1. UTILITY-OWNED POWER POLE. EXTEND PRIMARY RISER UP POLE PER UTILITY REQUIREMENTS. VERIFY ALL SERVICE REQUIREMENTS WITH XCEL REPRESENTATIVE PRIOR TO BEGINNING ANY ELECTRICAL WORK. CONTACT DANIEL HOLMES, XCEL ENERGY, PH. 575-391-3307. 2. EXTEND PRIMARY DUCT TO SERVICE POLE PER UTILITY REQUIREMENTS. 3. UTILITY-OWNED SERVICE TRANSFORMER WITH 208/120V, 3-PHASE SECONDARY. 4. CONCRETE TRANSFORMER PAD (BY G.C.) PER UTILITY REQUIREMENTS. 5. 1200A SERVICE FEEDER. PARALLEL RUN OF FOUR 3" CONDUITS EACH WITH 4 #350KCMIL CU. 6. FIELD VERIFY EXACT LOCATION OF METER BANK. PROVIDE SCALED SKETCH OF METER BANK LOCATION ON EXTERIOR WALL TO ARCHITECT FOR APPROVAL PRIOR TO ROUGH-IN. 7. ONE #3/0 BSD COPPER SERVICE GROUND IN 3/4" CONDUIT. REFER TO SERVICE GROUNDING SYSTEM DIAGRAM. PROVIDE 250KCMIL CU BONDING JUMPERS. 8. NOT USED. 9. SIEMENS MODULAR MAIN SERVICE DISCONNECTING MEANS, 1200A MCB, 240V, NEMA 3R ENCLOSURE. 10. NOT USED. 11. SIEMENS 4-GANG, 1-PHASE METER STACK WM SERIES WITH INTEGRAL MAIN BREAKERS. 12. NOT USED. 13. 125A, 1-PHASE, 208V ALUMINUM FEEDER. 3 #3/0 AL AND 1 #4 AL E.GR. IN 2" CONDUIT OR EQUIVALENTLY SIZED MC FEEDER CABLE. 14. 200A FEEDER. ELECTRICAL KEYED NOTES: POWER RISER DIAGRAM SCALE: NONE UTILITY-OWNED SERVICE TRANSFORMER 2 3 4 6 7 8 10 11 12 14 15 16 18 19 20 1 5 9 13 17 1200A MAIN (APTS) 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH CB PANEL 1-PHASE "BC" 120/208V (STYLE BC) PANEL 1-PHASE "B3" 120/208V (STYLE B3) PANEL 1-PHASE "B2" 120/208V (STYLE B2) PANEL 1-PHASE "B1" 120/208V (STYLE B1) PANEL 1-PHASE "A3" 120/208V (STYLE A3) PANEL 1-PHASE "A2" 120/208V (STYLE A2) PANEL 1-PHASE 125A MCB "A1" 120/208V (STYLE A1) 1 2 4 3 (TYP. OF 14) (TYP. OF 2) A. THE SERVICE ENTRANCE EQUIPMENT AND ALL METERING SHALL MEET XCEL STANDARDS. B. ALL GROUNDING SHALL MEET THE REQUIREMENTS OF SECTION 250 OF THE 2014 NEC. REFER TO THE SERVICE GROUNDING SYSTEM DIAGRAM, THIS SHEET. GENERAL NOTES: 5 SERVICE FEEDER NEUTRAL BUS GROUND BUS GROUNDING ELECTRODE CONDUCTOR SCHEDULE A. ALL CONDUCTORS USED FOR THE GROUNDING SYSTEM SHALL BE COPPER. B. CONNECT THE GROUNDING SYSTEM TO THE FOUR FOLLOWING COMPONENTS: 1. BUILDING STEEL. 2. METAL U.G. COLD WATER PIPE. 3. CONCRETE ENCASED REBAR OR #4 COPPER UFER. 4. 10' GROUND RODS. C. ANY SPLICING SHALL BE VIA CAD-WELD TYPE PROCESS. D. THE GROUNDING SYSTEM SHALL COMPLY WITH ALL REQUIREMENTS OF ARTICLE 250 OF THE 2014 NEC, AND SHALL PROVIDE 5 OHMS OR LESS RESISTANCE TO GROUND. PROVIDE TEST REPORT VERIFYING RESISTANCE LEVEL IS IN COMPLIANCE WITH 5 OHM MAXIMUM. NEC 250.52(1) COLD WATER PIPE, BUILDING STEEL, NEC 250.52(2) SERVICE GROUNDING SYSTEM DIAGRAM SCALE: NONE SERVICE ENTRANCE EQUIPMENT MAIN DRIVEN COPPER CLAD 5/8" X 10' GROUND ROD (SPACED 15' APART) #4 UFER GROUND, SLAB REBAR OR NEC 250.52(3) AS SHOWN ON GROUNDING CONDUCTOR, MINIMUM SIZE GROUNDING ELECTRODE COPPER SERVICE PANELBOARD SERVICE GROUNDING SYSTEM GENERAL NOTES 200A 225A 400A 600A 800A 1000A 1200A 150A 100A SERVICE AMPACITY METALLIC PIPE CONDUCTOR BUILDING STEEL CONDUCTOR #4 #2 #1/0 #2/0 #3/0 #3/0 250KCMIL #6 #8 #4 #2 #1/0 #2/0 #3/0 #3/0 250KCMIL #6 #8 #4 #2 #1/0 #2/0 #2/0 #3/0 #3/0 #6 #8 #4 #2 #1/0 #2/0 #2/0 #3/0 #6 #8 #3/0 ELECTRODE CONDUCTOR SCHEDULE NEC 250.28 MAIN BONDING JUMPER, NEC 250.102(C) EQUIP. BONDING JUMPER, REBAR OR UFER CONDUCTOR #4 #2 #1/0 #2/0 #2/0 #3/0 #6 #8 #3/0 GROUND ROD CONDUCTOR #4 #2 #1/0 #2/0 #2/0 #3/0 #6 #8 #3/0 PHASE BUSES NEUTRAL BUS GROUND BUS EQUIV. CU WIRE SIZE #3/0 #4/0 500 700 1000 1200 1400 #1/0 #2 MAIN BONDING JUMPER EQUIPMENT BONDING JUMPER INTERSYSTEM BONDING TERMINATION (IBT), NEC 250.94 #6 CU 7 9 11 11 11 11 11 22 23 24 1-PH 1-PH 1-PH 1-PH 11 26 27 28 1-PH 1-PH 1-PH 1-PH 11 30 31 32 1-PH 1-PH 1-PH 1-PH 11 34 35 36 1-PH 1-PH 1-PH 1-PH 13 37 38 39 1-PH 1-PH 1-PH 1-PH 11 21 25 29 33 SPR 13 13 15 13 13 13 13 14 TYPICAL TYPICAL TYPICAL TYPICAL TYPICAL TYPICAL TYPICAL 6 job no: drawn: checked: date: sheet no: ARCHITECTS & CONTRACTORS MAKING HOUSE CALLS Sheet Title: FOWLER ST PARKSIDE TERRACE APARTMENTS HOBBS, NM 88240 Consulting Engineers 125A MCB 125A MCB 125A MCB 125A MCB 125A MCB 125A MCB (TYP. OF 25) (TYP. OF 20) (TYP. OF 1) (TYP. OF 1) (TYP. OF 2) UTILITY-OWNED SERVICE TRANSFORMER 2 3 4 6 7 8 10 11 12 14 15 16 18 19 20 1 5 9 13 17 1200A MAIN (APTS) 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH 1-PH PHASE II APARTMENT BUILDING CB PANEL 1-PHASE "CC" 120/208V COMMUN. PANEL 1-PHASE "LM" 120/208V LAUNDRY/ PANEL 1-PHASE "BC" 120/208V (STYLE BC) PANEL 1-PHASE "B3" 120/208V (STYLE B3) PANEL 1-PHASE "B2" 120/208V (STYLE B2) PANEL 1-PHASE "B1" 120/208V (STYLE B1) PANEL 1-PHASE "A3" 120/208V (STYLE A3) PANEL 1-PHASE "A2" 120/208V (STYLE A2) PANEL 1-PHASE 125A MCB "A1" 120/208V (STYLE A1) 1 2 4 3 (TYP. OF 14) (TYP. OF 2) 5 7 9 SERVICE: 3-PHASE IN, 1-PHASE OUT 39 + SPARE METER BANK 11 11 11 11 11 22 23 24 1-PH 1-PH 1-PH 1-PH 11 26 27 28 1-PH 1-PH 1-PH 1-PH 11 30 31 32 1-PH 1-PH 1-PH 1-PH 11 34 35 36 1-PH 1-PH 1-PH 1-PH 11 37 38 39 1-PH 1-PH 1-PH 1-PH 11 21 25 29 33 SPR 13 13 13 13 13 13 13 14 TYPICAL TYPICAL TYPICAL TYPICAL TYPICAL TYPICAL TYPICAL 6 125A MCB 125A MCB 125A MCB 125A MCB 125A MCB 125A MCB MAINT. CENTER (TYP. OF 25) (TYP. OF 20) (TYP. OF 1) (TYP. OF 1) (TYP. OF 2) PHASE I APARTMENT BUILDING SERVICE: 3-PHASE IN, 1-PHASE OUT 39 + SPARE METER BANK (36 PANELS, TOTAL) (30 PANELS, TOTAL) POWER RISER DIAGRAMS E-01 1. E-01 POWER RISER DIAGRAMS 2. E-02 ELECTRICAL SYMBOL LEGEND & GENERAL NOTES 3. E-03 PANEL SCHEDULES 4. ES-01 ELECTRICAL SITE PLAN 5. E-1S ELECTRICAL PLAN FIRST FLOOR SOUTH - PHASE I 6. E-1N ELECTRICAL PLAN FIRST FLOOR NORTH - PHASE II 7. E-2S ELECTRICAL PLAN SECOND FLOOR SOUTH - PHASE I 8. E-2N ELECTRICAL PLAN SECOND FLOOR NORTH - PHASE II 9. E-3S ELECTRICAL PLAN SECOND FLOOR SOUTH - PHASE I 10. E-3N ELECTRICAL PLAN SECOND FLOOR NORTH - PHASE II 11. EU-01 TYPICAL APARTMENT UNIT ELECTRICAL PLANS 12. E-1.2 ELECTRICAL PLANS COMMUNITY CENTER & LAUNDRY 13. ESP-1.0 ELECTRICAL SPECIFICATIONS ELECTRICAL SHEET INDEX 200A 200A

PARKSIDE TERRACE APARTMENTS - Pavilion … · 2015-11-30 · 12.e-1.2electrical plans community center & laundry ... 72 / fire alarm code chapter 2. ... l.telephone wiring installation

Embed Size (px)

Citation preview

1. UTILITY-OWNED POWER POLE. EXTEND PRIMARY RISER UP POLE PER UTILITY REQUIREMENTS. VERIFY ALL

SERVICE REQUIREMENTS WITH XCEL REPRESENTATIVE PRIOR TO BEGINNING ANY ELECTRICAL WORK.

CONTACT DANIEL HOLMES, XCEL ENERGY, PH. 575-391-3307.

2. EXTEND PRIMARY DUCT TO SERVICE POLE PER UTILITY REQUIREMENTS.

3. UTILITY-OWNED SERVICE TRANSFORMER WITH 208/120V, 3-PHASE SECONDARY.

4. CONCRETE TRANSFORMER PAD (BY G.C.) PER UTILITY REQUIREMENTS.

5. 1200A SERVICE FEEDER. PARALLEL RUN OF FOUR 3" CONDUITS EACH WITH 4 #350KCMIL CU.

6. FIELD VERIFY EXACT LOCATION OF METER BANK. PROVIDE SCALED SKETCH OF METER BANK LOCATION ON

EXTERIOR WALL TO ARCHITECT FOR APPROVAL PRIOR TO ROUGH-IN.

7. ONE #3/0 BSD COPPER SERVICE GROUND IN 3/4" CONDUIT. REFER TO SERVICE GROUNDING SYSTEM

DIAGRAM. PROVIDE 250KCMIL CU BONDING JUMPERS.

8. NOT USED.

9. SIEMENS MODULAR MAIN SERVICE DISCONNECTING MEANS, 1200A MCB, 240V, NEMA 3R ENCLOSURE.

10. NOT USED.

11. SIEMENS 4-GANG, 1-PHASE METER STACK WM SERIES WITH INTEGRAL MAIN BREAKERS.

12. NOT USED.

13. 125A, 1-PHASE, 208V ALUMINUM FEEDER. 3 #3/0 AL AND 1 #4 AL E.GR. IN 2" CONDUIT OR EQUIVALENTLY SIZED

MC FEEDER CABLE.

14. 200A FEEDER.

ELECTRICAL KEYED NOTES:

POWER RISER DIAGRAM

SCALE: NONE

UTILITY-OWNED

SERVICE

TRANSFORMER

2

3

4

6

7

8

10

11

12

14

15

16

18

19

20

1

5 9 13 17

1200A

MAIN

(APTS)

1-PH

1-PH

1-PH

1-PH

1-PH

1-PH

1-PH

1-PH 1-PH

1-PH

1-PH

1-PH

1-PH 1-PH

1-PH 1-PH 1-PH

1-PH

1-PH

1-PH

CB

PANEL

1-PHASE

"BC"

120/208V

(STYLE BC)

PANEL

1-PHASE

"B3"

120/208V

(STYLE B3)

PANEL

1-PHASE

"B2"

120/208V

(STYLE B2)

PANEL

1-PHASE

"B1"

120/208V

(STYLE B1)

PANEL

1-PHASE

"A3"

120/208V

(STYLE A3)

PANEL

1-PHASE

"A2"

120/208V

(STYLE A2)

PANEL

1-PHASE

125A MCB

"A1"

120/208V

(STYLE A1)

1

2

4

3

(TYP. OF 14) (TYP. OF 2)

A. THE SERVICE ENTRANCE EQUIPMENT AND ALL METERING SHALL MEET XCEL STANDARDS.

B. ALL GROUNDING SHALL MEET THE REQUIREMENTS OF SECTION 250 OF THE 2014 NEC. REFER TO THE SERVICE

GROUNDING SYSTEM DIAGRAM, THIS SHEET.

GENERAL NOTES:

5

SERVICE FEEDER

NEUTRAL BUS

GROUND BUS

GROUNDING ELECTRODE CONDUCTOR SCHEDULE

A. ALL CONDUCTORS USED FOR THE GROUNDING SYSTEM SHALL BE COPPER.

B. CONNECT THE GROUNDING SYSTEM TO THE FOUR FOLLOWING COMPONENTS:

1. BUILDING STEEL.

2. METAL U.G. COLD WATER PIPE.

3. CONCRETE ENCASED REBAR OR #4 COPPER UFER.

4. 10' GROUND RODS.

C. ANY SPLICING SHALL BE VIA CAD-WELD TYPE PROCESS.

D. THE GROUNDING SYSTEM SHALL COMPLY WITH ALL REQUIREMENTS OF ARTICLE 250 OF THE 2014 NEC,

AND SHALL PROVIDE 5 OHMS OR LESS RESISTANCE TO GROUND. PROVIDE TEST REPORT VERIFYING

RESISTANCE LEVEL IS IN COMPLIANCE WITH 5 OHM MAXIMUM.

NEC 250.52(1)

COLD WATER PIPE,

BUILDING STEEL,

NEC 250.52(2)

SERVICE GROUNDING SYSTEM DIAGRAM

SCALE: NONE

SERVICE

ENTRANCE

EQUIPMENT

MAIN

DRIVEN

COPPER CLAD

5/8" X 10'

GROUND ROD

(SPACED 15' APART)

#4 UFER GROUND,

SLAB REBAR OR

NEC 250.52(3)

AS SHOWN ON GROUNDING

CONDUCTOR, MINIMUM SIZE

GROUNDING ELECTRODE

COPPER SERVICE

PANELBOARD

SERVICE GROUNDING SYSTEM GENERAL NOTES

200A

225A

400A

600A

800A

1000A

1200A

150A

100A

SERVICE

AMPACITY

METALLIC

PIPE

CONDUCTOR

BUILDING

STEEL

CONDUCTOR

#4

#2

#1/0

#2/0

#3/0

#3/0

250KCMIL

#6

#8

#4

#2

#1/0

#2/0

#3/0

#3/0

250KCMIL

#6

#8

#4

#2

#1/0

#2/0

#2/0

#3/0

#3/0

#6

#8

#4

#2

#1/0

#2/0

#2/0

#3/0

#6

#8

#3/0

ELECTRODE CONDUCTOR

SCHEDULE

NEC 250.28

MAIN BONDING JUMPER,

NEC 250.102(C)

EQUIP. BONDING JUMPER,

REBAR OR

UFER

CONDUCTOR

#4

#2

#1/0

#2/0

#2/0

#3/0

#6

#8

#3/0

GROUND

ROD

CONDUCTOR

#4

#2

#1/0

#2/0

#2/0

#3/0

#6

#8

#3/0

PHASE

BUSES

NEUTRAL

BUS

GROUND

BUS

EQUIV.

CU WIRE

SIZE

#3/0

#4/0

500

700

1000

1200

1400

#1/0

#2

MAIN

BONDING

JUMPER

EQUIPMENT

BONDING

JUMPER

INTERSYSTEM BONDING

TERMINATION (IBT),

NEC 250.94

#6 CU

7

9

11 11 11 11 11

22

23

24

1-PH

1-PH

1-PH

1-PH

11

26

27

28

1-PH

1-PH

1-PH

1-PH

11

30

31

32

1-PH

1-PH

1-PH

1-PH

11

34

35

36

1-PH

1-PH

1-PH

1-PH

13

37

38

39

1-PH

1-PH

1-PH

1-PH

11

21 25 29 33 SPR

13

13

15

13

13

13

13

14

TYPICAL

TYPICAL TYPICAL

TYPICAL TYPICAL TYPICAL TYPICAL

6

job no:

drawn:

checked:

date:

sheet no:

AR

CH

ITE

CTS

& C

ON

TRA

CTO

RS

MA

KIN

G H

OU

SE

CA

LLS

Sheet Title:

FOW

LER ST

PARKSIDE TERRACE APARTM

ENTS

HOBBS, NM

88240

Consulting Engineers

125A MCB 125A MCB

125A MCB 125A MCB 125A MCB 125A MCB

(TYP. OF 25)(TYP. OF 20)(TYP. OF 1)

(TYP. OF 1)

(TYP. OF 2)

UTILITY-OWNED

SERVICE

TRANSFORMER

2

3

4

6

7

8

10

11

12

14

15

16

18

19

20

1

5 9 13 17

1200A

MAIN

(APTS)

1-PH

1-PH

1-PH

1-PH

1-PH

1-PH

1-PH

1-PH 1-PH

1-PH

1-PH

1-PH

1-PH 1-PH

1-PH 1-PH 1-PH

1-PH

1-PH

1-PH

PHASE II APARTMENT BUILDINGCB

PANEL

1-PHASE

"CC"

120/208V

COMMUN.

PANEL

1-PHASE

"LM"

120/208V

LAUNDRY/

PANEL

1-PHASE

"BC"

120/208V

(STYLE BC)

PANEL

1-PHASE

"B3"

120/208V

(STYLE B3)

PANEL

1-PHASE

"B2"

120/208V

(STYLE B2)

PANEL

1-PHASE

"B1"

120/208V

(STYLE B1)

PANEL

1-PHASE

"A3"

120/208V

(STYLE A3)

PANEL

1-PHASE

"A2"

120/208V

(STYLE A2)

PANEL

1-PHASE

125A MCB

"A1"

120/208V

(STYLE A1)

1

2

4

3

(TYP. OF 14) (TYP. OF 2)

5

7

9

SERVICE: 3-PHASE IN, 1-PHASE OUT

39 + SPARE METER BANK

11 11 11 11 11

22

23

24

1-PH

1-PH

1-PH

1-PH

11

26

27

28

1-PH

1-PH

1-PH

1-PH

11

30

31

32

1-PH

1-PH

1-PH

1-PH

11

34

35

36

1-PH

1-PH

1-PH

1-PH

11

37

38

39

1-PH

1-PH

1-PH

1-PH

11

21 25 29 33 SPR

13

13

13

13

13

13

13

14

TYPICAL

TYPICAL TYPICAL

TYPICAL TYPICAL TYPICAL TYPICAL

6

125A MCB 125A MCB

125A MCB 125A MCB 125A MCB 125A MCB

MAINT.

CENTER

(TYP. OF 25)(TYP. OF 20)(TYP. OF 1)

(TYP. OF 1)

(TYP. OF 2)

PHASE I APARTMENT BUILDING

SERVICE: 3-PHASE IN, 1-PHASE OUT

39 + SPARE METER BANK

(36 PANELS, TOTAL)

(30 PANELS, TOTAL)

POW

ER RISER DIAGRAM

S

E-01

1. E-01 POWER RISER DIAGRAMS

2. E-02 ELECTRICAL SYMBOL LEGEND & GENERAL NOTES

3. E-03 PANEL SCHEDULES

4. ES-01 ELECTRICAL SITE PLAN

5. E-1S ELECTRICAL PLAN FIRST FLOOR SOUTH - PHASE I

6. E-1N ELECTRICAL PLAN FIRST FLOOR NORTH - PHASE II

7. E-2S ELECTRICAL PLAN SECOND FLOOR SOUTH - PHASE I

8. E-2N ELECTRICAL PLAN SECOND FLOOR NORTH - PHASE II

9. E-3S ELECTRICAL PLAN SECOND FLOOR SOUTH - PHASE I

10. E-3N ELECTRICAL PLAN SECOND FLOOR NORTH - PHASE II

11. EU-01 TYPICAL APARTMENT UNIT ELECTRICAL PLANS

12. E-1.2 ELECTRICAL PLANS COMMUNITY CENTER & LAUNDRY

13. ESP-1.0 ELECTRICAL SPECIFICATIONS

ELECTRICAL SHEET INDEX

200A

200A

A. ALL ELECTRICAL WORK SHALL COMPLY WITH THE 2014 NATIONAL ELECTRICAL

CODE (NEC), THE 2014 NMEC, AND REGULATIONS OF STATE AND LOCAL

AUTHORITIES HAVING JURISDICTION (AHJ).

B. PROVIDE HOUSEHOLD FIRE WARNING EQUIPMENT IN CONFORMANCE WITH NFPA

72 / FIRE ALARM CODE CHAPTER 2.

C. EACH DWELLING UNIT HAS SINGLE STATION SMOKE ALARM DEVICES WHICH

SOUND AN ALARM IN THAT DWELLING UNIT ONLY. IN EACH DWELLING UNIT THE

SMOKE DETECTORS SHALL BE HARDWIRED AND INTERLOCKED SUCH THAT ALL

SMOKE DETECTORS ALARM SIMULTANEOUSLY.

D. THE LOCATION OF DWELLING UNIT RECEPTACLES SHALL CONFORM TO NEC

210.5. EXACT RECEPTACLE LOCATIONS MAY BE ALTERED AS FIELD

CONDITIONS REQUIRE AS LONG AS MODIFIED LOCATION STAYS WITHIN NEC

PARAMETERS.

E. ALL 120V, 15 AND 20 AMP RECEPTACLES INSIDE APARTMENTS SHALL BE LISTED

TAMPER-RESISTANT RECEPTACLES PER NEC 406.11.

F. ALL KITCHEN GENERAL USE DUPLEX RECEPTACLES AND ALL BATHROOM

DUPLEX RECEPTACLES SHALL BE GFCI PROTECTED.

G. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION FOR 15 AND 20

AMP BRANCH CIRCUITS AS REQUIRED BY NEC 210.12.

H. RECEPTACLES AND SWITCHES SHALL BE DECORA STYLE, IVORY IN COLOR WITH

COMPATIBLE PLASTIC PLATES, INSTALLED FOR ADA COMPLIANCE UNLESS

NOTED OTHERWISE.

I. UTILIZE "DEEP" 4-SQUARES WHERE REQUIRED TO COMPLY WITH NEC 314.6

EXTRA CONSIDERATION SHALL BE GIVEN TO BOXES SUPPLYING HOME-RUNS.

J. SHARED NEUTRALS ARE NOT PERMISSIBLE UNLESS NOTED OTHERWISE.

H. CONDUCTOR TICK MARKS ARE SHOWN FOR CONVENIENCE ONLY, THE

CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL CONDUCTORS WHETHER

SHOWN OR NOT INCLUDING "TRAVELERS" AS NECESSARY FOR COMPLETELY

OPERATIONAL SYSTEMS.

I. CONFIRM EXACT ROUGH-IN DIMENSIONS WITH ARCHITECTURAL DRAWINGS,

KITCHEN EQUIPMENT, FURNITURE PLAN (IF AVAILABLE) AND SPECIALTY

EQUIPMENT.

J. BRANCH CIRCUITING SHALL BE COPPER WIRE IN MC CABLE UNLESS

SPECIFICALLY NOTED OTHERWISE. MINIMUM WIRE SIZE IS #12 AWG.

K. TELEVISION CABLE INSTALLATION SHALL CONFORM TO COMCAST CABLE INC.

MULTIPLE DWELLING CATV PREWIRING SPECIFICATIONS. COMCAST CONTACT:

TODD SCHNUELLE, PH. 271-3643.

L. TELEPHONE WIRING INSTALLATION SHALL CONFORM TO CENTURYLINK

PREWIRING SPECIFICATIONS. CENTURYLINK CONTACT: DON DAVALOS, PH.

245-8967.

M. ELECTRIC SERVICE INSTALLATION SHALL CONFORM TO PNM STANDARDS AND

REQUIREMENTS. CONTACT: DANIEL RODRIGUEZ, PH. 241-2700.

PROJECT GENERAL ELECTRICAL NOTES:

SUMMARY:

1. Provide electrical systems for the following:

a. Power.

b. Lighting.

c. Telephone.

d. Television.

e. Exit lighting.

f. Emergency lighting.

2. Electrical Service:

a. Provide new 208/120V, 3-phase service as indicated.

PRODUCTS:

1. Provide new materials suitable for service intended. Provide accessories such as

controls, coverplates, and connections to equipment. Coordinate location of all HVAC

equipment with mechanical trade.

2. Residential power panels shall be load center type.

3. 3-phase power panels shall have door-in-door trim.

4. General use convenience duplex receptacles shall be rated 15A.

5. Dedicated duplex receptacles shall be rated 20A.

6. Wall switches shall be rated 120/277V.

7. Fuses shall be dual element Buss fusetrons unless noted otherwise.

8. Wall switches and duplex receptacles shall be Decora style, white.

INSTALLATION:

1. Comply with the 2014 National Electrical Code (NEC) and regulations of state and local

authorities having jurisdiction.

2. Color code all wiring as follows: For 208/120V, Phase A-Black, Phase B-Red, Phase

C-Blue, Neutral-White, Ground-Green.

3. Branch circuiting shall be MC cable.

4. Feeders shall be in conduit, EMT when indoors, PVC when underground.

5. All j-boxes including voice/data outlets shall be provided with a coverplate.

6. Install light switches at uniform height, up 44" to center of j-box. Locate switches within

rooms at strike side of door unless noted otherwise.

7. Install thermostats up 54" to center of j-box.

8. Gang mount multiple switching locations. Mount multiple types of controls as close

together as possible and in line with each other.

9. Group multiple voice/data and receptacles together on walls.

10. Mount receptacles and combination voice/data outlets vertically at uniform height, up 18"

to center of j-box, unless noted otherwise.

11. Upsize 20A circuit conductors from #12 to #10 for any 20A, 120V circuits with total run

length greater than 90'.

12. Upsize 20A circuit conductors as required to limit overall voltage drop on farthest outlet

on the branch circuit to 5% maximum.

13. Maintain indicated fire ratings of walls, partitions, ceilings, and floors at penetrations.

Seal with firestopping to maintain fire rating.

14. Test all systems for proper operation.

15. Provide plastic nameplates for power panels. Nameplate to include panel designation,

voltage, and phase, e.g. PANEL "HVAC" / 208/120V / 3-PHASE.

16. Provide typewritten circuit directory in panelboards.

17. Instruct Owner's personnel in proper operation of systems.

18. Contractor shall coordinate special systems work with Owner and cabling Contractor.

ELECTRICAL SPECIFICATIONS

job no:

drawn:

checked:

date:

sheet no:

AR

CH

ITE

CTS

& C

ON

TRA

CTO

RS

MA

KIN

G H

OU

SE

CA

LLS

Sheet Title:

FOW

LER ST

PARKSIDE TERRACE APARTM

ENTS

HOBBS, NM

88240

Consulting Engineers

SYM

BOL LEGEND, SCH

EDULES, AND GENERAL NOTES

E-02

ABOVE FINISH FLOOR.

PHOTOCELL

THREE-WAY SWITCH

FOUR-WAY SWITCH

WEATHER-RESISTANT SWITCH

KEY OPERATED SWITCH

DIMMER SWITCH - NUMBER INDICATES WATTAGE.

AFF

G

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

ELECTRICAL SYMBOL LEGEND

(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)

THERMOSTAT

ABOVE COUNTER.AC

OCCUPANCY SENSOR SWITCH.

BELOW COUNTER.BC

CATV OUTLET

SPEAKER, CEILING MOUNTED

J

CEILING MOUNTED DUPLEX RECEPTACLE.

FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE.

ELECTRONIC TIME SWITCH OR MECHANICALLY WOUND TWIST TIMER

SWITCH. # INDICATES CIRCUIT.

THERMAL SWITCH.

EVAPORATIVE COOLER SWITCH.

1

T

GROUND FAULT CIRCUIT INTERRUPTER.GFCI

COMBINATION VOICE/DATA OUTLET, UP 18" U.N.O.

U.N.O.UNLESS NOTED OTHERWISE.

FLUORESCENT STRIP FIXTURE

PTZ

STA

V

T

T

S

S

S

S

S

S

S

S

S

S

S

GFCI

WR

#

J

E.GR.EQUIPMENT GROUND.

WEATHER-RESITANT.WR

job no:

drawn:

checked:

date:

sheet no:

AR

CH

ITE

CTS

& C

ON

TRA

CTO

RS

MA

KIN

G H

OU

SE

CA

LLS

Sheet Title:

FOW

LER ST

PARKSIDE TERRACE APARTM

ENTS

HOBBS, NM

88240

Consulting Engineers

PANEL SCH

EDULES

E03

WHITE STREET

E DUNNAM STREET

FOW

LER

STRE

ET

MCK

INLE

Y ST

REET

T

T

TYP

2

3

1

1

ELECTRICAL PLAN FIRST FLOOR NORTH

- PH

ASE II

job no:

drawn:

checked:

date:

sheet no:

AR

CH

ITE

CTS

& C

ON

TRA

CTO

RS

MA

KIN

G H

OU

SE

CA

LLS

Sheet Title:

FOW

LER ST

PARKSIDE TERRACE APARTM

ENTS

HOBBS, NM

88240

Consulting Engineers

ELECTRICAL KEYED NOTES:

GENERAL NOTES:

ELECTRICAL SITE PLAN

SCALE: 1" = 20'-0"

1. PROPOSED METER CENTERLOCATION, REFER TO POWER RISER DIAGRAM.

2. PROPOSED LOCATION FOR SERVICE TRANSFORMER TO SERVE SOUTH BUILDING

(PHASE I).

3. PROPOSED LOCATION FOR SERVICE TRANSFORMER TO SERVE NORTH BUILDING

(PHASE II).

4. PARKING LOT LIGHTING FIXTURE ON 18' POLE, REFER TO POLE BASE MOUNTING

DETAIL.

A. THE NORTH BUILDING FIRST FLOOR HAS (8) TOTAL APARTMENTS, (1) TYPE A3

APARTMENTS, (2) TYPE B2 APARTMENTS AND (5) TYPE B3 APARTMENTS.

B. ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL

ELECTRICAL CODE (NEC).

C. PROVIDE HOUSEHOLD FIRE WARNING EQUIPMENT IN CONFORMANCE WITH NFPA

72 / FIRE ALARM CODE (1996 EDITION) CHAPTER 2; SPECIFICALLY 2-2.1.1.1 AND

2-2.3.

D. EACH DWELLING UNIT HAS SINGLE STATION SMOKE ALARM DEVICES WHICH

SOUND AN ALARM IN THAT DWELLING UNIT ONLY. IN EACH DWELLING UNIT THE

SMOKE DETECTORS SHALL BE HARDWIRED AND INTERLOCKED SUCH THAT ALL

SMOKE DETECTORS ALARM SIMULTANEOUSLY.

E. THE LOCATION OF DWELLING UNIT RECEPTACLES SHALL CONFORM TO NEC

210.5. EXACT DEVICE LOCATIONS MAY BE ALTERED AS FIELD CONDITIONS

REQUIRE AS LONG AS MODIFIED LOCATION STAYS WITHIN NEC PARAMETERS.

F. ALL 120V, 15 AND 20 AMP RECEPTACLES INSIDE APARTMENTS SHALL BE LISTED

TAMPER-RESISTANT RECEPTACLES PER NEC 406.11.

G. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION FOR 15 AND 20

AMP BRANCH CIRCUITS AS REQUIRED BY NEC 210.12.

E1N

60"

FINISHED GRADE

24"

24" DIA.

POLE BASE MOUNTING DETAIL

SCALE: NONE

BOTH POLE AND BASE PLATE SHALL

BE FURNISHED AS PART OF LUMINAIRE,

REFER TO LUMINAIRE SCHEDULE

CHAMFER EDGE 1"

MINIMUM CONTINUOUS

HANDHOLE

INSTALL BUSHING

ON CONDUIT ENDS

3000 PSI CONCRETE

#5 VERTICAL REBAR WITH #4

HORIZONTAL REBAR TIES 12"

ON CENTER. FIRST TIE SHALL

BE 6" FROM BOTTOM.

BOLTS FURNISHED AS PART

OF LUMINAIRE. INSTALL PER

MANUFACTURER.

ELECTRICAL CONDUIT,

SEE ELECTRICAL SITE

PLAN FOR ROUTING

AROUND BASE

A ALL LIGHT POLE CONCRETE BASES SHOULD BE VERIFIED WITH

STRUCTURAL ENGINEER FAMILIAR WITH THE SOIL AND WIND

CONDITIONS OF THIS PROJECT.

B G.C. TO PROVIDE AND INSTALL ENTIRE POLE BASE.

C LIGHTING FIXTURES SHALL BE OF TYPE INDICATED ON DRAWINGS.

POLE BASE NOTES:

UP

UP

UP

2

3

4

5

1

PANEL "HPS"

6

10

7

9

11

11

11

11

9

11

11

11

F

TS

FS

15

ELEVATOR

BEDROOM BEDROOMBEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

EXTERIOR WALKWAY

5 TYP

5 TYP

E

X

T

E

R

IO

R

W

A

L

K

W

A

Y

EX

TE

RIO

R W

ALK

WA

Y

UP

UP

UPUP

UP

job no:

drawn:

checked:

date:

sheet no:

AR

CH

ITE

CTS

& C

ON

TRA

CTO

RS

MA

KIN

G H

OU

SE

CA

LLS

Sheet Title:

FOW

LER ST

PARKSIDE TERRACE APARTM

ENTS

HOBBS, NM

88240

Consulting Engineers

ELECTRICAL KEYED NOTES:

GENERAL NOTES:

ELECTRICAL PLAN FIRST FLOOR SOUTH - PHASE I

SCALE: 3/32" = 1'-0"

1. METER CENTER, REFER TO POWER RISER DIAGRAM.

2. COMBINATION BUILDING MAIN TELEPHONE TERMINAL CABINET (TTC) AND CABLE

TELEVISION (CATV) CABINET. PROVIDED BY PLATEAU, INSTALLED BY E.C.

FOR SOUTH BUILDING.

4. INTERMATIC #V45000 SERIES TIMECLOCK.

5. 120V FIRE SPRINKLER SYSTEM BELL. FIELD VERIFY EXACT LOCATION WITH

SPRINKLER SYSTEM INSTALLER.

6. APARTMENT UNIT POWER PANEL, REFER TO TYPICAL APARTMENT UNIT

ELECTRICAL PLANS ON SHEETS XXX.

7. REFER TO COMMUNITY BUILDING ELECTRICAL PLAN FOR WORK IN THIS AREA.

8. REFER TO TYPICAL UNIT "A3" TYPE - ELECTRICAL PLAN FOR WORK REQUIRED IN

THIS DWELLING UNIT.

9. REFER TO TYPICAL UNIT "B1" TYPE - ELECTRICAL PLAN FOR WORK REQUIRED IN

THIS DWELLING UNIT.

10. REFER TO TYPICAL UNIT "B2" TYPE - ELECTRICAL PLAN FOR WORK REQUIRED IN

THIS DWELLING UNIT.

11. REFER TO TYPICAL UNIT "B3" TYPE - ELECTRICAL PLAN FOR WORK REQUIRED IN

THIS DWELLING UNIT.

A. THE SOUTH BUILDING FIRST FLOOR HAS (10) TOTAL APARTMENTS, (2) TYPE B1

APARTMENTS, (1) TYPE B2 APARTMENTS AND (7) TYPE B3 APARTMENTS.

B. ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL

ELECTRICAL CODE (NEC).

C. PROVIDE HOUSEHOLD FIRE WARNING EQUIPMENT IN CONFORMANCE WITH NFPA

72 / FIRE ALARM CODE (1996 EDITION) CHAPTER 2; SPECIFICALLY 2-2.1.1.1 AND

2-2.3.

D. EACH DWELLING UNIT HAS SINGLE STATION SMOKE ALARM DEVICES WHICH

SOUND AN ALARM IN THAT DWELLING UNIT ONLY. IN EACH DWELLING UNIT THE

SMOKE DETECTORS SHALL BE HARDWIRED AND INTERLOCKED SUCH THAT ALL

SMOKE DETECTORS ALARM SIMULTANEOUSLY.

E. THE LOCATION OF DWELLING UNIT RECEPTACLES SHALL CONFORM TO NEC

210.5. EXACT DEVICE LOCATIONS MAY BE ALTERED AS FIELD CONDITIONS

REQUIRE AS LONG AS MODIFIED LOCATION STAYS WITHIN NEC PARAMETERS.

F. ALL 120V, 15 AND 20 AMP RECEPTACLES INSIDE APARTMENTS SHALL BE LISTED

TAMPER-RESISTANT RECEPTACLES PER NEC 406.11.

G. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION FOR 15 AND 20

AMP BRANCH CIRCUITS AS REQUIRED BY NEC 210.12.

E1S

KEY PLAN - FIRST FLOOR

SCALE: 1" = 30' (18) APARTMENTS + COMM. BLDG

ELECTRICAL PLAN FIRST FLOOR SOUTH

- PH

ASE I

UP

UPUP

UP

11

11

11

11

11

11

11

9

11

11

11

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM BEDROOM BEDROOM BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

8

8

88

8

8

8

8

23

4

7

1

PANEL "HPN"

6

F

TS FS

15

ELEVATOR

TYP5

TYP5

UP

UP

UPUP

UP

ELECTRICAL PLAN FIRST FLOOR NORTH

- PH

ASE II

job no:

drawn:

checked:

date:

sheet no:

AR

CH

ITE

CTS

& C

ON

TRA

CTO

RS

MA

KIN

G H

OU

SE

CA

LLS

Sheet Title:

FOW

LER ST

PARKSIDE TERRACE APARTM

ENTS

HOBBS, NM

88240

Consulting Engineers

ELECTRICAL KEYED NOTES:

GENERAL NOTES:

ELECTRICAL PLAN FIRST FLOOR NORTH - PHASE II

SCALE: 1/8" = 1'-0"

1. METER CENTER, REFER TO POWER RISER DIAGRAM.

2. COMBINATION BUILDING MAIN TELEPHONE TERMINAL CABINET (TTC) AND CABLE

TELEVISION (CATV) CABINET. PROVIDED BY PLATEAU, INSTALLED BY E.C.

4. INTERMATIC #V45000 SERIES TIMECLOCK.

5. SHALLOW, SURFACE MOUNTED L.E.D. "PUCK" LIGHTING FIXTURE.

6. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND HEIGHT OF

BUILDING MOUNTED FIXTURES.

7. 120V FIRE SPRINKLER SYSTEM BELL. FIELD VERIFY EXACT LOCATION WITH

SPRINKLER SYSTEM INSTALLER.

8. APARTMENT UNIT POWER PANEL, REFER TO TYPICAL APARTMENT UNIT

ELECTRICAL PLANS ON SHEETS EU1.0 AND EU1.1.

9. REFER TO TYPICAL UNIT "A3" TYPE - ELECTRICAL PLAN FOR WORK REQUIRED IN

THIS DWELLING UNIT.

10. REFER TO TYPICAL UNIT "B2" TYPE - ELECTRICAL PLAN FOR WORK REQUIRED IN

THIS DWELLING UNIT.

11. REFER TO TYPICAL UNIT "B3" TYPE - ELECTRICAL PLAN FOR WORK REQUIRED IN

THIS DWELLING UNIT.

12. 1.5 KW, 120V, ELECTRIC BASEBOARD HEATER.

13. VERIFY POST INDICATOR VALVE (P.I.V.) LOCATION WITH FIRE PROTECTION

PLANS, CONNECT TO FIRE ALARM SYSTEM AS REQUIRED.

14. CONNECT SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO FIRE ALARM

SYSTEM AS REQUIRED.

15. FIRE ALARM CONTROL PANEL (FACP) FOR THIS BUILDING (STAND-ALONE

SYSTEM).

A. THE NORTH BUILDING FIRST FLOOR HAS (8) TOTAL APARTMENTS, (1) TYPE A3

APARTMENTS, (2) TYPE B2 APARTMENTS AND (5) TYPE B3 APARTMENTS.

B. ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL

ELECTRICAL CODE (NEC).

C. PROVIDE HOUSEHOLD FIRE WARNING EQUIPMENT IN CONFORMANCE WITH NFPA

72 / FIRE ALARM CODE (1996 EDITION) CHAPTER 2; SPECIFICALLY 2-2.1.1.1 AND

2-2.3.

D. EACH DWELLING UNIT HAS SINGLE STATION SMOKE ALARM DEVICES WHICH

SOUND AN ALARM IN THAT DWELLING UNIT ONLY. IN EACH DWELLING UNIT THE

SMOKE DETECTORS SHALL BE HARDWIRED AND INTERLOCKED SUCH THAT ALL

SMOKE DETECTORS ALARM SIMULTANEOUSLY.

E. THE LOCATION OF DWELLING UNIT RECEPTACLES SHALL CONFORM TO NEC

210.5. EXACT DEVICE LOCATIONS MAY BE ALTERED AS FIELD CONDITIONS

REQUIRE AS LONG AS MODIFIED LOCATION STAYS WITHIN NEC PARAMETERS.

F. ALL 120V, 15 AND 20 AMP RECEPTACLES INSIDE APARTMENTS SHALL BE LISTED

TAMPER-RESISTANT RECEPTACLES PER NEC 406.11.

G. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION FOR 15 AND 20

AMP BRANCH CIRCUITS AS REQUIRED BY NEC 210.12.

E1N

KEY PLAN FIRST FLOOR

SCALE: 1" = 30' (18) APARTMENTS + COMM. BLDG

6

3

2

4

2

DN

UP

DN

UP

EXTERIOR WALKWAY

5 TYP

5 TYP

E

X

T

E

R

IO

R

W

A

L

K

W

A

Y

EX

TE

RIO

R W

ALK

WA

Y

2

3 3 3

OPEN TO

BELOW

3

3

3

3

2

2

OPEN TO

BELOW

OPEN TO

BELOW

DN

UP

DN

UP

UP

UP

job no:

drawn:

checked:

date:

sheet no:

AR

CH

ITE

CTS

& C

ON

TRA

CTO

RS

MA

KIN

G H

OU

SE

CA

LLS

Sheet Title:

FOW

LER ST

PARKSIDE TERRACE APARTM

ENTS

HOBBS, NM

88240

Consulting Engineers

ELECTRICAL KEYED NOTES:

GENERAL NOTES:

ELECTRICAL PLAN SECOND FLOOR SOUTH - PHASE I

SCALE: 3/32" = 1'-0"

A. THE SOUTH BUILDING SECOND FLOOR HAS (14) TOTAL APARTMENTS, (5) TYPE B1

APARTMENTS, (8) TYPE B2 APARTMENTS AND (1) TYPE B3 APARTMENT.

B. ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL

ELECTRICAL CODE (NEC).

C. PROVIDE HOUSEHOLD FIRE WARNING EQUIPMENT IN CONFORMANCE WITH NFPA

72 / FIRE ALARM CODE (1996 EDITION) CHAPTER 2; SPECIFICALLY 2-2.1.1.1 AND

2-2.3.

D. EACH DWELLING UNIT HAS SINGLE STATION SMOKE ALARM DEVICES WHICH

SOUND AN ALARM IN THAT DWELLING UNIT ONLY. IN EACH DWELLING UNIT THE

SMOKE DETECTORS SHALL BE HARDWIRED AND INTERLOCKED SUCH THAT ALL

SMOKE DETECTORS ALARM SIMULTANEOUSLY.

E. THE LOCATION OF DWELLING UNIT RECEPTACLES SHALL CONFORM TO NEC

210.5. EXACT DEVICE LOCATIONS MAY BE ALTERED AS FIELD CONDITIONS

REQUIRE AS LONG AS MODIFIED LOCATION STAYS WITHIN NEC PARAMETERS.

F. ALL 120V, 15 AND 20 AMP RECEPTACLES INSIDE APARTMENTS SHALL BE LISTED

TAMPER-RESISTANT RECEPTACLES PER NEC 406.11.

G. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION FOR 15 AND 20

AMP BRANCH CIRCUITS AS REQUIRED BY NEC 210.12.

E2S

KEY PLAN - FIRST FLOOR

SCALE: 1" = 30'

1. APARTMENT UNIT POWER PANEL, REFER TO TYPICAL APARTMENT UNIT

ELECTRICAL PLANS ON SHEETS EU1.0 AND EU1.1.

2. REFER TO TYPICAL SINGLE BEDROOM UNIT "B1" TYPE - ELECTRICAL PLAN FOR

WORK REQUIRED IN THIS DWELLING UNIT.

3. REFER TO TYPICAL TWO BEDROOM UNIT "B2" TYPE - ELECTRICAL PLAN FOR

WORK REQUIRED IN THIS DWELLING UNIT.

4. REFER TO TYPICAL THREE BEDROOM UNIT "B3" TYPE - ELECTRICAL PLAN FOR

WORK REQUIRED IN THIS DWELLING.

5. SHALLOW, SURFACE MOUNTED L.E.D. "PUCK" LIGHTING FIXTURE.

ELECTRICAL PLAN SECOND FLOOR SOUTH

- PH

ASE I

DN

UP

UP

UP

DN

UP

UP

UP

E

X

T

E

R

IO

R

W

A

L

K

W

A

Y

3

2

2

2

2

3

3

3

3

3

3

TYP5

TYP

5

OPEN TO

BELOW

OPEN TO

BELOW

DN

UP

DN

UP

UP

UP

job no:

drawn:

checked:

date:

sheet no:

AR

CH

ITE

CTS

& C

ON

TRA

CTO

RS

MA

KIN

G H

OU

SE

CA

LLS

Sheet Title:

FOW

LER ST

PARKSIDE TERRACE APARTM

ENTS

HOBBS, NM

88240

Consulting Engineers

ELECTRICAL KEYED NOTES:

GENERAL NOTES:

ELECTRICAL PLAN SECOND FLOOR NORTH - PHASE II

SCALE: 1/8" = 1'-0"

A. THE NORTH BUILDING SECOND FLOOR HAS (9) TOTAL APARTMENTS, (3) TYPE B1

APARTMENTS AND (6) TYPE B2 APARTMENTS.

B. ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL

ELECTRICAL CODE (NEC).

C. PROVIDE HOUSEHOLD FIRE WARNING EQUIPMENT IN CONFORMANCE WITH NFPA

72 / FIRE ALARM CODE (1996 EDITION) CHAPTER 2; SPECIFICALLY 2-2.1.1.1 AND

2-2.3.

D. EACH DWELLING UNIT HAS SINGLE STATION SMOKE ALARM DEVICES WHICH

SOUND AN ALARM IN THAT DWELLING UNIT ONLY. IN EACH DWELLING UNIT THE

SMOKE DETECTORS SHALL BE HARDWIRED AND INTERLOCKED SUCH THAT ALL

SMOKE DETECTORS ALARM SIMULTANEOUSLY.

E. THE LOCATION OF DWELLING UNIT RECEPTACLES SHALL CONFORM TO NEC

210.5. EXACT DEVICE LOCATIONS MAY BE ALTERED AS FIELD CONDITIONS

REQUIRE AS LONG AS MODIFIED LOCATION STAYS WITHIN NEC PARAMETERS.

F. ALL 120V, 15 AND 20 AMP RECEPTACLES INSIDE APARTMENTS SHALL BE LISTED

TAMPER-RESISTANT RECEPTACLES PER NEC 406.11.

G. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION FOR 15 AND 20

AMP BRANCH CIRCUITS AS REQUIRED BY NEC 210.12.

E2N

KEY PLAN - SECOND FLOOR

SCALE: 1" = 30'

1. APARTMENT UNIT POWER PANEL, REFER TO TYPICAL APARTMENT UNIT

ELECTRICAL PLANS ON SHEETS EU1.0 AND EU1.1.

2. REFER TO TYPICAL SINGLE BEDROOM UNIT "B1" TYPE - ELECTRICAL PLAN FOR

WORK REQUIRED IN THIS DWELLING UNIT.

3. REFER TO TYPICAL TWO BEDROOM UNIT "B2" TYPE - ELECTRICAL PLAN FOR

WORK REQUIRED IN THIS DWELLING UNIT.

4. NOT USED.

5. SHALLOW, SURFACE MOUNTED L.E.D. "PUCK" LIGHTING FIXTURE.

ELECTRICAL PLAN SECOND FLOOR NORTH

- PH

ASE II

1

DN

DN

3

2

3

2

3

3

2

22

3

4

3

3

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

2

BEDROOM

BEDROOM BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

EXTERIOR WALKWAY

5 TYP

5 TYP

E

X

T

E

R

IO

R

W

A

L

K

W

A

Y

EX

TE

RIO

R W

ALK

WA

Y

DN

DN

DN

UP

job no:

drawn:

checked:

date:

sheet no:

AR

CH

ITE

CTS

& C

ON

TRA

CTO

RS

MA

KIN

G H

OU

SE

CA

LLS

Sheet Title:

FOW

LER ST

PARKSIDE TERRACE APARTM

ENTS

HOBBS, NM

88240

Consulting Engineers

ELECTRICAL KEYED NOTES:

GENERAL NOTES:

ELECTRICAL PLAN THIRD FLOOR SOUTH - PHASE I

SCALE: 3/32" = 1'-0"

E3S

KEY PLAN - THIRD FLOOR

SCALE: 1" = 30'

1. APARTMENT UNIT POWER PANEL, REFER TO TYPICAL APARTMENT UNIT

ELECTRICAL PLANS ON SHEETS EU1.0 AND EU1.1.

2. REFER TO TYPICAL SINGLE BEDROOM UNIT "B1" TYPE - ELECTRICAL PLAN FOR

WORK REQUIRED IN THIS DWELLING UNIT.

3. REFER TO TYPICAL TWO BEDROOM UNIT "B2" TYPE - ELECTRICAL PLAN FOR

WORK REQUIRED IN THIS DWELLING UNIT.

4. REFER TO TYPICAL THREE BEDROOM UNIT "B3" TYPE - ELECTRICAL PLAN FOR

WORK REQUIRED IN THIS DWELLING.

5. SHALLOW, SURFACE MOUNTED L.E.D. "PUCK" LIGHTING FIXTURE.

A. THE NORTH BUILDING THIRD FLOOR HAS (14) TOTAL APARTMENTS, (6) TYPE B1

APARTMENTS, (7) TYPE B2 APARTMENTS, AND (1) B3 APARTMENT.

B. ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL

ELECTRICAL CODE (NEC).

C. PROVIDE HOUSEHOLD FIRE WARNING EQUIPMENT IN CONFORMANCE WITH NFPA

72 / FIRE ALARM CODE (1996 EDITION) CHAPTER 2; SPECIFICALLY 2-2.1.1.1 AND

2-2.3.

D. EACH DWELLING UNIT HAS SINGLE STATION SMOKE ALARM DEVICES WHICH

SOUND AN ALARM IN THAT DWELLING UNIT ONLY. IN EACH DWELLING UNIT THE

SMOKE DETECTORS SHALL BE HARDWIRED AND INTERLOCKED SUCH THAT ALL

SMOKE DETECTORS ALARM SIMULTANEOUSLY.

E. THE LOCATION OF DWELLING UNIT RECEPTACLES SHALL CONFORM TO NEC

210.5. EXACT DEVICE LOCATIONS MAY BE ALTERED AS FIELD CONDITIONS

REQUIRE AS LONG AS MODIFIED LOCATION STAYS WITHIN NEC PARAMETERS.

F. ALL 120V, 15 AND 20 AMP RECEPTACLES INSIDE APARTMENTS SHALL BE LISTED

TAMPER-RESISTANT RECEPTACLES PER NEC 406.11.

G. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION FOR 15 AND 20

AMP BRANCH CIRCUITS AS REQUIRED BY NEC 210.12.

(24) APARTMENTS

ELECTRICAL PLAN TH

IRD FLOOR SOUTH

- PH

ASE I

DN

DN

UP

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

BEDROOM

2

2

2

2

3

3

33

3

3

DN

DN

DN

UP

ELECTRICAL PLAN TH

IRD FLOOR NORTH

- PH

ASE II

job no:

drawn:

checked:

date:

sheet no:

AR

CH

ITE

CTS

& C

ON

TRA

CTO

RS

MA

KIN

G H

OU

SE

CA

LLS

Sheet Title:

FOW

LER ST

PARKSIDE TERRACE APARTM

ENTS

HOBBS, NM

88240

Consulting Engineers

ELECTRICAL KEYED NOTES:

GENERAL NOTES:

ELECTRICAL PLAN THIRD FLOOR NORTH - PHASE II

SCALE: 1/8" = 1'-0"

1. APARTMENT UNIT POWER PANEL, REFER TO TYPICAL APARTMENT UNIT

ELECTRICAL PLANS ON SHEETS EU1.0 AND EU1.1.

2. REFER TO TYPICAL UNIT "B1" TYPE - ELECTRICAL PLAN FOR WORK REQUIRED IN

THIS DWELLING UNIT.

3. REFER TO TYPICAL UNIT "B2" TYPE - ELECTRICAL PLAN FOR WORK REQUIRED IN

THIS DWELLING UNIT.

A. THE NORTH BUILDING THIRD FLOOR HAS (10) TOTAL APARTMENTS, (4) TYPE B1

APARTMENTS, (6) TYPE B2 APARTMENTS.

B. ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL

ELECTRICAL CODE (NEC).

C. PROVIDE HOUSEHOLD FIRE WARNING EQUIPMENT IN CONFORMANCE WITH NFPA

72 / FIRE ALARM CODE (1996 EDITION) CHAPTER 2; SPECIFICALLY 2-2.1.1.1 AND

2-2.3.

D. EACH DWELLING UNIT HAS SINGLE STATION SMOKE ALARM DEVICES WHICH

SOUND AN ALARM IN THAT DWELLING UNIT ONLY. IN EACH DWELLING UNIT THE

SMOKE DETECTORS SHALL BE HARDWIRED AND INTERLOCKED SUCH THAT ALL

SMOKE DETECTORS ALARM SIMULTANEOUSLY.

E. THE LOCATION OF DWELLING UNIT RECEPTACLES SHALL CONFORM TO NEC

210.5. EXACT DEVICE LOCATIONS MAY BE ALTERED AS FIELD CONDITIONS

REQUIRE AS LONG AS MODIFIED LOCATION STAYS WITHIN NEC PARAMETERS.

F. ALL 120V, 15 AND 20 AMP RECEPTACLES INSIDE APARTMENTS SHALL BE LISTED

TAMPER-RESISTANT RECEPTACLES PER NEC 406.11.

G. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION FOR 15 AND 20

AMP BRANCH CIRCUITS AS REQUIRED BY NEC 210.12.

E3N

KEY PLAN THIRD FLOOR

SCALE: 1" = 30' (24) APARTMENTS

LIVING

T

V

BEDROOM

DINING

STOR. PAN. COATS

CLOSET

LINEN

BATH

BALCONY

c

c

TYP6

S

S

S

S

PANEL "B1"9

KITCHEN

FC-1

SS

SS

1

3

4

F

S

TYP

TYP5

TYP7

TYP11

BEDROOM 2

BEDROOM 1

BATH

KITCHEN

STORAGE

LINEN

CLOSET

COATS

CLOSET

FC-1

LIVING

T

V

DINING

TYP6

S

SS

2

1

3

F

S

BALCONY

4

TYP

S

PANEL "B2"

SS

TYP5

TYP

7

c

c

c

SS

TYP11

S

BEDROOM 1

BEDROOM 2

BATH 1

BEDROOM 3

BATH 2

CLOSET

CLOSET

CLOSET

PAN.

COATS

STORAGE

FC-1

KITCHEN

LIVING

T

V

DINING

TYP6

S

SS

1

3

BALCONY

SS

TYP5

TYP11

4

TYP

F

SS

c

c c

c

SS

F

S

PANEL "B3"

S

S

S

2

TYP

7

BEDROOM 1

BEDROOM 2

BATH 1

BEDROOM 3

BATH 2

CLOSET

CLOSET

CLOSET

PAN.

COATS

STORAGE

FC-1

KITCHEN

LIVING

T

V

DINING

TYP6

S

SS

2

1

3

BALCONY

SS

TYP5

TYP11

4

TYP

F

SS

c

c c

c

SS

F

S

PANEL "A3"

S

S

S

S

BEDROOM 2

BEDROOM 1

BATH

KITCHEN

STORAGE

LINEN

CLOSET

COATS

CLOSET

FC-1

LIVING

T

V

DINING

TYP6

S

SS

2

1

3

F

S

BALCONY

4

TYP

S

PANEL "A2"

SS

TYP5

TYP

7

c

c

c

SS

TYP11

S

LIVING

T

V

BEDROOM

DINING

STOR. PAN. COATS

CLOSET

LINEN

BATH

BALCONY

c

c

TYP6

S

S

S

S

PANEL "A1"9

KITCHEN

FC-1

SS

SS

1

3

4

F

S

TYP

TYP5

TYP7

TYP11

DINING

LIVING

CLOSET

BATH

KITCHEN

CLOSET

COATS

LINEN

STORAGE

STORAGE

PANEL "B2"

9

FC-1

BEDROOM 1

4

TYP

c

S

F

1

2

3

BEDROOM 2

S

c

c

c

11

TYP

TYP

7

EU-1.1

TYPICAL APARTM

ENT UNIT ELECTRICAL PLANS

job no:

drawn:

checked:

date:

sheet no:

AR

CH

ITE

CTS

& C

ON

TRA

CTO

RS

MA

KIN

G H

OU

SE

CA

LLS

Sheet Title:

FOW

LER ST

PARKSIDE TERRACE APARTM

ENTS

HOBBS, NM

88240

Consulting Engineers

TYPE "A1" APARTMENT ELECTRICAL PLAN

SCALE: 3/16" = 1'-0"

TYPICAL 0F (2) APARTMENTS

TYPE "A2" APARTMENT ELECTRICAL PLAN

SCALE: 3/16" = 1'-0"

TYPICAL 0F (1) APARTMENT

TYPE "A3" APARTMENT ELECTRICAL PLAN

SCALE: 3/16" = 1'-0"

TYPICAL 0F (1) APARTMENT

TYPE "B1" APARTMENT ELECTRICAL PLAN

SCALE: 3/16" = 1'-0"

TYPICAL 0F (20) APARTMENTS

TYPE "B2" APARTMENT ELECTRICAL PLAN

SCALE: 3/16" = 1'-0"

TYPICAL 0F (27) APARTMENTS

TYPE "B3" APARTMENT ELECTRICAL PLAN

SCALE: 3/16" = 1'-0"

TYPICAL 0F (14) APARTMENTS

ELECTRICAL KEYED NOTES:

GENERAL NOTES:

A. ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL ELECTRICAL

CODE (NEC).

B. EACH DWELLING UNIT HAS SINGLE STATION SMOKE ALARM DEVICES WHICH SOUND AN

ALARM IN THAT DWELLING UNIT ONLY. IN EACH DWELLING UNIT THE SMOKE DETECTORS

SHALL BE HARDWIRED AND INTERLOCKED SUCH THAT ALL SMOKE DETECTORS ALARM

SIMULTANEOUSLY.

C. THE LOCATION OF DWELLING UNIT RECEPTACLES SHALL CONFORM TO NEC 210.5. EXACT

RECEPTACLE LOCATIONS MAY BE ALTERED AS FIELD CONDITIONS REQUIRE AS LONG AS

MODIFIED LOCATION STAYS WITHIN NEC PARAMETERS.

D. ALL 120V, 15 AND 20 AMP RECEPTACLES INSIDE APARTMENTS SHALL BE LISTED

TAMPER-RESISTANT RECEPTACLES PER NEC 406.11.

E. ALL KITCHEN GENERAL USE DUPLEX RECEPTACLES AND ALL BATHROOM DUPLEX

RECEPTACLES SHALL BE GFCI PROTECTED.

F. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION FOR 15 AND 20 AMP

BRANCH CIRCUITS AS REQUIRED BY NEC 210.12.

G. RECEPTACLES AND SWITCHES SHALL BE DECORA STYLE, WHITE IN COLOR WITH

COMPATIBLE PLASTIC PLATES, INSTALLED IN COMPLIANCE WITH ADA.

1. 50A RANGE RECEPTACLE, INSTALL 24" AFF. EXTEND 3 #6 CU AND 1 #10 E.GR. TO CIRCUIT

INDICATED.

2. SPLIT-WIRED RECEPTACLE BELOW COUNTER FOR DISPOSER AND DISHWASHER. PROVIDE

SWITCH FOR DISPOSER AT COUNTERTOP.

3. DEDICATED RECEPTACLE FOR REFRIGERATOR, INSTALL 36" AFF.

4. NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3 #12 CU TO

BREAKER IN ASSOCIATED APARTMENT PANEL.

5. TELEVISION OUTLET, REFER TO CATV RISER DIAGRAM.

6. TELEPHONE OUTLET, REFER TO TELEPHONE RISER DIAGRAM.

7. 20V COMBINATION SMOKE DETECTOR/

T PANEL.

8. DEDICATED RECEPTACLE FOR MICROWAVE ABOVE STOVE INSTALL RECEPTACLE UP 72"

AFF.

9. TYPICAL APARTMENT PANEL FOR THIS TYPE APARTMENT.

10. 120V COMBINATION SMOKE DETECTOR/

TYPE "B-CORNER" APARTMENT ELECTRICAL PLAN

SCALE: 3/16" = 1'-0"

TYPICAL 0F (2) APARTMENTS

S S

SS

S

PANEL "CC"

F F

E-1.2

COM

MUNITY CENTER AND LAUNDRY ELECTRICAL PLANS

job no:

drawn:

checked:

date:

sheet no:

AR

CH

ITE

CTS

& C

ON

TRA

CTO

RS

MA

KIN

G H

OU

SE

CA

LLS

Sheet Title:

FOW

LER ST

PARKSIDE TERRACE APARTM

ENTS

HOBBS, NM

88240

Consulting Engineers

ELECTRICAL KEYED NOTES:

GENERAL NOTES:

A. ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL ELECTRICAL

CODE (NEC).

B.

1. X

COMMUNITY CENTER LIGHTING PLAN

SCALE: 3/16" = 1'-0"

COMMUNITY CENTER POWER PLAN

SCALE: 3/16" = 1'-0"

LAUNDRY ELECTRICAL PLAN

SCALE: 3/16" = 1'-0"

job no:

drawn:

checked:

date:

sheet no:

AR

CH

ITE

CTS

& C

ON

TRA

CTO

RS

MA

KIN

G H

OU

SE

CA

LLS

Sheet Title:

FOW

LER ST

PARKSIDE TERRACE APARTM

ENTS

HOBBS, NM

88240

Consulting Engineers

ELECTRICAL SPECIFICATIONS

ESP-1.0

SECTION 26 0500- BASIC ELECTRICAL MATERIALS AND METHODS

PART 1 GENERAL

1.1 RELATED DOCUMENTS

A The Contractor shall make a thorough field investigation of all work described above and shown

on the contract drawings prior to submitting a bid on this project to ensure the bid is complete

and comprehensive.

1.2 SUMMARY

A This Section includes the following electrical materials and methods:

1. Building wire, connectors, and splices for branch circuits and feeders.

2. Supporting devices for electrical components.

B Furnish all labor and materials necessary for complete electrical service to all equipment which

requires electric connections installed as part of this project. Provide temporary electric power of

1.3 ELECTRICAL SPECIFICATION INDEX

26 0500 - Basic Electrical Materials and Methods

26 0533 - Raceways and Boxes

26 2816 - Enclosed Switches and Circuit Breakers

26 2416 - Panelboards

1.4 SUBMITTALS

A General: Electrical submittals shall be provided. The Contractor shall provide submittal

information for:

1. Panelboards

2. Safety switches

3. Fuses

4. Luminaires (Lighting Fixtures)

5. Occupancy Sensors (Controls)

6. Fire Alarm

1.5 QUALITY ASSURANCE

A Comply with the 2014 edition of NFPA 70 (NEC) for components and installation.

1.6 DRAWINGS

A All drawings included in the Contract Documents are to be considered as part of the work.

Architectural drawings shall take precedence over electrical drawings.

B As-built drawings: During project construction, the Contractor shall maintain an accurate record

of the installation of all electrical work, carefully noting any deviations from the contract

drawings. Upon project completion, the Contractor shall transfer all as-built information to a

single neat and legible drawing set.

C Upon completion of the fire alarm system installation, the contractor shall give the owner a complete

copy of the fire alarm programming manual (including passwords).

PART 2 - PRODUCTS

2.1 EQUIPMENT REQUIREMENTS

A The electrical equipment connections on the drawings are based on specific equipment

and models. Any additional costs resulting from any changes in equipment furnished will

be the complete responsibility of the Division furnishing the equipment.

2.2 BUILDING WIRE

A Description: Single conductor, copper. Solid conductor for No. 10 AWG and smaller; stranded

for larger than No. 10 AWG. Aluminum feeders of same capacity as copper may be used.

2.3 SUPPORTING DEVICES

A Channel and angle support systems, hangers, anchors, sleeves, brackets, fabricated items, and

fasteners are designed to provide secure support from the building structure for electrical

components.

1. Material: Steel, except as otherwise indicated, protected from corrosion with zinc coating or

with treatment of equivalent corrosion resistance using approved alternative finish or

inherent material characteristics.

2. Metal Items for Use Outdoors or in Damp Locations: Hot-dip galvanized steel, except as

otherwise indicated.

B Steel channel supports have 9/16-inch diameter holes at a maximum of 8 inches o.c., in at least 1

surface.

1. Fittings and accessories mate and match with channels and are from the same

manufacturer.

C Nonmetallic Channel and Angle Systems: Structural-grade, factory-formed, fiberglass-resin

channels and angles with 9/16-inch diameter holes at a maximum of 8 inches o.c., in at least one

surface.

1. Fittings and accessories shall mate with channels or angles and be of the same manufacturer.

2. Fitting and Accessory Material: Same as channels, except metal items may be stainless steel.

2.4 ELECTRICAL IDENTIFICATION

A Use colors prescribed by ANSI A13.1 and NFPA 70. Color code all wiring as follows: For 208/120V:

Phase A-Black; Phase B-Red; Phase C-Blue; Neutral-White; Ground-Green. For 480/277V:

2.5 TOUCH-UP PAINT

A For Equipment: Provided by equipment manufacturer and selected to match equipment finish.

B For Non-equipment Surfaces: Matching type and color of undamaged, existing adjacent finish.

PART 3 - EXECUTION

3.1 EQUIPMENT INSTALLATION REQUIREMENTS

A Where components and equipment are indicated to be installed, the term "install" includes all

work, materials, and associated accessories necessary to obtain a completely operational system.

B Install items level, plumb, and parallel and perpendicular to other building systems and

components, except where otherwise indicated.

3.2 WIRING METHODS

A Feeders: Type THHN/THWN, in copper conductor, RHW or XHHW in aluminum conductor, in

raceway, except as otherwise indicated. Branch Circuits: Type THHN/THWN, in raceway or type

MC Cable or type NM, NMC or NMS where allowed by NEC and State of New Mexico codes.

B Type MC cable shall be acceptable where in compliance with current NEC.

3.3 ELECTRICAL SUPPORTING METHODS

A Damp Locations and Outdoors: Hot-dip galvanized materials.

B Dry Locations: Steel materials.

C Strength of Supports: Adequate to carry all present and future loads, times and safety factor of at

least 4; 200-lb-minimum design load.

3.4 INSTALLATION

A Install wires in raceway according to manufacturer's written instructions and NECA's "Standard

of Installation". Coordinate special systems work with Owner and Cabling Contractor.

B Conductor Splices: Keep to the minimum possible.

C Install devices to securely and permanently fasten and support electrical components.

D Raceway Supports: Comply with NFPA 70 and the following requirements:

1. Conform to manufacturer's recommendations for selecting and installing supports.

E Fire stopping: Apply to cable and raceway penetrations of fire-rated floor and wall assemblies.

Perform fire stopping to reestablish the original fire-resistance rating of the assembly at the

penetration.

F Fastening: Unless otherwise indicated, securely fasten electrical items and their supporting

Install identification devices where required.

1. Install labels where indicated and at locations for best convenience of viewing.

3.5 DEMOLITION

A Where electrical work to remain is damaged or disturbed in the course of the Work, remove

damaged portions and install new products of equal capacity, quality, and functionality.

3.6 CUTTING AND PATCHING

A Cut, channel, chase, and drill floors, walls partitions, ceilings, and other surfaces necessary for

electrical installations. Perform cutting by skilled mechanics of the trades involved.

B General Contractor shall pair disturbed surfaces to match adjacent undisturbed surfaces.

3.7 TESTING

A Perform complete testing on all systems to ensure proper operation.

END OF SECTION 26 0500

SECTION 26 0533 - RACEWAYS AND BOXES

PART 1 GENERAL

1.1 SECTION INCLUDES

A Conduits and fittings

B Outlet boxes

1.2 QUALITY ASSURANCE

A Comply with the current National Electrical Code (NEC) for installation.

PART 2 PRODUCTS

2.1 COATINGS

A Provide products with zinc coating or with treatment of equivalent corrosion resistance.

2.2 INTERMEDIATE METAL CONDUIT AND FITTINGS (IMC)

A Furnish intermediate metal conduit (IMC) that meets the requirements of UL1242 - Intermediate

Metal Conduit, ANSI C80.6 - Electrical Intermediate Conduit (IMC).

B Furnish zinc-plated, threaded, malleable iron fittings and conduit bodies that meet the

requirements of UL514B - Fittings for Conduit and Outlet Boxes, and ANSI/NEMA FB1 - Fittings,

Cast Metal Boxes, and Conduit Bodies for Conduit and Cable Assemblies.

2.3 ELECTRICAL METALLIC TUBING AND FITTINGS (EMT)

A Furnish galvanized electrical metallic tubing (EMT) that meets the requirements of UL797 -

Electrical Metallic Tubing, NEMA C80.3 - Steel Electrical Metallic Tubing (EMT).

B Furnish compression or set-screw type fittings that meet the requirements of UL514B - Fittings

for Conduit and Outlet Boxes, and ANSI/NEMA FB1 - Fittings, Cast Metal Boxes, and Conduit

Bodies for Conduit and Cable Assemblies. Furnish insulated throat connectors.

2.4 FLEXIBLE METAL CONDUIT AND FITTINGS

A Furnish galvanized steel flexible metal conduit that meets the requirements of UL1 - Flexible

Metal Electrical Conduit.

2.5 LIQUID-TIGHT FLEXIBLE METAL CONDUIT AND FITTINGS

A Furnish liquid-tight flexible metal conduit that meets that requirements of UL360 - Liquid-Tight

Flexible steel Conduit, Electrical.

2.6 OUTLET BOXES

A Provide outlet boxes selected for specific installations using the guidance in NEMA OS 3, Selection

and Installation Guidelines for Electrical Outlet Boxes, and the requirements of this Selection.

B For dry locations provide galvanized steel outlet boxes that comply with UL Standard 514-A -

Metallic Outlet Boxes and ANSI/NEMA OS1 - Sheet-Steel Outlet Boxes, Device Boxes, Device

Boxes, Covers, and Box Supports.

C For damp or wet locations and for surface-mounted RMC or IMC raceways systems, provide

outlet boxes that comply with UL Standard 498 and 514, ANSI/NEMA FB1.

2.7 PULL AND JUNCTION BOXES

A For dry locations in clean, non-contaminated environments use galvanized sheet steel pull and

junction boxes that comply with UL Standard 50 Type 1 and the NEC as to size and construction.

Use boxes not less than 4 inches square x 1-1/2 inches deep with screw-secured covers. Provide

larger boxes as required by the number and size of conduits and conductors.

B For damp or wet, non-corrosive locations, in conduit runs 1 inch trade size and larger, provide

galvanized sheet-steel pull and junction boxes and covers that comply with UL 50 Type 3R.

PART 3 EXECUTION

3.1 EXISTING WORK

A Remove all exposed abandoned raceways, including abandoned raceways above accessible

ceiling finishes, to the point that non-removable building construction (e.g. concrete or masonry)

covers the raceway. Cut raceways flush with non-removable building construction.

B Disconnect abandoned outlets and remove devices. Remove abandoned outlets when raceway is

abandoned and removed. Install blank cover for abandoned outlets not removed.

3.2 EXAMINATION

A Examine surfaces to receive raceways and boxes for compliance with installation tolerances and

other conditions affecting performance of the raceway system. Do not proceed with installation

until unsatisfactory conditions have been corrected.

3.3 GENERAL

A Install complete systems of raceways and boxes for wiring systems.

B Install raceways and boxes according to NECA 1 Standard Practices for Good Workmanship in

Electrical Construction.

C Raceway termination points and box locations shown on the Drawings are in approximate

locations unless dimensioned. Verify locations before rough-in.

D Raceway routing is shown on the Drawings in approximate locations unless dimensioned.

Coordinate routing with structure and with work of other trades. Route as required for a

complete wiring system.

E Ground and bond raceways and boxes as required by the NEC.

F Support raceways and boxes in accordance with the NEC. Arrange raceways and boxes to

maintain headroom and present a neat, workmanlike appearance.

3.4 CONDUIT INSTALLATION

A For wiring systems less than 1000 volts use conduit materials in accordance with the NEC.

B Use 3/4-inch or larger conduit to enclose multiple conductors larger than 12 AWG. For

C Conceal conduits, unless noted otherwise on drawings, within walls, floors and ceilings.

D Install insulating bushing or connectors with an insulated throat to protect conductors or cables

at conduit terminations.

E Join nonmetallic conduit using cement as recommended by manufacturer.

F Install plastic-coated RMC and fittings according to the NEC and manufacturer's instructions. Use

only fittings approved for use with that material. Patch all nicks and scrapes in PVC coating after

installing conduits.

G Do not use RNC 90 degree elbows larger than 3 inch trade size; use plastic-coated RMC,

tape-wrapped RMC, or rape-wrapped IMC for 3-1/2 inch trade size and larger 90 degree elbows.

H Maintain the following minimum clearances between conduit and surfaces with temperatures

exceeding 104 degrees F (40 degrees C):

1. 6" at perpendicular crossings, 12" between parallel runs.

3.5 OUTLET BOX INSTALLATION

A Install outlet boxes with centers at the following heights unless noted otherwise on the Drawings:

1. Receptacles, general use duplex type: 18 inches to center of j-box above finished floor (AFF).

3. Light switches: center 44 inches AFF to center and within 6 inches of door frame.

5. Fire alarm audible/visible alarm devices: center of strobe light 80 inches AFF or 6 inches below

the ceiling, whichever is lower.

6. Fire alarm pull stations: center 44 inches AFF to center.

B Install a multi-gang box where more than one device is mounted together. Do not use sectional

type boxes. Mount multiple controls as close together as possible and in-line with each other.

C Install box with plaster ring for single or multiple device outlets.

D Use flush mounted outlet boxes in finished areas.

F Install a blank cover plate on each outlet box in which no device is installed.

3.6 CLEANING

A Clean interior of boxes to remove dust, debris, and other material.

B Repair damage to galvanized finishes with zinc-rich paint recommended by manufacturer.

C Repair damage to paint finishes with matching touch-up coating recommended by the

manufacturer.

END OF SECTION 26 0533

SECTION 26 2816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

PART 1 GENERAL

1.1 SECTION INCLUDES

A Safety switches

B Fuses

C Enclosed circuit breakers

1.2 SUBMITTALS

A Submit the following:

1. Product Data: Submit manufacturer's technical data for each type of safety switch and

enclosed circuit breaker. Provide catalog sheets showing voltage, current ratings, short

circuit ratings, dimensions, and enclosure details.

1.3 QUALITY ASSURANCE

A Comply with the current National Electrical Code (NEC) for components and installation.

B Provide safety switches and circuit breaks that are listed and labeled by a Nationally Recognized

Testing Laboratory (NRTL) for the application, installation condition, and the environment in

which installed.

C Comply with the following standards as applicable:

1. NEMA AB 1 (UL 489) Molded Case Circuit Breakers, Molded Case Switches, and Circuit

Breaker Enclosures.

2. UL 50 - Enclosures for Electrical Equipment.

PART 2 PRODUCTS

2.1 SAFETY SWITCHES

A Provide NRTL-listed, NEMA KS 1 Type HD safety switches with ratings and number of poles as

indicated on the Drawings. Use Type HD for switches rated 100A and above.

B Provide safety switches for use as service equipment that are NRTL labeled for the application.

C Provide enclosure type in accordance with NEMA ratings as required by the conditions of

installation and use.

D For fusible safety switches provide rejection clip designed to accommodate NEMA FU 1, Class R.

E Furnish each safety switch with an equipment ground bar.

F Furnish a neutral bar for each safety switch used on a circuit that includes a grounded "neutral"

G Provide each safety switch with a factory-installed cover-mounted viewing window positioned

over the blades to allow visual verification of ON-OFF status.

H Provide auxiliary electrical interlock switches with safety switches as indicated on the Drawings

or as required by the application.

2.2 FUSES

A Provide NRTL-listed, NEMA FU 1 Class R fuses for fusible safety switches as indicated on the

Drawings, required by the NEC, or required by the manufacturer of served equipment.

2.3 ENCLOSED CIRCUIT BREAKERS

A Provide NRTL-listed, NEMA AB 1 enclosed molded-case circuit breakers with ratings and number

of poles and indicated on the Drawings or as required by NEC.

PART 3 EXECUTION

3.1 EXAMINATION

A Examine surfaces to receive safety switches and enclosed circuit breakers for compliance with

installation tolerances and other conditions affecting performance of the product. Do not proceed

with installation until unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A Install safety switches and enclosed circuit breakers where indicated on the Drawings and

according to manufacturer's instructions, NECA 1, and the NEC. Have the manufacturer's

installation instruction available at the construction site.

B Install each safety switch and enclosed circuit breaker so the interlock bypass will be accessible.

C Provide supports and seismic anchorage in accordance with the manufacturer's installation

instructions.

D Ground and bond safety switches and enclosed circuit breakers as required by NEC.

E Install conduits as required in Section 26 0533 Raceways and Boxes for Electrical Systems.

F Install conductors as required in Section 26 0519, Low Voltage Electrical Power Conductors and

1. Use compression type lugs to connect all service, feeder, and branch circuit cables to

enclosed circuit breakers rated greater than 100 amperes, unless approved otherwise by

2. Tighten electrical connectors and terminals to the manufacturer's published torque

tightening values. Where manufacturer's torque values are not indicated, use those

specified in UL 486A.

G Install fuses in fusible safety switches as indicated on the Drawings or as required to match

installed motor or load characteristics.

3.3 IDENTIFICATION

A Identify safety switches and enclosed circuit breakers with unit name and circuit number.

3.4 FIELD QUALITY CONTROL

A Clean interior and exterior of safety switches and enclosed circuit breakers.

B Verify that ratings for safety switches and enclosed circuit breakers match values indicated on

the Drawings.

SECTION 26 2416 - PANELBOARDS

PART 1 GENERAL

A Power panelboards

1.2 SUBMITTALS

A Submit the following:

1. Catalog data: Submit catalog data describing each type panelboard, accessory item,

and component specified. Include data substantiating that materials comply with

specified requirements.

1.3 QUALITY ASSURANCE

A Comply with the current National Electrical Code (NEC) for installation.

PART 2 PRODUCTS

2.1 PANELBOARDS, GENERAL REQUIREMENTS

A Provide panelboard cabinets for flush or surface mounted as indicated on the Drawings.

1. Furnish NEMA Type 1 enclosures, except where the Drawings indicate the following

enclosure requirements: NEMA 3R - Raintight

2. Provide galvanized steel cabinets constructed according to UL 50 requirements.

B Provide trim fronts that meet the strength and rigidity requirements of UL 50.

1. Fronts for flush panels shall overlap boxes at least 1 inch.

2. Fronts shall have ANSI 49 medium gray enamel.

3. For NEMA 1 panel boards, provide fronts with hinged trim construction having a piano

hinge down one side. The front shall contain a smaller lockable door, which when open,

shall provide access to all conductors and wiring terminals.

4. Provide a metal panelboard directory frame mounted inside the panelboard door.

C Panelboard phase and neutral bus shall be copper.

D Provide compression type lugs for mains plus all feeder and branch circuits 100 amperes and

larger; smaller lugs shall be mechanical type.

E Provide copper equipment ground bus that is adequate for feeder and branch circuit equipment

ground conductors. Bond ground bus to cabinet.

F Provide thermal-magnetic circuit breakers that meet the requirements of UL 489 Molded Case

Circuit Breakers and NEMA AB 1 Molded Case Circuit Breakers and Molded Case Switches.

2.2 LIGHTING AND APPLIANCE PANELBOARDS

A Provide lighting and appliance branch circuit panelboards as indicated on the Drawings.

B Lighting and appliance branch circuit panelboards enclosures shall be not less than 20 inches or

more than 26 inches in width.

C Manufacturers:

1. Cutler-Hammer: PRL3a (480Y/277V) and PRL1a and PRL2a (208Y/120V or 120/240V).

2. General Electric: Spectra (480Y/277V) and AQ (208Y/120V or 120/240V).

3. Siemens: P2 (480Y/277V) and P1 (208Y/120V or 120/240V).

4. Square D: I-Line (480Y/277V) and NQOD (208Y/120V or 120/240V).

2.3 LIGHTING AND APPLIANCE LOAD CENTERS

A Provide lighting and appliance branch circuit load centers as indicated on the Drawings.

B Load centers identified for use as service equipment are to be labeled for this application.

C A directory label shall be provided with circuits identified as indicated on the schedule.

D Bus bar connections to the branch circuit breakers shall be the distributed phase type and shall

accept plug on circuit breakers.

E Manufacturers:

1 Cutler Hammer, General Electric, Siemens or Square D

PART 3 EXECUTION

A Examine surfaces to receive panelboards for compliance with installation tolerances and other

installation instructions.

3.2 INSTALLATION

A Install panelboards where indicated on the Drawings and according to manufacturer's

instructions, NECA 407, and the NEC.

B Ground and bond panelboards as required by NEC.

C At all flush panelboards install four 1-inch spare conduits, extend to above accessible ceiling space.

3.3 IDENTIFICATION

A Provide typewritten circuit directories for each branch circuit panel board. Revise directories to

reflect field circuiting changes including any changes required to balance phase loads.

3.4 FIELD QUALITY CONTROL

A Clean, inspect, test, and energize installed panel boards in accordance with NECA 407.

B After completing installation, cleaning, and testing, touch up scratches and mars on finish to

match original finish.

END OF SECTION 26 2916

END OF SECTION 26 2816

3.1 EXAMINATION

Cables.

engineer.

1.1 SECTION INCLUDES

4. Thermostats: center 44 inches AFF to center.

7. Dry-type transformers

C Upsize circuits and feeders as necessary to limit overall voltage drop to the furthest outlet on a

branch circuit to 8% maximum (NMEC).

B Duplex receptacles and wall switches shall be rated 20A.

C Fuses shall be dual element Buss Fusetrins unless noted otherwise.

D Safety switches rated 100A and above shall be heavy-duty rated.

Where shown within two feet of each other, group voice/data outlets and receptacles together.

2. Voice/data outlets: 18 inches AFF to center.

3.9 TOUCH-UP PAINT

A Thoroughly clean damaged areas and provide primer, intermediate, and finish coats.

I Install pull string in all empty and spare conduits.

B Provide plastic nameplates for power panels. Nameplate to include panel designation, voltage,

and phase, e.g. PANEL "MRA" / 120/208V / 3-PHASE.

3.8 TRAINING

A Instruct Owner's personnel in the proper operation of electrical systems.

sufficient capacity to allow construction.

home-run circuits, conduit shall be a minimum of 3/4".

D Home-run conduits (all conduits connected to a panel) shall be a minimum of 3/4 inch.

J Any conduit run below slab on grade shall be a minimum of 6" below slab.

conductor.

B Provide a lime green spare fuse cabinet with "Fuses" stenciled in OSHA purple. Cabinet shall be

sized to hold one set of (3) fuses of each size used on this project.

H Install spare fuse cabinet in main electrical room or alternate location as shown on Drawings.

PART 1 GENERAL

1.1 SUMMARY

A. SECTION INCLUDES

1. Receptacles, Snap switches, Dimmer switches, Wall plates, Multi-outlet assemblies.

1.2 QUALITY ASSURANCE

A. Furnish products listed and labeled by a nationally recognized testing laboratory (NRTL) for the

PART 2 PRODUCTS

2.1 RECEPTACLES

A. 120V convenience receptacles connected to general use branch circuits: Provide straight-blade

NEMA 5-20R, 20A, duplex receptacles.

B. 120V ground fault circuit interrupter (GFCI) receptacles: Provide straight-blade NEMA 5-20R, 20A,

feed-through type, self-testing GFCI, duplex receptacles that meet the requirements of UL

Standard 943, Ground Fault Circuit Interrupters. .

C. 120V exterior duplex receptacles: Provide GFCI type with integral weather-resistant (WR) cover.

2.4 SNAP SWITCHES

A. Provide single pole, double pole, three-way, four-way and pilot handle snap switches as indicated

on the Drawings.

B. Switches shall be rated 20A, 120-277 volts AC, back and side wired, screw pressure terminal,

quiet type AC switch with yoke grounding screw. .

2.5 WALLBOX DIMMING CONTROLS

A. Dimmer wattage rating shall exceed connected load by 10 percent minimum, contractor shall verify

load indicated on the Drawings matches actual fixtures/lamps supplied.

2.6 WALL PLATES

A. For flush mounted interior receptacles and wall switches, provide compatible plastic cover plate,

ivory in color.

PART 3 EXECUTION

3.1 PREPARATION

A. Verify outlet boxes are installed at proper locations and heights.

3.2 INSTALLATION

A. Install devices plumb, level, and secure.

B. All duplex receptacles in dwelling units shall be tamper-resistant in accordance with NEC 406.12.

C. All duplex receptacles in dwelling units shall be AFCI protected in accordance with NEC 210.12.

D. All duplex receptacles within 6' of a sink or bathtub/shower stall, in bathrooms, in garages, and in

laundry area shall be GFCI protected in accordance with NEC 210.8.

E. Install wall plates on each switch, receptacle, and blank outlet after painting is complete.

F. Install receptacle for electric water cooler (EWC) within EWC cabinet.

3.4 IDENTIFICATION

A. Identify wiring devices with circuit number written on back of cover plate using permanent ink pen

.

3.5 FIELD QUALITY CONTROL

A. Operate each switch and receptacle at least six times with circuit energized.

SECTION 26 2726 - WIRING DEVICES

26 2726 - Wiring Devices

END OF SECTION 26 2726

Phase A-Yellow; Phase B-Brown; Phase C-Orange; Neutral-White; Ground-Green.