HOCHIKI CORPORATIONSINGAPORE BRANCH OFFICE629 Aljunied Road #03-16 Cititech Industrial BuildingSingapore 389838Tel : 65-6841-9728 Fax : 65-6841-9781Email : [email protected]
HEAD OFFICE10-43 Kamiosaki 2-Chome. Shinagawa-Ku,Tokyo 141-8660, JapanTel : 81-(3)-3444-4116 Fax : 81-(3)-3444-4167URL : www.hochiki.co.jp
P-1 Type Fire Alarm Control Panel (Time Delay Type) : RPR-AAS
Features1. Multi purpose zone configuration
- Versatile zone configuration to suit various alarm needs
2. Easy installation
- By means of ‘Wire Insertion’ terminals
- Wide internal cabinet space of easy wiring
- 180 degree wide panel door opening
3. High reliability
- Improved lightning surge protection
- Improved noise immunity
- Self-diagnostic function (zones open circuit monitored, battery fault warning, etc…)
4. Time delay function
- Designed to minimize any false fire alarm and ensure increased reliability of automatic fire
alarm systems
- False fire alarm is found to often come from heat and/or smoke at the moment during cooking,
smoking or exhaust. Then, the fire alarm signal from every detector is checked if it lasts a
predetermined period of time, based on which true fire alarm is issued
5. More functions
- Easy configuration of local bell and interlock release control which can be monitored from the
zone panel.
- ‘Hands-free’ intercom communication at control panel
- Voltage display for ‘Standby Battery’ test
- Visual representation of fire alarm status by symbolic indication lamp
- Indication lamp alert during ‘Time Delay’ operation
- Zone open circuit monitored
Hochiki Conventional System
Specifications
RPR-AASType P1-Type Fire Alarm Control Panel (with Time Delay Function)Model Name RPR-AAS�Z (60, 70, 80, 90, A0, A1, A2, A3)Main AC220V, 50/60HzStand-by Battery DC 24V, 3.5 AHMain Sounder Voice synthesis system (speaker : DC15V, 80mA, ø77)Operating Temperature Range 0°C – 40°COperating Humidity 95% or less (No condensation)Material Main frame rear panal : Electro-galvanizing steel plate (Thickness : 2.3mm)
Enclosure other than the main frame : Steel plate (Thickness : 1.6mm, Baking finish)Color Enclosure : Equivalent color to Munsell 2.5Y9/1, Semi-gloss
Panel : Equivalent color to Munsell 5Y6/0.5, 30%-glossNumber of Zones 60,70,80,90,100,110,120 or 130 ZonesWeight Approx. 125Kg ~ 250KgDimension 600mm(W) X 2000mm(H) X 450mm(D)Made JAPAN
3
100
3
100400
100 100400
(Open area)
600
4-anchor bolt hole
ø15
Channel base
Wiring hole (with cover)
400 X 80
Wiring hole (with cover)
400 X 1602-anchor bolt hole
ø15
Operation and indication panel
6-1-034-0193-031
Cover
Equipment name plate
Fire alarm panel
Fire indication led (red)
Acrylic resin (transparency)
Handle
Takigen A-240-I
50
120
1000
2000
70
80
40
70 250
450
90
35
200 160(Open area)
50