Master-K Series Cnet
V1.5
2 | Master-K Series Cnet
V1.5
MASTER-K SERIES CNET ............................................................................................... 1
1. SYSTEM CONFIGURATION ..................................................................................... 3
2. SYSTEM SETTINGS ................................................................................................... 4
3. EXAMPLE ................................................................................................................... 6
3.1. EXAMPLE 1 ...................................................................................................................................................... 6
3.2. EXAMPLE 2 ...................................................................................................................................................... 9
3.3. EXAMPLE 3 .................................................................................................................................................... 11
4. CABLE WIRING DIAGRAMS ................................................................................ 13
4.1. RS232C CONNECTION 1 ............................................................................................................................... 13
4.2. RS232C CONNECTION 2 ............................................................................................................................... 14
4.3. RS485 (2 WIRED) ......................................................................................................................................... 15
5. DEVICE CODE ......................................................................................................... 16
6. TROUBLE SHOOTING ........................................................................................... 17
PLC’s Manual|3
V1.5
1. System Configuration
The weMX® supports LSIS Master-K Series Cnet. The series communication settings are described as below.
Series CPU Link I/F Communication
Type
Communication
Settings
Cable
K80S K7M-DT**S CPU Built-in
Cnet RS232C 3.1 Example 1 4.1. RS232C Connection 1
K200S K3P-07AS CPU Built-in
Cnet RS232C 3.2 Example 2 4.2. RS232C Connection 2
K200S K3P-07AS G6L-CUEC RS422/RS485 3.3 Example 3 4.3. RS485 Connection
■ Connection Configuration
① 1 : 1 (One display and one device/PLC) Connection – Available with RS232C/RS485.
② 1 : N (One display and certain number of device/PLCs) Connection – Available with RS485(2 wired).
4 | Master-K Series Cnet
V1.5
2. System Settings
Select ‘LS Industrial Systems Co., Ltd.’ for ‘Manufacturer’ and ‘Master-K Series Cnet’ for ‘Series’ in the ‘Add
Device/PLC’ setting window.
Add a device and set up a port to the device and a communication type.
The weMX® N series support as below.
COM weMX®N Series
COM1 RS-232C
COM2 RS-232C
COM3 Do not use ( Debug Port)
COM4 RS-485(2 wired)
Set up the selected COM port interface to the device.
Items Description
Speed Select one: ‘2400’, ‘4800’, ‘9600’, ‘19200’, ‘38400’, ‘57600’ and ‘115200’.
Data Length Select ‘7’ or ‘8’.
Parity Select one: ‘NONE’, ‘EVEN’ and ‘ODD’.
Stop Bit Select ‘1’ or ‘2’.
Flow Control No supported
Timeout Standby time for communication. (Unit: seconds)
Retry The number of attempts to communicate after a failure.
Wait to Send Time to wait before sending a message to the external device (Unit: milliseconds)
- This is the time required to wait every time before sending to the device.
Delayed
Interval
This is the time required to wait after the external device finishes reading values for
addresses to the screen. (Unit: milliseconds)
- Start to read those values again after waiting as long as delayed intervals.
PLC’s Manual|5
V1.5
Set up a unit ID to the added device. It indicates a station number in case of LSIS. The default value is ‘0’.
If the device’s station number is different, change it by clicking a unit ID displayed button, ‘Unit ID’ button.
Items Description
Default Unit ID Set up the station number. The default value is ‘0’ The range is from ‘0’ to ‘31’.
Click ‘ ’ button to finish setting up the rest features.
Items Description
BCC Tick ‘BCC’ if it is used for communication between devices.
6 | Master-K Series Cnet
V1.5
3. Example
3.1. Example 1
Set up RS232C Cnet with the CPU built-in Loader port between display and K7M-DT**S as below.
Items Display CPU Built-in
Port
COM Port COM1(RS232C) RS232C
Unit ID
(Station No.)
1 1
Speed 38400 38400
Data Length 8 8
Parity NONE NONE
Stop Bit 1 1
Timeout 3 -
Retry 2 -
Wait to Send 0 -
Delayed Interval 0 -
The screen as below shows that the setup is completed.
PLC’s Manual|7
V1.5
8 | Master-K Series Cnet
V1.5
Use ‘KGL for Windows’ or KGLWIN to change CPU port communication settings.
Follow as below.
① Connect a K7M-DT**S Loader port to a computer.
② Run KGLWIN and create a project with MK_S – 80S.
③ Change the K7M-DT**S mode to PAU/REM.
④ Click [Online] – [Connect] to connect to the K7M-DT**S.
⑤ Click [Online] – [Change Mode] – [Stop] to stop.
⑥ Click [Online] – [Read] to read the PLC’s parameter information.
⑦ Change features in the window as below once the reading is properly complete.
⑧ Send the changed information by clicking [Online] – [Write] once the change is complete.
PLC’s Manual|9
V1.5
3.2. Example 2
Set up RS232C Cnet with the CPU built-in Loader port between display and K3P-07AS as below.
Items Display CPU Built-in
Port
COM Port COM1(RS232C) RS232C
Unit ID
(Station No.)
1 1
Speed 38400 38400
Data Length 8 8
Parity NONE NONE
Stop Bit 1 1
Timeout 3 -
Retry 2 -
Wait to send 0 -
Delayed Interval 0 -
The screen as below shows that the setup is complete.
10 | Master-K Series Cnet
V1.5
Use ‘KGL for Windows’ or KGLWIN to change CPU port communication settings.
Follow as below.
① Connect a K3P-07AS Loader port to a computer.
② Run KGLWIN and create a project with MK_S – 200S.
③ Change the K3P-07AS mode to PAU/REM.
④ Click [Online] – [Connect] to connect to K3P-07AS.
⑤ Click [Online] – [Change Mode] – [Stop] to stop.
⑥ Click [Online] – [Read] to read the PLC’s parameter information.
⑦ Change features in the window as below once the reading is properly complete.
⑧ Send the changed information by clicking [Online] – [Write] once the change is complete.
PLC’s Manual|11
V1.5
3.3. Example 3
Set up as below for RS485 communication with G6L-CUEC I/F card between display and K3P-07AS as below.
Items Display G6L-CUEC
COM Port COM4(RS485) RS485
Unit ID
(Station No.)
1 1
Speed 115200 115200
Data Length 8 8
Parity NONE NONE
Stop Bit 1 1
Timeout 3 -
Retry 2 -
Wait to Send 0 -
Delayed Interval 0 -
The screen as below shows that the setup is complete.
12 | Master-K Series Cnet
V1.5
Set up the G6L-CUEC I/F card by referring to the manual and using the Cnet frame editor.
Follow as below.
① Connect a K3P-07AS Loader port to a computer.
② Run the Cnet frame editor and then click [Online] – [Connect] to connect to the K3P-07AS.
③ Click [Online] – [Read] and then try to read with the RS422 type and default parameter option to a slot
number where the G6L-CUEC I/F card is located.
④ Change the information to the communication settings once the reading is properly complete.
⑤ Send the changed information by clicking [Online] – [Write] once the change is complete.
⑥ There is a mode switch on the G6L-CUEC I/F card to decide an operation mode. The switch should be
set to indicate ‘1’ to communicate with display.
PLC’s Manual|13
V1.5
4. Cable Wiring Diagrams
4.1. RS232C Connection 1
① For connection between PC and PLC
PC Pin No. Pin No. CPU Built-in
Loader
By cable
D-SUB 9 Pin
Female type
1 1
By cable
D-SUB 9 Pin
Male type
2(RXD)
2
3(TXD)
3
4
4(RXD)
5(GND) 5(GND)
6 6
7
7(TXD)
8 8
9 9
② For connection between display and PLC
weMX® A Series Pin No. Pin No. CPU Built-in
Loader
By cable
D-SUB 9 Pin
Male type
1 1
By cable
D-SUB 9 Pin
Male type
2(TXD)
2
3(RXD)
3
4
4(RXD)
5(GND) 5(GND)
6 6
7
7(TXD)
8 8
9 9
14 | Master-K Series Cnet
V1.5
4.2. RS232C Connection 2
③ For connection between PC and PLC
PC Pin No. Pin No. CPU Built-in
Loader
By cable
D-SUB 9 Pin
Female type
1 1
By cable
D-SUB 9 Pin
Male type
2(RXD)
2
3(TXD)
3
4
4(RXD)
5(GND) 5(GND)
6 6
7
7(TXD)
8 8
9 9
④ For connection between display and PLC
weMX® A Series Pin No. Pin No. CPU Built-inLoader
By cable
D-SUB 9 Pin
Male type
1 1
By cable
D-SUB 9 Pin
Male type
2(TXD)
2
3(RXD)
3
4
4(RXD)
5(GND) 5(GND)
6 6
7
7(TXD)
8 8
9 9
PLC’s Manual|15
V1.5
4.3. RS485 (2 Wired)
weMX® N Series Pin No. Pin No. G6L-CUEC
TRX+
RDA
GND
RDB
GND
SDA
TRX-
SDB
SG
FG
16 | Master-K Series Cnet
V1.5
5. Device Code
Here are devices that the weMX® supports as below. 주1)
Device Type Bit Address Word Address 32
bits
Remark
Input / Output Relay Word P00000 – P0063F P0000 – P0063
L/H
Auxiliary Relay Word M00000 – M0191F M0000 – M0191
Keep Relay Word K00000 – K0031F K0000 – K0031
Link Relay Word L00000 – L0063F L0000 – L0063
Special Relay Word F00000 – F0063F F0000 – F0063 주2)
Timer (Contact) Bit TX0000 – TX0255 – 주3)
Counter (Contact) Bit CX0000 – CX0255 – 주3)
Timer (Current Value) Word – T0000 – T0255
Counter (Current Value) Word – C0000 – C0255
Step Controller Word – S000 – S099
Data Register Word D0000.0 – D9999.F D0000 – D9999
Note 주1)The weMX® supports the maximum address range among available CPUs in the series. Refer to
the manual given that which device/PLC is supported and device ranges basically depend on each
device/PLC.
주2) Write not allowed
주3) Bit timer and counter are set to ‘TX’ and ‘CX’ respectively to distinguish timer and counter in
word.
PLC’s Manual|17
V1.5
6. Trouble Shooting