71
P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations P1246™/D12 1 Draft Guide for Temporary Protective 2 Grounding Systems Used in 3 Substations 4 Sponsor 5 6 Substations Committee 7 of the 8 IEEE Power and Energy Society 9 10 11 Approved <Date Approved> 12 13 IEEE-SA Standards Board 14 15 Copyright © 2018 by The Institute of Electrical and Electronics Engineers, Inc. 16 Three Park Avenue 17 New York, New York 10016-5997, USA 18 All rights reserved. 19 This document is an unapproved draft of a proposed IEEE Standard. As such, this document is subject to 20 change. USE AT YOUR OWN RISK! IEEE copyright statements SHALL NOT BE REMOVED from draft 21 or approved IEEE standards, or modified in any way. Because this is an unapproved draft, this document 22 must not be utilized for any conformance/compliance purposes. Permission is hereby granted for officers 23 from each IEEE Standards Working Group or Committee to reproduce the draft document developed by 24 that Working Group for purposes of international standardization consideration. IEEE Standards 25 Department must be informed of the submission for consideration prior to any reproduction for 26 international standardization consideration ([email protected]). Prior to adoption of this document, in 27 whole or in part, by another standards development organization, permission must first be obtained from 28 the IEEE Standards Department ([email protected]). When requesting permission, IEEE Standards 29 Department will require a copy of the standard development organization's document highlighting the use 30 of IEEE content. Other entities seeking permission to reproduce this document, in whole or in part, must 31 also obtain permission from the IEEE Standards Department. 32 IEEE Standards Department 33 445 Hoes Lane 34 Piscataway, NJ 08854, USA 35 36

P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

P1246™/D12 1

Draft Guide for Temporary Protective 2

Grounding Systems Used in 3

Substations 4

Sponsor 5 6 Substations Committee 7 of the 8 IEEE Power and Energy Society 9 10 11 Approved <Date Approved> 12 13 IEEE-SA Standards Board 14 15

Copyright © 2018 by The Institute of Electrical and Electronics Engineers, Inc. 16 Three Park Avenue 17 New York, New York 10016-5997, USA 18

All rights reserved. 19

This document is an unapproved draft of a proposed IEEE Standard. As such, this document is subject to 20 change. USE AT YOUR OWN RISK! IEEE copyright statements SHALL NOT BE REMOVED from draft 21 or approved IEEE standards, or modified in any way. Because this is an unapproved draft, this document 22 must not be utilized for any conformance/compliance purposes. Permission is hereby granted for officers 23 from each IEEE Standards Working Group or Committee to reproduce the draft document developed by 24 that Working Group for purposes of international standardization consideration. IEEE Standards 25 Department must be informed of the submission for consideration prior to any reproduction for 26 international standardization consideration ([email protected]). Prior to adoption of this document, in 27 whole or in part, by another standards development organization, permission must first be obtained from 28 the IEEE Standards Department ([email protected]). When requesting permission, IEEE Standards 29 Department will require a copy of the standard development organization's document highlighting the use 30 of IEEE content. Other entities seeking permission to reproduce this document, in whole or in part, must 31 also obtain permission from the IEEE Standards Department. 32

IEEE Standards Department 33 445 Hoes Lane 34 Piscataway, NJ 08854, USA 35

36

Page 2: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Abstract: <Select this text and type or paste Abstract—contents of the Scope may be used> 1 2 Keywords: <Select this text and type or paste keywords> 3 4

5

The Institute of Electrical and Electronics Engineers, Inc. 3 Park Avenue, New York, NY 10016-5997, USA Copyright © 2018 by The Institute of Electrical and Electronics Engineers, Inc. All rights reserved. Published <Date Published>. Printed in the United States of America. IEEE is a registered trademark in the U.S. Patent & Trademark Office, owned by The Institute of Electrical and Electronics Engineers, Incorporated. PDF: ISBN 978-0-XXXX-XXXX-X STDXXXXX Print: ISBN 978-0-XXXX-XXXX-X STDPDXXXXX IEEE prohibits discrimination, harassment, and bullying. For more information, visit http://www.ieee.org/web/aboutus/whatis/policies/p9-26.html. No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior written permission of the publisher.

Page 3: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Important Notices and Disclaimers Concerning IEEE Standards Documents 1

IEEE documents are made available for use subject to important notices and legal disclaimers. These 2 notices and disclaimers, or a reference to this page, appear in all standards and may be found under the 3 heading “Important Notices and Disclaimers Concerning IEEE Standards Documents.” They can also be 4 obtained on request from IEEE or viewed at http://standards.ieee.org/IPR/disclaimers.html. 5

Notice and Disclaimer of Liability Concerning the Use of IEEE Standards 6 Documents 7

IEEE Standards documents (standards, recommended practices, and guides), both full-use and trial-use, are 8 developed within IEEE Societies and the Standards Coordinating Committees of the IEEE Standards 9 Association (“IEEE-SA”) Standards Board. IEEE (“the Institute”) develops its standards through a 10 consensus development process, approved by the American National Standards Institute (“ANSI”), which 11 brings together volunteers representing varied viewpoints and interests to achieve the final product. IEEE 12 Standards are documents developed through scientific, academic, and industry-based technical working 13 groups. Volunteers in IEEE working groups are not necessarily members of the Institute and participate 14 without compensation from IEEE. While IEEE administers the process and establishes rules to promote 15 fairness in the consensus development process, IEEE does not independently evaluate, test, or verify the 16 accuracy of any of the information or the soundness of any judgments contained in its standards. 17

IEEE Standards do not guarantee or ensure safety, security, health, or environmental protection, or ensure 18 against interference with or from other devices or networks. Implementers and users of IEEE Standards 19 documents are responsible for determining and complying with all appropriate safety, security, 20 environmental, health, and interference protection practices and all applicable laws and regulations. 21

IEEE does not warrant or represent the accuracy or content of the material contained in its standards, and 22 expressly disclaims all warranties (express, implied and statutory) not included in this or any other 23 document relating to the standard, including, but not limited to, the warranties of: merchantability; fitness 24 for a particular purpose; non-infringement; and quality, accuracy, effectiveness, currency, or completeness 25 of material. In addition, IEEE disclaims any and all conditions relating to: results; and workmanlike effort. 26 IEEE standards documents are supplied “AS IS” and “WITH ALL FAULTS.” 27

Use of an IEEE standard is wholly voluntary. The existence of an IEEE standard does not imply that there 28 are no other ways to produce, test, measure, purchase, market, or provide other goods and services related 29 to the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a standard is approved 30 and issued is subject to change brought about through developments in the state of the art and comments 31 received from users of the standard. 32

In publishing and making its standards available, IEEE is not suggesting or rendering professional or other 33 services for, or on behalf of, any person or entity nor is IEEE undertaking to perform any duty owed by any 34 other person or entity to another. Any person utilizing any IEEE Standards document, should rely upon his 35 or her own independent judgment in the exercise of reasonable care in any given circumstances or, as 36 appropriate, seek the advice of a competent professional in determining the appropriateness of a given 37 IEEE standard. 38

IN NO EVENT SHALL IEEE BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, 39 EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO: 40 PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; 41 OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, 42 WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR 43 OTHERWISE) ARISING IN ANY WAY OUT OF THE PUBLICATION, USE OF, OR RELIANCE 44 UPON ANY STANDARD, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE AND 45 REGARDLESS OF WHETHER SUCH DAMAGE WAS FORESEEABLE. 46

Page 4: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Translations 1

The IEEE consensus development process involves the review of documents in English only. In the event 2 that an IEEE standard is translated, only the English version published by IEEE should be considered the 3 approved IEEE standard. 4

Official statements 5

A statement, written or oral, that is not processed in accordance with the IEEE-SA Standards Board 6 Operations Manual shall not be considered or inferred to be the official position of IEEE or any of its 7 committees and shall not be considered to be, or be relied upon as, a formal position of IEEE. At lectures, 8 symposia, seminars, or educational courses, an individual presenting information on IEEE standards shall 9 make it clear that his or her views should be considered the personal views of that individual rather than the 10 formal position of IEEE. 11

Comments on standards 12

Comments for revision of IEEE Standards documents are welcome from any interested party, regardless of 13 membership affiliation with IEEE. However, IEEE does not provide consulting information or advice 14 pertaining to IEEE Standards documents. Suggestions for changes in documents should be in the form of a 15 proposed change of text, together with appropriate supporting comments. Since IEEE standards represent a 16 consensus of concerned interests, it is important that any responses to comments and questions also receive 17 the concurrence of a balance of interests. For this reason, IEEE and the members of its societies and 18 Standards Coordinating Committees are not able to provide an instant response to comments or questions 19 except in those cases where the matter has previously been addressed. For the same reason, IEEE does not 20 respond to interpretation requests. Any person who would like to participate in revisions to an IEEE 21 standard is welcome to join the relevant IEEE working group. 22

Comments on standards should be submitted to the following address: 23

Secretary, IEEE-SA Standards Board 24

445 Hoes Lane 25

Piscataway, NJ 08854 USA 26

Laws and regulations 27

Users of IEEE Standards documents should consult all applicable laws and regulations. Compliance with 28 the provisions of any IEEE Standards document does not imply compliance to any applicable regulatory 29 requirements. Implementers of the standard are responsible for observing or referring to the applicable 30 regulatory requirements. IEEE does not, by the publication of its standards, intend to urge action that is not 31 in compliance with applicable laws, and these documents may not be construed as doing so. 32

Copyrights 33

IEEE draft and approved standards are copyrighted by IEEE under U.S. and international copyright laws. 34 They are made available by IEEE and are adopted for a wide variety of both public and private uses. These 35 include both use, by reference, in laws and regulations, and use in private self-regulation, standardization, 36 and the promotion of engineering practices and methods. By making these documents available for use and 37 adoption by public authorities and private users, IEEE does not waive any rights in copyright to the 38 documents. 39

40

Page 5: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

1

Photocopies 2

Subject to payment of the appropriate fee, IEEE will grant users a limited, non-exclusive license to 3 photocopy portions of any individual standard for company or organizational internal use or individual, 4 non-commercial use only. To arrange for payment of licensing fees, please contact Copyright Clearance 5 Center, Customer Service, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission 6 to photocopy portions of any individual standard for educational classroom use can also be obtained 7 through the Copyright Clearance Center. 8

Updating of IEEE Standards documents 9

Users of IEEE Standards documents should be aware that these documents may be superseded at any time 10 by the issuance of new editions or may be amended from time to time through the issuance of amendments, 11 corrigenda, or errata. A current IEEE document at any point in time consists of the current edition of the 12 document together with any amendments, corrigenda, or errata then in effect. 13

Every IEEE standard is subjected to review at least every ten years. When a document is more than ten 14 years old and has not undergone a revision process, it is reasonable to conclude that its contents, although 15 still of some value, do not wholly reflect the present state of the art. Users are cautioned to check to 16 determine that they have the latest edition of any IEEE standard. 17

In order to determine whether a given document is the current edition and whether it has been amended 18 through the issuance of amendments, corrigenda, or errata, visit IEEE Xplore at http://ieeexplore.ieee.org/ 19 or contact IEEE at the address listed previously. For more information about the IEEE-SA or IEEE’s 20 standards development process, visit the IEEE-SA Website at http://standards.ieee.org. 21

Errata 22

Errata, if any, for all IEEE standards can be accessed on the IEEE-SA Website at the following URL: 23 http://standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata 24 periodically. 25

Patents 26

Attention is called to the possibility that implementation of this standard may require use of subject matter 27 covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to 28 the existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant 29 has filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the 30 IEEE-SA Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may 31 indicate whether the Submitter is willing or unwilling to grant licenses under patent rights without 32 compensation or under reasonable rates, with reasonable terms and conditions that are demonstrably free of 33 any unfair discrimination to applicants desiring to obtain such licenses. 34

Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not 35 responsible for identifying Essential Patent Claims for which a license may be required, for conducting 36 inquiries into the legal validity or scope of Patents Claims, or determining whether any licensing terms or 37 conditions provided in connection with submission of a Letter of Assurance, if any, or in any licensing 38 agreements are reasonable or non-discriminatory. Users of this standard are expressly advised that 39 determination of the validity of any patent rights, and the risk of infringement of such rights, is entirely 40 their own responsibility. Further information may be obtained from the IEEE Standards Association. 41

Page 6: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

6

Participants 1

At the time this draft guide was completed, the E4 Working Group had the following membership: 2

Jesse Rorabaugh, Chair 3 David Lane Garrett, Vice Chair 4

5 Participant1 6 Participant2 7 Participant3 8

Participant4 9 Participant5 10 Participant6 11

Participant7 12 Participant8 13 Participant9 14

15

The following members of the <individual/entity> balloting committee voted on this guide. Balloters may 16 have voted for approval, disapproval, or abstention. 17

[To be supplied by IEEE] 18

Balloter1 19 Balloter2 20 Balloter3 21

Balloter4 22 Balloter5 23 Balloter6 24

Balloter7 25 Balloter8 26 Balloter9 27

28

When the IEEE-SA Standards Board approved this guide on <Date Approved>, it had the following 29 membership: 30

[To be supplied by IEEE] 31

<Name>, Chair 32 <Name>, Vice Chair 33 <Name>, Past Chair 34

Konstantinos Karachalios, Secretary 35

SBMember1 36 SBMember2 37 SBMember3 38

SBMember4 39 SBMember5 40 SBMember6 41

SBMember7 42 SBMember8 43 SBMember9 44

*Member Emeritus 45 46

Page 7: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

vii

Introduction 1

This introduction is not part of P1246/D12, Draft Guide for Temporary Protective Grounding Systems Used in 2 Substations. 3

Practices for applying temporary protective grounds (TPGs) in substations vary from company to company. 4 These practices have come from a number of documents such as ASTM F855, IEC 61230, and IEEE Std 5 1048TM, as well as from field experience derived from line maintenance practices. This guide was 6 developed to consolidate into one document all the necessary information for the company to develop 7 sound personnel safety grounding practices in substations. The guide provides information on the physical 8 construction, application, and testing of TPGs as they are used in substations. 9

This revision emphasizes the electromechanical forces present with high short-circuit currents and with 10 high current offset (asymmetry). In recent tests, these forces were found to have significant impact on the 11 ability of a complete TPG assembly, including attachment points, to successfully handle these high short-12 circuit currents. It also introduces a new method for determining the TPG impedance (length and cable 13 size) for use in determining the current through the worker for an accidental energization. 14

Page 8: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

viii

Contents 1

1. Overview .................................................................................................................................................... 1 2 1.1 Scope ................................................................................................................................................... 1 3 1.2 Purpose ................................................................................................................................................ 1 4

2. Normative references .................................................................................................................................. 1 5

3. Definitions .................................................................................................................................................. 2 6

4. Considerations for temporary protective grounding systems ..................................................................... 3 7 4.1 General TPG ........................................................................................................................................ 3 8 4.2 General TPG ........................................................................................................................................ 3 9 4.3 Current magnitude and duration .......................................................................................................... 3 10 4.4 Special areas of concern ...................................................................................................................... 5 11 4.5 TPG cable assemblies .......................................................................................................................... 7 12 4.6 TPG cable ............................................................................................................................................ 7 13 4.7 Clamps ............................................................................................................................................... 12 14 4.8 Multiple assemblies ........................................................................................................................... 13 15 4.9 Attachment Points .............................................................................................................................. 15 16 4.10 Cable extensions .............................................................................................................................. 15 17

5. Application ............................................................................................................................................... 16 18 5.1 General .............................................................................................................................................. 16 19 5.2 Location of the TPGs ......................................................................................................................... 17 20 5.3 Ratings and selections........................................................................................................................ 19 21 5.4 Methods ............................................................................................................................................. 23 22

6. Installation and removal ........................................................................................................................... 23 23 6.1 General procedures ............................................................................................................................ 23 24 6.2 Tools .................................................................................................................................................. 24 25 6.3 Testing for voltage ............................................................................................................................. 25 26 6.4 Placing and removing of TPG’s......................................................................................................... 25 27 6.5 Equipment grounding ........................................................................................................................ 26 28

7. Minimizing static and capacitively coupled voltage on personnel ........................................................... 27 29 7.1 Protective garments ........................................................................................................................... 27 30 7.2 Attachments ....................................................................................................................................... 27 31

8. Testing ...................................................................................................................................................... 28 32 8.1 New TPG component and assembly testing ...................................................................................... 28 33 8.2 In-service inspection, maintenance and testing TPG’s ...................................................................... 28 34

Annex A (informative) Bibliography ........................................................................................................... 30 35

Annex B (normative) Terminology .............................................................................................................. 32 36 B.1 Voltage and currents at the worksite ................................................................................................. 32 37 B.2 Safety criteria .................................................................................................................................... 35 38

Annex C (normative) TPG Impedance Correction Factors .......................................................................... 38 39 C.1 Development of TPG impedance K factor ........................................................................................ 38 40 C.2 Application of TPG impedance K factors ......................................................................................... 44 41 C.3 TPG impedance K factor curves ....................................................................................................... 46 42

Page 9: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

ix

C.4 TPG reactance terms for calculation of Zg and K factor ................................................................... 60 1 2

Page 10: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

1

Draft Guide for Temporary Protective 1

Grounding Systems Used in 2

Substations 3

1. Overview 4

1.1 Scope 5

This guide covers the design, performance, use, testing, and installation of temporary protective grounding 6 (TPG) systems, including the connection points, as used in permanent and mobile substations. 7

1.2 Purpose 8

This guide suggests good practices, technical information, and safety criteria to assist in the selection and 9 application of temporary protective grounding systems, including the connection points, as used in 10 permanent and mobile substations. 11

12

2. Normative references 13

The following referenced documents are indispensable for the application of this document (i.e., they must 14 be understood and used, so each referenced document is cited in text and its relationship to this document is 15 explained). For dated references, only the edition cited applies. For undated references, the latest edition of 16 the referenced document (including any amendments or corrigenda) applies. 17

ASTM F855, Standard Specifications for Temporary Protective Grounds to be used on De-Energized 18 Electrical Power Lines and Equipment.1 19

ASTM F2249, Standard Specification for In-Service Test Methods for Temporary Grounding 20

1 ASTM publications are available from the American Society for Testing and Materials, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959, USA (http://www.astm.org/).

Page 11: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

2

IEC 60245-2, Rubber Insulated Cables of Rated Voltages Up To and Including 450/750 V—Part 2: Test 1 Methods. 2

IEC 61230, Live Working—Portable Equipment for Earthing or Earthing and Short-Circuiting. 3

IEEE Std 80TM, IEEE Guide for Safety in AC Substation Grounding. 2,3 4

IEEE Std 1048TM, IEEE Guide for Protective Grounding of Power Lines. 5

6

7

8

3. Definitions 9

For the purposes of this document, the following terms and definitions apply. The IEEE Standards 10 Dictionary Online should be consulted for terms not defined in this clause. 4 11

Bracket grounding: The location of temporary protective grounds (TPGs) on all sides of a worksite. The 12 location of the TPGs can be immediately adjacent to or some distance from the worksite. 13

Cluster ground assembly: A preassembled set of four cable or bar assemblies, with three phase 14 connections and one ground connection, all terminating at a common (cluster) point. 15

Continuity: A continuous, unbroken electrical circuit. For the purposes of temporary protective grounding, 16 any device capable of transforming voltage or producing a significant voltage drop cannot be considered as 17 maintaining continuity. Examples include transformers, fuses, reactors, resistors, circuit breakers, and line 18 traps. 19

Equipotential zone (equipotential grounding): A general term used to describe the application of 20 temporary protective grounds to limit the potential across the worker’s body. It is often associated with 21 worksite or single-point grounding, but also includes other applications of temporary grounding. 22

Ground potential rise (GPR): The maximum voltage that a station-grounding grid can attain relative to a 23 distant grounding point assumed to be at the potential of remote earth. 24

Multipoint grounding: The application of TPGs on either side of the worksite (see bracket grounds), plus 25 TPGs at the worksite (see worksite grounding). 26

2 IEEE publications are available from the Institute of Electrical and Electronics Engineers, 445 Hoes Lane, Piscataway, NJ 08854, USA (http://www.standards.ieee.org/).

3 The IEEE standards or products referred to in Clause 2 are trademarks owned by the Institute of Electrical and Electronics Engineers, Inc.

4IEEE Standards Dictionary Online is available at: http://dictionary.ieee.org

.

Page 12: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

3

Phase-to-ground (parallel) grounding: The installation of temporary protective grounds from each phase 1 to ground. The ground attachment point can be a common point for all three TPG ground connections or 2 can be a different point for one or more TPG ground connections, but a low-resistance connection between 3 any separated TPG ground connection points is required. 4

Phase-to-phase (chain) grounding: The installation of temporary protective grounds from phase to phase 5 to phase with an additional TPG connecting from one of the three phases to ground. 6

Source grounding: The location of TPGs so that a set of temporary protective grounds is between the 7 worksite and all possible sources of current. 8

Temporary protective ground equipment (TPG): Devices to limit the voltage difference between any 9 two accessible points at the worksite to an appropriate value for safety, and having sufficient current 10 withstand rating. These typically consist of cable assemblies, grounding switches, or temporarily installed 11 bars. 12

Ultimate rating (capacity): A calculated maximum symmetrical current that a temporary protective 13 ground cable is capable of carrying for a specified time without fusing or melting. When TPG assemblies 14 are exposed to currents that are close to the ultimate rating of the cable, they might be damaged. Some 15 companies replace TPGs subjected to any known current from an accidental energization. 16

Worksite (single-point) grounding: The application of temporary protective grounds only in the 17 immediate vicinity of an electrically continuous worksite. The location of the TPGs must be close enough 18 to the worksite to prevent a hazardous difference in potential across a worker at the worksite. 19

4. Considerations for temporary protective grounding systems 20

4.1 General TPG 21

Temporary protective ground equipment is used when grounding a substation power bus and equipment to 22 protect personnel from high voltages that can be induced or applied because of equipment failure or 23 operating error. The TPGs can be properly sized and assembled to protect personnel from injury during a 24 steady state or abnormal power system operation. This is accomplished by creating a short circuit (using the 25 TPGs) to de-energize the circuit as soon as possible while also minimizing the exposure voltage at the 26 worker. 27

4.2 General TPG 28

TPG assemblies are applicable for both mobile and permanent substations. 29

4.3 Current magnitude and duration 30

The current magnitude and duration of the short circuit current are critical factors in sizing TPGs. The 31 protective ground is sized to conduct the maximum available short circuit current at the short circuit 32 location without failure for the duration of the short circuit 33

Page 13: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

4

4.3.1 Current magnitude including dc offset 1

The current magnitude is one of the critical factors to be considered when sizing temporary protective 2 grounding systems. The short circuit current consists of an rms ac component and a dc offset current 3 component. The rms ac component is determined by the subtransient impedances of the rotating machinery, 4 the impedance of transformers, and the impedance of lines. The dc-offset component is determined by the 5 X/R ratio at the short circuit location looking back into the power system and the time of short circuit 6 initiation on the voltage waveform. 7

Analytical studies indicate that when full dc offsets occur in the locations with high X/R ratios (such as 8 close to a generating plant or a large transmission substation), the short duration (6 to 60 cycles) fusing 9 current ratings of grounding cables calculated using Onderdonk’s equation as considered in ASTM F855 10 might not be conservative. The additional heating from the dc current component reduces the cable current-11 carrying capability. The cable symmetrical current-carrying capability for the six-cycle rating is reduced 12 approximately 28% when the X/R ratio is changed from X/R =40 to X/R =0 as shown in Table 2 and Table 13 5, respectively. 14

At or near large generating plants and transmission substations, a large X/R ratio is likely since the 15 impedance of generators and transformers contains very little resistance. While in extreme cases the X/R 16 ratio can be as high as 50, under most circumstances the X/R ratio does not exceed 40 within the 17 substations. Several miles away from the substation, the X/R ratio is dominated by the impedance of the 18 line. The overall X/R ratio in such cases can be determined from the line’s X/R ratio. The typical range of 19 X/R ratios for lines are from 2 to 20 depending on the conductor configuration. A single small conductor 20 line will have a low X/R ratio while a bundled large conductor line will have a higher X/R ratio. 21

In addition to the effects on fusing current, the X/R ratio and dc offset can produce extremely high current 22 peaks in the first few cycles relative to the rms current. While the current peaks are proportional to the X/R 23 ratio, the rate of decay is inversely proportional to the X/R ratio. The slowly decaying high current peaks, 24 corresponding to higher X/R ratios, create the most severe electromechanical forces, which can destroy the 25 TPG assembly long before it fails thermally. In such a case, the worker would be without protection for a 26 longer duration before the short circuit clears. IEC 61230 requires temporary grounding (earthing) devices 27 to withstand a peak asymmetrical current of 2.5 times the rms current value. 28

4.3.2 Short circuit duration including primary and backup relaying 29

The short circuit duration is another critical factor to be considered when sizing protective grounds. The 30 short circuit duration is the time required to clear the short circuit by primary or backup relaying. The short 31 circuit clearing time is the sum of relay and breaker operation times. Primary relaying is the first line of 32 defense to clear a short circuit at high speed. Utilizing the primary relay short circuit clearing time 33 minimizes the grounding cable size: however, before relying on the primary relay operation to size the 34 protective grounds consider the reliability of the relays. Many circuits are protected by slower-clearing 35 fuses that can take many cycles or even seconds to interrupt the current. 36

Backup protection is provided for possible failure in the primary protection system or for possible failure of 37 the circuit breaker or other protective device. Remote backup and local backup are two forms of backup 38 protection in common use on power systems. In remote backup protection, short circuits s are cleared from 39 the system, one substation away from where the short circuit has occurred. In local backup protection, short 40 circuits are cleared locally in the same substation where the short circuit has occurred. Local backup 41 protection will clear the short circuit from the system in less time than that provided by remote backup 42 protection. Utilizing the backup protection short circuit clearing time provides a conservatively sized 43 protective ground. If more than one relay operates to clear a short circuit on the system, the total time 44 required for the last relay to operate determines the backup clearing time. For example, local breaker failure 45 can add from 8 to 12 cycles to the primary clearing time. Zone 2 or remote backup relaying can add from 46 12 to 24 cycles to the primary clearing time. Backup protection from fuses can add seconds to the primary 47 clearing time. Table 1 gives example ranges of clearing times for different protection schemes. Each 48

Page 14: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

5

company evaluates the primary and backup relay short circuit clearing times on their power system and 1 determines the short circuit clearing time to use for sizing the protective ground. 2

Table 1 Typical fault clearing times for various substation bus protection schemes 3

Bus protection scheme type Typical clearing time

(cycles)

Busses with differential protection 2–8 Busses without differential protection 12-60

Busses cleared remotely 20-90 Busses with fused primary protection 60-300

4

4.3.3 Circuit breaker re-closure considerations 5

Tests (EPRI EL-5258 [A8]) have indicated that the cooling of TPGs between re-closures is insignificant. If 6 the re-closing scheme is not disabled, the additional short circuit duration after re-closure(s) can be 7 included in the total time used to size the TPG. 8

4.4 Special areas of concern 9

4.4.1 General 10

For TPGs to provide proper protection continuity must be maintained between the point of connection and 11 the work location. Any device capable of transforming voltage or producing a voltage drop, not to be 12 considered as maintaining continuity for the purpose of personnel safety. Such devices include 13 transformers, fuses, reactors, resistors, and circuit breakers, disconnect switches and line traps. 14

Subclauses 4.4.2 through 4.4.6 are used when planning installation of TPGs on major equipment in 15 substations. 16

4.4.2 Main power transformers 17

Considerations when applying TPGs: 18

a) The turn ratio of many transformers makes them capable of transforming low voltages to high 19

voltages, even when they are not connected to the normal power source. These normally low 20

voltages can come from continuity checking instruments, insulation checking apparatus, and 21

electric arc welders. 22

b) Shorting of current transformer (CT) secondary leads, and opening of disconnect switches or 23

removal of fuses located in voltage transformer (VT) secondary leads. 24

c) During oil handling, the oil storage tank, the hose, the filtering, and pumping equipment can be 25

bonded together with the transformer tank being filled to minimize electric potentials on the 26

Page 15: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

6

equipment. Not only can the hose pick up an induced current, but also the oil flowing in the hose 1

can build up a static charge, unless prevented. 2

d) Ground all terminals (windings). 3

4.4.3 Circuit breakers and circuit switchers 4

The TPG assemblies are applied on both sides of the device when maintaining circuit breakers, circuit 5 switchers, or other devices that can have a circuit disconnection not visible to the worker. Consider the 6 following: 7

a) Shorting of circuit breaker bushing CT secondary leads. 8

b) Applying a TPG assembly between the breaker and its free standing CTs in order to prevent 9

creation of an electrical loop that can cause circulating current and spurious operation of protective 10

devices. 11

4.4.4 Instrument and substation service transformer 12

Voltage and substation service transformers, because of their very high turns ratio, are extremely hazardous 13 if they are hooked up to electrical equipment in such a way as to allow the applied voltages to be backfed. 14 Backfeeding could cause a severe electric shock to personnel who come in contact with any of the 15 connected circuits anywhere in the substation yard. Opening secondary disconnect switches and removing 16 fuses minimizes the hazards from secondary backfeed. 17

4.4.5 Capacitor banks 18

Substation capacitor banks retain stored charge even if the power source has been disconnected. After 19 allowing for self-discharge (typically 5 min), the de-energized capacitor bank can be fully discharged by 20 the application of a grounded short circuit across its terminal. In a capacitor bank comprised of two or more 21 parallel groups of series strings of units, each series group that is within reach can have a TPG connected 22 across the entire string, and each individual unit of a series string that is within reach can be shorted by 23 temporarily touching a wire across the unit terminals to provide full discharge. Similarly, in a capacitor 24 bank comprised of two or more series groups of parallel units, each parallel group that is within reach can 25 be have a TPG installed across the parallel group, and each individual unit that is within reach can be 26 shorted by temporarily touching a wire across the unit terminals or from a single terminal to ground to 27 provide full discharge. 28

4.4.6 Power cables and terminations 29

Before cutting the power cable, apply TPGs at each end of the power cable to dissipate capacitive energy. 30 To assist in grounding TPG attachment points may be installed at both ends of the cable in a fashion where 31 the TPGs can remain connected to the cable after the phase conductor is disconnected from the terminal. 32

4.4.7 Remote ground electrodes 33

Connecting TPGs to a remote ground electrode can significantly increase the exposure voltage at the 34 worksite. This is can happen if TPGs are connected to ground rods or a remote substation instead of to the 35

Page 16: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

7

substation ground grid where the work is being performed. When this is done the exposure voltage can be 1 up to the entire ground potential rise of that remote electrode. 2

4.5 TPG cable assemblies 3

The TPG cable assemblies typically consist of a combination of cable and ground clamps configured for 4 connecting the phase conductors or equipment to a substation grounding system. TPG cable assemblies are 5 appropriately sized and configured to survive the available short circuit current exposure. Refer to ASTM 6 F855,Table 1 and Table 2 for selecting the appropriate TPG cable assemblies based on the short circuit 7 clearing time, available short circuit current, and X/R ratio for thermal and electromechanical 8 considerations. 9

A TPG cable assembly consists of: 10

a) Ground end. The ground end consists of a clamp (to be connected to a grounded structure or to a 11

ground grid riser, a cable termination, and possibly heat-shrinkable tubing to seal exposed cable 12

strands. 13

b) Flexible conductor with a suitable jacket. 14

c) Source end. The source end consists of a clamp (typically with an ‘‘eye’’ for handling and 15

tightening) to be connected with the insulating stick to a de-energized conductor, bus, or an 16

attachment stud, a cable termination, and (possibly) heat-shrinkable tubing to seal exposed cable 17

strands. 18

There are multiple manufacturers that make specific TPG assemblies and components. For more details 19

refer to the manufacturer’s literature and 4.7.1. 20

4.6 TPG cable 21

4.6.1 Conductor material 22

Fine stranded copper conductors are used for temporary protective ground cables. (See section 4.6.4.) The 23 diameters of the strands are generally specified by the manufacturer or by the appropriate standard. 24 Inspection and testing ensures compliance with the cable material requirements. Check the electrical 25 resistance of the conductors at 20°C by the test given in IEC 60227- 2 [A2] and IEC 60245-2 [A3]. 26

4.6.2 Sizing protective ground cables 27

The rating of the cable is a key component of sizing the TPG cable assembly. For cables rated for low 28 current asymmetry, ASTM F855 defines grades 1-7 based on a withstand rating that is 70 to 80% of the 29 ultimate capacity. ASTM F855 defines ratings for grades 1H-7H for high current asymmetry applications 30 based on a percentage of the cable’s ultimate capacity. IEC 61230 only describes test procedures, with the 31 test assembly being rated at the tested current value (i.e., it does not refer to either the ultimate or withstand 32 rating of the cable). 33

Page 17: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

8

When selecting a cable for high current asymmetry, the dc-offset current should be considered, as it 1 considerably reduces the capacity of cables for short durations. For added safety, some companies use the 2 ultimate capacity and replace the assembly after exposure to an accidental energization. Tables 2 through 5 3 list the ultimate equivalent symmetrical current-carrying capability of cables for a worst-case dc offset for 4 X/R ratios of 40, 20, 10, and 0, respectively. Sizing TPG cable assemblies based on cable ampacity, alone, 5 may result in unexpected failures. Refer to section 4.5 for discussion of proper TPG assembly sizing. 6

7

Page 18: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

9

1

Table 2 Ultimate equivalent symmetrical current-carrying capabilities of copper grounding 2 cables (currents are rms values, for frequency of 60 Hz; X/R = 40; current in kA) 3

Cable size (AWG or

kcmil)

Nominal cross section (mm2)

6 cycles (100 ms)

15 cycles(250 ms)

30 cycles(500 ms)

45 cycles(750 ms)

60 cycles (1 s)

180 cycles(3 s)

#2 33.63 22 16 12 10 9 5 #1 42.41 28 21 16 13 11 7 1/0 53.48 36 26 20 17 14 8 2/0 67.42 45 33 25 21 18 11 3/0 85.03 57 42 32 27 23 14 4/0 107.20 72 53 40 34 30 17 250 126.65 85 62 47 40 35 21 350 177.36 119 87 67 56 49 29

4

Table 3 Ultimate equivalent symmetrical current-carrying capabilities of copper grounding 5 cables (currents are rms values, for frequency of 60 Hz; X/R = 20; current in kA) 6

Cable size (AWG or

kcmil)

Nominal cross section (mm2)

6 cycles (100 ms)

15 cycles (250 ms)

30 cycles (500 ms)

45 cycles (750 ms)

60 cycles (1 s)

180 cycles(3 s)

#2 33.63 25 18 13 11 9 5 #1 42.41 32 22 16 13 12 7 1/0 53.48 40 28 21 17 15 9 2/0 67.42 51 36 26 22 19 11 3/0 85.03 64 45 33 27 24 14 4/0 107.20 81 57 42 35 30 18 250 126.65 95 67 50 41 36 21 350 177.36 134 94 70 58 50 29

7

Table 4 Ultimate equivalent symmetrical current-carrying capabilities of copper grounding 8 cables (currents are rms values, for frequency of 60 Hz; X/R =10; current in kA 9

Cable size (AWG or

kcmil)

Nominal cross section (mm2)

6 cycles (100 ms)

15 cycles (250 ms)

30 cycles (500 ms)

45 cycles (750 ms)

60 cycles (1 s)

180 cycles(3 s)

#2 33.63 27 19 13 11 9 5 #1 42.41 35 23 17 14 12 7 1/0 53.48 44 30 21 17 15 9 2/0 67.42 56 38 27 22 19 11 3/0 85.03 70 48 34 28 24 14 4/0 107.20 89 60 43 36 31 18 250 126.65 105 71 51 42 36 21 350 177.36 147 99 72 59 51 30

10 11

Page 19: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

10

Table 5 Ultimate equivalent symmetrical current-carrying capabilities of copper grounding 1 cables (currents are rms values, for frequency of 60 Hz; X/R = 0; current in kA) 2

Cable size (AWG or

kcmil)

Nominal cross section (mm2)

6 cycles (100 ms)

15 cycles (250 ms)

30 cycles (500 ms)

45 cycles (750 ms)

60 cycles (1 s)

180 cycles (3 s)

#2 33.63 31 19 14 11 9 5 #1 42.41 39 24 17 14 12 7 1/0 53.48 49 31 22 18 15 9 2/0 67.42 62 39 28 22 19 11 3/0 85.03 79 50 35 28 25 14 4/0 107.20 99 63 44 36 31 18 250 126.65 117 74 52 43 37 21 350 177.36 165 104 73 60 52 30

3

NOTE 1— The current values in Tables 2 through 5 were calculated from the computer program RTGC, Reichman et 4 al. [A9]. This computer program can be used directly to determine the grounding cable size requirements for known 5 X/R ratio and short circuit clearing time. 6

NOTE 2— Angle of current initiation = 90° (maximum dc offset). Initial conductor temperature = 40°C; final conductor 7 temperature = 1083 °C. 8

NOTE 3— These current values consider the cable thermal limits only and do not consider the severe electromechanical 9 forces present during the first few cycles of a fully offset wave, which can mechanically damage the TPG cable 10 assembly or cause complete failure. 11

NOTE 4— For derating of multiple cables, refer to 4.8.3. 12

NOTE 5— Metric values are soft conversions. Soft conversion is a direct area calculation in metric units from the AWG 13 size. 14

4.6.3 Jacket 15

The following types of jacketing materials are generally used in cable designs, primarily for the protection 16 of the conductor: 17

a) A jacket based on a compound of vulcanized ethylene propylene rubber (EPR) or ethylene 18

propylene diene monomer (EPDM). 19

b) A general-purpose jacket based on a compound of thermoplastic polyvinylchloride (PVC), 20

copolymers, or silicone rubber compounds. 21

c) A cold-resistant jacket based on a compound of thermoplastic PVC or one of its copolymers or 22

silicone rubber compounds. 23

A separating tape, made of suitable material, might be placed between the conductor and the jacket. 24 Consider the fire-retardant characteristics of the jacket material. Because some jacketing materials produce 25 toxic fumes if overheated, their use might be limited to outdoor applications. An indoor application could 26 be permissible with forced-air ventilation. 27

The jacket should have adequate mechanical strength and elasticity within the temperature limits to which 28 it can be exposed in normal use. Compliance with the following references verifies the mechanical strength 29 and elasticity of each type of jacketing material: 30

Page 20: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

11

1) IEC 60502 [A4] for EPR or similar compound. Additionally, cables covered by this type of 1

compound are subject to a bending or elongation test at 50°C. 2

2) IEC 60227-2[A2] for a general-purpose compound. 3

4 The applicable test methods and the results to be obtained for each type of jacketing material are also 5 specified in these standards. 6

The jacket is normally applied closely to the conductor with separator, if any. It should be possible to 7 remove the jacket without damaging the strands. This may be checked by visual inspection. The jackets are 8 available in several colors. Typical colors include orange, yellow, black, and green. There is no preferred 9 color for the jacket. The PVC (thermoplastic) jackets are usually made transparent. Some users prefer 10 transparent jackets because it allows for visual inspection of the conductor. PVC (thermoplastic) jackets 11 can, over time, become opaque and brittle. 12

4.6.4 Cable stranding configuration 13

Cable stranding is specified in ASTM F855. TPG cables are typically furnished in three types. The type 14 depends on both the cable and protective jacket. The major characteristics of these ground cables are as 15 follows: 16

a) Type I 17

1) Conductor—Stranded soft drawn copper conductor with 665 strands or more of #30 or #34 18

AWG. 19

2) Jacket—Elastomer jacket, as rated by manufacturer, flexible for installation and serviceable 20

for continuous use within the temperature range -40°C to +90 °C. 21

b) Type II 22

1) Conductor—Stranded soft drawn copper conductor with 133 strands or more for #2, or 259 23

strands or more for 1/0 AWG, and greater. 24

2) Jacket—Elastomer jacket, as rated by manufacturer, flexible for installation and serviceable 25

for continuous use within the temperature range -25°C to +90 °C. 26

b) Type III 27

3) Conductor—Stranded soft drawn copper conductor with 665 strands or more of #30 AWG. 28

4) Jacket—Thermoplastic jacket, as rated by manufacturer, flexible for installation and 29

serviceable for continuous use within the temperature range -10°C to +60°C. 30

31 Use of type III cables is sometimes restricted to open areas or spaces with adequate ventilation so that any 32 fumes produced by overheating can be dispersed. 33

Page 21: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

12

4.7 Clamps 1

Clamps are rated for maximum available short circuit current, including asymmetry and duration, to which 2 they can be subjected without exceeding service requirements. The clamp and conductor assembly should 3 be capable of carrying the available short circuit current for the specific time without damage or separation 4 from the phase conductor or ground point. 5

Clamps for grounding applications are characterized by their time versus current ratings, their overall 6 general shape, and clamping configuration. The clamp configuration should accept the main and tap 7 conductor sizes and have the appropriate jaw configuration. 8

If inadequately rated, electromechanical forces due to a short circuit can break the connection of the clamp 9 from the phase conductor, or even break the clamp, or, the clamped connection can loosen and fail. ASTM 10 F855 provides information on clamp material and strength specifications. 11

4.7.1 Clamp types 12

A large variety of clamps are available in the industry, each suitable for either a specific or multiple 13 applications. Clamps are designed to fit various shapes of bus-work, stranded or solid conductors, and steel 14 tower structures. For more information, refer to the manufacturer’s literature. 15

A clamp can have either smooth or serrated jaws. The smooth jaw clamp is designed to minimize conductor 16 damage and is generally used on cleaned conductors to provide a reliable connection. The serrated jaw 17 clamps are designed to break through the buildup of corrosion or oxide film on the conductor. If a clamp 18 with serrated jaws is used improperly, the conductor surface could be damaged. 19

4.7.2 Clamp material 20

Clamps are typically made from aluminum or copper alloy. Copper cables should not be fitted directly into 21 aluminum alloy clamps because of corrosion and resulting loss of both electrical contact and mechanical 22 strength. To minimize corrosion, consider using tinned cable terminations or a suitable corrosion inhibitor.. 23 Even with these precautions, a corrosive atmosphere or excessive moisture might damage the TPG cable 24 assembly. 25

4.7.3 Mechanical considerations 26

For high short circuit currents, the clamps and the terminations are subjected to very high 27 electromechanical forces during short circuit conditions, especially when long cables are left unsecured. 28 Under such conditions, large magnetic forces can accelerate the cables to high velocities and the clamps are 29 called on to absorb much of this kinetic energy. Also, if a TPG were to fail mechanically, the failure would 30 most likely be within the first three cycles and the worker would be without any protection for the 31 remainder of the short circuit duration. 32

Violent cable whipping can be reduced by restraining the cable using a rope. If used, the restraint should 33 not create a rigid binding point, but it should absorb shock and prevent the violent cable movement 34 produced by the magnetic forces. If the cables are twisted or wrapped around the structure, a transformer 35 effect is created, inductive reactance increases and the cable could overheat and fail. The increase in 36 reactance also increases the worker exposure voltage. In addition, when there is a large dc offset with full 37 asymmetry, the peak current can be up to twice the value of the symmetrical peak current. The magnetic 38 forces can be up to four times as high in such cases. ASTM F855 now includes ratings for both low and 39 high asymmetrical currents. The ratings for the lower asymmetry are based on maximum peak current of 40 20% over the symmetrical peak current (1.75 times the RMS current) The lower asymmetries are classified 41

Page 22: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

13

Grade 1 to 7. The ratings for high asymmetries are based on maximum peak current of 90% over the 1 symmetrical peak current (2.69 times the RMS current). The higher asymmetries are classified Grade 1H to 2 7H. IEC 61230 requires rating at 84 % peak over the symmetrical peak current (2.6 times the rms current). 3

The mechanical adequacy of a given design and construction of a clamp, for a given short circuit current, 4 depends on the combination of cable type and length, and the type of cable-to-clamp attachment with which 5 it is to be used. For a given short circuit current magnitude and duration, a certain clamp can be entirely 6 adequate mechanically for one application, but inadequate for another. Only full-scale short circuit current 7 tests on the most adverse application of a clamp would allow one to determine its mechanical ruggedness 8 and acceptability for the specific application. 9

Most substation applications involve three-phase TPGs, and there can be high electromechanical forces 10 produced between the individual TPGs when subjected to high short circuit currents. A TPG assembly that 11 would otherwise pass a single-phase test might not survive a three-phase test. Examples would include the 12 chain grounding configuration (with two or three TPGs installed in close proximity on one of the phase 13 conductors) and parallel grounding (with all three TPG ground ends attached to a common ground). 14 Therefore consider inter-phase forces when applying TPGs and test as needed. 15

4.7.4 Cable to clamp termination 16

The most critical component of the TPG cable assembly for withstanding the extreme electromechanical 17 forces is probably the cable termination, and how it is attached to the clamp. The cable can be terminated at 18 the clamp in several ways. Typical cable terminations are compression type, but other types exist. For 19 compression ferrules, follow the manufacturer’s specifications closely, including compression die type, 20 size, pressure, and compression pattern (i.e., overlap versus non-overlap, how many compressions, etc.). 21 Cable terminations are available in threaded and non-threaded form. Terminations using solder are 22 generally not used because the low melting temperature of solder is likely to fail for high currents. 23 Terminations can provide a low-resistance connection at the cable-to-clamp interface. Due to the high 24 mechanical forces, one of the most important requirements of the cable-to-clamp termination is the 25 provision for strain relief for the cable. 26

Adhesive-lined heat-shrinkable tubing or cold-shrink tubing minimizes corrosion between the cable strands 27 and enhances strain relief. 28

4.8 Multiple assemblies 29

Multiple assemblies terminated at the same point provide multiple paths for the available short circuit 30 current. This can reduce the size requirement for any individual path (cable). However, unless the current 31 paths have equal impedance, the short circuit current will not divide equally. 32

Extreme electromechanical forces present under high short circuit current conditions can break the clamp 33 or cable termination, leaving a worker without protection. Unlike thermal energy, electromechanical forces 34 on individual TPGs do not reduce in the same proportion as the current. More likely, the electromechanical 35 forces on multiple assemblies would be similar to that developed by the total short circuit current. This is 36 because the various loops consisting of phase conductors, TPGs, and current-return circuits primarily 37 determine the electromechanical forces on a TPG regardless of its multiplicity. Also, using multiple 38 assemblies introduces additional forces between the multiple cables. 39

Even if properly sized for available short circuit current (including any derating factors for multiple 40 assemblies), the manner in which the TPGs are physically located and arranged on the phase conductor can 41 have significant impact on the ability of the multiple assemblies to handle successfully the high short 42 circuit current. The best arrangement, will be one that minimizes cable movement, or allows cable 43 movement only in a direction that the strain relief is intended to allow. 44

Page 23: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

14

More than two parallel TPGs will have uncertain short circuit current distribution and high 1 electromechanical forces, and is generally not used. It is possible to reduce the number of the TPG 2 assemblies by increasing conductor size, reducing the required protection time, reconfiguring the system to 3 reduce the available short circuit current, or any combination of these. If more than two TPGs are 4 necessary, use custom-designed assemblies with special installation techniques are required. 5

4.8.1 Path impedance 6

When it is necessary to use multiple temporary grounds in parallel per phase, it is very important to provide 7 equal impedance of each TPG. To be sure that balanced current flows through each TPG, the following 8 items can be made equal: 9

a) Size and type of stirrups 10

b) Size and type of clamp 11

c) Length and ampacity of each conductor 12

d) Similar connection of each conductor in the clamp 13

e) Cleanliness of conductors, stirrups, and mating surfaces of clamps 14

f) Torque applied to each clamp 15

g) Size and location of ground riser to which the TPGs are attached, if applicable 16

17

The cleanliness of each connection and the torque applied to the clamps are of major importance. Dirty 18 surfaces or insufficient torque can result in overheating and failure. 19

Inductive reactance is often more important than resistance in terms of the total impedance of the 20 grounding cable. However, differences in resistance where the cable is connected to the clamp and where 21 the clamp is connected to the phase conductor can be very significant in determining current sharing. 22

Inevitably, because some unbalance will cause a potential difference between cables, 600 V insulated 23 cables are used to minimize arcing. 24

4.8.2 Positioning 25

If two TPGs in parallel are used, attach the clamps as close together as possible to minimize unequal 26 currents in each TPG. Butting the clamps together will reduce the possibility of the clamps slipping off due 27 to the large attractive force between them during the short circuit. It is an industry practice to connect the 28 TPGs as close to each other as possible on the phase conductor, which further improves equal current 29 distribution. Install the parallel clamps no intentional delay to limit the exposure of a single cable to a short 30 circuit. 31

4.8.3 Derating of multiple TPGs 32

As stated above, the added electromechanical forces (EMF) due to the use of multiple TPGs are most likely 33 a greater factor in derating the ampacity of the multiple TPGs than are the unequal current division between 34 the TPGs. While some references suggest at least 10% derating due to thermal considerations, the 35 electromechanical forces require a much higher derating factor. In recent testing by NEETRAC (cite 36 reference), the derating due to EMF can be 30 to 50%, or higher. These tests were performed using a 37

Page 24: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

15

single-phase configuration. Other tests using a three-phase configuration have shown evidence of even 1 higher EMF derating factors in some cases. As stated in X5.2 of ASTM F855, only actual testing of 2 multiple TPG assembly setups can determine the appropriate derating factor and survivability of the 3 multiple TPGs. 4

In addition to both thermal and electromechanical force considerations, worker exposure voltage must be 5 considered. The magnetic coupling between the multiple cables reduces the paralleling effect of impedance 6 reduction (i.e., the total impedance of two closely-spaced identical TPGs is much higher than half the 7 impedance of a single TPG. Refer to 5.3.6. 8

4.9 Attachment Points 9

Fixed-point protective grounding terminals attached to the bus conductors, equipment terminals, cable 10 terminations or structures have been gaining acceptance in the utility industry. These terminals provide a 11 standard, consistent attachment point for temporary protective grounds (TPGs) that supports the usability of 12 standardized clamps. This avoids forcing TPG clamps to be designed and tested to work for a wide range of 13 conductor sizes and configurations. These fixed attachments (for example studs or stirrups) need to 14 withstand, mechanically and electrically, the available short circuit current. Corona protection of the 15 attachment points needs to be considered. 16

ASTM F-855standard does not include specific testing of attachment hardware similar to testing a TPG 17 cable or bar assembly. IEC 61230 does address testing of attachment hardware. To address thermal and 18 electromechanical capabilities for the available short circuit current, this hardware can be tested as 19 suggested in 4.5 and 8.1, or IEC 61230. 20

4.9.1 Bus conductors 21

A substation can include a wide range of conductor sizes and shapes. If 125 mm or larger diameter tubular 22 bus is used, dedicated attachment points (often stirrups) are usually provided for the installation of TPGs. 23 Regardless of the type of attachment point, it has to be compatible with the thermal and electromechanical 24 capabilities of the TPGs with which it will be used. 25

4.9.2 Stirrups 26

Stirrups of various sizes and shapes can be manufactured from material compatible with conductor material 27 to which the stirrup is attached. 28

4.9.3 Studs 29

Studs can be designed such that the clamps are prevented from sliding off during a short circuit. Studs can 30 be bolted, welded, or compressed on to the conductor and they can be manufactured from material 31 compatible with the conductor to which they are attached 32

4.10 Cable extensions 33

Dangerous voltage levels can develop across extremely small resistances during high current short circuits. 34 The TPGs with center splices to extend their length can increase the overall TPG resistance. This is not 35 intended to prohibit the use of cluster devices on a worksite, but to point out matters to be considered. 36

Page 25: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

16

5. Application 1

5.1 General 2

It is suggested that TPGs be installed, used, and serviced only by competent personnel using good work and 3 safety practices. This clause is intended to provide the user with information and guidance in the proper 4 selection and installation of TPGs. 5

5.1.1 Single phase 6

When maintenance is required on single-phase circuits, use a single-phase TPG assembly to connect the 7 phase conductor to a grounding electrode. 8

5.1.2 Three phase 9

When maintenance is required on three-phase circuits, use one of the following methods: 10

a) Three single-phase TPGs connecting each phase (phase-to-ground or parallel grounding) to ground. 11

b) TPGs connecting phase-to-phase-to-phase—with one of the three phases connecting to ground 12

(phase-to-phase or chain grounding). 13

c) One prefabricated three-phase TPG (cluster ground) connecting each phase to a common point, and 14

then connecting that common point to ground. 15

16 The type of three-phase configuration used will influence the available short circuit current distribution 17 among the individual TPGs and the worker, as illustrated in Figure 1, for both three-phase and single-phase 18 energizations. 19

20

Page 26: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

17

1

Figure 1 Variation of current flows for various TPG configurations. For illustration purpose 2 only, the circuits are simplified to illustrate all relative body currents for the TPG 3

configurations. 4

In the parallel configuration (Figure 1a), a TPG is in parallel with the worker between the phase and 5 ground, resulting in the minimum possible current through the worker. In the chain configuration, with one 6 of the outer phases connected through a TPG to the ground, the current is either the minimum (Figure 1b) 7 or maximum (Figure 1c) possible current, depending on the worker location relative to the phase with the 8 TPG to ground. This is because of the additional TPG conductor length from the contacted phase to the 9 grounded phase. Grounding the middle phase (Figure 1d) would reduce the current through the worker, as 10 compared with grounding one of the outer phases. In contrast, if the worker simultaneously contacts two 11 phases, chain grounding provides the minimum possible current through the worker, as a TPG is directly in 12 parallel with the worker contact points. Cluster TPGs provide some of the advantages of both parallel and 13 chain grounding. 14

5.2 Location of the TPGs 15

5.2.1 Source (bracket) grounding 16

Source grounding uses TPGs placed between the worksite and any possible energy source. The energy 17 sources include transformers, transmission lines, and generating units, and also include backfeed to the bus 18 from networked distribution lines, energized secondaries of VTs, and bus crossings (possible energized bus 19 dropping on to a de-energized bus, or vice versa). The TPGs connect the de-energized bus or equipment to 20 the substation ground, or to local grounded structures on which the worker might be located. The TPGs 21 might be located an appreciable distance from the worksite in large substations, which could increase the 22 total impedance of the TPGs in parallel with the worker and result in higher body currents when compared 23 to TPGs located in the immediate vicinity of the worker. 24

A variation of source grounding, generally involving two sources—one source on each side of the worksite, 25 is often referred to as bracket grounding. This term is more appropriate in transmission or distribution line 26 grounding, where the worksite can be energized from either end of the line. In a substation, improper 27 application of bracket grounding can result in energy sources connected to the de-energized bus between 28 the worksite and the TPG location(s). While many applications of bracket grounding are electrically the 29 same as source grounding (such as TPGs applied on either side of a circuit breaker), some applications 30 meet the visual requirements of a bracket (or working between grounds) but are electrically quite different. 31

Page 27: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

18

An example would be TPGs located at the ends of a straight bus, with one or more transmission line 1 terminations between the TPG locations. Personnel working on the straight bus would be between grounds 2 (bracketed by grounds), but the TPGs would not be between the worksite and all sources of energy. Figure 3 2a) and Figure 2b) use a simplified circuit to illustrate the difference in body current for improper and 4 proper bracket (source) grounding. A 1000 Ω body resistance is assumed for each worksite for these 5 calculations. The distances represent the separation between the worksite and the TPG or between the 6 worksite and the source (entry point) of current to the de-energized bus. 7

8

9

(b) Proper source (bracket) grounding

10 kA

TPG0.001 Ω

Accidentally closed switch

15.24 m0.015 ΩTPG

0.001 Ω 1000 Ω 1000 Ω

WS1 WS2

Worker at Body current

WS1 9 mA

WS2 2 mA

12.19 m0.012 Ω

3.05 m0.003 Ω

TPG 0.001 Ω

10

11

Figure 2 Effects of location of TPG relative to the worker. For illustration purpose only, the 12 circuits are simplified to illustrate relative body currents for the TPG locations. Body 13

resistance of 1000 is assumed at each worksite. 14

Page 28: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

19

5.2.2 Worksite (single-point) grounding 1

In worksite grounding, the TPGs are placed as close as possible to the worksite. They are used to connect 2 the de-energized bus or equipment to the substation ground or local ground. They are designed to carry the 3 maximum available short circuit current, both symmetrical and asymmetrical, that can occur at the 4 worksite, in the event of accidental re-energization. A perceived disadvantage is that the worker is not 5 working between two visible grounds on a circuit that can be energized from either of two directions, 6 resulting in a sense of a lack of safety at the work location. Typically, the current through the worker will 7 be greater if energization occurs from the side opposite the TPG location. To be considered a worksite 8 ground, the TPGs must be located very close to the actual worksite to minimize worker exposure voltage. A 9 good rule of thumb is to place the TPGs within a distance reachable from the worksite using a live-line 10 tool. Mechanical whipping of TPGs placed too close to the worker presents a safety concern. In this 11 situation, restrain the TPGs. An advantage of this method is that the worker makes fewer connections. See 12 4.7.3. 13

5.2.3 Multipoint grounds 14

Multipoint grounding is a combination of both worksite and bracket or source grounds. An advantage of 15 multipoint grounding follows from the principle of current division between ALL paths. Multipoint 16 grounding significantly reduces the current through the worker, as compared with either worksite or bracket 17 grounding. Due to redundancy of TPGs, the worker would be better protected even if one of the bracket 18 TPGs were to fail mechanically or thermally. 19

5.3 Ratings and selections 20

5.3.1 TPG conductor size 21

The size and maximum length of a TPG is based on the application and available short circuit current, 22 using the sizing criteria of 4.6.2 and, where applicable, worker exposure (touch) voltage evaluation 23 procedure in 5.3.2. When TPGs are located at two or more locations (electrically in parallel), the TPGs will 24 not share the available short circuit current equally. The majority of the current is carried by the TPG 25 closest to the source of energy. For example, with two TPGs placed 16 m apart on the same bus (e.g. 26 bracket grounding), the current division between the TPGs is on the order of 3 to 1 (75% to 25%). Size all 27 TPGs as though they are the only TPG installed. See also 5.3.6. 28

5.3.2 Worker exposure (touch) voltage evaluation 29

Worker exposure voltages present during an accidental energization of a grounded worksite in an 30 alternating-current substation are dependent on the magnitude of available short circuit current, size and 31 length of TPGs, grounding configuration (i.e. bracket, single-point, etc.), and location of the touch point in 32 relation to the attachment of TPGs to grounded conductors or equipment. The latter consideration involves 33 an induction ground loop formed by the closed circuit with the TPG, bus, worker, and ground return path to 34 the TPG. The TPG ground return path is an intentional conductor (not earth) of various forms, which 35 includes the substation ground grid, equipment ground conductor, conductive structure, and/or grounded 36 enclosures. 37

Exposure voltage at the worker touch point with TPG grounded bus or equipment is the total or phasor 38 summation of both resistive I•R and reactive I•XL voltage drops created by short circuit current in the TPGs, 39 connective bus, and, in some cases, ground return path. The reactive or induction ground loop I•XL voltage 40 drop component can be significant and generally increases with distance between the worker and point of 41 attachment of TPGs and increases with bus phase spacing. The net result of both effects makes the worst-42

Page 29: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

20

case worker exposure voltage, a single-phase energization with the worker more than 15.24 m [50 ft] away 1 from the TPG. In this scenario, the worker exposure voltage is proportional to the total impedance of the 2 TPG path to the ground grid, both resistive and reactive (self-impedance) components. This includes the 3 total TPG length plus any steel that is between the TPG and the grounding pigtail plus the length of the 4 ground grid pigtail that connects to the ground grid mesh. In some cases the actual exposure voltage, 5 accounting for induction, can exceed the resistive I•R voltage drop of the TPG alone by a factor of four or 6 more. Therefore, the effectiveness of TPGs in controlling worksite exposure voltage depends on the effects 7 of induction ground loops with the worker and self-impedance of the parallel path. 8

The following method of calculating touch voltage with TPG impedance K factors may be used to 9 approximate the total TPG-worker ground loop voltage drop for the three grounded worksite configurations 10 in 5.3.3, 5.3.4 and 5.3.5. It is emphasized that the method of K factors is sensitive to the actual physical 11 layout and connection of TPGs at a worksite, and modeling assumptions. Therefore, other worksite 12 grounding layouts require different TPG K factor values. 13

Annex C discusses TPG reactive (induction ground loop) voltage drop in more detail, and describes a way 14 to estimate its impact on the worker touch voltage for many work scenarios. The effect of the inductive 15 voltage drop is shown by developing families of curves of an impedance K factor for these grounding 16 configurations. The K factor relates the total worker touch voltage to the simple dc resistance of the TPG. 17 As shown in Annex C, this K factor varies depending on the application of the TPGs, the distance between 18 the worker and the TPGs, and many other factors. In some cases, however, a single value of K (Table C.1) 19 may be used for each size TPG that will give a reasonably accurate worker touch voltage over a specified 20 range of length TPG. Table C.1 is calculated based on the worker being in parallel with 10 m [32.81 ft] of 21 TPG and does not include any impedance values for additional steel or ground grid pigtail that is also part 22 of the parallel path. A single value of K cannot be appropriately used for all applications without first 23 examining and understanding the limitations of the curves shown in Annex C. 24

5.3.3 TPG impedance K factors for single-point grounded worksite with TPGs between 25 worker and source of energy. 26

The TPG impedance K factors in Annex C, Table C.1 may be used to approximate the total worker touch 27 voltage at a single-point grounded worksite during an accidental single or three-phase energization. The K 28 factors adjust the TPG cable resistance to an approximate effective impedance value based on stated 29 specific ground loop assumptions about the grounded worksite layout for the TPG and worker. The TPGs 30 are assumed to hang vertically from their point of attachment to bus or equipment to the ground-end 31 connection in a rectangular configuration with the worker location, as shown in Annex C, Figure C.1. 32

Worker touch voltage for a phase-to-ground contact may be approximated by the equation: 33

34

KRIV cft (5.1) 35

Where 36

Vt = touch voltage, V rms 37 If = available short circuit current, kA rms sym. 38 Rc = TPG cable dc resistance (excluding clamps & ferrules), mohms 39 K = TPG impedance K factor (Table C.1) 40

41

Refer to C.2 (Application of TPG impedance K factors) for step-by-step instructions for using equation 42 (5.1). 43

Page 30: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

21

Example 1

A 69-kV circuit breaker is connected to disconnect switches on either side via 5 m sections of horizontal 2 overhead bus. To maintain the breaker, the breaker is opened, along with the disconnect switches. Both 3 switches are single-point, single-phase or three-phase grounded with 4.57 m (15-foot long), number 4/0 4 AWG copper TPG(s). One TPG is connected from each switch terminal(s) (on the breaker side of switch) 5 to the station ground stub-ups for the switch. The worker position is assumed at the terminals of the 6 breaker. The likely energization would come from closing one of the disconnect switches, which means 7 the worker is 5 m away from the source side of the TPG (i.e., TPG between worker and source). The 8 available 3-phase short circuit current at the breaker is 25 kA rms sym. Determine the touch voltage at the 9 circuit breaker (worker touches overhead bus near breaker and grounded breaker enclosure). 10

Refer to Figure C.3. In this example length L of the TPGs is 4.57 m (15 feet) and distance D from TPG to 11 worker touch point is 5 m. From Table C.1 the value of K for 4/0 AWG TPG is 3.26. TPG conductor 12 resistance Arc is calculated from Table C.2 using the value 0.175 mΩ/m for 4/0 AWG conductor. Rc is then 13 0.175 x 4.57 = 0.80 mΩ. Using equation (5.1) the calculated worker touch voltage at the disconnect switch 14 structure is: 15

6526.380.025Vt V 16

Note that the K factor accounts for a nominal 0.3 mΩ total resistance of the TPG clamps and ferrules. 17

18

5.3.4 TPG impedance K factors for single-point grounded worksite with worker between 19 TPGs and source of energy 20

The situation of a worker positioned between the TPGs and source of energy presents a greater exposure 21 voltage than described in 5.3.3 for the same distance between worker and TPG. This is due to the additional 22 voltage drop of the section of short circuit current carrying grounded bus and station ground return 23 conductor (ground grid or structure), which form the induction ground loop with the TPG and worker. In 24 this case, no single value K factor is adequate for a given size TPG as in 5.3.3. Rather, the K factors 25 increase significantly in proportion to the distance from worker to TPG. Touch voltage calculation 26 procedure is similar as in 5.3.3, but the appropriate value of K must be chosen from the families of K curves 27 in C.3.2. However, to minimize worker exposure voltage with single-point worksite grounding, it is better 28 to position the TPGs between the energy source and worker(s) when practical (see discussion in 5.2.2). 29

Example 30

Same grounding scenario as in the example of 5.3.3, except TPGs are located at the terminals of the circuit 31 breaker and the worker is near (at) the switch end of the 5 m bus section from switch to breaker (worker 32 between TPGs and source of energy). Determine the touch voltage at the disconnect switch (worker 33 touches overhead bus disconnect switch and grounded switch structure). 34

In this example, a single-value K factor for TPG conductor size is not applicable. Use the K factor family of 35 curves in annex C.3.2, Figure C.19 for TPG length of 4.57 m. Reading the curve for 4/0 AWG conductor 36 at ground loop depth D = 5 m, the value of K is approximately 9.5. Using equation (5.1) the calculated 37 worker touch voltage at the disconnect switch structure is: 38

1905.980.025Vt V (5.2) 39

Page 31: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

22

5.3.5 TPG impedance K factors for bracket grounded worksite 1

For single or three-phase bracket grounded worksites (two TPGs per phase, Fig. C.2 in Annex C) involving 2 one or more short circuit current sources, the TPG impedance K factor curves in Annex C, Figure C.6 may 3 be used to approximate the maximum exposure voltage that can develop on the bus between the TPGs. 4 Touch voltage calculation procedure is similar as in 5.3.3, however note the total bracket TPGs or available 5 short circuit current must be used for If as discussed in C.2. 6

Example 7

An insulator is to be replaced atop a metal pedestal, which supports horizontal bus in a substation. Six 250 8 kcmil copper TPGs, 6m (19.7 feet) long, are connected to the bus on both sides of the pedestal in a three-9 phase bracket-grounding configuration (one TPG per phase at each bracket location, six TPGs total). The 10 bracket grounds are spaced 10 m apart with the pedestal somewhere between them. A source of short 11 circuit current exists on either side of the bracket grounded worksite, with available 1-phase short circuit 12 currents of 36 kA rms sym and 40 kA rms sym, respectively. Determine the touch voltage at the bus 13 support pedestal (worker touches grounded overhead bus and pedestal). 14

Refer to Figure C.2. The bus support pedestal is located at the worker touch point in the figure and short 15 circuit current sources exist from both right and left ends of the bus. It is reasonable to assume that the 16 grounded worksite could become accidentally energized by either, but not both energy sources at one time. 17 Therefore, choose the higher available short circuit current value (40 kA) to determine the worst-case touch 18 voltage. Use the K factor family of curves in Annex C.3.3, Figures C.23 and C.24 and linear interpolation 19 to determine the K factor for a 6m length, 250 kcmil copper TPG. The values of K for a 4.57 m and 10 m 20 length, 250 kcmil TPG for B = 10 m are approximately 2.15 and 1.85, respectively. By interpolation a 6m, 21 250 kcmil TPG has a K factor of approximately 2.1. TPG conductor resistance Rc is calculated from Table 22 C.2 using the value 0.148 mΩ/m for 250 kcmil conductor. Rc is then 0.148 x 6 = 0.89 mΩ. Using equation 23 (5.1) the calculated worker touch voltage at the bus support pedestal is: 24

751.289.040Vt V (5.3) 25

This calculated touch voltage represents the maximum voltage that would appear somewhere on the bus 26 between the bracket grounds, at an unspecified distance D from the TPG in Figure C.2. The available short 27 circuit current (combined TPG phase currents I1 + I2 in Fig. C.2) and not an individual bracket TPG current 28 is used to calculate touch voltage in equation (5.1). Refer to Annex C.1.3.3 for further explanation of K 29 factor modeling for bracket grounding. 30

5.3.6 Multiple assemblies (parallel TPGs) 31

In some grounding situations the calculated worksite touch voltage from above might exceed the company 32 safety criteria. It is then logical to question if installing a second, equally sized, adjacent parallel TPG at 33 each grounding point (not the same as bracket grounding) would significantly lower the touch voltage. The 34 effective impedance of two adjacent parallel TPGs is significantly greater than half the impedance of a 35 single TPG (parallel TPG resistance is one-half, reactance is greater than one-half). Therefore, the user 36 should understand how to predict the effect of paralleling TPGs for the purpose of reducing touch voltage. 37 Other means to lower touch voltage or shock exposure are discussed in 5.2. 38

Generally, exposure voltage at a grounded worksite can be minimized by using the shortest TPGs practical 39 for the application with the TPGs installed in parallel with and in close proximity to the worker (see 5.1.2), 40 between the worker and energy source; or use bracket grounding as conditions allow. However, among 41 typically used grounding methods, the multipoint grounding (5.2.3) would provide the most effective 42 protection. 43

Page 32: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

23

5.4 Methods 1

5.4.1 TPG cable or bar assemblies 2

The TPG cable or bar assemblies connect the phase conductors or equipment to a substation grounding 3 system or a local ground. 4

5.4.2 Grounding Switches 5

Grounding switches are permanently installed switches, kept in the open position until required. Grounding 6 switches are used for connecting the bus (de-energized, i.e., for maintenance) to the substation grounding 7 system. They are often used to connect the phase conductors to a ground electrode when the phase 8 conductors are too large in diameter or too high to accommodate a TPG effectively. They are also used 9 extensively in GIS equipment. 10

The advantages of grounding switches are their operational convenience when frequent grounding is 11 required, and the capability of including mechanical interlocks to prevent inadvertently opening the switch 12 or even to restrict access to an area. Ground switches designed to withstand the maximum asymmetrical 13 current anticipated at the substation have another advantage in that they facilitate multipoint grounds in the 14 substation. A disadvantage is that ground switches require maintenance and might not easily operate when 15 called upon, due to long periods between operations. If air insulated grounding switches are used, TPGs 16 provide worker protection at the worksite. For example, ground switches are located at the ends of a long 17 section of bus, with TPGs located at one or more worksites between the ground switches. 18

5.4.3 Ground and test devices 19

A ground and test device is a device used in metal-clad switchgear for accessing the primary bus (either 20 ‘‘main’’ bus or ‘‘outgoing’’ bus) and ground bus within an individual cell or cubicle. It provides visible, 21 protective grounding in the work area. 22

As a grounding device, it makes available the accessed primary bus and ground bus for interconnecting by 23 an equipment operator. This interconnecting is done either manually, using standard TPGs, or through an 24 integral ‘‘grounding’’ switch. 25

As a testing device, it makes the primary bus and ground bus accessible for voltage and phase relation 26 checks. These devices are installed in place of the standard circuit breakers. See IEEE Std 37.20.6 [A5] for 27 more information concerning ground and test devices. 28

6. Installation and removal 29

6.1 General procedures 30

The exact procedures for applying TPGs can differ, depending on the type, rating, configuration of the 31 equipment being isolated and grounded, and specific policies of the organization. Consider the possible arc 32 flash hazard involved with installing and removing TPGs and choose appropriate personnel protective 33 equipment to minimize burn hazards. (For further relevant information on arc-flash hazards, refer to IEEE 34 Std 1584TM [A7]). The TPG is applied between the ground electrode and the de-energized bus, line. The 35 ground electrode consists of the substation grounding system, which includes system neutrals, ground 36 grids, ground rods, overhead ground wires, and structures. Ensure that the ground electrode is capable of 37

Page 33: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

24

carrying the maximum available short circuit current at the point of application. General procedures are 1 listed below: 2

a) Check grounding assembly to verify that it is in good operating condition. 3

b) Isolate the section of bus, line, or equipment, including secondary circuits, if appropriate. 4

c) Install barrier, if required (rope off area). 5

d) Test for voltage on the de-energized bus, line, or equipment. 6

e) Clean areas on bus and ground electrodes following approved safety procedures. 7

f) Install assembly on ground electrode. 8

g) Install assembly on de-energized bus, line, or equipment. 9

h) Remove assembly from de-energized bus, line, or equipment. 10

i) Remove assembly from ground electrode 11

12

6.2 Tools 13

Live-line tools are protective operating devices made from suitable insulating materials. See IEEE Std 516 14 [A6]. Ground clamps, cleaning tools, and measuring instruments may be attached to live-line tools for 15 working on energized or statically charged conductors. Live-line tools are available in various shapes, 16 sizes, and lengths. 17

6.2.1 Clamp stick 18

Clamp sticks are a class of the live-line tool used when more complex operations are required. These live-19 line tools have mechanical linkages to improve maneuverability and control of ground clamps, tools, 20 measurement equipment, and other devices. 21

To increase the worker’s lifting capabilities, a hook lift stick (shepherd’s hook) with block and rope 22 assembly reduces the effort required to raise and install large capacity clamps on an overhead bus. 23

6.2.2 Bucket and platform truck 24

Bucket and platform trucks are used to reach otherwise inaccessible equipment or bus conductors requiring 25 grounding. Live-line tools might be used in conjunction with bucket and platform trucks for grounding 26 applications. Before work begins, ground the truck frame to the substation grounding system. (See 6.5.3.) 27 Platform 28

Platforms are used to elevate the worker to the work area for better access. Platforms can be either 29 insulating or non-insulating. Live-line tools may also be used in conjunction with platforms for grounding 30 applications. Ground temporary non-insulating platforms prior to beginning work. Ground permanent 31 platforms in accordance with IEEE Std 80. 32

Page 34: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

25

6.3 Testing for voltage 1

Before any grounding connections are made, test the bus or equipment to verify it is de-energized. The 2 following devices and methods are used to detect the presence of voltage on the bus, equipment and ground 3 electrode. 4

6.3.1 Proximity voltage detectors 5

These devices detect the presence of voltages by being placed in the electric field near the bus, using the 6 appropriate live-line tool. 7

6.3.2 Multi-range voltage detectors 8

These devices are voltage detectors, which are attached to live-line tools and have probes that need to be 9 placed directly on the bus to be tested. 10

6.3.3 Fuzzing (buzzing or teasing) 11

Fuzzing also known as buzzing or teasing, is a method using a conductive tool on the end of a clamp stick 12 and dragging the conductive device along the bus. A buzzing could indicate an energized bus. Since this 13 technique is very subjective, it is NOT suggested. 14

6.4 Placing and removing of TPG’s 15

The temporary protective grounding assembly may be placed at such locations, and arranged in such a 16 manner, as to minimize the risk of employee exposure to hazardous differences in electrical potential and 17 movement of the assembly under short circuit conditions. 18

6.4.1 Cleaning of bus and electrodes 19

Prior to making any grounding connection, clean all contact connection surfaces to remove any buildup of 20 dirt, oil, grease, or oxides. Remove protective coatings, such as paint, from steel surfaces prior to making 21 connections. Clean non-plated contact surfaces using V-shaped wire brushes, standard wire brushes, 22 sanders, or other similar tools. These cleaning tools are an attachment to live-line tools 23

In lieu of cleaning, use grounding clamps with serrated jaws to penetrate the corrosion on a tubular bus or 24 use clamps with piercing bolts to penetrate galvanized surfaces. Note that piercing bolts are sometimes 25 found to be ineffective under high short circuit current conditions and clamps with serrated jaws sometimes 26 deform conductor surfaces, causing corona at higher voltages. 27

6.4.2 Order of connections of TPG’s 28

When a ground is to be attached to a bus, incoming line, or equipment, the ground-end connection is 29 attached first, and then the other end is attached by means of a live-line tool. 30

Page 35: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

26

6.4.3 Order of removing TPG’s 1

When a TPG is to be removed, the TPG assembly is removed from the bus, line, or equipment using a live-2 line tool before the ground-end connection is removed. 3

6.5 Equipment grounding 4

6.5.1 General 5

Work in substations does not permit universal applications of grounding. Evaluate each job with regard to 6 the live equipment installed at the substation, other work activities, switching in the vicinity, and the type 7 of work being done. Additional rigging and physical barriers might be necessary to prevent contact with 8 live equipment. 9

Induction current can be a serious problem in a substation. A single ground will allow steady state charging 10 current to flow for a de-energized bus section that is parallel to an energized bus section. Applying two 11 grounds to a bus section can provide a loop for current from the magnetic field to flow. Some equipment 12 can develop voltage due to capacitive coupling with nearby live conductors, if the equipment is isolated 13 from the ground. Refer to Annex A for more information. 14

Temporary grounds are used to extend the permanent grounded work zone to include bus, lines, cables, and 15 equipment, which are normally energized. 16

6.5.2 Electrical bonding for static and capacitive coupled voltage 17

While working on a circuit that is properly grounded, a person is protected by proper bonding techniques. 18 Bonding is the electrical connection between metallic parts or conductors. The purpose of bonding is to 19 connect solidly every metallic part in the work area to minimize any potential differences. 20

6.5.3 Transport and work equipment 21

Ground all vehicles utilizing any type of aerial equipment in a substation. The vehicle ground is connected 22 to the vehicle first and the grounding system last to minimize sparks near the vehicle’s fuel or combustible 23 materials on the vehicle. 24

Grounding the vehicle provides for quick clearing of the circuit if the vehicle becomes energized, thus 25 reducing the time of exposure of persons in the work area to the electrical hazard. 26

External to the substation, protection to personnel is provided by avoiding contact between people on the 27 ground and the vehicle or equipment when it is being used in the vicinity of energized conductors or 28 apparatus. If, however, the vehicle is within the substation grid and the grid is properly designed, touching 29 the vehicle is no worse than touching any other grounded structure or equipment during a short circuit 30 current, though the probability of an inadvertent energization of the vehicle would be higher. 31

For persons standing on the ground, avoiding contact with a vehicle or an attached trailer while the boom 32 aerial device is being moved in the vicinity of energized conductors or apparatus will minimize the 33 possibility of hazards in the event the device comes in contact with the energized conductor. When it is 34 necessary to operate the controls at ground or vehicle level, protect the operator by one of the following 35 methods: 36

Page 36: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

27

a) Stand on a metal operator’s platform installed for this specific purpose. 1

b) Stand on the deck of the vehicle. 2

c) Stand on a portable conductive mat electrically attached to the grounded vehicle. 3

4

6.5.4 Arc welders 5

If the arc welder ground lead is placed to include a transformer or CT winding in the weld circuit, a 6 backfeed source is created that can produce a hazardous voltage in another winding. The fact that some 7 welding equipment operates on dc does not eliminate the hazard, because the voltage is induced when the 8 electrode makes or breaks the circuit. Attaching leads near capacitor banks can also charge the capacitors to 9 a hazardous voltage. 10

7. Minimizing static and capacitively coupled voltage on personnel 11

This clause serves as a guide to help alleviate the adverse effects due to static voltage and electric field 12 induction, in substations when a worker becomes isolated from the ground (i.e., working aloft, wearing 13 rubber soled or insulating footwear, etc.). 14

The purpose of protective equipment against static voltage and electric field induction is to bring the 15 worker and work surface to the same electrical potential and keep them at the same potential throughout the 16 job. 17

This clause does not constitute a recommendation, but only suggests a method to alleviate the adverse 18 effects of discharges due to static voltage and electric field induction. Many substation bus and equipment 19 arrangements reduce levels of electric field below the perceptible range. 20

7.1 Protective garments 21

Protective garments can include conductive jackets, undershirts, shirts, trousers, boots, and gloves worn 22 separately or in any combination as deemed necessary to mitigate the adverse effects of voltage discharges. 23

7.2 Attachments 24

Attachments to a grounded steel structure or other grounded devices can be made with conductive straps 25 using magnets or clamps for attaching to the grounded structure. The other end of the conductive strap is 26 connected to the worker’s conductive garments. A 2 m [6.56 ft] long conductive strap is suggested as an 27 optimum manageable length. 28

Page 37: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

28

8. Testing 1

8.1 New TPG component and assembly testing 2

Test the TPG assemblies and components in accordance with ASTM F855 or IEC 61230. ASTM F855 3 allows testing with currents with either low (Grades 1-7) or high (Grades 1H-7H) asymmetry. Choose the 4 appropriate grade level for the application. IEC 61230 requires testing with 1.15 times the rated current 5 and having an asymmetry factor of 2.6 times the rms value. 6

8.2 In-service inspection, maintenance and testing TPG’s 7

Inspect and test the TPG assemblies and components in accordance with ASTM F2249 8

8.2.1 Visual inspection 9

a) Check for the presence of broken strands, especially near the cable termination. If any defects are 10

found, either repair or replace the assembly (remove from service), as appropriate. 11

b) Check for damaged or burned jacket material, for cable material discoloration and corrosion. 12

c) Check for damaged cable terminations. Check the clamps for sharp edges, cracks, splits, or other 13

defects. 14

8.2.2 Operation check 15

Examine the individual components: 16

a) Verify that the clamps operate smoothly and are free of excessive looseness. If any defects are 17

found, either repair or remove from service, as appropriate. 18

b) Clean the clamp jaws, eye-screws, and T-handle screws of dirt, oil, grease, and/or any corrosion. 19

c) Verify that the interface connection between the cable termination and clamp is clean. 20

d) Verify that the cable termination to the clamp is tight. 21

8.2.3 Periodic testing of TPG’s 22

Experience has shown that TPGs can be damaged by rough usage or corrosion. Visual inspection and 23 electrical tests can be performed. 24

8.2.3.1 Visual test 25

The ability of the welded or compression cable termination to sustain electromechanical force has been 26 well demonstrated. The direct clamping of a conductor to the ground clamp is likely satisfactory when new, 27 but mechanical stresses on the conductor during its service life degrade it substantially. A thorough visual 28

Page 38: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

29

inspection is essential in the review of a TPG quality. Evidence of broken strands or corrosion within the 1 cable termination or the cable are signs of this degradation and require further investigation. 2

8.2.3.2 Electrical test 3

An electrical test provides a means of monitoring continuity and changes in the electrical properties of a 4 TPG. However, electrical tests alone do not adequately allow the user to predict the in-service performance 5 of the TPG (exposure voltage drop) when carrying short circuit current at the grounded worksite. (See 5.1) 6 Perform the electrical test on a TPG when it is new and at intervals thereafter. Differences in the electrical 7 properties of the TPG would be an indication of the changing condition of the TPG. The tests are 8 performed with dc or ac. Equipment is commercially available to perform an electrical test on a TPG cable 9 assembly. ASTM F2249 gives specific guidelines to test the assemblies. 10

8.2.3.2.1 Direct current test 11

A direct current of at least 10 A, but not exceeding the continuous current rating, is passed through the 12 complete TPG cable assembly. The direct current resistance of the TPG cable assembly is the voltage 13 across the assembly divided by the current. The dc test is not sensitive to placement or surroundings of the 14 TPG cable assembly being tested and, therefore, tends to be more repeatable than the ac test. Individual 15 components of the cable assembly (cable, ferrules, and clamps) are tested and tracked for change (increase) 16 in resistance, which can indicate wear, looseness, or corrosion. 17

8.2.3.2.2 Alternating current test 18

An ac current of at least 10 A, but not exceeding, the continuous current rating, is applied to the TPG cable 19 assembly. The impedance of the cable assembly is calculated by dividing the measured voltage across the 20 TPG by the test current. 21

8.2.4 Testing and maintenance intervals 22

Testing and maintenance intervals are dependent on applicable codes, exposure, manner of use, individual 23 company policy, and operating procedures. 24

Page 39: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

30

Annex A 1

(informative) 2

Bibliography 3

[B1] Grover, F.W., Inductance Calculations, Dover Publications, Inc., New York, 2004. 4

[B2] IEC 60227-1, Polyvinyl Chloride Insulated Cables of Rated Voltages Up To and Including 450/ 750 5 V—Part 2: Test Methods. 6

[B3] IEC 60245-2, Rubber Insulated Cables of Rated Voltages Up To and Including 450/750 V—Part 2: 7 Test Methods. 8

[B4] IEC 60502-1994, Extruded Solid Dielectric Insulated Power Cable for Rated Voltages from 1 kV Up 9 To 30 kV.5 10

[B5] IEEE Std 37.20.6, IEEE Standard for 4.76kV to 38kV Rated Ground and Test Devices 11 Used in Enclosures .6 12

[B6] IEEE Std 516, IEEE Guide for Maintenance Methods on Energized Power Lines. 13

[B7] IEEE Std 1584, IEEE Guide for Performing Arc-flash Hazard Calculations. 14

[B8] EPRI EL-5258, Fusing Research on Personal Grounding Cables, Final Report, July 1987. 15

[B9] Reichman, J., Vainberg, M., and Kuffel, J., ‘‘Short-circuit capacity of temporary grounding cables,’’ 16 Transactions on Power Delivery, vol. 4, no. 1, pp. 260–271, Jan. 1989. 17

For further reading 18

[B10] ASTM B 172, Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-19 Stranded Members for Electrical Conductors. 20

[B11] ASTM B 173, Standard Specification for Rope-Lay-Stranded Copper Conductors Having 21 Concentric-Stranded Members for Electrical Conductors. 22

[B12] Atwater, P.L., DeHaan, J.M., "Stage Fault Test Evaluation of High-Voltage Equipment Maintenance 23 Safety Grounding at a Large Hydro-Electric Powerplant", IEEE PES Summer Meeting, 1999. 24

[B13] ICEA S-19-81, Rubber-Insulated Wire and Cable for the Transmission and Distribution of Electrical 25 Energy.7 26

[B14] IEC 60068-2-42, Environmental Testing—Part 2: Tests. Test Kc: Sulfur Dioxide Test for Contacts 27 and Connections. 28

[B15] IEC 60479-1, Effects of Current on Human Beings and Livestock—Part 1: General Aspects. 29

[B16] IEC 60479-2, Effects of Current Passing Through the Human Body—Part 2: Special Aspects. 30

5 IEC 60502-1994 has been withdrawn; however, copies can be obtained from Global Engineering Documents, 15 Inverness Way East, Englewood, CO 80112, USA (http://www.global.ihs.com).

6 IEEE standards or products referred to in Annex B are trademarks owned by the Institute of Electrical and Electronics Engineers, Inc.

7 ICEA publications are available from Global Engineering Documents, 15 Inverness Way East, Englewood, CO 80112, USA (http://www.global.ihs.com/).

Page 40: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

31

[B17] IEEE Std 367TM , IEEE Recommended Practice for Determining the Electric Power Station Ground 1 Potential Rise and Induced Voltage from a Power Fault. 2

[B18] IEEE Std C37.09TM, IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on 3 a Symmetrical Current Basis. 4

[B19] Rustebekke, H. M., Electric Utility Systems and Practices, 4th ed., New York: Wiley, 1983. 5

Page 41: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

32

Annex B 1

(normative) 2

Terminology 3

B.1 Voltage and currents at the worksite 4

B.1.1.1 System voltage 5

System voltage refers to the bus or phase voltage and is generally specified in kilovolts (kV), phase-to-6 phase. 7

B.1.2 Static voltage 8

Static voltage can be built up on floating metallic objects (steel structures, bus conductors, etc.) due to wind 9 friction, dry conduction, or dust. Static voltage can also exist on a de-energized section of bus due to the 10 capacitive nature of the bus at de-energization (trapped charge). Generally, static voltage buildup or 11 trapped charge is less severe than the other worksite voltages that can exist. Once these static voltages are 12 removed by proper grounding, they do not immediately return. However, applying the first set of grounds 13 creates a new steady-state problem due to electric field induction. 14

B.1.3 Electric field induction (capacitive coupled) 15

Capacitive coupled voltages typically exist on a floating object in an electric field created by an energized 16 circuit as shown in Figure B.1. The floating object can be a de-energized bus, a metallic structure, a 17 transmission line, part of equipment, or a person on an insulating platform. 18

a b

Cag

Cab

Cbg

+

-

+

-Vag

Vbg

19

Figure B.1—Equivalent circuit for capacitive-coupled voltage. Conductor a is energized, 20 conductor b is floating 21

22 When an object in contact with the earth or a grounded object comes into contact with the de-energized 23 conductor, the circuit is as shown in Figure B.2. Before contact is made with the floating conductor, the 24 voltage on the conductor will be elevated due to the electric field of the energized conductor. This voltage 25 is a function of the operating voltage of the energized conductor, and the distance between the energized 26 and de-energized conductors. Once the de-energized conductor is grounded there no longer exists a 27 significant potential difference between the conductor and ground. However, unlike the case of the 28 electrically floating conductor, there is now a path for charging current to flow through the grounded object 29 to ground. The resulting charging current is not transient in nature; i.e. the resulting charge cannot be 30

Page 42: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

33

discharged, or “bled off.” It is sinusoidal and continuous. This charging current is a function of the 1 operating voltage of the energized conductor, the distance between the energized and de-energized 2 conductors, and the length that the conductors are paralleled. The charging current is independent of all 3 reasonable values of grid resistance, tower footing resistances, and series worker impedance; 1000 Ω or 4 less. It is believed that many fatalities and injuries attributed to induction are the result of a worker 5 inadvertently becoming in series with this charging current. The worker can do nothing to reduce the 6 charging current associated with installing the first set of TPGs, or removing the last set of TPGs at a given 7 location. The charging current can only be avoided. 8

9

10

Figure B.2—Case of contact with de-energized conductor 11

12

B.1.4 Magnetically coupled voltage 13

Magnetically induced voltage is similar to the action that occurs in a transformer. When the primary 14 winding is energized, the resulting current flow induces a voltage in the secondary winding. The same 15 phenomenon occurs when an energized conductor (primary winding) carrying current is adjacent to a de-16 energized (switched out) conductor (secondary winding). In this case, the transformer has an air core 17 instead of an iron core. A voltage is thus developed at point B. This circuit is illustrated in Figure B.3. 18 Grounding both ends of the de-energized conductor will minimize the potential difference across the 19 worker in contact with the de-energized conductor, even though this provides a closed loop (i.e., shorted 20 secondary) and allows current to flow in the de-energized conductor. 21

Page 43: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

34

1

2

Figure B.3—Magnetically coupled voltage 3

B.1.5 Currents 4

Under normal circumstances only rated load current is present at an energized worksite. During de-5 energized maintenance operations, with TPGs in place, consider available short circuit currents. This short 6 circuit current will be substantially larger than the steady-state current. In addition, consider the current 7 asymmetry and duration. 8

The asymmetry is a function of the reactance divided by the resistance (X/R ratio) of the circuit. The result 9 is a non-periodic, exponentially decaying dc component combined with the ac symmetrical component, as 10 illustrated in Figure B.4 (top graph). The peak current value can be increased to almost twice the 11 symmetrical peak value. The asymmetry causes an increase in electromechanical forces, and in the heating 12 of the protective equipment components. The bottom graph of Figure B.4 shows the typical current 13 waveform from an oscillograph. 14

Page 44: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

35

1

2

Figure B.4—Asymmetrical short circuit current components (example) 3

4

B.2 Safety criteria 5

B.2.1 Body current safety 6

Humans are highly sensitive to electrical current, primarily because their body nervous system is 7 electrically stimulated. The magnitude of current that a body can tolerate depends on frequency, duration, 8 and physical condition of the body. It is the consensus of researchers, however, that generally for 9 frequencies above 25 Hz and for a duration of a few seconds, the threshold of perception is 1 mA. A 10 current of 9 to 25 mA makes it difficult for a person to release their grip from a power circuit, and at 30 mA 11 muscular contractions can make breathing difficult. At higher currents, a person’s heart can cease to 12 function (ventricular fibrillation). See IEEE Std 80 for more information concerning body currents. 13

As previously stated, the magnitude of current a body can tolerate depends to a great extent on the duration 14 of the shock. Researchers have concluded that 99.5% of all persons could withstand, without ventricular 15 fibrillation, currents with a magnitude determined by Equation (1) or Equation (2) for short durations: 16

sB t

I116.0

for a 50 kg (110 lb) body (B.1) 17

or 18

Page 45: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

36

sB t

I157.0

for a 70 kg (155 lb) body (B.2) 1

where 2

IB is the rms magnitude of body current (A), 3 ts is the duration of current exposure (s). 4

5 Generally, Equation (1) is used for a more conservative approach. However, use Equation (2) provided that 6 the average population weight is expected to be at least 70 kg (155 lb). Equation (1) and Equation (2) also 7 indicate that much higher body currents are tolerated where fast operating protective devices are relied on 8 to limit short circuit current durations. 9

For capacitive-coupled voltage situations, where the conductor is energized continuously, the safety-related 10 let-go current is more appropriate as the safety-related current limit. 11

B.2.2 Shock hazard 12

B.2.2.1 Touch voltage 13

The potential difference between the ground potential rise (GPR) and the surface potential at the point 14 where a person is standing, while at the same time having a hand in contact with a grounded structure. (See 15 Figure B.5.) 16

B.2.2.2 Step voltage 17

The difference in surface potential experienced by a person bridging a distance of 1 m with the feet without 18 contacting any grounded object. (See Figure B.5.) 19

Page 46: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

37

1

2

Figure B.5—Basic shock situation 3

B.2.2.3 Transferred voltage 4

A special case of touch voltage where a voltage is transferred into or out of the substation from or to a 5 remote point external to the substation site. (See Figure B.5.) 6

B.2.2.4 Mesh voltage 7

The maximum touch voltage within a mesh of a ground grid. 8

B.2.2.5 Metal-to-metal touch voltage 9

The difference in potential between metallic objects or structures within the substation site that could be 10 bridged by direct hand-to-hand or hand-to-feet contact. 11

12

Page 47: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

38

Annex C 1

(normative) 2

TPG Impedance Correction Factors 3

C.1 Development of TPG impedance K factor 4

Historically, most computations of worker exposure voltage for temporary protective grounding in ac 5 substations have used only the resistance of the TPG cable in parallel with the assumed worker resistance to 6 determine the current through the worker. This neglects any mutual induction between the TPG and the 7 worker, the self-inductance of the TPG, any increase in TPG resistance as the TPG temperature increases 8 due to high current, and any impedances of external circuit components (such as bus). 9

Impedance correction factors (K factors) were developed to improve the TPG resistance I•R voltage drop 10 method of approximating worker exposure voltage at a grounded worksite. The use of K factors in this 11 Guide will provide more realistic values of exposure voltage by accounting for magnetic induction of the 12 TPGs and in some cases the impedance of the short circuit current carrying bus and ground return path at 13 the substation worksite. It is emphasized that the method of K factors is an approximation due to variation 14 in layout encountered at a grounded worksite and modeling assumptions. It may nonetheless be considered 15 a tool for evaluation of exposure voltage. 16

C.1.1 Grounded worksite touch (exposure) voltage 17

During accidental energization of a grounded worksite, a voltage drop develops across the TPGs and any 18 other segment of bus, which carries the short circuit current. This voltage drop becomes an exposure 19 voltage if contacted by a worker, either by phase–to-ground or phase-to-phase contact. For electrical shock 20 evaluation, it is common practice to determine touch voltage by calculating the resistive I•R voltage drop of 21 the TPGs using the worksite available short circuit current. For this purpose a TPG is assumed to be 22 directly in parallel with the worker’s body. Both theoretical study and experimental test results indicate that 23 using TPG cable resistance alone can be inaccurate (low) for determining exposure voltage. The formation 24 of induction ground loops with the TPG and worker can introduce a significant reactive component of 25 voltage drop. 26

C.1.2 Induction ground loop 27

Due to the spatial layout of TPGs in relation to a worker at a grounded worksite, a ground loop is usually 28 formed by a TPG, the grounded bus and equipment, worker’s body, and a ground return path to the TPG. In 29 substations and switchyards the worksite ground return path is conductor (ground grid, grounded 30 equipment, etc.) and not earth. The ground loop circuit becomes closed when the worker simultaneously 31 touches a conductor which has been grounded by a TPG and another grounded object in the station. See 32 Figure C.1. 33

C.1.2.1 Induction ground loop for single-point grounded worksite 34

During an accidental energization of a single-point grounded worksite with TPGs connecting each phase to 35 ground, a TPG conducts short circuit current which forms a ground loop with the worker (A-phase in 36 Figure C.1). The A-phase short circuit current creates both a resistive I•R voltage drop and a reactive I•XL 37 voltage drop across the TPG. The reactive voltage drop is created by magnetic induction from the short 38

Page 48: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

39

circuit current, whereby an alternating magnetic flux passes through (links with) the area enclosed by the 1 ground loop. For a three-phase energized grounded worksite as in Figure C.1, currents in the B and C-phase 2 TPGs also produce magnetic flux linkages, which induce additional voltages in the A-phase ground loop 3 with the worker. Therefore, both resistive and reactive components of potential are present at the worker 4 touch point; the reactance components being out of phase with the resistive component. 5

C

B

A

S

S

L

D

Fault Current Source

I 120

I -120

I 0

TPG Attachment Point

Worker Touch Point

B U S

VT

Rc

Ground Loop Circuit

TPGs

6

Figure C.1—Schematic illustration of substation single-point grounded worksite showing a 7 TPG induction ground loop with worker. TPGs positioned between worker and source of 8

energy. Ground symbols represent connection to station ground grid or grounded 9 conductive object (equipment, structure, etc.). 10

11

A similar induction ground loop can form when a worker is positioned between the TPGs and energy 12 source. In this case the voltage at the touch point includes additional resistive and reactive voltage drop 13 components due to the current in the bus section between the TPGs and the worker. 14

C.1.2.2 Induction ground loop for bracket grounding worksite 15

A TPG induction ground loop is formed with the worker as shown in Figure C.2. For modeling purposes in 16 this Guide, the TPG closest to the energy source defines the depth of the ground loop (dimension D). Note 17 that for any given position of the worker between bracket TPGs, the same worker exposure voltage would 18 be obtained if either TPG was chosen to define the ground loop (the sum of the voltages around either 19 ground loop circuit must be the same at a common point on the bus). 20

Page 49: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

40

Fault Current Source

DTPG

BUS

TPG Attachment

Point

Worker Touch Point

LRcGround Loop Circuit

B

TPG

Rc

TPG Attachment

Point

Vt

fluxes

Ground Grid

I1+I2

I1+I2

I1 I2

1

Figure C.2—Schematic illustration of substation bracket grounded worksite showing a 2 TPG induction ground loop with worker. Only one phase shown. Unequal currents flow in 3

the TPGs due to their separation or bracket distance B. 4

C.1.3 TPG impedance (induction ground loop) modeling 5

A composite value of impedance (reactance and resistance) can be derived for a TPG forming an induction 6 ground loop with the worker, for single or multiphase worksite grounding, which accounts for all of the 7 induced (reactive) voltage drops in the ground loop. This composite impedance, if multiplied by the 8 available short circuit current, approximates the true TPG voltage drop or worker touch voltage for a 9 specific grounded worksite layout. This composite impedance represents an equivalent lumped impedance 10 of a single TPG directly in parallel with the worker. Resistance of the worker’s body and associated voltage 11 drop in the ground loop circuit due to current through the body is negligible as the body resistance is 12 always several orders of magnitude greater than the TPG equivalent impedance. Therefore, the entire IZ 13 voltage drop produced by the TPG composite impedance would appear across the body. 14

TPG composite impedance equations were derived for single and three-phase, single-point grounding and 15 single-phase bracket grounding. The derivations are complex, therefore only basic derivation procedure, 16 final equations and graphed results are presented in this annex. Composite impedance was derived from 17 circuit analysis using self and mutual reactances of the short circuit current carrying conductors (TPGs, 18 overhead bus, and ground return where appropriate) for the specified grounded worksite configurations. 19 These conductors produce magnetic flux through the area enclosed by the TPG ground loop circuit with a 20 worker. 21

The general electrical circuit model used to develop TPG composite impedance and K factors for single-22 point worksite grounding is shown in Figure C.3. A similar circuit modeling method was used with Figure 23

Page 50: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

41

C.2 for bracket worksite grounding. In all cases, the mathematical derivations assume that the TPGs hang 1 vertically and straight for their entire length L. The worker completes the ground loop circuit by touching 2 the substation ground grid conductor, either directly or indirectly through a grounded conductive object 3 such as a substation structure. 4

Va

Vb

Vc

ØA

ØB

ØC

L

Rw

Vexp

S

S

Ia

Ib

Ic

ZTa

ZTb

ZTc

Flux

Ground Grid

ZBc

ZBb

ZBa

D

ZSa

ZSb

ZSc

Energy Source

Rg

TPGs

Ground Loop

5

Figure C.3—Electrical circuit model of worker exposure voltage (Vexp) at a single-point 6 grounded worksite for development of TPG composite impedance and K factor. Note TPGs 7

can be between worker (Rw) and energy source (shown) or worker can be between TPGs 8 and energy source. The defined exposure voltage does not include any portion of the 9

station ground potential rise, which appears across the grid earth resistance Rg. 10

11 A similar circuit modeling approach was used with Figure C.2 as the basic diagram for derivation of K 12 factors for bracket worksite grounding. 13

C.1.3.1 Derivation of TPG composite impedance for single-point grounded worksite, TPGs 14 positioned between worker and energy source 15

The defined worker exposure or touch voltage in Figure C.3 is the potential between the A-phase bus and 16 substation ground (ground grid conductor, grounded equipment or structure, etc.), at distance D from A-17 phase TPG of length L. Lumped impedances ZTa, ZTb, ZTc and associated magnetic fluxes represent the TPG 18 conductors resistance (RC) and self and mutual reactances associated with the ground loop circuit formed 19 by the A-phase TPG, grounded overhead bus, ground grid conductor, and worker’s body (RW). Balanced 20 three-phase short circuit current flows in the TPGs from the source at left. No current is assumed in the 21 ground grid conductor between the A-phase TPG and worker. The exposure (touch) voltage Vexp on the A-22 phase bus is then determined by summing the voltages induced in the ground loop circuit with the worker 23 due to current in each of the three TPGs as follows: 24

Page 51: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

42

accabbacaexp XIjXIjjXRIV (C.1) 1

where 2

Rc = TPG cable resistance (excluding clamps & ferrules), ohm 3 Xa = A-phase TPG self reactance out to touch point D, ohm 4 Xab = A-phase TPG coupled reactance out to touch point D due to current in B-phase TPG, ohm 5 Xac = A-phase TPG coupled reactance out to touch point D due to current in C-phase TPG, ohm 6 Ia = If(1+j0) 7 Ib = If(-0.5-j0.866) 8 Ic = If(-0.5+j0.866) 9 10

Note that only the A-phase TPG cable resistance produces an I•R voltage drop that appears in the ground 11 loop circuit with the worker. 12

Substituting the rectangular form of phase currents into equation C.1, collecting real and imaginary terms, 13 and then dividing by the short circuit current magnitude If provides the desired A-phase TPG composite 14 impedance Zg, equation (C.2). 15

2acaba2

acabcg XX5.0XXX866.03000.0RZ (C.2) 16

where: 17

Zg = A-phase TPG composite impedance for 3-phase single-point grounding 18 (TPGs between worker and energy source), ohm and the constant 0.0003 represents a nominal resistance 19 for the TPG clamps & ferrules8 Expressions for the TPG self and coupled reactances are given in C.4.1. 20

21 Note that equation C2 is derived specifically for the rectangular geometry depicted in Figures C.1 and C.3 22 with TPGs hung vertically from the bus, between worker and energy source. Equation (C2) is also valid for 23 a worker touching the C-phase bus due to symmetry. A similar derivation of TPG composite impedance for 24 the B-phase (middle) resulted in a slightly lower impedance and, therefore, is not presented here. Due to the 25 rectangular geometry, only the currents in the TPGs produce significant magnetic flux linkages with the 26 TPG ground loop formed with the worker. Currents in the overhead bus and station ground grid (ground 27 return current, if any, assumed to flow toward the source) do not produce flux that links with the worker 28 ground loop. 29

Equation (C2) is cumbersome and needs further refinement for ready use in this Guide. To accomplish this, 30 TPG impedance K factor curves were created with computer software. However, the reader may utilize 31 equation (C2) by determining values for reactance terms Xa, Xab, and Xac from formula in C.4.1. 32

TPG composite impedance Zg from equation (C2) can be normalized to the TPG cable resistance by 33 dividing by Rc. This normalized value, defined impedance K factor, can be plotted as a family of curves for 34 a given TPG conductor size and length, as shown in C.3.1. Impedance K factors were evaluated for 2 m, 35 [6.56 ft] 4.57 m [15 ft] and 10 m [32.81 ft] length TPGs in conductor sizes #2 AWG through 350 kcmil 36 (not all shown in C.3.1) to determine the worst case (highest) values. 37

8 Refer to ASTM F-855 for further evaluation of clamp and ferrule resistance.

Page 52: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

43

The single-value K factors in Table C.1 may be used to determine worst case touch voltage (see C.2) for the 1 following conditions: rectangular grounding layout as shown in Figures C.1 and C.3 and copper TPG 2 lengths of 2m through 10 m. Table C.1 may also be conservatively used for single-phase grounding, 3 assuming there is insignificant current in the ground grid between the TPG and the worker. For this single-4 phase condition, it is noteworthy that the reactive component of the TPG composite (ground loop) 5 impedance approaches the self-reactance of the TPG conductor when the loop depth D and bus spacing S 6 become large. This effect can be seen in the flattening of the K factor curves in C.3.1 for D greater than 7 about 10 m and S=24 m. For this reason, the values in Table C.1 were computed using only the self-8 impedance of the TPG conductor assuming length of 10 m. 9

Table C.1—60Hz TPG Impedance K Factors (Zg/Rc). For 1- and 3-Phase, Single-Point 10 Grounded Worksite. Single Copper Cable TPG, 10 m [32.8 ft] or less.Connecting Each 11

Phase to Ground Grid 12

TPG Cable SizeAWG or kcmil

K Factor

2 1.49 1 1.69

1/0 1.97 2/0 2.27 3/0 2.71 4/0 3.26 250 3.74 350 5.01

TPGs Positioned Between Worker and Short circuit Current Source 13

14

C.1.3.2 Derivation of TPG composite impedance for single-point grounded worksite, 15 worker positioned between TPGs and energy source 16

A worker positioned between the worksite TPGs and energy source creates a higher worker exposure 17 voltage situation than if the TPGs are positioned between worker and energy source. For this case (Fig. C.3 18 with worker touch point at A-phase bus to left of TPGs at distance D), the short circuit current related 19 voltage drops across the station bus and ground grid return conductor which form the ground loop with the 20 worker must be added to the exposure voltage in equation (C1). Equation (C2) must then be modified to 21 include associated bus and ground grid conductor impedances, resulting in equation (C3) for single-phase 22 grounding (Xab = Xac = 0). A single-phase grounding model was chosen for conservative (slightly higher 23 exposure voltage) results, with the assumption that all of the return-to-source short circuit current flows in a 24 single ground grid conductor between the TPG and worker. 25

2gba2

gbc1g XXXRR0003.0RZ (C.3) 26

where 27

Zg1 = TPG composite impedance for single-phase, single-point grounding with worker between TPG and 28 energy source, ohm 29

Rc = (see equation C.1) 30 Rb = resistance of bus forming ground loop with worker, ohm 31 Xa = (see equation (C.1)) 32 Xb = self-reactance of bus forming ground loop with worker, ohm 33 Rg = resistance of assumed 4/0 AWG ground grid conductor forming ground loop with worker, ohm 34 Xg = self-reactance of assumed 4/0 AWG ground grid conductor forming ground loop with worker, ohm 35

Page 53: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

44

1 Expressions for the resistance and self-reactance of bus and 4/0 AWG ground grid conductor are given in 2 C.4.2. 3

The computer generated K factor curves (Zg1/Rc) in C.3.2 show an ever-rising trend in value of K with 4 increasing distance between worker and TPG. Therefore, single-value K factors as in Table C.1 cannot be 5 applied to this situation. 6

Comparing the single-point grounding K curves in C.3.1 and C.3.2 makes it apparent that touch voltage can 7 be significantly higher when the worker is positioned between the TPGs and energy source. Locating the 8 TPGs between the worker and energy source is the preferred method for single-point grounding wherever 9 practical. If the energy source can be located on either side of the worksite, locate the TPGs as close as 10 possible to the worker to minimize the higher worker exposure voltage, or consider using bracket 11 grounding. 12

C.1.3.3 TPG impedance K factor for bracket grounded worksite 13

TPG impedance K factors can be developed for bracket grounding in similar manner as for single-point 14 grounding in C.1.3.2. However, in this case short circuit current division (mostly due to magnetic coupling) 15 in the bracket TPGs connected to the phase touched by the worker must be determined. Short circuit 16 current related voltage drop in the connecting bus and station ground grid return conductor between the 17 bracket TPGs forming the ground loop with the worker must also be determined (Figure C.2). This 18 increases the complexity of deriving the TPG composite impedance equation Zg. 19

Computer generated K factor data were created for single-phase bracket grounding and a portion of this 20 data is plotted for 4/0 AWG TPG conductor in C.3.3 for illustration of K vs. ground loop depth D for a 21 given bracket distance B (Figure C.21). The maximum or peak value of K in each curve is of interest for 22 determining worst-case worker exposure voltage for a given TPG bracket spacing. Therefore, maximum 23 values of K are plotted in Figure C.22 and C23 as families of curves for all TPG cable sizes that were 24 modeled. Examination of these peak K factor curves indicate that bracket grounding can provide lower K 25 factor values (worker exposure voltage) than single-point grounding. Three-phase bracket grounding was 26 not modeled, but has a similar variation in K curves with bus spacing S shown for single-point grounding. 27

As shown in Figures C.22 through C.24, there is considerably more variation in the K factors for bracket 28 grounding, with dependence on both TPG length and bracket separation distance. While these figures can 29 be used to determine the K factor within the range of parameters modeled, a conservative approximation 30 can also be obtained by using the same K factors as for worksite grounding and shown in Table C.1. A 31 single value of K cannot be appropriately used for all applications without first examining and 32 understanding the limitations of the curves. 33

C.2 Application of TPG impedance K factors 34

The TPG impedance K factors in this annex may be used to convert TPG conductor resistance to 35 approximate equivalent impedance that represents a single TPG, connected directly in parallel with the 36 worker’s body at a grounded worksite. This equivalent impedance accounts for the distributed resistance 37 and inductance of the ground loop formed by the TPG and worker. Magnetic coupling from short circuit 38 current in all three phase TPGs is included in the computation of K values for three-phase grounding where 39 specified. 40

Impedance K factors are provided for three grounding scenarios: 41

1) Single-point grounded worksite with TPGs positioned between worker and energy source. 42

Page 54: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

45

2) Single-point grounded worksite with worker positioned between TPGs and energy source. 1

3) Bracket grounded worksite with worker between bracket TPGs. 2

C.2.1 Calculation procedure for worker touch voltage 3

Worker touch voltage may be approximated by the equation: 4

KRIV cft (C.4) 5

where 6

Vt = touch voltage, V rms 7 If = available short circuit current, kA rms sym. 8 Rc = TPG cable resistance (excluding clamps & ferrules), milliohm 9 K = TPG impedance multiplier. 10

11 Use the following steps to calculate worker touch voltage for a specific grounding application: 12

1) Determine required TPG size based on the available short circuit current (4.6.2) 13

2) Determine required TPG conductor length L in meters 14

3) Select TPG K factor from: 15

Table C.1 for single-point grounding (TPG between worker and energy source). If 16 desired, the reader may select a value directly from the K curves in C.3 for a specific 17 application, or calculate K using the procedure in C.1.3.1. 18

Figures C.18 through C.20 for single-point grounding (worker between TPG & energy 19 source). The K curves in C.3.2 may be used for both single-phase and three-phase 20 grounding, or the reader may calculate K using the procedure in C.1.3.2. No single value 21 of K can be applied as for single-point grounding, as the K factors vary too much versus 22 the ground loop path. 23

Figures C.21 through C.24 for bracket grounding, or conservatively use K factor from 24 Table C.1 (see Note, this section). The maximum value K curves in Figures C.21 25 through C.24 may be used for both single-phase and three-phase grounding, or Table 26 C.1 may be used after reading C.1.3.3. No readily-available K factor calculation 27 procedure is provided for bracket grounding. 28

4) Calculate TPG conductor resistance from Table C.2 29

5) Calculate touch voltage from equation (C4), noting If must be in kA if Rc is in mΩ from Table 30 C.2 31

32 The K factor values given in the tables and curves of Annex C were calculated for copper TPG conductor 33 with radius and resistance Rc values based on Table C.2. The use of other conductor resistance values in 34 equation C4 will introduce error in Vt approximately in proportion to the ratio of the other-to-specified 35 conductor resistances. 36

Note: For calculation of bracket grounding touch voltage, use the total available short circuit current (I1 + 37 I2 in Figure C.2) for If in equation C4, not an individual TPG current. The derivation of Zg for calculating K 38 factor accounts for the current division. 39

40

Page 55: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

46

Table C.2—DC Resistance of Copper Welding Cable, Milliohms per Meter @ 25°C 1

Conductor size AWG or kcmil

Conductor radius (cm)

mΩ/m

2 0.428 0.551 1 0.478 0.436

1/0 0.537 0.344 2/0 0.645 0.278 3/0 0.732 0.220 4/0 0.819 0.175 250 0.906 0.148 350 1.048 0.106 From NEMA WC 58-1997, Table 5-1 2

(Average value for Class K & M conductors) 3

C.3 TPG impedance K factor curves 4

C.3.1 Single-point grounded worksite, TPGs positioned between worker and energy source 5

TPG impedance K curves for three-phase, single-point grounding are shown in the following charts. Note 6 that the three-phase, single-point grounding curves with bus spacing S = 24 m are also valid for single-7 phase grounding. 8

Fourteen of 24 charts created for the development of the method of K curves for this Guide are shown 9 below for observation and use. These charts are sufficient to demonstrate the trends in K values for various 10 worksite conditions. Charts not shown are for 2 and 10-meter length TPGs for some conductor sizes. 11

Note: All following TPG impedance K factor curves are plotted for a power system frequency of 60 Hz. 12

13

Page 56: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

47

1

2

Figure C.4—#2 AWG copper TPG length = 2m (6.56 ft) 3

4

5 Figure C.5—#2 AWG copper TPG length = 4.57 m (15 ft) 6

Page 57: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

48

1

2

Figure C.6—#2 AWG copper TPG length = 10 m (32.81 ft) 3

4

5

Figure C.7—#1 AWG copper TPG length = 4.57 m (15 ft) 6

Page 58: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

49

1 2

Figure C.8—1/0 AWG copper TPG length = 4.57 m (15 ft) 3

4

5

Figure C.9—2/0 AWG copper TPG Length = 4.57 m (15 ft) 6

Page 59: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

50

1

2

Figure C.10—3/0 AWG copper TPG length = 4.57 m (15 ft) 3

4

5

Figure C.11—4/0 AWG copper TPG length = 2m (6.56 ft) 6

Page 60: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

51

1

2

Figure C.12—4/0 AWG copper TPG length = 4.57 m (15 ft) 3

4

5

Figure C.13—4/0 AWG copper TPG length 10 m (32.81 ft) 6

Page 61: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

52

1

2

Figure C.14—250 kcmil copper TPG length = 4.57 m (15 ft) 3

4 Figure C.15—350 kcmil copper TPG length = 2m (6.56 ft) 5

Page 62: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

53

1

2

Figure C.16—350 kcmil copper TPG length = 4.57 m (15 ft) 3

4

5

Figure C.17—350 kcmil copper TPG length = 10 m (32.81 ft) 6

Page 63: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

54

1

C.3.2 Single –point grounded worksite, worker positioned between TPGs and energy 2 source 3

Families of TPG impedance K curves are shown below for TPG lengths of 2 m [6.56 ft], 4.57 m [15 feet], 4 and 10 m [32.81 ft] as depicted in figure C.1, except the worker is now positioned to the left of the TPGs 5 (between source and TPGs). Values of K for other lengths of TPGs between 2 m [6.56 ft] and 10 m [32.81 6 ft] may be interpolated from the curves. Ground loop depth D is the distance from TPG to worker (toward 7 source). These K curves account for impedance of the section of station bus 9 of length D and same length 8 of an assumed 4/0 AWG station ground grid conductor that together form the ground loop with the worker 9 and conduct the short circuit current. These curves are derived for single-phase, single-point worksite 10 grounding but are applicable to three-phase grounding as well. The observation here is that the value of K 11 and worker exposure voltage rises significantly as the distance between worker and TPG increase. Refer to 12 C.1.3.2. 13

Figures C.18 through C.20 show 60 Hz TPG impedance K factor curves for single-phase, single-point 14 grounding with worker positioned between the TPG and the energy source. 15

16 17

9 Station bus is assumed schedule 40 seamless bus pipe, 3-inch nominal size, 3.5-inch O.D., 3.06-inch I.D, AC resistance @ 70°C: 8.126 µΩ/ft. Larger bus sizes should result in slightly lower K factors.

Page 64: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

55

1

Figure C.18—2 m (6.56 ft) length TPGs 2

3

Page 65: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

56

1 2

3

4

Figure C.19—4.57 m (15 ft) length TPGs 5

6

Page 66: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

57

1 2

3

4

Figure C.20—10 m (32.81 ft) length TPGs 5

6

C.3.3 Single-phase bracket grounded worksite 7

Refer to C.1.3.3 for discussion of TPG impedance K factors for bracket grounding. Figure C.21 illustrates 8 impedance K factor model data curves for only one TPG cable size and length. This data and similar data 9 for all other TPG model data are plotted in another form of curves showing maximum K values vs. TPG 10 bracket spacing in Figures C.22 through C.24. These curves may be used to approximate worst-case worker 11 exposure voltage for a given TPG bracket spacing (see Figure C.2). These K factor curves account for 12 impedance of the section of station bus (see footnote 11, above) and an assumed single 4/0 AWG station 13 ground grid conductor that together form the ground loop with the worker and conduct the short circuit 14 current. 15

These single-phase TPG bracket maximum value K curves are applicable for three-phase grounding for bus 16 spacing S (Figure C.1) greater than 1.5 m and become conservative (high K values) for bus spacing less 17 than 1.5 m. 18

19 20

Page 67: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

58

1

2

Figure C.21—Example 60 Hz TPG Impedance K factor curves for 1-phase bracket 3 grounding with 4/0 copper TPGs. Curves include effect of impedance for a single 4/0 AWG 4 station ground grid conductor current return path below the overhead bus (Fig. C.2). B = 5

bracket separation distance between TPGs. 6

7 Figures C.22 through C.24 show curves for 60 Hz TPG maximum impedance K factors for 1-phase bracket 8 grounding, as shown in Figure C.2. The curves represent the highest value of K obtained at an unspecified 9 worker position between bracket TPGs. 10

11 12

13

Page 68: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

59

1

Figure C.22—2m (6.56 ft) TPGs 2

3

Figure C.23—4.57 m (15 ft) TPGs 4

Page 69: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

60

1

Figure C.24—10 m (32.81 ft) length TPGs 2

3

C.4 TPG reactance terms for calculation of Zg and K factor 4

C.4.1 Single-point grounded worksite (TPGs between worker and energy source) 5

The reader may calculate TPG composite impedance Zg (and K factor) with Equation (C.2) in C.1.3.1 by 6 determining values for reactance terms Xa, Xab, and Xac with the following equations: 7

madsa LLf2X (C.5) 8

mbdmabab LLf2X (C.6) 9

mcdmacac LLf2X (C.7) 10

where: 11

Ls = A-phase TPG self-inductance, H 12

Page 70: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

61

Lmad = A-phase TPG mutual inductance with worker body at touch point D, H 1 Lmbd = B-phase TPG mutual inductance with worker body at touch point D, H 2 Lmcd = C-phase TPG mutual inductance with worker body at touch point D, H 3 Lmab = mutual inductance of A & B-phase TPGs, H 4 Lmac = mutual inductance of A & C-phase TPGs, H 5 f = frequency, Hz (f = 60 Hz for K factor values given in this Guide). 6

7 The above reactance equations were derived specifically for the TPG induction ground loop arrangement 8 shown in Figures C.1.and C.3. Formulas for determining the self (Ls) and mutual (Lm) inductances of finite 9 length conductors from Grover [A1] are shown below: 10

91075.02

ln2

r

LLLs H (C.8) 11

L

d

L

d

d

L

d

LLLm

22

11ln002.0 H (C.9) 12

where: 13

L = TPG length (Figures C.1 and C.3), cm 14 r = TPG conductor radius (excluding jacket), cm 15 d = distance between center of conductors, cm. 16

17 In determining the mutual inductances, the user must carefully select distance d to be the horizontal length 18 between the mutually coupled conductors of interest. For calculation of Lmab and Lmac, distance d is equal to 19 S and 2S, respectively, in Figures C.1.and C.3. For calculation of the mutual inductances of TPGs with 20 worker’s body, distance d must be determined for the specific TPG to worker touch point on the bus; d is 21 dimension D in Figures C.1 and C.3 for Lmad, or d is the diagonal length from respective TPG to worker 22 touch point for Lmbd and Lmcd. 23

C.4.2 Single-point grounded worksite (worker between TPGs and energy source 24

The reader may calculate TPG composite impedance Zg (and K factor) with equation (C3) in C.1.3.2 by 25 determining values for Rb, Rg, Xb, and Xg with the following: 26

Self-inductance formula for bus and cable from Grover [A1] 27

Tubular Conductor 28

9101ln2

ln2

r

DDLb (C.10) 29

where 30

Lb = self-inductance of short circuit current carrying bus forming ground loop with TPG and worker, H 31 D = distance between TPG and worker, cm 32 r = pipe bus outer radius (1/2 O.D.), cm 33 lnξ = 0.0416 for pipe bus specified in footnote 11 34

Page 71: P1246™/D12 Draft Guide for Temporary Protective Grounding ...ewh.ieee.org/cmte/substations/sce0/wge4/D2292y... · 02.11.2018  · P1246/D12, November 2018 Draft Guide for Temporary

P1246/D12, November 2018 Draft Guide for Temporary Protective Grounding Systems Used in Substations

Copyright © 2018 IEEE. All rights reserved.

This is an unapproved IEEE Standards Draft, subject to change.

62

1 Solid Round Conductor 2

91075.02

ln2

r

DDLg (C.11) 3

where 4

Lg = self-inductance of short circuit current carrying station ground grid conductor (single conductor) 5 forming ground loop with TPG and worker, H 6

D = distance between TPG and worker, cm 7 r = radius of ground grid conductor, cm 8

9 Based on the above inductance formula and published resistance data for bus and cable (see footnote 5 and 10 Table C.2), values for the resistance and self-reactance of station bus and single 4/0 AWG ground grid 11 conductor used for the calculation of K values in C.3.2 with equation (C3) are: 12

Rb = 0.000 026 7 ohm/m and Xb = 0.000 46 ohm/m for bus 13

Rg = 0.000 175 ohm/m and Xg = 0.0006 ohm/m for 4/0 AWG copper conductor. 14

15

16