PASS Module Complete Manual - En

Embed Size (px)

Citation preview

  • 8/9/2019 PASS Module Complete Manual - En

    1/200

     Doc. 2GJ 700292Rev. D 10/2011 [AI]

     

    Type of D cumentManual

    TitlPASS Family

    1/10 ABB S.p.A. PPD U.O. ADDA

    PASS:

    Innovative Solutions for DistributionSubstations 

  • 8/9/2019 PASS Module Complete Manual - En

    2/200

     Doc. 2GJ 700292Rev. D 10/2011 [AI]

     

    Type of D cumentManual

    TitlPASS Family

    2/10 ABB S.p.A. PPD U.O. ADDA

    INDEX

    1. IMPORTANT INFORMATION ......................................................................................... 31.1 Supplier’s / Manufacturer’s Address .................................................................... 31.2 Contact Address ..................................................................................................... 31.3 Purpose of th is Manual .......................................................................................... 31.4 Safety Note .............................................................................................................. 3

    2. GLOSSARY .................................................................................................................... 33. CONCEPT ....................................................................................................................... 44. FLEXIBILITY ................................................................................................................... 4

    4.1 Integration with secondary sys tem ....................................................................... 6

    5. ENVIRONMENTAL IMPACT ........................................................................................... 66. QUALITY ASSURANCE ................................................................................................. 67. MANUFACTURING ......................................................................................................... 78. TRANSPORTATION ....................................................................................................... 79. ON-SITE ASSEMBLY ..................................................................................................... 710. STANDARDS............................................................................................................... 711. PASS VARIANTS ........................................................................................................ 812. TESTS ......................................................................................................................... 9

    12.1 Type tests ................................................................................................................ 912.2 Routine tests ........................................................................................................... 912.3 On-si te test ing ........................................................................................................ 9

  • 8/9/2019 PASS Module Complete Manual - En

    3/200

     Doc. 2GJ 700292Rev. D 10/2011 [AI]

     

    Type of D cumentManual

    TitlPASS Family

    3/10 ABB S.p.A. PPD U.O. ADDA

    1. IMPORTANT INFORMATION

    1.1 Supplier’s / Manufacturer’s Address

     ABB S.p.A PPDU.O. AddaVia dei Ceramisti26900 Lodi – ItalyTel. +39.0371 – 452.1Fax. +39.0371 – 452.222Internet: http://www.abb.it 

    1.2 Contact Address

     ABB S.p.A PPDU.O. AddaVia dei Ceramisti26900 Lodi – ItalyTel. +39.0371 – 452.2Fax. +39.0371 – 452.222Internet: http://www.abb.it 

    1.3 Purpose of this Manual

    This manual describes high-tech high voltage products, and is specifically aimed at explaining theuse of such products. These instructions are not meant to replace valid regulations, concerning highvoltage systems and appliances, and are intended for use by specialists in the electricity field.

    1.4 Safety Note

     Ac tivities desc ribed under “ Maintenance” must on ly be carr ied out f rom ourPersonnel o from Personnel trained by us when the notes have been read andunderstood and the preconditions described there fulfilled.Otherwise, the manufacturer shall not be liable for damage of any kind as a resultof improper handling

    2. GLOSSARY

    Key  PASS Plug And Switch System SBB Single Bus Bar  DBB Double Bus Bar  IOS Incoming Outgoing Substation DCB Double Circuit-breaker  LCC Local Control Cabinet OSCAR Optimal Substation Concept And ResearchSLD Single Line Diagram

    Mechanical Operation Informationt

    DANGER: Information indicatingthat danger or risk exists whichcould result in serious or fatalinjuries to personnel. 

    WarningInformation

  • 8/9/2019 PASS Module Complete Manual - En

    4/200

     Doc. 2GJ 700292Rev. D 10/2011 [AI]

     

    Type of D cumentManual

    TitlPASS Family

    4/10 ABB S.p.A. PPD U.O. ADDA

    3. CONCEPT

    NOTE: This document provides general information which does not take intoconsideration specific project requirement. Please refer to specific projectschematics for the working and interlock princip le of the equipment.

    PASS is equivalent to a high voltage bay. In PASS all live parts, excluding Bus Bars and CT’s, areencapsulated in a grounded aluminium tank which is filled with pressurised SF6 gas. Each pole hasits own enclosure to increase availability and safety. The main enclosures are made of castaluminium.Using standard components, the addition of a secondary Bus Bas system to PASS is straightforward.

    4. FLEXIBILITY

    PASS (Plug And Switch System) is based on ABB extensive experience in manufacturing both air

    insulated switchgear (AIS) and gas-insulated switchgear (GIS). PASS can also be thought as“Performance And Save Space”: any substation layout can be met while making efficient use ofavailable space. Performance is guaranteed by the wealth of experience in research anddevelopment, manufacture and operation of switchgear which constitute the basis of ABB know-how.The key characteristic of PASS is its compact and modular design which encompasses severalfunctions in one module, as for example:- Bushings for connection to one or two Bus Bar systems;- One or two circuit-breakers- One or more combined disconnector/earthing switches;- One or two current transformers

    PASS M0The PASS M0 is a complete High Voltage substation in incoming/outgoing configuration:

    - primary bushings are connected to the power transformer;- secondary bushings are connected to the outgoing line;- tertiary bushings are connected to the incoming line.Therefore there is no traditional Bus Bar, i.e. the Bus Bar is realized within the PASS M0 by means ofthe first and second bushings. PASS in this configuration is a really breakthrough as system concept(patented) for distribution substation. It may have he following configuration:

      Single Bus Bar (SBB)  Double Bus Bar (DBB)

      In and Out substation (IOS)

      Double Circuit Breaker (DCB)

    PASS M00 PASS M00 has been designed to meet the specific requirements of the fast-expanding market for

    72,5 kV and 100 kV systems.

    PASS M0SPASS M0S is born from experience that ABB Group has gained in the field of hybrid modules (PASSM0), to cover market request for transmission and distribution substations at 252 kV.

    The innovative characteristic of PASS M0S is a three-position disconnected, which allowssectionalising and earthing through one moving contact. PASS M0S has been realised as modularcomponent with basic standard functions, which can be increased according to other requirements ofthe substation.

  • 8/9/2019 PASS Module Complete Manual - En

    5/200

     Doc. 2GJ 700292Rev. D 10/2011 [AI]

     

    Type of D cumentManual

    TitlPASS Family

    5/10 ABB S.p.A. PPD U.O. ADDA

    PASS M00 PASS M0 PASS M0S PASS M0S 50 kA

    Rated Voltage kV 72,5 100 123 145 170 245 245

    Rated Current A 3150 3150 3150 3150

    Breaking Current kA 40 20 40 40 50

     AC Test Voltage kV 160 185 230 275 325 395 460

    Impulse Test

    Voltage - BIL

    kV 350 450 550 650 750 950 1050

     Altitude Above Sea m  1000  1000  1000  1000

    Max airTemperature

    °C + 40 (1)  + 40 (1)  + 40 (1)  + 40 (1) 

    Min airTemperature

    °C - 40 (1)  - 30 (1)  - 30 (1)  - 25 (1)  - 35(1) 

    Relative humidity % 100 100 100 100

    Wind pressure Pa 700 700 700 700

    Sun radiationW/m

    2  1000  1000  1000  1000

    Earthquake

    (IEC1166) g 0.5 0.5 0.5 0.5

    Protection deg.

    (IEC 60529)IP 44 (2)  44 (2)  44 (2)  44

    (2) 

    Pollution Level

    (IEC 60137)III Heavy (3)  IV Very Heavy

    IV VeryHeavy

    IV Very Heavy

    (1) different temperatures on request

    (2)different degree on request

    (3)level IV (Very Heavy) on request

    PASS M00 PASS M0 PASS M0S PASS M0S50kA

  • 8/9/2019 PASS Module Complete Manual - En

    6/200

     Doc. 2GJ 700292Rev. D 10/2011 [AI]

     

    Type of D cumentManual

    TitlPASS Family

    6/10 ABB S.p.A. PPD U.O. ADDA

    4.1 Integration with secondary system

    Pass is equipped with conventional coupling towards the external substation process: e.g. auxiliarycontacts for circuit-breaker and disconnector/earthing switch position and relay's contacts forsignalling (e.g. SF6 leak).This conventional interface allows the PASS to be connected with any control and protection system,thus enabling retrofitting and upgrading of already existing substations. 

    5. ENVIRONMENTAL IMPACT

    PASS is kind to the environment. Global life cycle cost and impact on the environment wereconsidered during PASS design right from the beginning. Compared to a conventional air insulatedsolution which implements the same functions, PASS meets the following targets:• SF6 reduced by 80%;

    • maintenance cost reduced by 38%;• space reduced by 70%;

    • total life cycle cost 60% lower;

    Compared to a conventional 5 bays H layout air insulated substation, the global life cycle cost forPASS is estimated to be more than 30% lower.Moreover PASS has been subjected to the LCA (Life Cycle Assessment), a study that covers allenvironmental aspects during the whole life of the product. In this regard, EDP (EnvironmentalProduct  Declaration) provides a quantitative and verified description of the environmentalperformance of PASS, viewed from a comprehensive life cycle perspective.

    6. QUALITY ASSURANCE

    Design, material, suppliers, sub-assemblies and working procedures are ruled by internal qualityassurance programs, which meet the requirements stated by ISO 9001 and 14001.

    Parts which are not directly manufactured are provided by other ABB companies or by approvedvendors.

     A test plan states the regular incoming material inspection.Disruptive and non-disruptive special tests are performed in our, or at third part, laboratories wherewe verify the conformance to the technical specification.

     All instruments and apparatus used for testing and checking are systematically and periodicallycalibrated in our metrological laboratory or at qualified third party labs.Standard operation procedures are the basis to ensure the correct assembling process.The documents provide step-by-step assembly instructions for each part of our product

     All check lists, filled at assembling and test step, are collected and stored, to ensure the wholetraceability of products and sub-assemblies.The final tests prove the conformity of the product to Client specifications and to the applicableInternational Standards.The completeness of the supply is one by one confirmed by a Final check.

  • 8/9/2019 PASS Module Complete Manual - En

    7/200

     Doc. 2GJ 700292Rev. D 10/2011 [AI]

     

    Type of D cumentManual

    TitlPASS Family

    7/10 ABB S.p.A. PPD U.O. ADDA

    7. MANUFACTURING

    PASS manufacturing process is mostly based on techniques like Lean Manufacturing and Theory OfConstraints. The “Assembly To Order” model is used to guarantee the traceability of allsubcomponents.

    Major targets like On Time Delivery are achieved thanks to the modularization of the product andrelevant standardization of sub-components, allowing a smooth supplying and assembling process.

    No stock is then needed, neither for sub-components not for finished products.

    Technical features like special automatic tools for the subcomponents assembling, fastreconfigurable production lines and tool carts for sub-assemblies handling make the factory flexibleenough to adapt itself to the always changing needs and demands from the market.

    8. TRANSPORTATION

    No special arrangements are needed for shipping and transportation. PASS, in its standard version,fits in a standard truck container and does not require special packaging. On receipt of the good,the entire module PASS and structure shall be checked; in particular the density switches thedrives of the circuit breaker and disconnector. The equipment shall show no sign of break ortampering. If any problems are found the Shipping office of ABB S.p.A. PPD U.O. Adda shall beimmediately informed. Once on site a simple 30° rotation of the outer poles is needed for the finallayout of PASS. If the equipment is stored before assembly, it must be kept in a covered, dry place.If this equipment is stored outside, it must be placed in a dry drained place and all packages mustbe covered with tarpaulins. The integrity of the packages and their covers must be checkedperiodically (ref. to STORAGE instruction 2GJA708375).

    9. ON-SITE ASSEMBLY

     A PASS module is equivalent or almost equivalent to a complete bay.

    It allows the installation of substations in a short period of time: each bay can be unloaded from thetrailer and directly installed on the platform foundation.

    The on-site erection of PASS modules is simplified since PASS is fully assembled in the factorybefore shipment.

    The installation of a PASS requires few hours with a crew of two (not including gas handling).

    10. STANDARDS

    PASS meets the requirements set out in the following documents:

    • IEC (all relevant standards - see technical data)

    • ISO 9001 and 14001.

    The enclosure complies with the following standard for pressure vessels:

    • CENELEC EN 50052.

    Quality handbooks and inspection plans can be provided to the customer on request.

    PASS switchgear is produced according to the following standards:

    • For pressure vessel construction: ..............................................CENELEC EN 50052

  • 8/9/2019 PASS Module Complete Manual - En

    8/200

     Doc. 2GJ 700292Rev. D 10/2011 [AI]

     

    Type of D cumentManual

    TitlPASS Family

    8/10 ABB S.p.A. PPD U.O. ADDA

    • For quality assurance: ............................................................... ISO 9001, 14001

    For switchgear and associated equipment:

    • High voltage switchgear..............................................................IEC 62271-1

    • Compact switchgear assembly...................................................IEC 62271-205

    • SF6 switchgear...........................................................................IEC 62271-203

    • Bushings.................................................................................... IEC 60137

    • Current transformers.................................................................. IEC 60044-1

    • Disconnect/earthing switch........................................................ IEC 62271-102

    • Circuit-breaker............................................................................ IEC 62271-100

    11. PASS VARIANTS

    Thanks to the modular approach, the number of possible variants is extremely high; the followinglist reports just some of the possible solutions.

      PASS M00 SBB

      PASS M00 DBB

      PASS M0 SBB

      PASS M0 DBB

      PASS M0 DCB

      PASS M0S SBB

      PASS M0S DBB

      PASS M0S DCB

      PASS M00 Cableends

      PASS M0 (SBB, DBB or DCB)o  with GIS VT’so

      with cable endso  with additional CT’s

      PASS M00 MobileSubstation

      PASS M0 Mobile Substation115/34,5 kV – 30 MVA

      PASS M0 Mobile Substation132/20 kV – 25 MVA

      PASS M0 Railway MobileSubstation

      PASS M0 IOS

  • 8/9/2019 PASS Module Complete Manual - En

    9/200

     Doc. 2GJ 700292Rev. D 10/2011 [AI]

     

    Type of D cumentManual

    TitlPASS Family

    9/10 ABB S.p.A. PPD U.O. ADDA

    12. TESTS

    12.1 Type tests

     All type tests specified by the relevant IEC standards have been passed. Tests can be repeated onrequest at customer’s expense. Copies of certificates and reports can be provided on request.

    12.2 Routine tests

    Before leaving the factory all PASS units are subject to the following routine tests:

    • AC High voltage test;

    • dielectric tests on auxiliary control units;

    • pressure tests of the enclosure according to CENELEC-EN 50052 1986 TC 17C WG MPE. Theenclosure is tested at double the design overpressure for one minute. This test also meets the

    requirements of IEC 60517;• gas tightness;

    • mechanical functional test of all moving parts;

    • test of all equipment and accessories;

    • AC high voltage test. These tests ensure perfect functionality of all components before they leavethe factory. A test report is produced for all tests.

    On request customers can attend the final acceptance test session.

    12.3 On-site testing

     After final assembly or commissioning of the substation, the following tests are done:

    • mechanical functional testing of circuit-breaker, and combined disconnector/earthing switch;

    • testing of SF6 gas-tightness;

    • random sampling of moisture content in individual components;

    • checking and functional testing of control and auxiliary equipment.

     After completion of these tests a handover report is completed.

  • 8/9/2019 PASS Module Complete Manual - En

    10/200

     Doc. 2GJ 700292Rev. D 10/2011 [AI]

     

    Type of D cumentManual

    TitlPASS Family

    10/10 ABB S.p.A. PPD U.O. ADDA

    NOTESIf you have some comments we kindly ask You to write that here below and send us this page back.

    Thank You for your collaboration.

    CopyrightWe reserve all rights concerning this document and the components described therein. It must not bereproduced or disclosed to thirdparties and the contents must not be made use of neither in part or in whole without our prior writtenpermission.© ABB Italy S.p.A., Division High Voltage Product.

    The information in this document is subject to alteration without prior notice and should not be regarded as anundertaking from ABB S.p.A. - Power Products Division - Unità Operativa Adda – HV. ABB S.p.A. - Power Products Division - Unità Operativa Adda - HV takes no responsibility for errors that canoccur in the documentation. ABB S.p.A. - Power Products Division - Unità Operativa Adda - HV is not responsible for damage incurred dueto the misuse of this document.

    Reproduction prohibitedBy law, we remain the owners of this document. Under no circumstances may it be reproduced, handed over ordisclosed to competitor companies or to third parties without our written authorisation.© ABB S.p.A. - Power Products Division - Unità Operativa Adda – HV.

     Address ABB S.p.A. - PPD U.O. Adda - HV

    Via dei Ceramisti26900 Lodi – Italytel. +39.0371 – 452.1fax +39.0371 – 452.222internet : http:/www.abb.com/it

    NotesThese instructions describe high voltage technology products and are intended specifically for making knownthe use of such products.These instructions are not intended to replace valid regulations, with regard to high voltage systems andequipment, and are intended for the use of specialists in the electrical field.

  • 8/9/2019 PASS Module Complete Manual - En

    11/200

    Doc. 2GJA700293/Rev. D 11/11 [MT]

    Typeof DocumentManual

    TitlPreventive Maintenance

    1/8ABB S.p.A. PPD U.O. ADDA

    PREVENTIVE MAINTENANCE GUIDE FOR PASS

  • 8/9/2019 PASS Module Complete Manual - En

    12/200

    Doc. 2GJA700293/Rev. D 11/11 [MT]

    Typeof DocumentManual

    TitlPreventive Maintenance

    2/8ABB S.p.A. PPD U.O. ADDA

    INDEX1. PREVENTIVE MAINTENANCE GUIDE………………………………………page 3

    1.1 Periodical inspection……………………………………………………page 3

    1.2 Preventive maintenance…….………………………………………….page 4

    1.3 Revision……………………………………………………………..........page 6

    CONTENTS OF TABLES

    Tab. 1 Periodical inspect ions…………………………………………………………page 3

    Tab. 2 Preventive maintenance……………………………………………………….page 5

  • 8/9/2019 PASS Module Complete Manual - En

    13/200

    Doc. 2GJA700293/Rev. D 11/11 [MT]

    Typeof DocumentManual

    TitlPreventive Maintenance

    3/8ABB S.p.A. PPD U.O. ADDA

    1. PREVENTIVE MAINTENANCE GUIDE

    The operational safety of the PASS main components CB, DS, ES, CT, is not affected by anyexternal impact (such as dirty, humidity, etc.) with the exception of the bushings.Bushings are qualified for use in polluted environment and in presence of rain. PASS modulerequires virtually no maintenance for a long time.The prescribed activities are:

    periodical inspectionspreventive maintenancerevision

    1.1 Periodical inspection

    Functional and visual inspections are carried out without opening the gas compartments.Every year a visual inspection (with the module in service) of the following parts is recommended:- bushings- SF6 density device and relevant indication;- number of circuit breaker operations;- tightness of Local Control Cabinet door gaskets;- general check of the compartments: position indicators, connectors, cables, equipotential

    connections, earthing circuit. None of the auxiliary equipment shall be worn or overheated andno vibration shall harm the relays.

     At the end of the first year we recommend to retighten screw joints related to anchor bolts andearthing connection and check the absence of corrosion or deterioration of components.

    NOTE: in case of daily breaker operations, all wirings shall be checked, of LCC and BLK(82-222) drive (if present). The check must be done every two years.

    Periodical inspections: module in-service

    Inspection type Timing / tools / personnel Instructions

    Visual inspection o f bushingEvery year 

    No Tools neededUnskilled personnel

    Standing on land check on allsides the condition of sheds

    Check of SF6 density device

    Every year Tools needed: reference values

    on Schematic DiagramUnskilled personnel

    Record the value seen on thedevice and compare it with the

    reference value

    Recording the number of circuit

    breaker operations

    Every year No Tools needed

    Unskilled personnel

    Record the number o f circuit-breaker operations repor ted on

    counter located on L CC

    Tightness of door gasketsEvery year 

    No Tools neededUnskilled personnel

    Open the door of L CC andcheck the gasket condition

    General check of thecomponents

    Every yearNo Tools needed

    Unskilled personnel

    Check position indicators,connectors, cables,

    equipotential connections,earthing circuit. None of theauxiliary equipment must beworn o r overheated and shallno vib ration harm the relays.

  • 8/9/2019 PASS Module Complete Manual - En

    14/200

  • 8/9/2019 PASS Module Complete Manual - En

    15/200

    Doc. 2GJA700293/Rev. D 11/11 [MT]

    Typeof DocumentManual

    TitlPreventive Maintenance

    5/8ABB S.p.A. PPD U.O. ADDA

    Preventive maintenance: module out of service

    Inspection type Timing / tools / personnel Instructions

    Check of alarms, trips andblocks and check of pressure

    gauge condition

    Every 20 yearsTool s needed: SF6 gas bottle,

    pressure gaugeSkilled personnel or personnelcertified by ABB Adda Service

    at level 2

    Check the alarm and tr ip/blockthreshold by decreasing thepressure and by comparing

    relevant values with the readingof the sample gauge previously

    connected.NOTE: be aware that the

    density switch supplied withthe module is temperaturecompensated (at 20°C): for

    comparison please refer to theconversion table in the Gas

    Manual.

    Check of humidi ty level in theSF6 compartments

    Every 20 yearsTool s needed: hygrometer

    Skilled personnel

    Connect the hygrometer to thePASS filling valve type DN8 and

    check the humidit y value iswith in the allowed range(please refer t o the Gas

    Manual).

    Check lubrication of gear boxof di sconnecting switch driveand inspect covers gaskets

    tightness

    Every 20 yearsNo tools n eeded

    Skilled personnel or personnelcertified by ABB Adda Service

    at level 1

    Refer to the “ MAINTENANCE”paragraph of specific

    components

    Check lubrication of circuitbreaker d rive mechanism and

    inspect covers gaskets

    tightness

    Every 20 yearsNo tools n eeded

    Skilled personnel

    Refer to the “ MAINTENANCE”paragraph of specific

    components

    Repetition o f commissioningmechanical test

    Every 20 yearsTools needed: recording tool,

    routine test reportSkilled personnel or personnelcertified by ABB Adda Service

    at level 3

    Repeat the commissioning test

    \Visual inspection of contactsand CB chamber condit ion

    Every 20 yearsTools needed: special tools

     ABB au thori zed Personnel on lyNo description n eed

    Check of contact resistance ofmain circuit

    Every 20 yearsTools needed: micro ohmmeter,

    routine test reportSkilled personnel or personnel

    certified by ABB Adda Serviceat level 2

    IEC 694 (IEC 62271 – 1):

    Injection of t est current > 100 AThe measured resistance shall

    be within the allowed range

    defined by manufacturer.

     Absence o f cor rosion ordeterioration o f components

    Every 20 years

    No tools n eededUnskilled personnel

    Refer to manual specificManual “ SPARE PARTS”

    Retighten screw joints relatedto anchor bol ts and earthing

    connection

    Every 20 yearsTool s needed: torque wrench,

    module layoutSkilled personnel

    Check the tigh ten of anchorbolts and earthing connection

    and retighten if necessary

    Tab. 2

  • 8/9/2019 PASS Module Complete Manual - En

    16/200

    Doc. 2GJA700293/Rev. D 11/11 [MT]

    Typeof DocumentManual

    TitlPreventive Maintenance

    6/8ABB S.p.A. PPD U.O. ADDA

    1.3 Revision

    The revision of the PASS is carried out with the module out of service.It shall be done if one of the following conditions is reached:

    10000 mechanical operations

    40 years of service

    The general revis ion foresees at 40th

     year is carried out with the replacement of PASSmodule with one previously recondit ioned in order to reduce the outage time. Completemodule revision and replacement of worn part is made.

    Revision : module out of service

    Note: all tools mentioned are not supplied by ABB, customer must provide them.Where ABB Personnel is indicated contact ABB Adda Service.

  • 8/9/2019 PASS Module Complete Manual - En

    17/200

    Doc. 2GJA700293/Rev. D 11/11 [MT]

    Typeof DocumentManual

    TitlPreventive Maintenance

    7/8ABB S.p.A. PPD U.O. ADDA

  • 8/9/2019 PASS Module Complete Manual - En

    18/200

    Doc. 2GJA700293/Rev. D 11/11 [MT]

    Typeof DocumentManual

    TitlPreventive Maintenance

    8/8ABB S.p.A. PPD U.O. ADDA

    NOTESIf you have some comments we kindly ask You to write that here below and send us this page back.

    Thank You for your collaboration.

    Copyright

    We reserve all rights concerning this document and the components described therein. It must not bereproduced or disclosed to thirdparties and the contents must not be made use of neither in part or in whole without our prior writtenpermission.© ABB Italy S.p.A., Division High Voltage ProductThe information in this document is subject to alteration without prior notice and should not be regarded asan undertaking from ABBPower Technologies S.p.A.. ABB Power Technologies S.p.A. takes no responsibility for errors that can occur in the documentation. ABB Power Technologies S.p.A. is not responsible for damage incurred due to the misuse of this document.

    Reproduction prohibited

    By law, we remain the owners of this document. Under no circumstances may it be reproduced, handed over ordisclosed to competitor companies or to third parties without our written authorisation.© ABB PT SpA U.O. Adda

     Address

     ABB PT SpA U.O. AddaVia dei Ceramisti26900 Lodi – Italy

    tel. +39.0371 – 452.1fax +39.0371 – 452.222internet : http:/www.abb.com/it

    Notes

    These instructions describe high voltage technology products and are intended specifically for making known the use ofsuch products.These instructions are not intended to replace valid regulations, with regard to high voltage systems and equipment, andare intended for the use of specialists in the electrical field.

  • 8/9/2019 PASS Module Complete Manual - En

    19/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    1/19ABB S.p.A. PPD U.O. ADDA

    SF6 Gas System

    ORIGIN - FD217

  • 8/9/2019 PASS Module Complete Manual - En

    20/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    2/19ABB S.p.A. PPD U.O. ADDA

    INDEX

    1. GENERAL DESCRIPTION........................................................................................................ 31.1 Health and Safety ............................................................................................................ 31.2 Environment .................................................................................................................... 31.3 Properties......................................................................................................................... 41.4 Decomposition Produc ts ................................................................................................ 41.5 Safety Information ........................................................................................................... 51.6 Evacuation of the Gas Compartments .......................................................................... 51.7 Packing............................................................................................................................. 6

    1.8 Control of gas quali ty ..................................................................................................... 61.9 Control of the dielectric strength................................................................................... 61.10 Air Content ....................................................................................................................... 61.11 Filling pressure of SF6.................................................................................................... 61.12 Filling of SF6 gas (Fig.2)................................................................................................. 81.13 Instruct ion for molecular bags ..................................................................................... 10

    2. MAINTENANCE ...................................................................................................................... 102.1 Control of gas pressu re................................................................................................ 102.2 Control of humidi ty contained in gas.......................................................................... 10

    3. OPERATION ........................................................................................................................... 18Reproduct ion prohibited .............................................................................................................. 19 Address .......................................................................................................................................... 19Notes .............................................................................................................................................. 19

  • 8/9/2019 PASS Module Complete Manual - En

    21/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    3/19ABB S.p.A. PPD U.O. ADDA

    1. GENERAL DESCRIPTION

    This document contains a description of the general properties of sulphur hexafluoride (SF6) and the safety

    measures to be taken when handling SF6 as new and its decomposition products.Sulphur hexafluoride gas (SF6) is used in PASS modules for insulation and to suppress electrical arcing.

    1.1 Health and Safety

    Commercially available SF6  gas is non-hazardous, and is therefore not subject to the Ordinance forHazardous Materials, including the technical regulations for hazardous materials (TRGS). New SF 6  gascomplies with Regulation IEC 376. Regulation IEC 480 applies to used SF6 gas from the installation. Thelocal regulations and safety regulations, as well as those of the gas supplier and the manufacturer of theservice units must be observed.Chemically pure SF6 gas cannot be detected with the sensory organs, whereas decomposed SF6 gas has apungent smell, even in small concentrations. It can cause irritation of the eyes, mucous membrane, therespiratory system and other unprotected skin surfaces. After an electrical discharge (switching operations, arcing), SF6 gas will become more or less decomposed,

    depending on the amount of energy released. As a result, gaseous and solid decomposition products aregenerated together with evaporated contact material, such as:

    - Metal fluorides, metal sulphides and metal oxides- Sulphur fluorides, such as SF4- Sulphur oxy-fluorides, such as SOF2, SO2F2, SOF4.

    SF6 decomposition products generated from normal switching operations will be absorbed by the built-inabsorber (filter) and thereby present no health risk.If SF6 decomposition products are present, the following protective devices shall be worn:

    - disposable protective clothing- Fully-protective breathing mask or breathing equipment (does not protect from a shortage of

    oxygen!), combined with close-fitting industrial goggles.- Disposable protective gloves.

    The protective equipment must be stored in an accessible location in rooms away from the installation.Density of Sulphur Hexafluoride gas (SF6) is approximately five times higher than the one of air. It can get

    collected in containers or low-lying rooms and replaces the oxygen. The maximum permissible concentrationof SF6 gas in the work room is 1000 ppm (by volume). There is a danger of asphyxiation if the ventilation isinadequate!Concentrations of SF6 in the air in excess of 35 % vol. lead to oxygen lack and possible suf focation.Such high concentrations may occur in open, non ventilated SF6 gas compartments, andoccasionally at low po ints of a bui lding (e. g. in basements and cable ducts).When working with SF6  gas, ensure that the working room is kept clean and well ventilated(extractor, blower). NO SMOKING, EATHING OR DRINKING!!

    1.2 Environment

    SF6 in the atmosphere contributes to global warming, thus the release of SF6 into the atmosphere must beavoided whenever possible; every treatment of the gas must take place in a closed loop.The commercially available gas service and filtering devices allow full recycling of SF6. In this way you willensure that the contribution to the greenhouse effect remains negligible.Do not release SF6 in the atmosphere.SF6 shall be handled in a closed loop with su itable SF6 service devices and by trained personnelonly.

  • 8/9/2019 PASS Module Complete Manual - En

    22/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    4/19ABB S.p.A. PPD U.O. ADDA

    1.3 Properties

    During normal operation the gas compartments are filled with SF6 gas. SF6 is an un-reactive and nearly inert

    gas with a dielectric strength of approximately three times the one of air. At identical pressures, SF6 has three to four times the arc quenching capability of air.In the meantime more than 30 years of operational experience with SF6-gas insulated switchgear have beengathered worldwide.SF6 is (Table 1.4-1):

    un reactive

    un poisonous

    non flammable

    colourless

    odourless

    nearly inert

    New SF6 is delivered as liquefied gas in steel bottles. For testing and gas analysis of SF6 please refer to IECrecommendation 376 „ Specification and acceptance of new Sulphur Hexafluoride (SF6) “.The return of SF6 gas is contractually regulated with the original suppliers. If requested by the customer, ABB will guarantee the return of the SF6 in strict accordance with the respective regulations.

    Technical Data of commercial SF6

    SF6

    Gas density at 20 °C kg/m3  6,07

    Specific weight 20 °C g / l 6,07

    Melting point °C - 63,7

    Boiling point °C - 51

    Water solubility per cm3 H2O cm

    3  0,0054

    Colour - Colourless

    Odour - Odourless

    1.4 Decomposition Products

    The switching of rated and short circuit currents and internal arcing faults partially decomposes the SF6 intogaseous and/or solid decomposition products.Gaseous decomposition products give some warning signs even at low concentrations; such signs appearwithin seconds and before causing any hazardous impact:

    Unpleasant pungent odourIrritation of nostrils, mouth and eyes

    These signs leave enough time for any personnel to leave the area before danger to health can arise.Decomposition products of SF6 can cause irritation of ski n, eyes and mucous membranes (“SafetyInformation”)!

    Paying attention to the following safety information eliminates the potential risks associated with handlingSF6 and its decomposition products.

  • 8/9/2019 PASS Module Complete Manual - En

    23/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    5/19ABB S.p.A. PPD U.O. ADDA

    1.5 Safety InformationWhen handling SF6 and its decomposition products the following safety measures shall be taken:Good Ventil ation. Ventilate the room during maintenance works on the gas compartments (e. g. evacuating,filling, opening and cleaning). For maximum safety, it is advisable to have a second person present during allworks. Avoid Contact wi th Decompos it ion Produc ts . Avoid contact, swallowing or inhaling of decompositionproducts when working on open gas compartments. Wear special protective clothing while working, such asplastic gloves, safety goggles and filtering mask, and properly dispose of them after completion of the works.Thorough Cleaning o f Eyes and Skin . After contact with decomposition products immediately rinse withsoap and plenty of water. Thoroughly clean face, neck, arms and hands with soap and plenty of water beforeany interruptions and after completion of the works. In case the eyes have been exposed to decompositionproducts, immediately rinse them with an aseptic solution (e. g. commercial NaCl solution). Consult a doctorin any case. Avoid d is turbing of dust depos its. Remove persistent solid decomposition products with a clean, dry cloth.Remove loose dust with a suitable vacuum cleaner with paper filters. The vacuum cleaner should work onthe cyclone principle.Used materials, single use suits, moisture filters of the gas compartments, filters of the vacuum cleaner, themasks and the service devices and all decomposition products and cleansers have to be disposed of in sucha way, that decomposition products and the water soluble fluorides contained therein will not be releasedinto the environment.Do not open the filter bags. If the waste can not disposed by a specialist, neutralize it in a soda lime solution(natrium hydroxide and calcium oxide).Wear Protective Clothing. When entering gas compartments that may contain toxic decompositionproducts (“Decomposition Products”), wear a dust-tight overall, protective gloves and boots, cover your headand use a suitable respirator (separator, e. g. Auer 3S with combination filter 89 ABEK 2Hg/St. or, if asufficient oxygen concentration has been measured, a filtering device).Do not Eat, Drink o r Smoke. Do not drink, eat, smoke or store food in any room with open compartmentsthat may contain decomposition products.Leave Contaminated Rooms. If an unpleasant pungent odour (similar to hydrogen sulphide) indicates thepresence of gaseous decomposition products, leave the room immediately. Do not enter the room beforehaving thoroughly ventilated it, or without wearing a suitable respirator.Check Oxygen Concentration. After faults, when potentially hazardous SF6 concentrations are to beexpected, do not enter the switchgear room and all rooms at a lower level before thoroughly ventilating themand measuring the present oxygen contents (minimum 17 vol.%), or without wearing a suitable respirator.Your local ABB Service will be happy to assist you with any problems related to reusing, cleaning ordisposing of SF6.

    1.6 Evacuation of the Gas Compartments

    The enclosure of the inducti ve voltage transformers must not be opened or evacuated withou t the

    prior consent of the manufacturer!If a gas compartment is evacuated after a long period of operation, the SF6 has to be thoroughly filtered.Gas Compartments:PASS consists of several individual gas compartments that are separated by means of gastight barrierinsulators.Each gas compartment is equipped with its own gas density relay and a gas fitting of Malmkvist-type forworks on the gas compartment. Both, the gas and the density relay fittings, have a non-return valve toprevent unintentional gas losses.Prior to filling it with SF6, a gas compartment has to be evacuated. The pressure in the gascompartment shall be measured with a sensitive pressure gauge.

  • 8/9/2019 PASS Module Complete Manual - En

    24/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    6/19ABB S.p.A. PPD U.O. ADDA

    Delivery:

     All gas compartments are delivered filled with SF6 at reduced pressure of approximately 0.03 MPa rel.

    1.7 Packing

    SF6  is delivered under pressure, in the liquid state at room temperature and is steel vessels (bottles,spheres, cylinders, etc.). The gas mass held in a vessel range from 3 to 500 kg; the maximum filling densityis 1.04 kg/dm

    3.

    1.8 Control of gas quality

    The quality of the gas SF6 can be tested using chemical and physical measurements stated by the IECRecommendation. These measurements generally require sampling and laboratory instruments thatguarantee a high accuracy in the measurement. However, it is possible to carry out some quality tests bothon the gas available on the market and on the operating gas using simple instruments.

    1.9 Control of the dielectric strengthThe dielectric strength is a basic characteristic of the SF6. The control of this strength makes theidentification of the gas possible and ensures that the gas can guarantee its function as an insulator. Thedielectric strength can be easily measured with a cell equipped with a spark gap that is fed by a high voltagegenerator.

    1.10  Ai r ContentOnly a considerable amount of air mixed in with SF6 will impair the dielectric strength of the SF6. The smallcontent of air allowed in the pure SF6 has no effect on the dielectric strength.Besides that, the treatments preceding the filling of SF6, when putting the equipment into service, leave asmall residual amount of air that has no influence on the characteristics of the gas. However, it is possible to

    check whether all the air has been removed before filling the enclosures with SF6, or whether, after amaintenance process in which the SF6 has been recovered, a casual intake of air (for instance in pipes) hasallowed a penetration of air in the SF6.Two methods are possible:

    - IEC method:chromatography in the gaseous state;

    analyser that measures the paramagnetic susceptivity of oxygen;

    - Quick method:

    measurement of the dielectric strength of gas with a suitable test cell.

    1.11 Filling pressure of SF6Filling pressure with SF6The rated filling pressure of the SF6 has been established at a Pn value, at 20°C temperature value and atsea level atmospheric pressure.It is necessary to adjust the pressure as a function of the actual temperature and/or adjust the pressure P2as a function of the altitude.

    Filling pressure as a function of temperatureThe filling pressure at 20°C for each compartment is shown on the specific layout drawing.For different temperatures the pressure shall be set acc. table 1.

  • 8/9/2019 PASS Module Complete Manual - En

    25/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    7/19ABB S.p.A. PPD U.O. ADDA

    Tab. 1. Filli ng pressure as a funct ion of temperature

  • 8/9/2019 PASS Module Complete Manual - En

    26/200

  • 8/9/2019 PASS Module Complete Manual - En

    27/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    9/19ABB S.p.A. PPD U.O. ADDA

    Warning: COMPARTMENT ONLY, NOT FOR VT FILLING

     At the end of the filling operation:close the cylinder valve (8) on the bottle (9);remove the hose (12) from the valve (6) and place the cap (5), on the latter;

    remove the pressure gauge (3) from the valve (2) and close with the cap (1), on the latter;check the seal of the valves (2 and 6) with the leak detector.

    LEGEND:

    1. cap2. valve

    3. pressure gauge4. nut5. cap6. filling device DILO DN87. regulation valve8. cylinder valve9. bottle10. H.P. gauge11. L.P. gauge12. hose13. hose valve14. non-return valve15. hose coupling16. nut17. instrument case

    Fig. 2. Filling of SF6 gas

  • 8/9/2019 PASS Module Complete Manual - En

    28/200

  • 8/9/2019 PASS Module Complete Manual - En

    29/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    11/19ABB S.p.A. PPD U.O. ADDA

    Fig. 3. Saturated steam pressure of SF6

  • 8/9/2019 PASS Module Complete Manual - En

    30/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    12/19ABB S.p.A. PPD U.O. ADDA

    Fig. 4. Pressure-Temperature diagram with constant specifi c weight

  • 8/9/2019 PASS Module Complete Manual - En

    31/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    13/19ABB S.p.A. PPD U.O. ADDA

    Fig. 5. Disruptive voltage of SF6, air and carbon d ioxide as a function of pressure.

  • 8/9/2019 PASS Module Complete Manual - En

    32/200

  • 8/9/2019 PASS Module Complete Manual - En

    33/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    15/19ABB S.p.A. PPD U.O. ADDA

    Fig. 7. Adjustment of filli ng pressure as function of altitude

  • 8/9/2019 PASS Module Complete Manual - En

    34/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    16/19ABB S.p.A. PPD U.O. ADDA

    Fig. 8. Absorption capacity of molecular bags

  • 8/9/2019 PASS Module Complete Manual - En

    35/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    17/19ABB S.p.A. PPD U.O. ADDA

    Fig. 9. Treatment process on each compartment

  • 8/9/2019 PASS Module Complete Manual - En

    36/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    18/19ABB S.p.A. PPD U.O. ADDA

    Fig. 10. Maintenance

    3. OPERATION

    WARNING: Do not operate the circuit b reaker at low p ressur e of 0.02-0.03 MPa at 20°C.Only operate when the pressure is 0.5 MPa relative (20°C)

  • 8/9/2019 PASS Module Complete Manual - En

    37/200

     

    Doc. 2GJA700294Rev. A

    Type of DocumentManual

    TitleSF Gas System

    19/19ABB S.p.A. PPD U.O. ADDA

    NOTES

    If you have some comments we kindly ask You to write that here below and send us this page back.

    Thank You for your collaboration.

    Copyright

    We reserve all rights concerning this document and the components described therein. It must not bereproduced or disclosed to thirdparties and the contents must not be made use of neither in part or in whole without our prior writtenpermission.© ABB Italy S.p.A., Division High Voltage ProductThe information in this document is subject to alteration without prior notice and should not be regarded asan undertaking from ABB S.p.A. - Power Products Division – U.O. Adda-HV ABB S.p.A. - Power Products Division – U.O. Adda-HV takes no responsibility for errors that can occur inthe documentation. ABB S.p.A. - Power Products Division – U.O. Adda-HV is not responsible for damage incurred due to themisuse of this document.

    Reproduction prohibited

    By law, we remain the owners of this document. Under no circumstances may it be reproduced, handed overor disclosed to competitor companies or to third parties without our written authorisation.

    © ABB S.p.A. - Power Products Division – U.O. Adda-HV

     Address

     ABB S.p.A. -PPD U.O. AddaVia dei Ceramisti26900 Lodi – Italytel. +39.0371 – 452.1fax +39.0371 – 452.222internet : http:/www.abb.com/it

    Notes

    These instructions describe high voltage technology products and are intended specifically for making knownthe use of such products.These instructions are not intended to replace valid regulations, with regard to high voltage systems andequipment, and are intended for the use of specialists in the electrical field.

  • 8/9/2019 PASS Module Complete Manual - En

    38/200

  • 8/9/2019 PASS Module Complete Manual - En

    39/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    2/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    INDEX

    Item Subject Page

    1 GENERAL INFORMATION 41.1 Components 4

    1.2 BLK 82 4

    1.31.4

    BLK 222 4BLK Optional Equipment 4

    2 MAIN COMPONENTS AND EQUIPMENT 82.1 Operating device cubicle 8

    2.2 Driving Mechanism 9

    2.2.1 Driving Mechanism without cubicle 9

    2.2.2 Operating Mechanism 102.2.3 Driving Mechanism sectioned through drive shaft 11

    2.2.4 Driving Mechanism operations 11

    2.3 Electrical Equipment 13

    3 OPERATION 143.1 Normal Operation 14

    3.1.1 Remote/Local operations from control room control panel 143.1.2 Closing Operation 143.1.3 Opening Operation 14

    3.1.4 Rapid auto-re-closing operation 153.2 Charging the closing spring 16

    3.2.1 Motor powered charging 16

    3.2.2 Manual charging and discharging of the spring control drive 163.3 Discharging the closing spring 22

    3.3.1 Discharge by command 223.4 Interlocking system 22

    3.5 Heating 22

    4 MAINTENANCE 224.1 General 224.2 Lubrication 224.3 Actions after periodic inspection 22

    4.4 Faults during operation 234.5 Analysis of deviations or faults 234.6 Overhaul of operating device 24

    4.6.1 Preparation 244.6.2 Change of OPENING or CLOSING catch gear 25

    4.6.3 Replacing catch gear in zero voltage condition 264.6.4 Replacing of coil in the OPENING or CLOSING catch gear 27

    4.6.5 Replacing of motor 284.6.6 Replacing of shock absorber 29

    4.6.7 Checks and reconnection 30

    5 TESTING AND RESTART AFTER OVERHAUL 31

    6 NECESSARY EQUIPMENT 31

    6.1 Lifting tools and equipment 316.2 Cleaning and lubricating equipment 31

    6.3 Testing equipment 31

    6.4 Locking liquid for threads 31

    7 OPTIONAL EQUIPMENTS 317.1 Manual operating device 317.2 Opening block 34

    8 VARIANT EQUIPMENT 368.1 Inductive limit switch 368.2 Snap action switches limit switch 38

     APPENDIX A 39

  • 8/9/2019 PASS Module Complete Manual - En

    40/200

  • 8/9/2019 PASS Module Complete Manual - En

    41/200

  • 8/9/2019 PASS Module Complete Manual - En

    42/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    5/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    During assembling and transport, the closing spring of control device must bedischarged. Discharged condition is shown by the color signs from the window (Figure

     A.1).

    Do not operate the control device before it has been coupled and adjusted to the circui t breaker andthe circui t breaker has been filled with gas, to full service pressure.

    Fig. A.1Back cover of BLK for manual

    charge of closing spring

    Fig. A.1Window under cover of BLK

  • 8/9/2019 PASS Module Complete Manual - En

    43/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    6/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    Fig. A.1.1 Descript ions of spri ng posit ion

    Fig. A.1.2 Descript ions of spri ng posit ion

    MANUAL SPRINGCHARGE

     ACCESS COVER

  • 8/9/2019 PASS Module Complete Manual - En

    44/200

  • 8/9/2019 PASS Module Complete Manual - En

    45/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    8/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    2. MAIN COMPONENTS AND EQUIPMENT

    2.1 Operating Device Cubicle (Fig. C)The control cubicle is heat proof. The centralised control cubicle has an internal pocket to hold the circuitdiagram and product information.

    Fig. C Legend:1. Cover2. Locking handle3. Mechanical limit switch with contacts4. Window5. Contact which breaks the motor circuit when the cubicle is opened6. Auxiliary contacts

    Fig. C. Operating Device Cubicle

  • 8/9/2019 PASS Module Complete Manual - En

    46/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    9/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    2.2 Driving Mechanism

    2.2.1 Driving mechanism withou t cubicle (Fig. D)Legend:

    1. OPEN latch2. CLOSE latch3. Operating arm

    4. Opening damper5. Auxiliary contacts6. Limit switch contacts8. Frame9. Closing spring (spiral spring)10. Spring container (drum)11. Driving Unit12. Motor, spur gears transmission and worm gears transmission13. Control pull-rod to circuit-breaker

    14. Zero voltage trip latch

    Fig. D. Driving mechanism without cub icle

  • 8/9/2019 PASS Module Complete Manual - En

    47/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    10/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    The auxiliary equipment is characterized by the following main components:

    -  robust auxiliary contacts and limit switches;

    -  indication of charged, partly charged or discharged closing spring.

    The housing  of the spring operating mechanism is characterized by the following feature:

    -  corrosion resistant housing of painted aluminium.

    2.2.2 Operating Mechanism (Fig. E)

    The Circuit Breaker is in a closed position with the closing spring charged.The Circuit B reaker opening spring is always charged when the circuit b reaker is c losed.

    Fig. E Legend

    1. OPEN latch2. CLOSE latch3. Operating arm4. Carrier5. Auxiliary contacts6. Drive auxiliary contact7. Opening Damper8. Control pull-rod to circuit-breaker9. Shaft for manual charging of spring10. Brake for discharging spring

    11. Transmission with worm gears12. Transmission with spur gears13. Motor14. Zero voltage trip latch (optional)

    Fig. E. Operating Mechanism

  • 8/9/2019 PASS Module Complete Manual - En

    48/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    11/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    2.2.3 Driving mechanism sectioned through dr ive shaft (Fig. F)

    Fig. F Legend1. Frame2. Driving shaft3. Control arm4. Carrier splined to driving shaft5. Spring container (drum)6. Closing spring (spiral spring)7. Motor8. Transmission with worm gears9. Transmission with spur gears10. Control pull-rod to Circuit Breaker

    Fig. F. Driving mechanism. Section through drive shaft

    2.2.4 Driving mechanism operations (Fig. G)

    Position 1:Circuit breaker in CLOSED position.

    Closing spring charged.Opening spring charged.

  • 8/9/2019 PASS Module Complete Manual - En

    49/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    12/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    Position 2:Circuit breaker in OPEN position.The damper has damped the circuit breaker’s contactmovement.The damper is in OPEN position at the end stop.Closing spring charged.

    Position 3:Circuit breaker after closing, prior to spring charging.Support 4 and catch dog 41 are free from Arm 5 and fromcatch dog 51. The damper piston is fully extracted and isready for an opening operation. The motor starts and re-charges the closing spring, after which position 1 isreached and the operating device is ready for a new closingoperation.

    Fig. G. Driving mechanism operations

  • 8/9/2019 PASS Module Complete Manual - En

    50/200

  • 8/9/2019 PASS Module Complete Manual - En

    51/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    14/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    3. OPERATION

    3.1 Normal Operation3.1.1 Remote/Local operations from the contro l room control panel

    The selector switch, located in the control cubicle, allows to select the control mode.The local position enables the opening and closing buttons located in the control cubicle.

    3.1.2 Closin g operation

    The following conditions must be satisfied to perform a closing operation using the push-button, or remoteelectric impulse:

    -  Selector switch must be in the remote or local position.-  Closing operation spring must be fully charged.-  The Circuit Breaker must be in the OPEN position.-  The gas density must be higher than the locking level.

    3.1.3 Opening operation (Fig. I)Opening can be performed locally with the Circuit Breaker in the CLOSED position, with the selector switchin the local position and by activating any one of the opening coils using the relevant push-button.If the control is equipped with a zero voltage opening coil operation Y3 (Fig. H) this may be de-activated byloosening screws (1) and moving plate (2) against the mobile anchor (3) to prevent the spring action. Thenre-tighten screws 1.

    WARNING: ensure when performing either 3.1.2 or 3.1.3 (above) that Y3 is mechanicallyde-activated or energized with the circuit breaker in the opening position and the closingspring discharged.

    Fig. I Legend

    1. Nut2. Clamping Plate

  • 8/9/2019 PASS Module Complete Manual - En

    52/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    15/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    Fig. I Zero Voltage opening operation coil

    3.1.4 Rapid auto re-closing operation

    The automatic rapid re-closing operation OPEN-0.3s-CLOSE-OPEN can be performed in the followingconditions:

    -  The Circuit Breaker is in the closed position.-  The closing spring in the operating device is fully charged when the operating cycle starts.

    Since the control circuits are interlocked using the auxiliary contact S1 (fig.H), a closing operation will alwaysbe finished before an opening operation starts.

  • 8/9/2019 PASS Module Complete Manual - En

    53/200

  • 8/9/2019 PASS Module Complete Manual - En

    54/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    17/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    -  Insert the crank in the “discharging side” and charge the spring by turning counterclockwise until thezero voltage is reaching.

    -  Once the yellow and white bars are aligned, extract the crank, turn and re-insert it in the “chargeside” and insert it, side charge.

    -  Position the support guide. Pushing to beat the guide supports against the nut A (Fig. L.3).

    Fig. L.3

    -  Turn the crank counterclockwise (view from under drive BLK), until the guide support reaches thenuts B (Fig. L.4).

    Nut A

    SupportGuide

  • 8/9/2019 PASS Module Complete Manual - En

    55/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    18/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    Fig. L.4

    -  At the end, check that the red bar is lined up to the white bar (Fig. L.5).

    Fig. L.5

    Nut BSupportguide

    Red bar onthe spring

    frame

    White bar onthe BLK

    support

  • 8/9/2019 PASS Module Complete Manual - En

    56/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    19/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    -  Without overshoot it (Fig. L.6)

    Fig. L.6

    -  In the case described above, discharge the spring until white and red bars are aligned (Fig. L.5).This is the last operation possible using the crank side discharge (Fig. L.7).

    Fig. L.7. Terminal end of crank, to disch arge the closing spr ing of BLK

  • 8/9/2019 PASS Module Complete Manual - En

    57/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    20/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    Utilization of the crank for manual di scharge- Switch off the motor protection F1 in the control cubi cle;-  Switch off auxiliary voltage of control circuit;

    -  Open the back cover (Fig. A.1);-  Insert the crank (fig. L.8) into hexagonal socket and press the button (2); discharge the spring by

    turning the crank with clockwise rotation (view from bottom), pay attention to relieve the spring.

    Fig. L.8

    Terminalend of the

    crank, todischargethe closingspring ofBLK

  • 8/9/2019 PASS Module Complete Manual - En

    58/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    21/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    -  Totally discharged spring is indicated when the roller releases the drive, (fig. M)-  And the spring charge indicator shows that the spring is fully discharged.

    NOTE: Bu tton 2 (Fig. L.8) must be pressed

    WARNING: Never release brake 2, until the manual di scharge process i s complete

    WARNING: MANUAL DISCHARGING REQUIRES ATTENTION.THE ACTING TORQUE, IF NOT PROPERLY SUPPORTED, CAN RESULT IN

    DANGEROUS FAST ROTATION OF THE HAND CRANK.

    Fig. M. Discharged spring

  • 8/9/2019 PASS Module Complete Manual - En

    59/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    22/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    3.3 Discharging the closing spr ing

    IMPORTANT: Always discharge the closing sp ring befo re starting maintenance work onthe Circuit B reaker or on the operating d evice.

    3.3.1 Discharge by command

    -  Switch off the motor protection switch F1 in the control cubicle.-  Position selector switch in the control cubicle to local.-  Perform a sequence of OPEN-CLOSE-OPEN operations.-  Check the position of spring means color signs from window, under drive cover (A.1).

    3.4 Interlocking system

    The following electrical interlocks are installed in the centralized control cubicle and in the control device.

    Closing circuit: (to be read in conjunction with schematic diagram)

    -  The closing impulse, which passes through the NC auxiliary contact (closed when the CircuitBreaker is open) only reaches the closing coil Y4 if the Circuit Breaker is open.

    -  The closing impulse reaches the closing coil Y4 by passing through a spring charging limit switchcontact which is closed only when the spring is charged.

    -  The closing impulse is stopped if the SF6 gas density is lower than the blocking level during anyphase.

    -  A prolonged closing impulse is interrupted by the anti-pumping relay after the closing operation hasbeen completed.

    Motor circuit:

    -  Microswitch S4 interrupts the motor circuit when the cover is open.

    3.5 HeatingEnergize the heater by closing the heating circuit protection switch in the control cubicle.

    1. MAINTENANCE

    1.1 General

    Refer to “PREVENTIVE MAINTENANCE GUIDE”.

    1.2 Lubrication

    Lubricate latch (1) and latch (2) (Fig. E) using grease L after 2.000 operations. (See appendix A at the end ofthis manual).

    1.3  Actions af ter periodic inspection

    Faults and anomalies, as well as deviations from functional values noted during periodic inspections can becorrected, for example, by cleaning, tightening, adjusting or lubricating, or may be regarded as more seriousand require corrective maintenance. This maintenance does not require immediate intervention, but can bescheduled for an appropriate time.

  • 8/9/2019 PASS Module Complete Manual - En

    60/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    23/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    1.4 Faults during operation

    Faults that occur during operation and that can cause the Circuit Breaker to breakdown must, as a rule, be

    corrected immediately. Before adequate measures can be taken, the type of fault and its possible causemust first be analyzed.

    1.5  Analysis of deviat ions or faul ts

    Type of fault Possible reason for anomalyor fault

    Corrective measure in order of prior ity

    1. Operation timestoo long at CLOSEand OPENoperations.

    -  Control voltage too low-  Catch gear sticks

    -  Check control voltage.-  Check the minimum control voltage. If this exceeds

    the original value by more than 20%, the catchgear must be checked and if necessary, lubricatewith grease “L”.

    2. Minimum controlvoltage too high

    -  Catch gear sticks -  Check catch gear-  Lubricate with grease “L”

    3. Time differencesbetween poles-  Deviation in some operatingdevice at single pole

    operation.-  Link system loosened.-  Worn arcing contacts.

    -  Check catch gear

    -  Lubricate with grease “L”.-  Comply with circuit-breaker fault analysis

    4. Circuit-breakerdoes not operate atimpulse to OPEN

    -  No control voltage

    -  Open control circuitinterrupted

    -  Control circuit interrupted-  Opening catch gear sticks

    -  Check position of selector switch located in thecentralised control cubicle

    -  Check control voltage-  Check the pressure/density gauge 63GB-  Check the blocking relay K3, K2-  Check control circuit-  Check opening catch gear

    5. Circuit-breaker

    does not operate atimpulse to CLOSE

    -  No control voltage

    -  Closing impulse blocked

    -  Catch gear sticks

    -  Gas pressure too low

    -  Check position of selector switch located on

    centralised control panel-  Check control voltage-  Check pressure/density gauge 63GB-  Check blocking relay K3-  Check control circuit-  Check spring closing limit switches S2, S3-  Circuit-breaker control circuit-  Check catch gear-  Lubricate with grease “L”-  Closing spring discharged

    -  Check that switch F1 is on-  Check the motor contactor KM-  Check micro switch S4-  Check motor voltage-  Refill gas

    6. Circuit-breakeroperates withoutimpulse to CLOSEor OPEN

    -  Short-circuit or connectionfault in control circuit

    -  Worn or broken catch gear

    -  Check control circuit according to circuit diagram

    -  Test insulation-  Check and change catch gear

    7. Circuit-breakerdoes not remain inCLOSED position atclosing operation

    - worn or broken catch gear 

    -  Opening spring isovercharged

    -  Closing spring isinsufficiently charged

    - Check opening catch gear 

    -  See note 1 below

    -  See note 1 below

  • 8/9/2019 PASS Module Complete Manual - En

    61/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    24/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    Type of anomaly orfault

    Possible reason foranomaly or fault

    Corrective measures in order of prio rity

    8. Circuit-breakercloses againimmediately after a

    CLOSE-OPENoperation

    -  Faulty anti-pumping relay -  Check control circuit-  Check anti-pumping relay

    9. Faulty dampingtime

    -  Oil leak in shock absorber-  Shock absorber sticks

    -  Check shock absorber and replace if necessary

    10. Charging timetoo long and motorcurrents too highgreater than 15seconds.

    -  Excessive friction in wormgear

    -  Electric fault in motor

    -  Check oil level in the gear-  Check control voltage

    -  Change motor

    11. Motor does notstart at closing

    operation

    - Motor protection tripped-  No motor voltage

    -  Fault in limit switchcontact BW

    - Check protection switch F1-  Check micro switch S4

    -  Check contactor KM-  Check contact S2 - S3

    12. Motor does notstop at fully chargedspring

    -  Electric fault in motorcircuit

    -  Check motor contactor KM-  Check contact S2 – S3

    13. Ice orcondensate in theoperating device

    -  Heater does not function -  Check heater operation R1

    Table.1. Analysis o f deviations or faults

    1) The Circuit Breaker does not remain in the closed position.This may be due to insufficient energy provided by the closing spring due to an insufficient charge or to

    an overcharge of the opening spring.Spring adjustments must be performed by our fully trained ABB SERVICE personnel.

    1.6 Overhaul o f operating device

    1.6.1 Preparation

    Read these instructions before opening the control device and follow the instructions during overhaulingoperations. All the applicable Electrical Industry Safety Regulations shall be strictly followed.

    WARNING: Carry o ut the OPEN operation, disconnect and earth the Circuit Breaker’s highvoltage connections. Interrupt the control voltage, moto r voltage and where appli cablealso the heater voltage before working on the contro l device. Discharge the closingspring.

    Overhauling can be carried out on site with the control device mounted on the Circuit Breaker. All essentialcomponents can be dismantled for checking or replacement, if necessary.

  • 8/9/2019 PASS Module Complete Manual - En

    62/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    25/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    1.6.2 Change of OPENING or CLOSING catch gear (Fig. N)

    Fig. N Legend1. Electromagnet2. Armature3. Spring4. Pin5. Auxiliary catch6. Intermediate catch7. Spring8. Pin9. Bearing10. Roller11. Main catch12. Roller13. Spring

    14. Bearing15. Shaft16. Catch holder17. Screw M5x2018. Screw M8x70 (torque 50Nm)

    Fig. NReplace the complete OPENING or CLOSING device by loosening the screws M18. Use the same screwswhen assembling the new catch gear.

  • 8/9/2019 PASS Module Complete Manual - En

    63/200

  • 8/9/2019 PASS Module Complete Manual - En

    64/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    27/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    1.6.4 Replacing coil s in OPENING or CLOSING catch gear

    Dismantle the electromagnet first by loosening screws M17 from the catch gear.

    Fig. P Legend1. Screw M6x302. Locking nut M63. Coil4. Armature5. Spring6. Support plate7. Arm8. Washer9. Pin10. Magnet core

    Fig. P

    Replace coil as follows:

    Loosen locking nut (2) and remove screw (1).

    Pull the support plate (6), including the armature and coil, upwards and to the side as indicated bythe arrow in the figure.

    Replace the coil, re-assemble the components in their original positions.

    Press arm (7) downwards with force, using a screwdriver as shown in fig. Q, before tighteninglocking nut (2, fig. P) to make the air gap as small as possible.

  • 8/9/2019 PASS Module Complete Manual - En

    65/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    28/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    Fig. Q. Armature Adjustment

    Install the electromagnet in its seat on the catch gear (fig. N). The nominal gap between the

    electromagnet arm (2 fig. N) and the auxiliary catch (5 fig. N) is 1±0,1 mm. Tighten all screws (17 fig.N).

    Connect all coil wires.

    Re-assemble the OPENING and CLOSING catch gears in the control device.

    1.6.5 Replacing of motor

    Fig. R Legend1. Motorized charging device2. Motor3. Screw M8x40 (Torque 50 Nm)4. Carrier5. Roller on close latch

    Fig. R. Driving mechanism, fron t

  • 8/9/2019 PASS Module Complete Manual - En

    66/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    29/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    Isolate control device according to relevant Electrical Industry Safety Regulations

    Remove the operating device cover.

    Discharge the closing spring completely. The spring symbol is green to indicate the spring isdischarged.

    Bring carrier (4 fig. R) in contact with roller (5 fig. R) by manually cranking in the direction of chargingthe closing spring.

    Loosen the two screws (3 fig. S) holding the motor.

    Disconnect the motor and lift it out.

    Install the new motor using the same screws. Tighten screws (3 fig. S).

    Connect the electric wires to the motor.

    Fig. S Legend1. Motor2. Screw M6x70 9.6 Nm

    3. Screw M6x75 9.6 Nm4. Washer 6.4x12x1.5

    Fig. S. Motor ized charging device

  • 8/9/2019 PASS Module Complete Manual - En

    67/200

  • 8/9/2019 PASS Module Complete Manual - En

    68/200

  • 8/9/2019 PASS Module Complete Manual - En

    69/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    32/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    Fig. U Legend

    1. Push button

    support2. Push buttons4. Lever5. Pin6. Pin13. Ring22. Adjustment23. Bushing24. Cable clamp25. Fitting screws30. Roller plate31. Spring

    32. Frame33. Trip lever40. Closing lever

    *)  Adjust the length of wire of the OPENING-CLOSING devices: DO NOT TOUCH items shown in Pos.3).

    Fig. U. Position 1, Position 2, Position 3.

  • 8/9/2019 PASS Module Complete Manual - En

    70/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    33/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    Fig. U4 An action on closing push button (2 fig. U) (pos. 1-2) rotates the lever (4 Fig. U) and, consequently, the wireis pulled. This turns the roller plates (30 fig. U) that rotates the closing lever (40 fig. U) (pos. 4), with littleeccentric motion that is transmitted to the pin (U pos 4) in the same way. The auxiliary catch moves andreleases the intermediate catch that lets the main catch move; the carrier is free to rotate. This starts theclosing operation. The opening operation is similar.

    U4Main catch U4

    Closinglever U-40

    U4

    Pin

    U4 Auxiliarycatch

    U4Intermediatecatch

  • 8/9/2019 PASS Module Complete Manual - En

    71/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    34/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    4.2 Opening block

    The drive BLK can be equipped with a device, on request, for the Opening block (see figure V) (for

    calibration of this device the closing spring must be discharged and the breaker open).

    Fig. V Legend1. Support2. Transmission3. Transmission4. Lever5. Support6. Pin

    8. Block9. Micro switch10. Regulating screw15. Pin17. Screws18. Stop ring19. Padlock

    Fig. V. OPENING BLOCK device

    The drawing V represents the opening block device in BLOCK position: the OPEN operation of C.B. isprevented.

  • 8/9/2019 PASS Module Complete Manual - En

    72/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    35/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    With the support (1), (5) mounted, assemble the transmission (2) and fit it by the pin (15) (upper hole as inpicture).

    Pull the transmission (3), carrying up the block (8) against the auxiliary catch.In this position join together the transmissions (2) and (3).Make sure that the block (8) is pressed against the auxiliary catch.Verify that micro switch is pressed, eventually adjust the screws. After adjustment, with the device in BLOCKED position, the BLK device does not open when the coil isenergized.

    Fig. VWith the pin 15 in the upper holethe BLOCK 8 is against theauxiliary catch: Open operationis blocked. The transmission 2,3 can be locked by a padlock

    Fig. VWith the pin 15 in the lower holethe BLOCK 8 is not against theauxiliary catch: OPEN operationis possible. The transmission 2, 3can be locked by a padlock.

  • 8/9/2019 PASS Module Complete Manual - En

    73/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    36/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    5. VARIANT EQUIPMENT

    6. Snap action switches limit switch

    To unify the design for each circuit breaker type inside the group a new limit switch was developed, testedand released for production.The new solution is based on micro switches acted by mechanical cammes placed on the main shaft and onthe indication disc (see picture below).The contacts for each camme are doubled so with the present solution we have a redundancy granting evena higher safety level than the actually used.

    Cam on the main shaft

    Micro switches

    Indication disc with cam

  • 8/9/2019 PASS Module Complete Manual - En

    74/200

    Doc.2GJ 700295Rev. A

    Typeof DocumentManual

    TitlBLK

    37/38ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

     APPENDIX A

    Grease “G”Low-temperature grease for all type of bearings, gearing and worm gears and valves in air-blast circuitbreakers. Also used for greasing sealing rings and crevice corrosion protection on breakers. Type HPL

    Grease “L ”Low temperature grease, especially suitable for lubricating precision components, such as latch mechanismoperating in very cold environment.

    Grease “M”Low temperature grease for long term and permanent lubrication of worm gears, and spur gears and othermachine elements. Counteracts wear and corrosion.

    SUPPLIER GREASE “ G” GREASE “ L” GREASE “ M”

     ABB art. No. 1171 4014-407 1171 4016-606 1171 4016-612

     ABB spare part No. 5316 318-A 5316 381-H 5316 381-J

     ASEOL AG - ASEOL SYLITEA 4-018 -

    Klüber Isoflex Topas NB 52

    GULF 718EP Synthetic grease - -

    MOBIL Mobil grease 28 - -

    SHELL Aero Shell Grease 223 - -

  • 8/9/2019 PASS Module Complete Manual - En

    75/200

  • 8/9/2019 PASS Module Complete Manual - En

    76/200

     

    Doc. n. 2GJA700296Rev. A 5/2008 [AI]

     

    Type of documentManual

    TitleBushing SF6/Air 145-170 kV

    1/5ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    BUSHING SF6/Air

    145-170 kV

  • 8/9/2019 PASS Module Complete Manual - En

    77/200

     

    Doc. n. 2GJA700296Rev. A 5/2008 [AI]

     

    Type of documentManual

    TitleBushing SF6/Air 145-170 kV

    2/5ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    INDEX

    1. GENERAL DESCRIPTION………………………………………………….page 31.1 Main Components page 31.2 Technical Data page 42. ERECTION & COMMISSIONING NOTES…………………………………page 43. MAINTENANCE……………………………………………………………….page 4

    CONTENTS OF FIGURE

    Fig. 1 Bushing Section…………………………………………………………page 3

    CONTENTS OF TABLE

    Tab. 1 Maintenance……………………………………………………………...page 4

  • 8/9/2019 PASS Module Complete Manual - En

    78/200

     

    Doc. n. 2GJA700296Rev. A 5/2008 [AI]

     

    Type of documentManual

    TitleBushing SF6/Air 145-170 kV

    3/5ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    1. GENERAL DESCRIPTION

    Overhead lines and Bus Bars are connected to the module by air bushings. The main insulation iscompressed SF6 gas. The insulator consists of an epoxy impregnated fibreglass tube with siliconrubbersheds. The flanges are heat shrunk and glued onto the tube making an extremely strongand gastight joint.The silicon rubber sheds are cast onto the tube and chemically bonded to it, thus allowing nomoisture orcontamination to enter between them. The silicon rubber sheds are hydrophobic andgive very good rain andpollution performance. The main features are:

    - High safety (crack and explosion resistant);- Low weight;- Excellent pollution and rain performance;- Sandstorm resistant;- Salty, tropical and polluted areas condition resistant;- Maintenance free.

    1.1 Main Components

    Bushings are composed of:

    Fig. 1 – Bushing section

    LEGEND:

    1. Reinforced cylinder made ofglass, aramid and polyesterendless fibres2. Base flange3. Lid4. Terminal5. Primary Bus Bar

    6. Silicone rubber

  • 8/9/2019 PASS Module Complete Manual - En

    79/200

     

    Doc. n. 2GJA700296Rev. A 5/2008 [AI]

     

    Type of documentManual

    TitleBushing SF6/Air 145-170 kV

    4/5ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    1.2 Technical data

    Bushings

    Type ........................................................................................... composite insulatorRated voltage .............................................................................145kV / 170 kV Arching distance ............... ......................... ..................... ............1304mm/1633 mmCreepage distance ......................................................................4670mm/5462 mmMax. permissible static mechanical force ...................................in accordo con la normativa IEC 62271-100

    2. ERECTION & COMMISSIONING NOTES

    Silicon bushing shall be protected, during transport, by means of 0,15 mm thick polyethylene bags.Bottom part shall be sealed with clamp and adhesive tape resistant to saline atmospheres and hightemperatures.

    WARNING: Never use any sharp tools during unpacking to avoid damages inbushing

    3. MAINTENANCE

    Silicon bushings can only be touched with clean protective gloves (plastic or rubber).For bushings which have been contaminated during transport or handling (greasy fingerprints orsooty gas exhaust, etc.) cleaning can be performed with different cleaning agents as follows:

    Contamination Level Cleaning Agent

    Slight contamination 5% watery solut ion of detergent

    Medium Contamination  Al iphatic hydrocarbons such as“ Rivolta M.T.X. 100)”

    Heavy Contamination  Acetone or t richloroethyleneTab. 1

     All cleaning has to be performed by penetrating the cleaning agent into a cotton cloth and wipingthe bushing with it. Before starting a qualification test, a recovery time after cleaning of minimum24 hours should be allowed for.

  • 8/9/2019 PASS Module Complete Manual - En

    80/200

     

    Doc. n. 2GJA700296Rev. A 5/2008 [AI]

     

    Type of documentManual

    TitleBushing SF6/Air 145-170 kV

    5/5ABB PT S.p.A. U.O. ADDAABB PT S.p.A. U.O. ADDA

    NOTES

    If you have some comments we kindly ask You to write that here below and send us this page back.

    Thank You for your collaboration.

    Copyright

    We reserve all rights concerning this document and the components described therein. It must not bereproduced or disclosed to thirdparties and the contents must not be made use of neither in part or in whole without our prior writtenpermission.© ABB Italy S.p.A., Division High Voltage ProductThe information in this document is subject to alteration without prior notice and should not be regarded asan undertaking from ABB S.p.A. - Power Products Division – U.O. Adda-HV

     ABB S.p.A. - Power Products Division – U.O. Adda-HV takes no responsibility for errors that can occur inthe documentation. ABB S.p.A. - Power Products Division – U.O. Adda-HV is not responsible for damage incurred due to themisuse of this document.

    Reproduction prohibited

    By law, we remain the owners of this document. Under no circumstances may it be reproduced, handed overor disclosed to competitor companies or to third parties without our written authorisation.

    © ABB S.p.A. - Power Products Division – U.O. Adda-HV

     Address

     ABB S.p.A. -PPD U.O. AddaVia dei Ceramisti

    26900 Lodi – Italytel. +39.0371 – 452.1fax +39.0371 – 452.222internet : http:/www.abb.com/it

    Notes

    These instructions describe high voltage technology products and are intended specifically for making knownthe use of such products.These instructions are not intended to replace valid regulations, with regard to high voltage systems andequipment, and are intended for the use of specialists in the electrical field.

  • 8/9/2019 PASS Module Complete Manual - En

    81/200

    Doc.2GJ 700297Rev. A

    Type of DocumentManual

    TitleSpare parts

    1/5ABB S.p.A. PPD U.O. ADDA

    SPARE PARTS

  • 8/9/2019 PASS Module Complete Manual - En

    82/200

    Doc.2GJ 700297Rev. A

    Type of DocumentManual

    TitleSpare parts

    2/5ABB S.p.A. PPD U.O. ADDA

    INDEX

    1. SET OF SPARE PARTS FOR OPERATION…….………………………………..pag. 4

    2. SPECIAL TOOLS, APPLIANCES AND SF6 GAS HANDLING EQUIPMENT…page 4

    3. LOGISTIC……..………………………………………………………………………page 4

    3.1 Information for ordering page 4

    4. EXPANDABLE AND AUXILIARY MATERIAL…..……………………………….page 5

    4.1 SF6 insulating gas page 5

    4.2 Cleaning material page 5

    4.3 Cleaning Agents page 5

    4.4 Greases and oils page 5

    4.5  Adhesives page 5

    5. TOOLS AND EQUIPMENT…………………………………………………………page 5

    5.1 Standard tools page 5

    5.2 Special tools page 5

    5.3 Equipment page 5

    CONTENTS OF TABLES

    Tab. 1 Set of Spare parts …..…………………………………………………page 4

    Tab. 2 Special Tools……………………………………………………………page 4

  • 8/9/2019 PASS Module Complete Manual - En

    83/200

    Doc.2GJ 700297Rev. A

    Type of DocumentManual

    TitleSpare parts

    3/5ABB S.p.A. PPD U.O. ADDA

    1. SET OF SPARE PARTS FOR OPERATION (NOT INCLUDED IN THE SUPPLY)(otherwise confirmed)

    Item Description Unit

    1 Drive mechanism (BLK 222 or/and 82) for circuit breaker 1

    2 Drive mechanism (BES7) for disconnector/earthing switch 1

    3 Drive mechanism (BES6) for disconnector FES (if present) 1

    4 Opening