PANEL POWER UP GUIDELINES Check the incoming voltage – 240V/110V Connect the AC wires to the appropriate terminals Connect the Ground Wire to the Body of the Panel It is recommended that the power cable entry taken from bottom right side of the panel Avoid any cable entry from beneath the panel box as this space is dedicated to battery Building DB shall have a dedicated breaker with ‘Fire Alarm’ marking on it. It is recommended to install a Fused Spur Switch next to the panel or inside the panel to isolate the power in case of requirement The AC wire plug from the SPS should be connected in the right direction- Force entry of the plug will damage or blow up the fuse. it is recommended to have a junction box for the cables and conduits before entering into the panel Once the system is stable connect the Battery leads Do not connect the batteries first To power down the panel the batteries shall be disconnected first and then the AC power shall be switched OFF

Panel Power Up Guidelines

Embed Size (px)

DESCRIPTION

simplex power up

Citation preview

Page 1: Panel Power Up Guidelines

PANEL POWER UP GUIDELINES

• Check the incoming voltage – 240V/110V

• Connect the AC wires to the appropriate terminals

• Connect the Ground Wire to the Body of the Panel

• It is recommended that the power cable entry taken from bottom right side

of the panel

• Avoid any cable entry from beneath the panel box as this space is dedicated

to battery

• Building DB shall have a dedicated breaker with ‘Fire Alarm’ marking on it.

• It is recommended to install a Fused Spur Switch next to the panel or inside

the panel to isolate the power in case of requirement

• The AC wire plug from the SPS should be connected in the right direction-

Force entry of the plug will damage or blow up the fuse.

• it is recommended to have a junction box for the cables and conduits

before entering into the panel

• Once the system is stable connect the Battery leads

• Do not connect the batteries first

• To power down the panel the batteries shall be disconnected first and then

the AC power shall be switched OFF