Upload
phungthu
View
225
Download
0
Embed Size (px)
Citation preview
OFFICE OF STATEWIDE HEALTH PLANNING AND DEVELOPMENT FACILITIES DEVELOPMENT DIVISION
“Access to Safe, Quality Healthcare Environments that Meet California’s Diverse and Dynamic Needs”
STATE OF CALIFORNIA – HEALTH AND HUMAN SERVICES AGENCY OSH-FD-759 (REV 10/21/14) Page 1 of 3
APPLICATION FOR OSHPD SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP)
OFFICE USE ONLY
APPLICATION #: OSP – 0400 – 10
OSHPD Special Seismic Certification Preapproval (OSP)
Type: New Renewal
Manufacturer Information
Manufacturer: Industrial Electric Mfg.
Manufacturer’s Technical Representative: Ashok Kulkarni
Mailing Address: 48205 Warm Springs Blvd., Fremont, CA 94539
Telephone: 510-360-1247 Email: [email protected]
Product Information
Product Name: 38kV Switchgear
Product Type: MV Switchgear
Product Model Number: See I. Certified Product Table attached (List all unique product identification numbers and/or part numbers)
General Description: 38kV Switchgear NEMA 1 Indoor & NEMA 3R Outdoor Sections. Seismic enhancements made to the
UUTs & modifications required to address anomalies observed during the tests shall be incorporated into the production units.
Mounting Description: Rigidly floor mounted
Applicant Information
Applicant Company Name: Industrial Electric Mfg.
Contact Person: Ashok Kulkarni
Mailing Address: 48205 Warm Springs Blvd., Fremont, CA 94539
Telephone: 510-360-1247 Email: [email protected]
I hereby agree to reimburse the Office of Statewide Health Planning and Development review fees in accordance with the California Administrative Code, 2013.
Signature of Applicant: Date: 11/26/2014
Title: Vice President of Engineering Company Name: Industrial Electric Mfg.
12/24/2014
OSP-0400-10
Page 1 of 7
OFFICE OF STATEWIDE HEALTH PLANNING AND DEVELOPMENT FACILITIES DEVELOPMENT DIVISION
“Access to Safe, Quality Healthcare Environments that Meet California’s Diverse and Dynamic Needs”
California Licensed Structural Engineer Responsible for the Engineering and Test Report(s)
Company Name: Forell/Elsesser Engineers, Inc.
Name: Marco Scanu, SE California License Number: S4454
Mailing Address: 160 Pine St., 6th Flr., San Francisco, CA 94111
Telephone: (415) 837-0700 Email: [email protected]
Supports and Attachments Preapproval
Supports and attachments are preapproved under OPM- (Separate application for OSHPD Preapproval of Manufacturer’s Certification (OPM) of Supports and attachments is required)
Supports and attachments are not preapproved
Certification Method
Testing in accordance with: ICC-ES AC156
Other (Please Specify):
Testing Laboratory
Company Name: UC Berkeley – PEER
Contact Name: Wesley Neighbour
Mailing Address: 1301 S. 46th Street, Building 420, Richmond, CA 94804
Telephone: 510-665-3409 Email: [email protected]
STATE OF CALIFORNIA – HEALTH AND HUMAN SERVICES AGENCY OSH-FD-759 (REV 10/21/14) Page 2 of 3
12/24/2014
OSP-0400-10
Page 2 of 7
OFFICE OF STATEWIDE HEALTH PLANNING AND DEVELOPMENT FACILITIES DEVELOPMENT DIVISION
“Access to Safe, Quality Healthcare Environments that Meet California’s Diverse and Dynamic Needs”
STATE OF CALIFORNIA – HEALTH AND HUMAN SERVICES AGENCY OSH-FD-759 (REV 10/21/14) Page 3 of 3
Seismic Parameters
Design in accordance with ASCE 7-10 Chapter 13: Yes No
Design Basis of Equipment or Components (Fp/Wp) = 1.54
SDS (Design spectral response acceleration at short period, g) = 2.05
ap (In-structure equipment or component amplification factor) = 2.5
Rp (Equipment or component response modification factor) = 6.0
Ω0 (System overstrength factor) = 2.5
Ip (Importance factor) = 1.5
z/h (Height factor ratio) = 1.0
Equipment or Component Natural Frequencies (Hz) = See attachment, “III. UUT Summary Sheets”
Overall dimensions and weight (or range thereof) = See attachment, “I. Certified Product Table”
Equipment or Components @ grade designed in accordance with ASCE 7-10 Chapter 15: Yes No
Design Basis of Equipment or Components (V/W) =
SDS (Design spectral response acceleration at short period, g) =
SD1 (Design spectral response acceleration at 1 second period, g) =
R (Response modification coefficient ) =
Ω0 (System overstrength factor) =
Cd (Deflection amplification factor) =
Ip (Importance factor) = 1.5
Height to Center of Gravity above base =
Equipment or Component Natural Frequencies (Hz) =
Overall dimensions and weight (or range thereof) =
Tank(s) designed in accordance with ASME BPVC, 2010: Yes No
List of Attachments Supporting Special Seismic Certification
Test Report(s) Drawings Calculations Manufacturer’s Catalog
Other(s) (Please Specify):
OSHPD Approval (For Office Use Only) – Approval Expires on December 31, 2019
Signature: Date: December 24, 2014
Print Name: Timothy J. Piland Title: SSE
Special Seismic Certification Valid Up to : SDS (g) = 2.05 z/h = 1
Condition of Approval (if applicable):
12/24/2014
OSP-0400-10
Page 3 of 7
Voltage RatingHeight
(in)
Width
(in)
Depth
(in)
Weight
(lbs)NEMA Rating Test Status
Individual Sections
38 kV 95 42 123 2,000 - 4,200 lbs 1, 3R Extrapolated
38 kV 95 42 123 4,200 Type 1 UUT-2
38 kV 95 42 123 4,200 - 6,000 lbs 1, 3R Interpolated
38 kV 95 42 123 4,500 lbs, 6,000 lbs Type 3R UUT-11
Notes
1. UUT1 consisted of two sections of the same dimensions with differing weights.
2. NEMA-3R non-walk-in enclosure: 107"H x 54"W x 132"D per section (+12"H x +12"W x +11"H per section).
IEM - 38kV Switchgear
I. Certified Products Table
12/24/2014
OSP-0400-10
Page 4 of 7
SEL-311 Differential and Distance Protection Relay Schweitzer 0311LXXB4 Extrapolated
SEL-351A Protection Relay Schweitzer 0351AXXB4 Extrapolated
SEL-387 Current Differ. And Overcurrent Relay Schweitzer 0387XXB4 Extrapolated
SEL-451 Protection Relay Schweitzer 045144151XXB4 UUT-1
SEL-487B Bus Differential Protection Relay Schweitzer 0487BXXB4 Interpolated
SEL-501 Overcurrent Relay Schweitzer 0501XXB4 Interpolated
SEL-751A Feeder Protection Relay Schweitzer 0751AXXB4 Interpolated
SEL-787 Transformer Differential Relay Schweitzer 0787EX1A1A0X UUT-1
BE1 Voltage Protective Relay Basler BE1−27-A3E-E1J UUT-2
BE1 Current Differential Protective Relay Basler BE1-CDS240-0N5F Interpolated
BE1 Overcurrent Protection System Basler BE1-951-B3ED0N1F Interpolated
BE1 Bus Differential Relay Basler BE1-87B-ED0N1F Interpolated
BE1 Under/Over Frequency Protective Relay Basler BE1-81O/U-XXX Interpolated
BE1 Directional Power Relay Basler BE1−32R-B3ED1PA UUT-2
Power Monitor 3000 Allen Bradley 1404-M405A-ENT UUT-1
GE Electronic Power Monitor (EPM) 5300P GE PL53002A0A00 Extrapolated
GE Electronic Power Monitor (EPM) 783 GE 783X9011001 UUT-2
GE Electronic Meter GE 783X901001 UUT-2
SEL-734 Advanced Metering System Schweitzer 0734009V1D11 UUT-1
Powerlogic ION 7330 Power Meter Square D S7330A0B0B0A UUT-2
FT1 Test Switch 6 Pole ABB FT129A516G01 UUT-1
Series 24 Control Switch Electroswitch 24202D UUT-1, UUT-2
Heavy Duty Indicating Light Red GE CR104PLT93R UUT-1, UUT-2
Heavy Duty Indicating Light Green GE CR104PLT93G UUT-1, UUT-2
Potential Transformer ABB 1VLT5212003507 UUT-1
15kVA Transformer IEM 89067-AFP-CT UUT-1
ITI 785-202 UUT-1
ITI 785-122MR UUT-2
38kV 1200A Vacuum Breaker VVAG-38140MABB UUT-2
38kV 2000A Vacuum Breaker VVAG-38240M-ABBBBBBA UUT-1
Innovative
Power
Technologies
Indicating Light
Switches
Power Components
Current Transformer
Power Monitors/Meters
Digital Relay
Part #Testing
Status
IEM - 38kV Switchgear
II. Certified Subcomponents Table
Internal Components Manufacturer
12/24/2014
OSP-0400-10
Page 5 of 7
3.47g 2.60g 1.45g 0.58g
12/24/2014
OSP-0400-10
Page 6 of 7
OSP APPLICATION Date: 8/29/2014
IEM – 38kV Switchgear
III. UUT Summary Sheets
Test Report 2014-08 – UUT 2
NEMA 1 Indoor Unit
Cold Formed Carbon Steel
42”W x 123”D x 95”H, 4,200 lbs
Floor mounted w/: (19) – 1/2” Gr. 5 bolts
Tested twice:
Setup B – bottom plates in place
Setup C – bottom plates removed
Internal Components Manufacturer Part #
BE-127 Voltage Relay Basler BE1−27-A3E-E1J
BE1-32R Directional Power Relay Basler BE1−32R-B3ED1PA
Powerlogic ION 7330 Power Meter Square D S7330A0B0B0A
KVV2C Electronic Switchboard Meter GE 783X901001
Heavy Duty Indicating Light Red GE CR104PLT93R
Heavy Duty Indicating Light Green GE CR104PLT93G
38kV 1200A Vacuum Breaker Innovative Power Technologies VVAG-38140MABB
Current Transformer ITI 785-122MR
Control Switch Electroswitch 24202D
Building Test SDS z/h
Horizontal Vertical
Code Criteria (g) AFLX-H ARIG-H AFLX-V ARIG-V
CBC 2013 ICC-ES
AC 156 2.05 1 3.28g 2.46g 1.37g 0.55g
Natural Frequencies* Test Results
F-B S-S V The UUT maintained structural integrity and
functionality after the AC156 test. 7.5 Hz 14.1 Hz >33 Hz
*as measured in Setup B The unit was full of content during testing.
12/24/2014
OSP-0400-10
Page 7 of 7