Genset
Citation preview
Prime Model:P200PBStandby Model:P220EB
Rating Range1500RPM 50Hz
Standby:
Prime:
176220160200
RATINGS: All three-phase units are rated at 0.8 power factor. Standby ratings : Standbyratings apply to installations served by a reliable utility source. The standby rating is for this rating. Ratings are in according with ISO-3046/1,BS 5514 ,AS 2789 , and DIN 6271.Prime Power Ratings: Prime power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with IS0-8528/1, overload capacity in accordance with ISO-3046/1,BS 5514,AS 2789, and DIN 6271. For limited running time and base load ratings, consult the factory. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. GENERAL GUIDELINES FOR DERATION: Altitude: Derate 2.0% per 300m(984 ft.) elevation above 1000m(3279 ft.) up to a maximum elevation of 2450m(8000 ft.).More than2 4 5 0 m ( 8 0 0 0 f t ) , p l e a s e c o n t a c t s w i t h u s o r o u r d e a l e r s e e k t h e h e l p . Temperature: Derate 6.0% per 11 (20 ) temperature above 40 (104 ).
kW
kWkVA
kVA
1
Voltage series starVoltage parallel star
Voltage series delta
Rating capacity(kVA)Rating power(kW)
Power efficiency(%)Input power(kW)
Alternator Model
Frequency and Speed
Class-TEMP Rise( )Prime Power Data
Standby Power Data
Voltage series starVoltage parallel star
Voltage series delta
Rating capacity(kVA)Rating power(kW)
Power efficiency(%)Input power(kW)
Class-TEMP Rise( )
200 200 200 N/A
160 160 160 N/A
171.5 171.3 N/A
93.3 93.4 N/A
220 220 220 N/A
176 176 176 N/A
189.2 188.8 N/A93.0 93.2 N/A
UCI274H(STAMFORD)
Cont.H -125/40
50Hz 1500rpm
220 230 240 254
190 200 208 220
380 400 415 440
Standby.H -163/27
220 230 240 254
190 200 208 220
380 400 415 440
172.0
93.0
189.9
92.7
200 200 200 N/A
160 160 160 N/A
171.5 171.3 N/A
93.3 93.4 N/A
220 220 220 N/A
176 176 176 N/A
189.2 188.8 N/A93.0 93.2 N/A
SPG341H(SPARKS)
Cont.H -125/40
50Hz 1500rpm
220 230 240 254
190 200 208 220
380 400 415 440
Standby.H -163/27
220 230 240 254
190 200 208 220
380 400 415 440
172.0
93.0
189.9
92.7
ISO 9001:2000110-480V 3P4W
SWT DIESEL GENERATOR SET
DIESEL GENERATOR SETStandard Features and Characteristics
All equipment is guaranteed for the period of 1000 hours or 12mouths from the date of commissioning or 18 months fromshipping, whichever occurs first.
Controllers are available for all applications. The controllersystem is used to start and stop the engine, indicateelectric date and protect the generator set. See controllerfeatures inside.
Convenience for operation and maintenance, backed by PERKINS, NEWAGE and LEROY SOMER global servicenetwork.
WARRANTY
The engine and alternator are close coupled by means of anSAE flange. A full torsional analysis has been carried out toguarantee no harmful vibration will occur.
QUALITY STANDARDSThe SUPERWATT generator set compliance with all mainstandards, such as ISO8528 (GB/T2820-97), GB755,BS5000, VDE0530, ISO3046, IEC34-1, CSA22-2, AS1359,ISO14001.
SUPERWATT Company provides one-source responsibility for the generator set and accessories.
Other standards and certifications can be considered on request.
Diesel engine and alternator OEM authorization certificateand their quality assurance.
ASSEMBLY
Anti-vibration pads are affixed between engine alternator feet and the baseframe. Thus ensuring complete vibration isolation of the rotating assemblies and enabling the machine to beplaced on an uneven surface without any detrimental effects.For durability and corrosion resistance, all iron and steel surfaces of canopy fabrications have been treated for coatingby grit blast cleaning. Then covered by a polyester powderpaint which provides an excellent corrosion resistant surface.
CONTROL SYSTEM AND PROTECTION
Each SUPERWATT generating set has been got through 2 hoursload test for running 0%,25%,50%,75%,100% and 110% load, all protective devices and control function are stimulated andchecked before dispatch.
The revolving parts are covered by safety net, and the placewhich easy to scald and got an electric shock all to have theobvious warning slogan.
The picture only for reference.
ALTERNATOR RATINGS
In line with our policy of continuous product development, we reserve the right tochange the specification without notice.
Engine Electrical System 1500RPM 50HzBattery charging alternator:
Ground(negative/positive) Volts(DC) Ampere rating 85A
Starter motor rated voltage(DC) Starter motor rated Capability Battery voltage
Fuel System 1500RPM 50Hz
Engine Electrical
Fuel
Type of injection System Fuel feed pump
Application DataEngine Specifications
ExhaustExhaust System
Fuel lift pump 1500RPM 50Hz
Pressure Maximum fuel pump suctionGovernor type
Lubrication System 1500RPM 50HzLubrication
Total lubrication capacity 16.5 litres
Maximum back pressure
Manufacturer
Cylinder arrangement Cycle Induction system
Compression ratio Bore
Cubic capacity 7.01 litresDirection of rotation Firing order
Estimated total weight(dry) 788kg
Exhaust gas flow (max) 36.6 m3/min
Number of cylinders
Stroke
Frequency regulation steady state 0.5%
Max. Power at rated rpm
Exhaust gas temperature (max) 580
Mean piston speed 6.75m/s
Fuel Consumption 1500RPM 50Hz
1106A-70TAG4 diesel engines are manufactured by PerkinsEngines Company Limited(UK).
191.3kW 1, 5, 3, 6, 2, 4
Anti-clockwise viewed on flywheel
135mm 105 mm
Turbocharged,Air to air charged cooled
4 stroke, compression ignition Vertical in-line
6 PERKINS
Electronic governor
DP210G Direct
12V 4KW12V
12V Negative
137.9 kPa10kPa
16:1
10.0 kPa
1500RPM 50Hz
1500RPM 50Hz
Fuel lift pump flow 180 litres/hr
45.0 litre/hr Standby powerPrime PowerAt 75% of Prime Power 34.7 litre/hr
46.3 litre/hr
At 50% of Prime Power 24.0 litre/hr
2
Fuel lift pump suction depression 17 kPa
ALTERNATOR
SpecificationType
Insulation
Voltage regulator(AS440)Exciter type
Protection Rated power factorStator windingWinding pitchWinding leadsMaximum overspeedSustained short circuit
Waveform distortion
Voltage regulation
Altitude
4-Pole, Rotating FieldBrushless, Self excited Solid State, Volts/Hz
1.5%Class HIP230.8Double layer concentricTwo thirds
122250 Rev/minSelf excited machines do notsustain a short circuit current
Non-distorting balancedlinear load < 5.0%
No load < 1.5%
1000 m
1500RPM 50HZ Alternators meet the requirement of BS EN 60034 and therelevant section of other international standards such asBS5000, VDE 0530, NEMA MG1-32, IEC34, CSAC22.2-100, As1359, and other standards and certifications can beconsidered on request.The 2/3 pitch design avoids excessive neutral currents. Withthe 2/3 pitch and carefully selected pole and tooth designs, ensures very low waveform distortion.Brushless alternator with brushless pilot exciter for excellentload response.The insulation system is class H, easy paralleling with mainsor other generators, standard 2/3 pitch stator windings avoid excessive neutral currents.Backed by worldwide service network.
DIESEL ENGINE
Application DataCooling System
Face area Pressure cap setting
Total system capacity
Drain down capacity
Minimum temperature to engineTemperature rise across engine Max permissible external system resistance Thermostat operation range
Coolant System 0.60 m2
68.9 kPa (9.90 lb/in2 )
82 - 95
5 79 (175 )
1.3 litres ( 2.3 UK pints) 21 litreswith radiator
35 kPa ( lbf/ )in 25.1
1500RPM 50Hz
Maximum top tank temperature 103 (218 )
Cooling fan air flow 375 m /min3
NOTE:All data is based on:1. All data based on operation to BSAU141A 1971; BS5514; ISO3046/1 1982; DIN6271.2. Engine operating with fuel corresponding to grade No. 2-D per ASTM D975.3. ISO 3046, Part 1, Standard Reference Conditions of: Barometric Pressure : 101.3 kPa (29.53 in Hg) Air Temperature : 25 (77 ) Altitude : 110 m (361 ft) Relative Humidity : 30% Air Intake Restriction : 254 mm H2O (10 in H2O) Exhaust Restriction : 51 mm Hg (2 in Hg)
TBA: To Be Determined
3
CONTROLLERS
The Model 702 is an Auto Start Engine Control Module designed tocontrol the engine via a remote input signal or a key switch.The module is used to start and stop the engine and indicate fault conditions, automatically shutting down the engine and indicating the engine failure by LED, giving true, first up fault annunciation.
Protection: Low Oil Pressure High Engine Temperature Auxiliary Shutdown Over speed
DC Supply: 8 to 35 V Continuous.
DSE 702 AS CONTROLLER(Standard)
The voltage selector and the current selector uses for tochoose the different phase voltage and current to display.
Panel introduction:Indicator type frequency, voltmeter and ampere meterto display unit's electrical parameter.
The big red button uses for the operator to stop the gensetemergently.
The controller. And an integral anti-tamper LCD hours run
counter is also provided.If the customer needs to use the preheating function, we will beable to increase the preheating button.
The oil pressure gauge, coolant temperature gauge and the battery voltage gauge.
Control panel for open
The controller made in UKThe controller made in UK
DEEPSEA genset controllerDEEPSEA genset controller
The DSE704 is an Automatic Mains Failure module with generatormonitoring, protection and start facilities. It utilises advanced surface mount construction techniques to provide a compact yet highly specified module. This model can start the generator automatically whenthe MAINS failure and then control the ATS turn to the genset side.Operation of the module is via three pushbuttons mounted on the front panel with STOP, MANUAL and AUTO positions.
DC Supply: 8 to 35V Continuous.
Protection: Over Speed Shutdown.
Optional Under speed Protection.
Low Oil Pressure Shutdown. High Engine Temp Shutdown. Charger failure alarm. Mains failure alarm.
The voltage selector and the current selector uses for tochoose the different phase voltage and current to display.
Panel introduction:Indicator type frequency, voltmeter and ampere meterto display unit's electrical parameter.
The controller.
DSE 704 AMF CONTROLLER(Optional)
Preheating button.
The oil pressure gauge, coolant temperature gauge and thebattery voltage gauge.
Control panel for soundproof
The controller made in UKThe controller made in UK
DEEPSEA genset controllerDEEPSEA genset controller
Panel introduction:Indicator or digital type frequency, voltmeter and ampere meterto display unit's electrical parameter.
COMAP AMF25NT CONTROLLER(Optional)
The controller.
The AMF25NT is an Automatic Mains Failure module with generator monitoring, protection and start facilities. The controller has a largeLCD screen, display the generator's each parameter, running andalarm information. The off/replacement button, mode switch button,start/stop button and the LED indicator light, makes the user easy tooperate and maintain the generator.
The big red button uses for the operator to stop the gensetemergently.
Function:Communication: RS232 connection, uses the industry rank MODBUS protocol can easily communicate with othersintelligence control system.Display function: LCD screen can display the generator'sparameter and the control system's running information.Set up parameter: Engineer can set up the controller parameterfrom the control panel or through the PC, 6 programmable fan-out may satisfy the user each kind of demand.Protection: The control system can protect the generator set ,manage each kind of electrical failure.
DC Supply: 8 to 35 V Continuous.Control Function of ATS.
Control panel for soundproof
The controller made in CzechThe controller made in Czech
Comap genset controllerComap genset controller
wH
L
Dimensions and WeightsOpen StyleOverall Size, L W H mm 2645 730 1630Weight(radiator model),net,Kg 1680
Soundproof StyleOverall Size, L W H mm 3430 1110 2060Weight(radiator model),net,Kg 2530
4
Standard Features and Optional AccessoriesStandard Features
Battery, Battery Rack and Battery CablesIntegral Vibration IsolationOil Drain Extension
Accessories
Block Heater(recommended for ambient temperatures below 0 )
Cooling System
Enclosed UnitSound Enclosure
Weather Enclosure (with enclosed critical silencer)
Radiator Duct Flange
Remote Radiator Cooling
Fuel SystemAuxiliary Fuel PumpFlexible Fuel Lines
Base Fuel Tank with Day Tank
Fuel fill cap with breather
10 hours running tank
Mechanical dipstick or fuel level sensor
Electrical SystemBattery Charger, Equalize/Float Type
Engine and Alternator
Air cleaner, Heavy Duty
Heavy duty industrial type exhaust silencerwith flexible pipe(supplied loose).
Oil Preheater
Anti-Condensation Heater
3 Pole Circuit Breaker
Fuel/Water Separator
Air Preheater
Open UnitExhaust Silencer, Critical KitFlexible Exhaust Connector, Stainless Steel
Automatic fuel--providing device
Maintenance and LiteratureGeneral Maintenance Literature Kit
Overhaul Literature Kit
Test Certificate and design paperQuality certificate and Maintenance card
Hand primer pump
Maintenance and Literature
Weather Housing (with roof-mounted critical silencer)Trailer(Causes the genset easily to move)
3 or 4 Pole Circuit Breaker with Shunt Trip
Maintenance Kit (includes air, oil, and fuel filters)
Paralleling SystemReactive Droop CompensatorVoltage Adjust ControlVoltage Regulator Relocation Kit
Controller SystemCommon Failure Relay KitCustomer Connection Kit(Except Open Style)Communications Products and PC SoftwareEngine Pre-alarm Sender KitRemote Annunciator Panel
Remote Audiovisual Alarm PanelRemote Emergency Stop Kit
Miscellaneous Accessories
PCRC series control system, with RS232 or RS485 communication connection and communication agreement.
NOTE: This drawing is provided for reference only and should not be used for planninginstallation. Contact your local distributor for more detailed information.