4
Performance Performance New requireme nts for circuit integrity : enhanced cables BS 5839-1 : 2002 Fire Detection and Fire Alarm Systems for Buildings Part 1: code of practice for system design, installation, commissioning and maintenance Par. 26 Cable, wiring and other interconnections Recommendation for two level of fire resistance: Standard for general use Enhanced when cables might need to operate correctly during a fire for periods in excess of those normally required for single phase evacuation of building under fire under fire condition condition

Performance New requirement s for circuit integrity: enhanced cables BS 5839-1 : 2002 Fire Detection and Fire Alarm Systems for Buildings Part 1: code

Embed Size (px)

Citation preview

Page 1: Performance New requirement s for circuit integrity: enhanced cables BS 5839-1 : 2002 Fire Detection and Fire Alarm Systems for Buildings Part 1: code

PerformancePerformance

New requirements for circuit integrity: enhanced cables

BS 5839-1 : 2002Fire Detection and Fire Alarm Systems for BuildingsPart 1: code of practice for system design, installation, commissioning and maintenancePar. 26 Cable, wiring and other interconnections Recommendation for two level of fire resistance:• Standard for general use• Enhanced when cables might need to operate correctly during a fire for periods in excess of those normally required for single phase evacuation of building

under fire conditionunder fire condition

Page 2: Performance New requirement s for circuit integrity: enhanced cables BS 5839-1 : 2002 Fire Detection and Fire Alarm Systems for Buildings Part 1: code

PerformancePerformance

New requirements for circuit integrity: enhanced cables

BS 5839-1 : 2002

StandardEN 50200 PH 30 classification (improved)830 °C mechanical shock for 15 min.

mechanical shock and water for 15 min.

EnhancedEN 50200 PH 120 classification (improved)930 °C mechanical shock for 60 min.

mechanical shock and water for 60 min.

under fire conditionunder fire condition

Page 3: Performance New requirement s for circuit integrity: enhanced cables BS 5839-1 : 2002 Fire Detection and Fire Alarm Systems for Buildings Part 1: code

PerformancePerformance

New requirements for circuit integrity: enhanced cables

BS 5839-1 : 2002Regarding fibre optic cables,“When fibre optic connections are used, they need to provide at least equivalent integrity and reliability to other cables that are recommended for the same purpose”.

under fire conditionunder fire condition

Page 4: Performance New requirement s for circuit integrity: enhanced cables BS 5839-1 : 2002 Fire Detection and Fire Alarm Systems for Buildings Part 1: code

ProductsProducts

SR 114EControl Cables 300/500 VThese cables have been designed to meet requirements of BS 5839-1 : 2002 for enhanced cables for certain specific building applications.

Standards:BS 6387 C W Z, BS 7629, SS 299 part 1, IEC 60331, IEC 60332-1, IEC 60332-3, IEC 60754-1, IEC 61034, EN 50200 PH120,CEI 20-35, CEI 20-36, CEI 20-37, CEI 20-38, CEI 20-22/3