WW
W.RIVETEN
G.CO
M | (720) 288-1580 | (719) 271-7419
PO
BO
X 1238, PARKER, CO
| PO
BO
X 64513, CO
LO
. SPG
S., CO
RIVET No.
DATE:ISSUE/REV:
SHEET No.
SHEET TITLE:
DESIGN by:
REVIEW by:
of
Panoram
a Estates
Deck and Stair Repair &
Reskin
502-544 Superior Street
Colorado Springs, CO
80904
BID SET 9/8/2017
JBP
JRW
170305X
10
BID SET ROOFS 1/10/2018
For Constr. 6/29/2018
-- --
-- --
6/29/2018
GENERAL NOTES
AND DETAILS
S1
1
DESIGN CRITERIA
BUILDING CODE: 2009 EDITION OF THE INTERNATIONAL RESIDENTIAL CODE (IRC) WITH ASCE7-05 DESIGN PROCEDURES
AND APPLICABLE LOCAL AMENDMENTS. ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE
APPLICABLE REQUIREMENTS THEREIN. THESE CONSTRUCTION DOCUMENTS WERE PREPARED BY RIVET ENGINEERING
GROUP, LLC ACTING AS THE ENGINEER OF RECORD FOR THE REPAIR PROJECT.
THE PROJECT CONSTITUTES A REPAIR UNDER THE CURRENT BUILDING CODE. THIS PROPERTY WAS ORIGINALLY
CONSTRUCTED UNDER A PREVIOUS BUILDING CODE AND MUST CONFORM TO THE MINIMUM STANDARDS OF THAT
CODE. NEW CONSTRUCTION MUST CONFORM TO THE CURRENT BUILDING CODE.
ROOF SNOW LOAD = 30 PSF ROOF DEAD LOAD = 15 PSF TOTAL
FLOOR LIVE LOAD = 40 PSF DECK DEAD LOAD = 10 PSF TOTAL
BASIC WIND SPEED = 100 MPH (3-SECOND GUST) EXPOSURE CATEGORY = C
SOIL SITE CLASS = D SEISMIC DESIGN CATEGORY = B
FROST DEPTH = 30 INCHES BELOW GRADE
GENERAL CONSTRUCTION NOTES
A. THE FOLLOWING GENERAL REQUIREMENTS FOR MATERIALS AND WORKMANSHIP APPLY UNLESS NOTED OTHERWISE
ON THESE DRAWINGS OR SUBSEQUENT DOCUMENTS ISSUED BY ENGINEER.
B. SEE ASSOCIATED SPECIFICATIONS FOR ADDITIONAL INFORMATION REGARDING MATERIALS USED.
C. PRODUCT SUBSTITUTIONS OR CHANGES TO THESE DOCUMENTS MUST BE APPROVED BY THE ENGINEER. DEVIATIONS
FROM THESE DRAWINGS DOES NOT IMPLY ACCEPTANCE BY ENGINEER.
D. PERIODIC CONSTRUCTION OBSERVATIONS BY ENGINEER DO NOT NECESSARILY CONSTITUTE "SPECIAL INSPECTIONS"
NOR DO THEY NECESSARILY MEET THE BUILDING DEPARTMENT'S REQUIREMENTS FOR INSPECTIONS. CONTRACTOR
SHALL BE RESPONSIBLE FOR RECEIVING AND PASSING THE INSPECTIONS REQUIRED BY THE BUILDING DEPARTMENT.
E. THESE DRAWINGS INDICATE THE COMPLETED STRUCTURE WITH THE ELEMENTS IN THEIR FINAL POSITION. THE
CONTRACTOR SHALL ASSEMBLE THE VARIOUS ELEMENTS, IN THE PROPER SEQUENCE, WITH ADEQUATE SHORING AND
BRACING DURING CONSTRUCTION TO ACHIEVE THE FINAL CONDITIONS DETAILED ON THESE DOCUMENTS.
F. SHOP DRAWINGS SUBMITTED TO ENGINEER ARE REVIEWED FOR GENERAL CONFORMANCE WITH THE DESIGN SHOWN
HEREIN. ENGINEER IS NOT RESPONSIBLE FOR CHECKING QUANTITIES, DIMENSIONS, OR COORDINATING SHOP
DRAWINGS WITH OTHER TRADES.
G. DO NOT SCALE THESE DRAWINGS FOR DIMENSIONS. COORDINATE WITH EXISTING CONDITIONS AND OTHER
PROJECT DOCUMENTS (IF ANY) FOR DIMENSION VERIFICATION.
H. DIMENSIONS INDICATED FOR EXISTING CONDITIONS ARE APPROXIMATE AND REQUIRE FIELD VERIFICATION BY
CONTRACTOR PRIOR TO FABRICATION AND INSTALLATION OF NEW MATERIALS.
I. GENERAL CONTRACTOR IS RESPONSIBLE FOR MEANS, METHODS, TECHNIQUES, SEQUENCES, AND PROCEDURES FOR
THIS PROJECT. NOTIFY ENGINEER OF OMISSIONS, CONFLICTS, OR DISCREPANCIES BETWEEN THESE DRAWINGS AND
THE DRAWINGS (IF ANY) FOR OTHER TRADES OR EXISTING CONDITIONS. COORDINATE REQUIREMENTS FOR
MECHANICAL / ELECTRICAL / PLUMBING / HVAC OR OTHER PENETRATIONS THROUGH STRUCTURAL MEMBERS WITH
ENGINEER PRIOR TO INSTALLATION. ENGINEER ASSUMES NO LIABILITY FOR JOBSITE SAFETY.
J. DETAILS FOR CONDITIONS NOT SPECIFICALLY SHOWN ON THESE DRAWINGS SHALL BE CONSTRUCTED IN A MANNER
SIMILAR TO THE DETAILS THAT ARE SHOWN FOR LIKE CONDITIONS. CONDITIONS THAT MAY NOT BE ADEQUATELY
DETAILED SHALL BE BROUGHT TO THE ENGINEER'S ATTENTION FOR REVIEW AND CLARIFICATION PRIOR TO
CONSTRUCTION.
K. CONTRACTOR SHALL BE RESPONSIBLE FOR CONTACTING ENGINEER TO SCHEDULE SITE OBSERVATION VISITS DURING
CONSTRUCTION. ENGINEER RESERVES THE RIGHT TO PERFORM OBSERVATIONS OF THE ONGOING CONSTRUCTION
ACTIVITY FOR PURPOSES OF VERIFICATION AND DOCUMENTATION. THESE DRAWINGS MAY BE REVISED BY ENGINEER
VIA SUPPLEMENTAL DOCUMENTS AS NEEDED DURING CONSTRUCTION PENDING FURTHER OBSERVATION AND FIELD
VERIFICATION OF EXISTING CONDITIONS.
L. DESPITE SIGNIFICANT EFFORTS TO PROVIDE A COMPLETE AND CLEAR SET OF CONSTRUCTION DOCUMENTS,
DISCREPANCIES OR OMISSIONS MAY OCCUR. RELEASE OF THESE DRAWINGS ANTICIPATES COOPERATION AND
CONTINUED COMMUNICATION BETWEEN THE ENGINEER, THE CONTRACTOR, AND THE OWNER TO ACHIEVE
SUCCESSFUL COMPLETION OF THE PROJECT. THESE DRAWINGS HAVE BEEN PREPARED FOR USE BY A QUALIFIED
CONTRACTOR EXPERIENCED IN THE CONSTRUCTION TECHNIQUES AND SYSTEMS DEPICTED HEREIN.
FOUNDATION DESIGN PARAMETERS
A. THE FOLLOWING PRESUMPTIVE SOIL PARAMETERS MUST BE VERIFIED BY A GEOTECHNICAL ENGINEER AT TIME OF
EXCAVATION. A COPY OF THE GEOTECHNICAL ENGINEER'S FINDINGS SHALL BE PROVIDED TO STRUCTURAL ENGINEER
FOR RE-EVALUATION OF THE FOUNDATION DESIGN PRIOR TO PLACING CONCRETE. A COPY OF ANY SUBSEQUENT
RECOMMENDATIONS FROM THE GEOTECHNICAL ENGINEER SHALL BE PROVIDED TO STRUCTURAL ENGINEER PRIOR TO
PLACING CONCRETE OR BACKFILL.
ALLOWABLE SOIL BEARING PRESSURE = 1,500PSF MINIMUM DEAD LOAD = 0 PSF
B. FOUNDATION EXCAVATIONS SHALL BE OBSERVED BY A GEOTECHNICAL ENGINEER PRIOR TO PLACING CONCRETE.
C. A COPY OF THE GEOTECHNICAL ENGINEER'S RECOMMENDATIONS SHALL BE PROVIDED TO THE ENGINEER FOR
RE-EVALUATION OF THE FOUNDATION DESIGN.
D. FOOTINGS SHALL BEAR BELOW FROST DEPTH ON NATURAL UNDISTURBED SOIL, OR COMPACTED FILL, PER THE
RECOMMENDATIONS OF THE GEOTECHNICAL ENGINEER.
CONCRETE REQUIREMENTS
A. CONCRETE DESIGN IS BASED ON THE "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE" (ACI 318) AS
ADOPTED BY CHAPTER 19 OF THE IBC.
B. CONCRETE INDICATED ON THESE DRAWINGS SHALL BE CONSTRUCTED AS FOLLOWS WITH NORMAL-WEIGHT
(NOT LIGHT-WEIGHT) AGGREGATE AS FOLLOWS:
C. CONTRACTOR SHALL SUBMIT CONCRETE MIX DESIGNS PREPARED BY BATCH PLANT ENGINEER FOR REVIEW PRIOR TO
CONSTRUCTION.
D. ADMIXTURES CONTAINING CHLORIDE SALTS ARE UNACCEPTABLE. NO FLY ASH ADDITIVES MAY BE USED IN
FLATWORK OR ARCHITECTURALLY EXPOSED CONCRETE. FLY ASH SHALL BE LIMITED TO 10% OF CEMENTITIOUS
MATERIALS AND SHALL HAVE A REPLACEMENT FACTOR OF 1.2 RELATIVE TO CEMENT.
E. CONTRACTOR SHALL SUBMIT BATCH PLANT TICKETS DOCUMENTING THEIR DELIVERIES TO JOB-SITE WITHIN 14 DAYS
OF PLACING CONCRETE.
F. COLD WEATHER / HOT WEATHER CONCRETING PROCEDURES SHALL BE IMPLEMENTED BY CONTRACTOR AS NEEDED
PER THE RECOMMENDATIONS OF THE ACI "MANUAL OF CONCRETE PRACTICE."
G. MECHANICALLY VIBRATE FRESHLY PLACED CONCRETE.
H. PROVIDE
3
4
" CHAMFER AT EXPOSED EDGES AND CORNERS.
REINFORCING STEEL REQUIREMENTS
A. DETAILING, FABRICATION, AND PLACING OF REINFORCING STEEL SHALL BE IN ACCORDANCE WITH ACI'S "MANUAL OF
CONCRETE PRACTICE"
B. REINFORCING STEEL SHALL COMPLY WITH ASTM A615, GRADE 60 UNLESS NOTED OTHERWISE.
C. #6 AND SMALLER BARS SHALL BE OVERLAPPED AT LEAST 36 BAR DIAMETERS AT SPLICES. BARS SHALL BE IN
PHYSICAL CONTACT AT SPLICES.
D. DO NOT USE MECHANICAL / WELDED SPLICES.
E. WELDED WIRE FABRIC (WWF) SHALL COMPLY WITH ASTM A-185. LAP WWF SHEETS A MINIMUM OF ONE FULL MESH
PLUS 2". LAPS SHALL BE TIED TOGETHER.
F. CONCRETE COVERAGE FOR REINFORCING STEEL SHALL BE AS FOLLOWS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH = 3"
CONCRETE EXPOSED TO EARTH OR WEATHER: #5 AND SMALLER = 1
1
2
" #6 OR LARGER = 2"
CONCRETE NOT EXPOSED TO EARTH OR WEATHER: SLABS, WALLS, AND JOISTS (#11 OR SMALLER) =
3
4
"
BEAMS AND COLUMNS = 1
1
2
"
CONCRETE MIX REQUIREMENTS MATRIX
LOCATION / USE
W/C
RATIO
(MAX)
28-DAY
STRENGTH,
F'c (MIN)
AGG.
SIZE
(MAX)
SLUMP
CEMENT
TYPE
AIR
CONTENT
ADMIXTURES
ACI
DURABILITY
NOTES
EXTERIOR SLAB ON
GRADE (SIDEWALK)
0.45
4,500psi 3/4"
3" - 5"
I / II
5% - 8%
N/AF2, S1, W1, C2
FOUNDATIONS:
FOOTINGS, PIERS,
AND WALLS
0.4
5,000psi 3/4"
3" - 5"
I / II
5% - 8%
N/A F3, S1, W1, C2
ANCHORAGE TO CURED CONCRETE REQUIREMENTS
A. EPOXY ANCHORS FOR CONCRETE SHALL BE “HILTI” HY-200 OR “SIMPSON” SET XP HIGH STRENGTH ANCHORING
ADHESIVE OR OTHER EQUIVALENT PRODUCT PRE-APPROVED BY ENGINEER.
B. STEEL ANCHOR RODS FOR EPOXIED ANCHORS SHALL BE GALVANIZED ASTM F1554 GRADE 36 OR 55. GALVANIZED
ASTM A36 ANCHORS ARE ALSO ACCEPTABLE.
C. MECHANICAL ANCHORS FOR CONCRETE SHALL BE "HILTI" KWIK BOLT 3, "SIMPSON" TITEN HD ANCHORS, "REDHEAD"
TRUBOLT ANCHORS, OR OTHER EQUIVALENT PRODUCT PRE-APPROVED BY ENGINEER.
A.B. = ANCHOR BOLT
ADJ. = ADJUSTABLE
A.F.F. = ABOVE FINISH FLOOR
A.F.G. = ABOVE FINISH GRADE
ALT. = ALTERNATE
ANCH. = ANCHOR
APPROX. = APPROXIMATELY
ARCH. = ARCHITECT
BD. = BOARD
BLDG. = BUILDING
BLKG. = BLOCKING
BM. = BEAM
BOT. = BOTTOM
B.O.W. = BOTTOM OF WALL
BRG. = BEARING
CANT. = CANTILEVER
C.J. = CONTROL JOINT
℄ = CENTER LINE
CLG. = CEILNG
CLR. = CLEAR/CLEARANCE
CMU = CONCRETE MASONRY UNIT
COL. = COLUMN
CONC. = CONCRETE
CONN. = CONNECTION
CONT. = CONTINUOUS
CONST. = CONSTRUCTION
C.U. = CODE UPGRADE
DBL. = DOUBLE
DIAG. = DIAGONAL
DIAM. = DIAMETER
DIMS. = DIMENSIONS
D&R = DETACH AND RESET
D.R. = DECAY RESISTANT
DTL. = DETAIL
DWG. = DRAWING
DWL. = DOWEL
(E) = EXISTING
EA. = EACH
E.J. = EXPANSION JOINT
ELEV. = ELEVATION
ENGR. = ENGINEER
EQ. = EQUAL
EQUIV. = EQUIVALENT
EXIST. = EXISTING
EXP. = EXPANSION
EXT. = EXTERIOR
FDN. = FOUNDATION
FLR. = FLOOR
FTG. = FOOTING
GA. = GUAGE (METAL)
GALV. = GALVANIZED
GEN. = GENERAL
G.L. = GLUE-LAM
GYP. = GYPSUM/GYPCRETE
HDR. = HEADER
HORIZ. = HORIZONTAL
HSS = HOLLOW STRUCTURAL STEEL
HT. = HEIGHT
IBC = INTERNATIONAL BUILDING CODE
ICF = INSULATED CONCRETE FORM
IRC = INTERNATIONAL RESIDENTIAL CODE
INSUL. = INSULATION
INT. = INTERIOR
INV. = INVERTED
J = JAMB STUD
JST. = JOIST
K = KING STUD
LAM = LAMINATED
LLH = LONG LEG HORIZONTAL
LLV = LONG LEG VERTICAL
LOC. = LOCATION
LONG. = LONGITUDINAL
LSL = LAMINATED STRAND LUMBER
LTWT. = LIGHTWEIGHT
LVL = LAMINATED VENEER LUMBER
MAS. = MASONRY
MAT. = MATERIAL
MFR. = MANUFACTURER
MAX. = MAXIMUM
MECH. = MECHANCIAL
MIN. = MINIMUM
M.R.B. = MOISTURE RESISTANT BARRIER
(N) = NEW
NOM. = NOMINAL
N.T.S. = NOT TO SCALE
O.A. = ON CENTER
O.H. = OPPOSITE HAND
OPNG. = OPENING
OSB = ORIENTED STRAND BOARD
PEN. = PENETRATION
⅊ = PROPERTY LINE
P.T. = PRESSURE TREATED
RAD. = RADIUS
REC. = RECOMMENDATION
REINF. = REINFORCEMENT
REQ'D. = REQUIRED
REQ'S. = REQUIREMENTS
RET. = RETAINING
R&R = REMOVE AND REPLACE
SIM. = SIMILAR
SQ. = SQUARE
STD. = STANDARD
STL. = STEEL
STRUC. = STRUCTURAL
T = TRIM STUD
T&B = TOP AND BOTTOM
T&G = TONGUE AND GROOVE
THRU = THROUGH
T.O.F. = TOP OF FOOTING
T.O.S. = TOP OF STEEL
T.O.W. = TOP OF WALL
TYP. = TYPICAL
U.N.O. = UNLESS NOTED OTHERWISE
VERT. = VERTICAL
V.I.F. = VERIFY IN FIELD
w/ = WITH
W.R.B. = WATER RESISTANT BARRIER
W.W.F. = WELDED WIRE FABRIC
ABBREVIATION LIST
2. Common or box nails are permitted to be used except where otherwise stated.
1. 2 3/8" x 0.113" nails and 3" x 0.131" nails are standard 8d and 10d Gun nails.
NOTES:
Sole plate to joist or blocking at braced
wall panel
6. Sole plate to joist or blocking
11. Blocking between joist or rafters
to top plate
14. Continuous header, two pieces
19. Rafter to plate
(See Section 2308.10.1, Table 2308.10.1)
13. Top plates, laps and intersections
29. Joist to band joist
2. Bridging to joist
7. Top plate to stud
9. Double Studs
Double top plates
1. Joist to sill or girder
8. Stud to sole plate
10. Double top plates
12. Rim joist to top plate
16. Continuous header to stud
23. Built-up corner studs
CONNECTION TYPE
braced wall panels
16" o.c. along edge
FASTENING
4 - 8d common
16d common
16d common
3" x 0.131" nail
2 - 8d common
2 - 3" x 0.131" nail
3 - 8d common
3 - 3" x 0.131" nail
3 - 16d per 16"
(4)-3" x 0.131" nail per 16"
16d at 16" o.c.
3" x 0.131" nail at 8" o.c.
2 - 16d common
3 - 3" x 0.131" nail
16d at 24" o.c.
3" x 0.131" nail at 8" o.c.
4 - 8d common
4 - 3" x 0.131" nail
2 - 16d common
3 - 3" x 0.131" nail
8d at 6" o.c.
3" x 0.131" nail at 6" o.c.
3 - 8d common
3 - 3" x 0.131" nail
16d at 16" o.c.
3" x 0.131" nail at 12" o.c.
8 - 16d common
12 - 3" x 0.131" nail
3 - 8d common
3 - 3" x 0.131" nail
2 - 16d common
3 - 3" x 0.131" nail
3 - 16d common
5 - 3" x 0.131" nail
face nail
toenail
toenail
face nail
toenail
toenail
24" o.c.
16" o.c.
toenail
end nail
toenail
face nail
end nail
lap splice
toenail each end
typical face nail
typical face nail
*THIS IS AN ABRIDGED SCHEDULE. SEE IBC TABLE 2304.10.1 FOR FULL SCHEDULE
NAILING SCHEDULE - ABRIGED*
STRUCTURAL WOOD FRAMING REQUIREMENTS
A. WOOD CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THE "NATIONAL DESIGN SPECIFICATION
FOR WOOD CONSTRUCTION" (NDS)
B. SAWN LUMBER FOR STRUCTURAL FRAMING SHALL COMPLY WITH THE GRADING RULES OF THE WESTERN WOOD
PRODUCTS ASSOCIATION (WWPA) OR THE WEST COAST LUMBER INSPECTION BUREAU (WCLIB).
C. MAXIMUM MOISTURE CONTENT AT TIME OF INSTALL IS 19%.
D. LUMBER PRODUCTS SHALL BEAR THE GRADE STAMP OF AN APPROVED LUMBER GRADING AGENCY.
E. WOOD FRAMING MEMBERS IN CONTACT WITH CONCRETE SHALL BE PRESSURE TREATED DOUGLAS FIR-LARCH #2
GRADE OR BETTER.
F. 2x AND 4x FRAMING LUMBER SHALL BE DOUGLAS FIR-LARCH #2 GRADE OR BETTER.
G. 6x AND WIDER FRAMING MEMBERS, INCLUDING BEAMS AND POSTS, SHALL BE DOUGLAS-FIR #1 GRADE OR BETTER.
H. BUILT-UP POSTS AND STUDPACKS SHALL CONSIST OF INDIVIDUAL STUDS NAILED TOGETHER WITH (2) ROWS OF 10d
NAILS @ 8"O.C. ALONG EACH STUD.
I. PROVIDE SOLID BLOCKING OR FRAMING BELOW POSTS, STUDPACKS, AND BEAM BEARING LOCATIONS CONTINUOUSLY
DOWN TO FOUNDATION OR TRANSFER BEAMS INDICATED ON THE PLANS. BLOCKING SIZE SHALL MATCH THE SIZE OF
THE POST, STUDPACK, OR BEAM BEARING AREA. SINGLE TRIM STUDS DO NOT REQUIRE CONTINUOUS BLOCKING.
MULTIPLE TRIM STUDS REQUIRE CONTINUOUS BLOCKING.
J. BUILT-UP BEAMS SHALL CONSIST OF INDIVIDUAL MEMBERS NAILED TOGETHER WITH (2) ROWS OF 10d NAILS @
12"O.C. OR BOLTED TOGETHER WITH (2) ROWS OF
1
2
"∅ BOLTS SPACED AT 24"O.C. UNLESS NOTED OTHERWISE.
K. WOOD BEAMS BEARING IN A BEAM POCKET AT CONCRETE WALLS SHALL BEAR ON 6,000PSI NON-SHRINK GROUT AND
A PRESSURE TREATED 2x6 BEARING BLOCK. PROVIDE
1
2
" CLEARANCE BETWEEN THE END OF THE WOOD BEAM AND
THE CONCRETE SURFACE. BLOCK OR SHIM THE SIDES OF THE WOOD BEAM WITH PRESSURE TREATED MATERIAL FOR
LATERAL SUPPORT OF THE BEAM.
L. MINIMUM NAILING SCHEDULES SHALL BE PER THE 2015 IBC TABLE 2304.10.1
M. BOLTS USED FOR FRAMING CONNECTIONS SHALL BE ASTM A307 (Gr.A) AND INCLUDE STANDARD WASHERS AND NUTS.
N. LEDGERLOK AND SIMILAR HIGH-STRENGTH FASTENERS SHALL BE INSTALLED AS AS SHOWN AD REQUIRED BY THE
MANUFACTURER, FASTENMASTER.
O. FRAMING CONNECTORS PROVIDED BY SIMPSON STRONG-TIE OR USP CONNECTORS SHALL BE ATTACHED USING
STANDARD FASTENERS IN EACH OF THE MANUFACTURER'S RECOMMENDED HOLE LOCATIONS. DRAWINGS TYPICALLY
INDICATE SIMPSON PRODUCTS, BUT OTHER PRODUCTS MAY BE USED PENDING STRUCTURAL ENGINEER'S APPROVAL.
P. WOOD NAILER PLATES INSTALLED OVER CONCRETE WALLS OR BEAMS SHALL BE RIPPED TO MATCH THE WIDTH OF
THE COVERED SURFACE.
Q. WOOD USED FOR EXPOSED EXTERIOR APPLICATIONS SHALL BE MOISTURE SEALED UNLESS A NATURALLY DECAY
RESISTANT SPECIES SUCH AS CEDAR OR REDWOOD IS USED.
R. GLUE LAMINATED BEAMS FOR SIMPLE SPANS SHALL BE ALASKAN YELLOW CEDAR 24F-V8 1.5E AT EXTERIOR
LOCATIONS.
S. WOOD STRUCTURAL PANELS FOR WALL, FLOOR, AND ROOF SHEATHING MAY BE NAILED OR SCREWED TO
SUPPORTING FRAMING MEMBERS IN ACCORDANCE WITH THE BUILDING CODE AND THESE DRAWINGS. APA RATED
ADHESIVES MAY ALSO BE USED. PANEL EDGES AT SHEAR WALLS SHALL BE BLOCKED SOLID.
S.1. EXTERIOR WALL SHEATHING SHALL BE
7
16
" THICK APA RATED PLYWOOD OR OSB, EXPOSURE 1,
32
16
SPAN
RATING, ATTACHED TO THE EXTERIOR FACE OF FRAMING WITH 8d NAILS AT 6"O.C. ALONG PANEL EDGES AND AT
12"O.C. TO INTERMEDIATE SUPPORTS.
S.2. FLOOR SHEATHING SHALL BE
23
32
" APA RATED, TONGUE AND GROOVE, PLYWOOD OR OSB SHEATHING WITH A
MINIMUM
48
24
SPAN RATING. SHEATHING SHALL BE GLUED AND NAILED WITH 10d NAILS (0.148"∅ x 3" LONG) @
6"O.C. ALONG ALL SUPPORTING PANEL EDGES AND 12"O.C. IN FIELD. LAY SHEATHING LONG DIRECTION
PERPENDICULAR TO SUPPORTS AND STAGGER PANEL END JOINTS.
T. CONTRACTOR SHALL NOT CUT, NOTCH, OR OTHERWISE MODIFY JOISTS, BEAMS, OR TRUSSES WITHOUT CONSENT OF
THE STRUCTURAL ENGINEER OF RECORD.
U. PROVIDE SOLID BLOCKING BETWEEN RAFTERS, JOISTS, BEAMS, TRUSSES, AND OTHER STRUCTURAL FRAMING
MEMBERS AT LOAD-BEARING SUPPORT LOCATIONS.
VICINITY MAP
STRUCTURAL AND MISCELLANEOUS STEEL REQUIREMENTS
A. STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, AND ERECTED IN ACCORDANCE WITH AISC'S “SPECIFICATION
FOR STRUCTURAL STEEL BUILDINGS” (AISC 360), LATEST EDITION, AND AISC'S “CODE OF STANDARD PRACTICE FOR
STEEL BUILDINGS AND BRIDGES” (AISC 303), LATEST EDITION, AND THE OTHER APPLICABLE SECTIONS OF THE
BUILDING CODE.
B. STRUCTURAL STEEL SHALL RECEIVE ONE SHOP COAT OF TNEMEC “SERIES 10 (99) RED” PRIMER OR EQUIVALENT.
PAINT ALL EXPOSED STEEL PER COLOR SELECTIONS BY OWNER. POWDER COATING SHALL BE PROVIDED AS
ALTERNATE #1.
C. SHOP DRAWINGS FOR INDIVIDUAL STAIRS SHALL BE PROVIDED FOR REVIEW BY THE ENGINEER PRIOR TO
FABRICATION OF NEW MATERIALS. FIELD VERIFY DIMENSIONS SHOWN HEREIN AS EXISTING CONDITIONS VARY BY
LOCATION. REVIEW BY ENGINEER OF SHOP DRAWINGS DOES NOT RELIEVE CONTRACTOR OF RESPONSIBILITIES FOR
QUANTITY, SIZE, AND DIMENSION VERIFICATION.
D. ASTM SPECIFICATIONS FOR STRUCTURAL STEEL SHAPES (TYPICAL UNLESS NOTED OTHERWISE)
D.1. STRUCTURAL STEEL ANGLES (L), PLATES (PL), BARS, AND CHANNELS (C AND MC), SHALL CONFORM TO ASTM A36.
D.2. SQUARE AND RECTANGULAR HOLLOW STRUCTURAL SECTIONS (HSS) SHALL CONFORM TO ASTM A500 GRADE B,
FY=46KSI.
E. BOLTED CONNECTIONS (TYPICAL UNLESS NOTED OTHERWISE)
E.1. BOLTED CONNECTIONS OF STRUCTURAL STEEL TO STRUCTURAL STEEL SHALL CONFORM TO AISC AND RCSC'S
“SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS”, LATEST EDITION.
E.2. BOLTS SHALL BE LONG ENOUGH TO EXTEND THROUGH THE CONNECTED PARTS AND NUT WITH AT LEAST 2
THREADS SHOWING.
E.3. FIELD CONNECTIONS OF STRUCTURAL STEEL TO STRUCTURAL STEEL SHALL BE MADE WITH 3/4-INCH TYPE 1
ASTM A325 BOLTS. CONNECTIONS SHALL BE BEARING TYPE TIGHTENED TO A “SNUG TIGHT” CONDITION.
E.4. SHOP CONNECTIONS OF STRUCTURAL STEEL MEMBERS SHALL BE WELDED.
F. WELDED CONNECTIONS
F.1. EQUIVALENT WELDED CONNECTIONS MAY BE SUBSTITUTED FOR BOLTED CONNECTIONS SUBJECT TO THE
STRUCTURAL ENGINEER OF RECORD'S APPROVAL.
F.2. STRUCTURAL WELDING SHALL BE DONE BY CERTIFIED WELDING OPERATORS AND SHALL CONFORM TO AWS
“STRUCTURAL WELDING CODE” (AWS D1.1), LATEST EDITION.
F.3. STRUCTURAL WELDING SHALL BE PERFORMED WITH AWS A5.1 OR A5.5 E70 X8 ELECTRODES.
F.4. WELD SIZES NOT OTHERWISE SHOWN SHALL BE CONTINUOUS FILLET WELDS, 1/4-INCH OR EQUAL TO THE
THICKNESS OF THE THINNER MATERIAL MINUS 1/16-INCH, WHICHEVER IS LESS.
F.5. AREAS WITHIN 2 INCHES OF FIELD WELDS SHALL NOT BE PAINTED UNTIL AFTER WELDING. FIELD WELDS, BOLT
HEADS, NUTS AND OTHER SURFACES NOT SHOP PAINTED AND SURFACES ABRADED DURING SHIPPING OR
ERECTIONS SHALL BE FIELD PAINTED IMMEDIATELY AFTER ERECTION.
SITE MAP
BLDG. 1
BLDG. 2
BLDG. 3
BLDG. 4
BLDG. 5
BLDG. 6
CORNER WALL BRACE
SCALE: 1" = 1'-0"
2
S1
EXIST. PARTIAL
HT. CONC. WALL
EXIST. GARAGE
FOUNDATION WALL
PLAN VIEW
L4x4x
1
4
x7'-0" w/
1
2
"ø
HILTI HY200 EPOXY
ANCHORS EA. FACE
2"
4"
2'-0" M
AX.
1
1
2
"
2"
SECTION VIEW
SHEET INDEX
S1 - GENERAL NOTES AND DETAILS
S2.1 - BUILDING 1 MAIN LEVEL AND FOUNDATION REPAIR PLANS
S2.1 - BUILDING 2 MAIN LEVEL AND FOUNDATION REPAIR PLANS
S2.1 - BUILDING 3 MAIN LEVEL AND FOUNDATION REPAIR PLANS
S2.1 - BUILDING 4 MAIN LEVEL AND FOUNDATION REPAIR PLANS
S2.1 - BUILDING 5 MAIN LEVEL AND FOUNDATION REPAIR PLANS
S2.1 - BUILDING 6 MAIN LEVEL AND FOUNDATION REPAIR PLANS
S3 - DETAILS
1
S1
ISOLATED PIER AND POST
SCALE:
1
2
" = 1'-0"
SECTION A-A
CHAMFER TOP OF
PIER TO DRAIN
CONCRETE PIER
#4 VERTICAL BAR
(4) TOTAL AS
SHOWN
VERTICAL BARS
#3 TIES AROUND VERTICAL
REINFORCEMENT. LOCATE
GROUP OF 3 TIES IN TOP 12"
AND SPACE TIES AT 12"O.C.
FULL HEIGHT OF PIER
LOCATE ON NATURAL, UNDISTURBED SOIL OR ON
APPROVED COMPACTED FILL PER GEOTECHNICAL
ENGINEER'S RECOMMENDATIONS
A A
SIMPSON ABUxxZ POST BASE w/
5
8
"ø ANCHOR(S) - EMBER 5" MIN.
DECAY-RESISTANT WOOD
POST/COL. PER PLAN
FLU
SH
or
6" M
AX.
30" M
IN
FRO
ST D
EPTH
36" M
IN
. AT 6x6 PO
STS
SEE PLAN
3"
2" CLR
TO TIES
GRADE OR FINISHED CONC.
DRIVEWAYS SOME LOC. - CORE
THRU CONC. WHERE OCCURS,
ELSE REPLACE SQUARE AS REQ'D.
PROVIDE FLUSH PIER TOP AT
MAIN WALKWAY AREAS SUCH AS
6x6 COL'S. BENEATH EDGE BM.
ADD
1
2
" EXP. JT. AROUND PIER
AT PAVEMENT AS OCCURS
WW
W.RIVETEN
G.CO
M | (720) 288-1580 | (719) 271-7419
PO
BO
X 1238, PARKER, CO
| PO
BO
X 64513, CO
LO
. SPG
S., CO
RIVET No.
DATE:ISSUE/REV:
SHEET No.
SHEET TITLE:
DESIGN by:
REVIEW by:
of
Panoram
a Estates
Deck and Stair Repair &
Reskin
502-544 Superior Street
Colorado Springs, CO
80904
BID SET 9/8/2017
JBP
JRW
170305X
10
BID SET ROOFS 1/10/2018
For Constr. 6/29/2018
-- --
-- --
6/29/2018
S2.1
BUILDING 1 FDN.
AND REPAIR PLAN
2
1. SEE GENERAL NOTES FOR TYPICAL CONNECTION AND FRAMING INFORMATION UNLESS NOTED OTHERWISE.
2. DO NOT SCALE THESE DRAWINGS.
3. ALL DIMENSIONS SHOWN ARE TO THE OUTSIDE FACE OF WOOD FRAMING or CENTERLINE AT COLUMNS.
4. ALL DIMENSIONS TO EXISTING MEMBERS ARE APPROXIMATE - CONTRACTOR TO VERIFY ALL DIMENSIONS AND
ELEVATIONS IN FIELD PRIOR TO FABRICATION OF NEW MATERIALS.
5. NOTIFY ENGINEER IF ADDITIONAL DAMAGE DISCOVERED DURING REPAIRS.
6. CONTRACTOR TO PROVIDE SHORING OF EXISTING MEMBERS AS REQUIRED TO REPAIR AND REPLACE MEMBERS
INDICATED. NOTIFY ENGINEER PRIOR TO DEMOLITION IF ADDITIONAL CLARIFICATION OR SHORING
RECOMMENDATIONS ARE REQUIRED.
A
S2.1
BLDG. 1 MAIN LEVEL REPAIR PLAN
SCALE:
1
4
" = 1'-0"
REMOVE DETERIORATED
DBL. LVL END (TYP.) -
CUT AT FACE OF WALL
(E) DBL. GIRDER TRUSS TO REMAIN (E) DBL. GIRDER TRUSS TO REMAIN (E) DBL. GIRDER TRUSS TO REMAIN(E) DBL. GIRDER TRUSS TO REMAIN
(E) DBL. LVL TO REMAIN -
REMOVE CANT. END - TYP.
(E) 2x10 TO REMAIN -
REMOVE CANT. END - TYP.
REMOVE DETERIORATED
2x END (TYP.) - CUT AT
FACE OF WALL
(E) CONC. WALL
BENEATH TO REMAIN
N
DO
WN
2x8
2x8
2x8
(2) 2x10
(2) 2x10
13'-9"
2x6 AT 18" O
.C.
2x8
3'-4"
LAN
DIN
G
4'-0"
8 RISERS AT 7
9
16
"
3'-3"
CANT.
7'-2"
6 RISERS AT 7
9
16
"
3'-0"
4 RISERS AT 7
9
16
"
4'-0"
(E) CONC. WALL
BENEATH TO REMAIN
(2) 2x10
LUS28-2
UNIT 502 UNIT 504 UNIT 506 UNIT 508
UP
GARAGE DOOR
UNIT 502
GARAGE
UNIT 504
GARGE
UNIT 506
GARAGE
UNIT 508
GARAGE
2
S1
STL. ANGLE
BRACKET FULL HT.
EXIST. CONC. PARTIAL
HT. WALL TO REMAIN
PROVIDE POLYURETHENE INJECTION
STABILIZATION/LIFT (MAX 1") BENEATH
EXISTING CONCRETE WALL THIS LOC.
(APPROX. 40 sf COVERAGE) WHERE
INDICATED THUS: .
1. DO NOT SCALE THESE DRAWINGS.
2. DIMENSIONS ARE APPROXIMATE AND SHOULD BE COORDINATED WITH THE STAIR DETAILS,
DIMENSIONS AND EXISTING CONDITIONS. ALL DIMENSIONS SHALL BE VERIFIED PRIOR TO PLACEMENT
AND/OR MANUFACTURING OF NEW MATERIALS.
3. ELEVATIONS OF CONCRETE FOUNDATION ELEMENTS ARE BASED ON EXISTING CONDITIONS. SEE
DETAILS AND OTHER NOTES FOR REQUIREMENTS.
4. ELEVATIONS OF FOUNDATION ELEMENTS RELATE TO 100'-0" AS A REFERENCE ELEVATION, AND DO NOT
REFER TO ACTUAL SITE ELEVATIONS.
5. BOTTOM OF FOOTING ELEVATION SHALL BE 30" MINIMUM BELOW TOP OF GRADE, 36" AT 6x6 POSTS.
6. FOOTINGS ARE CENTERED BENEATH FOUNDATION WALLS AND COLUMNS, UNLESS NOTED OTHERWISE.
7. PROVIDE UTILITY LOCATES PRIOR TO EXCAVATION OR DIGGING FOR FOUNDATIONS. PROVIDE POT
HOLES WHERE UTILITIES ARE WITHIN 18" OF PROPOSED FOUNDATION EDGE.
B
S2.1
BLDG. 1 FOUNDATION REPAIR PLAN
SCALE:
1
4
" = 1'-0"
N
7'-5
1
2
"
13'-10
3
4
" ±
EXIST. CONC.
STEPS TO REMAIN
STL. ANGLE
BRACKET FULL HT.
8.81'10.03'
INDICATES APPROX. HT. VARIANCE b/t
T.O. DECK AND T.O. (E) GROUND AT
B.O. STAIRS - VERIFY IN FIELD PRIOR
TO STAIR FABRICATION AND SPACE
ALL RISERS WITHIN EACH STAIRWAY
FLIGHT AT EQUAL HTS. ±
1
4
"
8.80'
CTR. OF
BLDG.
(E) W
ALL
TO
REM
AIN
3'-4
3
4
"
72'-0"
ALT#2 - REMOVE CONCRETE
LANDING AND REPLACE AT NEW
ELEV. TO MAKE LOWER STAIR RUNS
SYMMETRICAL WITH 5 RISERS
CONC.STEPS TO REMAIN - COORD.
STAIR LANDING
R&R APPROX. 45 sf OF
DAMAGED CONCRETE
DRIVEWAY
2
S1
O.H.
(2) 2x10
6'-5"
4'-7"
2'-9"
HSS 2x2x3/16 GUARDRAIL
POSTS - PROVIDE EQUAL
SPACING ACROSS SPANS,
MAXIMUM OF 48" O.C.
7
S3
LUS28- TYP.
EA. END
4
S3
3
S3
6
S3
6'-0"
PROVIDE GUARDRAIL SEPARATION
BETWEEN UNITS - TYP., INSTALL
BLOCKING AS REQ'D. IF NOT
ALIGNED WITH JOISTS
T.O. DECK = 100'- 0"
REFERENCE ELEVATION
REFERENCE ELEVATIONS VARY
AND DO NOT REFER TO ANY
ACTUAL SITE ELEVATIONS, TYP.
LUS28- TYP.
(
N
)
6
x
6
C
O
L
.
DO
WN
14 RISERS
(13) 11" TREAD
S =
11'-11"
3'-0"
5
S3
4x12 STRIN
GER
4x12 STRIN
GER
(2) 2x10
3
1
8
"x16
1
2
"24F-V8 GLULAM BM.
CANT.
(
N
)
6
x
6
C
O
L
.
DEM
O C
AN
T'D
EN
DS A
ND
NEW
2x8 A
T 1
6"
O.C
.
NEW LPC6Z POST
CAPS - TYP.
OPP.
HAND
DO
WN
2x6 AT 18" O
.C.
11"
11'-10"
3'-4"
3'-0" TYP.
4x12 - TYP. AT STAIR
STRINGERS/FRAME
4x12 STRIN
GER
10 RISERS AT 7
9
16
"
(9) 11" TREAD
S =
8'-3"
LAN
DIN
G
HSS 4x4 WOOD
POST (6 LOC.)
4'-0"
(2) 2x10
(2) 2x10
DO
WN
DO
WN
4x12 STRIN
GER
8
S3
2x8
2x8
2x8
CANT. CANT.
3
1
8
"x16
1
2
"24F-V8 GLULAM BM.3
1
8
"x16
1
2
"24F-V8 GLULAM BM.
(
N
)
6
x
6
C
O
L
.
6 RISERS AT 7
1
2
"
4'-7"
(2) 2x10
1
S1
TYP.
6 LOC.
(N) 12"ø CONC. PIER AT
EA. STAIR POST
6'-0
3
4
" 6'-0
3
4
"
SEE ADD#1 FOR BASE OF
STAIR FOOTING OPTION - TYP.
3'-5
1
2
"12'-3
1
4
"
5'-3"
24'-6"
NEW 14"ø CONC. PIER,
SEE 1/S1 - TYP. AT
NEW COL. LOC.
DEMO END OF
EXIST. STEP FOR
NEW PIER
DEM
O C
AN
T'D
EN
DS A
ND
NEW
2x8 A
T 1
6"
O.C
.
OPP.
HAND
3'-5
1
2
"
5'-9
1
4
"
LUS28-2
EA. END
1
S3
(
N
)
6
x
6
C
O
L
.
4x12 - TYP. AT STAIR
STRINGERS/FRAME
HSS 4x4 POST
(4 LOC.)
WW
W.RIVETEN
G.CO
M | (720) 288-1580 | (719) 271-7419
PO
BO
X 1238, PARKER, CO
| PO
BO
X 64513, CO
LO
. SPG
S., CO
RIVET No.
DATE:ISSUE/REV:
SHEET No.
SHEET TITLE:
DESIGN by:
REVIEW by:
of
Panoram
a Estates
Deck and Stair Repair &
Reskin
502-544 Superior Street
Colorado Springs, CO
80904
BID SET 9/8/2017
JBP
JRW
170305X
10
BID SET ROOFS 1/10/2018
For Constr. 6/29/2018
-- --
-- --
6/29/2018
3
BUILDING 2 FDN.
AND REPAIR PLAN
S2.2
1. SEE GENERAL NOTES FOR TYPICAL CONNECTION AND FRAMING INFORMATION UNLESS NOTED OTHERWISE.
2. DO NOT SCALE THESE DRAWINGS.
3. ALL DIMENSIONS SHOWN ARE TO THE OUTSIDE FACE OF WOOD FRAMING or CENTERLINE AT COLUMNS.
4. ALL DIMENSIONS TO EXISTING MEMBERS ARE APPROXIMATE - CONTRACTOR TO VERIFY ALL DIMENSIONS AND
ELEVATIONS IN FIELD PRIOR TO FABRICATION OF NEW MATERIALS.
5. NOTIFY ENGINEER IF ADDITIONAL DAMAGE DISCOVERED DURING REPAIRS.
6. CONTRACTOR TO PROVIDE SHORING OF EXISTING MEMBERS AS REQUIRED TO REPAIR AND REPLACE MEMBERS
INDICATED. NOTIFY ENGINEER PRIOR TO DEMOLITION IF ADDITIONAL CLARIFICATION OR SHORING
RECOMMENDATIONS ARE REQUIRED.
A
S2.2
BLDG. 2 MAIN LEVEL REPAIR PLAN
SCALE:
1
4
" = 1'-0"
(E) DBL. GIRDER TRUSS TO REMAIN (E) DBL. GIRDER TRUSS TO REMAIN (E) DBL. GIRDER TRUSS TO REMAIN(E) DBL. GIRDER TRUSS TO REMAIN
(E) DBL. LVL TO REMAIN -
REMOVE CANT. END - TYP.
(E) 2x10 TO REMAIN -
REMOVE CANT. END - TYP.
REMOVE DETERIORATED
2x END (TYP.) - CUT AT
FACE OF WALL
6'-0"
UNIT 510 UNIT 512 UNIT 514 UNIT 516
GARAGE DOOR GARAGE DOOR
1. DO NOT SCALE THESE DRAWINGS.
2. DIMENSIONS ARE APPROXIMATE AND SHOULD BE COORDINATED WITH THE STAIR DETAILS,
DIMENSIONS AND EXISTING CONDITIONS. ALL DIMENSIONS SHALL BE VERIFIED PRIOR TO PLACEMENT
AND/OR MANUFACTURING OF NEW MATERIALS.
3. ELEVATIONS OF CONCRETE FOUNDATION ELEMENTS ARE BASED ON EXISTING CONDITIONS. SEE
DETAILS AND OTHER NOTES FOR REQUIREMENTS.
4. ELEVATIONS OF FOUNDATION ELEMENTS RELATE TO 100'-0" AS A REFERENCE ELEVATION, AND DO NOT
REFER TO ACTUAL SITE ELEVATIONS.
5. BOTTOM OF FOOTING ELEVATION SHALL BE 30" MINIMUM BELOW TOP OF GRADE, 36" AT 6x6 POSTS.
6. FOOTINGS ARE CENTERED BENEATH FOUNDATION WALLS AND COLUMNS, UNLESS NOTED OTHERWISE.
7. PROVIDE UTILITY LOCATES PRIOR TO EXCAVATION OR DIGGING FOR FOUNDATIONS. PROVIDE POT
HOLES WHERE UTILITIES ARE WITHIN 18" OF PROPOSED FOUNDATION EDGE.
GARAGE DOOR GARAGE DOOR
UNIT 512
GARGE
UNIT 510
GARAGE
UNIT 514
GARAGE
EXIST. CONC. PARTIAL
HT. WALL TO REMAIN
UNIT 516
GARAGE
B BLDG. 2 FOUNDATION REPAIR PLAN
S2.2
SCALE:
1
4
" = 1'-0"
EXIST. CONC. PARTIAL
HT. WALL TO REMAIN
N
N
REFERENCE ELEVATIONS VARY
AND DO NOT REFER TO ANY
ACTUAL SITE ELEVATIONS, TYP.
CTR. OF
BLDG.
72'-0"
EXIST. UTIL. BOX TO
REMAIN - NOTIFY ENGINEER
IF OBSTRUCTS NEW STAIR
PLACEMENT AS SHOWN
LUS28 - TYP.
EA. END
PROVIDE GUARDRAIL SEPARATION
BETWEEN UNITS - TYP., INSTALL
BLOCKING AS REQ'D. IF NOT
ALIGNED WITH JOISTS
REMOVE DETERIORATED
DBL. LVL END (TYP.) -
CUT AT FACE OF WALL
T.O. DECK = 100'- 0"
REFERENCE ELEVATION
REFERENCE ELEVATIONS VARY
AND DO NOT REFER TO ANY
ACTUAL SITE ELEVATIONS, TYP.
HSS 2x2x3/16 GUARDRAIL
POSTS - PROVIDE EQUAL
SPACING ACROSS SPANS,
MAXIMUM OF 48" O.C.
REMOVE DETERIORATED
2x END (TYP.) - CUT AT
FACE OF WALL
LUS28- TYP.
(
N
)
6
x
6
C
O
L
.
DO
WN
14 RISERS
(13) 11" TREAD
S =
11'-11"
3'-0"
5
S3
4x12 STRIN
GER
4x12 STRIN
GER
(2) 2x10
3
1
8
"x16
1
2
"24F-V8 GLULAM BM.
CANT.
(
N
)
6
x
6
C
O
L
.
DO
WN
14 RISERS
(13) 11" TREAD
S =
11'-11"
3'-0"
5
S3
4x12 STRIN
GER
4x12 STRIN
GER
(2) 2x10
1
S3
T.O. DECK = 100'- 0"
DO
WN
15 RISERS AT 7
5
8
"
(14) 11" TREAD
S =
12'-10"
4'-0"
(2) 2x10
HSS 2x2x3/16 GUARDRAIL
POSTS - PROVIDE EQUAL
SPACING ACROSS SPANS,
MAXIMUM OF 48" O.C.
4'-0"
LUS28-2
EA. END
REMOVE DETERIORATED
2x END (TYP.) - CUT AT
FACE OF WALL
5
S3
REFERENCE ELEVATION
4x12 STRIN
GER
4x12 STRIN
GER
(2) 2x10
(2) 2x10
(
N
)
6
x
6
C
O
L
.
(
N
)
6
x
6
C
O
L
.
DEM
O C
AN
T'D
EN
DS A
ND
NEW
2x8 A
T 1
6"
O.C
.
3
1
8
"x16
1
2
"24F-V8 GLULAM BM.
CANT.
CANT.
8
S3
NEW LPC6Z POST
CAPS - TYP.
CANT.
3'-0"3'-0"
4'-0"
5'-3" 25'-0"
5'-9
1
4
"
NEW 16"ø CONC. PIER,
SEE 1/S1 - TYP. AT
NEW COL. LOC.
DEM
O C
AN
T'D
EN
DS A
ND
NEW
2x8 A
T 1
6"
O.C
.
17'-11"
WW
W.RIVETEN
G.CO
M | (720) 288-1580 | (719) 271-7419
PO
BO
X 1238, PARKER, CO
| PO
BO
X 64513, CO
LO
. SPG
S., CO
RIVET No.
DATE:ISSUE/REV:
SHEET No.
SHEET TITLE:
DESIGN by:
REVIEW by:
of
Panoram
a Estates
Deck and Stair Repair &
Reskin
502-544 Superior Street
Colorado Springs, CO
80904
BID SET 9/8/2017
JBP
JRW
170305X
10
BID SET ROOFS 1/10/2018
For Constr. 6/29/2018
-- --
-- --
6/29/2018
4
BUILDING 3 FDN.
AND REPAIR PLAN
S2.3
1. SEE GENERAL NOTES FOR TYPICAL CONNECTION AND FRAMING INFORMATION UNLESS NOTED OTHERWISE.
2. DO NOT SCALE THESE DRAWINGS.
3. ALL DIMENSIONS SHOWN ARE TO THE OUTSIDE FACE OF WOOD FRAMING or CENTERLINE AT COLUMNS.
4. ALL DIMENSIONS TO EXISTING MEMBERS ARE APPROXIMATE - CONTRACTOR TO VERIFY ALL DIMENSIONS AND
ELEVATIONS IN FIELD PRIOR TO FABRICATION OF NEW MATERIALS.
5. NOTIFY ENGINEER IF ADDITIONAL DAMAGE DISCOVERED DURING REPAIRS.
6. CONTRACTOR TO PROVIDE SHORING OF EXISTING MEMBERS AS REQUIRED TO REPAIR AND REPLACE MEMBERS
INDICATED. NOTIFY ENGINEER PRIOR TO DEMOLITION IF ADDITIONAL CLARIFICATION OR SHORING
RECOMMENDATIONS ARE REQUIRED.
A
S2.3
BLDG. 3 MAIN LEVEL REPAIR PLAN
SCALE:
1
4
" = 1'-0"
(E) DBL. GIRDER TRUSS TO REMAIN (E) DBL. GIRDER TRUSS TO REMAIN (E) DBL. GIRDER TRUSS TO REMAIN(E) DBL. GIRDER TRUSS TO REMAIN
(E) DBL. LVL TO REMAIN -
REMOVE CANT. END - TYP.
1
S3
(E) 2x10 TO REMAIN -
REMOVE CANT. END - TYP.
REMOVE DETERIORATED
2x END (TYP.) - CUT AT
FACE OF WALL
N
T.O. DECK = 100'- 0"
DO
WN
2x6 AT 18" O
.C.
11"
11'-10"
5 RISERS AT 7
7
8
"
3'-4"
3'-0" TYP.
4x12 - TYP. AT STAIR
STRINGERS/FRAME
4x12 STRIN
GER
10 RISERS AT 7
9
16
"
(9) 11" TREAD
S =
8'-3"
4'-0"
5 RISERS AT 7
9
16
"
LAN
DIN
G
6'-0"
(E) CONC. WALL
BENEATH TO REMAIN
DO
WN
2x8
2x8
2x8
(2) 2x10
(2) 2x10
13'-9"
2x6 A
T
18" O
.C
.
2x8
3'-4"
LAN
DIN
G
4'-0"
8 RISERS AT 7
3
8
"
3'-3"
CANT.
7'-2"
6 RISERS AT 7
3
8
"
3'-0"
15'-7"
(2) 2x10
UNIT 518 UNIT 520 UNIT 522 UNIT 524
HSS 4x4 WOOD
POST (6 LOC.)
4x4 WOOD POST
(4 LOC.)
UP
1
S1
REUSE EXIST. CONC.
PIER THIS LOC. IF
ALIGNS, ELSE R&R
TYP.
6 LOC.
GARAGE DOOR
UNIT 518
GARAGE
UNIT 520
GARGE
UNIT 522
GARAGE
UNIT 524
GARAGE
EXIST. CONC. PARTIAL
HT. WALL TO REMAIN
1. DO NOT SCALE THESE DRAWINGS.
2. DIMENSIONS ARE APPROXIMATE AND SHOULD BE COORDINATED WITH THE STAIR DETAILS AND
DIMENSIONS AND EXISTING CONDITIONS. ALL DIMENSIONS SHALL BE VERIFIED PRIOR TO PLACEMENT
AND/OR MANUFACTURING OF NEW MATERIALS.
3. ELEVATIONS OF CONCRETE FOUNDATION ELEMENTS ARE BASED ON EXISTING CONDITIONS. SEE
DETAILS AND OTHER NOTES FOR REQUIREMENTS.
4. ELEVATIONS OF FOUNDATION ELEMENTS RELATE TO 100'-0" AS A REFERENCE ELEVATION, AND DO NOT
REFER TO ACTUAL SITE ELEVATIONS.
5. BOTTOM OF FOOTING ELEVATION SHALL BE 30" MINIMUM BELOW TOP OF GRADE, 36" AT 6x6 POSTS.
6. FOOTINGS ARE CENTERED BENEATH FOUNDATION WALLS AND COLUMNS, UNLESS NOTED OTHERWISE.
7. PROVIDE UTILITY LOCATES PRIOR TO EXCAVATION OR DIGGING FOR FOUNDATIONS. PROVIDE POT
HOLES WHERE UTILITIES ARE WITHIN 18" OF PROPOSED FOUNDATION EDGE.
B
S2.3
BLDG. 3 FOUNDATION REPAIR PLAN
SCALE:
1
4
" = 1'-0"
(N) 12"ø CONC. PIER AT
EA. STAIR POST - REUSE
EXIST. WHERE NOTED
UP
6'-0
3
4
" 6'-0
3
4
"
GUARDRAIL RETURN - TYP.
EA. RECESSED STAIR LOC.
13'-10" ±
EXIST. CONC. STEP TO REMAIN -
REMOVE WOOD DECKING
(CONTRACTOR'S OPTION TO REMOVE
AND PROVIDE DRIVE SLAB AND ADD
(1) RISER TO LOWER STAIRS)
4'-0"
9.60'9.46'
8.60'
UP
6'-6" ±
R&R DAMAGED CONCRETE
DRIVE (APPROX. 80 sf)-
COMPACT SUBGRADE TO 95%
PROVIDE ISOLATION JOINT
AROUND NEW PIER
EXIST. CONC. PARTIAL
HT. WALL TO REMAIN
N
15'-6" ±
3'-4
3
4
"
3'-0" 2'-7" 2'-7" 3'-0"
SEE ADD#1 FOR BASE OF
STAIR FOOTING OPTION - TYP.
72'-0"
LUS28
EA. END
4
S3
2'-8"
3
S3
5
S3
REFERENCE ELEVATION
REFERENCE ELEVATIONS VARY
AND DO NOT REFER TO ANY
ACTUAL SITE ELEVATIONS, TYP.
INDICATES APPROX. HT. VARIANCE b/t
T.O. DECK AND T.O. (E) GROUND AT
B.O. STAIRS - VERIFY IN FIELD PRIOR
TO STAIR FABRICATION AND SPACE
ALL RISERS WITHIN EACH STAIRWAY
FLIGHT AT EQUAL HTS. ±
1
4
"
4'-7"
6'-5"
HSS 2x2x3/16 GUARDRAIL
POSTS - PROVIDE EQUAL
SPACING ACROSS SPANS,
MAXIMUM OF 48" O.C.
6
S3
LUS28- TYP.
EA. END
3'-8"
3'-8"
DEM
O C
AN
T'D
EN
DS A
ND
NEW
2x8 A
T 1
6"
O.C
.
DEM
O C
AN
T'D
EN
DS A
ND
NEW
2x8 A
T 1
6"
O.C
.
(2) 2x10
(2) 2x10
DO
WN
DO
WN
4x12 STRIN
GER
8
S3
(
N
)
6
x
6
C
O
L
.
(
N
)
6
x
6
C
O
L
.
DO
WN
15 RISERS
(14) 11" TREAD
S =
12'-10"
3'-0"
5
S3
4x12 STRIN
GER
4x12 STRIN
GER
(
N
)
6
x
6
C
O
L
.
(
N
)
6
x
6
C
O
L
.
CANT.
(2) 2x10
(2) 2x10
4x12 - TYP. AT STAIR
STRINGERS/FRAME
(2) 2x10
2x8
2x8
2x8
CANT. CANT.
CANT.
PROVIDE GUARDRAIL SEPARATION
BETWEEN UNITS - TYP., INSTALL
BLOCKING AS REQ'D. IF NOT
ALIGNED WITH JOISTS (2 LOC.)
3'-0"
7'-5
1
2
"
3'-5
1
2
"
3'-5
1
2
"12'-3
1
4
"
1
S1
TYP.
4 LOC.
5'-3"24'-6"
NEW 14"ø CONC. PIER,
SEE 1/S1 - TYP. AT
NEW COL. LOC.
3
1
8
"x16
1
2
"24F-V8 GLULAM BM.3
1
8
"x16
1
2
"24F-V8 GLULAM BM.
NEW LPC6Z POST
CAPS - TYP.
WW
W.RIVETEN
G.CO
M | (720) 288-1580 | (719) 271-7419
PO
BO
X 1238, PARKER, CO
| PO
BO
X 64513, CO
LO
. SPG
S., CO
RIVET No.
DATE:ISSUE/REV:
SHEET No.
SHEET TITLE:
DESIGN by:
REVIEW by:
of
Panoram
a Estates
Deck and Stair Repair &
Reskin
502-544 Superior Street
Colorado Springs, CO
80904
BID SET 9/8/2017
JBP
JRW
170305X
10
BID SET ROOFS 1/10/2018
For Constr. 6/29/2018
-- --
-- --
6/29/2018
4
BUILDING 3 FDN.
AND REPAIR PLAN
S2.4
1. SEE GENERAL NOTES FOR TYPICAL CONNECTION AND FRAMING INFORMATION UNLESS NOTED OTHERWISE.
2. DO NOT SCALE THESE DRAWINGS.
3. ALL DIMENSIONS SHOWN ARE TO THE OUTSIDE FACE OF WOOD FRAMING or CENTERLINE AT COLUMNS.
4. ALL DIMENSIONS TO EXISTING MEMBERS ARE APPROXIMATE - CONTRACTOR TO VERIFY ALL DIMENSIONS AND
ELEVATIONS IN FIELD PRIOR TO FABRICATION OF NEW MATERIALS.
5. NOTIFY ENGINEER IF ADDITIONAL DAMAGE DISCOVERED DURING REPAIRS.
6. CONTRACTOR TO PROVIDE SHORING OF EXISTING MEMBERS AS REQUIRED TO REPAIR AND REPLACE MEMBERS
INDICATED. NOTIFY ENGINEER PRIOR TO DEMOLITION IF ADDITIONAL CLARIFICATION OR SHORING
RECOMMENDATIONS ARE REQUIRED.
A
S2.4
BLDG. 4 MAIN LEVEL REPAIR PLAN
SCALE:
1
4
" = 1'-0"
REMOVE DETERIORATED
DBL. LVL END (TYP.) -
CUT AT FACE OF WALL
(E) DBL. GIRDER TRUSS TO REMAIN (E) DBL. GIRDER TRUSS TO REMAIN (E) DBL. GIRDER TRUSS TO REMAIN(E) DBL. GIRDER TRUSS TO REMAIN
(E) DBL. LVL TO REMAIN -
REMOVE CANT. END - TYP.
1
S3
(E) 2x10 TO REMAIN -
REMOVE CANT. END - TYP.
T.O. DECK = 100'- 0"
17 RISERS AT 7
9
16
"
(16) 11" TREAD
S =
14'-8"
6'-0"
UNIT 526 UNIT 528 UNIT 530 UNIT 532
1
S1
TYP.
4 LOC.
GARAGE DOOR
UNIT 526
GARAGE
UNIT 528
GARGE
UNIT 530
GARAGE
UNIT 532
GARAGE
EXIST. CONC. PARTIAL
HT. WALL TO REMAIN
1. DO NOT SCALE THESE DRAWINGS.
2. DIMENSIONS ARE APPROXIMATE AND SHOULD BE COORDINATED WITH THE STAIR DETAILS,
DIMENSIONS AND EXISTING CONDITIONS. ALL DIMENSIONS SHALL BE VERIFIED PRIOR TO PLACEMENT
AND/OR MANUFACTURING OF NEW MATERIALS.
3. ELEVATIONS OF CONCRETE FOUNDATION ELEMENTS ARE BASED ON EXISTING CONDITIONS. SEE
DETAILS AND OTHER NOTES FOR REQUIREMENTS.
4. ELEVATIONS OF FOUNDATION ELEMENTS RELATE TO 100'-0" AS A REFERENCE ELEVATION, AND DO NOT
REFER TO ACTUAL SITE ELEVATIONS.
5. BOTTOM OF FOOTING ELEVATION SHALL BE 30" MINIMUM BELOW TOP OF GRADE, 36" AT 6x6 POSTS.
6. FOOTINGS ARE CENTERED BENEATH FOUNDATION WALLS AND COLUMNS, UNLESS NOTED OTHERWISE.
7. PROVIDE UTILITY LOCATES PRIOR TO EXCAVATION OR DIGGING FOR FOUNDATIONS. PROVIDE POT
HOLES WHERE UTILITIES ARE WITHIN 18" OF PROPOSED FOUNDATION EDGE.
B
S2.4
BLDG. 4 FOUNDATION REPAIR PLAN
SCALE:
1
4
" = 1'-0"
EXIST. CONC. STEP TO REMAIN -
REMOVE WOOD DECKING
(CONTRACTOR'S OPTION TO REMOVE
AND EXTEND LENGTH TO REMOVE (1)
RISER AT LOWER STAIRS)
10.73'
R&R DAMAGED CONCRETE DRIVE
(APPROX. 280 sf)- COMPACT
SUBGRADE TO 95% - OPTION TO
REPLACE ADJACENT SLAB ALSO
PROVIDE ISOLATION JOINT
AROUND NEW PIER
EXIST. CONC. PARTIAL
HT. WALL TO REMAIN
N
SEE ADD#1 FOR BASE OF
STAIR FOOTING OPTION - TYP.
72'-0"
20'-8" ±
UP
5'-1" ±
SEE MAIN LEVEL REPAIR PLAN
FOR NEW WOOD POSTS
ABOVE - PAINT TO MATCH
NEW COLOR SCHEME
CTR. OF
BLDG.
REPLACE CONCRETE LANDING TO BE LEVEL
WITHIN 1" w/ GRADUAL SLOPE TO EXISTING
DRIVE ELEVATIONS (APPROX. 40sf)
3"
3'-2"
16'-9
7
8
" ±
7'-2
1
2
"
2'-9
3
4
"
8"
N
8
S3
REFERENCE ELEVATION
REFERENCE ELEVATIONS VARY
AND DO NOT REFER TO ANY
ACTUAL SITE ELEVATIONS, TYP.
INDICATES APPROX. HT. VARIANCE b/t
T.O. DECK AND T.O. (E) GROUND AT
B.O. STAIRS - VERIFY IN FIELD PRIOR
TO STAIR FABRICATION AND SPACE
ALL RISERS WITHIN EACH STAIRWAY
FLIGHT AT EQUAL HTS. ±
1
4
"
10'-0" ±
HSS 2x2x3/16 GUARDRAIL
POSTS - PROVIDE EQUAL
SPACING ACROSS SPANS,
MAXIMUM OF 48" O.C.
LUS210-2
- TYP.
PROVIDE GUARDRAIL SEPARATION
BETWEEN UNITS - TYP., INSTALL
BLOCKING AS REQ'D. IF NOT
ALIGNED WITH JOISTS
DO
WN
5
S3
4x12 STRIN
GER
4x12 STRIN
GER
(E) 2x10 TO REMAIN -
REMOVE CANT. END - TYP.
(SEE DEDUCT #2)
6'-0"
2x8
2x8
2x8
(2) 2x10
6'-0"
2'-8"
CANT.
(2) 2x10
4
x
4
P
O
S
T
5'-0"
(2)
2x10
REMOVE DETERIORATED
2x END (TYP.) - CUT AT
FACE OF WALL
DO
WN
2x6 AT 16" O
.C.
15'-9"
3'-4"
LAN
DIN
G
8 RISERS AT 7
1
16
"
9 RISERS AT 7
1
16
"
6'-11"
3'-0"
9.99'
11"
4
S3
2'-8"
3
S3
6
S3
6'-5"
7'-4"
LUS28- TYP.
4x4 WOOD POST
(4 LOC.)
4x12 FRAME - TYP. (SEE
DETAILS FOR OTHER MEMBERS)
(
N
)
6
x
6
C
O
L
.
DO
WN
15 RISERS
(14) 11" TREAD
S =
12'-10"
3'-0"
5
S3
4x12 STRIN
GER
4x12 STRIN
GER
(2) 2x10
LUS28- TYP.
DEMO C
ANT'D E
NDS AND N
EW 2
x8 AT 1
6" O.C
.
(
N
)
6
x
6
C
O
L
.
CANT.
CANT.
(
N
)
6
x
6
C
O
L
.
3
1
2
"x16
1
2
"24F-V8 GLULAM BM.
(
N
)
6
x
6
C
O
L
.
4
x
4
P
O
S
T
(2) 2x10
SPLICE GLULAM AT
THIS COL ONLY
SPLICE GLULAM AT
THIS COL ONLY
3'-0"
UP
4'-0"
5'-3"25'-0"
5'-9
1
4
"
NEW 16"ø CONC. PIER,
SEE 1/S1 - TYP. AT
NEW COL. LOC.
OPP.
HAND
4'-0"
3
1
8
"x16
1
2
"24F-V8 GLULAM BM.3
1
8
"x16
1
2
"24F-V8 GLULAM BM.
NEW LPC6Z POST
CAPS - TYP.
WW
W.RIVETEN
G.CO
M | (720) 288-1580 | (719) 271-7419
PO
BO
X 1238, PARKER, CO
| PO
BO
X 64513, CO
LO
. SPG
S., CO
RIVET No.
DATE:ISSUE/REV:
SHEET No.
SHEET TITLE:
DESIGN by:
REVIEW by:
of
Panoram
a Estates
Deck and Stair Repair &
Reskin
502-544 Superior Street
Colorado Springs, CO
80904
BID SET 9/8/2017
JBP
JRW
170305X
10
BID SET ROOFS 1/10/2018
For Constr. 6/29/2018
-- --
-- --
6/29/2018
4
BUILDING 5 FDN.
AND REPAIR PLAN
S2.5
1. SEE GENERAL NOTES FOR TYPICAL CONNECTION AND FRAMING INFORMATION UNLESS NOTED OTHERWISE.
2. DO NOT SCALE THESE DRAWINGS.
3. ALL DIMENSIONS SHOWN ARE TO THE OUTSIDE FACE OF WOOD FRAMING or CENTERLINE AT COLUMNS.
4. ALL DIMENSIONS TO EXISTING MEMBERS ARE APPROXIMATE - CONTRACTOR TO VERIFY ALL DIMENSIONS AND
ELEVATIONS IN FIELD PRIOR TO FABRICATION OF NEW MATERIALS.
5. NOTIFY ENGINEER IF ADDITIONAL DAMAGE DISCOVERED DURING REPAIRS.
6. CONTRACTOR TO PROVIDE SHORING OF EXISTING MEMBERS AS REQUIRED TO REPAIR AND REPLACE MEMBERS
INDICATED. NOTIFY ENGINEER PRIOR TO DEMOLITION IF ADDITIONAL CLARIFICATION OR SHORING
RECOMMENDATIONS ARE REQUIRED.
A
S2.5
BLDG. 5 MAIN LEVEL REPAIR PLAN
SCALE:
1
4
" = 1'-0"
(E) DBL. GIRDER TRUSS TO REMAIN (E) DBL. GIRDER TRUSS TO REMAIN
(E) DBL. LVL TO
REMAIN - TYP.
1
S3
(E) 2x10 TO REMAIN - TYP.
2
S3
T.O. DECK = 100'- 0"
TYP.
15 RISERS AT 7
3
8
"
(14) 11" TREAD
S =
12'-10"
6'-0"
UNIT 534 UNIT 536
GARAGE DOOR
UNIT 534
GARGE
UNIT 536
GARAGE
1. DO NOT SCALE THESE DRAWINGS.
2. DIMENSIONS ARE APPROXIMATE AND SHOULD BE COORDINATED WITH THE STAIR DETAILS,
DIMENSIONS AND EXISTING CONDITIONS. ALL DIMENSIONS SHALL BE VERIFIED PRIOR TO PLACEMENT
AND/OR MANUFACTURING OF NEW MATERIALS.
3. ELEVATIONS OF CONCRETE FOUNDATION ELEMENTS ARE BASED ON EXISTING CONDITIONS. SEE
DETAILS AND OTHER NOTES FOR REQUIREMENTS.
4. ELEVATIONS OF FOUNDATION ELEMENTS RELATE TO 100'-0" AS A REFERENCE ELEVATION, AND DO NOT
REFER TO ACTUAL SITE ELEVATIONS.
5. BOTTOM OF FOOTING ELEVATION SHALL BE 30" MINIMUM BELOW TOP OF GRADE, 36" AT 6x6 POSTS.
6. FOOTINGS ARE CENTERED BENEATH FOUNDATION WALLS AND COLUMNS, UNLESS NOTED OTHERWISE.
7. PROVIDE UTILITY LOCATES PRIOR TO EXCAVATION OR DIGGING FOR FOUNDATIONS. PROVIDE POT
HOLES WHERE UTILITIES ARE WITHIN 18" OF PROPOSED FOUNDATION EDGE.
B
S2.5
BLDG. 5 FOUNDATION REPAIR PLAN
SCALE:
1
4
" = 1'-0"
HSS2"x2" GUARDRAIL
POSTS - PROVIDE EQUAL
SPACING ACROSS SPANS,
MAXIMUM OF 48" O.C.
(E)
JOIS
TS T
O R
EM
AIN
9.20'
37'-0"
18'-10" ±
4'-0"
CTR. OF
BLDG.
EXIST. 2x LEDGER
TO REMAIN
NN
(E)
2x D
ECK J
OIS
TS T
O R
EM
AIN
(N) LUS28
- TYP.
REPLACE ONLY STAIRS,
GUARDRAILS, AND FRONT
EDGE BM. AT BUILDING 5
(
N
)
6
x
6
C
O
L
.
SEE ADD#1 FOR BASE OF
STAIR FOOTING OPTION - TYP.
6'-0" ±
SIM.
8
S3
REFERENCE ELEVATION
REFERENCE ELEVATIONS VARY
AND DO NOT REFER TO ANY
ACTUAL SITE ELEVATIONS, TYP.
INDICATES APPROX. HT. VARIANCE b/t
T.O. DECK AND T.O. (E) GROUND AT
B.O. STAIR - VERIFY IN FIELD PRIOR
TO STAIR FABRICATION AND SPACE
ALL RISERS WITHIN STAIRWAY
FLIGHT AT EQUAL HTS. ±
1
4
"
SIM.
(N) 3
1
8
"x16
1
2
"24F-V8 GLULAM BM.
NEW ACE6 POST
CAPS - TYP.
DO
WN
5
S3
4x12 STRIN
GER
4x12 STRIN
GER
(N) 3
1
8
"x16
1
2
"24F-V8 GLULAM BM.
(
N
)
6
x
6
C
O
L
.
(
N
)
6
x
6
C
O
L
.
(
N
)
6
x
6
C
O
L
.
NEW 14"ø CONC. PIER -
TYP. AT NEW COL. LOC.
- ALIGN WITH EXIST.
COL'S. TO BE REMOVED
5'-9
1
4
"
WW
W.RIVETEN
G.CO
M | (720) 288-1580 | (719) 271-7419
PO
BO
X 1238, PARKER, CO
| PO
BO
X 64513, CO
LO
. SPG
S., CO
RIVET No.
DATE:ISSUE/REV:
SHEET No.
SHEET TITLE:
DESIGN by:
REVIEW by:
of
Panoram
a Estates
Deck and Stair Repair &
Reskin
502-544 Superior Street
Colorado Springs, CO
80904
BID SET 9/8/2017
JBP
JRW
170305X
10
BID SET ROOFS 1/10/2018
For Constr. 6/29/2018
-- --
-- --
6/29/2018
7
BUILDING 6 FDN.
AND REPAIR PLAN
S2.6
1. SEE GENERAL NOTES FOR TYPICAL CONNECTION AND FRAMING INFORMATION UNLESS NOTED OTHERWISE.
2. DO NOT SCALE THESE DRAWINGS.
3. ALL DIMENSIONS SHOWN ARE TO THE OUTSIDE FACE OF WOOD FRAMING or CENTERLINE AT COLUMNS.
4. ALL DIMENSIONS TO EXISTING MEMBERS ARE APPROXIMATE - CONTRACTOR TO VERIFY ALL DIMENSIONS AND
ELEVATIONS IN FIELD PRIOR TO FABRICATION OF NEW MATERIALS.
5. NOTIFY ENGINEER IF ADDITIONAL DAMAGE DISCOVERED DURING REPAIRS.
6. CONTRACTOR TO PROVIDE SHORING OF EXISTING MEMBERS AS REQUIRED TO REPAIR AND REPLACE MEMBERS
INDICATED. NOTIFY ENGINEER PRIOR TO DEMOLITION IF ADDITIONAL CLARIFICATION OR SHORING
RECOMMENDATIONS ARE REQUIRED.
A
S2.6
BLDG. 6 MAIN LEVEL REPAIR PLAN
SCALE:
1
4
" = 1'-0"
REMOVE DETERIORATED
DBL. LVL END (TYP.) -
CUT AT FACE OF WALL
(E) DBL. GIRDER TRUSS TO REMAIN (E) DBL. GIRDER TRUSS TO REMAIN (E) DBL. GIRDER TRUSS TO REMAIN(E) DBL. GIRDER TRUSS TO REMAIN
(E) DBL. LVL TO REMAIN -
REMOVE CANT. END - TYP.
(SEE DEDUCT #2)
1
S3
(E) 2x10 TO REMAIN -
REMOVE CANT. END - TYP.
(SEE DEDUCT #2)
T.O. DECK = 100'- 0"
DO
WN
15 RISERS AT 7
5
8
"
(14) 11" TREAD
S =
12'-10"
4'-0"
6'-0"
(2) 2x10
UNIT 538 UNIT 540 UNIT 542UNIT 544
LUS28-2
1
S1
TYP.
4 LOC.
GARAGE DOOR
UNIT 538
GARAGE
UNIT 540
GARGE
UNIT 542
GARAGE
UNIT 544
GARAGE
EXIST. CONC. PARTIAL
HT. WALL TO REMAIN
1. DO NOT SCALE THESE DRAWINGS.
2. DIMENSIONS ARE APPROXIMATE AND SHOULD BE COORDINATED WITH THE STAIR DETAILS,
DIMENSIONS AND EXISTING CONDITIONS. ALL DIMENSIONS SHALL BE VERIFIED PRIOR TO PLACEMENT
AND/OR MANUFACTURING OF NEW MATERIALS.
3. ELEVATIONS OF CONCRETE FOUNDATION ELEMENTS ARE BASED ON EXISTING CONDITIONS. SEE
DETAILS AND OTHER NOTES FOR REQUIREMENTS.
4. ELEVATIONS OF FOUNDATION ELEMENTS RELATE TO 100'-0" AS A REFERENCE ELEVATION, AND DO NOT
REFER TO ACTUAL SITE ELEVATIONS.
5. BOTTOM OF FOOTING ELEVATION SHALL BE 30" MINIMUM BELOW TOP OF GRADE, 36" AT 6x6 POSTS.
6. FOOTINGS ARE CENTERED BENEATH FOUNDATION WALLS AND COLUMNS, UNLESS NOTED OTHERWISE.
7. PROVIDE UTILITY LOCATES PRIOR TO EXCAVATION OR DIGGING FOR FOUNDATIONS. PROVIDE POT
HOLES WHERE UTILITIES ARE WITHIN 18" OF PROPOSED FOUNDATION EDGE.
B
S2.6
BLDG. 6 FOUNDATION REPAIR PLAN
SCALE:
1
4
" = 1'-0"
(N) 12"ø CONC. PIER
AT EA. STAIR POST
HSS 2x2x3/16 GUARDRAIL
POSTS - PROVIDE EQUAL
SPACING ACROSS SPANS,
MAXIMUM OF 48" O.C.
9.54'
PROVIDE ISOLATION JOINT
AROUND NEW PIER
EXIST. CONC. PARTIAL
HT. WALL TO REMAIN
SEE ADD#1 FOR BASE OF
STAIR FOOTING OPTION - TYP.
72'-0"
4'-0"
LUS28-2
EA. END
2x8
2x8
2x8
(2) 2x10
6'-0"
2'-8"
CANT.
(2) 2x10
4
x
4
P
O
S
T
4
x
4
P
O
S
T
5'-0"
(2) 2x10
16'-10" ±
SEE MAIN LEVEL REPAIR
PLAN FOR NEW WOOD
POSTS ABOVE - PAINT TO
MATCH NEW COLOR SCHEME
CTR. OF
BLDG.
3'-0"
3"
14'-10
7
8
" ±
2'-9
3
4
"
8"
7'-2
1
2
"
N
N
REMOVE DETERIORATED
2x END (TYP.) - CUT AT
FACE OF WALL
EXIST. BOX TO REMAIN -
NOTIFY ENGINEER IF
OBSTRUCTS NEW STAIR
PLACEMENT AS SHOWN
DO
WN
2x6 AT 16" O
.C.
14'-10"
3'-4"
LAN
DIN
G
7 RISERS AT 7
1
2
"
8 RISERS AT 7
1
2
"
6'-11"
3'-0"
9.35'
11"
UP
5'-1" ±
WALKWAY FRAMING AT BUILDING 6 IS IN
BETTER CONDITION THAN REMAINDER -
DEDUCT #2 SHALL BE TO LEAVE EXISTING
FRAMING AND REPLACE ONLY THE STAIRS,
GUARDRAILS, AND FRONT DBL. 2x12 EDGE BEAM.
4
S3
2'-8"
3
S3
5
S3
6
S3
REFERENCE ELEVATION
REFERENCE ELEVATIONS VARY
AND DO NOT REFER TO ANY
ACTUAL SITE ELEVATIONS, TYP.
INDICATES APPROX. HT. VARIANCE b/t
T.O. DECK AND T.O. (E) GROUND AT
B.O. STAIRS - VERIFY IN FIELD PRIOR
TO STAIR FABRICATION AND SPACE
ALL RISERS WITHIN EACH STAIRWAY
FLIGHT AT EQUAL HTS. ±
1
4
"
5'-6"
6'-5"
10'-0" ±
4x12 STRIN
GER
LUS28- TYP.
4x4 POST (4 LOC.)
4x12 FRAME - TYP. (SEE
DETAILS FOR OTHER MEMBERS)
4x12 STRIN
GER
(2) 2x10
(2) 2x10
(
N
)
6
x
6
C
O
L
.
(
N
)
6
x
6
C
O
L
.
DO
WN
15 RISERS
(14) 11" TREAD
S =
12'-10"
3'-0"
5
S3
4x12 STRIN
GER
4x12 STRIN
GER
(2) 2x10
DEM
O C
AN
T'D
EN
DS A
ND
NEW
2x8 A
T 1
6"
O.C
.
LUS28- TYP.
DEM
O C
AN
T'D
EN
DS A
ND
NEW
2x8 A
T 1
6"
O.C
.
4'-0"
3'-0"
18'-10" ±
OPTION TO SETBACK
24" TO MATCH
CENTER STAIRS
3'-3"
(
N
)
6
x
6
C
O
L
.
(
N
)
6
x
6
C
O
L
.
5'-3" 25'-0"
CANT.
CANT.
CANT.CANT.
8
S3
5'-9
1
4
"
PROVIDE GUARDRAIL SEPARATION
BETWEEN UNITS - TYP., INSTALL
BLOCKING AS REQ'D. IF NOT
ALIGNED WITH JOISTS (2 LOC.)
NEW 16"ø CONC. PIER,
SEE 1/S1 - TYP. AT
NEW COL. LOC.
NEW LPC6Z POST
CAPS - TYP.
3
1
8
"x16
1
2
"24F-V8 GLULAM BM.3
1
8
"x16
1
2
"24F-V8 GLULAM BM.
(2) 2x10
WW
W.RIVETEN
G.CO
M | (720) 288-1580 | (719) 271-7419
PO
BO
X 1238, PARKER, CO
| PO
BO
X 64513, CO
LO
. SPG
S., CO
RIVET No.
DATE:ISSUE/REV:
SHEET No.
SHEET TITLE:
DESIGN by:
REVIEW by:
of
Panoram
a Estates
Deck and Stair Repair &
Reskin
502-544 Superior Street
Colorado Springs, CO
80904
BID SET 9/8/2017
JBP
JRW
170305X
10
BID SET ROOFS 1/10/2018
For Constr. 6/29/2018
-- --
-- --
6/29/2018
S3
DETAILS
8
ELEVATION RENDERING
*RENDERING DEPICTS REPRESENTATION OF FINAL CONDITIONS UPON
COMPLETION OF ENTIRETY OF PROJECT. CURRENT SCOPE INCLUDES
ITEMS DEPICTED HEREIN WHILE OTHERS WILL BE REPLACED ON A
SCHEDULE AS DETERMINED BY THE HOA GUIDELINES TO BE DETERMINED.
TYPICAL SISTERED FLOOR JOISTS
SCALE: 3" = 1'-0"
2
S3
EXIST. FLOOR JOIST BACKSPAN
TO REMAIN (SINGLE MEMBER
AT EVERY OTHER JOIST)
NEW DBL. 2x WOOD FLOOR JOIST
w/ CANTILEVER - SEE PLAN
NEW OR EXIST.
SHEATHING - SEE PLAN
SIMPSON WSNTL212S SCREWS
AT AT 12" O.C. STAGGERED
FULL LENGTH
EXIST. 2x FLAT
SLEEPERS TO REMAIN
R&R
5
8
" TYPE-X DRYWALL AT
GARAGE CEILING TO MATCH
EXIST. WHERE REQ'D
N
O
T
U
S
E
D
MAIN LEVEL CANTILEVERED DECK FRAMING
SCALE: 1" = 1'-0"
1
S3
(E) FLOOR SHEATHING
TO REMAIN
EXIST. DBL. WOOD
TRUSS GIRDER TO
REMAIN - SEE PLAN
NEW 1"x5.5" COMPOSITE
DECKING - TYP.
V.I.F. CONDITION OF RIM - REPLACE
IN FULL WHERE MOISTURE DAMAGE
IS PRESENT
EXIST. GARAGE HEADER TO
REMAIN (EXIST. WALL
FRAMING SOME LOC.)
NEW ALASKAN CEDAR GLULAM BM.
PER PLAN - STAIN TO MATCH NEW
COLOR SCHEME (BY OWNER)
SEE PLAN
UPPER LEVEL WALL
FRAMING TO REMAIN
NEW DECK JOIST PER PLAN - SAWCUT
EXIST. CANT. JOISTS AT WALL
SIMPSON FACE-MOUNT
HANGER PER PLAN, EA. END
EXIST. WALL FRAMING BEYOND
3'-6"
2"±
EXIST. PERPENDICULAR
SLEEPERS TO REMAIN
CUT. EXIST. CANT. ENDS
(3
1
2
" BRG. TO REMAIN)
EXIST. FRAMING
NEW COAT AT EXIST. STUCCO
VENEER or WOOD TRIM TO
REMAIN - PATCH AS REQ'D. FOR
NEW MATERIAL INSTALLATION
PATCH STUCCO AS
REQ'D., INSTALL WEEP
AS NECESSASRY
4" M
IN
.
3"
4"
NEW SELF-ADHERED-MEMBRANE
(BITUTHENE) OVER FLASHING
NEW 26ga 12" WIDE
COLLAR FLASHING ATOP
EA. NEW DBL. CANT. JOIST
PATCH TOP 24"± STUCCO
BENEATH DECKING
PROVIDE SELF-HEALING ICE
AND WATER FLASHING
STRIPS ATOP JOISTS
4"
HSS 2x2x
3
16
POST AT EQUAL
SPACING, 48" O.C. MAX
HSS 2x2x
3
16
TOP RAIL
1"SQ. ROD
4
1
2
"
5"
TYP.
1
2
"ø TRHU-BOLT w/
1
1
2
"ø GALV. WASHERS
1'-3"
4"
4"
FIELD VERIFY EXIST. WRB BEHIND
VENEER AND SHINGLE-LAP WRB
OVER NEW MEMBRANE
NEW 2x8 CONT. LEDGER w/
LEDGERLOK LL005 FASTENERS
AT 16" O.C. STAGGERED
NEW WOOD POST PER PLAN -
ALIGN OUTSIDE FACE w/
GLULAM BM. - FASTEN TOP w/
LPC6Z EA. FACE - NOTCH TOP
IN LIEU OF FLUSH CUT AT
CONTRACTOR OPTION
3
S3
TYPICAL LANDING SECTION
SCALE:
3
4
" = 1'-0"
2"
VARIES -
SEE PLAN
1
4
"
11"
4x12 P.T. STAIR TREAD -
STAIN TO MATCH FINISH
OF COMPOSITE DECKING
3'-3"
3"
HSS 2x2x
3
16
POST AT EQUAL
SPACING, 48" O.C. MAX
HSS 2x2x
3
16
TOP RAIL
1"SQ. ROD (EQUIV.
HOLLOW SECTION IS
ADEQUATE IF AVAILABLE)
3
1
2
"
5"
TYP.
3"
LUS26 EA. END
1"x5.5" COMPOSITE
DECKING AT LANDINGS
GUARDRAIL AND HANDRAIL
NOT SHOWN FOR CLARITY
- SEE OTHER DETAILS
WOOD FRAMING AT
LANDING PER PLAN
4x8 CROSS MEMBER
AT LANDING
L2x2x
1
4
x0'-2" - FASTEN
TO SLAB w/
1
2
"ø EXP.
ANCHOR
4x12 EDGE
BM. - TYP.
VARIES BY LOC.
- SEE PLAN
4x4 POST BEYOND -
SEE 1/S1 AND 7/S3
(2)
1
2
"ø LAG w/
1"ø WASHER AT
EA. POST - TYP.
2
5
8
"
6"
TYPICAL STAIR POST DETAIL
SCALE: 1" = 1'-0"
7
S3
PLAN VIEW
LANDING FRAMING -
SEE PLAN AND 3/S1
4x4 POST
PER PLAN
LANDING DECKING AND
JOISTS NOT SHOWN
FOR CLARITY
NEW 4x4 WOOD
POST - SEE PLAN
SIMPSON LCE4
EA. FACE
EDGE BM. PER PLAN
GUARDRAIL
- SEE 5/S3
TYPICAL STRINGER-TO-DECK CONNECTION
SCALE: 1" = 1'-0"
8
S3
SEE PLAN AND 1/S3
FOR REMAINDER
L3x3x
1
4
x0'-8
1
2
" w/ (3)
1
2
"ø
THRU-BOLTS AT DECK
AND STRINGER
NEW GLULAM EDGE BM.
OR DBL. 2x BM PER PLAN
WOOD 4x12 STAIR
STRINGER - TREADS
NOT SHOWN FOR
CLARITY
3"
2" M
IN
.
1
4
"
DECK FRAMING
PER PLAN
4
S3
TYPICAL STAIR GUARDRAIL
SCALE:
3
4
" = 1'-0"
3'-6"
3"
5
1
2
"
5"
TYP.
FULL-PEN WELD AT
STRINGER JOINTS - TYP.
3"
INTERMEDIATE STRINGER FOR
LOWER RUN NOT SHOWN
CANTILEVERED PURLIN BEYOND
WHERE OCCURS AT DECK END
OVERHANG - BEAR ATOP EXIST.
CONC. WALL OR POST AS
INDICATED ( EDGE BM. SOME LOC.)
3'-6"
FACE OF EXIST. BLDG.
EQ. EQ.
SEE 6/S3 FOR
CORNER CONN.
4
"
ALIGN T.O. BM. WITH
T.O. DECKING
RISER QUANTITY
AND DIMENSIONS
PER PLAN - TYP.
STL. POST PER PLAN
AND DETAIL 7/S3
SEE DETAIL 5/S3
FOR HANDRAIL
EDGE OF DECK/GUARDRAIL
BEYOND DOME LOC.
SEE 8/S3 FOR
STRINGER CONN.
3'-6" AT N
OSIN
G
CANTILEVER PURLIN TO EDGE STRINGER
SCALE: N.T.S.
6
S3
PLAN VIEW
CANTILEVERED
PURLIN or EDGE
BM. PER PLAN
EXIST. CONC. WALL SOME
LOC. - PROVIDE P.T. SHIM
PL WHERE NO POST OCCURS
STAIR TREADS
NOT SHOWN
POST DOWN TO EXIST.
CONC. WALL SOME LOC.
EXIST. BLDG. CORNER
1
2
"
WOOD DECK
FRAMING PER PLAN
CANTILEVERED WOOD
PURLIN PER PLAN
RAILING POST
INTERMEDIATE CANT'D PURLIN
AT BUILDINGS 4 and 6
WOOD POST
BELOW SOME LOC.
CONTINUE LEDGER
THROUGH CANT. (MIN 5'
BACKSPAN TO SPLICE)
4x12 STAIR STRINGER - SEE
8/S3 FOR CONN. - STRINGER
FASTENED TO FRONT GLULAM
BM. SOME LOC. - SEE PLAN
RAILING AND STRINGER DETAIL
SCALE: 1
1
2
" = 1'-0"
5
S3
3'-6"
3"
3
1
2
"
5"
TYP.
4x12 TREAD - TYP.
SIMPSON TA10Z STAIRCASE
ANGLE EA. END
HSS 2x2x
3
16
POST AT EQUAL
SPACING, 48" O.C. MAX
HSS 2x2x
3
16
TOP
AND BOT RAIL
1"SQ. ROD
CONT. HANDRAIL AT OUTER STRINGERS -
PROVIDE HSS 1
1
2
"x1
1
2
" OR EQUIV. - FASTEN
w/
1
2
" SUPPORT RODS AT EA. POST
2"
6"
4x12 STRINGER
(2)
1
2
"ø LAG w/
1"ø WASHER AT
EA. POST - TYP.
WW
W.RIVETEN
G.CO
M | (720) 288-1580 | (719) 271-7419
PO
BO
X 1238, PARKER, CO
| PO
BO
X 64513, CO
LO
. SPG
S., CO
RIVET No.
DATE:ISSUE/REV:
SHEET No.
SHEET TITLE:
DESIGN by:
REVIEW by:
of
Panoram
a Estates
Deck and Stair Repair &
Reskin
502-544 Superior Street
Colorado Springs, CO
80904
BID SET 9/8/2017
JBP
JRW
170305X
10
BID SET ROOFS 1/10/2018
For Constr. 6/29/2018
-- --
-- --
6/29/2018
S4.1
ROOF FRAMING
PLAN AND DETAILS
9
1. SEE GENERAL NOTES FOR TYPICAL CONNECTION AND FRAMING INFORMATION UNLESS NOTED OTHERWISE.
2. DO NOT SCALE THESE DRAWINGS.
3. ALL DIMENSIONS SHOWN ARE TO THE OUTSIDE FACE OF WOOD SHEATHING U.N.O.
4. ALL DIMENSIONS TO EXISTING MEMBERS ARE APPROXIMATE - CONTRACTOR TO VERIFY ALL DIMENSIONS AND
ELEVATIONS IN FIELD PRIOR TO FABRICATION OF NEW MATERIALS.
A
S4.1
BLDGS. 1, 2, 3, 4, 6 ROOF PLAN w/ EYEBROWS
SCALE:
1
4
" = 1'-0"
B
S4.1
BLDG.5 ROOF PLAN w/ EYEBROWS
SCALE:
1
4
" = 1'-0"
72'-0"
UNIT 502 UNIT 504 UNIT 506 UNIT 508
(
E
)
T
J
I
R
O
O
F
F
R
A
M
I
N
G
T
O
R
E
M
A
I
N
-
T
Y
P
.
EXIST. GUTTER DOWNSPOUT TO
REMAIN (NEW PAINT) - MAINTAIN
THRU-WALL SCUPPERS TO EXIST.,
PATCH AS REQ'D.
13'-10" 10'-6" 25'-6" 10'-6" 13'-10"
12'-9"
REMOVE EXIST. MANSAARD
ROOFING - TYP. ALL AROUND
14'-0" ±
INSTALL NEW STUCCO
WHERE OLD MANSAARD IS
REMOVED AND NEW FRAMING
DOES NOT EXTEND
1'-1"
7
3
4
"
1'-1"
30'-0"
3'-3" ±
72'-0"
REMOVE EXIST. MANSARD ROOF FEATURE
AND INSTALL NEW EYEBROW AT PARAPET
WHERE SHADED - SEE ELEVATION
1. SEE GENERAL NOTES FOR TYPICAL CONNECTION AND FRAMING INFORMATION UNLESS NOTED OTHERWISE.
2. DO NOT SCALE THESE DRAWINGS.
3. ALL DIMENSIONS SHOWN ARE TO THE OUTSIDE FACE OF WOOD SHEATHING U.N.O.
4. ALL DIMENSIONS TO EXISTING MEMBERS ARE APPROXIMATE - CONTRACTOR TO VERIFY ALL DIMENSIONS AND
ELEVATIONS IN FIELD PRIOR TO FABRICATION OF NEW MATERIALS.
1
S4.1
3
S4.1
2
S4.1
INSTALL NEW STUCCO WHERE
OLD MANSAARD IS REMOVED AND
NEW FRAMING DOES NOT EXTEND
BASE BID: NEW WOOD
TRIM, PAINT
ALTERNATE BID: NEW
CEMENT BOARD TRIM,
PAINTED or PRE-FINISHED
2
S4.1
SIM.
1
S4.1
SIM.
7'-8" ± 7'-8" ± 7'-8" ±7'-8" ±
5'-1"
THIS PLAN APPLIES TO BLDGS. 1, 2, 3, 4, AND 6. CONFIGURATION
OF EXISTING MANSARD ROOFING VARIES AT ENDS. PATCH ALL
LOCATIONS OF STUCCO WHERE MANSARD IS REMOVED AND NOT
REPLACED WITH NEW EYEBROW. SEE ELEVATION FOR EXTENT OF
APPROXIMATE STUCCO INSTALLATION.
37'-0"
UNIT 534 UNIT 536
(
E
)
T
J
I
R
O
O
F
F
R
A
M
I
N
G
T
O
R
E
M
A
I
N
-
T
Y
P
.
EXIST. GUTTER DOWNSPOUT TO
REMAIN (NEW PAINT) - MAINTAIN
THRU-WALL SCUPPERS TO EXIST.,
PATCH AS REQ'D.
13'-10" 11'-6" 13'-10"
12'-9"
14'-0" ±
INSTALL NEW STUCCO
WHERE OLD MANSAARD IS
REMOVED AND NEW FRAMING
DOES NOT EXTEND
1'-1"
7
3
4
"
1'-1"
30'-0"
3'-3" ±
37'-0"
REMOVE EXIST. MANSARD ROOF FEATURE
AND INSTALL NEW EYEBROW AT PARAPET
WHERE SHADED - SEE ELEVATION
1
S4.1
3
S4.1
2
S4.1
INSTALL NEW STUCCO WHERE
OLD MANSAARD IS REMOVED AND
NEW FRAMING DOES NOT EXTEND
2
S4.1
SIM.
1
S4.1
SIM.
7'-8" ±7'-8" ±
5'-1"
N
1'-1"
1'-1"
SEE OTHER
PLANS FOR
NORTH - TYP.
REMOVE EXIST. MANSARD
ROOFING - TYP. ALL AROUND
INDICATES STEP AT EYEBROW BETWEEN
TALL AND SHORT EYEBROWS PER 2/S4
AND 1/S4 RESPECTIVELY - TYP.
INDICATES STEP AT EYEBROW BETWEEN
TALL AND SHORT EYEBROWS PER 2/S4
AND 1/S4 RESPECTIVELY - TYP.
INSTALL NEW PRE-FINISHED METAL
PARAPET CAP AT REMAINDER
WHERE MANSARD IS REMOVED
INSTALL NEW PRE-FINISHED METAL
PARAPET CAP AT REMAINDER
WHERE MANSARD IS REMOVED
INSTALL NEW PRE-FINISHED METAL
PARAPET CAP AT REMAINDER
WHERE MANSARD IS REMOVED
INSTALL NEW PRE-FINISHED METAL
PARAPET CAP AT REMAINDER
WHERE MANSARD IS REMOVED
(E) 2x6 W
ALL
TO
REM
AIN
- TYP.
(E) 2x6 W
ALL
TO
REM
AIN
- TYP.
EXIST. SEPARATION WALLS
BELOW TO REMAIN - TYP.
EXIST. SEPARATION WALLS
BELOW TO REMAIN - TYP.
2
S4.1
DEEP EYEBROW SECTION AT WALL
SCALE:
3
4
" = 1'-0"
REMOVE EXIST. MANSARD
SHAKES AND FRAMING
NEW 2x4 NAILER w/ (2) 16d
NAIL AT 16" O.C. - NAIL TO (E)
WALL STUD WHERE OCCURS
EXIST. FINISHES
TO REMAIN
SEE 1/S4.1 FOR REMAINDER
EXIST. ROOF FRAMING
TO REMAIN (PERP. AT
SIM.)
BOT. OF EXIST. WINDOW
TRIM BEYOND (NOT AT SIM.)
9'-2"
OSB WALL SHEATHING -
SEE GENERAL NOTES
2x4 LOOKOUT
FRAMING AT 16" O.C.
EXIST. EPDM ROOFING
2x6 FRAMING AT EXIST. WALL
NEW 24 GA. PRE-FINISHED METAL
PARAPET CAP w/ DRIP EDGE AND HIDDEN
FASTENERS AT FACE - SLOPE TO BACK
MIN. (4) 10d NAILS AT
EA. INTERSECTION OF
FRAMING MEMBERS
NEW SOFFIT SHEATHING
AND PANELS
IN
STALL N
EW
STU
CCO
PER ELEV.
INSTALL NEW 30# FELT BENEATH
- SHINGLE LAP w/ EXIST. BELOW
EXIST. 2x6 WALL
FRAMING TO REMAIN
2x4 WEBS AT EVERY OTHER
FRAME - PROVIDE BIRDS-MOUTH
AND TOENAILS AT BOT.
2x4 BLOCKING AT EA.
CORNER AND THIRD POINTS
30# FELT BENEATH
PANELS
1'-1"
NEW S-DECK METAL PANEL
VENEER PER SPECS - FASTEN
PER MFR. RECOMMENDATIONS
- INSTALL OVER NEW W.R.B.
PROVIDE BLOCKING
AT CORNERS
1
S4.1
DEEP EYEBROW SECTION AT WINDOW
SCALE:
3
4
" = 1'-0"
REMOVE EXIST. MANSARD
SHAKES AND FRAMING
EXIST. 2x4 NAILER TO REMAIN
- ADD (1) 16d NAIL AT 6" O.C.
STAGGERED TOP AND BOT.
NEW WINDOWS PER HOA
GUIDELINES - NOT AT SIM.
(NOT IN CURRENT SCOPE)
EXIST. FINISHES
TO REMAIN
REMOVE 2x TOP PL - SPLICE NEW
2x6 STUDS TO EXIST. w/ (2) 10d
NAILS AT 4" O.C. (6 NAILS MIN.)
EXIST. ROOF FRAMING
TO REMAIN (PERP. AT
SIM.)
EXIST. HDR. AT
WINDOW
4'-6"
OSB WALL SHEATHING
- SEE GENERAL NOTES
2x4 LOOKOUT
FRAMING AT 16" O.C.
EXIST. EPDM ROOFING
EXTEND NEW 60mil ADHERED
EPDM UP AND OVER PARAPET
- TERMINATE PER MFR.
2x6 FRAMING AT EXIST. WALL
NEW 24 GA. PRE-FINISHED METAL
PARAPET CAP w/ DRIP EDGE AND HIDDEN
FASTENERS AT FACE - SLOPE TO BACK
MIN. (4) 10d NAILS AT
EA. INTERSECTION OF
FRAMING MEMBERS
NEW SOFFIT SHEATHING
AND PANELS
1'-1"
NEW S-DECK METAL PANEL
VENEER PER SPECS - FASTEN
PER MFR. RECOMMENDATIONS
- INSTALL OVER NEW W.R.B.
PROVIDE BLOCKING
AT CORNERS
4
1
2
"
3
S4.1
SHALLOW EYEBROW SECTION AT WALL
SCALE:
3
4
" = 1'-0"
REMOVE EXIST. MANSARD
SHAKES AND FRAMING
EXIST. FINISHES
TO REMAIN
SEE 1/S4.1 FOR REMAINDER (SIM.)
EXIST. ROOF FRAMING
TO REMAIN
3'-4"
OSB WALL SHEATHING
- SEE GENERAL NOTES
EXIST. EPDM ROOFING
2x6 FRAMING AT EXIST. WALL
NEW 24 GA. PRE0FINISHED METAL
PARAPET CAP w/ DRIP EDGE AND HIDDEN
FASTENERS AT FACE - SLOPE TO BACK
NEW SOFFIT SHEATHING
AND PANELS
NEW S-DECK METAL PANEL
VENEER PER SPECS - FASTEN
PER MFR. RECOMMENDATIONS
- INSTALL OVER NEW W.R.B.
6"
EXIST. FRAMING
TO REMAIN
INSTALL NEW STUCCO OVER EXIST.
WOOD SIDING PER ELEVATION
INSTALL NEW 30# FELT BENEATH -
SHINGLE LAP w/ EXIST. BELOW
NEW 2x8 STUDS AT 16" O.C. -
FASTEN TO EXIST. WALL w/
(2) A35 CLIPS
2x8 BLOCKING AT MID HT.
AND BOT.
8"
DEEP EYEBROW BEYOND
2x4 TIE AT TOP - ALIGN
STUDS - PROVIDE MIN. (4)
10d NAILS EA. MEMBER
WW
W.RIVETEN
G.CO
M | (720) 288-1580 | (719) 271-7419
PO
BO
X 1238, PARKER, CO
| PO
BO
X 64513, CO
LO
. SPG
S., CO
RIVET No.
DATE:ISSUE/REV:
SHEET No.
SHEET TITLE:
DESIGN by:
REVIEW by:
of
Panoram
a Estates
Deck and Stair Repair &
Reskin
502-544 Superior Street
Colorado Springs, CO
80904
BID SET 9/8/2017
JBP
JRW
170305X
10
BID SET ROOFS 1/10/2018
For Constr. 6/29/2018
-- --
-- --
6/29/2018
S4.2
ELEVATIONS
10
1
S4.2
FRONT ELEVATION
SCALE:
1
4
" = 1'-0"
2
S4.2
TYPICAL SIDE ELEVATION
SCALE:
1
4
" = 1'-0"
EXIST. RET. WALLS
AND LANDSCAPING
SOME LOC.
R&R WINDOW AND DOOR TRIM
(BASE AND ALTERNATE) - SEAL
AND PAINT - TYP. PER SPECS
S-DECK METAL PANEL
SIDING BY BERRIDGE
PER SPECIFICATIONS
NEW EYEBROWS PER
PLAN AND DETAILS
REMOVE EXIST.
MANSARD ROOF IN FULL
PATCH STUCCO BENEATH
REMOVED MANSARD - TYP.
NEW STUCCO AT REMOVED
MANSARD ROOF WHERE
OCCURS - ADD (2) LAYERS OF
GRADE D FELT, ATTACH NEW
LATH INTO EXIST. FRAMING
EXIST. GUTTER DOWNSPOUTS -
DETACH AND RESET AS REQ'D.
FOR STUCCO/PAINT APPLICATION
PATCH STUCCO WHERE
MANSARD IS REMOVED
S-DECK METAL PANEL
SIDING BY BERRIDGE
PER SPECIFICATIONS
LOW MANSARD SOME SIDES
- REMOVE AND PATCH
STUCCO WHERE OCCURS
AT EXISTING STUCCO THAT REMAINS, PROVIDE NEW
DIRECT-BOND STUCCO APPLICATION w/ MEDIUM FINISH
1. POWER WASH EXIST. SURFACE
2. SKIM COAT OVER EXIST. WITH ACRYLIC CEMENT BOND
3. ADD CRACK MESH IF CRACKING IS EXTENSIVE
4. PROVIDE FINAL COLOR COAT, ACRYLIC FINISH TO
MATCH SPECS
NEW COATING AT EXIST.
STUCCO TO MATCH PATCHED
STUCCO - SEE NOTES THIS
SHEET AND SPECS FOR
PROCESS, COLORS - TYP ALL
STUCCO SURFACES
NEW COATING AT EXIST.
STUCCO TO MATCH PATCHED
STUCCO - SEE NOTES THIS
SHEET FOR PROCESS - TYP
ALL STUCCO SURFACES
1
S4.1
2
S4.1
3
S4.1
1
S4.1
SIM.
2
S4.1
SIM.
WINDOW SOME LOC.
1. DECKING MATERIAL: TREX - SADDLE (SELECT) COLOR
2. STAIR TREAD MATERIAL: CLEAR SEALER
3. STUCCO COLOR 1: MEDIUM FINISH - DARK COLOR - MATCH SHERWIN WILLIAMS SW6279 BLACK SWAN
4. STUCCO COLOR 2: MEDIUM FINISH - LIGHT COLOR - MATCH SHERWIN WILLIAMS SW7029 AGREEABLE GRAY
5. METAL RAILING: TOP RAIL - MATCH SHERWIN WILLIAMS SW7067 CITYSCAPE
ALL EXCEPT TOP RAIL - MATCH SHERWIN WILLIAMS - SW7059 UNUSUAL GRAY
6. WINDOW TRIM: PAINTED WOOD BASE BID, CEMENT BOARD AS ALTERNATE: GRAY COLOR, MATCH SHERWIN
WILLIAMS - SW7059 UNUSUAL GRAY
7. METAL PANEL: EXPOSED FASTENER S-DECK BY BERRIDGE METAL, or APPROVED EQUAL, VERTICAL
APPLICATION, 24 GAUGE, MATTE BLACK COLOR, MATTE BLACK TRIM.
8. MISCELLANEOUS METALS: MATCH SHERWIN WILLIAMS SW6279 BLACK SWAN -or- MATTE BLACK TO MATCH
METAL PANELS
FINISH LEGEND:
SHADED AREA DENOTES
DARKER STUCCO COLOR 1
SHADED AREA DENOTES
DARKER STUCCO COLOR 1
PATCH STUCCO BELOW
DECK REPAIRS PER DECK
FRAMING DETAILS - TYP.