STD-0046-012303R2
SOVEREIGN TRACKING SYSTEMS LCC 1108 Industrial Parkway Brick, NJ 08742 732-836-3400 732-836-9899 www.sovtechcorp.com
Paltrack ATS Installation Manual
STD-0046-012303R2
Table of Contents
Introduction (1) Cable Installation (1 – 2) Materials (1) Restrictions (2) Procedure (2) Transceiver Installation (3 – 5) Materials (3) Restrictions (3) Procedure (3 – 5) Server Installation (5 – 6) Materials (5) Restrictions (5) Procedure (6) Calibration Instructions (7 – 9) Long Range / Full Triangulation (7 – 8) Short Range (8 – 9) Figure 1 – continuous branch configuration (10) Figure 2 – split branch configuration (10) Figure 3 – system configuration (11) Figure 4 – transceiver (12) Figure 5 – removed cover (13) Figure 6 – power / data interface (14) Figure 7 – master transceiver (15) Figure 8 – converter (16)
Paltrack RTLS
STD-0046-012303R2 1
ATS (Asset Tracking System) Installation Procedures
Prior to installation, SovTrack licensed installers must perform a site survey to
determine proper routing and placement of Transceivers, Power Supplies, and
Servers.
Cabling diagrams will be provided by SovTrack and must be stringently adhered to.
SovTrack recommends that all restrictions regarding the installation of all cables
such as ANSI cabling regulations and any additional restrictions warranted by the
facility’s project manager be adhered to.
This manual covers the following components:
• Cable Installation.
• Transceiver Installation.
• Server Installation.
• Calibration Instructions.
I. Cable Installation
A. Materials
1. 16 AWG 2-conductor twisted and shielded cable.
• Power Supply cable.
2. 22 AWG 2-conductor twisted and shielded cable.
• RS485 Data Interface cable.
3. Category 5 UTP cable.
• LAN Interface cable.
4. Wire Stripper/Cutter.
Paltrack RTLS
STD-0046-012303R2 2
B. Restrictions
1. On a single branch, Power Supply cabling must not exceed a total of 1500 feet
from Power Supply location to last Transceiver location.
• Should the total exceed the maximum restriction of 1500 feet but less
than 3000 feet, a Split Branch Configuration is required.
o Single Branch Configuration – see Figure 1. o Split Branch Configuration – see Figure 2.
o Refer to Appendix B for Master Transceiver Split instructions.
• Install Power Supply in nearest Communication Closet when necessary.
2. RS485 Data cabling must not exceed a total of 3500 feet from the Converter or
Master Transceiver to the last Transceiver location.
• Should the total exceed the maximum restriction of 3500 feet, a
RS485-RS485 repeater is required – see Figure 9.
o Refer to Appendix A for Repeater Data Sheet.
• Install Repeater in nearest Communication Closet when necessary
3. Category 5 UTP cable must not exceed a total of 330 feet.
• Should the total exceed the maximum restriction of 330 feet, a repeater
is required. C. Procedure
1. Each Transceiver is wired in parallel to each other with Power Supply and RS485
Data cabling.
• SovTrack does not recommend splicing RS485 Data cable.
2. A Service Loop of ten (10) feet should be at each Transceiver location.
3. RS485 Data cable is branched from the First Transceiver location with a fifteen
(15) foot Service Loop at the Paltrack Server location. 4. Cabling should be installed covertly above drop ceilings whenever necessary.
Paltrack RTLS
STD-0046-012303R2 3
5. Refer to Figure 3 for System Configuration Diagram.
II. Transceiver Installation
A. Materials
1. Wire Strippers/Cutter.
2. #1 and #2 Phillips Head Screw Driver. 3. Small Slotted Screw Driver. 4. Long Nose Pliers. 5. 1-1/16” Open End Wrench or 2” Adjustable Wrench. 6. Mounting Hardware.
B. Restrictions
1. SovTrack recommends only licensed and trained installers attempt this point of
installation.
2. Transceivers and/or Active Antennae must be free from surrounding RF
Radiating Devices such as plumbing, heating and air-conditioning ventilation, or
any ductwork and/or cable trays etc…
3. Transceivers and/or Active Antennae must not be attached to metal.
C. Procedure
1. Fasten Transceiver Enclosure to wall.
• With #2 Phillips Head Screw Driver, fasten screws through four mounting
holes located on side tabs of enclosure.
2. Remove Transceiver Cover.
Paltrack RTLS
STD-0046-012303R2 4
• With # 1 Phillips Head Screw Driver, remove four screws located on
Cover of Transceiver (see Figure 4 – transceiver).
• Take care not to unplug the cover from Transceiver PC Board (see Figure 5 – removed cover).
3. Set Transceiver ID.
• Using chart 1 (DIP switch settings) attached and slotted screwdriver.
4. Set Range.
• Set slide switch to proper range setting [SR (short range) / LR (long
range)].
5. Install Power Interface.
• Feed Power Supply cable through Strain Relief located on side of
Transceiver Enclosure. Loosen the Hex Nut as needed.
• Remove Terminal Block Header from 8-Position Connector.
• Using a slotted screwdriver attach Power Supply Ground (black) and
cable shield to Position 1 of Terminal Block Header.
• Using a slotted screwdriver attach Power Supply Positive (white or red) to
Position 2 of Terminal Block Header.
• Note proper connections on Figure 6 – power / data interface attached.
6. Install RS485 Data Interface.
• Feed RS485 Data cable through Strain Relief located on side of
Transceiver Enclosure. Loosen the Hex Nut as needed.
• Using a slotted screwdriver attach RS485 Data cable shield to Position 6
of Terminal Block Header.
• Using a slotted screwdriver attach RS485 Data cable “B” (black) to
Position 7 of Terminal Block Header.
• Using a slotted screwdriver attach RS485 Data cable “A” (white or red) to
Position 8 of Terminal Block Header.
• Note proper connections on Figure 6 – power / data interface attached.
Paltrack RTLS
STD-0046-012303R2 5
7. Reinstall Transceiver Cover.
• Reverse process outlined in 2.
8. Attach Active Antenna.
• SovTrack recommends only licensed and trained installers attempt this
point of installation.
• Using a #2 Phillips Head Screw Driver, attach Active Antenna with
screws through two mounting holes located on side tabs of enclosure.
• Active Antenna Whip must be screwed-in tightly.
• Cable connection must be tightly secure and away from any metal.
• With 1-1/16” Open End Wrench or 2” Adjustable Wrench Tighten
Transceiver Strain Relief Hex Nut.
III. Server Installation
A. Materials
1. Paltrack Server PC.
2. Master Transceiver or RS323 – RS485 Converter and 12-24Vdc Power Supply.
3. Server UPS.
4. Power Supply UPS.
5. Additional PC(s) – as needed.
6. Network Hub – as needed.
B. Restrictions
1. Paltrack Server and associated PC(s) will contain the following:
• Customized Paltrack Software.
• Blueprint Bitmaps.
• Transceiver Icons.
• Multi-port Digicard.
Paltrack RTLS
STD-0046-012303R2 6
C. Procedure
1. Remove Server from boxes and place on flat surface.
2. Assemble Server.
3. Connect Server and Power Supply connections to UPS – if provided.
4. Connect Ethernet LAN and Facility LAN connections. Use Ethernet HUB if more
than one PC are used.
o It is assumed that LAN interface cabling has been routed and RJ45
connectors are attached.
5. Using Serial Cable(s) provided, connect Master Transceiver(s) or RS232 –
RS485 Converter(s) to Multi-port Serial Digicard.
• One for each branch run.
• If connecting to a Split Branch Configuration, make sure the proper
RS232 Serial Connection is made from the Server to the RS232 – RS485
Converter Module.
5. Before making Power and/or RS485 Data connections to the system, do the
following:
• With an Ohmmeter, check resistance between Power cable Ground /
shield and Positive Power. Rework all Power connections if a very low
resistance reading.
• With an Ohmmeter, check resistance between RS485 “A”, RS485 “B” and
RS485 Data cable shield. Rework all RS485 Data connections if a very
low resistance reading.
• Each branch run should be individually checked and in respects to each
other.
6. Make appropriate Serial Connections from each branch to their perspective
Master Transceiver / RS232 – RS485 Converter Module.
• If connection is to Master Transceiver – Refer to Figure 7 for details.
Paltrack RTLS
STD-0046-012303R2 7
• If connection is to RS232 – RS485 Converter Module – refer to Figure 8
for details.
7. Apply Power to the system. Refer to users manual for system operation.
IV. Calibration Instructions
A. Materials
1. Operating Paltrack system.
2. Transmitter.
B. Restrictions
1. Two people are required for this operation.
C. Procedure
1. Long Range / Full Triangulation
• Power-up the Paltrack Server and activate the Paltrack Software.
• Verify that the Transmitter ID has been entered onto the system via the
data manager. Refer to users manual for assistance.
• Activate the transmitter by pressing the switch located on the bottom of
enclosure or attaching the transmitter on the device to be tracked.
• Place the activated transmitter in motion and note the activated yellow
LED on the Transceiver.
o Should the red LED activate during this process, check the range
switch for the proper setting.
• Click on the Paltrack Real-Time Monitoring Server located in the
Windows Task bar.
• Select Range from the Calibrate menu. A dialog box will be displayed to
allow data entry.
Paltrack RTLS
STD-0046-012303R2 8
• Select the Transceiver to calibrate from the drop-down box.
• Enter the Transmitter ID.
• Enter 2 for first distance.
• Enter 50 for second distance.
• Click OK.
• A message will prompt the user to move the transmitter to two feet. Click
OK after the transmitter is positioned.
o Transmitter must be activated and transmitting data.
o Transmits may be forced by gently tapping or rocking the transmitter.
• A second message will prompt the user to move the transmitter fifty feet.
Click OK after the transmitter is positioned.
o Transmitter must be activated and transmitting.
o Transmits may be forced by gently tapping or rocking the transmitter.
• Click YES if user is satisfied that the calibration was successfully done.
• Repeat process as needed for each transceiver.
2. Short Range Calibration
• Power-up the Paltrack Server and activate the Paltrack Software.
• Verify that the Transmitter ID has been entered onto the system via the
data manager. Refer to users manual for assistance.
• Activate the transmitter by pressing the switch located on the bottom of
enclosure or attaching the transmitter on the device to be tracked.
• Place the activated transmitter in motion and note the activated yellow
LED on the Transceiver.
o The red LED may activate during this process.
• Click on the Paltrack Real-Time Monitoring Server located in the
Windows Task bar.
• Select Test from the Calibrate menu. A dialog box will be displayed to
allow data entry.
• Select the Transceiver to calibrate from the drop-down box.
• Click OK.
• Move the activated transmitter to begin detection range.
Paltrack RTLS
STD-0046-012303R2 9
o This is the maximum distance from the transceiver of which detection
is indicated.
• Force transmits by gently tapping or rocking the transmitter.
• With the trimmer tool provided, trim the Range adjustment knob located
on the cover of the transceiver. CCW will increase the range indicator
while a CW trim will decrease range indicator.
• Increase the Range adjustment until the red indicator is flashing with
every receipt of transmitter data.
o If the Range adjustment is turned CCW 11 turns and the red indicator
is not responding to transmitted data, check the range switch setting.
• Decrease the Range adjustment until the red indicator stops flashing.
• Increase the Range adjustment by ¼ turn.
• For a fine adjustment, place the activated transmitter three (3) feet
greater than the desired range and make a Range adjustment until the
red indicator just stops flashing during data transmissions.
• Repeat the above for each transceiver.
Paltrack RTLS
STD-0046-012303R2 10
Figure 1 – continuous branch configuration
Figure 2 – split branch configuration
1500 feet
Trx Trx Trx Trx Trx
PC
RS232 – RS485 Converter
24V Power Supply
* may be included in some packages
Trx
1500 feet 1500 feet
Trx Trx Trx
V Power Supply
Trx Trx Trx
RS485 Interface Module
Converter PC
Master Transceiver
See Appendix B for Master Transceiver Split
Deleted: 24
Deleted: RS232 –
Paltrack RTLS
STD-0046-012303R2 11
Figure 3 – system configuration
Trx Trx Trx Trx
Trx Trx Trx Trx
Trx Trx Trx Trx
PC
PC
PC
Converter
Converter
Converter
24V Power Supply
24V Power Supply
24V Power Supply
Master Transceiver
RS232
RS485
+24Vdc
RS485
+24Vdc
RS485
+24Vdc
Ethernet LAN
32 Trx max
32 Trx max
32 Trx max
Facility LAN
Paltrack RTLS
STD-0046-012303R2 12
Figure 4 – Transceiver
Cover Mounting Screw
Strain Relief
Paltrack RTLS
STD-0046-012303R2 13
Figure 5 – removed cover
Cover Removed
DIP Switch - (set ID)
Range Switch
Power / Data Interface
Paltrack RTLS
STD-0046-012303R2 14
Figure 6 – power / data interface
Close-up of Interface Terminal Block
Position 1 Position 8
Ground + Shield
RS485 “A”
RS485 “B”
Data Cable Ground Positive Power
Paltrack RTLS
STD-0046-012303R2 15
Figure 7 – master transceiver
Close-up of Power / RS485 Interface
+24Vdc Output
Power Ground + Shield RS485 “A”
RS485 “B”
RS232 Serial Interface
Power / RS485 Interface
AC Power Input
RS232 Serial Cable Pin-put Pin 2 TXD Pin 3 RXD Pin 5 GND
Paltrack RTLS
STD-0046-012303R2 16
Figure 8 – RS232 to RS485 Converter Module
DB25F – Female Connection RS232 Interface
DB25M – Male Connection RS485 Interface
DB25M – Male Connector RS485 Pin-out
Pin 2 RS485 Data “B” Pin 7 Data Cable Shield Pin 12 GND Pin 14 RS485 Data “A” Pin 25 +24Vdc
DB25F – Female Connector RS232 Pin-out
Pin 2 RXD Pin 3 TXD Pin 7 GND
Paltrack RTLS
STD-0046-012303R2 17
Figure 9 – RS485 Repeater Configuration
Jump A(-) and B(+) both sides
Shield is SIG. GND. Connection both sides
Warning: Assure proper polarization
Paltrack RTLS
STD-0046-012303R2 18
Appendix A – RS485 – RS485 Repeater Data Sheet
Paltrack RTLS
STD-0046-012303R2 19
ured in USA of domestic and imported parts by
Paltrack RTLS
STD-0046-012303R2 20
Appendix B – Master Transceiver Split Configuration 1) Introduction: Methodology on split configuration applies only to Master Transceiver 33102-0998 or
models that contain a RS232 – RS485 Converter Module. The purpose of the split is to remedy the maximum linear foot cable restrictions between Power Supply and RS232 data communications protocol. In regards to the Power Supply, the maximum linear foot restriction is not to exceed 1500 feet. After which a spit configuration must be performed to a lot another 1500 feet for a total of 3000 feet. In addition, the maximum linear foot restriction for RS232 and RS232C data communications cable is not to exceed 10 feet. In result, a split configuration must be performed whenever the Power Supply is located greater than 10 feet from the Paltrack Server.
2) Requirements: The necessary materials needed to perform a Master Transceiver split configuration
is as follows:
a) Master Transceiver 33102-0998 or equivalent containing a RS232 – RS485 Converter Module. b) RS485 Converter Module enclosure. c) RS232 Data Communications cable. d) Power Supply and cable(s). e) Small blade slotted screwdriver. f) Large blade slotted screwdriver. g) # 1 Phillips screwdriver. h) Wire Cutters. i) Wire Strippers. j) Tape.
3) Procedure: Power Supply / Converter Module Split
a) With Large blade slotted or # 2 Phillips screwdriver, remove four lid screws on Master Transceiver and remove lid from the unit.
b) Locate and remove RS232 – RS485 Converter Module attached to side of Power Supply
enclosure. The Converter Module will be attached with double face adhesive.
c) Detach both D – Sub connectors from the Converter Module and remove Converter from the Power Supply.
d) Cut the DB25M (25 pin male D – Sub) connector from the cable inside the Power Supply
enclosure. If unwarranted, this may be discarded or returned to the manufacture
e) Remove the remaining RS232 Cable from the Power Supply by carefully pulling on the cable located outside the Power Supply enclosure. This is the cable with the DB09F (9 pin female D – Sub) connector attached. If unwarranted, this may be discarded or returned to the manufacture.
f) Wrap the DB25F (25 pin female D – Sub) connector located inside the Power Supply enclosure
with electrical tape. Do not attempt to remove or cut the cable.
g) Install and secure Power Supply enclosure lid.
h) Power Supply is ready for installation.
i) Reference Figure B1
Paltrack RTLS
STD-0046-012303R2 21
4) Procedure: RS485 Converter Module assembly.
a) With a # 1 Phillips screwdriver, locate and remove four enclosure screws. b) If installed, push the RS232 cable through the strain relief to open enclosure.
c) Attach RS232 – RS485 Converter to each corresponding D – Sub connectors located inside the
Converter Module enclosure.
d) Secure D – Sub connectors to the Converter with nylon wire ties.
e) Through two large holes located on the enclosure PC Board, secure the Converter to PC Board with a nylon wire tie.
f) If not installed, feed RS232 Data Cable through open end of strain relief into the Converter
enclosure.
g) With wire strippers and small blade slotted screwdriver, strip open end of RS232 cable and install cable in following configuration:
i) Red wire to “TX” location. ii) Black wire to “RX” location.
iii) Green wire to “GND” location.
h) Feed RS485 Data Cable through open end of strain relief into the Converter enclosure. i) With wire strippers and small blade slotted screwdriver, strip open end of RS485 cable and install
cable in following configuration:
i) White / Red (user defined) to “A”.
ii) Blue / Black (user defined) to “B”.
iii) Cable Shield to “CG”.
j) It is installer discretion to secure RS232 and/or RS485 cables with cable clamps inside Converter enclosure.
k) Inspect and correct any loose, frayed or exposed wire or shielding. l) Assemble two haves of Converter enclosure and secure with same four screws.
m) Pull loose slack tighten strain relief.
n) Repeat entire process as needed.
o) Reference Figures B2 and B3
Paltrack RTLS
STD-0046-012303R2 22
5) Procedure: RS485 Converter Module installation.
a) Organize 485 Converter Module(s) within six feet from Paltrack Server multiple serial port. b) With Power Cable(s) provided, cascade power connections as needed.
i) RS485 Converters may be individually powered. ii) Can cascade up to eight RS485 Converters on a single Power Supply.
c) Install RS232 connections to Paltrack multiple serial port.
d) Wrap remaining RS232 cabling in an organized fashion and secure with wire tie(s).
e) Plug +24 Vdc Power Pack into nearest AC outlet.
f) Plug Power Pack into first cascaded Converter.
g) All power indicators will be activated.
h) Reference Figure B4.
Vdc In
Vdc Out
Vdc In
Vdc Out
Vdc In
Vdc Out
Vdc In
Vdc Out
Last unit is no
connection
Power Supply Input
Paltrack Multi-Port Serial Connection
Paltrack Server
RS232 Data Cable
System Outline Configuration with Cascading RS-485 Interface Modules connected to a multiple Serial Interface Adapter.
Paltrack RTLS
STD-0046-012303R2 23
Figure B1. Master Transceiver with RS232 – RS485 Converter
RS232 Data Cable includes the following: DB25M (male) connector (located within Master Transceiver enclosure). 6’ four conductor cable (located outside Master Transceiver enclosure). DB09F (female) connector (located outside Master Transceiver enclosure).
RS232 – RS485 Converter
RS232 Data Cable
Paltrack RTLS
STD-0046-012303R2 24
Figure B2. RS485 Converter Mounting Screws.
Enclosure Mounting Screw Location
Paltrack RTLS
STD-0046-012303R2 25
Figure B3. RS485 Converter Module Opened
Paltrack RTLS
STD-0046-012303R2 26
Figure B4. RS485 Module with Converter installed
A B CG GND RXD TXD
RS485 RS232 A - WHT / RED GND - GRN B - BLU / BLK RXD - BLK CG - SHIELD TXD - RED