A brand of the
l
FP200 Gold®
Key Applications > Fire detection and fire alarm systems for buildings> Voice alarm systems > Emergency voice communication> Emergency and escape lighting> Control circuits for life safety and fire fighting systems > Other essential service control circuits for ‘standard’ fire resistance
British Standards. Tests & Approvals> BS7629-1, Standard 60 (1.0mm² Standard 30)> BS EN 50200 PH30, PH60, PH120 and ANNEX E> BS 5839-1, 6, 8 & 9 ‘standard’ fire resisting cable> BS 5266-1 ‘standard’ fire resisting cable> BS 8519 Category 1 control cable> BASEC approved > London Underground 1.085 Approved Product Register (Section 12)> LPCB approved (specific products and fire tests only)
Core identification Harmonised - standardo o brown-blueo o o brown-black-grey o o o o blue-brown-black-grey
Conductor Plain annealed copper. Solid (1.0 - 2.5 mm²) or stranded circular conductors (4.0 mm²) to meet the requirements of BS EN 60228 class 1 or class 2.
InsulationHigh performance, damage resistant Insudite™ to meet BS EN 50363-5, Type EI5.
Overall metallic screen and CPCPolyester backed laminated aluminium tape bonded to outer sheath to provide overall screen. In contact with full sized, tinned annealed copper circuit protective conductor and laid-up with the cores to provide automatic screen earthing.
SheathRobust thermoplastic low smoke, zero halogen and reduced flame propagation outer sheath. Standard colours white and red with bespoke colours available to special order. Suitable for outdoor installation with exposure to normal daylight UV.
Ref
:FP2
00Go
ld/1
0/17
THE ORIGINAL ‘STANDARD’ FIRE RESISTANT CABLE (300/500 V)
BSEN60332-1-2BSEN61034-2
EN50200 PH30 & PH60
TemperatureRange
-20 to +70˚C
Bending RadiusFixed r=6D
Mechanical ImpactMedium
Fire PerformanceBS EN 60332-1-2BS EN 50266-2-4
FlexibiltyRigid
Halogen FreeBS EN 50267-2-1
Low Smoke EmissionsBS EN 61034-2
Fire ResistanceBS6387 Category CWZ
BS EN 50200 PH30 & PH603
BS EN 50200 Annex E
CABLE DESCRIPTION
Non harmonised – to special ordero o red-blacko o o red-yellow-blueo o o o black-red-yellow-blue
Fire resistanceBS EN 50200 PH30
PH60 & PH120BS EN 50200 ANNEX E
BS6387 CWZ
BS EN 60332-1-2BS EN 60332-3-24
Rigid BS EN60754-1r=6D
Two core
1.0 1/1.13 7.8 79 18.1 13 15 44 AP7 251/GL2520 UFPNF02
1.5 1/1.38 7.9 90 12.1 16.5 19.5 29 AP7 251/GL2520
2.5 1/1.78 9.5 140 7.41 23 27 18 AP9 251/GL2520 -
4.0 7/0.85 12.0 205 4.6 30 36 11 AP11 252/GL2520 -
Three core
1.5 1/1.38 8.3 115 12.1 16.5 19.5 29 AP8 251/GL2520 UFPNF04
2.5 1/1.78 10.5 180 7.41 23 27 18 AP10 252/GL2520 -
4.0 7/0.85 12.5 260 4.6 30 36 11 AP12 252 -
Four Core
1.5 1/1.38 10.0 150 12.1 16.5 19.5 29 AP9 251/GL2520 -
2.5 1/1.78 12.0 225 7.41 23 27 18 AP11 252/GL2520 -
4.0 7/0.85 13.5 320 4.6 30 36 11 AP13 254 -
> Recommended clip spacing 300 mm horizontal and 400mm vertical using only metallic fixings. > Minimum recommended installation temperature 0°C. Installation methods for current rating in accordance with BS7671/IET Wiring Regulations. > The tabulated ratings are based upon a 30°C ambient temperature and 70°C operating temperature. For other ambient temperatures or where cables are grouped together, appropriate rating factors should be applied.> FP200 Gold® is also available in multi-core versions (7,12 & 19 core)> De-rate by factor 0.8 when 4 cores are loaded
Nominal cross
sectional area
mm2
Conductor Construction
no/mm
Approximate overall
diameter
mm
Approximate cable
weight
kg/km
Maximum conductor resistance
at 20°C
Ω/km
Current rating DC or single phase
AC Enclosed
Amps
Current rating DC or single phase
AC Clipped direct
Amps
Volt drop DC or single
phase AC
mV/A/m
LSOH®
fixingclips
NylonLSOH®
gland
Recommended accessoriesColour - White or Red
FP FirefixTM
fixingclips
Notes to table
UFPNF01UFPNF02
Overseas sales enquiriesTel: +44 (0) 23 5029 5481Fax: +44 (0) 23 8029 5465
Overseas technicalTel: +44 (0) 23 8029 5481Fax: +44 (0) 23 8029 5002
Information hotlineTel: +44 (0) 23 8029 5029Fax: +44 (0) 23 8029 5437
Sales enquiriesTel: 0845 767 8345Fax: 023 8029 5465
UK Technical helplineTel: 0845 767 8345Fax: 023 8029 5002
Prysmian Cables & Systems LimitedChickenhall LaneEastleighHampshireSO50 6YUUnited Kingdom
Ref
: FP2
00Go
ld/1
0/17For further information please
see our dedicated FP Cables website:www.fpcables.co.uk
Correction factors for Ambient temperatures: Table 4B1
Correction factors for grouping of cables: Table 4C1
Table 4B1
Ambient Temperature°C 25 30 35 40 45 50
Rating factor 1.03 1.00 0.94 0.87 0.79 0.71
Table 4C1
Number of circuits 2 3 4 5 6 7
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54
Should you have any concerns aboutunsafe, non-approved or counterfeitcable, please contact the ACI
Tel: 020 8946 6978Email: [email protected]
BF1345 Rev. 0.3 Page 1 of 3 © BRE Global Ltd, 2015
This Certificate is maintained and held in force through regular surveillance activities and subject to the corresponding ISO 9001 Certificate being maintained.
Damien Ward 10 August 2016 14 August 2003 Signed for LPCB Certification Scheme Manager Date of Issue Date of First issue
This certificate and appendix remain the property of BRE Global Ltd and is issued subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Garston, Watford, WD25 9XX T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: [email protected]
Certificate of Product Approval Certificate Number: 077f Issue: 06
PRYSMIAN CABLE & SYSTEMS LIMITED
Chickenhall Lane Bishopstoke Eastleigh Hants SO50 6YU United Kingdom is authorised to use the LPCB mark in association with the product(s) listed in this certificate and appendix having complied with the requirements of the standard(s) detailed below:
Product(s) Standard(s) (see Appendix for details) Cable Types as listed below: FP200 Gold
See Certificate Appendix for details
BS 7629-1:2015 (STANDARD 30) BS 7629-1:2015 (STANDARD 60) BS 6387:2013 (CWZ) EN 50200:2015 (Class PH30 & PH60) EN 50200:2015 Annex E (30 mins) BS 5839-1:2013 (Clause 26.2d Standard)
BF1345 Rev. 0.3 Page 2 of 3 © BRE Global Ltd, 2015
Appendix to Certificate No: 077f Issue: 06 PRYSMIAN CABLE & SYSTEMS LIMITED
This Certificate is maintained and held in force through regular surveillance activities and subject to the corresponding ISO 9001 Certificate being maintained.
Damien Ward 10 August 2016 14 August 2003 Signed for LPCB Certification Scheme Manager Date of Issue Date of First issue
This certificate and appendix remain the property of BRE Global Ltd and is issued subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Garston, Watford, WD25 9XX T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: [email protected]
Product name LPCB Ref.
No.
FP200 Gold 077f/01
Nominal csa of conductor (mm2)
Core Construction
(excluding drain wire and earth)
BS 7629-1 BS 6387 EN 50200 EN 50200
(Annex E)
EN 5839-1
(clause 26.2)
1.0 2 (1) STANDARD 30 C,W,Z PH30 30min(4) Standard(5)
1.5 2, 3 & 4(1) STANDARD 60 C,W,Z PH60 30min(4) Standard(5)
2.5 2, 3 & 4(1) STANDARD 60 C,W,Z PH60 30min(4) Standard(5)
4.0 2, 3 & 4(2) STANDARD 60 C,W,Z PH60 30min(4) Standard(5)
Uo/U 300/500V
Notes: 1. Solid conductor only. 2. Stranded conductor only. 3. In meeting the requirements of BS 7629-1:2015, the FP200 Gold cables listed met the requirements for smoke
density of EN 61034-2:2005+A1:2013, and achieved less than 0.5% HCl for the insulation, binder tape and outer covering when tested in accordance with EN 60754-1:2014 and in addition also met the fire resistance requirements of BS 6387:2013 Categories CWZ.
4. The duration of 30min when tested in accordance with EN 50200:2015 Annex E is achieved by 15min for the fire and mechanical shock phase and a further 15min for the fire, mechanical shock and water phase.
5. The FP200 Gold cables listed conform to BS 7629-1:2015 achieving Category STANDARD 30 & 60 and hence met the requirements for a standard fire resistant cable as described in Clause 26.2 of BS 5839-1:2013.
Cross-Listed products and alternative branding are detailed on page 3.
BF1345 Rev. 0.3 Page 3 of 3 © BRE Global Ltd, 2015
Appendix to Certificate No: 077f Issue: 06 PRYSMIAN CABLE & SYSTEMS LIMITED
This Certificate is maintained and held in force through regular surveillance activities and subject to the corresponding ISO 9001 Certificate being maintained.
Damien Ward 10 August 2016 14 August 2003 Signed for LPCB Certification Scheme Manager Date of Issue Date of First issue
This certificate and appendix remain the property of BRE Global Ltd and is issued subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Garston, Watford, WD25 9XX T: +44 (0)333 321 8811 F: +44 (0)1923 664603 E: [email protected]
LPCB Ref No. Model No. Alternative Model No. Labelled Distributors Cert/Ref No.
077f/01
FP200 Gold
1.5mm2 – 4.0mm2
at 2, 3 & 4 cores only
FT30 SAFFIRE
1.5mm2 – 4.0mm2
at 2, 3 & 4 cores only
Draka UK Ltd 1134j/01