over a 24 hour period is not uncommon.

    Heatedwatershouldnotbecirculatedthroughthenishedpourfora

    minimum o 28 days, or until the concrete slab is ully cured.

    Maniold Pressure Test Kit and Connection Detail

    Slab Loop Installation Detail

    Rewireor Rebar Heating PEX or

    HeatingPEX-AL-PEX

    Cable Tie

    Barb

    Compression Ring

    Compression Nut

    Heating PEX or

    Heating PEX-AL-PEX

    Balance Valve

    SupplyManifold

    Mounting Bracket

    AirTestGauge

    SchraderValve

    ReturnManiold

    Vent/Purge

    Drain

    Drain

    Slab-on-grade Cutaway

    Rewireor Rebar Heating PEX or

    Heating PEX-AL-PEX

    Slab

    Subgrade

  • 7/28/2019 PEX-AL-PEX Installation Manual

    9/20

    9

    Slab Layout Examples

    ManioldLocation

    ManioldLocation

  • 7/28/2019 PEX-AL-PEX Installation Manual

    10/20

    10

    Thin Slab over Frame Floor Applications

    Most thin slab applications are installed during the initial construction

    o a building, due to the increased structural requirements to carry the

    added weight.

    Lightweight concrete products will increase the foor height by a

    minimum o 1.5" (38.1 mm) and the foor load anywhere between

    12 to 18 lbs/sq.t (5.44 k to 8.16 k).

    Theincreaseinloadusuallymeansamodicationtothejoistsystem

    and/or other supports.

    Veriy a foors ability to withstand these loads prior to installing a

    lightweight concrete product.

    Tube Spacing

    Residential thin slabs will use 6" (152.4 mm), 9" (228.6 mm), or

    12" (304.8 mm) tube spacing with some perimeter banding. Banding

    is any area where the tubing is installed with a tighter on center

    spacing. Usually seen along exterior walls with higher than normal

    heat loss.

    Tubing is generally attached directly to the subfoor with the use o

    staples and/or NailTites.

    Fasteners

    The sub-material the thin slab is installed over will determine how

    the tubing can be attached. The most common sub-material is a

    wooden subfoor.

    Staplesspacedevery18"-24"(457.2mm-609.6mm)oncenter.Use a staple gun set to 100 psi.

    Thin slab Profle

    It is important to maintain at least 3/4" (19.1 mm) o thin slab material

    above the tubing.

    More coverage may be necessary depending on the structural

    requirements o the slab/structure.

    Installation Steps

    Manifoldlocations,nalconcretethickness,andzoningdetailsarejust

    a ew items that can aect how a thin slab application is installed. The

    ollowing guidelines cover the most common installation conditions. I

    a given situation is not covered here, or i unexpected circumstancesarise, please contact Watts or a heating proessional.

    1. Install Maniolds

    Locate where the maniolds are to be placed.

    With the use o Watts maniold brackets or maniold mounting

    enclosure, secure the maniolds to the wall.

    Allowances may need to be made to allow the tubing to transer

    through the wall base plate and into the thin slab.

    Follow local code guidelines when penetrating raming base plates.

    12" max(304.8 mm)

    Thin Slab Over Framed Cross Section

    Thin Slab Tube Spacing

    Thin Slab - Maniold Installation Detail

    ThinSlab

    SubFloor

    Heating PEX orHeatingPEX-AL-PEX

    Insulation

    Floor Covering

    Mimimum 1-1/2"

    (38.1mm)ThinSlab

    Insulation

    Maniold

    ThinSlab

    Heating PEX oHeatingPEX-AL-PEX

    Note: Local building or plumbing codes may require

    modiications to the inormation provided. You

    are required to consult the local building and

    plumbing codes prior to installation. I this

    inormation is not consistent with local building

    or plumbing codes, the local codes should

    be ollowed.

  • 7/28/2019 PEX-AL-PEX Installation Manual

    11/20

    11

    2. Determine Zone Boundaries

    Beore tubing is installed, visually inspect the area to determine the

    zoneboundaries.Thishelpsdeterminewheretherstcircuitistobe

    placed, while identiying any obstacles.

    3. Confrm Tubing Requirements

    Measure the distance rom the

    maniolds to the arthest point in

    the zone.

    Make sure the minimum circuit lengthis at least twice this distance. I not, the

    tubing will not be long enough to reach

    the arthest point and still have enough

    length to return to the maniold.

    4. Install Tubing

    Pull one end o tubing o the unwinder

    andattachittotherstbarbonthe

    supply maniold.

    Lay the tubing along the perimeter

    walls to the arthest point in the zone,

    keeping the tubing 6"-8" (152.4 mm -

    203.2 mm) rom the edge o the slab.This will help protect the tubing rom

    possible penetrations later on when the

    nalfloorcoveringisinstalled.

    Pay attention to the ootage marking on

    the tubing and cut at the correct length.

    Bend supports may be used to secure

    the tubing as it transitions rom the thin

    slab to the wall.

    In most thin slab applications, built-ins

    such as cabinets, showers, and walls

    are already in place beore the thin slab

    is poured. Tubing is generally run around

    these built-ins.

    Most structural code requirements

    restrict the amount o material that

    can be removed rom a wall member.

    It is advised to run the tubing through

    doorways, or other openings,

    whenever possible.

    Supply Manifold

    Return Manifold

    Thin Slab20 8 (6 3 m)

    16 8(5 1 m)

    Supply Manifold

    Return Manifold

    Thin Slab

    ManioldLocation

  • 7/28/2019 PEX-AL-PEX Installation Manual

    12/20

    12

    5. Securing Tubing

    When installing a thin slab over a subfoor, standard staples are used.

    Make sure the staple gun is set to 100 psi (6.9 bar) and does not

    comeincontactwiththetubing.Securethetubingtothefloorevery

    18"-24" (457.2 mm - 609.6 mm).

    Trytokeepallcircuitswithin10%ofthesamelength.

    6. Inspection

    Visually inspect each circuit o tubing or possible damage caused

    during installation. I damage is ound, repair it using an approvedWatts repair kit. Wrap the repair with electrical tape (do not use duct

    tape) to protect the connection rom the concrete.

    7. Pressure Test

    Pressure test the system with 50-100 psi (3.4 - 6.9 bar) water or air or

    24 hours. Do not use water i exterior temperatures are near or below

    reezing (32.0F (0.0C)) conditions.

    Attach the pressure test kit to the maniold pair making certain

    the rubber o-rings are properly seated beore threading the

    unions together.

    UsingtheSchraedervalveforairorthewaterllvalvesforliquid,llthesystem(airorwater,butnotboth).

    Closethevalveandll.Pressuretestthesystemwith50 - 100 psi

    (3.4 - 6.9 bar) water or air or 24 hours.

    Note: I the exterior temperatures are near or below

    reezing (32.0F (0.0C)) use air to pressure test. I

    a luid must be used, use a 50-50 water/glycol

    solution. Failure to use glycol may result in rozen

    circuits. The cool night air will usually cause less

    than a 10 psi drop in pressure as the water or air

    contracts rom the cold.

    Do not test over 100 psi, (6.9 bat) as this will damage

    the gauge on the test kit.

    Some minor pressure changes will occur due to

    the increased internal temperatures o the concrete

    as it begins the curing process. Fluctuations in air

    temperature may also cause a slight change in the

    test pressure. In most cases, a 10-15 psi (0.7 - 1.0

    bar) drop in pressure over a twenty our hour period

    is not uncommon.

    8. The Thin Slab Pour

    To help detect possible damage caused during the concrete pour, keep

    the system under pressure. I damage is apparent, locate the area in

    question and repair. Minor pressure changes will occur during the concrete curing process.

    Fluctuations in air temperature may cause slight changes in the test

    pressure. In most cases, a 10-15 lb (0.7 - 1.0 bar) drop in pressure

    over a twenty our hour period is not uncommon.

    Heatedwatershouldnotbecirculatedthroughthenishedpourfora

    minimum o 28 days, or until the concrete slab is ully cured.

    Thin Slab Loop Installation Detail

    ThinSlab

    Heating PEX orHeating PEX-AL-PEX

    Staple18" to 24"

    Maniold Pressure Test Kit and Connection Detail

    Barb

    Compression Ring

    Compression Nut

    Heating PEX or

    Heating PEX-AL-PEX

    Balance Valve

    SupplyManifold

    Mounting BracketAirTestGauge

    SchraderValve

    ReturnManiold

    Vent/Purge

    Drain

    Drain

    Thin Slab Cutaway

    ThinSlab

    Heating PEX or

    Heating PEX-AL-PEX

    Finished Floor

    Subfloor

  • 7/28/2019 PEX-AL-PEX Installation Manual

    13/20

    13

    Insulation Requirements

    A standard paper aced insulation can be used in the joist cavity.

    Install the insulation tight against the subfoor to minimize any

    convective losses that may be generated.

    The insulation should be a minimum o 3-1/2" (88.9 mm), or R-13,

    berglassbattwhentheradiantfloorisinstalledoveraheatedspace,

    such as a basement. 5-1/2"(139.7 mm), or R-19, batt (or thicker,

    depending on the climate) should be used when the area below the

    radiant foor is unheated or exposed to the elements.

    Thin Slab with Sleepers

    Wooden sleepers are sometimes installed within a thin slab

    application to allow or points o attachment or hardwood or other

    foor coverings.

    Please note:In a thin slab application,typically the tubing will berun through doorways andother openings rather than

    directly through walls.

    Thin Slab Insulation Detail

    Thin Slab Layout Example

    12" max(304.8 mm) ThinSlab

    Insulation

    SHOWERSPA TUB

    LINEN

    STORAGE

    WALK-IN

    CLOSET

    GASFIREP

    LACE

    MASTER

    BATH

    MASTER SUITE

    Thin Slab with Sleepers Insulation Detail

    8"(203.2 mm) ThinSlab

    Insulation

    Heating PEX or

    Heating PEX-AL-PEX

    ManioldLocation

    Heating PEX or

    Heating PEX-AL-PEX

    WoodenSleeper

  • 7/28/2019 PEX-AL-PEX Installation Manual

    14/20

    14

    Under Floor Applications

    Minimizes the structural load requirements oten associated with lightweight concrete (thin slab) construction.

    Requires no foor height additions, or removal o existing foor

    coverings to install. Ideal or renovation projects.

    Make sure the tubing is installed in accordance with the design

    parameters. I not, the system may not unction as desired.

    Requires the use o either a 1" (25.4 mm) or a 1-3/4" (44.4 mm)

    auger drill to install between joist bays, depending on how tubing

    is installed.

    Tube Spacing

    Tubing is installed 8" (203.2 mm) on center, to the underside o the

    subfoor with the use o heat transer plates.

    Method o InstallationExtruded aluminum heat transer plates are the primary astening

    method o installing an under loor system. Watts oers heat transer

    plates designed to be used with 1/2" (12.7 mm) Heating PEX or

    Heating PEX-AL-PEX and are available in 4' (1.2 m) lengths. The plates

    are installed 8" (203.2 mm) on center with a 2"-4" (50.8 mm - 101.6

    mm) gap between plates.

    Bend Supports

    Bend supports may be required i it is necessary to maintain a

    certainbendradius,orifconnectingtoattingimmediatelyafter

    a bend.

    Pulling Tubing

    Install the heat transer plates beore beginning to pull the tubing.Make sure the end o the plate is de-burred ater cutting the plate

    totbeforeinstallingthetubing.

    Measure the distance rom the maniold to the arthest point moving

    in right angles to ensure proper circuit length is being used. This

    distance should be less than the circuit length or the zone.

    Installation Steps

    1. Install maniolds.

    Locate where the maniolds are to be placed.

    With the use o Watts maniold brackets or maniold mounting

    enclosure, secure the maniolds to the wall.

    2. Determine Zone Boundaries

    Beore tubing is installed, visually inspect the area to determine thezoneboundaries.Thishelpsdeterminewheretherstcircuitistobe

    placed, while identiying any obstacles.

    3. Confrm Tubing Requirements

    Measure the distance rom the maniolds to the arthest point in the

    zone. Make sure the minimum circuit length is at least twice this dis-

    tance. I not, the tubing will not be long enough to reach the arthest

    point o the zone and return (see slab section or illustration)

    Return Manfold

    Supply Manifold

    Under Floor Application Cross Section

    Confrm Tubing Requirements

    Under Floor Tube Spacing

    8"

    2 (50.8 mm) air gap

    (203.2 mm)

    Heating PEX orHeatingPEX-AL-PEX Heat Transer Plate

    Foil Faced Insulation

    anser

    Heating PEX orHeatingPEX-AL-PEX

    Foil Faced Insulation

    SubFloor

    Note: Local building or plumbing codes may require

    modiications to the inormation provided. You

    are required to consult the local building and

    plumbing codes prior to installation. I this

    inormation is not consistent with local building

    or plumbing codes, the local codes should

    be ollowed.

  • 7/28/2019 PEX-AL-PEX Installation Manual

    15/20

    15

    4. Drill joists (i necessary)

    Drill in accordance to structural requirements. To help keep the holes

    inline,itmaybehelpfultorstmarkthejoistswithachalkline.

    I the supply and return sections o the circuit are to be installed

    through a common joist transition point, a 1-3/4" (44.4 mm) hole is

    required (option 1). I the supply and return sections are to be run in

    dedicated transition points, 1" (25.4 mm) holes can be used (option 2).

    I using TJI joists, it may be possible to use the pre-abricated

    knock-outs instead o having to drill transition points. Make sure

    the knock-outs are large enough or the tubing beore proceeding.

    Frame Floor Section - Maniold Installation

    Under Floor Joist Penetration Detail

    1-3/4"(44.4 mm)

    Option 1

    Option 2

    Under Floor - Maniold Installation Detail

    Whencrossingajoistataperpendicularangle,itisrecommendedtofollowBOCA2305.3.2 guidelines or allowable joist penetrations.

    Penetrations can not be closer

    than 2" (50.8 mm) to the top

    or bottom o the joist.

    2" (50.8 mm) minimum

    spacing between penetrations.

    center linepenetration zone joist heightmax. bore size: 1/3 joist height

    Stayamin.of8"

    (203.2 mm) rom

    end o joist.

    BOCA Joist Penetration Guideline

  • 7/28/2019 PEX-AL-PEX Installation Manual

    16/20

    16

    5. Install Tubing

    Pull one end o the tubing rom the unwinder and eed through the

    rstjoist.

    Create a large loop with the tube and eed the ree end through the

    adjacent joist.

    Make a small loop in each bay as you work towards the bay arthest

    fromthemanifold.Pullenoughtubingtollthelastbay.Ifadditional

    tubing is required, pull it rom the loop in the previous bay. I too much

    was pulled, push it back into the previous bay. Care should be taken

    not to kink the tubing.

    Run the end o the tubing back to the maniold. Drill a return hole 8"

    (203.2mm)awayfromtherst.

    Place the tubing into the asteners. Begin by attaching the run o

    tubing that is part o the return line going back to the maniold. This

    sideoftheloopisxed.Theothersideisfreetofeedfromthe

    unwinder and previous bays in case extra tubing is required.

    Always remember to place the tubing so bends have the largest

    radius possible.

    Inspection

    Ater all the circuits are installed, take a ew minutes to walk each

    circuit and visually inspect the tubing or possible damage caused

    during installation. I damage is ound, repair it using an approved

    Watts repair kit.

    Pressure Test

    Pressure test the system with 50-100 psi (3.4 - 6.9 bar) water or air or

    24 hours. Do not use water i exterior temperatures are near or below

    reezing (32.0F (0.0C)) conditions.

    Attach the pressure test kit to the maniold pair making certain

    the rubber o-rings are properly seated beore threading the

    unions together.

    UsingtheSchraedervalveforairorthewaterllvalvesforliquid,

    llthesystem(airorwater,butnotboth).

    Closethevalveandll.Pressuretestthesystemwith50-100psi

    (3.4 - 6.9 bar) water or air or 24 hours.

    Note: I the exterior temperatures are near or below

    reezing (32.0F (0.0C)) use air to pressure test.

    I a luid must be used, use a 50-50 water/glycol

    solution. Failure to use glycol may result in rozen

    circuits. The cool night air will usually cause less

    than a 10 psi drop in pressure as the water or air

    contracts rom the cold.

    Do not test over 100 psi (6.9 bar), as this will damage

    the gauge on the test kit.

    Some minor pressure changes will occur due to

    the increased internal temperatures o the concrete

    as it begins the curing process. Fluctuations in air

    temperature may also cause a slight change in the

    test pressure. In most cases, a 10-15 psi (0.7 - 1.0

    bar) drop in pressure over a twenty our hour period

    is not uncommon.

    Maniold Pressure Test Kit and Connection Detail

    Barb

    Compression Ring

    Compression Nut

    Heating PEX or

    Heating PEX-AL-PEX

    Balance Valve

    SupplyManifold

    Mounting Bracket

    AirTestGauge

    SchraderValve

    ReturnManiold

    Vent/Purge

    Drain

    Drain

    1. Pull a loop o tubing in the

    rstjoistbay.

    2. Continue to the next bay,

    pulling rom the previous

    loop. Tubing will need to be

    pulled rom the unwinder

    as well to keep enough o

    aloopintherstbay.

    3. Repeat or each

    subsequent bay

    4. Pull enough tubing to complete the last

    bay using the loop in the previous bay as a

    buer or extra tubing.

  • 7/28/2019 PEX-AL-PEX Installation Manual

    17/20

    17

    2 (50.8 mm)

    Return Manifold

    Supply Manifold

    Under Floor Layout Example

    Heating PEX or

    Heating PEX-AL-PEXHeat Transer Plate

    Foil Faced Insulation

    Insulation Requirements

    It is important to have a tight seal between the horizontal insulation

    and the joist itsel. The tighter the joist cavity, the better the system

    will perorm.

    Foil insulation will ensure most o the heat and energy coming rom

    the tubing is refected upward towards the subfoor where it is evenly

    distributed..

    A 2-4" (50.8 -101.6 mm) air gap is necessary between the tubing and

    insulation. This air gap helps increase the eective R-value o the in-

    sulation while optimizing the ability o the oil to refect energy.

    An R-value o at least 4 times higher than the foor is desire. For most

    interior conditions, an R-13, or a 3-1/2" (88.9 mm) batt should be used.

    When installing over an unheated area, exposed area or crawlspace, a

    minimum R-19 or 6" (152.4 mm) batt should be used.

  • 7/28/2019 PEX-AL-PEX Installation Manual

    18/20

    18

    HEATING PEX and Heating PEX-AL-PEXHEATING, COOLING, and

    SNOW MELTING LIMITED WARRANTY

    From Watts

    1. Watts warrants its Heating PEX cross-linked polyethylene tubing, Heating PEX-AL-PEX cross-linked polyethylene/

    aluminum/cross linked polyethylene tubing, fittings, and factory manufactured manifolds to be free of defects in materialand workmanship when used in hydronic heating, cooling, and snow melting systems. This limited warranty for tubing

    is valid for a period of twenty-five years from the date of manufacture. This limited warranty for Watts manufactured

    manifolds and fittings expires two years from the date of manufacture. All other Heating PEX and Heating PEX-AL-PEX

    accessories are warranted for one year after date of installation.

    2. Watts obligation will be to repair or replace, at its discretion, any material proven to be defective when such material is cov-

    ered under the following limited warranty.

    3. In order to qualify for a labor allowance to repair or replace defective materials, you must contact Watts in advance

    and receive a written authorization for this allowance. Labor and freight expenses not authorized in writing in

    advance by Watts will not be compensated.

    4. In the event of a system malfunction or leak caused by defective materials (and not by incorrect installation procedures

    or damage from handling procedures/jobsite conditions) repair materials and a reasonable labor allowance will be allowed.

    In the event of a leak occurring in a factory manifold, you may contact Watts for a free replacement manifold or any needed

    parts (freight prepaid). In the case of field-assembled manifolds, Watts warrants the quality and serviceability of theindividual components sold by Watts that the contractor incorporates in that manifold, but Watts cannot warrant the

    complete manifold assembly or any field-assembled connections. That is the responsibility of the installing contractor.

    5. To qualify for the above warranty you must do the following:

    a. Use good construction techniques to install our materials, as specified in our current design and installation guidelines

    and technical notes. This must include field pressure testing our materials before they are covered by concrete or

    otherwise made inaccessible.

    b. Install our materials according to all specific instructions furnished for your installation.

    c. Install Heating PEX or Heating PEX-AL-PEX in a system that will not operate at temperatures exceeding ratings as

    marked on the tubing.

    d. Product must be installed in compliance with all applicable plumbing, heating, cooling, and/or mechanical codes.

    6. Evidence of tampering, mishandling, neglect, accidental damage, freeze damage, or unauthorized repairs that cause damage

    to Watts products will void any warranty coverage for these particular damages, although it will not void warranty coverage

    for unrelated items. Field repair joints and tubing-to-manifold connections are specifically excluded from the terms of

    this warranty.

    7. Watts provides a complete radiant system offering so that it is possible to complete an installation with Watts products.

    However, it is possible that other manufacturers tubing and/or fittings may be installed in any given installation. Providing

    that the tubing and/or fittings are manufactured to the applicable ASTM standards, and have been certified by a recognized

    third-party testing agency, the Watts product in the given installation will continue to be covered under this warranty. In

    the event of a system malfunction or leak that has other tubing and/or fitting manufacturers components installed within

    the failed system, Watts will be responsible only for Watts products. Products manufactured by another company should be

    reported to that manufacturer for their warranty response.

    WATTS DISCLAIMS ANY WARRANTY NOT PROVIDED HEREIN, INCLUDING ANY IMPLIED WARRANTY OF

    MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. WATTS FURTHER DISCLAIMS ANY RESPONSIBILITY

    FOR SPECIAL, INDIRECT, SECONDARY, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING FROM OWNERSHIP OR

    USE OF THIS PRODUCT, INCLUDING INCONVENIENCE OR LOSS OF USE OR THE COST OF REPLACING OR REPAIRING

    OTHER PROPERTY WHICH IS DAMAGED IF THIS PRODUCT DOES NOT WORK PROPERLY. THERE ARE NO WARRANTIES

    WHICH EXTEND BEYOND THE FACE OF THIS DOCUMENT. NO AGENT OR REPRESENTATIVE OF Watts HAS ANY

    AUTHORITY TO EXTEND OR MODIFY THIS WARRANTY UNLESS SUCH EXTENSION OR MODIFICATION IS MADE IN

    WRITING BY A CORPORATE OFFICER.

    8. Some states do not allow the exclusion or limitation of incidental or consequential damages and some states do not allow

    limitations on how long implied warranties may last. Therefore, the above limitations or exclusions may not apply to you.

    This warranty gives you specific legal rights and you may also have other rights which vary from state to state.

    Effective: July 1, 2011

    This warranty applies to all products purchased after this date.

    Watts Regulator Company 815 Chestnut St. No. Andover, MA 01845

    855-699-2887 (USA and Canada) 978-794-1848 (Fax) radiant.watts.com

  • 7/28/2019 PEX-AL-PEX Installation Manual

    19/20

    19

  • 7/28/2019 PEX-AL-PEX Installation Manual

    20/20

    815ChestnutSt

    No. Andover, MA 01845

    ph: 855.699.2887

    ax: 978.794.1848

    radiant.watts.com

    In Canada5435NorthServiceRoad

    Burlington,ONL7L-5H7

    ph: 888.208.8927

    905.332.4090

    ax: 888.882.1979

    905.332.7068

    radiant.watts.com

    Materials and Tools Checklist

    Measuring Tape

    Chalk Line

    Electrical Tape

    Marker

    Electric Drill

    1-3/4"(44.5mm)HoleSaw

    SafetyGlasses

    Tubing Unwinder

    Tubing Cutter

    BendSupports(forHeatingPEXinstallationonly)

    Maniold Box (optional)

    Heating PEX or Heating PEX-AL-PEX tubing

    WattsCopperCompressionManifoldKit(withcorrectnumberofcircuitconnectionsfortubingtypeinstalled)

    Heating PEX-AL-PEX Reamer (i installing Heating PEX-AL-PEX tubing)

    Railways (or slab-on-grade installations)

    FoamBoardStapler(forinsulatedslab-on-gradeinstallationsonly)

    FoamBoardStaples(forinsulatedslab-on-gradeinstallationsonly)

    FoamBoardScrewClipTool(forinsulatedslab-on-gradeinstallationsonly)

    FoamBoardScrewClips(forinsulatedslab-on-gradeinstallationsonly)

    Cable Ties (or slab-on-grade installations)

    Heat Transer Plates (or under loor installations only)

    Under Floor Clips (or under loor suspended installations only)

    WattsPressureTestKit

    NOTFOR

    PO

    TABL E USE