59
PENTAIR ENVIRONMENTAL SYSTEMS MP GROUPING CONTROLLER OPERATION AND CONFIGURATION MANUAL

OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

PENTAIR ENVIRONMENTAL SYSTEMS

MP GROUPING CONTROLLER

OPERATION AND CONFIGURATION MANUAL

Page 2: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

2

Table of Contents 1.0 QUICK START ..........................................................................................................................4

1.1 QUICK TIPS ABOUT KEYS ..........................................................................................................4 2.0 THE BASICS ............................................................................................................................5

2.1 THE SPLIT DISPLAY ..................................................................................................................5 2.2 PASSWORD KEY ......................................................................................................................5 2.3 EXIT KEY (STATUS SCREEN) .....................................................................................................6 2.4 SYSTEM STATUS KEY ...............................................................................................................7 2.5 STATUS SCREEN KEYS .............................................................................................................9 2.6 ALARM LIST KEY ................................................................................................................... 10 2.7 STATIONS KEY ..................................................................................................................... 11 2.8 ENVIRONMENT STATUS KEY .................................................................................................. 12 3.0 SETTINGS ............................................................................................................................ 14

3.1 % WATER BOOST .................................................................................................................. 14 3.2 RAIN SWITCH ....................................................................................................................... 15 3.3 SET TIME / DATE ................................................................................................................... 16 3.4 SYSTEM SETPOINTS ............................................................................................................. 17 4.0 PROGRAMS.......................................................................................................................... 18 4.1 THE PROGRAMMING STRUCTURE ........................................................................................... 18 4.2 PROGRAMS .......................................................................................................................... 19 4.3 OPTIONAL PROGRAMS .......................................................................................................... 25 4.4 LOOPING ............................................................................................................................. 25 4.5 FROST PROTECTION PROGRAM ............................................................................................. 26 4.6 HEAT PROTECTION PROGRAM ............................................................................................... 27 4.7 FERTIGATION PROGRAM ....................................................................................................... 28 4.8 FILTER FLUSH PROGRAM ....................................................................................................... 28 4.9 CURRENT PROFILE PROGRAM ............................................................................................... 29 4.10 POND FILL PROGRAM .......................................................................................................... 29 4.11 CLEAR PROGRAMS ............................................................................................................. 30 5.0 MANUAL OPERATION ............................................................................................................ 31

5.1 TEST OUTPUTS ..................................................................................................................... 31 5.2 MANUAL CONTROL ............................................................................................................... 32 5.3 SEMI AUTO START ................................................................................................................ 33 6.0 ALARMS .............................................................................................................................. 34

6.1 ALARM LIST .......................................................................................................................... 34 6.2 ALARM SETPOINTS ............................................................................................................... 34 7.0 SYSTEM CONFIGURATION ..................................................................................................... 39 8.0 SERIAL PORTS ..................................................................................................................... 44 9.0 CONNECTION INFORMATION .................................................................................................. 45 10.0 SYSTEM CONFIGURATION RECORDS ................................................................................... 46

Page 3: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

3

RAINMAN MP – 1 CARD – 16 OUTPUT CONFIGURATION ............................................................ 51 RAINMAN MP – 2 CARD – 32 OUTPUT CONFIGURATION ............................................................ 52 RAINMAN MP – 2 CARD – 48 OUTPUT CONFIGURATION ............................................................ 53 RAINMAN MP – 3 CARD – 64 OUTPUT CONFIGURATION ............................................................ 54 RAINMAN MP – 3 CARD – 96 OUTPUT CONFIGURATION ............................................................ 56 RAINMAN MP – 2 CARD – 16 OUTPUT CONFIGURATION WITH TWO WIRE IRRIGATION NETWORK 57 RAINMAN MP – 2 CARD – 32 OUTPUT CONFIGURATION WITH TWO WIRE IRRIGATION NETWORK 58

Page 4: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

4

1.0 QUICK START

1.1 QUICK TIPS ABOUT KEYS If you are familiar with computers and irrigation controllers, or you are just keen to get started, here are a few tips about the keys to get you started.

x First you need to press the PASSWORD key before you can enter a password.

x The SYSTEM STATUS key changes only the left hand side of the display and does not affect the screen that you are currently using.

x The EXIT key takes you back to the default status screen but does not undo changes you have made. (Older keypads may have a CANCEL key instead which does the same thing as the EXIT key).

x Function keys will jump you straight to the function that they select. Pressing the same function key again allows you to navigate through a function.

x You can also navigate using the NEXT and PREV keys in most cases.

x ENTER is required to confirm everything you type.

x Use the CLEAR key if you make a mistake. (will only remove the last action)

x The IRRIGATION STOP key is an emergency stop button that turns off all stations and pumps.

x To minimise the possibility of error, all times are in 24-hour format.

x The DONE key is used to go to the next step on multiple entry screens.

Page 5: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

5

2.0 THE BASICS

2.1 THE SPLIT DISPLAY The display is split into two parts as shown below.

12:00:03 | System idle 12:00 08/04/02 | Day 9

System status

User input

System status – the left hand side of the screen is used for system status and operated by the SYSTEM STATUS Key (see 2.4 SYSTEM STATUS KEY).

User input – the right hand side of the display is used for user input and operates with all other keys.

2.2 PASSWORD KEY The RAINMAN Mp controller uses multi-level password security to prevent unauthorised access. Until you have gained access to the controller the display backlight will turn on for only five seconds after each key press.

To get to the password screen press the PASSWORD key as shown.

The password entry screen is shown below.

Password

Enter password _

Passwordentry

Password entry – as the password is entered a * will appear for each number key that is pressed. If you make a mistake you can press the PASSWORD key and start again.

If, for example, the password is 1234, press the following keys.

When you have been granted access the display back light will remain on. Once you stop using the controller for more than 10 minutes it will automatically turn the display back light off and you will require a password to gain access again.

Page 6: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

6

2.3 EXIT KEY (STATUS SCREEN) The EXIT key takes you out of any other function and brings you to status screen.

2.3.1 IDLE STATUS When no programs are running and the rain switch is not activated the display will look similar to the display below.

15:35:00|System Idle 15:35 08/04/03| Day 9

Day number

Status indicator Time Time & Date

Status indicator – System idle shows that the system is idle.

Time – 15:35 shows the current time of day.

Day number – Day 9 shows the current day is Monday in the second week. The day number is from a 14-day cycle where day 1 is Sunday of the first week and day 14 is Saturday of the second week.

2.3.2 RAIN SWITCH STATUS The following is displayed when the rain switch is in operation.

15:35:35| Rain switch 15:35

08/04/03| Timer 1 hour 0 minutes Day 9

state

Status indicator

Rain switch

Time

Status indicator – Rain switch indicates that the rain switch function is activated.

Rain switch state – 1 hour 0 minutes indicates that the rain switch has been manually operated and has 1 hour remaining time to run. The rain switch state can display any of the following.

x Sensor – the rain sensor switch has activated the rain switch operation.

x Manual On – the rain switch has manually been enabled indefinitely

x The number of hours and minutes remaining for the manual operation of the rain switch.

(see 3.2 RAIN SWITCH for more information on rain switch operation).

2.3.3 PROGRAM STATUS The following is displayed when a program is running.

Page 7: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

7

1 Irrigation GP 1 00:05:00 Stns 1, 2, 3

remaining

Status indicator

Minutes

Group number

Station No’s

Status indicator – Irrigation 1 indicates that program 1 is running. The status indicator may also display Test to indicate valve test operation or Manual to indicate manual station on operation.

Group number – Gp 1 indicates that the program is up to group 1.

Station numbers – Stn 1,2,3 indicates that stations number 1, 2 and 3 are on due to this program.

Minutes remaining – 5 minutes indicates that there is five minutes remaining on the current group (group 1).

2.4 SYSTEM STATUS KEY The SYSTEM STATUS key allows the operator to select different aspects of the system status. It starts at the time and date then cycles through all the sensor inputs. It only displays sensors that have been configured so which sensors are shown may vary from controller to controller.

To select the next system status item press the SYSTEM STATUS key.

2.4.1 TIME AND DATE Time and date is the initial state that is shown below.

12:00:03 08/04/02

Date

Time

Time – 12:00:03 is the time current time in 24-hour format.

Date – 08/04/02 is the current date in the format DD/MM/YY so the date is the 8th of April ‘02.

Page 8: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

8

2.4.2 ADDRESS The DNP address is shown as follows:

Address

1

DNP address

The DNP address is the unique address used by the central computer to communicate with this controller.

2.4.3 SENSOR DISPLAY (CURRENT, MOISTURE, FLOW, PRESSURE, CURRENT SENSE, VOLUME, TEMPERATURE, LEVEL ETC.)

The sensor display shows the state of different sensors:

Volume 0 L

Sensor

name Sensor

reading Engineering units

Sensor name – Volume indicates the amount of water that has passed through the flow meter.

Sensor reading – 0 indicates that the water volume is currently 0.

Engineering units – Volume is measured in Litres.

2.4.3 SERIAL STATUS The serial port status is shown to help diagnose problems with serial communications.

Serial

--xxxx--

A B C D There are two characters shown for each port, A, B, C and D. They may be any of the following combinations:

Code Description xx Port is closed -- Port is open but not currently communicating T- Transmitting but not receiving -R Receiving but not transmitting TR Transmitting and receiving

Page 9: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

9

2.5 STATUS SCREEN KEYS

2.5.1 NEXT To skip to the next group in a program or the next station in a valve test press the NEXT key as shown.

2.5.2 PREVIOUS To move back to the previous group in a program or station on a valve test press the PREV key as shown.

2.5.3 PAUSE To temporarily turn off all stations and pumps (pause operation) press the OFF key as shown.

2.5.4 RESUME To resume after a pause operation (or to update the program display) press the ON key as shown.

Page 10: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

10

2.6 ALARM LIST KEY The alarm list shows a list of events which may indicate a problem with the irrigation system. The alarm list records the power on and off times, events that cause the irrigation system to skip to the next station, events that cause irrigation to stop immediately and other events that may indicate a potential problem. There are up to 10 alarms numbered 1 through 10. Alarm 1 is the most recent alarm and alarm 10 is the least recent alarm

Pressing the ALARM LIST key at any time will jump you straight to the alarm list screen from any other screen.

Alarm 1 11:58:12 15/11/04

Power on

Alarm description

number Alarm

Time Date Alarm Alarm

Alarm number – 1 indicates the most recent alarm.

Alarm time – 11:58:12 indicates that the alarm occurred at 11:58:12 am. The time is shown in 24-hour format.

Alarm date – 15/11/04 indicates that the alarm occurred on the 15th of November ’04.

Alarm description – Power on indicates that the alarm has been caused by the power being turned on.

To see the next alarm, use the ALARM LIST key as shown.

You can also use the PREV and NEXT keys to navigate through the alarms.

Page 11: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

11

2.7 STATIONS KEY The STATIONS key will bring up several screens displaying information on which stations are running and the current function of each pump and the status of pump run inputs as shown below.

Station/Pump Status

Stn On: 2,4,5

Pumps: OFF RUN OFF

Pump List

Station List

Station List – This is a list of the currently running stations.

Pump List – This is the current function of each pump connected to the controller where the left most is for pump 1.

The pump status can be :

x OFF – The pump is currently off

x RUN – The pump is running.

x FLT – The pump fault input is active and the pump can not run.

x xxHz – The pump is running on a VFD currently at xx Hz.

x LCL – The VFD Connecter to the pump is in Local mode.

x N/F – The pump selection mode is on flow and there is no flow rate entered for the pump.

x VFT – The Pump is connected to a VFD and the VFD is reporting a fault.

Input Status There are two input status screens, the first displays status the five possible pump run inputs and the filter flush input, the second displays the status of the jockey pump inputs.

Page 12: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

12

Label – Currently displayed input status screen

Input Status – The current status of the inputs, pumps are displayed from left to right.

The input status can be:

x N/A – The input is not configured.

x OFF – The pump /jockey pump input is currently inactive.

x RUN – The pump/jockey pump input is currently active.

x FLUSH – The filter flush input is currently active.

2.8 ENVIRONMENT STATUS KEY The environment status shows a list of sensor readings from the WeatherMaster 2000. The list consists of current readings and daily readings:

Current Readings:

Description Symbol Unit Air Temperature AirTmp DegC Wind Speed WndSpd Km/h Wind Direction WndDir Deg Solar Radiation SolRad W/m^2 Relative Humidity RelHum % Rainfall RnFall Mm Wind Run WndRun Km Peak Wind Gust PW Km/h Evaporation Evaptn Mm Daily Readings

Description Symbol Unit Average Air Temperature AvgTmp DegC Maximum Air Temperature MaxTmp DegC Minimum Air Temperature MinTmp DegC Average Wind Speed AvWSpd Km/h Maximum Wind Speed MxWSpd Km/h Current Wind Direction WndDir Deg Average Solar Radiation AvSRad W/m^2 Maximum Solar Radiation MxSRad W/m^2 Average Relative Humidity AvgHum % Maximum Relative Humidity MaxHum % Minimum Relative Humidity MinHum % Total Rainfall RnFall mm Ave Evaporation AvEvap mm Pressing the ENVIRONMENT STATUS key at any time will jump you straight to the Environment Status list screen from any other screen.

Page 13: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

13

AirTmp WndSpd WndDir SolRad

Data

21.1 10.0 46.0 724.0

Symbol

Symbol – represents each reading

Data – Readings with +/- 0.1 accuracy

To see the next batch of readings, use the ENVIRONMENT STATUS key. You can also use the PREV and NEXT keys to navigate through the readings.

Page 14: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

14

3.0 SETTINGS

3.1 % WATER BOOST The % Water Boost acts as a multiplier to change the amount of water used when running a program. The % Water Boost can be any value from 0% to 999%.

Pressing the % WATER BOOST key will scroll you through each program and allow you to change the percentage.

The % Water Boost screen will be similar to the display below.

1 Irrigation Budget 100%

% Water Boost

Run 120 mins Scaled 120 mins

Program Number

Program Number – indicates which program you are looking at, use the NEXT and PREV keys to scroll through the programs.

Water budget – 100% indicates that the current % Water Boost for Program 1 is 100%.

If for example you wish to change the % Water Boost to 50% press the following keys.

Page 15: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

15

3.2 RAIN SWITCH The rain switch prevents any programs from automatically starting for a specified number of hours or can stop all programs until told otherwise.

Pressing the RAIN SWITCH key at any time will jump you straight to the rain switch screen from any other screen.

The rain switch screen will be similar to the display below.

Rain switch

Timer 1 hour

Rain switch setting

Rain switch setting – Timer 1 hour indicates the number of hours that the rain switch will run for. If the word OFF appears on the screen this indicates that the rain switch timer is off.

If you want turn the rain switch on until you manually turn it off, press the following keys.

After pressing ENTER you will return to the status screen (see 2.3 EXIT KEY (STATUS SCREEN)). The status will show that the rain switch has been activated.

If you want to manually turn the rain switch timer off then press the following keys.

If for example you wish to turn the rain switch on for 24 hours (i.e. until the same time the following day) then press the following keys.

After pressing ENTER you will return to the status screen (see 2.3 EXIT KEY (STATUS SCREEN)). The status will show the number of hours and minutes remaining for the rain switch operation.

Page 16: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

16

3.3 SET TIME / DATE The SET TIME / DATE key allows you to set the time and date.

Pressing the SET TIME / DATE key at any time (except when you are already in the set time / date function) will jump you straight to the set time/date function from any other screen.

The set time screen is similar to the one shown below.

Set time / date

Time 11:31:47_

Currenttime

Current time – 11:31:47 indicates that current time is 11:31:47.

If for example you wish to set the clock to 11:40:00 then press the keys shown below.

After you press ENTER you will move to the set date screen as shown below.

Set time / date

Date 07/04/02_

Currentdate

Current date – 07/04/02 indicates that current time is the 7th of April ’02.

If for example you wish to set the date to 18/02/08 then press the keys shown below.

Page 17: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

17

3.4 SYSTEM SETPOINTS The system setpoints screen is used to enter the flow information for every pump and station connected to the controller.

Pressing the SYSTEM SETPOINTS key at any time will jump you straight to the flow entry function from any other screen.

The flow entry screen is similar to the one shown below.

Set total flow rate (L/sec)

Pump 1 = 60

Flow rate

The flow rate for pumps is the flow each pump will produce and the flow rate for each station is the flow required by that station. Enter the flow rate and press ENTER this will then automatically advance you to the next pump/station. You can also use the NEXT and PREV keys to scroll through the entries. Once all of the flow rates have been entered press the EXIT key to exit. These flow rates are used when the pump selection mode is set to flow. It calculates the total flow required by all the active stations and works out how many pumps are required to service the required flow rate.

Page 18: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

18

4.0 PROGRAMS

4.1 THE PROGRAMMING STRUCTURE There are fifteen standard programs and seven optional programs. A standard program consists of 5 start times and is capable of activating up to 20 groups. Each standard program has a 14-day Day Table and a Water Budget facility. If the current day is active and the current time is equal to any one of the five start times the program will commence. All stations in Group 1 will run for the run time in Group 1 scaled by the Water Budget if applicable.

Once Group 1 has finished Group 2 will commence in the same manner. All groups, assigned with valves and run times, will operate sequentially right through to Group 20 and once finished will return to an idle status.

NOTE: All 15 programs have the ability to overlap therefore care must be taken when setting up programs not to overload the system.

Start Times 1 2 3 4 5

Day Table

0101010 1010101

Group1 Runtime * Water budget

Group 1 stations

X mins

A B C D

Group2 Runtime * Water budget

Group 2 stations

Y mins

E F G H

Group20 Runtime * Water budget

Group 20 stations

Z mins

I J K L

Program 1 Program 15

Start Times 1 2 3 4 5

Day Table

0101010 1010101

Group1 Runtime * Water budget

Group 1 stations

X mins

A B C D

Group2 Runtime * Water budget

Group 2 stations

Y mins

E F G H

Group20 Runtime * Water budget

Group 20 stations

Z mins

I J K L

Page 19: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

19

4.2 PROGRAMS Standard programs are accessed through the PROGRAMS key. There are fifteen standard programs numbered 1 through 15. Each program has 5 start times, a day table and 20 groups.

Pressing the PROGRAMS key at any time (except when you are already in the programs function) will jump you straight to the programs function from any other screen.

The programs screen is shown below.

Programs

Program number 1

Program number

(1- 15)

Program number – 1 indicates that pressing ENTER will allow you to edit program number 1 of the currently selected library.

4.2.1 SELECTING A PROGRAM If for example you want to view or change program number 2, then press the following keys.

To select program 2 using the NEXT key, press the following keys.

You can press the NEXT key several times to select other programs. You can also use the PREV key to assist with selecting in this way.

Page 20: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

20

4.2.2 START TIME After you have chosen the program to view or change you will see the start time screen which looks similar to the display below.

Irrigation Start time 1

00:00 OFF OFF OFF OFF

Program

Start time

Start time no.

Program number – 1 indicates that you are accessing program number 1.

Start time – There are 5 start times per program, to navigate through the start times use the NEXT and PREV keys. For each start time, the OFF indicates that the start time is not used (set by pressing the OFF key). If all start times are OFF, the program may still be started by the Semi Auto Start function (see 5.3 SEMI AUTO START).

The start time is in 24-hour format.

If for example you want to start the program at 1:30am you would press the following keys.

All times are in 24-hour format so if you wish to start a program at 11:15pm then you would press the following keys.

Once all the start times you require are set up press the DONE key to progress to the next step.

Page 21: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

21

4.2.3 DAY TABLE After you have set up the start times and pressed the DONE key you will see the Day Table screen which looks similar to the display below.

Irrigation SMTWTFS SMTWTFS

Day table ������� �������

Program

Day table

_

Program number – 1 indicates that you are accessing program number 1.

Day table – ������� ������� indicates that the program is scheduled to run automatically on all days. The first digit corresponds to day 1 (Saturday of week 1) and the second digit corresponds to day 2 and so on. If a x is shown instead of a � this would indicate that the program is not scheduled to run on the corresponding day.

Set up the Day Table using the NEXT, PREV, ON and OFF keys. The 1 key and the ON key are equivalent. Similarly the 0 key and the OFF key are also equivalent. You can also use the NEXT and PREV keys to navigate across. Once finished you can use the DONE key and this will progress you to the next step.

If for example you want run a program from Monday to Friday every week then you press the following keys.

This would show a display as follows.

Irrigation SMTWTFS SMTWTFS

Day table ������� �������

Program

Day table

_

Page 22: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

22

4.2.4 GROUP RUNTIME AND SELECTION After you have set up the day table and pressed the DONE key you will see the group runtime and selection screen which looks similar to the display below.

Prog 1 Group 1 Runtime

Program number

Run Time

0:00 0:00 0:00 0:00 0:00

Group Number

Program number – 1 indicates that you are accessing program number 1.

Group number – 1 indicates that the cursor is currently on group 1 of program 1.

To select a group use the NEXT and PREV key until the cursor is on the group you wish to edit. To enter a runtime for the group enter the time when the cursor is at the appropriate group and press ENTER. If you wish to enter the group station selection screen without changing the runtime simply press the ENTER key. This will take you to the group station selection screen.

Pressing the DONE key in this screen will advance you to the next step which will be Pump selection if the pump selection is set to manual or the water budget entry.

4.2.5 GROUP STATION SELECTION Once you have entered the group runtime you will proceed to the group station selection screen similar to the display below.

Prog 1 Group 1 Stn 1 ON

Stns 1, 2, 3

Program number

Station Numbers

Group number

Program number – 1 indicates that you are accessing program number 1.

Group number – Group 1 indicates that Group 1 has been selected.

Station Numbers – 1,2,3 This is a list of the stations which are currently selected to run in this group.

To add stations to the group enter the station number followed by the ON key. Once the ON key is pressed the station will appear in the station numbers list.

For example, to add station 5 press the following:

To remove a station enter the station number and press the OFF key. Once the OFF key is pressed the station will disappear from the station numbers list.

Page 23: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

23

For example, to remove station 5 press the following:

Once you have entered the stations you require press the DONE key.

4.2.6 PUMP SELECTION The pump selection screen will only be available if the pump selection is set to manual. If the pump selection is set to manual then a screen similar to the display below will be displayed.

Irrigation Pump 1 ON

Program

Pumps 1

Pump Number

Pump List

Program number – 1 indicates that you are accessing program number 1.

Pump Number – Pump 1 ON indicates that pump 1 is selected and currently on.

Pump List – Pumps 1 is a list of the pumps which are currently selected to run in this program.

To add pumps to the list enter the pump number followed by the ON key. Once the ON key is pressed the pump will appear in the pump list.

For example, to add pump 2 press the following:

To remove a pump, enter the pump number and press the OFF key. Once the OFF key is pressed the pump will disappear from the pump list.

For example, to remove pump 2 press the following:

Once you have entered the pumps you require press the DONE key

Page 24: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

24

4.2.7 WATER BUDGET ENTRY After you have set up the Groups and pumps and pressed the DONE key you will see the Water Budget Entry screen which looks similar to the display below.

Irrigation Water budget 100%

Program

Run 120 mins Scaled 120 mins

Water Budget %

Run Time Scaled Run Time

Program – Irrigation indicates that you are accessing irrigation program.

Water Budget % – Water budget 100% indicates that the current water budget for this program is 100%.

Run Time – Run 120 mins. This is the entered run time for the program.

Scaled Run Time – Scaled 120 mins. This is the time the program will run for with the current water budget.

To change the water budget enter the new water budget and press ENTER. This will update the water budget and the scaled run time. The water budget can be between 0% and 999%

Once you have entered the water budget you require press the DONE key to progress to the next step.

4.2.8 SUMMARY At the end of the program all the information entered into the program is condensed in to a final summary screen. This screen is displayed for 10 seconds after the program has been entered for the user to perform a quick check of the program.

The program summary screen will look similar to the display below.

Irrigation Summary

2 starts 7 days 120 mins

Program

Starts Days Runtime Program – indicates that you are accessing program number 1 of the currently selected library.

Starts – 2 indicates the number of start times which are active.

Run time – 120 indicates that the total runtime of all groups.

Number of days – 7 indicates that the day table is scheduled to run the program for 7 days out of the 14-day cycle.

Page 25: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

25

4.3 OPTIONAL PROGRAMS Optional programs are accessed through the OPTIONAL PROGRAMS key. There are five optional standard programs numbered 16 through 20. Program 16 is Frost Protection, Program 17 is Heat Protection, Program 18 is Fertigation, Program 19 is Looping and Program 20 is a Filter Flush program.

Pressing the OPTIONAL PROGRAMS key will scroll you through each of the above programs. You can also use the NEXT and PREV keys to navigate through these programs.

The optional programs screen is similar to the one shown below.

Optional Programs

16 Looping

Program number

Program Name

4.4 LOOPING The looping program is designed to be used if there is a requirement for a program to run with a large number of starts. The operation of the looping program is different from the normal programs in that the watering restarts each time the loop time has expired and does not cease until it reaches the end time.

After pressing ENTER on the Loop Program screen you move to the start time screen. The start time screen is similar to the one shown below.

Loop Start End Cycle

Time 00:00 00:00 00:00

Loop Time

_

End Time

Cycle Time

Start Time – Time of the day the program will commence.

End Time – The time of day the program will stop looping.

Cycle Time – The time between restarting the program.

Enter the times as per standard times. Once you have entered the required times press the DONE key to progress to the next step. The next steps are as per the standard program starting from the day table entry (see 4.2.3 DAY TABLE).

Page 26: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

26

4.5 FROST PROTECTION PROGRAM The frost protection program works in a similar method to the standard programs except it does not use start times or day tables to start. The frost program will activate when the temperature outside drops below a predetermined setpoint. When the frost program activates it will stop any other programs which are running and continue to cycle until the temperature recovers above the frost setpoint.

After pressing ENTER on the Frost Protection screen you move to the low temperature screen. The low temperature screen is similar to the one shown below.

Frost Protection Min Off(deg) 0

Low temperature

Program Name

Program Name – Frost Protection indicates that you are accessing the Frost Protection program.

Low Temperature – indicates that the low temperature is set to 0 degrees.

If for example you want to enter a temperature of 5 degrees press the following keys.

To enter a negative number use the CLEAR key twice. The CLEAR key will first clear the number. If the CLEAR key is pressed again it will toggle the negative value on and off. Once the temperature has been entered the rest of the program entry is as per the standard programs from the group runtime entry (see 4.2.4 GROUP RUNTIME AND SELECTION).

Page 27: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

27

4.6 HEAT PROTECTION PROGRAM The Heat Protection Program works in a similar method to the standard programs except it does not use start times or day tables to start. The heat program will activate when the temperature outside is above the predetermined setpoint. When the heat program activates it will stop any other programs which are running and continue to cycle until the temperature drops below the heat setpoint.

After pressing ENTER on the Heat Protection Program screen you move to the high temperature screen. The high temperature screen is similar to the one shown below.

Heat Protection Max(deg) = 0

High temperature

Program Name

Program Name – Heat Protection indicates that you are accessing the Heat Protection program.

High Temperature – indicates that the high temperature is set to 0 degrees.

If for example you want to enter a temperature of 5 degrees press the following keys.

Once the temperature has been entered the rest of the program entry is as per the standard programs from the group runtime entry (see 4.2.4 GROUP RUNTIME AND SELECTION).

Page 28: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

28

4.7 FERTIGATION PROGRAM The Fertigation Program is used to control a fertigation pump connected to the irrigation system. After pressing ENTER on the Fertigation Program screen you move to the start time screen. The start time screen is similar to the one shown below.

Fertn Start Pre Post

Time Off Off Off

Start Time

Pre Wash Time

Post Wash Time

Start Time – Time of the day the program will commence.

Pre Wash time – The time the program will run each group for before activating the fertigation pump.

Post Wash time – The time each group will run for after the fertigation pump has stopped.

Enter the times as per standard times. Once you have entered the required times press the DONE key to progress to the next step. The next steps are as per the standard program starting from the day table entry (see 4.2.3 DAY TABLE).

The only difference is that the runtime for each group is the time the fertigation is applied to each group. The total runtime for each group is the addition of the pre wash time, the post wash time and the fertigation time.

4.8 FILTER FLUSH PROGRAM The filter flush program is used to control and flush up to six filters. After pressing ENTER on the Filter Flush Program screen you move to the start time screen. The start time screen is similar to the one shown below.

Flush Run Flush Pause

hr:min 1:00 0:00 0:00

Run Time

Flush Time

Pause Time

Run Time – This is how long the pumps have to run for before forcing a flush cycle to happen.

Flush time – This is the time each filter will flush for this time is in minutes and seconds.

Pause time – This is the time after flushing a filter and before each filter will flush for this time in minutes and seconds.

Note: The runtime can be overridden by a Pressure differential switch if one is connected to the controller.

Once the times are set up press the DONE key to finish.

Page 29: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

29

4.9 CURRENT PROFILE PROGRAM The current profile program is used to detect the deterioration of valve solenoids. It turns on each solenoid for three seconds in turn. This is done without turning on the pump. As each valve is turned on, the current consumption is measured. For consistency, the current profile program is configured the same as normal irrigation programs with five start times and a day table. The results of the current profile are stored in the controller for retrieval by the central control computer.

4.10 POND FILL PROGRAM The pond fill program is used to control a digital output which can be connected to a pump or outlet used to fill a pond or tank. This program uses the analogue level sensor to determine if the low start point or the high stop point has been reached.

The fill level can be specified differently depending on an off peak and an on peak time period.

In the above example the off peak time is set to 9pm to 5am so the on peak time will be 5am to 9pm.

Press the DONE key to move to the next screen.

As shown in the above examples. If the time is currently between 9pm and 5am and the level gets below 100 mm it the controller will turn on the pond fill output until the level reached 1m

There are also set points for the start and stop level for the on peak time period.

Page 30: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

30

4.11 CLEAR PROGRAMS The CLEAR PROGRAMS key can be used to clear an individual program or all programs in memory.

Pressing the CLEAR PROGRAMS key at any time will jump you straight to the Clear Programs function from any other screen.

The Clear Programs screen is similar to the one shown below.

Clear programs

Program number _ (0 = all)

Program number

Enter the program number you wish to clear or entering a 0 will clear all of the programs and then press ENTER. A conformation as shown below will appear.

Press CLEAR to confirm

clearing program 1

Press the CLEAR key to erase the program otherwise press the EXIT key.

Page 31: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

31

5.0 MANUAL OPERATION

5.1 TEST OUTPUTS The Test Outputs function turns on a station without turning on the pump. This is used for testing valves. To run a valve test press the TEST OUTPUTS key shown below.

The Test Outputs screen is shown below.

Valve test

Station number 1

Stationnumber

_

Station number – 1 indicate that the default station to test is station 1.

If you want to test station number 1 simply press ENTER as shown.

If for example you want to test station number 2 then, press the keys shown.

After pressing ENTER, it will confirm the station you have selected with a display similar to the one below.

Valve test

Valve 1 on

Stationnumber

Station number – 1 indicates that the station 1 valves have been opened.

After a short delay it will return to the status screen (see 2.3 EXIT KEY (STATUS SCREEN)). Once the valve test has started the NEXT and PREV keys can be used to scroll through the valves.

Page 32: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

32

5.2 MANUAL CONTROL The Manual Control function turns on a station (it also turns on pumps if applicable). To turn a station on press the MANUAL CONTROL key shown below.

The station on screen is shown below.

Manual Control Stn 5 OFF

Stns 3,4

Station List

Station List – This is a list of the stations that have been selected to run with this manual control.

To add stations to the list enter the station number and press the ON key. To remove a station enter the station number and press the OFF key. Once all the required stations have been entered press the DONE key and the Manual Control Runtime screen will be displayed as shown below:

Manual Control

Runtime: :10

Runtime The runtime is represented in hours and minutes. Enter the desired time and press ENTER. This will display the Manual Control pump selection screen, as shown below, only if pump control mode is set to pump selection.

Manual Control Pump 1 ON

Pumps 1,2

Pump list

.Pump List – this is a list of the pumps that will run with this manual control.

Once all the required pumps have been entered press the DONE key and the Manual Control will start immediately. When the Manual Control has finished the controller will revert to an idle state.

Page 33: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

33

5.3 SEMI AUTO START The Semi Auto Start function is used to manually start programs. To operate the Semi Auto Start press the SEMI AUTO key shown below.

The Semi Auto Start screen is shown below.

Semi auto

Program number 1 (1-21)

Program number

Program number – 1 indicates that the default program to start is program 1.

If you want to start program number 1 simply press ENTER as shown.

If for example you want to start program number 2, then press the keys shown.

After pressing ENTER, it will confirm the program you have selected with a display similar to the one below.

Semi auto

Program 1 started

Program number

Program number – 1 indicates that program number 1 will start at the beginning of the next minute.

After a short delay it will return to the status screen (see 2.3 EXIT KEY (STATUS KEY)).

Page 34: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

34

6.0 ALARMS Alarms are used to prevent damage to equipment as well as informing the user that something has changed in the system. When used correctly, alarms are a very useful tool in determining faults in the irrigation system. If an alarm is triggered, a message will be displayed on the screen and will remain there until a key has been pressed.

6.1 ALARM LIST

When pressed, the ALARM LIST key will display the last ten alarms along with the problem and time alarm occurred. For example:

ALARM 1 Power Restored AT 07:15:44 on 12/01/01

The NEXT and PREV keys will navigate through the most recent ten alarms.

6.2 ALARM SETPOINTS Displays Alarm Setpoints for the controller.

Pressing the ALARM SETPOINTS key will scroll through the following setpoints:

x Pump Fault X input – This alarm will only be shown if the corresponding pump input is activated in the config system screen. This is and entry on how long the input is to be active until a pump fault alarm is triggered. If the input remains on for longer than the time entered then a pump fault alarm will be triggered and the pump will not be run until the input is removed.

x Pump Station Fault input - This Alarm will appear if the Pump Station Fault input is set up in the system config. This is the time the switch has to remain active before the alarm is triggered. Enter the time in minutes and seconds and press ENTER. The OFF key can be used to disable this alarm.

x Filter Running sw Error - This Alarm will appear if the Filter Running input is set up in the system config. This is the time the switch has to remain active before the alarm is triggered. Enter the time in minutes and seconds and press ENTER. The OFF key can be used to disable this alarm.

x High Pressure Error sw - This Alarm will appear if the High Pressure Error sw is set up in the system config. This is the time the switch has to remain active while a pump is running before the alarm is triggered. When triggered it will shut down all programs. Enter the time in minutes and seconds and press ENTER. The OFF key can be used to disable this alarm.

x Int Pressure Error sw Warning - This Alarm will appear if the Intermediate Pressure Error sw is set up in the system config. This is the time the switch has to remain active while a pump is running before the alarm is triggered. When triggered it will skip the currently run group. If this alarm skips 3 times in a row it will then shutdown all programs. Enter the time in minutes and seconds and press ENTER. The OFF key can be used to disable this alarm.

Page 35: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

35

x Low Pressure Error sw Warning - This Alarm will appear if the Low Pressure Error sw is set up in the system config. This is the time the switch has to remain active while a pump is running before the alarm is triggered. When triggered it will skip the currently run groups. If this alarm skips 3 times in a row it will then shutdown all programs. The OFF key can be used to disable this alarm.

x High Level sw Warning - This Alarm will appear if the High Level Warning sw is set up in the system config. This is the time the switch has to remain active while a pump is running before the alarm is triggered. When triggered it will notify the central. Enter the time in minutes and seconds and press ENTER. The OFF key can be used to disable this alarm.

x High Level sw Error - This Alarm will appear if the High Level Error sw is set up in the system config. This is the time the switch has to remain active while a pump is running before the alarm is triggered. When triggered it will shut down all programs. Enter the time in minutes and seconds and press ENTER. The OFF key can be used to disable this alarm.

x Low Level sw Error - This Alarm will appear if the Low Level Error sw is set up in the system config. This is the time the switch has to remain active while a pump is running before the alarm is triggered. When triggered it will shut down all programs. Enter the time in minutes and seconds and press ENTER. The OFF key can be used to disable this alarm.

x Bore Draw Down Error sw - This Alarm will appear if the Bore Draw Down Error sw is set up in the system config. This is the time the switch has to remain active while a pump is running before the alarm is triggered. When triggered it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x Phase Failure Error sw - This Alarm will appear if the Phase Failure Error sw is set up in the system config. This is the time the switch has to remain active while a pump is running before the alarm is triggered. When triggered it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x Aux Fault Error sw - This Alarm will appear if the Aux Fault Error sw is set up in the system config. This is the time the switch has to remain active while a pump is running before the alarm is triggered. When triggered it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x Door Switch - This Alarm will appear if the Door Switch is set up in the system config. This is the time the switch has to remain active while a pump is running before the alarm is triggered. When triggered it will notify the central. Enter the time in minutes and seconds and press ENTER. The OFF key can be used to disable this alarm.

x Power Fail Switch - This Alarm will appear if the Power Fail Switch is set up in the system config. This is the time the switch has to remain active while a pump is running before the alarm is triggered. When triggered it will notify the central. Enter the time in minutes and seconds and press ENTER. The OFF key can be used to disable this alarm.

x Diff Pressure - This Alarm will appear if the Differential Pressure Switch is set up in the system config. This is the time the switch has to remain active while a pump is running before the alarm is triggered. When triggered it will notify the central. Enter the time in minutes and seconds and press ENTER. The OFF key can be used to disable this alarm.

x High TWIN 1 Error - The Current draw of the twin stations is monitored and the High Current Sense Error alarm is used when the current draw reaches a critical level and all outputs must be turned off to prevent any damage. There are two entries on this screen they are the high current sense setpoint and the alarm timeout. The setpoint is the current draw the local stations should not exceed (in mA) and the time out (in minutes and seconds) is the time the system will remain in the current sense error

Page 36: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

36

condition before triggering the alarm. When triggered it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x High TWIN 1 Warning - The Current draw of the twin stations is monitored and the High Current Sense Warning alarm is used when the current draw reaches a high level and the current station is to be skipped to try and reduce the current draw. There are two entries on this screen they are the high current sense warning setpoint and the alarm timeout. The setpoint is the current draw the local stations should not exceed (in mA) and the time out (in minutes and seconds) is the time the system will remain in the current sense warning condition before triggering the alarm. When triggered it will skip the currently running station. If this alarm is triggered three times in a row it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x Low TWIN Current Sense Error - The Current draw of the twin stations is monitored and the Low Current Sense Warning alarm is used when the current draw is less than expected. There are two entries on this screen they are the low current sense warning setpoint and the alarm timeout. The setpoint is the current draw the local stations should not run below (in mA) and the time out (in minutes and seconds) is the time the system will remain in the low current sense warning condition before triggering the alarm. When triggered it will skip the currently running station. If this alarm is triggered three times in a row it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x High Pressure X Error - This alarm will appear if the pressure transducer is setup. The high pressure alarm is used for when the pressure in the line reaches a critical level and the pumps must be shut down. There is two entries on this screen they are the pressure setpoint and the alarm timeout. The setpoint is the pressure the system should not exceed (in Kpa) and the time out (in minutes and seconds) is the time the system will remain in the high pressure condition before triggering the alarm. When triggered it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x Int Pressure X Warning - This alarm will appear if the pressure transducer is setup. The Intermediate pressure alarm is used for when the pressure in the line reaches a high level and the system must try and reduce this pressure by skipping to the next group. There is two entries on this screen they are the pressure setpoint and the alarm timeout. The setpoint is the pressure the system should not exceed (in Kpa) and the time out (in minutes and seconds) is the time the system will remain in the intermediate pressure condition before triggering the alarm. When triggered it will skip the currently running groups. If this alarm is triggered three times in a row it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x Low Pressure X Warning - This alarm will appear if the pressure transducer is setup. The Low pressure alarm is used for when the pressure in the line is too low to run the system properly. There is two entries on this screen they are the pressure setpoint and the alarm timeout. The setpoint is the pressure the system should not run below (in Kpa) and the time out (in minutes and seconds) is the time the system will remain in the low pressure condition before triggering the alarm. When triggered it will skip the currently running groups. If this alarm is triggered three times in a row it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x High Flow X Warning - This alarm will appear if the flow meter is setup. The High Flow alarm is used for when the flow in the line is higher than expected. There is two entries on this screen they are the flow setpoint and the alarm timeout. The setpoint is the flow the system should not exceed (in L/min) and the time out (in minutes and seconds) is the time the system will remain in the high flow condition before triggering the alarm. When triggered it will skip the currently running station. If this alarm is triggered three times in a row it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

Page 37: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

37

x Low Flow X Warning - This alarm will appear if the flow meter is setup for system 1. The Low Flow alarm is used for when the flow in the line is lower than expected. There is two entries on this screen they are the flow setpoint and the alarm timeout. The setpoint is the flow the system should run below (in L/min) and the time out (in minutes and seconds) is the time the system will remain in the low flow condition before triggering the alarm. When triggered it will skip the currently running station. If this alarm is triggered three times in a row it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x Unscheduled Flow X - This alarm will appear if the flow meter is setup for system 1. The Unscheduled Flow alarm is used when there is a flow above a certain level recorded while no irrigation is taking place. There is two entries on this screen they are the flow setpoint and the alarm timeout. The setpoint is the flow the system should not exceed while no irrigation is occurring (in L/min) and the time out (in minutes and seconds) is the time the system will remain in the unscheduled flow condition before triggering the alarm. When triggered it will notify the central this alarm is information only. The OFF key can be used to disable this alarm.

x High Fert Flow Warning - This alarm will appear if the fert flow meter is setup. The High Fert Flow alarm is used for when the fert flow is higher than expected. There is two entries on this screen they are the fert flow setpoint and the alarm timeout. The setpoint is the fert flow that should not exceed (in L/min) and the time out (in minutes and seconds) is the time the fert will remain in the high flow condition before triggering the alarm. The OFF key can be used to disable this alarm.

x Low Fert Flow Warning - This alarm will appear if the fert flow meter is setup. The Low Fert Flow alarm is used for when the fert flow is lower than expected. There is two entries on this screen they are the fert flow setpoint and the alarm timeout. The setpoint is the lowest fert flow that is acceptable (in L/min) and the time out (in minutes and seconds) is the time the fert will remain in the low flow condition before triggering the alarm. The OFF key can be used to disable this alarm.

x Unscheduled Fert Flow - This alarm will appear if the fert flow meter is setup for system 1. The Unscheduled fert Flow alarm is used when there is a fert flow above a certain level recorded while no irrigation is taking place. There is two entries on this screen they are the fert flow setpoint and the alarm timeout. The setpoint is the fert flow that should not be exceed while no irrigation is occurring (in L/min) and the time out (in minutes and seconds) is the time the system will remain in the unscheduled fert flow condition before triggering the alarm. When triggered it will notify the central this alarm is information only. The OFF key can be used to disable this alarm

x High Pump Current X Error - This alarm will appear if the pump current sensor is setup. The high pump current alarm is used for when the pump current reaches a critical level and the pumps must be shut down. There is two entries on this screen they are the current setpoint and the alarm timeout. The setpoint is the current the system should not exceed (in Amps) and the time out (in minutes and seconds) is the time the system will remain in the high current condition before triggering the alarm. When triggered it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x High Current Sense Error - The Current draw of the local stations is monitored and the High Current Sense Error alarm is used when the current draw reaches a critical level and all outputs must be turned off to prevent any damage. There are two entries on this screen they are the high current sense setpoint and the alarm timeout. The setpoint is the current draw the local stations should not exceed (in mA) and the time out (in minutes and seconds) is the time the system will remain in the current sense error condition before triggering the alarm. When triggered it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x High Current Sense Warning - The Current draw of the local stations is monitored and the High Current Sense Warning alarm is used when the current draw reaches a high level and the current station is to be skipped to try and reduce the current draw.

Page 38: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

38

There are two entries on this screen they are the high current sense warning setpoint and the alarm timeout. The setpoint is the current draw the local stations should not exceed (in mA) and the time out (in minutes and seconds) is the time the system will remain in the current sense warning condition before triggering the alarm. When triggered it will skip the currently running station. If this alarm is triggered three times in a row it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x Low Current Sense Error - The Current draw of the local stations is monitored and the Low Current Sense Warning alarm is used when the current draw is less than expected. There are two entries on this screen they are the low current sense warning setpoint and the alarm timeout. The setpoint is the current draw the local stations should not run below (in mA) and the time out (in minutes and seconds) is the time the system will remain in the low current sense warning condition before triggering the alarm. When triggered it will skip the currently running station. If this alarm is triggered three times in a row it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x High Level Error - This alarm will appear if the level sensor is setup. The high level alarm is used for when the level critical level and the pumps must be shut down. There is two entries on this screen they are the level setpoint and the alarm timeout. The setpoint is the level the system should not exceed (in mm) and the time out (in minutes and seconds) is the time the system will remain in the high level condition before triggering the alarm. When triggered it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x Level Warning - This alarm will appear if the level sensor is setup. The level warning is used for when the level reaches a low level. There is two entries on this screen they are the level setpoint and the alarm timeout. The setpoint is the level the system should not drop below (in mm) and the time out (in minutes and seconds) is the time the system will remain in the level warning condition before triggering the alarm. When triggered it will notify the central. The OFF key can be used to disable this alarm.

x Low Level Error - This alarm will appear if the level sensor is setup. The low level alarm is used for when the level critical level and the pumps must be shut down. There is two entries on this screen they are the level setpoint and the alarm timeout. The setpoint is the level the system should not drop below (in mm) and the time out (in minutes and seconds) is the time the system will remain in the low level condition before triggering the alarm. When triggered it will shut down any programs/manual controls that are running. The OFF key can be used to disable this alarm.

x RIC X High Flow - If the RIC port is enabled and RICs are set up, a high flow alarm will be activated for each RIC. The RIC high flow alarm is an information only alarm as the flow calculations and hence the alarms are only calculated at the end of the irrigation on that RIC. There is only one setting this is the High flow rate in L/min. This alarm is triggered if when the average flow rate calculated for that RIC on the last irrigation cycle exceeds this setting.

x RIC X Low Flow - If the RIC port is enabled and RICs are set up, a low flow alarm will be activated for each RIC. The RIC low flow alarm is an information only alarm as the flow calculations and hence the alarms are only calculated at the end of the irrigation on that RIC. There is only one setting this is the low flow rate in L/min. This alarm is triggered if when the average flow rate calculated for that RIC on the last irrigation cycle is less than this setting.

Page 39: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

39

7.0 SYSTEM CONFIGURATION This key will toggle through the configuration of the controller. The amount of values you can access will vary depending on the access you have. This menu sets up what is connected to the controller and how the controller will operate. Do not adjust these values unless you are authorized to do so as damage to the irrigation system is possible with incorrect settings.

Using the SYSTEM CONFIGURATION key the following information can be entered:

x Pump Configuration – This is the number of pumps physically connected to the controller. If no pumps are connected then set to 0 else up to 5 pumps can be configured. These pumps are in addition to the master valve output.

x Pump Control Method – This setting dictates how the multiple pumps will be controlled. There are 4 ways in which the pumps can be controlled, they are:

1) Flow – In this mode each station and pump has a flow rate. The controller will add the total flow required to service the active stations and run the appropriate pumps to give the required flow.

2) Program – In this mode every time a program is written or a manual control activated the user is specifically asked which pumps they need to run.

x Pump Configuration Fertigation Pumps – Set this parameter to 1 if a fertigation pump is connected otherwise set it to 0.

x Fertigation Program Mode – The fertigation pump can be controlled in two ways, time and volume. If you want the fertigation program to operate on a time basis set to 1, otherwise set to 2 if to operate using volume.

x Filter Configuration Filter Stations – This is the number of filter stations that are connected to the controller. If no filter stations are connected then set to 0 else up to 6 filter stations can be connected.

x Alarm Output – This creates an output that is activated when an alarm is active.

x Pond Fill Run Output – Set this to 1 to create an output that will be used by the pond fill program. (see 4.10 POND FILL PROGRAM)

x Local Station Configuration – This setting is the number of local stations connected to the controller. Local stations are the conventionally wired stations that are connected to the controller by a single common and a separate active for each station. These are usually 24VAC solenoids. The total number allowable will vary according to the number of pumps, fertigation and filter stations.

x Twin Stations Configuration – This setting will only be active if the TWIN (Two Wire Irrigation Network) port is set up in the system config and the number of TWIN stations connected to the controller via the TWIN translator is configured. A TWIN station is a station which is connected to the controller using only two wires, these wires can connect up to 96 stations. The controller will access these stations immediately after the local stations. This means that the first TWIN station will be addressed by the controller as the station number directly after the last local station. I.e. if there are 5 local stations and 10 TWIN stations the first TWIN station would be station 6 to the controller and the last TWIN station would be station 15.

x RIC Stations Configuration – This setting will only be active if the RIC (Remote Irrigation Controller) port is set up in the system config. This is used to set the number of stations connected to each RIC. There can be a maximum of 16 RICs with a maximum of 7 stations per RIC. A RIC’s stations entry will only be displayed if the previous RIC has an entry for the number of stations. i.e. RIC 2 number of stations will only be displayed if RIC

Page 40: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

40

1 has stations set. The controller will access these stations immediately after the local stations and the TWIN stations. This means that the first RIC station will be addressed by the controller as the station number directly after the last local plus TWIN station. i.e. if there are 5 local stations and 10 TWIN stations the first RIC station would be station 11 to the controller.

x Pump Settings Duty Pump – This setting is only used when the pump control mode is set to flow. It is the pump which will be selected first when determining the pumps to run.

x Cancel When Power Out – The RAINMAN controller has the ability to resume any irrigation programs during power up that were running when power was lost to the controller. The Cancel When Power Out setting is the maximum amount of time the power can be off for to resume programs. If the power is off for longer than this time no programs will be resumed. The OFF key can be used to disable this function.

x Watering End – The Water End time is a time of day at which no automatic irrigation is to take place. If an irrigation program is running and this time of day is reached the program will be stopped and an alarm logged. The OFF key can be used to disable this function.

x Rain Shutdown – If there is a weather station attached the rain shutdown will stop irrigation if the recorded rainfall reaches the setpoint.

x Pump Fault Sys X input – If the pumps connected to the controller have a fault output then this input needs to be configured in this menu. Enter the digital input number it is connected to and press ENTER. Once entered the switch will be enabled and the pump fault X input alarm will be activated (X represents the pump number 1-5). The OFF key can be used to disable this function.

x High Pressure Error sw – The High Pressure Error Switch is a pressure switch that will activate when the pressure in the line reaches a critical level and must be shut down. If a high-pressure switch is fitted then the input it is connected to must be set up in this menu. Enter the digital input number it is connected to and press ENTER. Once entered the switch will be enabled and the High Pressure Error sw alarm will be activated (see 6.0 ALARM LIST). The OFF key can be used to disable this function.

x Int Pressure Error sw – The Int Pressure Error Switch is a pressure switch that will activate when the pressure in the line reaches a high level. This causes the current group to skip to reduce the pressure in the line. If an int-pressure switch is fitted then the input it is connected to must be set up in this menu. Enter the digital input number it is connected to and press ENTER. Once entered the switch will be enabled and the Int Pressure Error sw alarm will be activated (see 6.0 ALARM LIST). The OFF key can be used to disable this function.

x Low Pressure Error sw – The Low Pressure Error Switch is a pressure switch which is active when the pressure in the line is to low. This causes the current group to skip to increase the pressure in the line. If a low-pressure switch is fitted then the input it is connected to must be set up in this menu. Enter the digital input number it is connected to and press ENTER. Once entered the switch will be enabled and the Low Pressure Error sw alarm will be activated (see 6.0 ALARM LIST). The OFF key can be used to disable this function.

x High Level sw - The High Level Error Switch is a level switch that will activate when the level in the dam or tank reaches an overflow level and must be shut down. If a high-level switch is fitted then the input it is connected to must be set up in this menu. Enter the digital input number it is connected to and press ENTER. Once entered the switch will be enabled and the High Level Error sw alarm will be activated (see 6.0 ALARM LIST). The OFF key can be used to disable this function.

x Low Level sw - The Low Level Error Switch is a level switch that will activate when the level in the dam or tank reaches a critical level and must be shut down. If a low-level switch is fitted then the input it is connected to must be set up in this menu. Enter the digital input number it is connected to and press ENTER. Once entered the switch will be enabled and the Low Level Error sw alarm will be activated (see 6.0 ALARM LIST). The OFF key can be used to disable this function.

Page 41: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

41

x Phase Failure Error sw – The Phase Failure sensor detects when one of the three phases is out, this means that the pumps should not run to prevent damage. If this sensor is installed then the input it is connected to must be set up in this menu. Enter the digital input number it is connected to and press ENTER. Once entered the switch will be enabled and the Phase Failure Error sw alarm will be activated (see 6.0 ALARM LIST). The OFF key can be used to disable this function.

x Aux Fault Error sw – The Aux Fault is a spare fault input that will shut the system down. If this sensor is installed then the input it is connected to must be set up in this menu. Enter the digital input number it is connected to and press ENTER. Once entered the switch will be enabled and the Aux Fault Error sw alarm will be activated (see 6.0 ALARM LIST). The OFF key can be used to disable this function.

x Rain Switch – The Rain switch is a sensor which will activate when a certain amount of rain has fallen. When the sensor is activated it will stop any programs which are running and display “Rain Switch Sensor” in the Idle Status display. If this sensor is installed then the input it is connected to must be set up in this menu. Enter the digital input number it is connected to and press ENTER.

x Door Switch – The Door Switch is a sensor which will activate when the cabinet in which the controller is stored in is opened.

x Diff Press input – If there are filter flush stations connected to the controller and they have a differential pressure switch override then this input needs to be configured in this menu. Enter the digital input number it is connected to and press ENTER. Once entered the switch will be enabled and the filter flush program run time can be overridden by this input. The OFF key can be used to disable this function.

x Pressure X Input – This is the pressure transducer setup for the system. If a pressure transducer is installed press the ON key and two entries will appear. The first is the analogue input number this is the analogue input that the pressure transducer is to be connected to, enter the input number and press ENTER. The second entry is the maximum scale of the pressure transducer in kPa, enter the maximum scale (located on the transducer) and press ENTER. Once set up this will enable a High, Intermediate and Low pressure alarms (see 6.0 ALARM LIST). The OFF key can be used to disable this function.

x Temp Input – This is the temperature transducer setup for the system. If a temperature transducer is installed press the ON key and three entries will appear. The first is the analogue input number this is the analogue input that the temperature transducer is to be connected to, enter the input number and press ENTER. The second entry is the minimum reading, pressing the CLEAR key will put up a negative symbol it the number is negative, enter the minimum reading and press ENTER. The third entry is the maximum scale of the temperature transducer in deg, enter the maximum scale (located on the transducer) and press ENTER. Once set up this will enable the heat and frost programs. The OFF key can be used to disable this function.

x Moisture Input – This input is for a 4 – 20mA moisture sensor. If you wish to connect a moisture sensor to the controller press the ON key and two entries will appear. The first is the analogue input number this is the analogue input that the Moisture sensor is to be connected to, enter the input number and press ENTER. The second entry is the maximum scale of the moisture sensor in %, enter the maximum scale and press ENTER.

x Flow X Input – Flow input is the setup for the flow meter. There is three different methods to measure the flow which and be toggled through using the ON key, they are:

x Analogue – This is for a flow meter that has a 4-20mA output, usually Mag flow meters. There are two entries required for this type of flow meter. The first is the analogue input number; this is the analogue input that the Flow meter is to be connected to, enter the input number and press ENTER. The second entry is the maximum scale of the flow meter in L/min, enter the maximum scale and press ENTER.

Page 42: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

42

x Frequency – This is for a flow meter with a high pulse rate, usually used on insertion paddle wheel type flow meters. There are two entries required for this type of flow meter. The first is the frequency input number, this is the input that the Flow meter is to be connected to, enter the input number and press ENTER. The second entry is the litres per pulse of the flow meter, enter the litres per pulse and press ENTER.

x Period – This is for a flow meter with a low pulse rate, usually used on inline type flow meters. There are two entries required for this type of flow meter. The first is the frequency input number, this is the input that the Flow meter is to be connected to, enter the input number and press ENTER. The second entry is the litres per pulse of the flow meter, enter the litres per pulse and press ENTER.

x Fert Flow Input – Flow input is the setup for the fert flow meter. It is set up the same as the flow meter as described above.

x Pump Current X Input - This is the pump current sensor setup for the system. If a current sensor is installed press the ON key and two entries will appear. The first is the analogue input number this is the analogue input that the current sensor is to be connected to, enter the input number and press ENTER. The second entry is the maximum scale of the current sensor in Amps, enter the maximum scale and press ENTER. Once set up this will enable a High current alarms (see 6.0 ALARM LIST). The OFF key can be used to disable this function.

x Level Input - This input is for a 4 – 20mA level sensor. If you wish to connect a level sensor to the controller press the ON key and two entries will appear. The first is the analogue input number this is the analogue input that the level sensor is to be connected to, enter the input number and press ENTER. The second entry is the maximum scale of the level sensor in mm, enter the maximum scale and press ENTER.

x Slave Cards – This entry is to activate any slave cards a controller is connected to. Pressing the ON key will make the system automatically search for any slave cards. If any cards are detected the total configuration will be displayed. For example:

Slave cards (ON: auto detect)

1 slave card 48DO/8DI/4AI

Digital outputs

Digital inputs

Analogue inputs

The example above shows the standard two card controller configuration of with a total of 48 Digital Outputs (relays), 8 Digital Inputs (switches) and four Analogue Inputs (sensors).

x TWIN Serial Port – The TWIN serial port is the port the Two-Wire interface translator will be connected to. Select the port the Two-Wire interface translator is to be connected to and press ENTER. Activating this port will activate all the features of the TWIN system including High and low TWIN current alarm setpoints, Number of TWIN stations, and TWIN Curr System Status. The OFF key can be used to disable this function.

x TWIN Special Functions – This area is used when first setting up a TWIN translator board. Under this menu you can set the sensitivity or set up the decoder map by pressing the ON key.

x RIC Serial Port – The RIC serial port is the port the Remote Irrigation Controller Master will be connected to. Select the port the Remote Irrigation Controller Master is to be connected to and press ENTER. Activating this port will activate all the features of the RIC system including Number of RIC stations, and RIC System Status displays. The OFF key can be used to disable this function.

x RIC Comms Timeout – Once RICs have been configured this option will become available. Enter the time that the controller will wait for a reply from the remote RICs and press ENTER.

Page 43: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

43

x RIC Status Interval – Once RICs have been configured this option will become available. Enter the time period that the controller will poll RICs for status and press ENTER.

x RIC X Litres per pulse – For every RIC configured there is and entry to let the controller know the size of the flow meter connected to the RIC. Enter the litres per pulse of the flow meter connected to the RIC and press ENTER. The OFF key can be used to disable this function.

x Weather Station Serial Port – The Weather Station serial port is the port the Weather Station will be connected to. Valid ports are 2 – Port B and 4 – Port D. Select the port the Weather Station is to be connected to and press ENTER. Activating this port will activate all the features of the Weather Station system including Environ Status display activation. The OFF key can be used to disable this function.

x Moisture Probe MODBUS port – The Moisture Probe serial port is the port which is connected to Sentek moisture probes. Valid ports are 2 – Port B and 4 – Port D. Select the port the Moisture Probes are to be connected to and press ENTER. Activating this port will activate all the features of the Moisture Probe system including Environ Status display activation. The OFF key can be used to disable this function.

x Moisture Probe Settings – When the Moisture Probe port is configured this option will become available. Configure the number of probes attached by imputing the number and pressing ENTER. If using RS485 up to 32 probes may be connected.

x Station Delay – Station delay is the time after the last station closed before the current station opens. This is used on a system that requires the pressure to build up before opening the next station. This time is in minutes and seconds, enter the required time and press ENTER. The OFF key can be used to disable this function.

x Clear Monthly Volumes – This is used for commissioning the clear any volume which the controller has accumulated before installation. Pressing the clear key will cause all current volume data to be lost and reset to 0.

x DNP serial port 1, 2 and 3 – DNP can operate on up to three serial ports and the controller will automatically forward messages from one serial port to another if necessary. Select the ports that the controller will use for DNP.

x Set DNP Baud Rate – This tells the controller what board rate to talk to other DNP devices. This should be set the same for all DNP devices and the central. Supported baud rates are 1200, 2400, 4800, 9600, 19200, 57600, 115200.

x Controller Address – this is the address for the local controller. It is a unique number if you want to override the DIP switch settings. Use the OFF key to default to reading the DIP switches.

x DNP Master Station – This is the address for the central control computer. It should normally be set to 43690.

Page 44: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

44

8.0 SERIAL PORTS The master controller board is fitted with four serial ports, named A, B, C and D. Serial ports on slave cards can not be used except to communicate with the master. Each serial port can be configured for either RS-232 or RS-485 operation via jumper settings. The positioning of the jumpers varies between board models but the numbering is consistent across all of them:

Port Jumper number RS-232 RS-485 A J17 remove 1-2

B J14 1-2 2-3

C J15 1-2 2-3

D J16 1-2 2-3 Note: the serial port jumpers only affect the receive side of the circuit. An incorrectly configured serial port will still be able to transmit data but will be unable to receive any response.

On the terminating ends of an RS-485 cable it is necessary to set the terminating resistors. Installing a jumper across pins 1-2 of the following connectors will enable the terminating resistors.

Port Terminating resistor jumpers

A J2, J3

B J4, J5

C J6, J7

D J8, J9

Page 45: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

45

9.0 CONNECTION INFORMATION To maximize the available outputs on the RAINMAN Mp Grouping controller the output connections will vary depending on the following parameters:

x Number of pumps, fertigation pumps.

x Number of filter stations.

x Disable Output, Alarm Output, Pond Fill Output, Fault Reset Output ON/OFF

x Number of conventional stations.

On the RAINMAN Mp Grouping 15 the pumps will start from output 15 and work their way back. The output directly before the number of pumps will be for the fertigation output (if defined) and the filter stations will precede this fertigation output directly Disable output, Alarm output Pond Fill output and finally the Fault Reset output. The conventional stations will start from output 1 and through to number of conventional stations.

For example:

No. Pumps 2 4 0 4 1

No. Fert 0 1 0 1 1

No. Filters 4 0 0 3 2

Disable Output

0 0 0 1 0

Alarm Output

0 0 0 1 0

Pond Fill Output

0 0 0 1 1

Fault Reset Output

0 0 0 1 0

No. Con Stn 6 9 14 2 0

Output 1 Stn 1 Stn 1 Stn 1 Stn 1 Spare

Output 2 Stn 2 Stn 2 Stn 2 Stn 2 Spare

Output 3 Stn 3 Stn 3 Stn 3 Spare Spare

Output 4 Stn 4 Stn 4 Stn 4 Fault Reset Spare

Output 5 Stn 5 Stn 5 Stn 5 Pond Fill Spare

Output 6 Stn 6 Stn 6 Stn 6 Alarm Spare

Output 7 Spare Stn 7 Stn 7 Disable Spare

Output 8 Spare Stn 8 Stn 8 Filter 3 Spare

Output 9 Spare Stn 9 Stn 9 Filter 2 Spare

Output 10 Filter 4 Spare Stn 10 Filter 1 Spare

Output 11 Filter 3 Fert 1 Stn 11 Fert 1 Pond Fill

Output 12 Filter 2 Pump 4 Stn 12 Pump 4 Filter 2

Output 13 Filter 1 Pump 3 Stn 13 Pump 3 Filter 1

Output 14 Pump 2 Pump 2 Stn 14 Pump 2 Fert 1

Output 15 Pump 1 Pump 1 Spare Pump 1 Pump 1

Page 46: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

46

10.0 SYSTEM CONFIGURATION RECORDS NOTE: Enter in the Mp configuration settings for future reference.

System Configuration Settings Settings Settings Settings Settings COMMENTS (date) Pump Settings Local Pumps Pump Control Method Pump Settings Fertigation Pumps Fertigation Program Mode Filter Setting Filter Stations Disable Output Alarm Output Alarm Output Timeout Pond Fill Output Fault Reset Output Fault Reset Output Timeout Local Station Settings TWIN Stations RIC Stations Pump Settings Duty Pump Cancel When Power Out Water End Rain Shutdown Pump Fault Pump Station Fault Pump/Bore Running Jockey Pump Running Filter Running sw High Pressure Error sw Int Pressure Warning sw Low Pressure Warning sw High Level sw Low Level sw Bore Draw Down Error sw Phase Failure Error sw Aux Fault Error sw Rain Switch Door Switch Power Fail Switch Diff Pressure Pressure 1 Input Temp Input Moisture Input Flow Input

Page 47: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

47

Fert Flow Input System Configuration Settings Settings Settings Settings Settings Pump Current Input Level Input Slave Cards TWIN Serial Port RIC Serial Port RIC Comms Timeout RIC Status Interval RIC Litres per pulse RIC Litres per pulse cont. Weather Station Serial Port Moisture Probe Serial Port Num of Moisture Probes VFD Serial Port VFD Model Pump Delays VFD PID VFD Pressure Setpoint Station Delays DNP Serial Port DNP Baud Rate Controller Address DNP Master Station

Page 48: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

48

Index A address

DNP............................................... 43 DNP master ................................... 43 status ............................................... 8

alarm list key ..................................... 10 alarm setpoints .................................. 34

int pressure warning sw 1 ............. 34 alarms

list .................................................. 10 aux fault error sw 1 ........................... 35

B baud rate

DNP............................................... 43 bore draw down error sw 1 ............... 35

C calibration

RIC ................................................ 43 connection information ..................... 45 current system status ........................... 7

D day table

programs key ........................... 21, 24 DNP

address....................................... 8, 43 baud rate ........................................ 43 controller address .......................... 43 serial port ...................................... 43 station address ............................... 43

E exit key ................................................ 6

F fertigation

program mode ............................... 39 filter stations

configuring .................................... 39 flow system status ............................... 7

H high current sense error .................... 37 high current sense warning ............... 37 high flow 1 warning .................... 36, 37 high pressure 1 error ............. 36, 37, 38 high pressure error sw 1 .................... 34 high TWIN current sense error ......... 35 high TWIN current sense warning .... 36

I idle

status display ................................... 6 int pressure 1 warning ................. 36, 38 int pressure warning sw 1 ................. 34

J jumpers

serial ports ..................................... 44

K keys

alarm list ....................................... 10 exit .................................................. 6 next ................................................. 9 off .................................................... 9 on .................................................... 9 password ......................................... 5 prev ................................................. 9 rain switch ..................................... 15 semi auto ....................................... 33 set time / date ................................ 16 station on ....................................... 32 stations .......................................... 11 system status ................................... 7 valve test ....................................... 31 water budget .................................. 14

L library

status display ................................... 6 local stations

configuring .................................... 39 looping program ................................ 25 low current sense error ...................... 38 low flow 1 warning ........................... 37

Page 49: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

49

low pressure 1 warning ..................... 36 low pressure warning sw 1 ................ 35 low TWIN current sense error .......... 36

M moisture system status ........................ 7 monthly volumes

clearing .......................................... 43

N next ...................................................... 9

O optional programs key....................... 25

P password key ....................................... 5 pause ................................................... 9 phase failure error sw 1 ..................... 35 pressure system status ......................... 7 previous ............................................... 9 program library

status display ................................... 6 program status display ........................ 6 programs

day table .................................. 21, 24 key ................................................. 19 looping .......................................... 25 optional ......................................... 25 start time........................................ 20 station number ............................... 22

pumps configuration ................................. 39 control method .............................. 39

R rain switch

key ................................................. 15 status display ................................... 6

resume ................................................. 9 RIC

litres per pulse ............................... 43 serial port ...................................... 42

RIC high flow ................................... 38 RIC low flow..................................... 38 RIC stations ....................................... 39

S semi auto key .................................... 33 sense system status ............................. 7 sensors

status ............................................... 8 serial port

DNP .............................................. 43 RIC ................................................ 42 TWIN ............................................ 42 weather station .............................. 43

serial ports jumpers ......................................... 44 status ............................................... 8

set time / date key ................................................. 16

start time programs key ................................ 20

station delay ...................................... 43 station number

programs ....................................... 22 station on key .................................... 32 stations

RIC stations .................................. 39 TWIN ............................................ 39

stations key ....................................... 11 status (exit key) ................................... 6 system configuration ......................... 39

aux fault error sw sys 1 ................. 41 cancel when power out ................. 40 clear monthly volumes .................. 43 controller address .......................... 43 DNP address ................................. 43 DNP baud rate ............................... 43 DNP master address ...................... 43 DNP serial port ............................. 43 fertigation program mode ............. 39 fertigation pumps .......................... 39 filter stations ................................. 39 flow sys 1 input ....................... 41, 42 high pressure error sw sys 1 .......... 40 int pressure warning sw sys 1 ....... 40 local stations ................................. 39 low pressure warning sw sys 1 ..... 40 moisture sys 1 input ...................... 41 phase failure error sw sys 1 .......... 41 pressure sys 1 input ....................... 41 pump control method .................... 39 pumps ............................................ 39 rain switch ..................................... 41

Page 50: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

50

records ........................................... 46 RIC litres per pulse ....................... 43 RIC serial port ............................... 42 RIC stations ................................... 39 slave cards ..................................... 42 station delay .................................. 43 TWIN serial port ........................... 42 TWIN special functions ................ 42 TWIN stations ............................... 39 water end ....................................... 40 weather station serial port ............. 43

system status address............................................. 8 pressure, current, moisture, flow and

current sense................................ 7 sensor .............................................. 8 time and date ................................... 7

system status key................................. 7

T time and date system status ................. 7

TWIN serial port ...................................... 42 special functions ........................... 42

TWIN stations ................................... 39

U unscheduled flow 1 ........................... 37

V valve test key .................................... 31

W water budget

key ................................................. 14 status display ................................... 6

weather station display ........................................... 12 serial port ...................................... 43

Page 51: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

RAINMAN MP – 1 CARD – 16 OUTPUT CONFIGURATION

B C D

Com Port

B +

B - E D +

D - E

A +

A - E C +

C - E

M V

1 2 3 4 5 6 7 C C 1 2 3 4 C C 1 2 V C

8 9 10 11 12 13 14 15 C C 5 6 7 8 C C 3 4 V C

C

C

Digital Outputs Analogue Inputs RS 485 Digital Inputs

+ - E

Power

24V AC/DC

Page 52: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

52

RAINMAN MP – 2 CARD – 32 OUTPUT CONFIGURATION

B C D

Com Port

B +

B - E D +

D - E

A +

A - E C +

C - E

M V

1 2 3 4 5 6 7 C C 1 2 3 4 C C 1 2 V C

8 9 10 11 12 13 14 15 C C 5 6 7 8 C C 3 4 V C

C

C

Digital Outputs Analogue Inputs RS 485 Digital Inputs

+ - E

Power

24V AC/DC

B C D

Com Port

B +

B - E D +

D - E

A +

A - E C +

C - E

16

17 18 19 20 21 22 23 C C 9 10 11 12 C C 5 6 V C

24 25 26 27 28 29 30 31 C C 13 14 15 16 C C 7 8 V C

C

C

Digital Outputs Analogue Inputs RS 485 Digital Inputs

+ - E

Power

24V AC/DC

Page 53: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

53

RAINMAN MP – 2 CARD – 48 OUTPUT CONFIGURATION

B C D

Com Port

B +

B - E D +

D - E

A +

A - E C +

C - E

M V

1 2 3 4 5 6 7 C C 1 2 3 4 C C 1 2 V C

8 9 10 11 12 13 14 15 C C 5 6 7 8 C C 3 4 V C

C

C

Digital Outputs Analogue Inputs RS 485 Digital Inputs

+ - E

Power

24V AC/DC

B C D

B+ B- E D+ D- E

A+ A- E C+ C- E

16 17 18 19 20 21 22 23 C C 32 33 34 35 36 37 38 39 C C

24 25 26 27 28 29 30 31 C C 40 41 42 43 44 45 46 47 C C

Digital Outputs RS 485 Digital Outputs

+ - E

24V AC/DC

Power

Page 54: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

54

RAINMAN MP – 3 CARD – 64 OUTPUT CONFIGURATION

B C D

Com Port

B +

B - E D +

D - E

A +

A - E C +

C - E

M V

1 2 3 4 5 6 7 C C 1 2 3 4 C C 1 2 V C

8 9 10 11 12 13 14 15 C C 5 6 7 8 C C 3 4 V C

C

C

Digital Outputs Analogue Inputs RS 485 Digital Inputs

+ - E

Power

24V AC/DC

B C D

Com Port

B +

B - E D +

D - E

A +

A - E C +

C - E

16

17 18 19 20 21 22 23 C C 9 10 11 12 C C 5 6 V C

24 25 26 27 28 29 30 31 C C 13 14 15 16 C C 7 8 V C

C

C

Digital Outputs Analogue Inputs RS 485 Digital Inputs

+ - E

Power

24V AC/DC

B C D

B+ B- E D+ D- E

A+ A- E C+ C- E

32 33 34 35 36 37 38 39 C C 48 49 50 51 52 53 54 55 C C

40 41 42 43 44 45 46 47 C C 56 57 58 59 60 61 62 63 C C

Digital Outputs RS 485 Digital Outputs

+ - E

24V AC/DC

Power

Page 55: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

55

RAINMAN MP – 3 CARD – 80 OUTPUT CONFIGURATION

B C D

Com Port

B +

B - E D +

D - E

A +

A - E C +

C - E

M V

1 2 3 4 5 6 7 C C 1 2 3 4 C C 1 2 V C

8 9 10 11 12 13 14 15 C C 5 6 7 8 C C 3 4 V C

C

C

Digital Outputs Analogue Inputs RS 485 Digital Inputs

+ - E

Power

24V AC/DC

B C D

B+ B- E D+ D- E

A+ A- E C+ C- E

16 17 18 19 20 21 22 23 C C 32 33 34 35 36 37 38 39 C C

24 25 26 27 28 29 30 31 C C 40 41 42 43 44 45 46 47 C C

Digital Outputs RS 485 Digital Outputs

+ - E

24V AC/DC

Power

B C D

B+ B- E D+ D- E

A+ A- E C+ C- E

48 49 50 51 52 53 54 55 C C 64 65 66 67 68 69 70 71 C C

56 57 58 59 60 61 62 63 C C 72 73 74 75 76 77 78 79 C C

Digital Outputs RS 485 Digital Outputs

+ - E

24V AC/DC

Power

Page 56: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

56

RAINMAN MP – 3 CARD – 96 OUTPUT CONFIGURATION

B C D

B+ B- E D+ D- E

A+ A- E C+ C- E

MV 1 2 3 4 5 6 7 C C 16 17 18 19 20 21 22 23 C C

8 9 10 11 12 13 14 15 C C 24 25 26 27 28 29 30 31 C C

Digital Outputs RS 485 Digital Outputs

+ - E

24V AC/DC

Power

B C D

B+ B- E D+ D- E

A+ A- E C+ C- E

32 33 34 35 36 37 38 39 C C 48 49 50 51 52 53 54 55 C C

40 41 42 43 44 45 46 47 C C 56 57 58 59 60 61 62 63 C C

Digital Outputs RS 485 Digital Outputs

+ - E

24V AC/DC

Power

B C D

B+ B- E D+ D- E

A+ A- E C+ C- E

64 65 66 67 68 69 70 71 C C 80 81 82 83 84 85 86 87 C C

72 73 74 75 76 77 78 79 C C 88 89 90 91 92 93 94 95 C C

Digital Outputs RS 485 Digital Outputs

+ - E

24V AC/DC

Power

Page 57: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

57

RAINMAN MP – 2 CARD – 16 OUTPUT CONFIGURATION WITH TWO WIRE IRRIGATION NETWORK

B C D

Com Port

B +

B - E D +

D - E

A +

A - E C +

C - E

M V

1 2 3 4 5 6 7 C C 1 2 3 4 C C 1 2 V C

8 9 10 11 12 13 14 15 C C 5 6 7 8 C C 3 4 V C

C

C

Digital Outputs Analogue Inputs RS 485 Digital Inputs

+ - E

Power

24V AC/DC

+ - E

Power

36V AC

Two Wire 2 — Live (White)

3 — Neutral (Yellow)

1 2 3

485 COMMS LEDS EARTH

+ - E

LED Legend 1 — Power

2 — Signalling 3 — Line Active

4 — Comms 1 2 3 4

Page 58: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

58

RAINMAN MP – 2 CARD – 32 OUTPUT CONFIGURATION WITH TWO WIRE IRRIGATION NETWORK

B C D

B+ B- E D+ D- E

A+ A- E C+ C- E

MV 1 2 3 4 5 6 7 C C 16 17 18 19 20 21 22 23 C C

8 9 10 11 12 13 14 15 C C 24 25 26 27 28 29 30 31 C C

Digital Outputs RS 485 Digital Outputs

+ - E

24V AC/DC

Power

+ - E

Power

36V AC

Two Wire 2 — Live (White)

3 — Neutral (Yellow)

1 2 3

485 COMMS LEDS EARTH

+ - E

LED Legend 1 — Power

2 — Signalling 3 — Line Active

4 — Comms 1 2 3 4

Page 59: OPERATION AND CONFIGURATION MANUAL · To resume after a pause operation (or to update the program display) press the ON key as shown. 10 2.6 ALARM LIST KEY The alarm list shows a

New South Wales: Ph: 1300 797 246268 Milperra Rd, Milperra, NSW 2214

Victoria: Ph: (03) 5821 404419a New Dookie Rd, Shepparton, VIC 3630

Western Australia: Ph: (08) 9477 11881/30 Oxleigh St, Malaga, WA 6090

www.aquamonix.com.au Ph: 1300 797 246