Parasolo™ PVC Details
2
Table of Contents
Detail Number Page Number100A Parafast RhinoBond Staggered Insulation Board Layout Detail 1
100B Parafast Rhinobond Assembly Detail 2
101A Roof Membrane Layout Mechanically Attached 3
101B Roof Membrane Layout Adhered Detail 4
102A Side Lap Detail Mechanically Attached 5
102B Side Lap Detail Fully Adhered System 6
103 Cover Strip End Lap Detail 7
104 End Lap Detail 8
107 Parafast RhinoBond Fastening Zones
Locations Over Approved Steel or Concrete Decks 9
108 Parafast RhinoBond Fastening Zones Locations
Over Wood Decks 10
110A Ridge Detail 11
111A Parafast RhinoBond Standard Fastening Pattern
over Approved Steel or Concrete Decks Detail 12
111B Parafast RhinoBond Standard Fastening Pattern
Over Wood Decks Detail 13
112 Change of Deck Plane Detail 14
113 Valley Detail 15
121 Parafast RhinoBond Insulation Fastening Pattern
Approved Steel or Concrete Decks Detail 16
122 Parafast RhinoBond Insulation Fastening Pattern
Approved Steel or Concrete Decks Detail 17
202 Coated Metal Roof Edge Detail 18
204 Coated Metal Joint Detail 19
205 Paraguard Extruded Edge Detail 20
206 Paraguard M Raised Edge Detail 21
211 Gutter with Coated Metal Edge Detail 22
301 Parapet Wall Flashing with Counter Flashing 23
302 Wall and Curb Flashing with Termination Bar Detail 24
303 New Construction with Wall Cap Detail 25
304 Wall Flashing with Coated Metal Edge Detail 26
307A Alternate Wall Base Termination Detail 27
307B Parafast RhinoBond Base Tie In at Angle Change Detail 28
311 Coated Metal Wall Scupper Detail 29
312 Door Threshold Flashing Detail 30
314 Vertical Wall Edge Termination with Coated Metal Detail 31
315 RhinoBond Wall Flashing Fastening Pattern Detail 32
3
317A High Wall Flashing Detail - 10 ft Sheet 33
317B High Wall Flashing Detail - 5 ft Sheet 34
317C High Wall Flashing Detail With Plates and Fasteners 35
317D High Wall Flashing Detail - Intermittent fastening 36
318A Termination Details 1-3 37
318B Termination Details 4-5 38
319 Counter Flashing Re-Roof Detail 39
325 Corner Curb Wrap Detail 40
327A Inside Corner Reinforcement - Preformed Corner Detail 41
327D Inside Corner Reinforcement - Field Fabrication Detail 42
328A Inside Corner Fabrication - 2 Step Joint Patch Up Detail 43
328B Inside Corner Fabrication - 2 Step Joint Patch-Down Detail 44
329A Outside Corner Reinforcment - Universal Corner Detail 45
401B Field Fabricated Expansion Joint - Flat Type Detail 46
402B Field Fabricated Expansion Joint - Curb Type Detail 47
403B Field Fabricated Wall Expansion Joint Detail - Flat Type Detail 48
404B Field Fabricated Wall Expansion Joint Detail - Curb Type 49
503A Termination At RTU With Welded Lap 50
503B Termination At RTU With Counter Flashing 51
507 Field-Wrapped Penetration Flashing Detail 52
508 High Temperature Stack Flashing Detail 53
510A Penetration with Parapro Flashing - Option 1 54
510B Penetration with Parapro Flashing - Option 2 55
511 Exposed Wood Equipment Support Sleeper Detail 56
512 Concealed Wood Equipment Support Detail 57
513 Drain - Standard Flashing 58
518 Drain - Severe Sump Target Detail 59
519 Drain - Pre Target Detai 60
520 Drain - Post Target Detail 61
525 Pourable Sealant Pocket 62
526A Conical Pipe Boot (Non-Split) 63
526B Conical Pipe Boot (Split) 64
602 Curb Type Tie-In at Flat Roof Detail 65
604 Heat-Welded Walkway Installation Detail 66
605 Lightning Protection Terminal - Roof Mount Detail 67
607 Lightning Protection Terminal - Wall Mount Detail 68
608 Satellite Dish Mounting Detail 69
1
PARAFAST STAGGERED INSULATIONBOARD LAYOUT DETAIL
NOTES:
1. REFER TO THE PARASOLO DESIGN & APPLICATION GUIDELINES FOR DETAILED INSTALLATIONREQUIREMENTS.
2. INSULATION BOARDS INSTALLED IN SINGLE OR MULTIPLE LAYERS MUST HAVE THE JOINTS BETWEENTHE BOARDS STAGGERED IN ALL DIRECTIONS A MINIMUM OF 6" (152 mm) BETWEEN LAYERS.
3. INSULATION BOARDS INSTALLED OVER STEEL DECKING MUST HAVE BOARDS PLACEDPERPENDICULAR TO DECK FLUTES WITH EDGES OVER FLUTE SURFACE FOR BEARING SUPPORT.
ROOF INSULATION-FIRST LAYER
APPROVED ROOF DECK ORSUBSTRATE
APPROVED COVERBOARD OR ROOFINSULATION (IF REQUIRED).-SECOND LAYER
SECTION VIEW
SEE NOTE #2
6" MIN.(152 mm)
ROOF DECK
SECOND INSULATION LAYER
FIRST INSULATION LAYER
PLAN VIEW
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
100ATHIS DETAIL APPLIES TO:
08-26-2019FIELD OF ROOF SERIES
R
PARASOLO ROOF MEMBRANE SYSTEMTM
2
PARAFAST RHINOBOND ASSEMBLYDETAIL
NOTES:
1. REFER TO THE PARAFAST RHINBOND ATTACHMENT TABLES FOR DETAILED INSTALLATIONREQUIREMENTS REGARDING DECK TYPE, PLATE & FASTENER TYPE, AND MIN. EMBEDMENT.
2. TOP LAYER OF INSULATION DOES NOT HAVE TO BE STAGGERED IF BASE LAYER IS STAGGERED.
ROOF INSULATION
PARAFAST RHINOBONDPLATES & FASTENERS
REINFORCED PARASOLO MEMBRANE (SMOOTH ONLY)
METAL DECK
APPROVED COVERBOARD ORSECOND LAYER OF INSULATION IFREQUIRED. SEE NOTE 2
APPROVED FLUTE FILLERIF REQUIRED
AIR/VAPOR RETARDER-AS REQUIRED
PLATE WELDED DETAIL
INDUCTION HEAT-WELD
PARAFAST RHINOBOND 3" (76 mm) PLATE
PVC= BLACK PLATE
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
www.siplast.com
DRAWING #
100BTHIS DETAIL APPLIES TO:
08-26-2019FIELD OF ROOF SERIES
R
PARASOLO ROOF MEMBRANE SYSTEMTM
R
HEAT INDUCTIONSYSTEM
3
ROOF MEMBRANE LAYOUTMECHANICALLY ATTACHED
1. SEE PARASOLO MECHANICALLY ATTACHED SYSTEM GUIDELINES TO DETERMINE FASTENER SPACING FORVARIOUS DECK TYPES AND WIND UPLIFT REQUIREMENTS, AND FOR REQUIRED NUMBER OF PERIMETERHALF SHEETS.
NOTES:
HEAT-WELDED SEAMS
PARAFAST PLATES & FASTENERS
TYPICAL PARASOLO PERIMETER HALFSHEETS
ALTERNATE
REFERENCE PARASOLO 200 SERIESROOF EDGE FLASHING DETAILS FOREDGE TERMINATION
REFERENCE PARASOLO 300 SERIESPARAPET WALL & CURB FLASHING DETAILSFOR WALL TERMINATION
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
www.siplast.com
DRAWING #
101ATHIS DETAIL APPLIES TO:
08-26-2019PARAPET WALL & CURB SERIES
PARAPET WALL
PAR
APET
WAL
L
PARASOLO MEMBRANE
PARASOLO ROOF MEMBRANE SYSTEMTM
MECHANICALLYATTACHEDSYSTEMS
4
ROOF MEMBRANE LAYOUT ADHEREDDETAIL
REFERENCE PARASOLO 200SERIES ROOF EDGE FLASHINGDETAILS FOR EDGE TERMINATION
REFERENCE PARASOLO 300 SERIESPARAPET WALL & CURB FLASHINGDETAILS FOR WALL TERMINATION
1. SEE PARASOLO ADHERED SYSTEM TECHNICAL GUIDELINES TO DETERMINE PERIMETER ANDPENETRATION FASTENER SPACING FOR VARIOUS DECK TYPES AND WIND UPLIFT REQUIREMENTS.
NOTES:
PARASOLO MEMBRANE
ALTERNATE
HEAT-WELDED SEAMS
SEE NOTE 1
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
www.siplast.com
DRAWING #
101BTHIS DETAIL APPLIES TO:
09-10-2019PARAPET WALL & CURB SERIES
PARAPET WALL
PAR
APET
WAL
L
PARASOLO ROOF MEMBRANE SYSTEMTM
ADHEREDSYSTEMS
5
NOTES:
1. FOR HEAT-WELDING LAPS USE 1.5" MIN. (25.4 mm) WELD WITH AUTOMATIC MACHINE WELDERAND 2" MIN. (127 mm) WELD WITH HAND WELDER.
ROOF INSULATION
ROOF DECK/SUBSTRATE
HEAT-WELDED LAP (SEE NOTE #1)
REINFORCED PARASOLO MEMBRANE
SIDE LAP DETAIL MECHANICALLYATTACHED
6" (152 mm)
PARAFAST FASTENERS & PLATES 12" (305 mm) O.C. MAX
REINFORCED PARASOLOMEMBRANE FIELD SHEETS(NOT TO SCALE)
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
www.siplast.com
DRAWING #
102ATHIS DETAIL APPLIES TO:
08-26-2019FIELD OF ROOF SERIESPARASOLO ROOF MEMBRANE SYSTEM
TM
MECHANICALLYATTACHEDSYSTEMS
6
SIDE LAP DETAIL FULLY ADHEREDSYSTEM
NOTES:
ROOF INSULATION
ROOF DECK/SUBSTRATE
HEAT-WELDED LAP (SEE NOTE #1)
REINFORCED PARASOLO MEMBRANE
1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN.WELD WITH HAND WELDER.
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
www.siplast.com
DRAWING #
102BTHIS DETAIL APPLIES TO:
09-10-2019FIELD OF ROOF SERIES
3" (76 mm)min.
PARASOLO ROOF MEMBRANE SYSTEMTM
ADHEREDSYSTEMS
7
NOTES:
ROOF INSULATION
ROOF DECK/SUBSTRATE
REINFORCED PARASOLO MEMBRANE
HEAT-WELDED LAP (SEE NOTE #1)
COVER STRIP END LAP DETAIL
PARASOLO FLASHING STRIP ACCESSORY OR 8" (203 mm) WIDEREINFORCED PARASOLO MEMBRANE
THIS DETAIL REQUIRED FOR ALLFLEECE-BACK MEMBRANES ANDOPTIONAL FOR ALL OTHER LISTEDSYSTEMS BELOW
PARASOLO T-JOINT COVERPATCHES REQUIRED IFFIELD FABRICATED STRIP IS80 MIL REINFORCEDPARASOLO MEMBRANE.
REINFORCED PARASOLOMEMBRANE FIELD SHEETS(NOT TO SCALE)
8" (203 mm)
2" (51 mm)
2" (51 mm)
1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITHHAND WELDER.
PARAFAST PLATES ANDFASTENERS (MECHANICALLYATTACHED SYSTEMS ONLY)
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
103THIS DETAIL APPLIES TO:
08-26-2019FIELD OF ROOF SERIES
TM
PARASOLO ROOF MEMBRANE SYSTEMTM
8
END LAP DETAIL
NOTES:
ROOF INSULATION
ROOF DECK/SUBSTRATE
HEAT-WELDED LAP (SEE NOTE #2)
REINFORCED PARASOLO MEMBRANE
REINFORCED PARASOLOMEMBRANE FIELD SHEETS(NOT TO SCALE)
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
104THIS DETAIL APPLIES TO:
08-26-2019FIELD OF ROOF SERIES
3" (76 mm)MINIMUM
1. PARASOLO T-JOINT PATCH REQUIRED FOR 80 MIL PARASOLO MEMBRANE, REFER TO PARASOLO DETAIL 105.
2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
9
FIELD OF ROOF SERIES
PARAFAST RHINOBOND INSULATIONFASTENING ZONES/LOCATIONS APPROVED
STEEL OR CONCRETE DECKS
CO
RN
ER
CORNERRAISED ROOF EDGEOR PARAPET WALL
1. SEE PARASOLO SYSTEM GUIDELINES IN SPECIFICATIONS TO DETERMINE FIELD PERIMETER, AND CORNERFASTENER PLACEMENT FOR VARIOUS DECK TYPES AND WIND UPLIFT REQUIREMENTS.
2. IF A PORTION OF A BOARD EXTENDS INTO ANOTHER ZONE, IT MUST DEFER TO THE ZONE OF THE GREATERFASTENING PATTERN.
NOTES:
8'(2.44 m)
PERIMETER
4'(1.22 m)
4'(1.22 m)
4'(1.22 m)
4'(1.22 m)
FIELD
PER
IMET
ERFI
ELD
FIELD
PERIMETER
CORNER
ZONE LEGEND
6 FASTENERS PER BOARD
12"
36"
36"
12"
12" 12"24"
12"
36"
36"
12"
12"
8"
16"
8"
12" 12"24"
16"
16"
16"
16"
9 FASTENERS PER BOARD
12 FASTENERS PER BOARD
CORNERC
C
B
A
B
PERIMETERB
FIELDA
TRANSITION
SEE NOTE #2
PERIMETERFASTENING
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
www.siplast.com
DRAWING #
107THIS DETAIL APPLIES TO:
08-27-2019
RR
12" 12" 12"
PARASOLO ROOF MEMBRANE SYSTEMTM
HEAT INDUCTIONSYSTEMS
10
PARAFAST RHINOBOND INSULATIONFASTENING ZONES/LOCATIONS, APPROVED
WOOD DECKS
CO
RN
ER
CORNERRAISED ROOF EDGEOR PARAPET WALL
1. SEE PARASOLO SYSTEM GUIDELINES IN SPECIFICATION MANUAL TO DETERMINE FIELD, PERIMETER ANDCORNER FASTENER PLACEMENT FOR VARIOUS DECK TYPES AND WIND UPLIFT REQUIREMENTS.
2. IF A PORTION OF A BOARD EXTENDS INTO ANOTHER ZONE, IT MUST DEFER TO THE ZONE OF THE GREATERFASTENING PATTERN.
NOTES:
8'(2.44 m)
PERIMETER
4'(1.22 m)
4'(1.22 m)
4'(1.22 m)
4'(1.22 m)
FIELD
PER
IMET
ERFI
ELD
FIELD
PERIMETER
CORNER
ZONE LEGEND
8 FASTENERS PER BOARD
12"
24"
12"
12" 12"24"
6"
24"
6"
12 FASTENERS PER BOARD
16 FASTENERS PER BOARD
CORNERC
C
B
A
B
PERIMETERB
FIELDA
TRANSITION
SEE NOTE #2
8"
12" 12"24"
12"6"
PERIMETERFASTENING
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
www.siplast.com
DRAWING #
108THIS DETAIL APPLIES TO:
08-27-2019FIELD OF ROOF SERIES
R
24"
24"
12" 12" 6"
16"
16"
16"
16"
16"
8"
24"
24"
PARASOLO ROOF MEMBRANE SYSTEMTM
R
HEAT INDUCTIONSYSTEMS
11
RIDGE DETAIL
ROOF DECK/ SUBSTRATE
ROOF INSULATION
FOR MECHANICALLY ATTACHEDSYSTEMS OVER 2:12 USE A HALF SHEETOF MEMBRANE AS A CAP
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
110ATHIS DETAIL APPLIES TO:
08-28-2019
REFER TO APPROPRIATEPARASOLO LAP DETAIL
FIELD OF ROOF SERIESPARASOLO ROOF MEMBRANE SYSTEM
TM
12
PARAFAST RHINOBOND STANDARDFASTENING PATTERN
APPROVED STEEL AND CONCRETE DECKS
NOTES:
1. REFERENCE SPECIFIC SYSTEM/INSULATION TYPE AND THICKNESS REQUIREMENTS.
2. REFER TO THE PARAFAST RHINOBOND APPLICATION AND SPECIFICATION MANUAL FOR FASTENER AND DECKREQUIREMENTS.
3. CONTACT SIPLAST FOR RECOMMENDED FASTENING FREQUENCIES TO MEET SPECIFIC TESTING, CODE AGENCYOR GUARANTEE REQUIREMENTS.
12"
36"
36"
12"
12" 24" 12" 12" 24" 12"
16"
16"
4' 4'
8' 8'
CORNER AREAPERIMETER AREAFIELD AREA
6 FASTENERS PERBOARD
12 FASTENERS PERBOARD
8"
8"
16"
16"
16"
12"
12"
12" 12"4'
8'
9 FASTENERS PERBOARD
36"
36"
12"12"
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
www.siplast.com
DRAWING #
111ATHIS DETAIL APPLIES TO:
08-28-2019FIELD OF ROOF SERIES
R R
PARASOLO ROOF MEMBRANE SYSTEMTM
(1 FASTENER PER 5.33 sq ft) (1 FASTENER PER 3.56 sq ft) (1 FASTENER PER 2.7 sq ft)
HEAT INDUCTIONSYSTEMS
13
NOTES:
FIELD OF ROOF SERIES
PARAFAST RHINOBOND STANDARDFASTENING PATTERN
APPROVED WOOD DECKS
CORNER AREAPERIMETER AREAFIELD AREA
12"
12"
12" 24" 12"4'
8'
8 FASTENERS PERBOARD
12"
12"
12"
12"
12"
12"
12"
12"
6" 6"4'
8'
16 FASTENERS PERBOARD
12"
12"
12"
12"
12"
12"
12" 12" 12"12" 24" 12"
16"
16"
4'
8'
12 FASTENERS PERBOARD
8"
8"
16"
16"
16"
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
www.siplast.com
DRAWING #
111BTHIS DETAIL APPLIES TO:
08-28-2019
RR
PARASOLO ROOF MEMBRANE SYSTEMTM
1. REFERENCE SPECIFIC SYSTEM/INSULATION TYPE AND THICKNESS REQUIREMENTS.
2. REFER TO THE PARAFAST RHINOBOND APPLICATION AND SPECIFICATION MANUAL FOR FASTENER AND DECKREQUIREMENTS.
3. CONTACT SIPLAST FOR RECOMMENDED FASTENING FREQUENCIES TO MEET SPECIFIC TESTING, CODE AGENCYOR GUARANTEE REQUIREMENTS.
(1 FASTENER PER 4 sq ft) (1 FASTENER PER 2.7 sq ft) (1 FASTENER PER 2 sq ft)
HEAT INDUCTIONSYSTEMS
14
ROOF DECK/ SUBSTRATE
NOTES:
HEAT-WELD LAP (SEE NOTE #2)
CHANGE OF DECK PLANE DETAIL
PARAFAST PLATES & FASTENERSAT SPECIFIED FASTENING PATTERN.
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
112THIS DETAIL APPLIES TO:
08-28-2019PARAPET WALL & CURB SERIES
REINFORCED PARASOLOMEMBRANE
REINFORCED PARASOLOMEMBRANE
ROOF INSULATION
1. ALL OTHER SLOPES 1:12 OR GREAT NEED TO BE FASTENED AT ANGLE CHANGE.
2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINEWELDER AND 2" MIN. WELD WITH HAND WELDER..
PARASOLO ROOF MEMBRANE SYSTEMTM
15
VALLEY DETAIL
ROOF DECK/ SUBSTRATE
ROOF INSULATION
NOTES:
HEAT-WELDED LAP (SEE NOTE #2)
REINFORCED PARASOLO MEMBRANE
1. FOR MECHANICALLY ATTACHED SYSTEMS, VALLEYS MUST BE ADHERED USING APPROVED SPECIFICPARASOLO ADHESIVE.
2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELDWITH HAND WELDER.
PARASOLO ADHESIVE
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
113THIS DETAIL APPLIES TO:
08-28-2019FIELD OF ROOF SERIES
REINFORCED PARASOLO MEMBRANE
PARAFAST FASTENERS & PLATES PERSPECIFIED FASTENING PATTERN
PARASOLO ROOF MEMBRANE SYSTEMTM
16
FIELD OF ROOF SERIES
12"
36"
36"
12"
12" 24" 12"4'
8'
CORNER AREAPERIMETER AREA*FIELD AREA
6 FASTENERS PERBOARD
12"
18"
18"
12"
12" 12"4'
8'
15 FASTENERS PERBOARD
18"
18"
12"12"
12"
18"
18"
12"
12" 24" 12"4'
8'
10 FASTENERS PERBOARD
18"
18"
PARAFAST RHINOBOND INSULATIONFASTENING PATTERN
APPROVED STEEL AND CONCRETE DECKS
NOTES:
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
www.siplast.com
DRAWING #
121THIS DETAIL APPLIES TO:
09-06-2019
RR
1. REFERENCE SPECIFIC SYSTEM/INSULATION TYPE AND THICKNESS REQUIREMENTS.
2. PARAFAST RHINOBOND PLATE-WELDED SYSTEM IS NOT ACCEPTABLE FOR GYPSUM, CEMENTITIOUS WOODFIBER OR OSB.
3. REFER TO THE PARAFAST RHINOBOND APPLICATION AND SPECIFICATIONS FOR FASTENER AND DECKREQUIREMENTS.
4. CONTACT SIPLAST FOR RECOMMENDED FASTENING FREQUENCIES TO MEET SPECIFIC TESTING, CODEAGENCY, OR GUARANTEE REQUIREMENTS.
*THE FIELD OF ROOF ATTACHMENTS ABOVE EQUATE TO FM 1-90 RATINGS
PARASOLO ROOF MEMBRANE SYSTEMTM
(1 FASTENER PER 5.33 sq ft)
HEAT INDUCTIONSYSTEMS
(1 FASTENER PER 3.2 sq ft) (1 FASTENER PER 2.13 sq ft)
17
FIELD OF ROOF SERIES
NOTES:
CORNER AREAPERIMETER AREA*FIELD AREA
12"
12"
12" 24" 12"4'
8'
8 FASTENERS PERBOARD
12"
12"
12"
12"
12"
12"
12"
18"
18"
12"
12" 12"4'
8'
15 FASTENERS PERBOARD
18"
18"
12"12"
12"
18"
18"
12"
8'
20 FASTENERS PERBOARD
18"
18"
6" 6"4'
12" 12" 12"
PARAFAST RHINOBOND INSULATIONFASTENING PATTERN
APPROVED STEEL AND CONCRETE DECKS N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
www.siplast.com
DRAWING #
122THIS DETAIL APPLIES TO:
09-06-2019
RR
1. REFERENCE SPECIFIC SYSTEM/INSULATION TYPE AND THICKNESS REQUIREMENTS.
2. PARAFAST RHINOBOND PLATE-WELDED SYSTEM IS NOT ACCEPTABLE FOR GYPSUM, CEMENTITIOUS WOODFIBER OR OSB.
3. REFER TO THE PARAFAST RHINOBOND APPLICATION AND SPECIFICATIONS FOR FASTENER AND DECKREQUIREMENTS.
4. CONTACT SIPLAST FOR RECOMMENDED FASTENING FREQUENCIES TO MEET SPECIFIC TESTING, CODEAGENCY, OR GUARANTEE REQUIREMENTS.
*THE FIELD OF ROOF ATTACHMENTS ABOVE EQUATE TO FM 1-120 RATINGS
PARASOLO ROOF MEMBRANE SYSTEMTM
(1 FASTENER PER 4 sq ft)
HEAT INDUCTIONSYSTEMS
(1 FASTENER PER 2.13 sq ft) (1 FASTENER PER 1.2 sq ft)
18
NOTES:
ROOF INSULATION
ROOF DECK/SUBSTRATE
HEAT-WELDED LAP (SEE NOTE #1)
HEAT-WELDED LAP (MIN. 2" WELD)
PARASOLO COATED METAL EDGE (SEE NOTE#3)
CONTINUOUS CLEAT SECURED WITH RING SHANKROOFING NAILS @ 12" (305 mm) O.C.
WOOD NAILER SECURED TO DECK.
REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)
COATED METAL ROOF EDGE DETAIL
FOR ALTERNATE TAPERED ROOFEDGE, USE TAPERED INSULATION
8" (203 mm) WIDE PARASOLO FLASHING STRIPHEAT-WELDED
1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELDWITH HAND WELDER.
2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY.THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.
3. CONTACT THE SIPLAST TECHNICAL DEPARTMENT FOR INFORMATION REGARDING THE APPROPRIATEPROFILES AND GAUGES FOR CLEAT AND PARASOLO METAL.
RING SHANK GALVANIZED NAIL @ 3"(77 mm) O.C. STAGGERED 2" MINIMUMFROM OUTSIDE EDGE OF METAL.
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
202THIS DETAIL APPLIES TO:
09-06-2019ROOF EDGE SERIESPARASOLO ROOF MEMBRANE SYSTEM
TM
19
USE 2" (52 mm) FOILTAPE OR DUCT TAPEAS BOND BREAKERPARASOLO COATEDMETAL DRIP EDGE
1/4" (6.35 mm) EXPANSION
WOOD NAILER SECUREDTO DECK
ROOF INSULATION
ROOF DECK/SUBSTRATE
CONTINUOUS CLEATSECURED WITH RINGSHANK ROOFING NAILS @12" (305 mm) O.C.
REINFORCED PARASOLOMEMBRANE
COATED METAL JOINT DETAIL
STEP 1.
STEP 2.
STEP 3.
8" (203 mm) WIDE PARASOLOFLASHING STRIP OR 6" (152 mm) WIDE PARASOLOMEMBRANE HEAT WELDED
6" (152 mm) WIDE PARASOLOJOINT TREATMENT
SPACE
EXTEND MIN 2" (52 mm)
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
204THIS DETAIL APPLIES TO:
08-28-2019ROOF EDGE SERIES
HEAT-WELDED LAP(MIN. 2" WELD)
HEAT-WELDED LAP(MIN. 2" WELD)
PARASOLO ROOF MEMBRANE SYSTEMTM
1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOPFABRICATION AND JOB-SITE ASSEMBLY. THESE COMPONENTSSHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TOGENERALLY ACCEPTED INDUSTRY PRACTICES, STANDARDS, ANDAPPROVALS.
2. CONTACT SIPLAST FOR INFORMATION REGARDING THE APPROPRIATEPROFILES AND GAUGES FOR CLEAT AND PARASOLO METAL.
NOTES:
20
PARAGUARD EXTRUDED EDGEDETAIL
ROOF DECK/SUBSTRATE
ROOF INSULATION
WOOD NAILER SECURED TO DECK
REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)
EXTRUDED RETAINING CLEAT(FASTEN THROUGH PRE-PUNCHED HOLESIN EXTERIOR FACE)
NOTES:
PARAGUARD EXTRUDED EDGE
PARASOLO FLEXSEAL CAULK GRADESEALANT
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
205THIS DETAIL APPLIES TO:
09-10-2019ROOF EDGE SERIES
1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY.THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.
2. FASCIA FASTENERS ARE PROVIDED WITH THE PARAGUARD EXTRUDED EDGE SYSTEM.
3. IF THE BOTTOM ROW OF FASTENERS ALIGN WITH A SUBSTRATE OTHER THAN A NAILER, ANAPPROPRIATE AND APPROVED FASTENER SHALL BE USED.
PARASOLO ROOF MEMBRANE SYSTEMTM
21
PARAGUARD M RAISED EDGEDETAIL
ROOF DECK/SUBSTRATE
ROOF INSULATION
HEAT-WELDED LAP (MIN 2" WELD)
METAL FORMED RAIL FACE FASTENED12" 9305 mm) O.C.
WOOD NAILER SECURED TO DECK
REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)
PARAGUARD M RAISED EDGE
METAL CONTINUOUS CANT DAMFASTENED 6" (305 mm) O.C.
NOTES:
REINFORCED PARASOLO MEMBRANE
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
206THIS DETAIL APPLIES TO:
08-31-2019ROOF EDGE SERIES
SECTION
1. THE CARPENTRY WORK SHOWN DEPICTS JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.
2. REFER TO THE PARAGUARD ROOF PERIMETER SYSTEMS INSTALLER'S GUIDEFOR INFORMATION ON PRODUCTS, SIZING, AND INSTALLATION OF THEPARAGUARD SYSTEM.
PARASOLO ROOF MEMBRANE SYSTEMTM
22
GUTTER WITH COATED METAL EDGEDETAIL
ROOF DECK/SUBSTRATE
ROOF INSULATION
SHEET METAL GUTTER BY OTHERS
WOOD NAILER SECURED TO SUBSTRATE
CONTINUOUS CLEAT SECURED WITH RINGSHANK ROOFING NAILS @ 12" (305 mm) O.C.
PARASOLO COATED METAL EDGE(SEE NOTE #4)
REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)
8" (203 mm) WIDE PARASOLOFLASHING STRIP HEAT-WELDED
RING SHANK GALVANIZED NAILS @ 3" (77 MM)O.C. STAGGERED 2" MINIMUM FROM OUTSIDEEDGE OF METAL.
HEAT-WELDED LAP (MIN. 2" WELD)
NOTES:
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
211THIS DETAIL APPLIES TO:
09-06-2019ROOF EDGE SERIES
HEAT-WELDED LAP (SEE NOTE #1)
1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.
2. REFER TO PARASOLO DETAIL 204 FOR COATED METAL JOINTS.
3. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.
4. CONTACT THE SIPLAST TECHNICAL DEPARTMENT FOR INFORMATION REGARDING THE APPROPRIATE PROFILES ANDGAUGES FOR CLEAT AND PARASOLO METAL.
PARASOLO ROOF MEMBRANE SYSTEMTM
23
PARASOLO FASTENERS & PLATES 12"(305 mm) O.C.
24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE
ROOF DECK/SUBSTRATE
ROOF INSULATION
HEAT-WELDED LAP (SEE NOTE #1)
PARASOLO WATER BLOCK SEALANT
PARAFAST TERMINATION BAR FASTENED 8"(203 mm) O.C. W/PARAFAST FASTENERS
REINFORCED PARASOLO MEMBRANE
NOTES:
PARASOLO FLEXSEAL CAULK GRADE SEALANT
PARASOLO BONDING ADHESIVE(SEE FLASHING KEY)
REGLET OR SURFACE-MOUNT COUNTERFLASHING BY OTHERS(REQUIRED FOR EXTENDED-LENGTHGUARANTEE)
4" (1
02 m
m) M
IN.
8" (2
03 m
m)
PARAPET WALL FLASHING WITHCOUNTER FLASHING
PARASOLO FLEXSEAL CAULK GRADESEALANT
WOOD NAILER SECURED TO DECK(OPTIONAL)
ALTERNATE BASEREFER TO DETAIL 307A
min
.
UP TO 24" (610 mm) DRY HUNG
FLASHING KEY
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
301THIS DETAIL APPLIES TO:
09-06-2019PARAPET WALL & CURB SERIES
1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN.WELD WITH HAND WELDER.
2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITEASSEMBLY. THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDINGTO GENERALLY ACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.
PARASOLO ROOF MEMBRANE SYSTEMTM
24
PARAFAST FASTENERS & PLATES12" (305 mm) O.C.
NOTES:
PARASOLO WATER BLOCK
PARAFAST TERMINATION BARFASTENED 6" (152mm) O.C.
ROOF DECK/SUBSTRATE
HEAT-WELDED LAP (SEE NOTE #1)
ROOF INSULATION
REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)
ALTERNATE BASEREFER TO PARASOLO DETAIL 307A
WALL AND CURB FLASHING WITHTERMINATION BAR DETAIL
PARASOLO FLEXSEAL CAULK GRADESEALANT
PARASOLO ADHESIVE(SEE FLASHING KEY)
24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE
UP TO 24" (610 mm) DRY HUNG
FLASHING KEY
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
302THIS DETAIL APPLIES TO:
08-31-2019PARAPET WALL & CURB SERIES
8" (2
03 m
m) M
IN.
1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
1/4" TO 3/4"
25
PARASOLO ADHESIVE(SEE FLASHING KEY)
PARAFAST FASTENERS & PLATES 12"(305 mm) O.C.
NOTES:
COPING CAP
ROOF DECK/SUBSTRATE
HEAT-WELDED LAP (SEE NOTE #1)
ROOF INSULATION
CONTINUOUS CLEAT
BACK SIDE
ALTERNATE BASEREFER TO PARASOLO DETAIL 307A
12" (305 mm) O.C.
NEW CONSTRUCTION WITH WALL CAPDETAIL
REINFORCED PARASOLO MEMBRANE
WOOD NAILER SECURED TO DECK(OPTIONAL)
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
303THIS DETAIL APPLIES TO:
09-06-2019PARAPET WALL & CURB SERIES
24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE
UP TO 24" (610 mm) DRY HUNG
FLASHING KEY
8" (2
03 M
M)
MIN
.
1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITEASSEMBLY. THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDINGTO GENERALLY ACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.
PARASOLO ROOF MEMBRANE SYSTEMTM
1/4" TO 3/4"
26
ROOF DECK/SUBSTRATE
PARASOLO ADHESIVE (SEE FLASHING KEY)
PARAFAST FASTENERS & PLATES 12"(305 mm) O.C.
ROOF INSULATION
PARASOLO COATED METAL (SEE NOTE #3)
REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)
NOTES:
CONTINUOUS CLEAT SECURED WITHRING SHANK ROOFING NAILS @ 12"(305mm) O.C.
PARASOLO FLASHING STRIP OR 6" (152 mm)PARASOLO REINFORCED PVC MEMBRANE
GALV. RING SHANK NAIL 3" (77 mm) O.C.STAGGERED.
ALTERNATE BASE
HEAT-WELDED LAP (MIN. 2" WELD)
REFER TO PARASOLO DETAIL 307A
FASTEN 12" (305 mm) O.C.
WALL FLASHING WITH COATED METALEDGE DETAIL
REINFORCED PARASOLO MEMBRANE
WOOD NAILER SECURED TODECK (OPTIONAL)
HEAT-WELDED LAP(SEE NOTE #1)
24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE
UP TO 24" (610 mm) DRY HUNG
FLASHING KEY
1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY.THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.
3. CONTACT THE SIPLAST TECHNICAL DEPARTMENT FOR INFORMATION REGARDING THEAPPROPRIATE PROFILES AND GAUGES FOR CLEAT AND PARASOLO METAL.
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
304THIS DETAIL APPLIES TO:
08-31-2019PARAPET WALL & CURB SERIESPARASOLO ROOF MEMBRANE SYSTEM
TM
1/4" TO 3/4"
27
ALTERNATE WALL BASETERMINATION DETAIL
ROOF DECK/SUBSTRATE
HEAT-WELDED LAP (SEE NOTE #3)
ROOF INSULATION
PARAFAST TERMINATION BAR &FASTENERS/ANCHORSFASTENED 8" (203 mm) O.C.
NOTES:
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
307ATHIS DETAIL APPLIES TO:
08-31-2019PARAPET WALL & CURB SERIES
24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE
UP TO 24" (610 mm) DRY HUNG
FLASHING KEY
PARASOLO ADHESIVE(SEE FLASHING KEY)
REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)
REINFORCED PARASOLOMEMBRANE
1. PLATES & FASTENERS MAY BE USED IN LIEU OF TERMINATION BAR IN NON-PRESSURIZEDSITUATIONS.
2. THIS DETAIL NEEDS TO BE USED FOR PRESSURIZED SITUATIONS, IN ALL SYSTEMS.
3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN.WELD WITH HAND WELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
PARASOLOWATER BLOCK
SEALANT
28
PARAFAST RHINOBOND BASE TIE IN ATANGLE CHANGE DETAIL
ROOF DECK/SUBSTRATE
INDUCTION HEAT-WELD
NOTES:
WALL/CURB
REINFORCED PARASOLOMEMBRANE
PARAFAST FASTENERSAND RHINOBOND PLATES12" (305 mm) O.C. MAX
ROOF INSULATION
SEE NOTE #1
INSULATION-FLUTE FILLER IF REQUIRED
APPROVED PARASOLOBONDING ADHESIVE(SEE FLASHING KEY)
REFERENCE PARASOLO300 SERIES PARAPET WALL ANDCURB DETAILS FOR TERMINATION
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
www.siplast.com
DRAWING #
307BTHIS DETAIL APPLIES TO:
08-31-2019PARAPET WALL & CURB SERIES
24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE
UP TO 24" (610 mm) DRY HUNG
FLASHING KEY
1. PARAFAST FASTENER & RHINOBOND PLATE MUST BE INSTALLED A MAXIMUM 6" (152 MM) FROMTHE ANGLE CHANGE.
2. REFER TO THE PARAFAST ATTACHMENT TABLES FOR DETAILED INSTALLATION REQUIREMENTSREGARDING DECK TYPE, PLATE & FASTENER TYPE, AND MIN. EMBEDMENT.
PARASOLO ROOF MEMBRANE SYSTEMTM
HEAT INDUCTIONSYSTEMS
R R
29
ROOF DECK/SUBSTRATE
ROOF INSULATION
PARASOLO FLEXSEAL CAULK GRADE SEALANT
NOTES:
REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)
PREMANUFACTURED OUTSIDE CORNERSHEAT-WELDED (ALL CORNERS)
CONTINUOUS HEAT-WELDED LAP (MIN. 2" WELD)
UNREINFORCED FIELD-FABRICATEDCORNERS - HEAT-WELDED (OPTION 1)
WOOD NAILER SECURED TO DECK(OPTIONAL)
REINFORCED PARASOLO MEMBRANE ORPARASOLO DETAILING MEMBRANE
PARASOLO COATED METAL SCUPPER
CONTINUOUS PERIMETER HEATWELDED LAP (MIN. 2" WELD)
COATED METAL WALLSCUPPER DETAIL
PARAFAST FASTENERS & PLATES 12"(305 mm) O.C.
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
311THIS DETAIL APPLIES TO:
08-31-2019PARAPET WALL & CURB SERIES
PARAFAST FASTENERS 12" (305 mm)O.C. MAX
1. SCUPPERS MUST BE CLOSED OFF ON OUTSIDE OF BUILDING.
2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.
PARASOLO ROOF MEMBRANE SYSTEMTM
30
PARAFAST FASTENERS & PLATES12" (305 mm) O.C.
NOTES:
THRESHOLD BY OTHERS
ROOF DECK/SUBSTRATE
HEAT-WELDED LAP (SEE NOTE #1)
ROOF INSULATION
PARASOLO WALK PAD (REQUIRED)
REINFORCED PARASOLO MEMBRANE
METAL COUNTERFLASHING
ALTERNATE BASE
DOOR THRESHOLD FLASHING DETAIL
REFER TO PARASOLO DETAIL 307A
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
312THIS DETAIL APPLIES TO:
08-31-2019PARAPET WALL & CURB SERIES
PARASOLO BONDING ADHESIVE(OPTIONAL)
PARASOLO WATER BLOCK ORPARASOLO FLEX SEAL CAULK GRADE
PARASOLO WATER BLOCK ORPARASOLO FLEX SEAL CAULK GRADE
1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.
2. FOR HEIGHTS LESS THAN 8" (203 MM) CONTACT SIPLAST FOR MORE INFORMATION.
PARASOLO ROOF MEMBRANE SYSTEMTM
31
ROOF DECK/SUBSTRATE
REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)
PARAFAST FASTENERS @12" (305 mm) O.C.
ROOF INSULATION
PARASOLO COATED METALEDGING WITH HEMMED EDGE
VERTICAL WALL EDGE TERMINATIONWITH COATED METAL DETAIL
REFERENCE PARASOLO ROOFEDGE FLASHING DETAIL 211 FOREDGE TERMINATION.
HEAT-WELDED LAP (MIN. 2" WELD)
WOOD NAILER SECURED TO DECK(OPTIONAL)
NOTES:
ALTERNATE BASE ATTACHED(SEE PARASOLO DETAIL 307)
REFERENCE PARASOLO300 SERIES PARAPET WALLAND CURB DETAILS FORTERMINATION
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
314THIS DETAIL APPLIES TO:
08-31-2019PARAPET WALL & CURB SERIESPARASOLO ROOF MEMBRANE SYSTEM
TM
1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.
2. CONTACT THE SIPLAST TECHNICAL DEPARTMENT FOR INFORMATION REGARDING THE APPROPRIATE PROFILES ANDGAUGES FOR CLEAT AND PARASOLO METAL.
32
RHINOBOND WALL FLASHING FASTENINGPATTERN DETAIL
PARAFAST FASTENERS& RHINOBOND PLATES
1. BASE ATTACHMENT TO FOLLOW FIELD OF ROOF APPLICATION
24" O.C.(610 mm)
12" O.C.(305 mm)
12" O.C.(305 mm)
24" O.C.(610 mm)
NOTE:
12" O.C.(305 mm)
12" O.C.(305 mm)
4" O.C.(102 mm)
FROM BASE OF WALLFIRST ROW OF FASTENERS 24" (610 mm) OFF WALL BASECONTINUE 24" (610 mm) UP WALL.
FROM CORNER OF WALLFIRST ROW 4" (102 mm)O.C FROM CORNERTHEN FASTENERS12" (305 mm) O.C.
PLACEMENT LINES TOBE ASSOCIATED WITHFIGURE 1 ABOVE
FIGURE 1
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
315THIS DETAIL APPLIES TO:
08-31-2019PARAPET WALL & CURB SERIES
R
PARASOLO ROOF MEMBRANE SYSTEMTM
33
12" O
.C.
(305
mm
)
HIGH WALL FLASHING DETAIL10' (3.05 m) WIDE SHEETS
NOTES:
PARAFAST FASTENERS &PLATES FASTENED 12" (305mm) O.C. VERTICALLY UP WALLIN LAPS
ROOF DECK/SUBSTRATE
ROOF INSULATION
HEAT-WELD LAPS(SEE NOTE #3)
REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)
REINFORCED 10' (3.05 m) WIDEPARASOLO MEMBRANE-RUN MEMBRANE WIDTHVERTICALLY UP AND OVERWALL
REFERENCE PARASOLO 300SERIES PARAPET WALL ANDCURB DETAILS FORTERMINATION
20' (3.05 m) MAX
FASTENER SPACING
9' (2
.74
m)
MAX
PARASOLO ADHESIVEREQUIRED
REFERENCE PARASOLO DETAIL 317DFOR VERTICAL SHEET LAYOUT
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
317ATHIS DETAIL APPLIES TO:
09-06-2019PARAPET WALL & CURB SERIES
1. MUST BE FASTENED VERTICALLY ON THE WALL A MINIMUM 10' (3.05 M) FROM ALL ENDS ORCORNERS OF WALL, THEN MAX 20' (6.10 M) THEREAFTER. PARAFAST FASTENERS SPACED 12"(305 MM) O.C.
2. MAX PARAPET WALL HEIGHT NOT TO EXCEED THE WIDTH OF A 10' (3.05 M) SHEET. PARAPETWALL SHOULD BE NO TALLER THAN 9' (2.74 M) TO USE A FULL 10' (3.05 M) SHEET OF MEMBRANEAS FLASHING.
3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PALTES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
1/4" TO 3/4"
34
HIGH WALL FLASHING DETAIL5' (1.52 m) WIDE SHEETS
NOTES:
PARAFAST FASTENERS &PLATES FASTENED 12"(305 mm) O.C. VERTICALLYUP WALL
ROOF DECK/SUBSTRATE
ROOF INSULATION
HEAT-WELD LAPS (SEE NOTE #2)
REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)
REINFORCED 5' (1.52 m) WIDEPARASOLO MEMBRANE-RUN MEMBRANE WIDTHVERTICALLY UP AND OVERWALL
REFERENCE PARASOLO300 SERIES PARAPET WALLAND CURB DETAILS FORTERMINATION
5' (1.52 m) WIDE
FASTENER SPACING
REFERENCE PARASOLO DETAIL 317DFOR INTERMITTENT FASTENING
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
317BTHIS DETAIL APPLIES TO:
09-06-2019PARAPET WALL & CURB SERIES
12" O
.C.
(305
mm
)
1. WALL HEIGHTS OVER 10' (3.05 M) HIGH REQUIRE THE ENTIRE WALL TO BE FULLY ADHERED.UNDER 10' (3.05 M) CAN BE DRY HUNG WITHOUT ADHESIVE.
2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PALTES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
1/4" TO 3/4"
35
PARAFAST FASTENERS &PLATES 12" (305 mm) O.C.
HEAT-WELDED LAP (MIN. 2" WELD)
NOTES:
ROOF INSULATION
PARASOLO ADHESIVE REQUIRED24" - 54" (610 mm - 1.37 m) ONSMOOTH MEMBRANE ONLY.
HEAT-WELDED LAP (SEE NOTE #3)
ROOF DECK/SUBSTRATE
REINFORCED PARASOLOMEMBRANE
ALTERNATE BASEREFER TO PARASOLO DETAIL 307A
HIGH WALL FLASHING DETAIL- WITH PLATES AND FASTENERS
REINFORCED PARASOLOMEMBRANE
PARAFAST FASTENERS &PLATES 12" (305 mm) O.C.
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
317CTHIS DETAIL APPLIES TO:
09-06-2019PARAPET WALL & CURB SERIES
1. 24" (610 MM) MAX. DIMENSION FOR LOOSE-APPLIED FLASHINGS.
2. 54" (1.37 M) MAX. DIMENSION FOR FULLY ADHERED FLASHINGS.
3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
24" - 54" (610 mm -1.37 m)REQUIRES BONDING ADHESIVE
UP TO 24" (610 mm) DRY HUNG
FLASHING KEY
SEE
NO
TES
1 &
2SE
E N
OTE
S1
& 2
1/4" TO 3/4"
36
HIGH WALL FLASHING DETAIL -INTERMITTENT FASTENING
FOR 5' (1.52 m) WIDE SHEETSREFERENCE PARASOLO DETAIL 317B
PARAFAST FASTENERS &PLATES FASTENED 12" (305mm) O.C. HORIZONTALLY
NOTE:
1. FIRST THREE SHEETS FROM THE CORNER AND FIRST THREESHEETS FROM THE WALL EDGE REQUIRE A ROW OF PARAFASTFASTENERS & PLATES 12" O.C. MID WAY UP THE WALL AS SHOWN.
FOR 10' (3.05 m) WIDE SHEETSREFERENCE PARASOLO DETAIL 317A
NOTE:
1. FIRST SHEET FROM THE CORNER AND FIRST SHEET FROM THE WALL EDGE ARE 10' (3.05 m) WIDE.ALL SHEETS IN BETWEEN ARE 20' (6.10 m) WIDE.
REINFORCED PARASOLOMEMBRANE - 5 FT. (1.52 m)WIDE SHEETS
REINFORCED PARASOLOMEMBRANE
8" (203 mm) PARASOLOFLASHING STRIP HEAT-WELDEDOVER ROW OF FASTENERS.
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
317DTHIS DETAIL APPLIES TO:
09-03-2019PARAPET WALL & CURB SERIESPARASOLO ROOF MEMBRANE SYSTEM
TM
37
PARASOLO ADHESIVE (OPTIONAL)
REINFORCED PARASOLO MEMBRANE
1. MECHANICAL TERMINATION
METAL SURFACE MOUNTED COUNTER FLASHING
PARASOLO BONDING ADHESIVE (OPTIONAL)
REINFORCED PARASOLO MEMBRANE
2. MECHANICAL TERMINATION
FASTENERS 12" (305 mm) O.C.
PARAFAST TERMINATION BAR
PARASOLO ADHESIVE (OPTIONAL)
3. MECHANICAL TERMINATION (15-YR MAX GUARANTEE)
FASTENERS 6" (152 mm) O.C.
METAL COUNTER FLASHING (MAY BE FACE MOUNTED ALSO)
TERMINATION DETAIL 1-3
PARASOLO FLEXSEAL CAULK GRADE SEALANT
PARASOLO FLEXSEAL CAULK GRADE SEALANT
PARAFAST TERMINATION BAR FASTENED 8" (203 MM)O.C (OPTIONAL)
NOTE: EXISTING COUNTERFLASHING MUST BE IN GOODWORKABLE CONDITION AND TIGHT TO WALL.
FASTENERS 8" (203 mm) O.C.
PARASOLO WATER-BLOCK SEALANT
PARASOLO FLEXSEAL CAULK GRADE SEALANT
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
318ATHIS DETAIL APPLIES TO:
REINFORCED PARASOLO MEMBRANE
09-06-2019PARAPET WALL & CURB SERIES
PARASOLO WATER BLOCK SEALANT
NOTE: EXISTING COUNTERFLASHING MUST BE IN GOODWORKABLE CONDITION AND TIGHT TO WALL.
PARASOLO ROOF MEMBRANE SYSTEMTM
PARASOLO WATER BLOCK SEALANT
PARASOLO WATER BLOCK SEALANT
38
COPING STONE (BY OTHERS)
PARASOLO ADHESIVE (OPTIONAL)
REINFORCED PARASOLO MEMBRANE
4. COPING STONE TERMINATION
METAL CAP (BY OTHERS)
REINFORCED PARASOLO MEMBRANE
5. CAP FLASHING TERMINATION
PARASOLO WATER BLOCK
PARASOLO ADHESIVE (OPTIONAL)
FASTENERS 12" (305 mm) O.C.
TERMINATION DETAILS 4-5
MORTAR (BY OTHERS)
20 YEAR MAXGUARANTEE
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
318BTHIS DETAIL APPLIES TO:
09-03-2019PARAPET WALL & CURB SERIESPARASOLO ROOF MEMBRANE SYSTEM
TM
39
HEAT-WELDED LAP (SEE NOTE #1)
PARAFAST FASTENERS & PLATES 12" O.C.
REINFORCED PARASOLO MEMBRANE
ROOF DECK/SUBSTRATE
ROOF INSULATION
METAL COUNTER FLASHING WITHATTACHMENT
8" m
in.
PARASOLO ADHESIVE
COUNTER FLASHING RE-ROOF DETAIL
REINFORCED PARASOLO MEMBRANE
WOOD NAILER SECURED TO DECK
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
319THIS DETAIL APPLIES TO:
09-06-2019PARAPET WALL & CURB SERIES
PARASOLO WATERBLOCK SEALANT
PARASOLO FLEXSEAL CAULK GRADESEALANT
1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATIC MACHINEWELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY.THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.
NOTES:
PARASOLO ROOF MEMBRANE SYSTEMTM
PARAFAST TERMINATION BAR FASTENED8" (203 MM) O.C
1/4" TO 3/4"
40
CORNER CURB WRAP DETAIL
NOTES:
PARASOLO CORNER CURB WRAP
HEAT-WELDED LAP(SEE NOTE #3)
REFER TO PARASOLO 300 SERIESPARAPET AND WALL DETAIL FORTERMINATION
6"
(152 mm)
12"(
305
mm
)
ADJUSTABLE CORNER LAPFOR CORNERS GREATERTHAN OR LESS THAN 90DEGREES
REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)
PARAFAST FASTENERS 12"(305 mm) O.C.
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
325THIS DETAIL APPLIES TO:
09-06-2019PARAPET WALL & CURB SERIES
1. FOUR CORNER CURB WRAP PIECES ARE NEEDED TO COMPLETE. VARYING SIZES MAY BENEEDED TO COMPLETE.
2. CORNER WRAP MAY BE ADHERED OR INSTALLED DRY.
3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
1/4" TO 3/4"
41
NOTES:
REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)
PARASOLO UNIVERSALCORNER - HEAT-WELDED
CORNER-WELD ORHEAT-WELD MEMBRANEPIECE TO MEMBRANEFLASHING
HEAT-WELDED LAP(SEE NOTE #3)
INSIDE CORNER REINFORCMENT-PREFORMED CORNER DETAIL
PARAFAST FASTENERS &PLATES 12" (305mm) O.C.
ROOF INSULATION
ROOF DECK/SUBSTRATE
HEAT-WELDED LAP (SEE NOTE #3)
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
327ATHIS DETAIL APPLIES TO:
09-06-2019PARAPET WALL & CURB SERIESPARASOLO ROOF MEMBRANE SYSTEM
TM
1. FLASHINGS MAY BE ADHERED OR INSTALLED DRY. SEE MANUAL FOR DIMENSIONS.
2. INSIDE CORNERS MAY ALSO BE FIELD-FABRICATED USING UNREINFORCED MEMBRANE.
3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATIC MACHINE WELDER AND 2"MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
4. EDGE OF MEMBRANE SHOULD NOT TERMINATE BELOW GUTTER EDGES.
1/4"
TO
3/4
"
42
CUT A SECTION OF NON-REINFORCEDPARASOLO MEMBRANE. FOLD ALONG LINEAS INDICATED.
MEMBRANEUNDERSIDE
FOLDLINE
MEMBRANESURFACE
HEAT-WELD AREAAS SHOWN
REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)
UNFOLD PIECE
FOLD CORNER
PUSH IN
FIELD FABRICATED INSIDECORNER HEAT WELDED INCORNER
1 2 3
4 5 6
INSIDE CORNER REINFORCEMENT -FIELD FABRICATION DETAIL
APPROX. 8" (203 mm)
APPROX. 8"(203 mm)
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
327DTHIS DETAIL APPLIES TO:
09-06-2019PARAPET WALL & CURB SERIES
TM
PARASOLO ROOF MEMBRANE SYSTEMTM
43
INSIDE CORNER FABRICATION -2 STEP "JOINT PATCH" UP DETAIL
CURB OR WALL
HEAT-WELDED LAP(SEE NOTE #3)
CONTINUOUS HEAT-WELDEDLAP AND ALL SEGMENTS(SEE NOTE #3)
ONE PIECE FOLD WITH "PIGEAR" (DO NOT CUT) ALLSEGMENTS MUST BE WELDEDTO THE VERTICAL FLASHINGS
HEAT-WELDED LAP(SEE NOTE #3)
STEP 1
STEP 2
NOTES:
REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)
CURB OR WALL
REINFORCED PARASOLOMEMBRANE
REINFORCED PARASOLOMEMBRANE
REINFORCED PARASOLO MEMBRANE(PERIMETER SHEET IF REQUIRED)
PARAFAST FASTENERS &PLATES 12" (305 mm) O.C.
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
328ATHIS DETAIL APPLIES TO:
09-06-2019PARAPET WALL & CURB SERIES
1. ALL SEGMENTS OF THE EAR MUST BE WELDED TOGETHER AND WELDED TO THE WALL.
2. CHECK SYSTEM SPECIFICATION FOR GUIDELINES ON ADHERING FLASHINGS.
3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATICMACHINE WELDER AND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
1/4" TO 3/4"
44
HEAT-WELDED LAP(SEE NOTE #3)
INSIDE CORNER FABRICATION -2 STEP "JOINT PATCH" DOWN DETAIL
PARASOLO JOINT PATCH ATMEMBRANE OVERLAP
ONE PIECE FOLD WITH "JOINT PATCH"(DO NOT CUT) ALL SEGMENTS MUSTBE WELDED DOWN
1 PIECEMETHOD
2 PIECEMETHOD
REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)
CURB OR WALL
REINFORCED PARASOLOMEMBRANE
NOTES:
HEAT-WELDED LAP(SEE NOTE #3)
PARASOLO JOINT PATCH ATMEMBRANE OVERLAP
ONE PIECE FOLD WITH "JOINTPATCH" (DO NOT CUT) ALLSEGMENTS MUST BE WELDED DOWN
REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)
CURB OR WALL
REINFORCED PARASOLOMEMBRANE
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
328BTHIS DETAIL APPLIES TO:
09-06-2019PARAPET WALL & CURB SERIESPARASOLO ROOF MEMBRANE SYSTEM
TM
1. ALL SEGMENTS OF THE EAR MUST BE WELDED TOGETHER AND WELDED TO THE WALL.
2. CHECK SYSTEM SPECIFICATION FOR GUIDELINES ON ADHERING FLASHINGS.
3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN.WELD WITH HAND WELDER.
45
ALTERNATEWALL/CURB ATTACHMENT
OUTSIDE CORNER REINFORCEMENT -UNIVERSAL CORNER DETAIL
NOTES:
REINFORCED PARASOLOMEMBRANE (PERIMETERSHEET IF REQUIRED)
PARASOLO UNIVERSALCORNER
HEAT-WELDED LAP(SEE NOTE #3)
REFER TO PARAPET AND WALLDETAIL FOR TERMINATION
STEP 1
STEP 2
HEAT-WELDED LAP(SEE NOTE #3)
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
329ATHIS DETAIL APPLIES TO:
09-06-2019PARAPET WALL & CURB SERIES
1. KEEP FASTENERS BACK FROM CORNER 6" (152 MM) MAX. IN BOTHHORIZONTAL AND VERTICAL APPLICATIONS.
2. CHECK SYSTEM SPECIFICATION FOR GUIDELINES ON ADHERING FLASHINGS.
3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATESWITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD BEYOND FASTENERPLATES WITH HAND WELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
1/4" TO 3/4"
46
ROOF DECK/SUBSTRATE
ROOF INSULATION
HEAT-WELDED LAP (SEE NOTE #3)
REINFORCED PARASOLO MEMBRANE
TAPERED-EDGE INSULATION
PARASOLO SMOOTH-BACKMEMBRANE ONLY
PARAFAST FASTENERS & PLATES
BATT INSUALTION
BACKER ROD 1-1/2 TIMES OPENING
6" MIN.
HEAT WELDED LAP (SEE NOTE #3)
FIELD FABRICATED EXPANSIONJOINT - FLAT TYPE DETAIL
6" (152 mm) TYPICAL SEAM AREA
NOTES:
WOOD NAILER SECURED TO DECK
WOOD NAILER SECURED TO DECK
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
401BTHIS DETAIL APPLIES TO:
09-04-2019EXPANSION SERIES
1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.
2. FIELD-FABRICATED EXPANSION JOINT SHOULD NOT BE FLEECE-BACK MEMBRANE. USE STANDARD PARASOLOMEMBRANE.
3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATIC MACHINE WELDERAND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
47
NOTES:
BATT INSULATION
ROOF DECK/SUBSTRATE
REINFORCED PARASOLO MEMBRANE
PARASOLO ADHESIVE
ROOF INSULATION
HEAT-WELDED LAP (MIN. 2" WELD)
FIELD FABRICATED EXPANSIONJOINT - CURB TYPE DETAIL
PARASOLO MEMBRANE
BACKER ROD 1-1/2 TIMES THE OPENING
REINFORCED PARASOLO MEMBRANE
PARAFAST FASTENERS AND PLATES12" (305 mm) O.C.
SECURE MEMBRANE AT TOP OF CURBWITH RING SHANK ROOFING NAILS 12"(305 mm) O.C.
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
402BTHIS DETAIL APPLIES TO:
09-06-2019EXPANSION SERIES
WOOD NAILER SECURED TO DECK
1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.
2. FIELD-FABRICATED EXPANSION JOINT SHOULD NOT BE FLEECE-BACK MEMBRANE. USE PARASOLO SMOOTHMEMBRANE.
3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
HEAT-WELDED LAP (SEE NOTE #3)
48
NOTES:
FIELD FABRICATED WALL EXPANSIONJOINT DETAIL - FLAT TYPE DETAIL
ROOF DECK/SUBSTRATE
PARASOLO MEMBRANE
PARASOLO ADHESIVE (OPTIONAL)
HEAT-WELDED LAP (MIN. 2" WELD)
REINFORCED PARASOLO MEMBRANE
ROOF INSULATION
BATT INSULATION
HEAT-WELDED LAP (SEE NOTE #2)
REINFORCED PARASOLO MEMBRANE
BACKER ROD 1-1/2 TIMES THEOPENING
PARAFAST FASTENERS AND PLATES12" (305 mm) O.C.
WOOD NAILER SECURED TO DECK
REFERENCE PARASOLO PARAPET WALL &CURB FLASHING DETAILS (300 SERIES) FORWALL OR CURB TERMINATION
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
403BTHIS DETAIL APPLIES TO:
09-06-2019EXPANSION SERIESPARASOLO ROOF MEMBRANE SYSTEM
TM
1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.
2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.
3. FIELD-FABRICATED EXPANSION JOINT SHOULD NOT BE FLEECE-BACK MEMBRANE. USE STANDARD PARASOLOMEMBRANE.
49
ROOF DECK/SUBSTRATE
PARASOLO ADHESIVE (OPTIONAL)
HEAT-WELDED LAP (MIN. 2" WELD)
REINFORCED PARASOLO MEMBRANE
ROOF INSULATION
BATT INSULATION
PARASOLO ADHESIVE (OPTIONAL)
PARASOLO MEMBRANE
BACKER ROD 1-1/2 TIMES THE OPENING.
HEAT-WELDED LAP (MIN. 2" WELD)
HEAT-WELD LAP (SEE NOTE #2)
PARASOLO MEMBRANE
FIELD FABRICATED WALL EXPANSIONJOINT DETAIL - CURB TYPE
PARAFAST FASTENERS AND PLATES12" (305 mm) O.C.
NOTES:
REFERENCE PARASOLO PARAPET WALL &CURB FLASHING DETAILS (300 SERIES) FORWALL OR CURB TERMINATION
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
404BTHIS DETAIL APPLIES TO:
09-06-2019EXPANSION SERIES
PARAFAST FASTENERS AND PLATES12" (305 mm) O.C.
RING SHANKED GALVANIZED NAILS 12"(305 mm) O.C.
1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESE COMPONENTS SHOULDBE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.
2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HAND WELDER.
3. FIELD-FABRICATED EXPANSION JOINT SHOULD NOT BE FLEECE-BACK MEMBRANE. USE PARASOLO SMOOTH MEMBRANE.
WOOD NAILER SECURED TO DECK
PARASOLO ROOF MEMBRANE SYSTEMTM
50
TERMINATION AT R.T.U. WITHWELDED LAP DETAIL
ROOF INSULATION
R.T.U.
GALVANIZED ROOF NAILS AT 12" (305 mm)
PARAFAST FASTENERS 12" (305 mm) O.C.
ROOF INSULATION
ROOF DECK/SUBSTRATE
WOOD NAILER THICKNESS OF INSULATION
HEAT-WELDED LAP (SEE NOTE #2)
REINFORCED PARASOLO MEMBRANE
INSULATED METAL CURB
REINFORCED PARASOLO MEMBRANE
REFERENCE PARASOLO PARAPET WALL& CURB FLASHING DETAILS (300 SERIES)FOR BASE TERMINATION
NOTES:
O.C. MAX
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
503ATHIS DETAIL APPLIES TO:
09-06-2019PENETRATION SERIES
1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY.THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.
2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELDWITH HAND WELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
51
ROOF INSULATION
R.T.U.
PARAFAST FASTENERS 12" (305 mm) O.C.
ROOF INSULATION
ROOF DECK/SUBSTRATE
WOOD NAILER SECURED TO DECK
HEAT-WELD (SEE NOTE #1)
REINFORCED PARASOLO MEMBRANE
INSULATED METAL CURB
REINFORCED PARASOLO MEMBRANE
REFERENCE PARASOLO PARAPET WALL &CURB FLASHING DETAILS (300 SERIES)FOR BASE TERMINATION
NOTES:
TERMINATION AT EXISTING R.T.U. WITHCOUNTER FLASHING DETAIL
PARAFAST FASTENERS 12" (305 mm) O.C MAX
WOOD NAILER
METAL COUNTER FLASHING OR SLIPFLASHING BY OTHERS 3" (76.2 mm) MIN. FACE.
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
503BTHIS DETAIL APPLIES TO:
09-06-2019PENETRATION SERIES
1. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELDWITH HAND WELDER.
2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY.THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLYACCEPTED INDUSTRY PRACTICES, STANDARDS, AND APPROVALS.
PARASOLO ROOF MEMBRANE SYSTEMTM
52
NOTES:
PARASOLO MEMBRANE TARGET
VENT STACK
STAINLESS STEEL CLAMP
PARASOLO DETAILING MEMBRANE
REINFORCED PARASOLO MEMBRANE
HEAT-WELDED LAP (SEE NOTE #3)
PARASOLO BONDING ADHESIVE
ROOF DECK/SUBSTRATE
ROOF INSULATION
PARASOLO WATER-BLOCK SEALANT
(OPTIONAL)
FIELD-WRAPPED PENETRATIONFLASHING DETAIL
PLAN VIEW
TARGET MADE FROM PARASOLO MEMBRANE
1/2" UP PIPE
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
507THIS DETAIL APPLIES TO:
09-05-2019PENETRATION SERIES
2" (52 mm)
2" (52 MM)
PARASOLO FLEXSEAL CAULKGRADE SEALANT
PARASOLO FASTENERS & PLATES(4 PER PENETRATION)
8" (2
03 m
m)
1"(25.4 mm)
1. FOR INSULATION THICKNESS GREATER THAN 8” (203 MM), AN APPROVED COVERBOARD IS REQUIRED ONMECHANICALLY ATTACHED SYSTEMS ONLY.
2. APPLY HEAT TO UNREINFORCED DETAIL MEMBRANE AND FORM BY HAND PRIOR TO HOT AIR WELDING.
3. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATIC MACHINE WELDERAND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
53
PARAFAST FASTENERS &PLATES 12" (305 mm) O.C.
NOTES:
HEAT-WELDED LAP (SEE NOTE #4)
REINFORCED PARASOLO
METAL BASE
HIGH TEMPERATURE
STAINLESS STEEL CLAMP
RAIN HOOD
PIPE STACK
MEMBRANE
ROOF DECK/SUBSTRATE
PARATHERM ROOF
PLAN VIEW
INSULATION
PARASOLO MEMBRANE TARGET(SEE ABOVE)
HIGH TEMPERATURE STACK FLASHINGDETAIL
TARGET MADE FROM PARASOLOMEMBRANE
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
508THIS DETAIL APPLIES TO:
09-06-2019PENETRATION SERIES
2" (52 mm)
2" (52 MM)
PARASOLO FLEX SEAL CAULKGRADE SEALANT
WOOD NAILER SECURED TODECK (OPTIONAL)
PARASOLO DETAILINGMEMBRANE
1. TO BE USED WHEN TEMPERATURE OF STACK EXCEEDS 160° F.
2. FOR INSULATION THICKNESS GREATER THAN 8” (203 MM), AN APPROVED COVERBOARD IS REQUIRED ONMECHANICALLY ATTACHED SYSTEMS ONLY.
3. APPLY HEAT TO DETAIL MEMBRANE AND FORM BY HAND PRIOR TO INSTALLING.
4. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATIC MACHINE WELDERAND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
PARASOLO WATER-BLOCKSEALANTPARASOLO BONDINGADHESIVE (OPTIONAL)
54
NOTES:
REINFORCED PARASOLO MEMBRANE
ROOF DECK/SUBSTRATE
ROOF INSULATION
PENETRATION with PARAPROFLASHING - OPTION 1
PLAN VIEW
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #510A
THIS DETAIL APPLIES TO:
09-10-2019PENETRATION SERIES
PARAFAST FASTENERS & PLATES(4 PER PENETRATION)
8" (2
03 m
m)
PARASOLO ROOF MEMBRANE SYSTEMTM
PARAPRO 123 FLASHING SYSTEM(FULLY ADHERE)
PENETRATION(SEE NOTE #1 FOR PREPARATION)
3" MIN.
PARASOLO FLEXSEAL CAULKGRADE SEALANT
PARAPRO 123 FLASHING SYSTEM(FULLY ADHERE)
1. REFER TO SIPLAST PREPARATION GUIDELINES FOR PROPER SURFACE TREATMENT OF ALL MATERIALS PRIOR TO APPLICATION OF PARAPROMATERIALS.
2. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS AND THE PARAPRO 123 FLASHING SYSTEM INSTALLER'SGUIDE SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.
4"
PARASOLO MEMBRANE TARGET
HEAT-WELDED LAP (MIN. 2" WELD)
PARASOLO MEMBRANE TARGET
REINFORCED PARASOLO MEMBRANE
55
NOTES:
REINFORCED PARASOLO MEMBRANE
ROOF DECK/SUBSTRATE
ROOF INSULATION
PENETRATION with PARAPROFLASHING - OPTION 2
PLAN VIEW
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #510B
THIS DETAIL APPLIES TO:
09-10-2019PENETRATION SERIES
PARAFAST FASTENERS &RHINOBOND PVC PLATES(4 PER PENETRATION)
8" (2
03 m
m)
PARASOLO ROOF MEMBRANE SYSTEMTM
PARAPRO 123 FLASHING SYSTEM(FULLY ADHERE)
PENETRATION(SEE NOTE #1 FOR PREPARATION)
3"
PARASOLO FLEXSEAL CAULKGRADE SEALANT
PARAPRO 123 FLASHING SYSTEM(FULLY ADHERE)
1. REFER TO SIPLAST PREPARATION GUIDELINES FOR PROPER SURFACE TREATMENT OF ALL MATERIALS PRIOR TO APPLICATION OF PARAPROMATERIALS.
2. REQUIREMENTS AND RECOMMENDATIONS DETAILED IN CURRENT SIPLAST SPECIFICATIONS AND THE PARAPRO 123 FLASHING SYSTEM INSTALLER'SGUIDE SHALL APPLY IN ADDITION TO THE ABOVE DRAWING.
REINFORCED PARASOLOMEMBRANE
56
EXPOSED WOOD EQUIPMENTSUPPORT SLEEPER DETAIL
REINFORCED PARASOLO MEMBRANE
WOOD SLEEPER
WOOD BLOCKING
NOTES:
ROOF DECK/SUBSTRATE
ROOF INSULATION
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
511THIS DETAIL APPLIES TO:
09-05-2019PARAPET WALL & CURB SERIES
PARASOLO WALKWAY PADCONTINUOUS UNDER BLOCKING
1. IF THE INSULATION COMPRESSIVE STRENGTH IS INSUFFIENT FOR THE EQUIPMENT WEIGHT, INSTALL WOODBLOCKING UNDER THE EQUIPMENT CARRYING WOOD SLEEPER, MATCHING THE HEIGHT OF THE INSULATION.
2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.
PARASOLO ROOF MEMBRANE SYSTEMTM
57
EQUIPMENT SUPPORT BRACKET
HEAT-WELDED LAP (SEE NOTE #2)
SECURED TO DECKEQUIPMENT SUPPORT
PARASOLO ADHESIVE (OPTIONAL)
REINFORCED PARASOLO MEMBRANE
NOTES:
ROOF DECK/SUBSTRATE
ROOF INSULATION
CONCEALED WOOD EQUIPMENTSUPPORT DETAIL
REINFORCED PARASOLO MEMBRANE
PARAFAST FASTENERS & PLATES12" (305 mm) O.C.
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
512THIS DETAIL APPLIES TO:
PARASOLO FLEXSEAL CAULK GRADESEALANT
09-06-2019PENETRATION SERIES
1. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESE COMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.
2. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
58
TAPERED INSULATION
REINFORCED PARASOLO MEMBRANE
DRAIN CLAMP RING
DRAIN STRAINER
NOTES:
ROOF DECK/SUBSTRATE
DRAIN CLAMP RING
DRAIN STRAINER
ROOF DECK/SUBSTRATE
ROOF INSULATION
DRAIN - STANDARD FLASHING DETAIL
PARASOLO WATER-BLOCK SEALANT
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
513THIS DETAIL APPLIES TO:
09-05-2019PENETRATION SERIES
1"
1. A FIELD WELD CANNOT PASS WITHIN 9" (227 MM) OF THE CLAMP RING, OR WITHIN THE DRAIN SUMP ITSELF.
2. MEMBRANE MUST EXTEND MINIMUM 1" (25.4 MM) BEYOND THE BOLT HOLES. THE CLAMPING RING BOLTS MUSTPENETRATE THE MEMBRANE.
3. TAPERED INSULATION TO CREATE A ROOF SUMP MINIMUM 36" (0.914 M) X 36" (0.914 M) IN SIZE. (IF APPLICABLE).
4. USE ONE FULL TUBE OF PARASOLO WATER BLOCK SEALANT PER DRAIN.
PARASOLO ROOF MEMBRANE SYSTEMTM
59
DRAIN BASE
CUT SECTION OFUNREINFORCED PARASOLOMEMBRANE AS SHOWN ANDPOSITIONED INTO DRAIN SUMP.EXTEND MEMBRANE OUT OF DRAINSUMP APPROX. 6" (152 mm).
EXTEND REINFORCED PARASOLOMEMBRANE ONTO MEMBRANE SECTIONPOSITIONED AT DRAIN SUMP AND CUTAS SHOWN TO LAY FLAT IN SUMP. HOTAIR WELD A MIN.OF 2" (52 mm)COMPLETELY SURROUNDING AREA.
MIN. 1-1/2" (38.1 mm) WIDE HEAT-WELD
DRAIN CLAMPING
DRAIN SUMPBOUNDARY
UNREINFORCED PARASOLOMEMBRANE
FIELDMEMBRANECUT TO LAYFLAT IN SUMPAREA
MIN. 1-1/2" (38.1mm) WIDEHEAT-WELD
DRAIN- SEVERE SUMP TARGET DETAIL
MIN. 12" (305 mm)
APPROX. 6" (152 mm)
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
518THIS DETAIL APPLIES TO:
09-05-2019PENETRATION SERIES
TM
3" (76 mm) MIN.
PARASOLO ROOF MEMBRANE SYSTEMTM
60
DRAIN - PRE TARGET DETAIL
PLAN VIEW
DRAIN CLAMP RING
DRAIN STRAINER
ROOF DECK/SUBSTRATE
HEAT-WELDED LAP (SEE NOTE #7)
REINFORCED PARASOLO MEMBRANE
PARAFAST FASTENERS & PLATES 12"(305 mm) O.C.
REINFORCED PARASOLO MEMBRANE(SMOOTH ONLY) TARGET
PARAFAST FASTENERS & PLATES 12"(305 mm) O.C.
PARASOLO WATER BLOCK SEALANT
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
519THIS DETAIL APPLIES TO:
09-05-2019PENETRATION SERIES
NOTES:
1. A FIELD WELD CANNOT PASS WITHIN 9" (227 MM) OF THE CLAMP RING, OR WITHIN THE DRAIN SUMP ITSELF.
2. MEMBRANE MUST EXTEND MINIMUM 1" (25.4 MM) BEYOND THE BOLT HOLES. THE CLAMPING RING BOLTS MUSTPENETRATE THE MEMBRANE.
3. TAPERED INSULATION TO CREATE A ROOF SUMP MINIMUM 36" (0.914 M) X 36" (0.914 M) IN SIZE. (IF APPLICABLE).
4. IF ASPHALT OR ASPHALTIC PRODUCT IS PRESENT, STOP AT BEGINNING OF SUMP AND FLASH WITH FLEECEBACKMEMBRANE.
5. DO NOT RUN SEPARATION SHEET INTO BOWL AREA IF USED IN SYSTEM.
6. USE ONE FULL TUBE OF PARASOLO WATER BLOCK SEALANT PER DRAIN.
7. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD BEYOND FASTENER PLATES WITH AUTOMATIC MACHINE WELDERAND 2" MIN. WELD BEYOND FASTENER PLATES WITH HAND WELDER.
1"
TAPERED ROOF INSULATION
PARASOLO ROOF MEMBRANE SYSTEMTM
61
DRAIN - POST TARGET DETAIL
NOTES:
ROOF INSULATION
ROOF DECK/SUBSTRATE
REINFORCED PARASOLO MEMBRANE
DRAIN CLAMP RING
DRAIN STRAINER
HEAT-WELDED LAP (SEE NOTE #6)
REINFORCED PARASOLO MEMBRANE(SMOOTH ONLY)
TAPERED ROOF INSULATION(OPTIONAL)
PARASOLO WATER-BLOCK SEALANT
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
520THIS DETAIL APPLIES TO:
09-06-2019PENETRATION SERIES
1"
1. A FIELD WELD CANNOT PASS WITHIN 9" (227 MM) OF THE CLAMP RING, OR WITHIN THE DRAIN SUMP ITSELF.
2. MEMBRANE MUST EXTEND MINIMUM 1" (25.4 MM) BEYOND THE BOLT HOLES. THE CLAMPING RING BOLTS MUSTPENETRATE THE MEMBRANE.
3. TAPERED INSULATION TO CREATE A ROOF SUMP MINIMUM 36" (0.914 M) X 36" (0.914 M) IN SIZE. (OPTIONAL).
4. DO NOT RUN SEPARATION SHEET INTO BOWL AREA IF USED IN SYSTEM.
5. USE ONE FULL TUBE OF PARASOLO WATER BLOCK SEALANT PER DRAIN.
6. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
62
POURABLE SEALANT POCKET DETAIL
NOTES:
ROOF INSULATION
ROOF DECK/SUBSTRATE
ROOF PROJECTION
QUICK SET NON-SHRINK GROUT INPOCKET UNDER SEALANT
PREMOLDED PARASOLOSEALANT POCKET
PARASOLO REINFORCEDMEMBRANE
PARASOLO APPROVED SEALANTS
HEAT WELD FLANGE MIN.2" (52 mm)
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
525THIS DETAIL APPLIES TO:
09-05-2019PENETRATION SERIESPARASOLO ROOF MEMBRANE SYSTEM
TM
1. ALLOW 2" (52 MM) CLEARANCE AROUND THE PROJECTION. IF MULTIPLE PROJECTIONS, ALLOW 1" (25.4 MM)BETWEEN PROJECTION AND POCKET.
2. THE EXISTING PROJECTION MUST BE CLEAN OF ALL DEBRIS BEFORE INSTALLATION.
3. FOUR PARAFAST FASTENERS & PLATES INSERTED AROUND PENETRATION.
4. IF SEALANT POCKET MUST BE CUT, STRIP IN CUT WITH UNREINFORCED PVC STRIP MIN 4" (102 MM) WIDE AND RUNOUT ONTO DECK SHEET MINIMUM 2" (52 MM).
5. IF PLATES AND FASTENERS ENCROACH INTO THE SEAM AREA OF THE POCKET, THEN A TARGET MUST BE ADDEDFIRST TO COVER FASTENERS.
63
CONICAL PIPE BOOT (NON-SPLIT)
2" (51 MM) HEAT-WELDEDLAP AROUND PERIMETERBEYOND FASTENER PLATES
PARASOLO FLEXSEALCAULK GRADE SEALANT
EXISTING PENETRATION
PARASOLO CONICALPIPE BOOT
REINFORCED PARASOLOMEMBRANE
ROOF INSULATION
ROOF DECK/SUBSTRATE
NOTES:
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
526ATHIS DETAIL APPLIES TO:
09-05-2019PENETRATION SERIES
STAINLESS STEEL CLAMP
1. FOUR PARAFAST FASTENERS & PLATES AROUND PENETRATION.
2. IF PLATES AND FASTENERS ENCROACH INTO THE SEAM AREA OF THE POCKET, A TARGET MUST BE ADDED FIRSTTO COVER FASTENERS.
3. THIS PRODUCT IS AVAILABLE IN CUSTOM SIZES. CONTACT SIPLAST FOR MORE INFORMATION.
PARASOLO ROOF MEMBRANE SYSTEMTM
64
CONICAL PIPE BOOT (SPLIT)
HEAT-WELDED LAP(MIN. 2" WELD)
2" (51 MM) HEAT-WELDEDLAP AROUND PERIMETERBEYOND FASTENER PLATES
PARASOLO FLEXSEALCAULK GRADE SEALANT
EXISTING PENETRATION
PARASOLO CONICAL PIPEBOOT
REINFORCED PARASOLOMEMBRANE
ROOF INSULATION
ROOF DECK/SUBSTRATE
NOTES:
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
526BTHIS DETAIL APPLIES TO:
09-06-2019PENETRATION SERIES
1. FOUR PARAFAST FASTENERS & PLATES AROUND PENETRATION.
2. IF PLATES AND FASTENERS ENCROACH INTO THE SEAM AREA OF THE POCKET, A TARGET MUST BE ADDED FIRSTTO COVER FASTENERS.
3. THIS PRODUCT IS AVAILABLE IN CUSTOM SIZES. CONTACT SIPLAST FOR MORE INFORMATION.
PARASOLO ROOF MEMBRANE SYSTEMTM
STAINLESS STEEL CLAMP
65
ROOF INSULATION
REINFORCED PARASOLO MEMBRANE
PARASOLO ADHESIVE
PARASOLO WATER BLOCK SEALANT
METAL CAP BY OTHERS
ROOF DECK/SUBSTRATE
HEAT-WELDED LAP (SEE NOTE #4)
12" (305 mm) O.C. - BOTH SIDESGROMMETTED FASTENERS
NOTES:
USE LIKE MATERIALS ACCORDING TOEXISTING ROOF SYSTEM
ADJACENT ROOF SYSTEM
REINFORCED PARASOLO MEMBRANE
CURB TYPE TIE-IN AT FLAT ROOF
(OPTIONAL)
WOOD NAILERS SET IN SEALANT
PARAFAST FASTENERS & PLATES12" (305 mm) O.C.
WOOD NAILERS FASTENED TO DECK(MUST BE 4" HIGHER THAN FINISHED DECK)
WOOD NAILERS FASTENED TO DECK
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
602THIS DETAIL APPLIES TO:
09-05-2019SPECIAL CONSTRUCTION SERIES
8" (2
03 M
M)
PARASOLO ROOF MEMBRANE SYSTEMTM
1. FOR INSULATION THICKNESS GREATER THAN 8” (203 MM), AN APPROVED COVERBOARD IS REQUIRED ONMECHANICALLY ATTACHED SYSTEMS ONLY.
2. THE CARPENTRY AND METAL WORK SHOWN DEPICTS SHOP FABRICATION AND JOB-SITE ASSEMBLY. THESECOMPONENTS SHOULD BE DESIGNED/FABRICATED/INSTALLED ACCORDING TO GENERALLY ACCEPTED INDUSTRYPRACTICES, STANDARDS, AND APPROVALS.
3. SIPLAST DOES NOT GUARANTEE THE WATERTIGHT INTEGRITY OF TIE-INS TO MEMBRANE ROOF SYSTEMS BYOTHER MANUFACTURERS.
4. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.
66
HEAT WELDED WALKWAYINSTALLATION
PARASOLO REINFORCED MEMBRANE
HEAT-WELDED LAP (SEE NOTE #4)
PARASOLO WALKWAY PAD CUT FROM
30" (762 mm)
ROUND CORNERS
NOTES:
ROOF INSULATION
ROOF DECK / SUBSTRATE
HEAT-WELDED AREA 2" (52 mm)CONTINUOUSLY AROUND PERIMETER
6"min
WALKWAY ROLL
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
604THIS DETAIL APPLIES TO:
09-05-2019SPECIAL CONSTRUCTION SERIES
6" (152 MM)
6" (152 MM)
1. DO NOT CROSS SEAMS WITH WALKWAY PADS 6" (152 MM) OFF EACH SEAM.
2. HEAT-WELD EDGE OF WALKWAY PADS CONTINUOUSLY.
3. REQUIRED AT ALL ROOF ACCESS POINTS.
4. FOR HEAT-WELDING LAPS USE 1.5" MIN. WELD WITH AUTOMATIC MACHINE WELDER AND 2" MIN. WELD WITH HANDWELDER.
PARASOLO ROOF MEMBRANE SYSTEMTM
67
CABLE LINE/LIGHTNING ROD BASE
HEAT-WELDED LAP (MIN. 2" WELD)
LIGHTNING ROD
HEAT WELD (MIN. 2" WELD)(BOTH SIDES)
A
A
ROOF INSULATIONROOF DECK / SUBSTRATE
SECTION A
REINFORCED PARASOLO MEMBRANE
REINFORCED PARASOLO MEMBRANE6" (152 mm) x 6" (152 mm) PATCH
LIGHTNING PROTECTION TERMINAL -ROOF MOUNT DETAIL N.T.S.
SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
605THIS DETAIL APPLIES TO:
09-05-2019SPECIAL CONSTRUCTION SERIES
5" (127 MM) M
AX
1. DAMAGE TO PARASOLO MEMBRANE EXCLUDED FROM GUARANTEE COVERAGE.
NOTE:
PARASOLO ROOF MEMBRANE SYSTEMTM
68
LIGHTNING PROTECTION TERMINAL -WALL MOUNT DETAIL
REINFORCED PARASOLOMEMBRANE
PARASOLO FLEXSEALSEALANT AROUND PLATE
PARASOLO WATER BLOCKSEALANT BETWEEN PLATEAND FLASHING MEMBRANE
SUPPORT PLATE
REINFORCED PARASOLOMEMBRANE STRAP HOT AIRWELDED TO FLASHING
REINFORCED PARASOLOMEMBRANE
PARASOLO WATER BLOCKSEALANT BETWEEN PLATEAND FLASHING MEMBRANE
PARASOLO FLEXSEALSEALANT AROUND PLATE
SIDE MOUNT AIR TERMINALBASE
SUPPORT PLATE
SIDE MOUNT LIGHTING RODHOLDER
ALTERNATE ROD WALL MOUNT
TWISTED COPPER ORALUMINUM CABLE
TWISTED COPPER ORALUMINUM CABLE
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
607THIS DETAIL APPLIES TO:
09-05-2019SPECIAL CONSTRUCTION SERIESPARASOLO ROOF MEMBRANE SYSTEM
TM
1. DAMAGE TO PARASOLO MEMBRANE EXCLUDED FROM GUARANTEE COVERAGE.
NOTE:
69
PARASOLO REINFORCED
PARASOLO WALKWAY PAD
CONCRETE BLOCK WEIGHT
SATELLITE DISH BASE TRAY
ROOF INSULATION
ROOF DECK / SUBSTRATE
MEMBRANE
N.T.S.SCALE:
REVISION DATE:1000 ROCHELLE BOULEVARD - IRVING, TX 75062
(800) 922-8800
ALL SYSTEMS
www.siplast.com
DRAWING #
608THIS DETAIL APPLIES TO:
SATELLITE DISH MOUNTING DETAIL
09-05-2019SPECIAL CONSTRUCTION SERIESPARASOLO ROOF MEMBRANE SYSTEM
TM
70
71
72
73
September 2019
For information on Siplast Roofing and Waterproofing Systems, scan our QR Code.
Siplast
1000 Rochelle Blvd.
Irving, Texas 75062
469-995-2200
Facsimile: 469-995-2205
In Canada:
201 Bewicke Ave., Suite 208
Vancouver, BC,
Canada V7M 3M7
604-929-7687
Customer Service in
North America:
Toll Free 1-800-922-8800
www.siplast.com