Pursuant to SB 1371, Leno - Natural gas: leakage abatement, the California Public Utilities Commission (CPUC) requests that the following information be transmitted to the CPUC and the State Air Resources Board (ARB):
Note - Definitions in Data Request Pacific Gas and Electric R15-01-008 2017 June Report
The following question in the above mentioned data request is answered using the spreadsheets in this Appendix (#3):(6) Calculable or estimated fugative emissions and non-graded gas leaks, as defined in Data Request Pacific Gas and Electric R15-01-008 2017 June Report.
Notes:
Use a formula-derived value with the formula used in the Annual Emissions column. Do not use a copy and paste-as-value.
At the end of Annual Emissions Column, add a summation total in a cell for a column total, and then highlight orange.The emissions captured on this tab represent the emissions associated with the operational design and function of the compressor. Any intentional release of natural gas for safety or maintenance purposes should be included on the Blowdowns worksheet.
Response:
Transmission Compressor Vented Emissions:
IDGeographic
Location
Compressor
Type
Prime
Mover
Number
of
Cylinders
Number
of
Seals
Seal
Type
Operating Mode:
Pressurized Operating
(hours)
Operating Mode:
Pressurized Idle
(hours)
Operating Mode:
Depressurized Idle
(hours)
Emission Factor:
Pressurized
Operating(scf/hr)
Emission Factor:
Pressurized Idle
(scf/hr)
Emission Factor:
Depressurized Idle
(scf/hr)
Annual
Emissions
(Mscf)
Explanatory Notes / Comments
TIO-K-196015 C C 1 D 7,675.00 829.00 280.00 2.00 Not applicable 11.60 18.60 Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
BUR-K-296013 C C 1 D 6,644.00 1,891.00 249.00 1.70 Not applicable 11.00 14.03 Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
GER-K-196035 C C 1 D 7,511.00 1,051.00 222.00 1.20 Not applicable 13.00 11.90 Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
DEL-K-195979 C E 1 D 8,235.00 252.00 297.00 2.00 Not applicable 13.80 20.57 Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
DEL-K-295979 C E 1 D 7,941.00 498.00 345.00 2.00 Not applicable 14.30 20.82 Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
DEL-K-395979 C C 1 D 3,680.00 4,662.00 442.00 2.00 Not applicable 14.30 13.68
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
KET-K-193204 C C 1 D 2,018.00 6,558.00 208.00 0.60 Not applicable 6.90 2.65
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
KET-K-293204 C C 1 D 909.00 7,534.00 341.00 0.80 Not applicable 6.90 3.08
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
KET-K-393204 C C 1 D 1,189.00 7,388.00 207.00 5.60 Not applicable 6.90 8.09
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
HIN-K-192347 R C 3 D 3,205.00 4,632.00 948.00 214.90 1.20 6.60 700.57
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
HIN-K-292347 R C 3 D 683.00 7,233.00 868.00 364.00 2.10 10.70 273.09
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
HIN-K-392347 R C 3 D 1,292.00 4,649.00 2,843.00 120.60 1.20 7.70 183.29
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
HIN-K-492347 R C 3 D 3,987.00 3,850.00 948.00 269.80 3.90 4.10 1,094.59
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
HIN-K-592347 R C 3 D 40.00 6,143.00 2,602.00 1.40 1.20 7.30 26.42
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
HIN-K-692347 R C 3 D 388.00 7,479.00 917.00 179.80 1.20 7.70 85.80
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
HIN-K-792347 R C 3 D 1,389.00 1,018.00 6,377.00 281.00 31.30 5.50 457.25
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
HIN-K-892347 R C 3 D 100.00 6,375.00 2,309.00 39.40 1.40 7.30 29.72
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
HIN-K-992347 R C 3 D 537.00 4,980.00 3,267.00 482.20 0.70 7.30 286.28
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
HIN-K-1092347 R C 3 D 3,404.00 3,062.00 2,319.00 230.30 0.70 8.10 804.87
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
HIN-K-1192347 R C 6 D 3,260.00 4,278.00 1,247.00 149.50 2.30 8.00 507.19
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
HIN-K-1292347 R C 6 D 5,274.00 2,927.00 583.00 479.50 16.80 26.80 2,593.68
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
TOP-K-292363 R C 3 D 2,228.00 5,707.00 849.00 369.70 14.00 8.60 910.89
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
TOP-K-392363 R C 3 D 3,619.00 2,156.00 3,009.00 1,537.80 0.90 3.90 5,578.97
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
TOP-K-492363 R C 3 D 1,297.00 6,855.00 633.00 77.50 2.10 9.00 120.61
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
TOP-K-592363 R C 3 D 2,020.00 5,993.00 772.00 74.30 0.80 7.30 160.52
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
TOP-K-692363 R C 3 D 4,051.00 2,534.00 2,199.00 232.90 0.60 3.70 953.13
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
TOP-K-792363 R C 3 D 1,003.00 6,053.00 1,728.00 387.60 0.80 12.90 415.90
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
TOP-K-892363 R C 3 D 1,233.00 7,377.00 174.00 544.80 1.30 9.80 683.03
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
TOP-K-992363 R C 3 D 3,071.00 4,371.00 1,342.00 129.70 0.60 4.30 406.70
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
TOP-K-1092363 R C 3 D 1,017.00 7,500.00 268.00 102.30 1.40 10.00 117.22
Emission factors used based upon the GHG leak measurement taken as required under the
GHG mandatory reporting requirement.
Rev. 3/31/17
Pacific Gas and Electric
Rulemaking (R.) 15-01-008 to Adopt Rules and Procedures Governing Commission Regulated Natural Gas Pipelines and Facilities to Reduce Natural Gas Leaks Consistent with Senate Bill 1371, Leno.and In Response to Data Request Pacific Gas and Electric R15-01-008 2017 June Report
3/31/2017Appendix 3
3-1
Pursuant to SB 1371, Leno - Natural gas: leakage abatement, the California Public Utilities Commission (CPUC) requests that the following information be transmitted to the CPUC and the State Air Resources Board (ARB):
Note - Definitions in Data Request Pacific Gas and Electric R15-01-008 2017 June Report
The following question in the above mentioned data request is answered using the spreadsheets in this Appendix (#3):(6) Calculable or estimated fugative emissions and non-graded gas leaks, as defined in Data Request Pacific Gas and Electric R15-01-008 2017 June Report.
Notes:
Use a formula-derived value with the formula used in the Annual Emissions column. Do not use a copy and paste-as-value.
At the end of Annual Emissions Column, add a summation total in a cell for a column total, and then highlight orange.The emissions captured on this tab represent the emissions associated with the operational design and function of the compressor. Any intentional release of natural gas for safety or maintenance purposes should be included on the Blowdowns worksheet.
Response:
Transmission Compressor Vented Emissions:
IDGeographic
Location
Compressor
Type
Prime
Mover
Number
of
Cylinders
Number
of
Seals
Seal
Type
Operating Mode:
Pressurized Operating
(hours)
Operating Mode:
Pressurized Idle
(hours)
Operating Mode:
Depressurized Idle
(hours)
Emission Factor:
Pressurized
Operating(scf/hr)
Emission Factor:
Pressurized Idle
(scf/hr)
Emission Factor:
Depressurized Idle
(scf/hr)
Annual
Emissions
(Mscf)
Explanatory Notes / Comments
Rev. 3/31/17
Pacific Gas and Electric
Rulemaking (R.) 15-01-008 to Adopt Rules and Procedures Governing Commission Regulated Natural Gas Pipelines and Facilities to Reduce Natural Gas Leaks Consistent with Senate Bill 1371, Leno.and In Response to Data Request Pacific Gas and Electric R15-01-008 2017 June Report
3/31/2017Appendix 3
SR-K-195403 R E 2 2 D
No measurement taken due to System not meeting GHG gas Mandatory reporting
Requirement
SR-K-295403 R E 2 2 D
No measurement taken due to System not meeting GHG gas Mandatory reporting
Requirement
BET K-1 94514 C E 1 D
No measurement taken due to System not meeting GHG gas Mandatory reporting
Requirement
BET K-2 94514 C E 1 D
No measurement taken due to System not meeting GHG gas Mandatory reporting
Requirement
Total 16,503.12
3-2
Pursuant to SB 1371, Leno - Natural gas: leakage abatement, the California Public Utilities Commission (CPUC) requests that the following information be transmitted to the CPUC and the State Air Resources Board (ARB):
Note - Definitions in Data Request [Pacific Gas and Electric] R15-01-008 2017 June Report
The following question in the above mentioned data request is answered using the spreadsheets in this Appendix (#3):(6) Calculable or estimated fugative emissions and non-graded gas leaks, as defined in Data Request [Pacific Gas and Electric] R15-01-008 2017 June Report.
Notes:
Use a formula-derived value with the formula used in the Annual Emissions column. Do not use a copy and paste-as-value.
At the end of Annual Emissions Column, add a summation total in a cell for a column total, and then highlight orange.
Response:
Transmission Compressor Fugitive Leaks:
IDGeographic
Location
Compressor
Type
Prime
Mover
Number
of
Cylinders
Number
of
Seals
Seal
Type
Operating Mode:
Pressurized Operating
(hours)
Operating Mode:
Pressurized Idle
(hours)
Operating Mode:
Depressurized Idle
(hours)
Emission Factor:
Pressurized
Operating(scf/hr)
Emission Factor:
Pressurized Idle
(scf/hr)
Emission Factor:
Depressurized Idle
(scf/hr)
Discovery Date
(MM/DD/YY)
Repair Date
(MM/DD/YY)
Number
of
Days Leaking
Annual
Emissions
(Mscf)
Explanatory Notes /
Comments
PG&E does not track emission associated with unintentional leaks at a Compressor level that if repaired would not be leaking. Leaks and Emission are tracked at the Component Level only
Sum Total - Provided as an example.
The emissions captured on this tab represent the emissions associated unintentional leaks that if repaired would not leaking. If the Compressor is releasing gas or "bleeding" as a result of
its design or function then it is not to be captured in this tab.
Pacific Gas and Electric
Rulemaking (R.) 15-01-008 to Adopt Rules and Procedures Governing Commission Regulated Natural Gas Pipelines and Facilities to Reduce Natural Gas Leaks Consistent with Senate Bill 1371, Leno.and In Response to Data Request [Pacific Gas and Electric] R15-01-008 2017 June Report
3/31/2017Appendix 3Rev. 3/31/17
3-3
Pursuant to SB 1371, Leno - Natural gas: leakage abatement, the California Public Utilities Commission (CPUC) requests that the following information be transmitted to the CPUC and the State Air Resources Board (ARB):
Note - Definitions in Data Request Pacific Gas and Electric R15-01-008 2017 June Report
The following question in the above mentioned data request is answered using the spreadsheets in this Appendix (#3):
(6) Calculable or estimated fugative emissions and non-graded gas leaks, as defined in Data Request Pacific Gas and Electric R15-01-008 2017 June Report.
Notes:
Use a formula-derived value with the formula used in the Annual Emissions column. Do not use a copy and paste-as-value.
At the end of Annual Emissions Column, add a summation total in a cell for a column total, and then highlight orange.
Response:
Transmission Compressor Station Blowdowns:
IDGeographic
Location
Number
of
Blowdown
Events
Annual
Emissions
(Mscf)
Explanatory Notes / Comments
TIO-STA 96015 3 1316.42
TIO-K-1 96015 12 325.67
BUR-STA 96013 4 1548.69
BUR-K-2 96013 10 307.68
GER-STA 96035 5 3038.53
GER-K-1 96035 18 1444.57
DEL-STA 95979 6 6073.35
DEL-K-1 95979 12 605.03
DEL-K-2 95979 12 603.84
DEL-K-3 95979 21 751.66
KET-STA 93204 2 1062.78
KET-K-1 93204 17 292.24
KET-K-2 93204 11 186.53
KET-K-3 93204 14 241.66
HIN-STA 92347 0 0.00
HIN-K-1 92347 15 103.19
HIN-K-2 92347 12 82.55
HIN-K-3 92347 12 82.55
HIN-K-4 92347 18 123.83
HIN-K-5 92347 13 89.43
HIN-K-6 92347 13 89.43
HIN-K-7 92347 8 55.04
HIN-K-8 92347 9 61.92
HIN-K-9 92347 9 61.92
HIN-K-10 92347 20 161.99
HIN-K-11 92347 16 708.15
HIN-K-12 92347 21 929.45
TOP-STA 92363 0 0.00
Rev. 3/31/17
Pacific Gas and Electric
Rulemaking (R.) 15-01-008 to Adopt Rules and Procedures Governing Commission Regulated Natural Gas Pipelines and Facilities to Reduce Natural Gas Leaks Consistent with Senate Bill 1371, Leno.and In Response to Data Request Pacific Gas and Electric R15-01-008 2017 June Report
3/31/2017Appendix 3
3-4
Pursuant to SB 1371, Leno - Natural gas: leakage abatement, the California Public Utilities Commission (CPUC) requests that the following information be transmitted to the CPUC and the State Air Resources Board (ARB):
Note - Definitions in Data Request Pacific Gas and Electric R15-01-008 2017 June Report
The following question in the above mentioned data request is answered using the spreadsheets in this Appendix (#3):
(6) Calculable or estimated fugative emissions and non-graded gas leaks, as defined in Data Request Pacific Gas and Electric R15-01-008 2017 June Report.
Notes:
Use a formula-derived value with the formula used in the Annual Emissions column. Do not use a copy and paste-as-value.
At the end of Annual Emissions Column, add a summation total in a cell for a column total, and then highlight orange.
Response:
Transmission Compressor Station Blowdowns:
IDGeographic
Location
Number
of
Blowdown
Events
Annual
Emissions
(Mscf)
Explanatory Notes / Comments
Rev. 3/31/17
Pacific Gas and Electric
Rulemaking (R.) 15-01-008 to Adopt Rules and Procedures Governing Commission Regulated Natural Gas Pipelines and Facilities to Reduce Natural Gas Leaks Consistent with Senate Bill 1371, Leno.and In Response to Data Request Pacific Gas and Electric R15-01-008 2017 June Report
3/31/2017Appendix 3
TOP-ADHOC 1 92363 1 325.63
TOP-ADHOC 2 92363 1 316.69
TOP-K-2 92363 16 160.92
TOP-K-3 92363 23 231.33
TOP-K-4 92363 12 120.69
TOP-K-5 92363 13 130.75
TOP-K-6 92363 19 191.10
TOP-K-7 92363 17 170.98
TOP-K-8 92363 9 90.52
TOP-K-9 92363 13 130.75
TOP-K-10 92363 11 138.41
SR-K-1
SR-K-2
BET-STA 94514 0 0 As of 3/31/17, V-9 status closed
BET-K1 94514 7 267 V-101 V-102 closed, V-103 or V-127 open
BET-K2 94514 3 108 V-201 V-202 closed, V-203 or V-227 open
Total 22,730.90
3-5
Pursuant to SB 1371, Leno - Natural gas: leakage abatement, the California Public Utilities Commission (CPUC) requests that the following information be transmitted to the CPUC and the State Air Resources Board (ARB):
Note - Definitions in Data Request Pacific Gas and Electric R15-01-008 2017 June Report
The following question in the above mentioned data request is answered using the spreadsheets in this Appendix (#3):(6) Calculable or estimated fugative emissions and non-graded gas leaks, as defined in Data Request Pacific Gas and Electric R15-01-008 2017 June Report.
Notes:
Use a formula-derived value with the formula used in the Annual Emissions column. Do not use a copy and paste-as-value.
At the end of Annual Emissions Column, add a summation total in a cell for a column total, and then highlight orange.
The emissions captured on this tab represent the emissions associated with the operational design and function of the component. Any intentional release of natural gas for safety or maintenance purposes should be included on the Blowdowns worksheet.
Response:
Transmission Compressor Station Component Vented Emissions:
IDGeographic
Location
Device
TypeBleed Rate Manufacturer
Engineering or
Manufacturer's based
Estimate of Emissions
Annual Emissions
(Mscf) Explanatory Notes / Comments
Tionesta Compressor Station - 13 96015 P I not readily available 0.0576 274.06 Estimated emissions = EF x 366 days x count of devices
Tionesta Compressor Station - 1 96015 P H not readily available 0.4457 163.13 Estimated emissions = EF x 366 days x count of devices
Burney Compressor Station - 14 96013 P I not readily available 0.0576 295.14 Estimated emissions = EF x 366 days x count of devicesBurney Compressor Station - 1 96013 P H not readily available 0.4457 163.13 Estimated emissions = EF x 366 days x count of devices
Gerber Compressor Station - 19 96035 P I not readily available 0.0576 400.55 Estimated emissions = EF x 366 days x count of devices
Gerber Compressor Station - 2 96035 P H not readily available 0.4457 326.25 Estimated emissions = EF x 366 days x count of devices
Delevan Compressor Station - 36 95979 P I not readily available 0.0576 758.94 Estimated emissions = EF x 366 days x count of devices
Delevan Compressor Station - 3 95979 P H not readily available 0.4457 489.38 Estimated emissions = EF x 366 days x count of devices
Kettleman Compressor Station - 38 93204 P I not readily available 0.0576 801.10 Estimated emissions = EF x 366 days x count of devices
Kettleman Compressor Station - 1 93204 P L not readily available 0.0336 12.30 Estimated emissions = EF x 366 days x count of devices
Hinkley Compressor Station - 35 92347 P I not readily available 0.0576 737.86 Estimated emissions = EF x 366 days x count of devices
Topock Compressor Station - 31 92363 P I not readily available 0.0576 653.53 Estimated emissions = EF x 366 days x count of devices
SANTA ROSA COMPRESSOR STATION 082485 PR Anderson Greenwood 0.0492 18.01 Estimated emissions = EF x 366 days
SANTA ROSA COMPRESSOR STATION 082485 PR Anderson Greenwood 0.0492 18.01 Estimated emissions = EF x 366 days
TOPOCK COMPRESSOR STATION 383655 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
TOPOCK COMPRESSOR STATION 383655 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
TOPOCK COMPRESSOR STATION 383655 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
TOPOCK COMPRESSOR STATION 383655 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
TOPOCK COMPRESSOR STATION 383655 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
TOPOCK COMPRESSOR STATION 383655 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
TOPOCK COMPRESSOR STATION 383655 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
TOPOCK COMPRESSOR STATION 383655 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
TOPOCK COMPRESSOR STATION 383655 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
TOPOCK COMPRESSOR STATION 383655 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
TOPOCK COMPRESSOR STATION 383655 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
TOPOCK COMPRESSOR STATION 383655 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
Kettleman Compressor Station 487667 PR Anderson Greenwood 0.0492 18.01 Estimated emissions = EF x 366 days
Kettleman Compressor Station 487667 PR Anderson Greenwood 0.0492 18.01 Estimated emissions = EF x 366 days
Kettleman Compressor Station 487667 PR Anderson Greenwood 0.0492 18.01 Estimated emissions = EF x 366 days
Kettleman Compressor Station 487667 PR U.S. Industries 0.0492 18.01 Estimated emissions = EF x 366 days
McDONALD ISLAND COMPRESSOR STATION 385179 PR AXELSON 0.0492 18.01 Estimated emissions = EF x 366 days
McDONALD ISLAND COMPRESSOR STATION 385179 PR AXELSON 0.0492 18.01 Estimated emissions = EF x 366 days
McDONALD ISLAND COMPRESSOR STATION 385179 PR AXELSON 0.0492 18.01 Estimated emissions = EF x 366 days
McDONALD ISLAND COMPRESSOR STATION 385179 PR AXELSON 0.0492 18.01 Estimated emissions = EF x 366 days
McDONALD ISLAND COMPRESSOR STATION 385179 PR AXELSON 0.0492 18.01 Estimated emissions = EF x 366 days
McDONALD ISLAND COMPRESSOR STATION 385179 PR AXELSON 0.0492 18.01 Estimated emissions = EF x 366 days
TIONESTA COMPRESSOR STATION 284541 PR USI-Axelson 0.0492 18.01 Estimated emissions = EF x 366 days
TIONESTA COMPRESSOR STATION 284541 PR USI-Axelson 0.0492 18.01 Estimated emissions = EF x 366 days
HINKLEY COMPRESSOR STATION 383654 PR Axelson 0.0492 18.01 Estimated emissions = EF x 366 days
Rev. 3/31/17
Pacific Gas and Electric
Rulemaking (R.) 15-01-008 to Adopt Rules and Procedures Governing Commission Regulated Natural Gas Pipelines and Facilities to Reduce Natural Gas Leaks Consistent with Senate Bill 1371, Leno.and In Response to Data Request Pacific Gas and Electric R15-01-008 2017 June Report
3/31/2017Appendix 3
3-6
Pursuant to SB 1371, Leno - Natural gas: leakage abatement, the California Public Utilities Commission (CPUC) requests that the following information be transmitted to the CPUC and the State Air Resources Board (ARB):
Note - Definitions in Data Request Pacific Gas and Electric R15-01-008 2017 June Report
The following question in the above mentioned data request is answered using the spreadsheets in this Appendix (#3):(6) Calculable or estimated fugative emissions and non-graded gas leaks, as defined in Data Request Pacific Gas and Electric R15-01-008 2017 June Report.
Notes:
Use a formula-derived value with the formula used in the Annual Emissions column. Do not use a copy and paste-as-value.
At the end of Annual Emissions Column, add a summation total in a cell for a column total, and then highlight orange.
The emissions captured on this tab represent the emissions associated with the operational design and function of the component. Any intentional release of natural gas for safety or maintenance purposes should be included on the Blowdowns worksheet.
Response:
Transmission Compressor Station Component Vented Emissions:
IDGeographic
Location
Device
TypeBleed Rate Manufacturer
Engineering or
Manufacturer's based
Estimate of Emissions
Annual Emissions
(Mscf) Explanatory Notes / Comments
Rev. 3/31/17
Pacific Gas and Electric
Rulemaking (R.) 15-01-008 to Adopt Rules and Procedures Governing Commission Regulated Natural Gas Pipelines and Facilities to Reduce Natural Gas Leaks Consistent with Senate Bill 1371, Leno.and In Response to Data Request Pacific Gas and Electric R15-01-008 2017 June Report
3/31/2017Appendix 3
HINKLEY COMPRESSOR STATION 383654 PR Axelson 0.0492 18.01 Estimated emissions = EF x 366 days
HINKLEY COMPRESSOR STATION 383654 PR Axelson 0.0492 18.01 Estimated emissions = EF x 366 days
HINKLEY COMPRESSOR STATION 383654 PR Axelson 0.0492 18.01 Estimated emissions = EF x 366 days
HINKLEY COMPRESSOR STATION 383654 PR Axelson 0.0492 18.01 Estimated emissions = EF x 366 days
HINKLEY COMPRESSOR STATION 383654 PR Axelson 0.0492 18.01 Estimated emissions = EF x 366 days
HINKLEY COMPRESSOR STATION 383654 PR Axelson 0.0492 18.01 Estimated emissions = EF x 366 days
HINKLEY COMPRESSOR STATION 383654 PR Axelson 0.0492 18.01 Estimated emissions = EF x 366 days
HINKLEY COMPRESSOR STATION 383654 PR Axelson 0.0492 18.01 Estimated emissions = EF x 366 days
HINKLEY COMPRESSOR STATION 383654 PR Axelson 0.0492 18.01 Estimated emissions = EF x 366 days
HINKLEY COMPRESSOR STATION 383654 PR Garrett 0.0492 18.01 Estimated emissions = EF x 366 days
HINKLEY COMPRESSOR STATION 383654 PR Garrett 0.0492 18.01 Estimated emissions = EF x 366 days
BURNEY COMPRESSOR STATION 284542 PR Anderson Greenwood 0.0492 18.01 Estimated emissions = EF x 366 days
BURNEY COMPRESSOR STATION 284542 PR Anderson Greenwood 0.0492 18.01 Estimated emissions = EF x 366 days
BURNEY COMPRESSOR STATION 284542 PR Anderson Greenwood 0.0492 18.01 Estimated emissions = EF x 366 days
Los Medanos Compressor Station 3807802 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
Los Medanos Compressor Station 3807802 PR Anderson Greenwood & Co 0.049218.01 Estimated emissions = EF x 366 days
Los Medanos Compressor Station 3807802 PR AGCO 0.0492 18.01 Estimated emissions = EF x 366 days
Los Medanos Compressor Station 3807802 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
Los Medanos Compressor Station 3807802 PR Anderson Greenwood 0.0492 18.01 Estimated emissions = EF x 366 days
Los Medanos Compressor Station 3807802 PR not readily available 0.0492 18.01 Estimated emissions = EF x 366 days
Los Medanos Compressor Station 3807802 PR Anderson Greenwood 0.0492 18.01 Estimated emissions = EF x 366 days
5,939.70
3-7
Pursuant to SB 1371, Leno - Natural gas: leakage abatement, the California Public Utilities Commission (CPUC) requests that the following information be transmitted to the CPUC and the State Air Resources Board (ARB):
Note - Definitions in Data Request Pacific Gas and Electric R15-01-008 2017 June Report
The following question in the above mentioned data request is answered using the spreadsheets in this Appendix (#3):
(6) Calculable or estimated fugative emissions and non-graded gas leaks, as defined in Data Request Pacific Gas and Electric R15-01-008 2017 June Report.
Notes:
Use a formula-derived value with the formula used in the Annual Emissions column. Do not use a copy and paste-as-value.
At the end of Annual Emissions Column, add a summation total in a cell for a column total, and then highlight orange.
Response:
Transmission Compressor Station Component Fugitive Leaks:
IDGeographic
Location
Device
TypeBleed Rate Manufacturer
Discovery Date
(MM/DD/YY)
Repair Date
(MM/DD/YY)
Number
of
Days Leaking
Emission Factor
(Mscf/day)
Annual Emissions
(Mscf)Explanatory Notes / Comments
Burney Compressor Station - 1 Compressor Components 196013 C N/A Not Readily Available 09/14/16 N/A 366 0.13416 49.10256
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Burney Compressor Station - 4 Non-Compressor Components 496013 V N/A Not Readily Available 09/14/16 N/A 366 0.1572 230.1408
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Burney Compressor Station - 1 Non-Compressor Components 196013 C N/A Not Readily Available 09/14/16 N/A 366 0.1399 51.2034
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Burney Compressor Station - 1 Non-Compressor Components 196013 PR N/A Not Readily Available 09/14/16 N/A 366 0.0492 18.0072
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Delevan Compressor Station - 10 Non-Compressor Components 1095979 V N/A Not Readily Available 09/20/16 N/A 366 0.1572 575.352
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Delevan Compressor Station - 3 Non-Compressor Components 395979 C N/A Not Readily Available 09/20/16 N/A 366 0.1399 153.6102
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Delevan Compressor Station - 1 Non-Compressor Components 195979 PR N/A Not Readily Available 09/16/16 N/A 366 0.0492 18.0072
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Delevan Compressor Station - 1 Non-Compressor Components 195979 M N/A Not Readily Available 09/20/16 N/A 366 0.0728 26.6448
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Gerber Compressor Station - 1 Non-Compressor Components 196035 V N/A Not Readily Available 09/15/16 N/A 366 0.1572 57.5352
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Hinkley Compressor Station - 2 Compressor Components 292347 C N/A Not Readily Available 11/15/16 N/A 366 0.13416 98.20512
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Hinkley Compressor Station - 26 Non-Compressor Components 2692347 V N/A Not Readily Available 11/15/16 N/A 366 0.1572 1495.9152
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Hinkley Compressor Station - 13 Non-Compressor Components 1392347 C N/A Not Readily Available 11/15/16 N/A 366 0.1399 665.6442
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Hinkley Compressor Station - 1 Non-Compressor Components 192347 O N/A Not Readily Available 10/12/16 N/A 366 0.276 101.016
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Hinkley Compressor Station - 12 Non-Compressor Components 1292347 M N/A Not Readily Available 10/12/16 N/A 366 0.0728 319.7376
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Kettleman Compressor Station - 2 Compressor Components 293204 V N/A Not Readily Available 08/16/16 N/A 366 0.35616 260.70912
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Kettleman Compressor Station - 1 Compressor Components 193204 C N/A Not Readily Available 08/16/16 N/A 366 0.13416 49.10256
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Kettleman Compressor Station - 2 Non-Compressor Components 293204 V N/A Not Readily Available 08/15/16 N/A 366 0.1572 115.0704
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Tionesta Compressor Station - 3 Non-Compressor Components 396015 V N/A Not Readily Available 09/22/16 N/A 366 0.1572 172.6056
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Tionesta Compressor Station - 1 Non-Compressor Components 196015 C N/A Not Readily Available 09/13/16 N/A 366 0.1399 51.2034
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Topock Compressor Station - 1 Compressor Components 192363 C N/A Not Readily Available 08/26/16 N/A 366 0.13416 49.10256
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Topock Compressor Station - 9 Non-Compressor Components 992363 V N/A Not Readily Available 08/25/16 N/A 366 0.1572 517.8168
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Topock Compressor Station - 7 Non-Compressor Components 792363 C N/A Not Readily Available 08/26/16 N/A 366 0.1399 358.4238
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
Topock Compressor Station - 2 Non-Compressor Components 292363 M N/A Not Readily Available 08/26/16 N/A 366 0.0728 53.2896
Leak detected during GHG leak survey pursuant to the GHG Mandatory Reporting Regulation.
The leak is assumed to be leaking the entire year.
total Mscf 5,487.45
The emissions captured on this tab represent the emissions associated unintentional leaks that if repaired would not leaking. If the component is releasing gas or "bleeding" as a result of its design or function then it is not to be captured in this tab.
Pacific Gas and Electric
Rulemaking (R.) 15-01-008 to Adopt Rules and Procedures Governing Commission Regulated Natural Gas Pipelines and Facilities to Reduce Natural Gas Leaks Consistent with Senate Bill 1371, Leno.and In Response to Data Request Pacific Gas and Electric R15-01-008 2017 June Report
3/31/2017Appendix 3Rev. 3/31/17
3-8
Pursuant to SB 1371, Leno - Natural gas: leakage abatement, the California Public Utilities Commission (CPUC) requests that the following information be transmitted to the CPUC and the State Air Resources Board (ARB):
Note - Definitions in Data Request Pacific Gas and Electric R15-01-008 2017 June Report
The following question in the above mentioned data request is answered using the spreadsheets in this Appendix (#3):
(6) Calculable or estimated fugative emissions and non-graded gas leaks, as defined in Data Request Pacific Gas and Electric R15-01-008 2017 June Report.
Notes:
Use a formula-derived value with the formula used in the Annual Emissions column. Do not use a copy and paste-as-value.
At the end of Annual Emissions Column, add a summation total in a cell for a column total, and then highlight orange.
Response:
Transmission Compressor Station Storage Tank Emissions:
Total NumberDiscovery Date
(DD/MM/YY)
Repair Date
(DD/MM/YY)
Number
of
Days Emitting
Emission
Factor
(Mscf/yr)
Annual
Emissions
(Mscf)
No leaks detected at the other compressor stations that have storage tanks on site: Kettleman and Topock Compressor Stations.
D-250 (Center Vent) 12/27/2016 N/A 366 5,138.64 5,138.64
Leak detected during GHG leak survey pursuant to the
GHG Mandatory Reporting Regulation. The leak is
assumed to be leaking the entire year.
D-250 (West Side Vent) 12/27/2016 N/A 366 5,138.64 5,138.64
Leak detected during GHG leak survey pursuant to the
GHG Mandatory Reporting Regulation. The leak is
assumed to be leaking the entire year.
Sum Total 10,277.28
Rev. 3/31/17
Pacific Gas and Electric
Rulemaking (R.) 15-01-008 to Adopt Rules and Procedures Governing Commission Regulated Natural Gas Pipelines and Facilities to Reduce Natural Gas Leaks Consistent with Senate Bill 1371, Leno.and In Response to Data Request Pacific Gas and Electric R15-01-008 2017 June Report
3/31/2017Appendix 3
3-9