OIL INDIA LIMITED (A Government of India Enterprise)
P.O. Duliajan – 786602, Assam, India Website: www.oil-india.com
Corrigendum No. 1 to IFB No. CPI9724P19
Engineering, Fabrication and Supply of Modular Electrical Packages
respectively for OCS at Nadua and GGS at East Khagorijan in Dibrugarh district, Assam
1. This Corrigendum is issued to notify the following:
a) In view of queries received from bidders in matter corresponding to
technical SOW, the final OIL’s responses to the queries are generated. All the bidders are requested to refer to Annexure- I attached herewith.
b) Revised Price Bid format/ SOR is attached herewith as Attachment – 1 c) Detailed Electrical schedule/ BOQ for GGS at East Khagorijan and OCS
at Nadua are attached herewith as Attachment – 2 & 3 respectively.
d) Heat Tracing Line List for GGS at East Khagorijan and OCS at Nadua has been updated. Refer respective Attachment – 4 & 5.
e) Data sheets for capacitor banks for GGS at East Khagorijan and OCS at Nadua are issued as per Attachment – 6 & 7 respectively.
2. All other terms and conditions of the tender remain unaltered.
3. All the prospective bidders are requested to regularly visit OIL’s website: www.oil-india.com and e-procurement portal
https://etender.srm.oilindia.in/irj/portal for further announcements/latest information related to this tender.
4. Bidder to submit this Corrigendum No. 01 along with Annexure – I and Attachments 1-7 duly signed & stamped in all pages as token of acceptance and shall upload this document in the un-priced folder of the e-
bid.
Annexure – I
SUMMARY OF CONSULTANT/OIL’s RESPONSE TO PRE-BID QUERIES
SL No RFQ Section Ref. Clause Vendor Query / Existing
Clause OIL/ Consultant Response / Modified Clause
1. SCC ANNEXURE- II SCHEDULE OF
RATES/PRICES (SOR/P)
FOR ELECTRICAL PACKAGE
Refer Attachment 1 for revised Annexure – II & refer attachment 2 & 3 for
detailed SOR
2. CPI9724P19 technical part III & technical part VII – SOR for ND & EK
Clause 2.1 LV Switchboard – New item xxvii
Newly added In LV switchboard one new feeder(630A ACB) shall be added for load bank
3. CPI9724P19 technical part III & technical part VII – SOR for ND & EK
Clause 7 - No. of outgoing circuit for the Heat tracing DB shall be sized based on the heat
tracing line list. Refer attachment 4 & 5
4. CPI9724P19 technical part
III – SOR for ND Clause 9 - High mast quantity shall be referred in revised SOR. Refer attachment 2 & 3
5. CPI9724P19 technical part III & technical part VII – SOR for ND & EK
Clause 18.1 Cables - Cables size and quantity shall be referred in revised SOR. Refer attachment 2 &
3.
6.
CPI9724P19 technical part
III & technical part VII – SOR for ND & EK
Clause 18.2 Lug - Cable Lug size and quantity have been added and shall be referred in revised
SOR. Refer attachment 2 & 3
7. CPI9724P19 technical part III & technical part VII –
SOR for ND & EK
Clause 21 Cable Gland
- Cable Gland size and quantity shall be referred in revised SOR. Refer attachment
2 & 3.
8.
CPI9724P19 technical part
III & technical part VII – SOR for ND & EK
Clause 25 Newly added
-
Anchor bolts for modular package (Container) and Steel foundation template for
anchor bolt fixation shall be provided. Anchor bolts and Steel template shall be
provided by MPC Contractor 60 days prior to delivery of package
9. CPI9724P19
TABLE-1: Electrical Scope of supply for Nadua site & TABLE-2: Electrical Scope of
supply for East Khagorijan site.
Table 1 contains Electrical scope of supply .However we understand scope of supply of Quantity shall as per
Electrical SOR document only. Kindly confirm
Scope of supply of quantity shall be SOR document .In addition if any other
items need to be supplied to fulfil the scope of supply based on vendor design
,need to be included as part of scope. Refer attachment 2 & 3 for SOR.
10. CPI9724P19
TABLE-1: Electrical Scope of supply for
Nadua site Page 59 of 161 item
As per the Table 1 Electrical Scope of supply for Nadua /
East Khagorijan site, item No 19 specify the Local control
Bidder shall provide unit rate for LCS
SL No RFQ Section Ref. Clause Vendor Query / Existing
Clause OIL/ Consultant Response / Modified Clause
No.19 station requirement, but the quantity is not mentioned & the same is not reflecting in
SOR document. Kindly mention the quantity, if required.
11. CPI9724P19
TABLE-2: Electrical
Scope of supply for East Khagorijan site. Page 66 of 161 item No.19
Bidder shall provide unit rate for LCS
12. CPI9724P19
Spares and Special tools
Page 69 of 161 Clause No.21
Kindly provide the list for mandatory , Start-up and commissioning,
Maintenance tools and tackles & 2 year operational spares to be quoted.
Bidder shall list out and provide offer for mandatory, start up and commissioning
spares required based on the quoted system.
13. CPI9724P19
Spares and Special
tools Page 69 of 161 Clause No.21
As OEM, we don't envisage
extension rails & portable lift devices. Kindly confirm the requirement to bidder.
Noted. Bidder shall supply required special tools applicable for the quoted
model of the equipment.
14. CPI9724P19
19.0 Bidder shall
submit the vendors list for supply of following major items for this project.
Page 79 of 161 Clause No.19
Kindly share the approved Vendor list.
There is No approved vendor list for this project. However bidder shall select the
sub vendors with proven track record who has supplied reliable product to Oil
and Gas industries and meet the performance criteria.
15. Tech part-I
TABLE-1: Electrical Scope of supply for
Nadua site & TABLE-2: Electrical Scope of supply for East Khagorijan site
Page 8 to 22 of 193 Clause No 2.1
Table 1 contains Electrical
scope of supply, However we Understand scope of supply of Quantity shall as per Electrical SOR document
only. Kindly confirm
Scope of supply of quantity shall be as per electrical SOR document .In addition
if any other items need to be supplied to fulfil the scope of supply based on
vendor design ,need to be included as part of scope.
16. Tech part-I
TABLE-1: Electrical Scope of supply for
Nadua site Page 13 of 193 item
As per the Table 1 Electrical Scope of supply for Nadua /
East Khagorijan site, item No 19 specify the Local control
LCS is supplied by respective MPC contractor. However Bidder shall provide unit
rate for LCS
SL No RFQ Section Ref. Clause Vendor Query / Existing
Clause OIL/ Consultant Response / Modified Clause
No.19 station requirement, but the quantity is not mentioned & the same is not reflecting in
SOR document. Kindly mention the quantity, if required.
17. Tech part-I
TABLE-2: Electrical
Scope of supply for East Khagorijan site. Page 20 of 193 item No.19
LCS is supplied by respective MPC contractor. However Bidder shall provide unit
rate for LCS
18. Tech part-I
ANNEXURE – 1 :- Piping & Instrumentation
Diagram Page 176 to 193 of 193
This document is not applicable to Electrical supply. Kindly specify
requirement, if any.
P&ID is provided for reference to identify the electrical equipments and the
control scheme/associated signals which bidder may use it along with SLD for
the MCC, interface signal design.
19. Tech part-II
Piping &Instrumentation
Diagram Page 1 to 32 of 32 sheets
This document is not applicable to Electrical
supply. Kindly specify requirement, if any.
P&ID is provided for reference to identify the electrical equipments and the
control scheme/associated signals which bidder may use it along with SLD for
the MCC, interface signal design.
20. Tech part-III
Piping
&Instrumentation Diagram Page 1 to 15 of 111 sheets
This document is not
applicable to Electrical supply. Kindly specify requirement, if any.
P&ID is provided for reference to identify the electrical equipments and the
control scheme/associated signals which bidder may use it along with SLD for
the MCC , interface signal design.
21. Tech part-III
ELECTRICAL LOAD LIST for NADUA &
EAST KHAGORIJAN Page No. 40 to 49 of 111
We have consider the feeder quantity as mentioned in the electrical SOR line item No. 2 only.
Kindly confirm if any spare feeders to be considered / electrical load list to be followed.
Feeder quantity mentioned in SOR line item 2 shall be followed.
Bidder also quotes for unit price for starters of different rating for any addition
later. Refer attachment 2 & 3 for SOR.
22. Tech part-III
ELECTRICAL SOR FOR NADUA Page No. 51 of 111 ,
item No. 2
As per the Electrical SOR for Nadua (line item No. 2) 850 kVAR APFC system is mentioned, kindly mention
the quantity. If required, kindly Share the specification
Quantity is for one set. The capacitor banks shall be in 12 steps. Datasheet for
the capacitor bank is attached. Refer attachment 6 & 7.
SL No RFQ Section Ref. Clause Vendor Query / Existing
Clause OIL/ Consultant Response / Modified Clause
& datasheet for the same.
23. Tech part-III
ELECTRICAL SOR FOR NADUA Page No. 55 of 111 , item No. 7
Kindly confirm the scope of
heat tracing system. As per our Understanding bidder to provide only EHT type distribution board &
Transformer only.
Bidder understanding is not correct. Bidder shall design, supply and install and test ,commissioning the following
1.Heat tracing control panel which will receive RTD input from various heat
tracing circuits (as per the heat tracing line list) – Refer attachment 4 for Heat Tracing Line list
2. Heat tracing transformer of adequate capacity.
3. Heat tracing DB with adequate no of outgoing feeders.
4. Associated power cable from the feeder to transformer , transformer to DB, From DB to field junction box
5. RTD sensor cable from the field to the Control system.
24. Tech part-III
ELECTRICAL SOR
FOR NADUA Page No. 57 of 111 , item No. 18
Kindly confirm the scope of cable trenching to the bidder
Cable trenching is not in the scope of bidder.
25. Tech part-III
ELECTRICAL SOR FOR NADUA Page NO. 58 of 111 , item No. 19
Kindly confirm the scope of civil structural / works like structural supports for cable trays at field to bidder.
All supports for cable trays at field is in bidder scope
26. Tech part-III
ELECTRICAL SOR FOR NADUA Page NO. 59 of 111 , item No. 20
Kindly specify the scope for civil works for No. of road cross over / culverts & specify the No. of road cross
over / culverts required.
Civil works are excluded from scope of bidder. Bidder shall supply hume pipes of
250 mm and 400 mm of standard length.
Bidder shall refer the plot plan of Nadua and EK for the no of roads and culvert.
27. Tech part-III
ELECTRICAL SOR FOR NADUA Page NO. 59 of 111 ,
item No. 20.2 & 20.3
Kindly specify the scope of RCC foundation to bidder.
It is not in bidder scope. Bidder shall provide required inputs for civil foundation
design
28. Tech part-III
Datasheet for clarified water disposal pump motor
local control station
Kindly specify the scope of Motors. If required, please share the specification &
datasheet of each rating.
Scope of supply of motors for process modules is not in bidder scope
SL No RFQ Section Ref. Clause Vendor Query / Existing
Clause OIL/ Consultant Response / Modified Clause
Page NO. 100 to 104 of 111 sheet.
29. Tech part-III
Datasheet for
clarified water disposal pump motor local control station Page NO. 105 to 111
of 111 sheet.
Disposal pump motor local control station is not in bidder scope.
30. Tech part-IV
ANNEXURE – 1 :- Piping &Instrumentation
Diagram Page 179 to 193 of 193
This document is not applicable to Electrical
supply. Kindly specify requirement, if any.
P&ID is provided for reference to identify the electrical equipments and the
control scheme/associated signals which bidder may use it along with SLD for
the MCC, interface signal design.
31. Tech part-V
Piping &Instrumentation Diagram Page 1 to 31 of 31
sheets
This document is not applicable to Electrical supply. Kindly specify requirement, if any.
P&ID is provided for reference to identify the electrical equipments and the
control scheme/associated signals which bidder may use it along with SLD for
the MCC, interface signal design.
32. Tech part-VI
Piping &Instrumentation Diagram
Page 1 to 31 of 31 sheets
This document is not applicable to Electrical supply. Kindly specify
requirement, if any.
P&ID is provided for reference to identify the electrical equipments and the
control scheme/associated signals which bidder may use it along with SLD for
the MCC, interface signal design.
33. Tech part-VII
ELECTRICAL LOAD
LIST for NADUA & EAST KHAGORIJAN Page No. 34 to 44 of
105
We have consider the feeder quantity as mentioned in the
electrical SOR line item No. 2 only. Kindly confirm if any spare feeders to be considered /
electrical load list to be followed.
Feeder quantity mentioned in Electrical SOR line item 2 shall be followed.
Bidder also quotes for unit price for starters of different rating for any addition
later. Refer attachment 2 & 3 for SOR.
34. Tech part-VII
ELECTRICAL SOR FOR EAST KHAGORIJAN Page No. 49 of 105 ,
item No. 7
Kindly confirm the scope of heat tracing system. As per our Understanding bidder to provide only EHT type
distribution board & Transformer only.
Bidder understanding is not correct. Bidder shall design, supply and install and
test ,commissioning the following
1.Heat tracing control panel which will receive RTD input from various heat
tracing circuits (as per the heat tracing line list)
SL No RFQ Section Ref. Clause Vendor Query / Existing
Clause OIL/ Consultant Response / Modified Clause
2. Heat tracing transformer of adequate capacity.
3. Heat tracing DB with adequate no of outgoing feeders.
4. Associated power cable from the feeder to transformer , transformer to DB,
From DB to field junction box
5. RTD sensor cable from the field to the Control system.
35. Tech part-VII
ELECTRICAL SOR FOR EAST KHAGORIJAN
Page No. 51 of 105 , item No. 18
Kindly confirm the scope of
cable trenching to bidder. Cable trenching is not in the scope of bidder.
36. Tech part-VII
ELECTRICAL SOR FOR EAST
KHAGORIJAN Page No. 52 of 105 , item No. 19
Kindly confirm the scope of
civil structural / works like structural supports for cable trays at field to bidder.
All supports for cable trays at field is in bidder scope
37. Tech part-VII
ELECTRICAL SOR
FOR EAST KHAGORIJAN Page No. 53 of 105 , item No. 20
Kindly specify the scope for
civil works for No. of road cross over / culverts & specify the No. of road cross over / culverts required.
Civil works are excluded from scope of bidder. Bidder shall supply hume pipes of
250 mm and 400 mm of standard length.
Bidder shall refer the plot plan of Nadua and EK for the no of roads and culvert.
38. Tech part-VII
ELECTRICAL SOR FOR EAST KHAGORIJAN
Page No. 53 of 105 , item No. 20.2 & 20.3
Kindly specify the scope of RCC foundation to bidder.
It is not in bidder scope. Bidder shall provide required inputs for civil foundation
design
39. General Specification for
Distribution Board
Please share the specification
for Distribution board.
Bidder shall refer the datasheet for the Distribution board of AC UPS and Battery
charger
40. General Datasheet for 10KVA UPS
Please share the Datasheet for 10 KVA UPS.
Bidder shall refer to doc no 17039-ND-E-DS-9013. in Tech Part III page 69/111
41. General Specification & Datasheet for Lighting transformer
Please share the Specification & Datasheet for Lighting transformer.
No separate Datasheet/specification prepared for Lighting transformer.
&&&&&&&&&&&&&&&&&&&&
2
SCHEDULE OF RATES/PRICES (SOR/P) FOR ELECTRICAL PACKAGE
Note: Price quoted 1, 2 and 3 above is exclusive of GST, which is extra as applicable
Refer detailed SOR for description
DESCRIPTION PRICE (INR)
1. Electrical Package 1 (EP1) Price covering Engineering, Supply, Installation, Testing and
Commissioning including, packing/forwarding on Ex Work’s basis.
2. Electrical Package 2 (EP 2) Price covering Engineering, Supply, Installation, Testing and Commissioning including, packing/forwarding on
Ex Work’s basis.
3. Freight & Insurance Charges for delivery & Unloading at site Price
TOTAL (1 to 3)
GRAND TOTAL PRICE
Annexure - 1
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
1.0 PREFABRICATED SUBSTATION
1.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Containerized electrical equipment room, UPS room, battery room with all accessories like lighting DB, cable tray,
Lighting Fixtures, Exhaust Fans, MCT, Cable Trays, Cable conduits, smoke detectors, fire alarm panel, fire extinguishers, etc suitable for housing all the electrical systems specified items from 01 – 10. Preferable size of
container is 40' X 8' X 8'.6''. Please refer the specification attached. Bidder shall considered accessories which are needed for completion of work.
EA 1 0 EP-2
1.2Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of MCT frame, It shall be painted mild steel, MCT blocks shall be flame retardant. The ingress protection shall be IP 55 min.
The transist shall have fire, water or gas tight integrity and MCT will maintain fire integrity and prevent gas migration. MCTs shall be with 120 minutes fire rating.
FRAME SIZE
1.2.1 S 2X1 AISI 316 EA 3 0
1.2.2 S 2X2 AISI 316 EA 111 0
1.2.3 S 2X3 AISI 316 EA 62 0
1.2.4 S 4X1 AISI 316 EA 102 0
1.2.5 S 4X2 AISI 316 EA 110 0
1.2.6 S 4X3 AISI 316 EA 10 0
1.2.7 S 4X4 AISI 316 EA 55 0
1.2.8 S 6X1 AISI 316 EA 25 0
1.2.9 S 6X1 PRIMED EA 15 0
MODULE SIZE
1.2.10 RM 20 EA 1056 0
1.2.11 RM 30 EA 5180 0
1.2.12 RM 40 EA 3423 0
1.2.13 RM 60 EA 125 0
1.2.14 RM 60 WOC EA 301 0
1.2.15 RM 10/0X12
ACCESSORIES
1.2.16 WEDGE 120MM AISI 316 EA 1028 0
1.2.17 STAYPLATE 120MM AISI 316 EA 2903 0
1.2.18 Lubricant 25 ml EA 1026 0
1.3 CONTAINER LIGHTING
1.3.1
Supply, installation, testing and commissioning of Normal lighting fixture with lamp, 240VAC PH-PH,36W/40W LED, Industrial type Wall/Suspension/Ceiling mounting luminaires with polycarbonate frosted cover along with
mounting brackets & fixing accessories, suitable for degree of protection of IP42 and all other electrical equipment which are necessary to make the system complete and safe in all respect. Lighting fixtures shall be
suitable for loop-in/loop-out. Fixture shall be suitable for 16 SWG G.I. earth-wire connections. The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable
Glands (Lighting layout shall be finalized during detail engineering).
EA 120 0 EP-2
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
EP-1
Page 1 of 12
Annexure- 2
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
1.3.2
Supply, installation, testing and commissioning of Emergency lighting fixture with lamp, 240VAC PH-PH,36W/40W LED (with built-in battery back-up time of 90min), Industrial type Wall/Suspension/Ceiling mounting
luminaires with polycarbonate frosted cover along with mounting brackets & fixing accessories, suitable for degree of protection of IP42 and all other electrical equipment which are necessary to make the system complete
and safe in all respect. Lighting fixtures shall be suitable for loop-in/loop-out. Fixture shall be suitable for 16 SWG G.I. earth-wire connections. The fixtures shall be provided with 2 numbers of M20 threaded entries having 2
numbers of M20 Brass Nickel Plated Cable Glands (Lighting layout shall be finalized during detail engineering).
EA 54 0 EP-2
2.0 LV SWITCHBOARD
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, 415VAC LV Normal Switchboard of Double Front, Draw out type with form of separation as 4b
having copper busbar rated for 3200A, TP, 50 Hz with short circuit capacity of 50kA for 1 Sec. Switchgear Panel shall have the following I/C & O/G breakers. All the outgoing feeders shall be provided with CBCT & ELR with
adjustable time & current setting for Earth Leakage protection with Residual Current Monitoring System (RCMS) as per CEAR 2010. Shunt Release shall be provided in all the Outgoing MCCB's.Panel should have busduct
entry at the rear(Refer the attached sketch).
Incomer:
a) 2 Nos. of 3200A, 415VAC, 50kA for 1 Sec, TP, NSPBD, EDO ACB with µp based LSING(Overload protection (L), short-time delayed short-circuit protection (S), instantaneous short-circuit protection (I) and ground-fault
protection (N)). protection having communication capability for GEG incomers and the same shall be suitable for bus duct entry from Top/Rear(shall be confirmed during detail engineering).
On, Off, Trip, Spring Charged indication Lamps for the incomers. MFM with Communication capability and analog Voltmeter and Ammeter with 240° deflection shall be provided for incomer feeders.
Outgoing Feeders:
a) Motor Feeders up to 40HP shall be provided with MCCB having adjustable Thermal Magnetic protection.
b) Motor Feeders above 40 HP shall be provided with MCCB having µp based protection and Numerical Motor Protection Relay having protective functions as per OISD RP149.
c) Power Feeders shall be provided with MCCB having adjustable Thermal Magnetic Protection.
d) 850 kVAr APFC System (in 12 Steps) with APP Capacitor banks & microprocessor based APFC relays with On, Off & Trip indication shall be provided. MCCB with Thermal Magnetic Protection & Capacitor duty
contactors.
On, Off & Trip indication Lamps shall be provided for Motor Feeders and Power Feeders.
EA 1 0
i. 0.25kW DOL Motor Starter EA 16 0
ii. 0.37kW DOL Motor Starter EA 2 0
iii. 0.55kW DOL Motor Starter EA 2 0
iv.1.5kW DOL Motor Starter EA 4 0
v. 2.2kW DOL Motor Starter EA 2 0
vi. 3.0kW DOL Motor Starter EA 7 0
vii. 3.7kW DOL Motor Starter EA 6 0
viii. 4.7kW DOL Motor Starter EA 2 0
ix. 5kW DOL Motor Starter EA 3 0
x. 5.5kW DOL Motor Starter EA 2 0
xi. 7.5kW DOL Motor Starter EA 2 0
xii.1kW Star-Delta (SD) Motor Starter EA 6 0
xiii. 5kW Star-Delta (SD) Motor Starter EA 4 0
xiv. 8.5kW Star-Delta (SD) Motor Starter EA 3 0
xv. 22kW Star-Delta (SD) Motor Starter EA 2 0
xvi. 37kW Soft Starter (SS) Motor Starte EA 2 0
xvii. 110kW Soft Starter (SS) Motor Starter EA 3 0
xviii.16A Power Feeder EA 16 0
xix. 32A Power Feeder EA 1 0
xx. 63A Power Feeder EA 14 0
xxi. 80A Power Feeder EA 1 0
xxii.100A Power Feeder EA 4 0
EP-22.1
Page 2 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
xxii. 250A Power Feeder with power contactor, auto-off-manual selector switch and overload relay controlled by a photocell. EA 1 0
xxiv. 400A Power Feeder EA 1 0
xxv. 800A Power Feeder 415VAC, 50kA for 1 Sec, TP, EDO ACB with µp based LSING, protection having communication capability EA 1 0
xxvi. 1000A Power Feeder 415VAC, 50kA for 1 Sec, TP, EDO ACB with µp based LSING, protection having communication capability EA 2 0
xxvi. 630A Power Feeder 415VAC, 50kA for 1 Sec, TP, EDO ACB with µp based LSING, protection having communication capability EA 1 0
Switchboard shall be designed as per the following specifications.
i. LV Switchgear Specification - 17039-EK-E-SP-9001
ii. Electrical Design Basis - 17039-EK-E-DB-9001.
Quantity of feeders in the Switchboard shall be designed in accordance with the following documents.
i. Electrical Load List - 17039-EK-E-GD-9001
ii. Electrical Single Line Diagram – 17039-EK-E-DW-9001
Switchboard shall be assembled and wired up in a containerized substation. Panel shall be suitable for bus duct entry in the top/rear for incomer section & Cable from the bottom for the outgoing sections provided with gland
plate (GI/Brass for multicore & Aluminium for Single Core) of min. 3mm thk. Panel shall be fabricated of CRCA Sheet steel having min. 2.0mm thk. for door and load bearing sections. Panel shall be powder coated after
nine tank process with Shade 631 as per IS-5. Panel shall be of Dust & Vermin proof and shall be confirming to IP42 degree of Protection. Panel shall be fabricated as per the relevant Indian Standards and above
mentioned reference documents. Control supply (110VAC for Motor Protection) shall be derived internally from the main incomer via control transformer (2X100%). Control supply for the metering & indication of incomer
feeders shall be derived from PT Secondary of respective incomer. Power Supply to the Spring Charging motor, Closing Coil, Tripping Coil & Protection relays of incomer shall be suitable for 110 VDC and the same shall
be provided by client. Panel fabricator shall have CPRI Type test certificate for Short Circuit, Temperature Rise and IP Protection. Drawing & QAP should be approved before the fabrication of panel. Breaker handling
accessories such as tools, trolleys, etc., and commissioning spares. Two year operational spares list with price shall be submitted by vendor.
Location: Normal Switchgear Room
i. 3.0kW DOL Motor Starter EA 1 0
ii. 22kW Star-Delta (SD) Motor Starter EA 2 0
iii. 40kW Soft Starter (SS) Motor Starter EA 3 0
iv. 90kW Soft Starter (SS) Motor Starter EA 2 0
v. 25A Power Feeder EA 2 0
vi. 32A Power Feeder EA 2 0
vii. 63A Power Feeder EA 3 0
viii.100A Power Feeder EA 2 0
ix.150A Power Feeder EA 3 0
EP-2
EP-2
2.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, 415VAC LV Emergency Switchboard of Single Front, Draw out type with form of separation as 4b
having copper busbar rated for 800A, TP, 50 Hz with short circuit capacity of 50kA for 1 Sec. Switchgear Panel shall have the following I/C & O/G breakers. all the outgoing feeders shall be provided with CBCT & ELR with
adjustable time & current setting for Earth Leakage protection with Residual Current Monitoring System (RCMS). Shunt Release shall be provided in all the Outgoing MCCB's.
Incomer:
a) 2 Nos. of 800A, 415VAC, 50kA for 1 Sec, TP, EDO ACB with µp based LSING(Overload protection (L), short-time delayed short-circuit protection (S), instantaneous short-circuit protection (I) and ground-fault protection
(N)). protection having communication capability for incomers and the same shall be suitable for cable entry from Bottom.
On, Off, Trip, Spring Charged indication Lamps for the incomers. MFM with Communication capability and analog Voltmeter and Ammeter with 240° deflection shall be provided for incomer feeders.
Outgoing Feeders:
a) Motor Feeders up to 40HP shall be provided with MCCB having adjustable Thermal Magnetic protection.
b) Motor Feeders above 40 HP shall be provided with MCCB having µp based protection and Numerical Motor Protection Relay having protective functions as per OISD RP149. Ammeter shall be provided in the
switchboard for indication current in Local Pushbutton Station (LPBS).
c) Power Feeders shall be provided with MCCB having adjustable Thermal Magnetic Protection.
On, Off & Trip indication Lamps shall be provided for Motor Feeders and Power Feeders.
2.2 EP-2
0EA 1
Page 3 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
Switchboard shall be designed as per the following specifications.
i. LV Switchgear Specification - 17039-EK-E-SP-9001
ii. Electrical Design Basis - 17039-EK-E-DB-9001.
Quantity of feeders in the Switchboard shall be designed in accordance with the following documents.
i. Electrical Load List - 17039-EK-E-GD-9001
ii. Electrical Single Line Diagram – 17039-EK-E-DW-9001
The system shall be assembled and wired up in a containerized substation. Panel shall be suitable for Cable entry from the bottom for incoming & outgoing sections provided with gland plate (GI/Brass for multicore &
Aluminium for Single Core) of min. 3mm thk. Panel shall be fabricated of CRCA Sheet steel having min. 2.0mm thk. for door and load bearing sections. Panel shall be powder coated after nine tank process with Shade 631
as per IS-5. Panel shall be of Dust & Vermin proof and shall be confirming of IP42 degree of Protection. Panel shall be fabricated as per the relevant Indian Standards and above mentioned reference documents. Incomer
shall have Synchronizing scheme with control logic shall be provided. Control supply (110VAC for Motor Protection) shall be derived internally from the main incomer via control transformer (2X100%). Control supply for the
metering & indication of incomer feeders shall be derived from PT Secondary of respective incomer. Power Supply to the Spring Charging motor, Closing Coil, Tripping Coil & Protection relays of incomer shall be suitable
for 110 VDC and the same shall be provided by client. Panel fabricator shall have CPRI Type test certificate for Short Circuit, Temperature Rise and IP Protection. Drawing & QAP should be approved before the fabrication
of panel. Breaker handling accessories such as tools, trolleys, etc,. and commissioning spares. Two year operational spares list with price shall be submitted by vendor.
Location: Emergency Switchgear Room
2.2 EP-2
Page 4 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
3.0 INTERPOSING RELAY PANEL
3.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Interposing Relay Panel with following relays.
1. 5×64 Nos. of 30 VAC relay for signals to / from LPBS.
2. 7×73 Nos. of 24 VDC relay for signals to / from DCS.
3. 7×2 Nos. of 24 VDC relay for incomers.
4. 5×9 Nos. of 110VAC relay for signals to / from LPBS.
In addition to the quantity of relays mentioned above, 20% of spare in each rating & type shall be provided.
Location: Normal Switchgear Room
EA 1 0
3.2
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Interposing Relay Panel with following relays.
1. 7×9 Nos. of 24 VDC relay for signals to / from DCS.
3. 7×2 Nos. of 24 VDC relay for incomers.
4. 5×9 Nos. of 110VAC relay for signals to / from LPBS.
In addition to the quantity of relays mentioned above, 20% of spare in each rating & type shall be provided.
Location: Emergency Switchgear Room
EA 1 0
4.0 UPS
4.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of 30 kVA AC UPS (UPS rating shall be confirmed during Detailed Engineering) suitable for 3 phase input of 415 VAC, 50 Hz
& 3 phase output of 415 VAC, 50 Hz,3 phase, 4 wire, online, 2 X 100% parallel redundant UPS with static bypass, floor mounted, sheet steel panel with 2 x 50% Ni Cd type battery bank, AC UPS Distribution Board with
required number of incoming and outgoing feeders. Battery Backup time shall be 6 hours. Input power supply for the Main AC UPS shall be 415V ± 10%, 50 Hz, 3 phase, 3wire.The system shall be assembled and wired up
in a containerized substation as per attached sketch. UPS shall be complied as per the Electrical Design Basis -17039-EK-E-DB-9001 & Datasheet for Instrumentation UPS.
Location:UPS Room
EA 1 0
4.2
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of 110 V DC, 10 kVA (UPS rating shall be confirmed during Detailed Engineering), 2 Wire unearthed DC UPS System with
insulating monitoring device at the incomer of DCDB 2 X 50 %, 110V Nickel Cadmium Battery Bank (Ni Cd type) with Float and Float cum Boost Charger with stand/rack, DC Distribution Board of 110 V DC, 32 A Copper
busbar. Battery backup time shall be 2 hours.The system shall be assembled and wired up in the containerized substation as per attahced sketch. UPS shall be complied as per the Electrical Design Basis -17039-EK-E-DB-
9001 & Datasheet for Battery Charger & DCDB.
Location:UPS Room
EA 1 0
4.3
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of 5 kVA Telecom UPS (UPS rating shall be confirmed during Detailed Engineering) suitable for 3 phase input of 415 VAC,
50 Hz & 1 phase output of 240 VAC, 50 Hz, online, 2 X 100% parallel redundant UPS with static bypass, floor mounted, sheet steel panel with 2x50% Ni Cd type battery bank, Telecom AC UPS Distribution Board with
required number of incoming and outgoing feeders. Battery Backup time shall be 12 hours. Input power supply for the Telecom AC UPS shall be 415V ± 10%, 50 Hz, 3 phase, 3wire. The system shall be assembled and
wired up in the containerized substation as per attached sketch. UPS shall be complied as per the Electrical Design Basis -17039-EK-E-DB-9001 & Datasheet for Telecom UPS.
Location:UPS Room
EA 1 0
5.0 MAIN POWER DISTRIBUTION BOARD
5.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type 415VAC LV Main Power Distribution Board (MPDB) for Search light, having Copper busbar rated for
400A, TP, 50 Hz with short circuit capacity of 10kA for 1 Sec.
MPDB shall have 1 No. of 400A, TP, MCCB incomer & 8 Nos. of 25A, TP MCCB Outgoing feeders.
Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
Location:UPS Room
EA 1 0 EP-2
6.0 LIGHTING TRANSFORMER WITH DISTRIBUTION BOARD AND UTILITY TRANSFORMER WITH DISTRIBUTION BOARD
6.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, Normal Lighting Transformer and Normal Lighting Distribution Board complete with 1 number of
75kVA, 415V/240V AC, 50Hz, 3 phase, 3 wire, Delta/Delta, 4% impedance, Off Load Tap changer (OCTC) with ±5% in steps of 2.5%, Lighting Transformer which forms a part/separate of MLDB. Main Lighting Distribution
Board (MLDB) shall be rated for 240V AC, 3 Phase, 3 Wire, 250A, 10kA for 1 sec, Cu busbar.
Incomer : 1 No. of 250A, 240VAC, TP MCCB
Outgoing Feeders :
1. 22 Nos. of 16A, 240VAC, TP MCCB
2. 10 Nos. of 32A, 240VAC, TP MCCB
Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
The system shall be assembled and wired up in a containerized substation as per attached sketch.
Location: Refer Electrical Substation layout
EA 1 0 EP-2
EP-2
EP-2
Page 5 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
6.2
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, Emergency Lighting Transformer and Emergency Lighting Distribution Board (ELDB) complete with
1 number of 50kVA, 415V/240V AC, 50Hz, 3 phase, 3 wire, Delta/Delta, 4% impedance, Off Load Tap Changer (OCTC) with ±5% in steps of 2.5%, Lighting Transformer which forms a part/separate of ELDB. Emergency
Lighting Distribution Board shall be rated for 240V AC, 3 Phase, 3 Wire, 150A, 10kA for 1 sec, Cu busbar.
Incomer : 1 No. of 150A, 240VAC, TP MCCB
Outgoing Feeders :
1. 18 Nos. of 16A, 240VAC, TP MCCB
2. 10 Nos. of 32A, 240VAC, TP MCCB
Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
The system shall be assembled and wired up in a containerized substation as per attached sketch.
Location: Refer Electrical Substation layout
EA 1 0 EP-2
6.3
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, Utility Transformer and Utility Distribution Board complete with 1 number of 50kVA, 415V/415V AC,
50Hz, 3 phase, 4 wire, Dyn11, effectively grounded, 4% impedance, Off Load Tap changer (OCTC) with ±5% in steps of 2.5%, Utility Transformer which forms a part/separate of Utility Distribution Board. Utility Distribution
board shall be rated for 415V AC, 3 Phase, 4 Wire, 150A, 10kA for 1 sec, Cu busbar.
UDB shall have 1 No. of 150A, TPN, MCCB incomer & 16 Nos. of 32A, TPN MCB Outgoing feeders.
Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
The system shall be assembled and wired up in a containerized substation as per attached sketch.
Location: Emergency Switchgear Room
EA 1 0 EP-2
6.4
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, Security Room Utility Transformer and Utility Distribution Board complete with 1 number of 50kVA,
415V/415V AC, 50Hz, 3 phase, 4 wire, Dyn11, effectively grounded, 4% impedance, Off Load Tap changer (OCTC) with ±5% in steps of 2.5%, Utility Transformer which forms a part/separate of Utility Distribution Board.
Utility Distribution board shall be rated for 415V AC, 3 Phase, 4 Wire, 150A, 10kA for 1 sec, Cu busbar.
SRUDB shall have 1 No. of 150A, TPN, MCCB incomer & 16 Nos. of 32A, TPN MCB Outgoing feeders.
Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
The system shall be assembled and wired up in a containerized substation as per attached sketch.
Location: Outdoor plant area for security room AC
EA 1 0 EP-1
6.5
Design,Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Wall / Floor mountable type 240VAC ETP &OWS Normal Lighting Distribution Board (ETP&OWS-NLDB) having Copper
busbar rated for 32A, TP, 50 Hz with short circuit capacity of 10kA for 1 Sec. NLDB shall have the following I/C & O/G breakers. Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per
CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
Incomer : 1 No. of 32A, 240VAC, 16kA for 1 Sec, TP MCCB
Outgoing Feeders :
1. 12 Nos. of 6A, 240VAC, 16kA for 1 Sec, DP RCBO with ∆In of100mA.
NLDB shall be suitable for Cable entry from the bottom for Incoming & outgoing feeders provided with aluminium gland plate of min. 3mm thk. NLDB shall have double/single door arrangement for the outgoing feeders. DB
shall be fabricated of CRCA Sheet steel having min. 2.0mm thk. and shall be powder coated after seven tank process with Shade 631 as per IS-5. DB shall be of Dust & Vermin proof and shall be confirming of IP52 degree
of Protection. Panel fabricator shall have CPRI Type test certificate for Short Circuit, Temperature Rise and IP Protection. Drawing & QAP should be approved before the fabrication of DB.
Location : ETP container
EA 1 0 EP-1
6.6
Design,Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Wall / Floor mountable type 240VAC ETP &OWS Emergency Lighting Distribution Board (ETP&OWS-ELDB) having
Copper busbar rated for 32A, TP, 50 Hz with short circuit capacity of 10kA for 1 Sec. ELDB shall have the following I/C & O/G breakers. Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as
per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
Incomer : 1 No. of 32A, 240VAC, 16kA for 1 Sec, TP MCCB
Outgoing Feeders :
1. 12 Nos. of 6A, 240VAC, 16kA for 1 Sec, DP RCBO with ∆In of100mA.
ELDB shall be suitable for Cable entry from the bottom for Incoming & outgoing feeders provided with aluminium gland plate of min. 3mm thk. ELDB shall have double/single door arrangement for the outgoing feeders. DB
shall be fabricated of CRCA Sheet steel having min. 2.0mm thk. and shall be powder coated after seven tank process with Shade 631 as per IS-5. DB shall be of Dust & Vermin proof and shall be confirming of IP52 degree
of Protection. Panel fabricator shall have CPRI Type test certificate for Short Circuit, Temperature Rise and IP Protection. Drawing & QAP should be approved before the fabrication of DB.
Location : ETP container
EA 1 0 EP-1
7.0 HEAT TRACING DISTRIBUTION BOARD
7.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, Electric Heat Tracing System complete with EHT Transformer of 50kVA, 415V/240V AC, 50Hz, 3
phase, 3 wire, Delta/delta, 4% impedance, Off Load Tap changer (OCTC) with ±5% in steps of 2.5%. Heat Tracing Distribution Board shall be rated for 240V AC, 50Hz, 3 Ph, 3 Wire shall be preferably placed in safe area.
EHT system should have certification for hazardous area(class 1, zone 2, gas grp. IIA/IIB) and Temperature Rating(Temp.T3) by statutory body of India. Sub distribution boards (as applicable) shall be suitable for 240V,
50Hz, phase to phase, two wire (derived from a 415 V, 50 Hz, 3 phase, 3 wire neutral solidly earthed system) system.
Electrical Heat Tracing system shall be designed suitable for the steady state voltage tolerance of +6/-10% and frequency tolerance of ±3%.
Transformer incomer : 1 No. of 100A, 415VAC, TP MCCB
Transformer outgoing : 1 No. of 150A, 240VAC, TP MCCB
Heat tracing DB Outgoing Feeders : 20 Nos. of 32A, 240VAC, TP MCCB
Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
Location: Normal switchgear room
EA 1 0 EP-2
8.0 BUSDUCT
Page 6 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
8.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Non-Segregated Phase Bus Duct enclosing Copper bus bars for service voltage of 415V AC, 3 Phase, 3 wire, 3200A,
50kA for 1 sec., including necessary rigid connections at switchgear end with required numbers of vertical and horizontal elbows. Busduct enclosure material shall be of Aluminum alloy sheets having minimum 3mm thk.
with suitable bolted covers. Bus bar shall be of electrolytic grade, high conductivity copper bus bar confirm to BIS and it shall be of electro-tinned. All bus-bar shall be insulated with heat shrinkable PVC sleeves (or better)
and shall be supported at required intervals with non- hygroscopic, non-deteriorating, and non–inflammable SMC / FRP (or better) supports having adequate mechanical strength and a high tracking resistance, to withstand
short circuit fault levels more than the designed. Bus bar system shall be designed with required clearance between phases as specified in the standards. Any separator used shall be made of non-hygroscopic material
having adequate mechanical strength to withstand the worst fault conditions. Insulating sheet barriers shall be as per Bus duct Specification and Layout. All gasketed- flanged joints shall be suitably protected against direct
splashing of rainwater in case of outdoor runs portion. Outdoor installed busduct portion shall be provided with rain canopy/sunshade. Bus Duct shall be suitable for Indoor & outdoor installation as applicable as per the
attached layout. Bidder shall consider required number of Elbows, tee joints, phase crossover chamber based on this layout.The bus duct shall be provided with adequate number of thermostatically controlled space heaters
of adequate capacity to maintain the internal temperature above the dew point to prevent moisture condensation within the bus duct.
EA 2 0 EP-1
9.0 HIGH MAST LIGHTING FIXTURE
9.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of the Complete High mast lighting system with High mast (30m height) of double sided arrangement with 18 numbers of 1 X
350W LED flood light fixture with LED lamps, Lantern carriage, 2 Nos. of Plu & Socket, control gear, termination box, winching device, winch motor, winch motor panel, Raising and Lowering system (R & L), lighting wiring
materials such as flexible cable of EPR insulated from Plug & Socket assembly to the control gear on the top, cable glands, lugs, inbuilt junction boxes within the high mast pole, 2 numbers of aviation obstruction warning
light, lightning finial, flame proof feeder pillar for automatic switching operation of luminaires based on Duck-Dawn Electronic timer, cabling from feeder pillar to individual fixtures, cabling for winch motor, power tools and all
other electrical equipment which are necessary to make the system complete and safe in all aspects.
EA 6 0 EP-1
Page 7 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
10.0 LIGHTING DISTRIBUTION BOARD
10.1
Design,Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Wall / Floor mountable type 240VAC LV Normal Lighting Distribution Board (NLDB) having Copper busbar rated for 32A,
TP, 50 Hz with short circuit capacity of 10kA for 1 Sec. NLDB shall have the following I/C & O/G breakers. Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt
Release shall be provided in Incoming MCCB.
Incomer : 1 No. of 32A, 240VAC, 16kA for 1 Sec, TP MCCB
Outgoing Feeders :
1. 12 Nos. of 6A, 240VAC, 16kA for 1 Sec, DP RCBO with ∆In of100mA.
NLDB shall be suitable for Cable entry from the bottom for Incoming & outgoing feeders provided with aluminium gland plate of min. 3mm thk. NLDB shall have double/single door arrangement for the outgoing feeders. DB
shall be fabricated of CRCA Sheet steel having min. 2.0mm thk. and shall be powder coated after seven tank process with Shade 631 as per IS-5. DB shall be of Dust & Vermin proof and shall be confirming of IP52 degree
of Protection. Panel fabricator shall have CPRI Type test certificate for Short Circuit, Temperature Rise and IP Protection. Drawing & QAP should be approved before the fabrication of DB.
Location: Process Area
EA 10 0 EP-1
10.2
Design,Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Wall / Floor mountable type 240VAC LV Emergency Lighting Distribution Board (ELDB) having Copper busbar rated for
32A, TP, 50 Hz with short circuit capacity of 10kA for 1 Sec. ELDB shall have the following I/C & O/G breakers. Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt
Release shall be provided in Incoming MCCB.
Incomer : 1 No. of 32A, 240VAC, 16kA for 1 Sec, TP MCCB
Outgoing Feeders :
1. 12 Nos. of 6A, 240VAC, 16kA for 1 Sec, DP RCBO with ∆In of100mA.
ELDB shall be suitable for Cable entry from the bottom for Incoming & outgoing feeders provided with aluminium gland plate of min. 3mm thk. ELDB shall have double/single door arrangement for the outgoing feeders. DB
shall be fabricated of CRCA Sheet steel having min. 2.0mm thk. and shall be powder coated after seven tank process with Shade 631 as per IS-5. DB shall be of Dust & Vermin proof and shall be confirming of IP52 degree
of Protection. Panel fabricator shall have CPRI Type test certificate for Short Circuit, Temperature Rise and IP Protection. Drawing & QAP should be approved before the fabrication of DB.
Location: Process Area
EA 10 0 EP-1
11.0 OUTDOOR
11.1 SHED LIGHTING
11.1.1
Supply, installation, testing and commissioning of Normal lighting fixture with lamp, 240VAC PH-PH, 42W LED, Industrial type,weather proof, well glass type lighting fixture along with mounting brackets & fixing
accessories, suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture
shall be suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands.
EA 86 0 EP-1
11.1.2
Supply, installation, testing and commissioning of Emergency lighting fixture with lamp, 240VAC PH-PH, 42W LED, Industrial type,weather proof, well glass type lighting fixture along with mounting brackets & fixing
accessories, suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture
shall be suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands. 25% of emergency lighting shall
be self contained emergency type with integral battery backup time of 90min.
EA 30 0 EP-1
11.1.3
Supply, installation, testing and commissioning of Critical lighting fixture with lamp, 110VDC, 2WIRE, 15W LED, Industrial type Wall/Suspension/Ceiling/Column mounting luminaires with polycarbonate frosted cover along
with mounting brackets & fixing accessories, suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect. Lighting fixtures shall be
suitable for loop-in/loop-out. Fixture shall be suitable for 16 SWG G.I. earth-wire connections. The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable
Glands (Lighting layout shall be finalized during detail engineering).
EA 16 0 EP-1
11.1.4
Supply, installation, testing and commissioning of Normal lighting fixture with lamp, 240VAC PH-PH, 42W LED, Flame proof type, well glass type lighting fixture suitable along with mounting brackets & fixing accessories,
for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture shall be suitable for
16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands. FLP Light fittings, Cable Glands & Plugs shall be
certified by CMRI/PESO.
EA 46 0 EP-1
11.1.5
Supply, installation, testing and commissioning of Emergency lighting fixture with lamp, 240VAC PH-PH, 42W LED, Flame proof type, well glass type lighting fixture along with mounting brackets & fixing accessories,
suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture shall be
suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands. FLP Light fittings, Cable Glands & Plugs
shall be certified by CMRI/PESO. 25% of emergency lighting shall be self contained emergency type with integral battery backup time of 90min.
EA 20 0 EP-1
11.1.6
Supply, installation, testing and commissioning of Critical lighting fixture with lamp, 110VDC, 2WIRE, 15W LED, Flame proof type, Wall/Suspension/Ceiling/Column mounting luminaires with polycarbonate frosted cover
along with mounting brackets & fixing accessories, suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect. Lighting fixtures shall
be suitable for loop-in/loop-out. Fixture shall be suitable for 16 SWG G.I. earth-wire connections. The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable
Glands (Lighting layout shall be finalized during detail engineering).
EA 10 0 EP-1
12.0 CONTAINER OUTDOOR LIGHTING
Page 8 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
12.1
Supply, installation, testing and commissioning of Normal lighting fixture with lamp, 240VAC PH-PH, 90W LED, Industrial type,weather proof, Wall/Column mounting luminaires along with mounting brackets & fixing
accessories, suitable for degree of protection of IP42 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture
shall be suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands.
EA 35 0 EP-1
12.2
Supply, installation, testing and commissioning of Emergency lighting fixture with lamp, 240VAC PH-PH 90W LED, Industrial type,weather proof, Wall/Column mounting luminaires along with mounting brackets & fixing
accessories, suitable for degree of protection of IP42 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture
shall be suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands.25% of emergency lighting shall
be self contained emergency type with integral battery backup time of 60min.
EA 27 0 EP-1
13.0 STREET LIGHTING
13.1
Supply, installation, testing and commissioning of Normal lighting fixture with lamp, 240VAC PH-PH, 40W LED street light of 8m height from FGL with Swaged Pole, Industrial type,weather proof, luminaires along with
mounting brackets & fixing accessories, suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable
for loop-in/loop-out. Fixture shall be suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands.
EA 57 0 EP-1
14.0 PIPE RACK LIGHTING
14.1
Supply, installation, testing and commissioning of Normal lighting fixture with lamp, 240VAC PH-PH 36W Well glass LED, flame proof type, channel/Column mounting luminaires along with mounting brackets & fixing
accessories, suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture
shall be suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands.
EA 50 0 EP-1
15.0 WELDING SOCKET
15.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Weather Proof Type 415V, 3P+E, 63A rating with heavy duty plug and socket with MCB protection along with mounting
accessories. Plug & Socket shall have the necessary mechanical interlocks and earthing facilities. The enclosure shall have suitable protection for site conditions specified such as weather-proof, dust proof, corrosion
resistant, etc. Welding receptacles shall be provided at suitable locations as specified in the layout.
EA 9 0 EP-1
15.2
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of flame proof Type 415V, 3P+E, 63A rating with heavy duty plug and socket with MCB protection along with mounting
accessories. Plug & Socket shall have the necessary mechanical interlocks and earthing facilities. The enclosure shall have suitable protection for site conditions specified such as weather-proof, dust proof, corrosion
resistant, etc. Welding receptacles shall be provided at suitable locationsas specified in the layout.
EA 5 0 EP-1
16.0 CONVENIENT SOCKET
16.1Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Industrial Type 240V, 2P+E, 15/16A rating with heavy duty plug and socket along with mounting accessories. The
enclosure shall have suitable protection for site conditions specified such as weather-proof, dust proof, corrosion resistant, etc. Convenient Socekt shall be provided at suitable locations as specified in the layout.EA 40 0 EP-2
17.0 AIR CONDITIONERS
16
(based on heat load)
18.0 CABLES & CABLE LUGS
18.1
Design, Supply and laying of 1100V grade, single/multi-core, stranded copper conductor, extruded XLPE insulated, with extruded PVC inner sheath (type ST-2), galvanised steel wire armoured and overall sheath with
extruded flame retardant low smoke (FRLS) PVC compound (type ST-2). Outer Sheath shall be resistant to water, ultra violet radiation, fungus, termite and rodent attacks. Consumables such as cable ferrulers, cable tie,
name plates,equipment fixing hardwares and cable markers.Colour of the outer sheath shall be black. Cables shall confirm to IS- 7098-PART-I, IS-5831, IS-10810-PART-33, IS-10810-PART-53, IS-10810-PART-61, IS-
10810-PART-62
18.1.1 3CX2.5 Sq.mm MTR 9456 0
18.1.2 3CX4 Sq.mm MTR 2244 0
18.1.3 3CX6 Sq.mm MTR 2544 0
18.1.4 3CX10 Sq.mm MTR 1524 0
EP-1
0
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of SPLIT / DUCTABLE SPLIT TYPE AIR CONDITIONERS Complete with indoor unit with remote, outdoor unit, copper
tubing, insulating materials, supporting materials, adequate sized voltage stabilizer, isolating breakers, cables/ wires and with all accessories, hardwares etc,. for switchgear room, ups room, battery room, CCR rooms.
Number of AC unit(N) shall be based on heat load calculation. Bidder shall consider (N+1) for redundancy.
2 Ton High Wall Split AC - 5 Star
Location: All containerized room
EA17.1 EP-2
Page 9 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
18.1.5 3CX16 Sq.mm MTR 4308 0
18.1.6 3CX25 Sq.mm MTR 4464 0
18.1.7 3CX35 Sq.mm MTR 2352 0
18.1.8 3CX50 Sq.mm MTR 600 0
18.1.8 3CX70 Sq.mm MTR 840 0
18.1.9 3CX95 Sq.mm MTR 864 0
18.1.10 3CX120 Sq.mm MTR 900 0
18.1.11 1CX240 Sq.mm MTR 6480 0
18.1.12 2CX2.5 Sq.mm MTR 2340 0
18.1.13 7CX2.5 Sq.mm MTR 16008 0
18.1.14 10CX2.5 MTR 2340 0
18.2Design, Supply, Installation & Commissioning of 1100V grade, Cable lugs suitable for the voltage grade of 0.6/1kv , lugs shall be insulated / non-insulated ring / pin type and made from high conductivity, tinned copper,
compression type lug. Cable lug shall confirm to IS-8309 and IS-8337.Each core shall have separate cable lug. Copper lugs for copper cables and aluminium lugs for aluminium cables shall be used
18.2.1 3CX2.5 Sq.mm PIN TYPE INSULATED COPPER EA 270 0
18.2.2 3CX4 Sq.mm PIN TYPE INSULATED COPPER EA 60 0
18.2.3 3CX6 Sq.mm RING TYPE NON-INSULATED COPPER EA 60 0
18.2.4 3CX10 Sq.mm RING TYPE NON-INSULATED COPPER EA 54 0
18.2.5 3CX16 Sq.mm RING TYPE NON-INSULATED COPPER EA 96 0
18.2.6 3CX25 Sq.mm RING TYPE NON-INSULATED COPPER EA 108 0
18.2.7 3CX35 Sq.mm RING TYPE NON-INSULATED COPPER EA 66 0
18.2.8 3CX50 Sq.mm RING TYPE NON-INSULATED COPPER EA 12 0
18.2.9 3CX70 Sq.mm RING TYPE NON-INSULATED COPPER EA 18 0
18.2.10 3CX95 Sq.mm RING TYPE NON-INSULATED COPPER EA 18 0
18.2.11 3CX120 Sq.mm RING TYPE NON-INSULATED COPPER EA 18 0
18.2.12 1CX240 Sq.mm RING TYPE NON-INSULATED COPPER EA 42 0
18.2.13 2CX2.5 PIN TYPE INSULATED COPPER EA 32 0
18.2.14 7CX2.5 PIN TYPE INSULATED COPPER EA 910 0
18.2.15 10CX2.5 PIN TYPE INSULATED COPPER EA 160 0
19.0 CABLE TRAY
19.1Design, Supply and laying of Ladder/ Perforated type cable trays of FRP material, 3mm/4mm thick heavy duty straight ladder/Perforated type suitable for indoor / outdoor areas. Straight sections shall be provided in
standard lengths of 3m. All splice plates and assembly hardwares shall be of FRP material. FRP sheet cover of 3mm thick heavy duty type shall be provided.
19.1.1 750mm width ladder type cable tray, 150 mm height with cover MTR 900 0
19.1.2 600mm width ladder type cable tray, 150 mm height with cover MTR 150 0
EP-1
EP-1
EP-1
Page 10 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
19.1.3 450mm width ladder type cable tray, 150 mm height with cover MTR 350 0
19.1.4 300mm width ladder type cable tray, 150 mm height with cover MTR 600 0
19.1.5 150mm width perforated type cable tray, 100 mm height with cover MTR 1343 0
19.1.6 100mm width perforated type cable tray, 50 mm height with cover MTR 250 0
19.2 Horizontal Bends (90°), of FRP material
19.2.1 750mm width ladder type cable tray, 150 mm height with cover NOS 13 0
19.2.2 600mm width ladder type cable tray, 150 mm height with cover NOS 2 0
19.2.3 450mm width ladder type cable tray, 150 mm height with cover NOS 12 0
19.2.4 300mm width ladder type cable tray, 150 mm height with cover NOS 10 0
19.2.5 150mm width perforated type cable tray, 100 mm height with cover NOS 19 0
19.2.6 100mm width perforated type cable tray, 50 mm height with cover NOS 10 0
19.3 Inside Bends (90°), of FRP material
19.3.1 750mm width ladder type cable tray, 150 mm height with cover NOS 21 0
19.3.2 600mm width ladder type cable tray, 150 mm height with cover NOS 2 0
19.3.3 450mm width ladder type cable tray, 150 mm height with cover NOS 12 0
19.3.4 300mm width ladder type cable tray, 150 mm height with cover NOS 8 0
19.3.5 150mm width perforated type cable tray, 100 mm height with cover NOS 16 0
19.3.6 100mm width perforated type cable tray, 50 mm height with cover NOS 4 0
19.4 Outside Bends (90°), of FRP material
19.4.1 750mm width ladder type cable tray, 150 mm height with cover NOS 26 0
19.4.2 600mm width ladder type cable tray, 150 mm height with cover NOS 3 0
19.4.3 450mm width ladder type cable tray, 150 mm height with cover NOS 12 0
19.4.4 300mm width ladder type cable tray, 150 mm height with cover NOS 8 0
19.4.5 150mm width perforated type cable tray, 100 mm height with cover NOS 16 0
19.4.6 100mm width perforated type cable tray, 50 mm height with cover NOS 4 0
19.5 Reducer (Straight Type) of FRP material
19.5.1 750mm(W1) x 600mm(W2) x 150mm(H) Ladder Type with Cover NOS 2 0
19.5.2 750mm(W1) x 450mm(W2) x 150mm(H) Ladder Type with Cover NOS 2 0
19.5.3 600mm(W1) x 450mm(W2) x 150mm(H) Ladder Type with Cover NOS 1 0
19.5.4 600mm(W1) x 300mm(W2) x 150mm(H) Ladder Type with Cover NOS 1 0
19.5.5 450mm(W1) x 300mm(W2) x 150mm(H) Ladder Type with Cover NOS 3 0
19.5.6 450mm(W1) x 150mm(W2) x 150mm(H) Ladder Type with Cover NOS 1 0
19.5.7 300mm(W1) x 150mm(W2) x 150mm(H) Ladder Type with Cover NOS 3 0
EP-1
EP-1
Page 11 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
19.5.8 300mm(W1) x 100mm(W2) x 150mm(H) Ladder Type with Cover NOS 1 0
19.5.9 150mm(W1) x 100mm(W2) x 100mm(H) Performated Type with Cover NOS 2 0
19.6 CABLE TRAY FITTINGS
19.6.1 Flat splice plate (750mm width ladder type cable tray, 150 mm height ) NOS 321 0
19.6.2 Flat splice plate (600mm width ladder type cable tray, 150 mm height) NOS 53 0
19.6.3 Flat splice plate (450mm width ladder type cable tray, 150 mm height) NOS 129 0
19.6.4 Flat splice plate (300mm width ladder type cable tray, 150 mm height) NOS 209 0
19.6.5 Flat splice plate (150mm width perforated type cable tray, 100 mm height) NOS 466 0
19.6.6 Flat splice plate (100mm width perforated type cable tray, 50 mm) NOS 90 0
19.6.7 Set of round head square neck type bolts and hex nuts M10 X25 MM NOS 10136 0
19.6.8 Hold-down clamps, S-type, as per drawing number , c/w stainless steel fastening hardware NOS 531 0
19.6.9 Hold-down clamps, J-type, as per drawing number , c/w stainless steel fastening hardware NOS 667 0
19.7 Supply and installation of cable tray support & electrical equipment supports
19.7.1 50×50×6 mm L angle MTR 370 0
20.0 HUME PIPE & HDPE
20.1 Design, Supply & laying RCC Hume pipes under driveway or culverts or road crossover including excavation, providing collar joints, backfilling etc,. Which shall be NP2 and length of each pipe shall be 1.50M.
20.1.1 250 MTR 24 0
20.1.2 450 MTR 24 0
20.2 Supply & laying of 50mm dia heavy duty HDPE pipes in RCC foundation of Lighting poles with all required accessories MTR 100 0
20.2 Supply & laying of 50mm dia heavy duty HDPE pipes in RCC foundation of lighting poles with all required accessories such as Bends, Elbows, Couplers, etc to complete as per the instruction of site engineer. MTR 100 0
20.3 Supply & laying of 100mm dia heavy duty HDPE pipes in RCC foundation of lighting poles with all required accessories such as Bends, Elbows, Couplers, etc to complete as per the instruction of site engineer. MTR 20 0
21.0 CABLE GLAND
21.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of FLP HEAVY DUTY DOUBLE COMPRESSION Cable Termination(FLP):Providing termination of 1.1 kV grade armoured
cable for the following sizes including supply of FLP heavy duty double compression cable glands of Baliga/CEAG-FCG /FlexPro/ FEPL make, crimping lugs and allied jointing materials, etc. all complete as per
specification & direction of Engineer In-charge. Cable Glands & Plugs shall be certified by CMRI/PESO.
21.1.1 M20×1.5 EA 41 0
21.1.2 M25×1.5 EA 31 0
21.1.3 M32×1.5 EA 9 0
21.1.4 M40×1.5 EA 3 0
21.2
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of NON-FLP HEAVY DUTY DOUBLE COMPRESSION Cable Termination (NON FLP): Providing termination of 1.1 kV grade
armoured cable for the following sizes including supply of NON FLP heavy duty Double Compression cable glands, crimping type lugs and allied jointing materials, etc. all complete as per specification & direction of
Engineer In-charge. Glands and lugs shall be of approved make.
21.2.1 M20×1.5 EA 107 0
EP-1
EP-1
EP-1
EP-1
EP-2Page 12 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
21.2.2 M25×1.5 EA 59 0
21.2.3 M32×1.5 EA 15 0
21.2.4 M40×1.5 EA 9 0
22.0 EARTHING & LIGHTNING
22.1
Design, Engineering, Supply, Installation, Testing and Commissioning of maintenance free Chemically treated Electrical Earth Pit consisting of Copper solid earth electrode of 50mm dia & 3m long. Earth enhancement
material shall be of superior conductive material so that it improves earthing effectiveness. The quantity of earth enhancing material required per earth electrode shall be minimum 10Kg shall be supplied for each
electrodes or as per OEM recommendation. Electrical Earth Pit shall consists of Copper Rod, Test Links, Connections Bolts made of SS, Bimetallic connector for connection of aluminium earth strip to the test link,
Inspection Chamber made of Brick masonry work/precast RCC chamber of 900×900mm.
EA 58 0 EP-1
22.2
Design, Engineering, Supply, Installation, Testing and Commissioning of maintenance free Chemically treated Lightning Earth Pit consisting of Copper solid earth electrode of 50mm dia & 3m long. Earth enhancement
material shall be of superior conductive material so that it improves earthing effectiveness. The quantity of earth enhancing material required per earth electrode shall be minimum 10Kg shall be supplied for each
electrodes or as per OEM recommendation. Electrical Earth Pit shall consists of Copper Rod, Test Links, Connections Bolts made of SS, Bimetallic connector for connection of aluminium earth strip to the test link,
Inspection Chamber made of Brick masonry work/precast RCC chamber of 900×900mm.
EA 41 0
22.3
Design, Engineering, Supply, Installation, Testing and Commissioning of maintenance free Chemically treated Control Earth Pit consisting of Copper solid earth electrode of 50mm dia & 3m long. Earth enhancement
material shall be of superior conductive material so that it improves earthing effectiveness. The quantity of earth enhancing material required per earth electrode shall be minimum 10Kg shall be supplied for each
electrodes or as per OEM recommendation. Electrical Earth Pit shall consists of Copper Rod, Test Links, Connections Bolts made of SS, Bimetallic connector for connection of aluminium earth strip to the test link,
Inspection Chamber made of Brick masonry work/precast RCC chamber of 900×900mm.EA 4 0
22.4
Design, Engineering, Supply, Installation, Testing and Commissioning of maintenance free Chemically treated Signal Earth Pit consisting of Copper solid earth electrode of 50mm dia & 3m long. Earth enhancement material
shall be of superior conductive material so that it improves earthing effectiveness. The quantity of earth enhancing material required per earth electrode shall be minimum 10Kg shall be supplied for each electrodes or as
per OEM recommendation. Electrical Earth Pit shall consists of Copper Rod, Test Links, Connections Bolts made of SS, Bimetallic connector for connection of aluminium earth strip to the test link, Inspection Chamber
made of Brick masonry work/precast RCC chamber of 900×900mm.
EA 4 0
22.5 Design, Engineering, Manufacturing, Assembling, Supply, Installation & Testing of Grounding strips of aluminium flat/wire or Copper Wire and trench work as per requirement and back filling wherever required.
22.5.1 100 x 6 mm Aluminium strip - Buried in soil MTR 2800 0
22.5.2 100 x 6 mm Aluminium strip - Above ground MTR 900 0
22.5.3 30 x 6 mm Aluminium strip MTR 300 0
22.5.4 25 x 3 mm Aluminium strip MTR 800 0
22.6 Supplying and fixing of Stranded Aluminium wire (8 SWG) with PVC insulation MTR 200 0
22.7 Supplying and fixing of Stranded Aluminium wire (10 SWG) with PVC insulation MTR 300 0
22.8 Supplying and fixing of Stranded 16 Sq.mm insulated flexible aluminium cable MTR 50 0
22.9 Aluminium Earth bar with 10 holes as minimum supplied complete with washer, nuts and bolts(hardware accessories shall be SS). EA 10 0
23.0 MOV DISTRIBUTION BOARD
23.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Structure/Coloumn mountable type 415VAC MOV Distribution Board (MOVDB) having Copper busbar rated for 63A, TP,
50 Hz with short circuit capacity of 10kA for 1 Sec. MOV DB shall be suitable for installation in Hazardous area Class 1, Zone-2, Gas Group IIA/IIB, Temp. Class T3. MOV DB shall be of Ex'd' type with min. IP 66 made from
Aluminium alloy (LM-06), provided with required no. of metric/inches threaded cable entries for the entry of cables and suitable certified glands and plugs. MOV DB shall be supplied with rain canopy/sun shade for weather
protection. Final Paint colour shade for the DB shall be shade 631 as per IS-5. Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in
Incoming MCCB.
MOVDB shall have 1 No. of 63A, TP, MCCB incomer & 20 Nos. of 10A, TP MCCB Outgoing feeders.
Location: Outdoor process Area
EA 1 0
23.2
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Structure/Coloumn mountable type 415VAC MOV Distribution Board (MOVDB) having Copper busbar rated for 63A, TP,
50 Hz with short circuit capacity of 10kA for 1 Sec. MOV DB shall be suitable for installation in Hazardous area Class 1, Zone-2, Gas Group IIA/IIB, Temp. Class T3. MOV DB shall be of Ex'd' type with min. IP 66 made from
Aluminium alloy (LM-06), provided with required no. of metric/inches threaded cable entries for the entry of cables and suitable certified glands and plugs. MOV DB shall be supplied with rain canopy/sun shade for weather
protection. Final Paint colour shade for the DB shall be shade 631 as per IS-5. Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in
Incoming MCCB.
MOVDB shall have 1 No. of 63A, TP, MCCB incomer & 20 Nos. of 10A, TP MCCB Outgoing feeders.
Location: Outdoor Tank Area
EA 1 0
24.0 SEARCH LIGHTING FIXTURE
EP-1
EP-1
EP-2
Page 13 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
Service Description UOM
TENDER OFFER
PACKAGES.No
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - EAST KHAGORIJAN
ESTIMATEDQU
ANTITY
24.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of lighting system of 240V, 50Hz, Phase to Phase 1X350W LED Industrial type Search lighting fixture– 360/180 deg.
Rotation, coverage area 600 to 700 mtr., motorised operated luminaire along with mounting brackets & fixing accessories (10m height), suitable for degree of protection of IP65 and all other electrical equipment which are
necessary to make the system complete and safe in all respect. Lighting fixtures shall be suitable for loop-in/loop-out at both ends of the fittings. Fixture shall be suitable for 19 mm conduit entry and 16 SWG G.I. earth-wire
connections. The fixtures shall be provided with 3 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands and 1 entries shall be plugged using certified plugs.
Location: Watch tower
EA 4 0 EP-1
25.0 ANCHOR BOLTS
Design, Engineering, Manufacturing, Assembling, Supply & Installation of Anchor bolts for modular package (Container) and Steel foundation template for anchor bolt fixation shall be provided. Anchor bolts and Steel
template shall be provided by MPC Contractor 60 days prior to delivery of package.
Location: Container
EA As per requirement 0 EP-1
0 0 0
NOTES :
1.Bidder shall consider the following as part of their scope
a) Unloading of material at site
b) Storing of material at site
c) Shifting material to site (by use of crane/ forklift etc., shall are covered
d) Installation, testing, commissioning, PGTR.
f) Scaffolding as required
2. Values provided in the SOR may vary slightly. Vendor shall round of the quantity to nearest 500/1000 mtr drum.
3. Busduct routing and required number of fittings shall be as per site conditions.
TOTAL
Page 14 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
1.0 PREFABRICATED SUBSTATION
1.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Containerized electrical equipment room, UPS room, battery room with all accessories like lighting DB, cable tray,
Lighting Fixtures, Exhaust Fans, MCT, Cable Trays, Cable conduits, smoke detectors, fire alarm panel, fire extinguishers, etc suitable for housing all the electrical systems specified items from 01 – 10. Preferable size of
container is 40' X 8' X 8'.6''. Please refer the specification attached. Bidder shall considered accessories which are needed for completion of work.
EA 1 0 EP-2
1.2Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of MCT frame, It shall be painted mild steel, MCT blocks shall be flame retardant. The ingress protection shall be IP 55 min.
The transist shall have fire, water or gas tight integrity and MCT will maintain fire integrity and prevent gas migration. MCTs shall be with 120 minutes fire rating.
FRAME SIZE
1.2.1 S 2X1 AISI 316 EA 3 0
1.2.2 S 2X2 AISI 316 EA 111 0
1.2.3 S 2X3 AISI 316 EA 62 0
1.2.4 S 4X1 AISI 316 EA 102 0
1.2.5 S 4X2 AISI 316 EA 110 0
1.2.6 S 4X3 AISI 316 EA 10 0
1.2.7 S 4X4 AISI 316 EA 55 0
1.2.8 S 6X1 AISI 316 EA 25 0
1.2.9 S 6X1 PRIMED EA 15 0
MODULE SIZE
1.2.10 RM 20 EA 1056 0
1.2.11 RM 30 EA 5180 0
1.2.12 RM 40 EA 3423 0
1.2.13 RM 60 EA 125 0
1.2.14 RM 60 WOC EA 301 0
1.2.15 RM 10/0X12
ACCESSORIES
1.2.16 WEDGE 120MM AISI 316 EA 1028 0
1.2.17 STAYPLATE 120MM AISI 316 EA 2903 0
1.2.18 Lubricant 25 ml EA 1026 0
1.3 CONTAINER LIGHTING
1.3.1
Supply, installation, testing and commissioning of Normal lighting fixture with lamp, 240VAC PH-PH,36W/40W LED, Industrial type Wall/Suspension/Ceiling mounting luminaires with polycarbonate frosted cover along with
mounting brackets & fixing accessories, suitable for degree of protection of IP42 and all other electrical equipment which are necessary to make the system complete and safe in all respect. Lighting fixtures shall be
suitable for loop-in/loop-out. Fixture shall be suitable for 16 SWG G.I. earth-wire connections. The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable
Glands (Lighting layout shall be finalized during detail engineering).
EA 120 0 EP-2
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
EP-1
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
Page 1 of 12
Annexure- 3
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
1.3.2
Supply, installation, testing and commissioning of Emergency lighting fixture with lamp, 240VAC PH-PH,36W/40W LED (with built-in battery back-up time of 90min), Industrial type Wall/Suspension/Ceiling mounting
luminaires with polycarbonate frosted cover along with mounting brackets & fixing accessories, suitable for degree of protection of IP42 and all other electrical equipment which are necessary to make the system complete
and safe in all respect. Lighting fixtures shall be suitable for loop-in/loop-out. Fixture shall be suitable for 16 SWG G.I. earth-wire connections. The fixtures shall be provided with 2 numbers of M20 threaded entries having 2
numbers of M20 Brass Nickel Plated Cable Glands (Lighting layout shall be finalized during detail engineering).
EA 54 0 EP-2
2.0 LV SWITCHBOARD
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, 415VAC LV Normal Switchboard of Double Front, Draw out type with form of separation as 4b
having copper busbar rated for 3200A, TP, 50 Hz with short circuit capacity of 50kA for 1 Sec. Switchgear Panel shall have the following I/C & O/G breakers. All the outgoing feeders shall be provided with CBCT & ELR with
adjustable time & current setting for Earth Leakage protection with Residual Current Monitoring System (RCMS) as per CEAR 2010. Shunt Release shall be provided in all the Outgoing MCCB's.Panel should have busduct
entry at the rear(Refer the attached sketch).
Incomer:
a) 2 Nos. of 3200A, 415VAC, 50kA for 1 Sec, TP, NSPBD, EDO ACB with µp based LSING(Overload protection (L), short-time delayed short-circuit protection (S), instantaneous short-circuit protection (I) and ground-fault
protection (N)). protection having communication capability for GEG incomers and the same shall be suitable for bus duct entry from Top/Rear(shall be confirmed during detail engineering).
On, Off, Trip, Spring Charged indication Lamps for the incomers. MFM with Communication capability and analog Voltmeter and Ammeter with 240° deflection shall be provided for incomer feeders.
Outgoing Feeders:
a) Motor Feeders up to 40HP shall be provided with MCCB having adjustable Thermal Magnetic protection.
b) Motor Feeders above 40 HP shall be provided with MCCB having µp based protection and Numerical Motor Protection Relay having protective functions as per OISD RP149.
c) Power Feeders shall be provided with MCCB having adjustable Thermal Magnetic Protection.
d) 850 kVAr APFC System (in 12 Steps) with APP Capacitor banks & microprocessor based APFC relays with On, Off & Trip indication shall be provided. MCCB with Thermal Magnetic Protection & Capacitor duty
contactors.
On, Off & Trip indication Lamps shall be provided for Motor Feeders and Power Feeders.
EA 1 0
i. 0.25kW DOL Motor Starter EA 16 0
ii. 0.37kW DOL Motor Starter EA 2 0
iii. 0.55kW DOL Motor Starter EA 2 0
iv.1.5kW DOL Motor Starter EA 4 0
v. 2.2kW DOL Motor Starter EA 2 0
vi. 3.0kW DOL Motor Starter EA 7 0
vii. 3.7kW DOL Motor Starter EA 6 0
viii. 4.7kW DOL Motor Starter EA 2 0
ix. 5kW DOL Motor Starter EA 3 0
x. 5.5kW DOL Motor Starter EA 2 0
xi. 7.5kW DOL Motor Starter EA 2 0
xii.1kW Star-Delta (SD) Motor Starter EA 6 0
xiii. 5kW Star-Delta (SD) Motor Starter EA 4 0
xiv. 8.5kW Star-Delta (SD) Motor Starter EA 3 0
xv. 22kW Star-Delta (SD) Motor Starter EA 2 0
xvi. 37kW Soft Starter (SS) Motor Starte EA 2 0
xvii. 110kW Soft Starter (SS) Motor Starter EA 3 0
xviii.16A Power Feeder EA 16 0
xix. 32A Power Feeder EA 1 0
xx. 63A Power Feeder EA 14 0
xxi. 80A Power Feeder EA 1 0
xxii.100A Power Feeder EA 4 0
EP-22.1
Page 2 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
xxii. 250A Power Feeder with power contactor, auto-off-manual selector switch and overload relay controlled by a photocell. EA 1 0
xxiv. 400A Power Feeder EA 1 0
xxv. 800A Power Feeder 415VAC, 50kA for 1 Sec, TP, EDO ACB with µp based LSING, protection having communication capability EA 1 0
xxvi. 1000A Power Feeder 415VAC, 50kA for 1 Sec, TP, EDO ACB with µp based LSING, protection having communication capability EA 2 0
xxvi. 630A Power Feeder 415VAC, 50kA for 1 Sec, TP, EDO ACB with µp based LSING, protection having communication capability EA 1 0
Switchboard shall be designed as per the following specifications.
i. LV Switchgear Specification - 17039-ND-E-SP-9001
ii. Electrical Design Basis - 17039-ND-E-DB-9001.
Quantity of feeders in the Switchboard shall be designed in accordance with the following documents.
i. Electrical Load List - 17039-ND-E-GD-9001
ii. Electrical Single Line Diagram – 17039-ND-E-DW-9001
Switchboard shall be assembled and wired up in a containerized substation. Panel shall be suitable for bus duct entry in the top/rear for incomer section & Cable from the bottom for the outgoing sections provided with gland
plate (GI/Brass for multicore & Aluminium for Single Core) of min. 3mm thk. Panel shall be fabricated of CRCA Sheet steel having min. 2.0mm thk. for door and load bearing sections. Panel shall be powder coated after
nine tank process with Shade 631 as per IS-5. Panel shall be of Dust & Vermin proof and shall be confirming to IP42 degree of Protection. Panel shall be fabricated as per the relevant Indian Standards and above
mentioned reference documents. Control supply (110VAC for Motor Protection) shall be derived internally from the main incomer via control transformer (2X100%). Control supply for the metering & indication of incomer
feeders shall be derived from PT Secondary of respective incomer. Power Supply to the Spring Charging motor, Closing Coil, Tripping Coil & Protection relays of incomer shall be suitable for 110 VDC and the same shall
be provided by client. Panel fabricator shall have CPRI Type test certificate for Short Circuit, Temperature Rise and IP Protection. Drawing & QAP should be approved before the fabrication of panel. Breaker handling
accessories such as tools, trolleys, etc., and commissioning spares. Two year operational spares list with price shall be submitted by vendor.
Location: Normal Switchgear Room
i. 3.0kW DOL Motor Starter EA 1 0
ii. 22kW Star-Delta (SD) Motor Starter EA 2 0
iii. 40kW Soft Starter (SS) Motor Starter EA 3 0
iv. 90kW Soft Starter (SS) Motor Starter EA 2 0
v. 25A Power Feeder EA 2 0
vi. 32A Power Feeder EA 2 0
vii. 63A Power Feeder EA 3 0
viii.100A Power Feeder EA 2 0
ix.150A Power Feeder EA 3 0
EP-2
2.2
EP-2
EA
EP-2
1 0
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, 415VAC LV Emergency Switchboard of Single Front, Draw out type with form of separation as 4b
having copper busbar rated for 800A, TP, 50 Hz with short circuit capacity of 50kA for 1 Sec. Switchgear Panel shall have the following I/C & O/G breakers. all the outgoing feeders shall be provided with CBCT & ELR with
adjustable time & current setting for Earth Leakage protection with Residual Current Monitoring System (RCMS). Shunt Release shall be provided in all the Outgoing MCCB's.
Incomer:
a) 2 Nos. of 800A, 415VAC, 50kA for 1 Sec, TP, EDO ACB with µp based LSING(Overload protection (L), short-time delayed short-circuit protection (S), instantaneous short-circuit protection (I) and ground-fault protection
(N)). protection having communication capability for incomers and the same shall be suitable for cable entry from Bottom.
On, Off, Trip, Spring Charged indication Lamps for the incomers. MFM with Communication capability and analog Voltmeter and Ammeter with 240° deflection shall be provided for incomer feeders.
Outgoing Feeders:
a) Motor Feeders up to 40HP shall be provided with MCCB having adjustable Thermal Magnetic protection.
b) Motor Feeders above 40 HP shall be provided with MCCB having µp based protection and Numerical Motor Protection Relay having protective functions as per OISD RP149. Ammeter shall be provided in the
switchboard for indication current in Local Pushbutton Station (LPBS).
c) Power Feeders shall be provided with MCCB having adjustable Thermal Magnetic Protection.
On, Off & Trip indication Lamps shall be provided for Motor Feeders and Power Feeders.
2.1
Page 3 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
Switchboard shall be designed as per the following specifications.
i. LV Switchgear Specification - 17039-ND-E-SP-9001
ii. Electrical Design Basis - 17039-ND-E-DB-9001.
Quantity of feeders in the Switchboard shall be designed in accordance with the following documents.
i. Electrical Load List - 17039-ND-E-GD-9001
ii. Electrical Single Line Diagram – 17039-ND-E-DW-9001
The system shall be assembled and wired up in a containerized substation. Panel shall be suitable for Cable entry from the bottom for incoming & outgoing sections provided with gland plate (GI/Brass for multicore &
Aluminium for Single Core) of min. 3mm thk. Panel shall be fabricated of CRCA Sheet steel having min. 2.0mm thk. for door and load bearing sections. Panel shall be powder coated after nine tank process with Shade 631
as per IS-5. Panel shall be of Dust & Vermin proof and shall be confirming of IP42 degree of Protection. Panel shall be fabricated as per the relevant Indian Standards and above mentioned reference documents. Incomer
shall have Synchronizing scheme with control logic shall be provided. Control supply (110VAC for Motor Protection) shall be derived internally from the main incomer via control transformer (2X100%). Control supply for the
metering & indication of incomer feeders shall be derived from PT Secondary of respective incomer. Power Supply to the Spring Charging motor, Closing Coil, Tripping Coil & Protection relays of incomer shall be suitable
for 110 VDC and the same shall be provided by client. Panel fabricator shall have CPRI Type test certificate for Short Circuit, Temperature Rise and IP Protection. Drawing & QAP should be approved before the fabrication
of panel. Breaker handling accessories such as tools, trolleys, etc,. and commissioning spares. Two year operational spares list with price shall be submitted by vendor.
Location: Emergency Switchgear Room
2.2 EP-2
Page 4 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
3.0 INTERPOSING RELAY PANEL
3.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Interposing Relay Panel with following relays.
1. 5×64 Nos. of 30 VAC relay for signals to / from LPBS.
2. 7×73 Nos. of 24 VDC relay for signals to / from DCS.
3. 7×2 Nos. of 24 VDC relay for incomers.
4. 5×9 Nos. of 110VAC relay for signals to / from LPBS.
In addition to the quantity of relays mentioned above, 20% of spare in each rating & type shall be provided.
Location: Normal Switchgear Room
EA 1 0
3.2
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Interposing Relay Panel with following relays.
1. 7×9 Nos. of 24 VDC relay for signals to / from DCS.
3. 7×2 Nos. of 24 VDC relay for incomers.
4. 5×9 Nos. of 110VAC relay for signals to / from LPBS.
In addition to the quantity of relays mentioned above, 20% of spare in each rating & type shall be provided.
Location: Emergency Switchgear Room
EA 1 0
4.0 UPS
4.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of 30 kVA AC UPS (UPS rating shall be confirmed during Detailed Engineering) suitable for 3 phase input of 415 VAC, 50 Hz
& 3 phase output of 415 VAC, 50 Hz,3 phase, 4 wire, online, 2 X 100% parallel redundant UPS with static bypass, floor mounted, sheet steel panel with 2 x 50% Ni Cd type battery bank, AC UPS Distribution Board with
required number of incoming and outgoing feeders. Battery Backup time shall be 6 hours. Input power supply for the Main AC UPS shall be 415V ± 10%, 50 Hz, 3 phase, 3wire.The system shall be assembled and wired up
in a containerized substation as per attached sketch. UPS shall be complied as per the Electrical Design Basis -17039-ND-E-DB-9001 & Datasheet for Instrumentation UPS.
Location:UPS Room
EA 1 0
4.2
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of 110 V DC, 10 kVA (UPS rating shall be confirmed during Detailed Engineering), 2 Wire unearthed DC UPS System with
insulating monitoring device at the incomer of DCDB 2 X 50 %, 110V Nickel Cadmium Battery Bank (Ni Cd type) with Float and Float cum Boost Charger with stand/rack, DC Distribution Board of 110 V DC, 32 A Copper
busbar. Battery backup time shall be 2 hours.The system shall be assembled and wired up in the containerized substation as per attahced sketch. UPS shall be complied as per the Electrical Design Basis -17039-ND-E-DB-
9001 & Datasheet for Battery Charger & DCDB.
Location:UPS Room
EA 1 0
4.3
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of 5 kVA Telecom UPS (UPS rating shall be confirmed during Detailed Engineering) suitable for 3 phase input of 415 VAC,
50 Hz & 1 phase output of 240 VAC, 50 Hz, online, 2 X 100% parallel redundant UPS with static bypass, floor mounted, sheet steel panel with 2x50% Ni Cd type battery bank, Telecom AC UPS Distribution Board with
required number of incoming and outgoing feeders. Battery Backup time shall be 12 hours. Input power supply for the Telecom AC UPS shall be 415V ± 10%, 50 Hz, 3 phase, 3wire. The system shall be assembled and
wired up in the containerized substation as per attached sketch. UPS shall be complied as per the Electrical Design Basis -17039-ND-E-DB-9001 & Datasheet for Telecom UPS.
Location:UPS Room
EA 1 0
5.0 MAIN POWER DISTRIBUTION BOARD
5.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type 415VAC LV Main Power Distribution Board (MPDB) for Search light, having Copper busbar rated for
400A, TP, 50 Hz with short circuit capacity of 10kA for 1 Sec.
MPDB shall have 1 No. of 400A, TP, MCCB incomer & 8 Nos. of 25A, TP MCCB Outgoing feeders.
Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
Location:UPS Room
EA 1 0 EP-2
6.0 LIGHTING TRANSFORMER WITH DISTRIBUTION BOARD AND UTILITY TRANSFORMER WITH DISTRIBUTION BOARD
6.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, Normal Lighting Transformer and Normal Lighting Distribution Board complete with 1 number of
75kVA, 415V/240V AC, 50Hz, 3 phase, 3 wire, Delta/Delta, 4% impedance, Off Load Tap changer (OCTC) with ±5% in steps of 2.5%, Lighting Transformer which forms a part/separate of MLDB. Main Lighting Distribution
Board (MLDB) shall be rated for 240V AC, 3 Phase, 3 Wire, 250A, 10kA for 1 sec, Cu busbar.
Incomer : 1 No. of 250A, 240VAC, TP MCCB
Outgoing Feeders :
1. 22 Nos. of 16A, 240VAC, TP MCCB
2. 10 Nos. of 32A, 240VAC, TP MCCB
Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
The system shall be assembled and wired up in a containerized substation as per attached sketch.
Location: Refer Electrical Substation layout
EA 1 0 EP-2
6.2
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, Emergency Lighting Transformer and Emergency Lighting Distribution Board (ELDB) complete with
1 number of 50kVA, 415V/240V AC, 50Hz, 3 phase, 3 wire, Delta/Delta, 4% impedance, Off Load Tap Changer (OCTC) with ±5% in steps of 2.5%, Lighting Transformer which forms a part/separate of ELDB. Emergency
Lighting Distribution Board shall be rated for 240V AC, 3 Phase, 3 Wire, 150A, 10kA for 1 sec, Cu busbar.
Incomer : 1 No. of 150A, 240VAC, TP MCCB
Outgoing Feeders :
1. 18 Nos. of 16A, 240VAC, TP MCCB
2. 10 Nos. of 32A, 240VAC, TP MCCB
Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
The system shall be assembled and wired up in a containerized substation as per attached sketch.
Location: Refer Electrical Substation layout
EA 1 0 EP-2
EP-2
EP-2
Page 5 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
6.3
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, Utility Transformer and Utility Distribution Board complete with 1 number of 50kVA, 415V/415V AC,
50Hz, 3 phase, 4 wire, Dyn11, effectively grounded, 4% impedance, Off Load Tap changer (OCTC) with ±5% in steps of 2.5%, Utility Transformer which forms a part/separate of Utility Distribution Board. Utility Distribution
board shall be rated for 415V AC, 3 Phase, 4 Wire, 150A, 10kA for 1 sec, Cu busbar.
UDB shall have 1 No. of 150A, TPN, MCCB incomer & 16 Nos. of 32A, TPN MCB Outgoing feeders.
Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
The system shall be assembled and wired up in a containerized substation as per attached sketch.
Location: Emergency Switchgear Room
EA 1 0 EP-2
6.4
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, Security Room Utility Transformer and Utility Distribution Board complete with 1 number of 50kVA,
415V/415V AC, 50Hz, 3 phase, 4 wire, Dyn11, effectively grounded, 4% impedance, Off Load Tap changer (OCTC) with ±5% in steps of 2.5%, Utility Transformer which forms a part/separate of Utility Distribution Board.
Utility Distribution board shall be rated for 415V AC, 3 Phase, 4 Wire, 150A, 10kA for 1 sec, Cu busbar.
SRUDB shall have 1 No. of 150A, TPN, MCCB incomer & 16 Nos. of 32A, TPN MCB Outgoing feeders.
Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
The system shall be assembled and wired up in a containerized substation as per attached sketch.
Location: Outdoor plant area for security room AC
EA 1 0 EP-1
6.5
Design,Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Wall / Floor mountable type 240VAC ETP &OWS Normal Lighting Distribution Board (ETP&OWS-NLDB) having Copper
busbar rated for 32A, TP, 50 Hz with short circuit capacity of 10kA for 1 Sec. NLDB shall have the following I/C & O/G breakers. Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per
CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
Incomer : 1 No. of 32A, 240VAC, 16kA for 1 Sec, TP MCCB
Outgoing Feeders :
1. 12 Nos. of 6A, 240VAC, 16kA for 1 Sec, DP RCBO with ∆In of100mA.
NLDB shall be suitable for Cable entry from the bottom for Incoming & outgoing feeders provided with aluminium gland plate of min. 3mm thk. NLDB shall have double/single door arrangement for the outgoing feeders. DB
shall be fabricated of CRCA Sheet steel having min. 2.0mm thk. and shall be powder coated after seven tank process with Shade 631 as per IS-5. DB shall be of Dust & Vermin proof and shall be confirming of IP52 degree
of Protection. Panel fabricator shall have CPRI Type test certificate for Short Circuit, Temperature Rise and IP Protection. Drawing & QAP should be approved before the fabrication of DB.
Location : ETP container
EA 1 0 EP-1
6.6
Design,Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Wall / Floor mountable type 240VAC ETP &OWS Emergency Lighting Distribution Board (ETP&OWS-ELDB) having
Copper busbar rated for 32A, TP, 50 Hz with short circuit capacity of 10kA for 1 Sec. ELDB shall have the following I/C & O/G breakers. Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as
per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
Incomer : 1 No. of 32A, 240VAC, 16kA for 1 Sec, TP MCCB
Outgoing Feeders :
1. 12 Nos. of 6A, 240VAC, 16kA for 1 Sec, DP RCBO with ∆In of100mA.
ELDB shall be suitable for Cable entry from the bottom for Incoming & outgoing feeders provided with aluminium gland plate of min. 3mm thk. ELDB shall have double/single door arrangement for the outgoing feeders. DB
shall be fabricated of CRCA Sheet steel having min. 2.0mm thk. and shall be powder coated after seven tank process with Shade 631 as per IS-5. DB shall be of Dust & Vermin proof and shall be confirming of IP52 degree
of Protection. Panel fabricator shall have CPRI Type test certificate for Short Circuit, Temperature Rise and IP Protection. Drawing & QAP should be approved before the fabrication of DB.
Location : ETP container
EA 1 0 EP-1
7.0 HEAT TRACING DISTRIBUTION BOARD
7.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Floor mountable type, Electric Heat Tracing System complete with EHT Transformer of 50kVA, 415V/240V AC, 50Hz, 3
phase, 3 wire, Delta/delta, 4% impedance, Off Load Tap changer (OCTC) with ±5% in steps of 2.5%. Heat Tracing Distribution Board shall be rated for 240V AC, 50Hz, 3 Ph, 3 Wire shall be preferably placed in safe area.
EHT system should have certification for hazardous area(class 1, zone 2, gas grp. IIA/IIB) and Temperature Rating(Temp.T3) by statutory body of India. Sub distribution boards (as applicable) shall be suitable for 240V,
50Hz, phase to phase, two wire (derived from a 415 V, 50 Hz, 3 phase, 3 wire neutral solidly earthed system) system.
Electrical Heat Tracing system shall be designed suitable for the steady state voltage tolerance of +6/-10% and frequency tolerance of ±3%.
Transformer incomer : 1 No. of 100A, 415VAC, TP MCCB
Transformer outgoing : 1 No. of 150A, 240VAC, TP MCCB
Heat tracing DB Outgoing Feeders : 20 Nos. of 32A, 240VAC, TP MCCB
Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in Incoming MCCB.
Location: Normal switchgear room
EA 1 0 EP-2
8.0 BUSDUCT
8.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Non-Segregated Phase Bus Duct enclosing Copper bus bars for service voltage of 415V AC, 3 Phase, 3 wire, 3200A,
50kA for 1 sec., including necessary rigid connections at switchgear end with required numbers of vertical and horizontal elbows. Busduct enclosure material shall be of Aluminum alloy sheets having minimum 3mm thk.
with suitable bolted covers. Bus bar shall be of electrolytic grade, high conductivity copper bus bar confirm to BIS and it shall be of electro-tinned. All bus-bar shall be insulated with heat shrinkable PVC sleeves (or better)
and shall be supported at required intervals with non- hygroscopic, non-deteriorating, and non–inflammable SMC / FRP (or better) supports having adequate mechanical strength and a high tracking resistance, to withstand
short circuit fault levels more than the designed. Bus bar system shall be designed with required clearance between phases as specified in the standards. Any separator used shall be made of non-hygroscopic material
having adequate mechanical strength to withstand the worst fault conditions. Insulating sheet barriers shall be as per Bus duct Specification and Layout. All gasketed- flanged joints shall be suitably protected against direct
splashing of rainwater in case of outdoor runs portion. Outdoor installed busduct portion shall be provided with rain canopy/sunshade. Bus Duct shall be suitable for Indoor & outdoor installation as applicable as per the
attached layout. Bidder shall consider required number of Elbows, tee joints, phase crossover chamber based on this layout.The bus duct shall be provided with adequate number of thermostatically controlled space heaters
of adequate capacity to maintain the internal temperature above the dew point to prevent moisture condensation within the bus duct.
EA 2 0 EP-1
9.0 HIGH MAST LIGHTING FIXTURE
Page 6 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
9.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of the Complete High mast lighting system with High mast (30m height) of double sided arrangement with 18 numbers of 1 X
350W LED flood light fixture with LED lamps, Lantern carriage, 2 Nos. of Plu & Socket, control gear, termination box, winching device, winch motor, winch motor panel, Raising and Lowering system (R & L), lighting wiring
materials such as flexible cable of EPR insulated from Plug & Socket assembly to the control gear on the top, cable glands, lugs, inbuilt junction boxes within the high mast pole, 2 numbers of aviation obstruction warning
light, lightning finial, flame proof feeder pillar for automatic switching operation of luminaires based on Duck-Dawn Electronic timer, cabling from feeder pillar to individual fixtures, cabling for winch motor, power tools and all
other electrical equipment which are necessary to make the system complete and safe in all aspects.
EA 5 0 EP-1
Page 7 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
10.0 LIGHTING DISTRIBUTION BOARD
10.1
Design,Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Wall / Floor mountable type 240VAC LV Normal Lighting Distribution Board (NLDB) having Copper busbar rated for 32A,
TP, 50 Hz with short circuit capacity of 10kA for 1 Sec. NLDB shall have the following I/C & O/G breakers. Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt
Release shall be provided in Incoming MCCB.
Incomer : 1 No. of 32A, 240VAC, 16kA for 1 Sec, TP MCCB
Outgoing Feeders :
1. 12 Nos. of 6A, 240VAC, 16kA for 1 Sec, DP RCBO with ∆In of100mA.
NLDB shall be suitable for Cable entry from the bottom for Incoming & outgoing feeders provided with aluminium gland plate of min. 3mm thk. NLDB shall have double/single door arrangement for the outgoing feeders. DB
shall be fabricated of CRCA Sheet steel having min. 2.0mm thk. and shall be powder coated after seven tank process with Shade 631 as per IS-5. DB shall be of Dust & Vermin proof and shall be confirming of IP52 degree
of Protection. Panel fabricator shall have CPRI Type test certificate for Short Circuit, Temperature Rise and IP Protection. Drawing & QAP should be approved before the fabrication of DB.
Location: Process Area
EA 10 0 EP-1
10.2
Design,Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Wall / Floor mountable type 240VAC LV Emergency Lighting Distribution Board (ELDB) having Copper busbar rated for
32A, TP, 50 Hz with short circuit capacity of 10kA for 1 Sec. ELDB shall have the following I/C & O/G breakers. Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt
Release shall be provided in Incoming MCCB.
Incomer : 1 No. of 32A, 240VAC, 16kA for 1 Sec, TP MCCB
Outgoing Feeders :
1. 12 Nos. of 6A, 240VAC, 16kA for 1 Sec, DP RCBO with ∆In of100mA.
ELDB shall be suitable for Cable entry from the bottom for Incoming & outgoing feeders provided with aluminium gland plate of min. 3mm thk. ELDB shall have double/single door arrangement for the outgoing feeders. DB
shall be fabricated of CRCA Sheet steel having min. 2.0mm thk. and shall be powder coated after seven tank process with Shade 631 as per IS-5. DB shall be of Dust & Vermin proof and shall be confirming of IP52 degree
of Protection. Panel fabricator shall have CPRI Type test certificate for Short Circuit, Temperature Rise and IP Protection. Drawing & QAP should be approved before the fabrication of DB.
Location: Process Area
EA 10 0 EP-1
11.0 OUTDOOR
11.1 SHED LIGHTING
11.1.1
Supply, installation, testing and commissioning of Normal lighting fixture with lamp, 240VAC PH-PH, 42W LED, Industrial type,weather proof, well glass type lighting fixture along with mounting brackets & fixing
accessories, suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture
shall be suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands.
EA 86 0 EP-1
11.1.2
Supply, installation, testing and commissioning of Emergency lighting fixture with lamp, 240VAC PH-PH, 42W LED, Industrial type,weather proof, well glass type lighting fixture along with mounting brackets & fixing
accessories, suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture
shall be suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands. 25% of emergency lighting shall
be self contained emergency type with integral battery backup time of 90min.
EA 30 0 EP-1
11.1.3
Supply, installation, testing and commissioning of Critical lighting fixture with lamp, 110VDC, 2WIRE, 15W LED, Industrial type Wall/Suspension/Ceiling/Column mounting luminaires with polycarbonate frosted cover along
with mounting brackets & fixing accessories, suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect. Lighting fixtures shall be
suitable for loop-in/loop-out. Fixture shall be suitable for 16 SWG G.I. earth-wire connections. The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable
Glands (Lighting layout shall be finalized during detail engineering).
EA 16 0 EP-1
11.1.4
Supply, installation, testing and commissioning of Normal lighting fixture with lamp, 240VAC PH-PH, 42W LED, Flame proof type, well glass type lighting fixture suitable along with mounting brackets & fixing accessories,
for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture shall be suitable for
16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands. FLP Light fittings, Cable Glands & Plugs shall be
certified by CMRI/PESO.
EA 46 0 EP-1
11.1.5
Supply, installation, testing and commissioning of Emergency lighting fixture with lamp, 240VAC PH-PH, 42W LED, Flame proof type, well glass type lighting fixture along with mounting brackets & fixing accessories,
suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture shall be
suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands. FLP Light fittings, Cable Glands & Plugs
shall be certified by CMRI/PESO. 25% of emergency lighting shall be self contained emergency type with integral battery backup time of 90min.
EA 20 0 EP-1
11.1.6
Supply, installation, testing and commissioning of Critical lighting fixture with lamp, 110VDC, 2WIRE, 15W LED, Flame proof type, Wall/Suspension/Ceiling/Column mounting luminaires with polycarbonate frosted cover
along with mounting brackets & fixing accessories, suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect. Lighting fixtures shall
be suitable for loop-in/loop-out. Fixture shall be suitable for 16 SWG G.I. earth-wire connections. The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable
Glands (Lighting layout shall be finalized during detail engineering).
EA 10 0 EP-1
12.0 CONTAINER OUTDOOR LIGHTING
12.1
Supply, installation, testing and commissioning of Normal lighting fixture with lamp, 240VAC PH-PH, 90W LED, Industrial type,weather proof, Wall/Column mounting luminaires along with mounting brackets & fixing
accessories, suitable for degree of protection of IP42 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture
shall be suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands.
EA 35 0 EP-1
Page 8 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
12.2
Supply, installation, testing and commissioning of Emergency lighting fixture with lamp, 240VAC PH-PH 90W LED, Industrial type,weather proof, Wall/Column mounting luminaires along with mounting brackets & fixing
accessories, suitable for degree of protection of IP42 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture
shall be suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands.25% of emergency lighting shall
be self contained emergency type with integral battery backup time of 60min.
EA 27 0 EP-1
13.0 STREET LIGHTING
13.1
Supply, installation, testing and commissioning of Normal lighting fixture with lamp, 240VAC PH-PH, 40W LED street light of 8m height from FGL with Swaged Pole, Industrial type,weather proof, luminaires along with
mounting brackets & fixing accessories, suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable
for loop-in/loop-out. Fixture shall be suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands.
EA 57 0 EP-1
14.0 PIPE RACK LIGHTING
14.1
Supply, installation, testing and commissioning of Normal lighting fixture with lamp, 240VAC PH-PH 36W Well glass LED, flame proof type, channel/Column mounting luminaires along with mounting brackets & fixing
accessories, suitable for degree of protection of IP65 and all other electrical equipment which are necessary to make the system complete and safe in all respect.Lighting fixtures shall be suitable for loop-in/loop-out. Fixture
shall be suitable for 16 SWG G.I. earth-wire connections.The fixtures shall be provided with 2 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands.
EA 50 0 EP-1
15.0 WELDING SOCKET
15.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Weather Proof Type 415V, 3P+E, 63A rating with heavy duty plug and socket with MCB protection along with mounting
accessories. Plug & Socket shall have the necessary mechanical interlocks and earthing facilities. The enclosure shall have suitable protection for site conditions specified such as weather-proof, dust proof, corrosion
resistant, etc. Welding receptacles shall be provided at suitable locations as specified in the layout.
EA 9 0 EP-1
15.2
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of flame proof Type 415V, 3P+E, 63A rating with heavy duty plug and socket with MCB protection along with mounting
accessories. Plug & Socket shall have the necessary mechanical interlocks and earthing facilities. The enclosure shall have suitable protection for site conditions specified such as weather-proof, dust proof, corrosion
resistant, etc. Welding receptacles shall be provided at suitable locationsas specified in the layout.
EA 5 0 EP-1
16.0 CONVENIENT SOCKET
16.1Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Industrial Type 240V, 2P+E, 15/16A rating with heavy duty plug and socket along with mounting accessories. The
enclosure shall have suitable protection for site conditions specified such as weather-proof, dust proof, corrosion resistant, etc. Convenient Socekt shall be provided at suitable locations as specified in the layout.EA 40 0 EP-2
17.0 AIR CONDITIONERS
16
(based on heat load)
18.0 CABLES & CABLE LUGS
18.1
Design, Supply and laying of 1100V grade, single/multi-core, stranded copper conductor, extruded XLPE insulated, with extruded PVC inner sheath (type ST-2), galvanised steel wire armoured and overall sheath with
extruded flame retardant low smoke (FRLS) PVC compound (type ST-2). Outer Sheath shall be resistant to water, ultra violet radiation, fungus, termite and rodent attacks. Consumables such as cable ferrulers, cable tie,
name plates,equipment fixing hardwares and cable markers.Colour of the outer sheath shall be black. Cables shall confirm to IS- 7098-PART-I, IS-5831, IS-10810-PART-33, IS-10810-PART-53, IS-10810-PART-61, IS-
10810-PART-62
18.1.1 3CX2.5 Sq.mm MTR 9456 0
18.1.2 3CX4 Sq.mm MTR 2244 0
18.1.3 3CX6 Sq.mm MTR 2544 0
18.1.4 3CX10 Sq.mm MTR 1524 0
18.1.5 3CX16 Sq.mm MTR 4308 0
18.1.6 3CX25 Sq.mm MTR 4464 0
18.1.7 3CX35 Sq.mm MTR 2352 0
0
EP-1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of SPLIT / DUCTABLE SPLIT TYPE AIR CONDITIONERS Complete with indoor unit with remote, outdoor unit, copper
tubing, insulating materials, supporting materials, adequate sized voltage stabilizer, isolating breakers, cables/ wires and with all accessories, hardwares etc,. for switchgear room, ups room, battery room, CCR rooms.
Number of AC unit(N) shall be based on heat load calculation. Bidder shall consider (N+1) for redundancy.
2 Ton High Wall Split AC - 5 Star
Location: All containerized room
EA17.1 EP-2
Page 9 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
18.1.8 3CX50 Sq.mm MTR 600 0
18.1.8 3CX70 Sq.mm MTR 840 0
18.1.9 3CX95 Sq.mm MTR 864 0
18.1.10 3CX120 Sq.mm MTR 900 0
18.1.11 1CX240 Sq.mm MTR 6480 0
18.1.12 2CX2.5 Sq.mm MTR 2340 0
18.1.13 7CX2.5 Sq.mm MTR 16008 0
18.1.14 10CX2.5 MTR 2340 0
18.2Design, Supply, Installation & Commissioning of 1100V grade, Cable lugs suitable for the voltage grade of 0.6/1kv , lugs shall be insulated / non-insulated ring / pin type and made from high conductivity, tinned copper,
compression type lug. Cable lug shall confirm to IS-8309 and IS-8337.Each core shall have separate cable lug. Copper lugs for copper cables and aluminium lugs for aluminium cables shall be used
18.2.1 3CX2.5 Sq.mm PIN TYPE INSULATED COPPER EA 270 0
18.2.2 3CX4 Sq.mm PIN TYPE INSULATED COPPER EA 60 0
18.2.3 3CX6 Sq.mm RING TYPE NON-INSULATED COPPER EA 60 0
18.2.4 3CX10 Sq.mm RING TYPE NON-INSULATED COPPER EA 54 0
18.2.5 3CX16 Sq.mm RING TYPE NON-INSULATED COPPER EA 96 0
18.2.6 3CX25 Sq.mm RING TYPE NON-INSULATED COPPER EA 108 0
18.2.7 3CX35 Sq.mm RING TYPE NON-INSULATED COPPER EA 66 0
18.2.8 3CX50 Sq.mm RING TYPE NON-INSULATED COPPER EA 12 0
18.2.9 3CX70 Sq.mm RING TYPE NON-INSULATED COPPER EA 18 0
18.2.10 3CX95 Sq.mm RING TYPE NON-INSULATED COPPER EA 18 0
18.2.11 3CX120 Sq.mm RING TYPE NON-INSULATED COPPER EA 18 0
18.2.12 1CX240 Sq.mm RING TYPE NON-INSULATED COPPER EA 42 0
18.2.13 2CX2.5 PIN TYPE INSULATED COPPER EA 32 0
18.2.14 7CX2.5 PIN TYPE INSULATED COPPER EA 910 0
18.2.15 10CX2.5 PIN TYPE INSULATED COPPER EA 160 0
19.0 CABLE TRAY
19.1Design, Supply and laying of Ladder/ Perforated type cable trays of FRP material, 3mm/4mm thick heavy duty straight ladder/Perforated type suitable for indoor / outdoor areas. Straight sections shall be provided in
standard lengths of 3m. All splice plates and assembly hardwares shall be of FRP material. FRP sheet cover of 3mm thick heavy duty type shall be provided.
19.1.1 750mm width ladder type cable tray, 150 mm height with cover MTR 900 0
19.1.2 600mm width ladder type cable tray, 150 mm height with cover MTR 150 0
19.1.3 450mm width ladder type cable tray, 150 mm height with cover MTR 350 0
19.1.4 300mm width ladder type cable tray, 150 mm height with cover MTR 600 0
19.1.5 150mm width perforated type cable tray, 100 mm height with cover MTR 1343 0
19.1.6 100mm width perforated type cable tray, 50 mm height with cover MTR 250 0
EP-1
EP-1
EP-1
Page 10 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
19.2 Horizontal Bends (90°), of FRP material
19.2.1 750mm width ladder type cable tray, 150 mm height with cover NOS 13 0
19.2.2 600mm width ladder type cable tray, 150 mm height with cover NOS 2 0
19.2.3 450mm width ladder type cable tray, 150 mm height with cover NOS 12 0
19.2.4 300mm width ladder type cable tray, 150 mm height with cover NOS 10 0
19.2.5 150mm width perforated type cable tray, 100 mm height with cover NOS 19 0
19.2.6 100mm width perforated type cable tray, 50 mm height with cover NOS 10 0
19.3 Inside Bends (90°), of FRP material
19.3.1 750mm width ladder type cable tray, 150 mm height with cover NOS 21 0
19.3.2 600mm width ladder type cable tray, 150 mm height with cover NOS 2 0
19.3.3 450mm width ladder type cable tray, 150 mm height with cover NOS 12 0
19.3.4 300mm width ladder type cable tray, 150 mm height with cover NOS 8 0
19.3.5 150mm width perforated type cable tray, 100 mm height with cover NOS 16 0
19.3.6 100mm width perforated type cable tray, 50 mm height with cover NOS 4 0
19.4 Outside Bends (90°), of FRP material
19.4.1 750mm width ladder type cable tray, 150 mm height with cover NOS 26 0
19.4.2 600mm width ladder type cable tray, 150 mm height with cover NOS 3 0
19.4.3 450mm width ladder type cable tray, 150 mm height with cover NOS 12 0
19.4.4 300mm width ladder type cable tray, 150 mm height with cover NOS 8 0
19.4.5 150mm width perforated type cable tray, 100 mm height with cover NOS 16 0
19.4.6 100mm width perforated type cable tray, 50 mm height with cover NOS 4 0
19.5 Reducer (Straight Type) of FRP material
19.5.1 750mm(W1) x 600mm(W2) x 150mm(H) Ladder Type with Cover NOS 2 0
19.5.2 750mm(W1) x 450mm(W2) x 150mm(H) Ladder Type with Cover NOS 2 0
19.5.3 600mm(W1) x 450mm(W2) x 150mm(H) Ladder Type with Cover NOS 1 0
19.5.4 600mm(W1) x 300mm(W2) x 150mm(H) Ladder Type with Cover NOS 1 0
19.5.5 450mm(W1) x 300mm(W2) x 150mm(H) Ladder Type with Cover NOS 3 0
19.5.6 450mm(W1) x 150mm(W2) x 150mm(H) Ladder Type with Cover NOS 1 0
19.5.7 300mm(W1) x 150mm(W2) x 150mm(H) Ladder Type with Cover NOS 3 0
19.5.8 300mm(W1) x 100mm(W2) x 150mm(H) Ladder Type with Cover NOS 1 0
19.5.9 150mm(W1) x 100mm(W2) x 100mm(H) Performated Type with Cover NOS 2 0
19.6 CABLE TRAY FITTINGS
19.6.1 Flat splice plate (750mm width ladder type cable tray, 150 mm height ) NOS 321 0
19.6.2 Flat splice plate (600mm width ladder type cable tray, 150 mm height) NOS 53 0
EP-1
EP-1
Page 11 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
19.6.3 Flat splice plate (450mm width ladder type cable tray, 150 mm height) NOS 129 0
19.6.4 Flat splice plate (300mm width ladder type cable tray, 150 mm height) NOS 209 0
19.6.5 Flat splice plate (150mm width perforated type cable tray, 100 mm height) NOS 466 0
19.6.6 Flat splice plate (100mm width perforated type cable tray, 50 mm) NOS 90 0
19.6.7 Set of round head square neck type bolts and hex nuts M10 X25 MM NOS 10136 0
19.6.8 Hold-down clamps, S-type, as per drawing number , c/w stainless steel fastening hardware NOS 531 0
19.6.9 Hold-down clamps, J-type, as per drawing number , c/w stainless steel fastening hardware NOS 667 0
19.7 Supply and installation of cable tray support & electrical equipment supports
19.7.1 50×50×6 mm L angle MTR 370 0
20.0 HUME PIPE & HDPE
20.1 Design, Supply & laying RCC Hume pipes under driveway or culverts or road crossover including excavation, providing collar joints, backfilling etc,. Which shall be NP2 and length of each pipe shall be 1.50M.
20.1.1 250 MTR 24 0
20.1.2 450 MTR 24 0
20.2 Supply & laying of 50mm dia heavy duty HDPE pipes in RCC foundation of Lighting poles with all required accessories MTR 100 0
20.2 Supply & laying of 50mm dia heavy duty HDPE pipes in RCC foundation of lighting poles with all required accessories such as Bends, Elbows, Couplers, etc to complete as per the instruction of site engineer. MTR 100 0
20.3 Supply & laying of 100mm dia heavy duty HDPE pipes in RCC foundation of lighting poles with all required accessories such as Bends, Elbows, Couplers, etc to complete as per the instruction of site engineer. MTR 20 0
21.0 CABLE GLAND
21.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of FLP HEAVY DUTY DOUBLE COMPRESSION Cable Termination(FLP):Providing termination of 1.1 kV grade armoured
cable for the following sizes including supply of FLP heavy duty double compression cable glands of Baliga/CEAG-FCG /FlexPro/ FEPL make, crimping lugs and allied jointing materials, etc. all complete as per
specification & direction of Engineer In-charge. Cable Glands & Plugs shall be certified by CMRI/PESO.
21.1.1 M20×1.5 EA 41 0
21.1.2 M25×1.5 EA 31 0
21.1.3 M32×1.5 EA 9 0
21.1.4 M40×1.5 EA 3 0
21.2
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of NON-FLP HEAVY DUTY DOUBLE COMPRESSION Cable Termination (NON FLP): Providing termination of 1.1 kV grade
armoured cable for the following sizes including supply of NON FLP heavy duty Double Compression cable glands, crimping type lugs and allied jointing materials, etc. all complete as per specification & direction of
Engineer In-charge. Glands and lugs shall be of approved make.
21.2.1 M20×1.5 EA 107 0
21.2.2 M25×1.5 EA 59 0
21.2.3 M32×1.5 EA 15 0
21.2.4 M40×1.5 EA 9 0
22.0 EARTHING & LIGHTNING
EP-1
EP-1
EP-1
EP-1
EP-2
Page 12 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
22.1
Design, Engineering, Supply, Installation, Testing and Commissioning of maintenance free Chemically treated Electrical Earth Pit consisting of Copper solid earth electrode of 50mm dia & 3m long. Earth enhancement
material shall be of superior conductive material so that it improves earthing effectiveness. The quantity of earth enhancing material required per earth electrode shall be minimum 10Kg shall be supplied for each
electrodes or as per OEM recommendation. Electrical Earth Pit shall consists of Copper Rod, Test Links, Connections Bolts made of SS, Bimetallic connector for connection of aluminium earth strip to the test link,
Inspection Chamber made of Brick masonry work/precast RCC chamber of 900×900mm.
EA 58 0 EP-1
22.2
Design, Engineering, Supply, Installation, Testing and Commissioning of maintenance free Chemically treated Lightning Earth Pit consisting of Copper solid earth electrode of 50mm dia & 3m long. Earth enhancement
material shall be of superior conductive material so that it improves earthing effectiveness. The quantity of earth enhancing material required per earth electrode shall be minimum 10Kg shall be supplied for each
electrodes or as per OEM recommendation. Electrical Earth Pit shall consists of Copper Rod, Test Links, Connections Bolts made of SS, Bimetallic connector for connection of aluminium earth strip to the test link,
Inspection Chamber made of Brick masonry work/precast RCC chamber of 900×900mm.
EA 41 0
22.3
Design, Engineering, Supply, Installation, Testing and Commissioning of maintenance free Chemically treated Control Earth Pit consisting of Copper solid earth electrode of 50mm dia & 3m long. Earth enhancement
material shall be of superior conductive material so that it improves earthing effectiveness. The quantity of earth enhancing material required per earth electrode shall be minimum 10Kg shall be supplied for each
electrodes or as per OEM recommendation. Electrical Earth Pit shall consists of Copper Rod, Test Links, Connections Bolts made of SS, Bimetallic connector for connection of aluminium earth strip to the test link,
Inspection Chamber made of Brick masonry work/precast RCC chamber of 900×900mm.EA 4 0
22.4
Design, Engineering, Supply, Installation, Testing and Commissioning of maintenance free Chemically treated Signal Earth Pit consisting of Copper solid earth electrode of 50mm dia & 3m long. Earth enhancement material
shall be of superior conductive material so that it improves earthing effectiveness. The quantity of earth enhancing material required per earth electrode shall be minimum 10Kg shall be supplied for each electrodes or as
per OEM recommendation. Electrical Earth Pit shall consists of Copper Rod, Test Links, Connections Bolts made of SS, Bimetallic connector for connection of aluminium earth strip to the test link, Inspection Chamber
made of Brick masonry work/precast RCC chamber of 900×900mm.
EA 4 0
22.5 Design, Engineering, Manufacturing, Assembling, Supply, Installation & Testing of Grounding strips of aluminium flat/wire or Copper Wire and trench work as per requirement and back filling wherever required.
22.5.1 100 x 6 mm Aluminium strip - Buried in soil MTR 2800 0
22.5.2 100 x 6 mm Aluminium strip - Above ground MTR 900 0
22.5.3 30 x 6 mm Aluminium strip MTR 300 0
22.5.4 25 x 3 mm Aluminium strip MTR 800 0
22.6 Supplying and fixing of Stranded Aluminium wire (8 SWG) with PVC insulation MTR 200 0
22.7 Supplying and fixing of Stranded Aluminium wire (10 SWG) with PVC insulation MTR 300 0
22.8 Supplying and fixing of Stranded 16 Sq.mm insulated flexible aluminium cable MTR 50 0
22.9 Aluminium Earth bar with 10 holes as minimum supplied complete with washer, nuts and bolts(hardware accessories shall be SS). EA 10 0
23.0 MOV DISTRIBUTION BOARD
23.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Structure/Coloumn mountable type 415VAC MOV Distribution Board (MOVDB) having Copper busbar rated for 63A, TP,
50 Hz with short circuit capacity of 10kA for 1 Sec. MOV DB shall be suitable for installation in Hazardous area Class 1, Zone-2, Gas Group IIA/IIB, Temp. Class T3. MOV DB shall be of Ex'd' type with min. IP 66 made from
Aluminium alloy (LM-06), provided with required no. of metric/inches threaded cable entries for the entry of cables and suitable certified glands and plugs. MOV DB shall be supplied with rain canopy/sun shade for weather
protection. Final Paint colour shade for the DB shall be shade 631 as per IS-5. Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in
Incoming MCCB.
MOVDB shall have 1 No. of 63A, TP, MCCB incomer & 20 Nos. of 10A, TP MCCB Outgoing feeders.
Location: Outdoor process Area
EA 1 0
23.2
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of Structure/Coloumn mountable type 415VAC MOV Distribution Board (MOVDB) having Copper busbar rated for 63A, TP,
50 Hz with short circuit capacity of 10kA for 1 Sec. MOV DB shall be suitable for installation in Hazardous area Class 1, Zone-2, Gas Group IIA/IIB, Temp. Class T3. MOV DB shall be of Ex'd' type with min. IP 66 made from
Aluminium alloy (LM-06), provided with required no. of metric/inches threaded cable entries for the entry of cables and suitable certified glands and plugs. MOV DB shall be supplied with rain canopy/sun shade for weather
protection. Final Paint colour shade for the DB shall be shade 631 as per IS-5. Incoming feeder shall be provided with CBCT & ELR for Earth Leakage protection as per CEAR 2010. Shunt Release shall be provided in
Incoming MCCB.
MOVDB shall have 1 No. of 63A, TP, MCCB incomer & 20 Nos. of 10A, TP MCCB Outgoing feeders.
Location: Outdoor Tank Area
EA 1 0
24.0 SEARCH LIGHTING FIXTURE
24.1
Design, Engineering, Manufacturing, Assembling, Supply, Installation, Testing & Commissioning of lighting system of 240V, 50Hz, Phase to Phase 1X350W LED Industrial type Search lighting fixture– 360/180 deg.
Rotation, coverage area 600 to 700 mtr., motorised operated luminaire along with mounting brackets & fixing accessories (10m height), suitable for degree of protection of IP65 and all other electrical equipment which are
necessary to make the system complete and safe in all respect. Lighting fixtures shall be suitable for loop-in/loop-out at both ends of the fittings. Fixture shall be suitable for 19 mm conduit entry and 16 SWG G.I. earth-wire
connections. The fixtures shall be provided with 3 numbers of M20 threaded entries having 2 numbers of M20 Brass Nickel Plated Cable Glands and 1 entries shall be plugged using certified plugs.
Location: Watch tower
EA 4 0 EP-1
25.0 ANCHOR BOLTS
EP-1
EP-1
Page 13 of 12
SUPPLY /
UNIT PRICE
(INR)
INSTALLATION &
COMMISSIONING /
UNIT PRICE (INR)
TOTAL
PRICE
(INR)
ESTIMATEDQU
ANTITYUOM
TENDER OFFER
MODULAR PACKAGE CONTRACT
ENGINEERING, PROCUREMENT, SUPPLY & INSTALLATION
OCS, Nadua and GGS, East Khagorijan
DELIVERY,
SUPPLY +
INSTALLATION
TIME (WEEK)
DETALIED SCHEDULE OF RATES - NADUA
ELETRICAL PACKAGE - 1 (EP-1) : Non-Modular Electrical Packages
ELETRICAL PACKAGE - 2 (EP-2) : Modular Electrical Packages
PACKAGES.No Service Description
Design, Engineering, Manufacturing, Assembling, Supply & Installation of Anchor bolts for modular package (Container) and Steel foundation template for anchor bolt fixation shall be provided. Anchor bolts and Steel
template shall be provided by MPC Contractor 60 days prior to delivery of package.
Location: Container
EA As per requirement 0 EP-1
0 0 0
NOTES :
1.Bidder shall consider the following as part of their scope
a) Unloading of material at site
b) Storing of material at site
c) Shifting material to site (by use of crane/ forklift etc., shall are covered
d) Installation, testing, commissioning, PGTR.
f) Scaffolding as required
2. Values provided in the SOR may vary slightly. Vendor shall round of the quantity to nearest 500/1000 mtr drum.
3. Busduct routing and required number of fittings shall be as per site conditions.
TOTAL
Page 14 of 12
MIN MAX
Temp. °C Temp. °C
1 8" HOT OIL/CRUDE OIL 8"-PT-13-0158-FC01 ESDV 1000 8"-PT-13-0192-FC0117039-EK-P-DW-0202-09 TO 17039-EK-P-DW-
0203-01- - 3 7 250 50 50 2 41 CS 30 - - - - -
2 6" HOT OIL/CRUDE OIL ESDV 1000 N1NOZZLE OF ND-HBG-1470 6"-PT-13-0192-FC01 17039-EK-P-DW-0203-01 - - 3 8 250 50 50 2 41 CS 30 - - - - -
3 2" HOT OIL/CRUDE OIL LV0216 8"-PT-13-0192-FC01 2"-PT-13-0205-FC0117039-EK-P-DW-0202-12 TO 17039-EK-P-DW-
0203-01- - 4 14 250 50 50 2 41 CS 30 - - - - -
4 6" HOT OIL/CRUDE OIL 8"-PT-13-0192-FC01 6"-PT-20-0350-DC01 6"-PT-20-0352-DC01 17039-EK-P-DW-0203-01 - - 2 4 250 50 50 2 41 CS 30 - - - - -
5 6" HOT OIL/CRUDE OIL N2NOZZLE OF ND-HBG-1470 N1NOZZLE OF ND-HBG-1470 6"-PT-20-0350-DC0117039-EK-P-DW-0203-01 TO 17039-EK-P-DW-
0203-02- - 2 9 250 50 50 2 41 CS 30 - - - - -
6 6"CRUDE
OIL/WATER/HC GAS6"-PT-20-0350-DC01 N1 NOZZLE OF EK-MBD-1020 6"-PT-13-0350A-DC01
17039-EK-P-DW-0203-01 TO 17039-EK-P-DW-
0203-02- - 2 6 80 50 50 2 41 CS 30 - - - - -
7 6"CRUDE
OIL/WATER/HC GASWELL FLUID TO INLET SEPERATOR 6"-PT-20-0350-DC01 6"-PT-13-0690-DC01
17039-EK-P-DW-0203-05 TO 17039-EK-P-DW-
0203-022 4 80 50 50 2 41 CS 30 - - - - -
8 -CRUDE
OIL/WATER/HC GASK3B NOZZLE OF ND-MBD-1020 24"MW1 ND-MBD-1020 17039-EK-P-DW-0203-02 - - 1 4 80 50 50 2 41 CS - - - - - -
9 -CRUDE
OIL/WATER/HC GASK3B NOZZLE OF ND-MBD-1020 K3A NOZZLE OF ND-MBD-1020 LT 0404 17039-EK-P-DW-0203-02 - - 2 4 80 50 50 2 41 CS 3 - - - - -
10 -CRUDE
OIL/WATER/HC GASK4A NOZZLE OF ND-MBD-1020 K4B NOZZLE OF ND-MBD-1020 LG 1068 17039-EK-P-DW-0203-02 - - 0 4 80 50 50 2 41 CS 3 - - - - -
11 -CRUDE
OIL/WATER/HC GASK1A NOZZLE OF ND-MBD-1020 K1B NOZZLE OF ND-MBD-1020 ILT 4502 17039-EK-P-DW-0203-02 - - 0 3 80 50 50 2 41 CS 3 - - - - -
12 -CRUDE
OIL/WATER/HC GASK1A NOZZLE OF ND-MBD-1020 K1B NOZZLE OF ND-MBD-1020 ILT 0402 17039-EK-P-DW-0203-02 - - 0 2 80 50 50 2 41 CS 3 - - - - -
13 - CRUDE OIL K8 NOZZLE OF ND-MBD-1340 PT 0405 - 17039-EK-P-DW-0203-02 - - 0 1 80 50 50 2 41 CS 3 - - - - -
14 - CRUDE OIL K6 NOZZLE OF ND-MBD-1020 PT 0406 - 17039-EK-P-DW-0203-02 - - 0 1 80 50 50 2 41 CS 3 - - - - -
15 -CRUDE
OIL/WATER/HC GASK5 NOZZLE OF ND-MBD-1020 PT 1067 - 17039-EK-P-DW-0203-02 - - 0 1 80 50 50 2 41 CS 3 - - - - -
16 3"CRUDE
OIL/WATER/HC GASN3 NOZZLE OF ND-MDB-1020 LV 1068 3"-PL-20-0357-BC01 17039-EK-P-DW-0203-02 - - 3 10 80 50 50 2 41 CS 30 - - - - -
17 3"CRUDE
OIL/WATER/HC GASLV 1068 4"-PT-20-0396-AC01 3"-PT-20-0358-AC01
17039-EK-P-DW-0203-02 TO 17039-EK-P-
DW-0203-06- - 2 7 80 50 50 2 41 CS 30 - - - - -
18 - CRUDE OIL 3"-PL-20-0357-BC01 3"-PT-20-0358-AC01 BY PASS LINE OF LV 1068 17039-EK-P-DW-0203-02 - - 1 2 80 50 50 2 41 CS 30 - - - - -
19 10" CRUDE OIL/HOT OILWELL FLUID FROMLP
PRODUCTION HEADERESDV 0476 10"-PT-13-0182-FC01 17039-EK-P-DW-0203-03 - - 3 11 250 50 50 2 41 CS 30 - - - - -
20 8" CRUDE OIL/HOT OIL ESDV 0476 N1 NOZZLE OF ND-HBG-1480 8"-PT-13-0182-FC01 17039-EK-P-DW-0203-03 - - 2 7 250 50 50 2 41 CS 30 - -
21 3" CRUDE OIL/HOT OIL 10"-PT-13-0182-FC01WELL FLUID FROM TEST TANK
TRANSFER PUMP3"-PL-13-0881-BC01 17039-EK-P-DW-0203-03 - - 2 6 250 50 50 2 41 CS 30 - -
22 2" CRUDE OIL/HOT OIL 10"-PT-13-0182-FC01WELL FLUID FROM TEST
SEPERATOR2"-PT-13-0206-FC01 17039-EK-P-DW-0203-03 - - 2 6 250 50 50 2 41 CS 30 - -
23 8" CRUDE OIL/HOT OIL 8"-PT-13-0182-FC01 8"-PT-20-0366-BC01 8"-PT-20-7818-BC01 17039-EK-P-DW-0203-03 - - 2 4 250 50 50 2 41 CS 30 - - - - -
24 8" CRUDE OIL/HOT OIL 8"-PT-20-0366-BC01 CRUDE TO INLET SEPERATOR-C 8"-PT-20-0366A-BC01 17039-EK-P-DW-0203-03 TO 17039-EK-P-
DW-0203-05- - 0 0 250 50 50 2 41 CS 30 - - - - -
25 8" CRUDE OIL/HOT OIL N2 NOZZLE OF ND-HBG-1480 CRUDE TO INLET SEPERATOR-B 8"-PT-20-0366-BC01 17039-EK-P-DW-0203-03 TO 17039-EK-P-
DW-0203-04- - 2 9 250 50 50 2 41 CS 30 - - - - -
26 8"CRUDE
OIL/WATER/HC GAS8"-PT-20-0366-BC01 8"-PT-20-4175A-BC01 8"-PT-20-0366A-BC01
17039-EK-P-DW-0203-04 TO 17039-EK-P-DW-
0203-05- - 1 4 80 50 50 2 41 CS 30 - - - - -
27 -CRUDE
OIL/WATER/HC GASK3B NOZZLE OF ND-MBD1340 NITROGEN PURGE CONNECTION INLET SEPERATOR-B 17039-EK-P-DW-0203-04 - - 0 1 80 50 50 2 41 CS 30 - - - - -
28 -CRUDE
OIL/WATER/HC GASN7 NOZZLE OF ND-MBD-1340 NITROGEN PURGE CONNECTION - 17039-EK-P-DW-0203-04 - - 1 5 80 50 50 2 41 CS 3 - - - - -
29 -CRUDE
OIL/WATER/HC GASK1A NOZZLE OF ND-MBD-1340 K1B NOZZLE OF ND-MBD-1340 ILIT 0466 17039-EK-P-DW-0203-04 - - 0 2 80 50 50 2 41 CS 3 - - - - -
30 -CRUDE
OIL/WATER/HC GASK4A NOZZLE OF ND-MBD-1340 K4B NOZZLE OF ND-MBD-1340 LG 0463 17039-EK-P-DW-0203-04 - - 0 4 80 50 50 2 41 CS 3 - - - - -
31 -CRUDE
OIL/WATER/HC GASK9A NOZZLE OF ND-MBD-1340 K9B NOZZLE OF ND-MBD-1340 ILIT 0464 17039-EK-P-DW-0203-04 - - 0 2 80 50 50 2 41 CS 3 - - - - -
32 -CRUDE
OIL/WATER/HC GASK8 NOZZLE OF ND-MBD-1340 PIT0454 - 17039-EK-P-DW-0203-04 - - 0 1 80 50 50 2 41 CS 3 - - - - -
33 -CRUDE
OIL/WATER/HC GASK6 NOZZLE OF ND-MBD-1340 PIT0455 - 17039-EK-P-DW-0203-04 - - 0 1 80 50 50 2 41 CS 3 - - - - -
34 -CRUDE
OIL/WATER/HC GASK5 NOZZLE OF ND-MBD-1340 PIT0456 - 17039-EK-P-DW-0203-04 - - 0 1 80 50 50 2 41 CS 3 - - - - -
35 3"CRUDE
OIL/WATER/HC GASN3 NOZZLE OF ND-MBD-1340 LV0463 3"-PL-20-0369-AC01 17039-EK-P-DW-0203-04 - - 3 10 80 50 50 2 41 CS 30 - - - - -
36 3"CRUDE
OIL/WATER/HC GASLV0463A 6"-PT-20-0396-AC01 3"-PL-20-0370-AC01
17039-EK-P-DW-0203-04 TO 17039-EK-P-
DW-0203-07- - 1 5 80 50 50 2 41 CS 30 - - - - -
37 -CRUDE
OIL/WATER/HC GAS3"-PL-20-0369-AC01 3"-PL-20-0370-AC01 BYE PASS LINE OF LV0463 17039-EK-P-DW-0203-04 - - 1 2 80 50 50 2 41 CS 30 - - - - -
38 -CRUDE
OIL/WATER/HC GAS
WELL FLUID FROM INLET
SEPERATOR-A8"-PT-20-4175A-BC01 N1 NOZZLE OF EK-MBD-1500
17039-EK-P-DW-0203-02 TO 17039-EK-P-
DW-0203-05- - 0 0 80 50 50 2 41 CS 30 - - - - -
AMBIENT Temp. °C
TRAID
CABLE
POWER CABLE
LENGTH
POWER CABLE
SIZESERVICE LINE No. / EQUIPMENT
FROM LINE No. /
EQUIPMENT TO LINE No. / EQUIPMENT
OPERATING
Temp. °C DESIGN TEMP. °C
No's VALVES
(NOTE-4)
P&ID NUMBER (NOTE-4)
HEAT TRACING LINE LIST
PIPING /
EQUIPMENT
DIA(inch)
PIPE
MATERIAL
HEAT TRACING PIPE CABLE
LENGTH (M)
NO. OF CRK.
REQ
MATERIAL
SL.NO
INSULATION
THICKNESS. (mm)
MAINTAINED
Temp. °C
No's FLANGES
INSULATION VALVE / FLANGE Q'TY
PIPE / EQUIPMENT
LENGTH (M)
Page 1 of 5
Annexure- 4
MIN MAX
Temp. °C Temp. °C
AMBIENT Temp. °C
TRAID
CABLE
POWER CABLE
LENGTH
POWER CABLE
SIZESERVICE LINE No. / EQUIPMENT
FROM LINE No. /
EQUIPMENT TO LINE No. / EQUIPMENT
OPERATING
Temp. °C DESIGN TEMP. °C
No's VALVES
(NOTE-4)
P&ID NUMBER (NOTE-4)
HEAT TRACING LINE LIST
PIPING /
EQUIPMENT
DIA(inch)
PIPE
MATERIAL
HEAT TRACING PIPE CABLE
LENGTH (M)
NO. OF CRK.
REQ
MATERIAL
SL.NO
INSULATION
THICKNESS. (mm)
MAINTAINED
Temp. °C
No's FLANGES
INSULATION VALVE / FLANGE Q'TY
PIPE / EQUIPMENT
LENGTH (M)
39 -CRUDE
OIL/WATER/HC GASK3B NOZZLE OF ND-MBD-1500 24" MW1 ND-MBD-1500 17039-EK-P-DW-0203-05 - - 0 0 80 50 50 2 41 CS - - - - - -
40 -CRUDE
OIL/WATER/HC GASK8 NOZZLE OF ND-MBD-1500 PIT 0454A - 17039-EK-P-DW-0203-05 - - 0 1 80 50 50 2 41 CS 30 - - - - -
41 -CRUDE
OIL/WATER/HC GASK6 NOZZLE OF ND-MBD-1500 PIT 0455A - 17039-EK-P-DW-0203-05 - - 0 1 80 50 50 2 41 CS 30 - - - - -
42 -CRUDE
OIL/WATER/HC GASK5 ND-MBD-1500 PIT 0456A - 17039-EK-P-DW-0203-05 - - 0 1 80 50 50 2 41 CS 30 - - - - -
43 3"CRUDE
OIL/WATER/HC GASN3 NOZZLE OF ND-MBD-1500 LV 0463A 3"-PL-20-0369A-BC01 17039-EK-P-DW-0203-05 - - 3 10 80 50 50 2 41 CS 30 - - - - -
44 3"CRUDE
OIL/WATER/HC GASLV 0463A 6"-PT-20-0396-AC01 3"-PT-20-0890-AC01
17039-EK-P-DW-0203-05 TO 17039-EK-P-DW-
0203-06- - 2 7 80 50 50 2 41 CS 30 - - - - -
45 -CRUDE
OIL/WATER/HC GAS3"-PL-20-0369A-BC01 3"-PT-20-0890-AC01 BYEPASS LINE OF LV 0463A 17039-EK-P-DW-0203-05 - - 1 2 80 50 50 2 41 CS 30 - - - - -
46 3"CRUDE
OIL/WATER/HC GAS3"-PT-20-0358-AC01 N3 NOZZLE OF ND-HBG-B-1030 3"-PT-0396B-AC01
17039-EK-P-DW-0203-17 TO 17039-EK-P-DW-
0203-066 14 80 50 50 2 41 CS 30
47 -CRUDE
OIL/WATER/HC GAS3"-PT-20-0358-AC01 3"-PT-0396B-AC01 BY PASS LINE OF FV0200B 17039-EK-P-DW-0203-06 1 2 80 50 50 2 41 CS 30
48 3" CRUDE OIL 4"-PT-20-0370-AC01 4"-PT-20-0396-AC01 3"-PT-20-0370-AC0117039-EK-P-DW-0203-04 TO 17039-EK-P-DW-
0203-06- 1 4 150 50 50 2 41 CS 30 - - - - -
49 3" CRUDE OIL 4"-PT-20-0890-AC01 4"-PT-20-0396-AC01 3"-PT-20-0890-AC0117039-EK-P-DW-0203-05 TO 17039-EK-P-DW-
0203-06- - 1 4 150 50 50 2 41 CS 30 - - - - -
50 3" CRUDE OIL 4"-PT-20-0396-AC01 N3 NOZZLE OF ND-HBG-B-1030 3"-PT-20-0383-AC01 17039-EK-P-DW-0203-06 3 10 150 50 50 2 41 CS 30 - - - - -
51 3" CRUDE OIL 6"-PT-20-0396-AC01 3"-PT-20-0383-AC01 BYPASS LINE OF FV 0200B 17039-EK-P-DW-0203-06 - - 1 2 150 50 50 2 41 CS 30 - - - - -
52 2" CRUDE OILCRUDE FROM INLET
SEPERATOR-C4"-PT-20-0396-AC01 2"-PL-20-*0810-AC01
17039-EK-P-DW-0203-05 TO 17039-EK-P-DW-
0203-06- - 1 4 150 50 50 2 41 CS 30 - - - - -
53 3" CRUDE OIL N1 NOZZLE OF ND-HBG-A-1030 LV 0476 3"-PL-20-0374-AC01 17039-EK-P-DW-0203-06 - - 1 5 150 50 50 2 41 CS 30 - - - - -
54 3" CRUDE OIL LV 0476 XV 0473A 3"-PL-20-0397A-AC01 17039-EK-P-DW-0203-06 - - 3 5 150 50 50 2 41 CS 30 - - - - -
55 3" CRUDE OIL XV 0473ACRUDE TO CRUDE STORAGE
TANK3"-PL-20-0376A-AC01
17039-EK-P-DW-0203-06 TO 17039-EK-P-DW-
0203-11- - 3 5 150 50 50 2 41 CS 30 - - - - -
56 4" CRUDE OIL 3"-PL-20-0376A-AC01 6"-PL-20-0440-AC01 4"-PL-20-0375A-AC0117039-EK-P-DW-0203-06 TO 17039-EK-P-DW-
0203-14- - 1 2 150 50 50 2 41 CS 30 - - - - -
57 - CRUDE OIL 20-BL-1256 20-BL-1270 PDIT0470 17039-EK-P-DW-0203-06 - - 0 2 150 50 50 2 41 CS 3 - - - - -
58 - CRUDE OIL 20-BL-1267 20-BL-1269 PDIT0480 17039-EK-P-DW-0203-06 - - 0 2 150 50 50 2 41 CS 3 - - - - -
59 4" CRUDE OIL N4 NOZZLE OF ND-HBG-A-1030 N1 NOZZLE OF ND-HBG-A-1040 4"-PT-20-0377-AC0117039-EK-P-DW-0203-06 TO 17039-EK-P-DW-
0203-07- - 3 9 150 50 50 2 41 CS 30 - - - - -
60 3" CRUDE OILCRUDE FROM CRUDE
TRANSFER PUMPSN2 NOZZLE OF ND-HBG-A-1030 3"-PL-20-0457-AC01
17039-EK-P-DW-0203-06 TO 17039-EK-P-DW-
0203-09- - 0 5 150 50 50 2 41 CS 30 - - - - -
61 4" CRUDE OIL N2 NOZZLE OF ND-HBG-A-1040 N1 NOZZLE OF ND-MBD-A-1050 4"-PT-20-0384-AC0117039-EK-P-DW-0203-07 TO 17039-EK-P-DW-
0203-08- - 2 7 250 50 50 2 41 CS 30 - - - - -
62 - CRUDE OIL 20-BL-1281 20-BL-1283 PDIT3605 17039-EK-P-DW-0203-07 - - 0 2 250 50 50 2 41 CS 3 - - - - -
63 3" CRUDE OIL ND-MBD-A-1050 ND-MBM-A-1060 3"-PL-20-0359-AC01 17039-EK-P-DW-0203-08 - - 0 0 150 50 50 2 41 CS 30 - - - - -
64 - CRUDE OIL N4 NOZZLE OF ND-MBM-A-1060 N3 NOZZLE OF ND-MBM-A-1060 ND-MBM-A-1060 17039-EK-P-DW-0203-08 - - 0 0 150 50 50 2 41 CS - - - - - -
65 2" CRUDE OILCOCNDENSATE FROMTRUNKK
LINE KOD6"-PT-20-0384-AC01 2"-PL-20-0460A-AC01
17039-EK-P-DW-0204-01 TO 17039-EK-P-DW-
0203-08- - 0 0 150 50 50 2 41 CS 30 - - - - -
66 2" CRUDE OILHC GAS FROM TEST
SEPERATOR6"-PT-20-0384-AC01 2"-PV-13-0203-AC01
17039-EK-P-DW-0204-01 TO 17039-EK-P-DW-
0203-08- - 0 0 150 50 50 2 41 CS 30 - - - - -
67 4" CRUDE OILHC COCNDENSATE FROM LP
GAS COMPRESSION PACKAGE6"-PT-20-0384-AC01 4"-PL-20-0470-AC01
17039-EK-P-DW-0204-01 TO 17039-EK-P-DW-
0203-08- - 1 6 150 50 50 2 41 CS 30 - - - - -
68 4" CRUDE OIL N2 NOZZLE OF ND-MBM-A-1060 4"-PL-20-0452-AC01 4"-PL-20-0360-AC0117039-EK-P-DW-0203-08 TO 17039-EK-P-DW-
0203-10- - 0 1 150 50 50 2 41 CS 30 - - - - -
69 4" CRUDE OIL 4"-PL-20-0360-AC01 NI NOZZLE OF ND-PBA-A-1070B 4"-PL-20-0452-AC01 17039-EK-P-DW-0203-09 1 6 150 50 50 2 41 CS 30
70 4" CRUDE OIL 4"-PL-20-0360-AC01 NI NOZZLE OF ND-PBA-A-1070A 4"-PL-20-0451-AC01 17039-EK-P-DW-0203-09 0 1 150 50 50 2 41 CS 30
71 3" CRUDE OIL N2 NOZZLE OF ND-PBA-A-1070A 3"-PL-20-0457-AC01 3"-PL-20-0454-AC01 17039-EK-P-DW-0203-09 - - 1 6 150 50 50 2 41 CS 30 - - - - -
72 3" CRUDE OIL N2 NOZZLE OF ND-PBA-A-1070B 3"-PL-20-0457-AC01 3"-PL-20-0453-AC01 17039-EK-P-DW-0203-09 - - 1 6 150 50 50 2 41 CS 30 - - - - -
73 3" CRUDE OIL 3"-PL-20-0824-AC01TREATED CRUDE FROM
CRUDE/CRUDE EXCHANGER3"-PL-20-0376B-AC01
17039-EK-P-DW-0203-10 TO 17039-EK-P-DW-
0203-11- - 2 5 90 50 50 2 41 CS 30 - - - - -
74 3" CRUDE OILTREATED CRUDE FROM
CRUDE/CRUDE EXCHANGERMOV0978B 3"-PL-20-0376-AC01
17039-EK-P-DW-0203-10 TO 17039-EK-P-DW-
0203-11- - 2 5 90 50 50 2 41 CS 30 - - - - -
75 3" CRUDE OIL MOV0978B N1 NOZZLE OF ND-BBJ-1120B 3"-PL-20-0818-AC0117039-EK-P-DW-0203-10 TO 17039-EK-P-DW-
0203-11- - 2 5 90 50 50 2 41 CS 30 - - - - -
76 3" CRUDE OIL 3"-PL-20-0823-AC01 4"-PL-20-0828-AC01 3"-PL-20-0820-AC0117039-EK-P-DW-0203-10 TO 17039-EK-P-DW-
0203-11- - 1 2 90 50 50 2 41 CS 30 - - - - -
77 3" CRUDE OIL 3"-PL-20-0823-AC01 MOV 0978A 3"-PL-20-0816-AC01 17039-EK-P-DW-0203-10 - - 1 2 90 50 50 2 41 CS 30 - - - - -
Page 2 of 5
MIN MAX
Temp. °C Temp. °C
AMBIENT Temp. °C
TRAID
CABLE
POWER CABLE
LENGTH
POWER CABLE
SIZESERVICE LINE No. / EQUIPMENT
FROM LINE No. /
EQUIPMENT TO LINE No. / EQUIPMENT
OPERATING
Temp. °C DESIGN TEMP. °C
No's VALVES
(NOTE-4)
P&ID NUMBER (NOTE-4)
HEAT TRACING LINE LIST
PIPING /
EQUIPMENT
DIA(inch)
PIPE
MATERIAL
HEAT TRACING PIPE CABLE
LENGTH (M)
NO. OF CRK.
REQ
MATERIAL
SL.NO
INSULATION
THICKNESS. (mm)
MAINTAINED
Temp. °C
No's FLANGES
INSULATION VALVE / FLANGE Q'TY
PIPE / EQUIPMENT
LENGTH (M)
78 3" CRUDE OIL MOV 0978A N1 NOZZLE OF ND-BBJ-1120A 3"-PL-20-0816-AC01 17039-EK-P-DW-0203-10 - - 1 2 90 50 50 2 41 CS 30 - - - - -
79 3" CRUDE OIL 4"-PL-20-0827-AC01 3"-PL-20-0816-AC01 3"-PL-20-0817-AC01 17039-EK-P-DW-0203-10 - - 0 2 90 50 50 2 41 CS 30 - - - - -
80 10" CRUDE OIL N2 NOZZLE OF ND-BBJ-1120A 10"-PL-20-0833-AC01 10"-PL-20-0822-AC0117039-EK-P-DW-0203-10 TO 17039-EK-P-DW-
0203-12- - 2 5 90 50 50 2 41 CS 30 - - - - -
81 10" CRUDE OIL N2 NOZZLE OF ND-BBJ-1120B 10"-PL-20-0833-AC01 10"-PL-20-0825-AC0117039-EK-P-DW-0203-11 TO 17039-EK-P-DW-
0203-12- - 2 5 90 50 50 2 41 CS 30 - - - - -
82 2" CRUDE OIL 4"-PL-20-8639-AC01 FV 1012C 2"-PL-20-0841C-AC01 17039-EK-P-DW-0203-12 - - 2 3 90 50 50 2 41 CS 30
83 2" CRUDE OIL FV 1012CMINIMUM RECYCLE FLOW TO
CRUDE STORAGE TANK2"-PL-20-0891-AC01
17039-EK-P-DW-0203-12 TO 17039-EK-P-DW-
0203-10- - 2 5 90 50 50 2 41 CS 30
84 2" CRUDE OIL FV 1012AMINIMUM RECYCLE FLOW TO
CRUDE STORAGE TANK2"-PL-20-0891-AC01
17039-EK-P-DW-0203-12 TO 17039-EK-P-DW-
0203-10- - 2 5 90 50 50 2 41 CS 30
85 2" CRUDE OIL FV 1012DMINIMUM RECYCLE FLOW TO
CRUDE STORAGE TANK2"-PL-20-0892-AC01
17039-EK-P-DW-0203-12 TO 17039-EK-P-DW-
0203-10- - 2 5 90 50 50 2 41 CS 30
86 3" CRUDE OIL N2 NOZZLE OF ND-PM-1130A - 3"-PL-20-0838-AC01 17039-EK-P-DW-0203-12 - - 1 9 90 50 50 2 41 CS 30
87 3" CRUDE OIL N2 NOZZLE OF ND-PM-1130B - 3"-PL-20-0839-AC01 17039-EK-P-DW-0203-12 - - 1 9 90 50 50 2 41 CS 30
88 - CRUDE OIL 2"-PL-20-0841C-AC01 2"-PL-20-0827-AC01 BYPASS LINE OF FV 1012C 17039-EK-P-DW-0203-12 - - 1 2 90 50 50 2 41 CS 30
89 4" CRUDE OIL 3"-PL-20-8640-AC01 FV 1012D 4"-PL-20-0841D-AC01 17039-EK-P-DW-0203-12 - - 2 5 90 50 50 2 41 CS 30
90 - CRUDE OIL 4"-PL-20-0841D-AC01 2"-PL-20-0827-AC01 BYPASS LINE OF FV 1012D 17039-EK-P-DW-0203-12 - - 1 2 90 50 50 2 41 CS 30
91 2" CRUDE OIL 3"-PL-20-0838-AC01 FV 1012B 2"-PL-20-0841A-AC0117039-EK-P-DW-0203-12 TO 17039-EK-P-DW-
0203-10- - 1 3 90 50 50 2 41 CS 30 - - - - -
92 - CRUDE OIL 3"-PL-20-0838-AC01 4"-PL-20-0827-AC01 BY PASS LINE OF FV 1012B 17039-EK-P-DW-0203-12 - - 1 2 90 50 50 2 41 CS 30 - - - - -
93 2" CRUDE OIL FV 1012BMINIMUM RECYCLE FLOW TO
CRUDE STORAGE TANK2"-PL-20-0890-AC01 17039-EK-P-DW-0203-12 - - 2 3 90 50 50 2 41 CS 30 - - - - -
94 - CRUDE OIL 2"-PL-20-0841A-AC01 2"-PL-20-0827-AC01 BYPASS LINE OF FV 1012A 17039-EK-P-DW-0203-12 - - 1 2 90 50 50 2 41 CS 30 - - - - -
95 4" CRUDE OIL 10"-PL-20-0833-AC01 20-BL-9000 4"-PL-20-8637-AC01 17039-EK-P-DW-0203-12 - - 0 0 90 50 50 2 41 CS 30 - - - - -
96 4" CRUDE OIL 10"-PL-20-0833-AC01 20-BL-9001 4"-PL-20-2638-AC01 17039-EK-P-DW-0203-12 - - 0 0 90 50 50 2 41 CS 30 - - - - -
97 4" CRUDE OIL
CRUDE FROM CRUDE CRUDE
CHARGE PUMP COMMON
SUCTION HEADER
NI NOZZLE OF ND-PBA-1130C 4"-PL-20-0840-AC01 17039-EK-P-DW-0203-12 - - 0 0 90 50 50 2 41 CS 30 - - - - -
98 3" CRUDE OIL N2 NOZZLE OF ND-PBA-1130CTO CRUDE CHARGE PUMPS
COMMON DISCHARGE3"-PL-20-8639-AC01 17039-EK-P-DW-0203-12 2 9 90 50 50 2 41 CS 30
99 4" CRUDE OIL
CRUDE FROM CRUDE CRUDE
CHARGE PUMP COMMON
SUCTION HEADER
NI NOZZLE OF ND-PBA-1130D 4"-PL-20-8638-AC01 17039-EK-P-DW-0203-12 - - 0 0 90 50 50 2 41 CS 30 - - - - -
100 3" CRUDE OIL N2 NOZZLE OF ND-PBA-1130DTO CRUDE CHARGE PUMPS
COMMON DISCHARGE3"-PL-20-8640-AC01 17039-EK-P-DW-0203-12 2 9 90 50 50 2 41 CS 30
101 4" CRUDE OIL 10"-PL-20-0833-AC01 N1 NOZZLE OF ND-PM-1130A 4"-PL-20-0840-AC01 17039-EK-P-DW-0203-12 - - 1 6 90 50 50 2 41 CS 30 - - - - -
102 4" CRUDE OIL 10"-PL-20-0833-AC01 N1 NOZZLE OF ND-PM-1130B 4"-PL-20-0837-AC01 17039-EK-P-DW-0203-12 - - 1 6 90 50 50 2 41 CS 30 - - - - -
103 4" CRUDE OIL 4"-PL-20-0840-AC01 N1 NOZZLE OF ND-PBA-1140A 4"-PL-20-0842-AC0117039-EK-P-DW-0203-12 TO 17039-EK-P-DW-
0203-13- - 2 8 90 50 50 2 41 CS 30 - - - - -
104 3" CRUDE OIL N2 NOZZLE OF ND-PBA-1140A 4"-PL-20-0848-DC01 3"-PL-20-0845-DC01 17039-EK-P-DW-0203-13 - - 2 7 90 50 50 2 41 CS 30 - - - - -
105 4" CRUDE OIL 4"-PL-20-0840-AC01 N1 NOZZLE OF ND-PBA-1140B 4"-PL-20-0843-AC0117039-EK-P-DW-0203-12 TO 17039-EK-P-DW-
0203-13- - 2 8 90 50 50 2 41 CS 30 - - - - -
106 4" CRUDE OIL N2 NOZZLE OF ND-PBA-1140B 4"-PL-20-0848-DC01 3"-PL-20-0846-DC01 17039-EK-P-DW-0203-13 - - 2 7 90 50 50 2 41 CS 30 - - - - -
107 4" CRUDE OIL 4"-PL-20-0840-AC01 N1 NOZZLE OF ND-PBA-1140C 4"-PL-20-0844-AC0117039-EK-P-DW-0203-12 TO 17039-EK-P-DW-
0203-13- - 2 8 90 50 50 2 41 CS 30 - - - - -
108 3" CRUDE OIL N2 NOZZLE OF ND-PBA-1140C 4"-PL-20-0848-DC01 3"-PL-20-0847-DC01 17039-EK-P-DW-0203-13 - - 2 7 90 50 50 2 41 CS 30 - - - - -
109 4" CRUDE OIL 4"-PL-20-0840-AC01 N1 NOZZLE OF ND-PBA-1140D 4"-PL-20-8641-AC0117039-EK-P-DW-0203-12 TO 17039-EK-P-DW-
0203-13- - 2 8 90 50 50 2 41 CS 30 - - - - -
110 3" CRUDE OIL N2 NOZZLE OF ND-PBA-1140D 4"-PL-20-0848-DC01 3"-PL-20-8642-DC01 17039-EK-P-DW-0203-13 - - 2 7 90 50 50 2 41 CS 30 - - - - -
111 6" CRUDE OIL 4"-PL-20-0848-DC01 6"-PL-20-0855-DC01 6"-PL-20-0854-DC0117039-EK-P-DW-0203-13 TO 17039-EK-P-DW-
0203-16- - 0 3 90 50 50 2 41 CS 30 - - - - -
112 8" CRUDE OIL N2 NOZZLE OF ND-BBJ-1090 8"-PL-20-0386-AC01 8"-PL-20-0459-AC0117039-EK-P-DW-0203-14 TO 17039-EK-P-DW-
0203-15- - 3 6 90 50 50 2 41 CS 30 - - - - -
113 8" CRUDE OIL 8"-PL-20-0459-AC01 N1 NOZZLE OF ND-PBA-1100A 8"-PL-20-0386-AC01 17039-EK-P-DW-0203-15 - - 1 6 90 50 50 2 41 CS 30 - - - - -
114 6" CRUDE OIL N2 NOZZLE OF ND-PBA-1100A 6"-PL-20-0393-AC01 6"-PL-20-0388-AC01 17039-EK-P-DW-0203-15 - - 1 7 90 50 50 2 41 CS 30 - - - - -
115 8" CRUDE OIL 8"-PL-20-0459-AC01 N1 NOZZLE OF ND-PBA-1100B 8"-PL-20-0387-AC07 17039-EK-P-DW-0203-15 - - 1 6 90 50 50 2 41 CS 30 - - - - -
116 3" CRUDE OIL N2 NOZZLE OF ND-PBA-1100B 6"-PL-20-0393-AC01 3"-PL-20-0389-AC01 17039-EK-P-DW-0203-15 - - 1 7 90 50 50 2 41 CS 30 - - - - -
117 6" CRUDE OIL 6"-PL-20-0388-AC01 INLET SEPERATOR-B 6"-PL-20-0393-AC01 17039-EK-P-DW-0203-15
Page 3 of 5
MIN MAX
Temp. °C Temp. °C
AMBIENT Temp. °C
TRAID
CABLE
POWER CABLE
LENGTH
POWER CABLE
SIZESERVICE LINE No. / EQUIPMENT
FROM LINE No. /
EQUIPMENT TO LINE No. / EQUIPMENT
OPERATING
Temp. °C DESIGN TEMP. °C
No's VALVES
(NOTE-4)
P&ID NUMBER (NOTE-4)
HEAT TRACING LINE LIST
PIPING /
EQUIPMENT
DIA(inch)
PIPE
MATERIAL
HEAT TRACING PIPE CABLE
LENGTH (M)
NO. OF CRK.
REQ
MATERIAL
SL.NO
INSULATION
THICKNESS. (mm)
MAINTAINED
Temp. °C
No's FLANGES
INSULATION VALVE / FLANGE Q'TY
PIPE / EQUIPMENT
LENGTH (M)
118 3" CRUDE OIL 3"-PL-20-0457B-AC01 N2 NOZZLE OF ND-HBG-B-1030 3"-PL-20-0457B-AC0117039-EK-P-DW-0203-20 TO 17039-EK-P-DW-
0203-17- - 0 4 150 50 50 2 41 CS 30 - - - - -
119 3" CRUDE OIL N1 NOZZLE OF ND-HBG-B-1030 LV 0476B 3"-PT-20-03764B-AC01 17039-EK-P-DW-0203-17 - - 4 7 150 50 50 2 41 CS 30
120 3" CRUDE OIL LV 0476B XV0473C 3"-PL-20-0397B-AC01 17039-EK-P-DW-0203-17 - - 1 4 150 50 50 2 41 CS 30
121 3" CRUDE OIL LV 0476BCRUDE TO CRUDE STORAGE
TANK3"-PL-20-0376B-AC01
17039-EK-P-DW-0203-17 TO 17039-EK-P-DW-
0203-06- - 2 3 150 50 50 2 41 CS 30
122 3" CRUDE OIL 3"-PL-20-0397B-AC01OFF SPEC CRUDE TO OFF SPEC
CRUDE STORAGE TANK3"-PL-20-0376A-AC01
17039-EK-P-DW-0203-17 TO 17039-EK-P-DW-
0203-14- - 2 3 150 50 50 2 41 CS 30
123 - CRUDE OIL 20-BL-1256B 20-BL-1270B PDIT0470B 17039-EK-P-DW-0203-17 - - 2 2 150 50 50 2 41 CS 30
124 - CRUDE OIL 20-BL-1267B 20-BL-1259B PDIT0480B 17039-EK-P-DW-0203-17 - - 2 2 150 50 50 2 41 CS 30
125 4" CRUDE OIL N4 NOZZLE OF ND-HBG-B-1030 N1 NOZZLE HBG-B-1040 4"-PT-20-0377B-AC0117039-EK-P-DW-0203-17 TO 17039-EK-P-DW-
0203-18- - 3 10 150 50 50 2 41 CS 30 - - - - -
126 6" CRUDE OIL N2 NOZZLE OF ND-HBG-1040 N1 NOZZLE OF ND-MBD-B-1050 6"-PT-20-0384B-AC0117039-EK-P-DW-0203-19 TO 17039-EK-P-DW-
0203-19- - 2 7 150 50 50 2 41 CS 30 - - - - -
127 CRUDE OIL N3 NOZZLE OF ND-MBM-B-1060 N4 NOZZLE OF ND-MBM-B-1060 ND-MBM-B-1060 17039-EK-P-DW-0203-19 - - 0 0 150 50 50 2 41 CS 30 - - - - -
128 - CRUDE OIL 20-BL-1281B 20-BL-1283B PDIT3605B 17039-EK-P-DW-0203-18 - - 0 2 250 50 50 2 41 CS 30 - - - - -
129 4" CRUDE OIL N2 NOZZLE OF ND-MBM-B-1060 4"-PL-20-0452-AC01 4"-PL-20-0360B-AC01 17039-EK-P-DW-0203-19 - - 0 1 150 50 50 2 41 CS 30 - - - - -
130 4" CRUDE OIL 4"-PL-20-0360B-AC01 N1 NOZZLE OF ND-PBA-B-1070A 4"-PL-20-0451B-AC0117039-EK-P-DW-0203-19 TO 17039-EK-P-DW-
0203-20- - 1 7 150 50 50 2 41 CS 30 - - - - -
131 3" CRUDE OIL N2 NOZZLE OF ND-PBA-B-1070A 3"-PL-20-0457B-AC01 3"-PL-20-0454B-AC01 17039-EK-P-DW-0203-20 - - 1 6 150 50 50 2 41 CS 30 - - - - -
132 4" CRUDE OIL 4"-PL-20-0360B-AC01 N1 NOZZLE OF ND-PBA-B-1070B 3"-PL-20-0453B-AC0117039-EK-P-DW-0203-19 TO 17039-EK-P-DW-
0203-20- - 1 7 150 50 50 2 41 CS 30 - - - - -
133 3" CRUDE OIL N2 NOZZLE OF ND-PBA-B-1070B 3"-PL-20-0454B-AC01 3"-PL-20-0457B-AC0117039-EK-P-DW-0203-20 TO 17039-EK-P-DW-
0203-17- - 1 6 150 50 50 2 41 CS 30 - - - - -
134 4" CRUDE OIL 6"-PT-13-0157-FC01 N1 NOZZLE OF ND-MBD-1110 4"-PT-13-0196-FC0117039-EK-P-DW-0202-10 TO 17039-EK-P-DW-
0202-12- - 1 3 108 50 50 2 41 CS 30 - - - - -
135 4" CRUDE OILWELL FLUID FROM HP WELL-1
8"-PT-13-0158-FC01
EK-GAY-1460 TEST HEADER4"-PT-13-0001-FC01
17039-EK-P-DW-0202-05 TO 17039-EK-P-DW-
0202-09- - 8 18 108 50 50 2 41 CS 30 - - - - -
136 4" CRUDE OILWELL FLUID FROM HP WELL-2
8"-PT-13-0158-FC01
EK-GAY-1460 TEST HEADER4"-PT-13-0002-FC01
17039-EK-P-DW-0202-05 TO 17039-EK-P-DW-
0202-09- - 8 18 108 50 50 2 41 CS 30 - - - - -
137 4" CRUDE OILWELL FLUID FROM HP WELL-3
8"-PT-13-0158-FC01
EK-GAY-1460 TEST HEADER4"-PT-13-0003-FC01
17039-EK-P-DW-0202-05 TO 17039-EK-P-DW-
0202-09- - 8 18 108 50 50 2 41 CS 30 - - - - -
138 4" CRUDE OILWELL FLUID FROM HP WELL-4
8"-PT-13-0158-FC01
EK-GAY-1460 TEST HEADER4"-PT-13-0014-FC01
17039-EK-P-DW-0202-06 TO 17039-EK-P-DW-
0202-09- - 8 18 108 50 50 2 41 CS 30 - - - - -
139 4" CRUDE OILWELL FLUID FROM HP WELL-5
8"-PT-13-0158-FC01
EK-GAY-1460 TEST HEADER4"-PT-13-0015-FC01
17039-EK-P-DW-0202-06 TO 17039-EK-P-DW-
0202-09- - 8 18 108 50 50 2 41 CS 30 - - - - -
140 4" CRUDE OILWELL FLUID FROM HP WELL-6
8"-PT-13-0158-FC01
EK-GAY-1460 TEST HEADER4"-PT-13-0016-FC01
17039-EK-P-DW-0202-06 TO 17039-EK-P-DW-
0202-09- - 8 18 108 50 50 2 41 CS 30 - - - - -
141 4" CRUDE OIL 10"-PT-13-0068-FC01 WELL FLUID TO LP PRODUCTION
TEST HEADER EK-GAY-12904"-PT-13-0001-FC01
17039-EK-P-DW-0202-05 TO 17039-EK-P-DW-
0202-06- - 2 5 108 50 50 2 41 CS 30 - - - - -
142 4" CRUDE OIL 4"-PT-13-0014-FC01 10"-PT-13-0068-FC01 4"-PT-13-0017-FC01 17039-EK-P-DW-0202-06 - - 2 5 108 50 50 2 41 CS 30 - - - - -
143 4" CRUDE OIL 4"-PT-13-0015-FC01 10"-PT-13-0068-FC01 4"-PT-13-8604-FC01 17039-EK-P-DW-0202-06 - - 3 6 108 50 50 2 41 CS 30 - - - - -
144 4" CRUDE OIL 4"-PT-13-0016-FC01 10"-PT-13-0068-FC01 4"-PT-13-8605-FC01 17039-EK-P-DW-0202-06 - - 2 4 108 50 50 2 41 CS 30 - - - - -
145 2" CRUDE OIL 4"-PT-13-8604-FC01 13-GL-8182 2"-PT-13-7738-FC01 17039-EK-P-DW-0202-06 - - 2 5 108 50 50 2 41 CS 30 - - - - -
146 2" CRUDE OIL 4"-PT-13-0014-FC01 13-GL-0050 2"-PT-13-8602-FC01 17039-EK-P-DW-0202-06 - - 2 5 108 50 50 2 41 CS 30 - - - - -
147 2" CRUDE OIL 4"-PT-13-0015-FC01 13-GL-0066 2"-PT-13-8603-FC01 17039-EK-P-DW-0202-06 - - 2 5 108 50 50 2 41 CS 30 - - - - -
148 2" CRUDE OIL 4"-PT-13-0016-FC01 13-GL-0077 2"-PT-13-0022-FC01 17039-EK-P-DW-0202-06 - - 2 5 108 50 50 2 41 CS 30 - - - - -
149 6" CRUDE OILTP- 0041 - WELL FLUID FROM LP
WELL -1
WELL FLUID TO LP PRODUCTION
TEST HEADER EK-GAY-12906"-PT-13-0118-FC01 17039-EK-P-DW-0202-07 - - 4 8 108 50 50 2 41 CS 30 - - - - -
150 6" CRUDE OILTP- 0042 - WELL FLUID FROM LP
WELL -2
WELL FLUID TO LP PRODUCTION
TEST HEADER EK-GAY-12906"-PT-13-0119-FC01 17039-EK-P-DW-0202-07 - - 4 8 108 50 50 2 41 CS 30 - - - - -
151 6" CRUDE OILTP- 0043 - WELL FLUID FROM LP
WELL -3
WELL FLUID TO LP PRODUCTION
TEST HEADER EK-GAY-12906"-PT-13-0111-FC01 17039-EK-P-DW-0202-07 - - 4 8 108 50 50 2 41 CS 30 - - - - -
152 2" CRUDE OIL 6"-PT-13-0118-FC01 13-GL-0305 2"-PT-13-0112-FC01 17039-EK-P-DW-0202-07 - - 1 3 108 50 50 2 41 CS 30 - - - - -
153 2" CRUDE OIL 6"-PT-13-0119-FC01 13-GL-0305 2"-PT-13-0113-FC01 17039-EK-P-DW-0202-07 - - 1 3 108 50 50 2 41 CS 30 - - - - -
154 2" CRUDE OIL 6"-PT-13-0111-FC01 13-GL-0326 2"-PT-13-0114-FC01 17039-EK-P-DW-0202-07 - - 1 3 108 50 50 2 41 CS 30 - - - - -
155 6" CRUDE OIL WELL FLUID FROM LP WELL -1 10"-PT-13-0184-FC01 6"-PT-13-0109-FC0117039-EK-P-DW-0202-09 TO 17039-EK-P-DW-
0202-10- - 4 10 108 50 50 2 41 CS 30 - - - - -
156 6" CRUDE OIL WELL FLUID FROM LP WELL -2 10"-PT-13-0184-FC01 6"-PT-13-0110-FC0117039-EK-P-DW-0202-09 TO 17039-EK-P-DW-
0202-10- - 4 10 108 50 50 2 41 CS 30 - - - - -
157 6" CRUDE OIL WELL FLUID FROM LP WELL -3 10"-PT-13-0184-FC01 6"-PT-13-0111-FC0117039-EK-P-DW-0202-09 TO 17039-EK-P-DW-
0202-10- - 4 10 108 50 50 2 41 CS 30 - - - - -
Page 4 of 5
MIN MAX
Temp. °C Temp. °C
AMBIENT Temp. °C
TRAID
CABLE
POWER CABLE
LENGTH
POWER CABLE
SIZESERVICE LINE No. / EQUIPMENT
FROM LINE No. /
EQUIPMENT TO LINE No. / EQUIPMENT
OPERATING
Temp. °C DESIGN TEMP. °C
No's VALVES
(NOTE-4)
P&ID NUMBER (NOTE-4)
HEAT TRACING LINE LIST
PIPING /
EQUIPMENT
DIA(inch)
PIPE
MATERIAL
HEAT TRACING PIPE CABLE
LENGTH (M)
NO. OF CRK.
REQ
MATERIAL
SL.NO
INSULATION
THICKNESS. (mm)
MAINTAINED
Temp. °C
No's FLANGES
INSULATION VALVE / FLANGE Q'TY
PIPE / EQUIPMENT
LENGTH (M)
158 8" CRUDE OIL 13-BL-0807 FLANGE 8"-PT-13-0158-FC01 17039-EK-P-DW-0202-09 - - 1 3 108 50 50 2 41 CS 30 - - - - -
159 2" CRUDE OIL 8"-PT-13-0158-FC01 13-GL-0568 2"-PT-13-0188-FC01 17039-EK-P-DW-0202-09 - - 1 3 108 50 50 2 41 CS 30 - - - - -
160 8" CRUDE OIL 8"-PT-13-0158-FC01 13-BL-0980 8"-PT-13-0256-FC01 17039-EK-P-DW-0202-09 - - 1 2 108 50 50 2 41 CS 30 - - - - -
161 8" CRUDE OIL 13-BL-0835 FLANGE 8"-PT-13-0184-FC01 17039-EK-P-DW-0202-10 - - 1 3 108 50 50 2 41 CS 30 - - - - -
162 10" CRUDE OIL 8"-PT-13-0184-FC01 WELL FLUID TO INLET HEATER-B 10"-PT-13-0182-FC0117039-EK-P-DW-0202-10 TO 17039-EK-P-DW-
0232-03- - 4 8 108 50 50 2 41 CS 30 - - - - -
163 6" CRUDE OIL 8"-PT-13-0184-FC01 WELL FLUID TO INLET SEPERATOR 6"-PT-13-0196-FC0117039-EK-P-DW-0202-10 TO 17039-EK-P-DW-
0202-13- - 2 4 108 50 50 2 41 CS 30 - - - - -
164 6" CRUDE OIL 8"-PT-13-0184-FC01 13-BL-0679 6"-PT-13-0196-FC01 17039-EK-P-DW-0202-10 - - 2 4 108 50 50 2 41 CS 30 - - - - -
165 4" CRUDE OILWELL FLUID FROM TEST
HEADERSDV 0206 4"-PT-13-0196-FC01 17039-EK-P-DW-0202-12 - - 1 4 108 50 50 2 41 CS 30 - - - - -
166 4" CRUDE OIL SDV 0206 N1 NOZZLE OF EK-MBD-1110 4"-PT-13-7810-DC01 17039-EK-P-DW-0202-12 - - 1 2 108 50 50 2 41 CS 30 - - - - -
167 6" CRUDE OIL N2 NOZZLE OF EK-MBD-1110 LV0216 6"-PL-13-0204-DC01 17039-EK-P-DW-0202-12 - - 2 13 108 50 50 2 41 CS 30 - - - - -
168 6" CRUDE OIL 6"-PL-13-0205-DC01 TO CRUDE OIL TEST TANK 6"-PL-13-0205-DC01 17039-EK-P-DW-0202-12 - - 2 13 108 50 50 2 41 CS 30 - - - - -
169 6" CRUDE OIL WELL FLUID FROM LP WELL -4 10"-PT-13-0184-FC01 6"-PT-13-0118-FC0117039-EK-P-DW-0202-08 TO 17039-EK-P-DW-
0202-10 - - 4 10 108 50 50 2 41 CS 30 - - - - -
170 2" CRUDE OIL 6"-PT-13-0118-FC01 13-BL-7966 2"-PT-13-0121-FC01 17039-EK-P-DW-0202-08 - - 1 3 108 50 50 2 41 CS 30 - - - - -
171 6" CRUDE OIL WELL FLUID FROM LP WELL -5 10"-PT-13-0184-FC01 6"-PT-13-0119-FC0117039-EK-P-DW-0202-08 TO 17039-EK-P-DW-
0202-10 - - 4 10 108 50 50 2 41 CS 30 - - - - -
172 2" CRUDE OIL 6"-PT-13-0119-FC01 13-BL-0322 2"-PT-13-0122-FC01 17039-EK-P-DW-0202-08 - - 1 3 108 50 50 2 41 CS 30 - - - - -
173 6" CRUDE OIL WELL FLUID FROM LP WELL -6 10"-PT-13-0184-FC01 6"-PT-13-0120-FC0117039-EK-P-DW-0202-08 TO 17039-EK-P-DW-
0202-10 - - 4 10 108 50 50 2 41 CS 30 - - - - -
174 2" CRUDE OIL 6"-PT-13-0120-FC01 13-BL-0355 2"-PT-13-0123-FC01 17039-EK-P-DW-0202-08 - - 1 3 108 50 50 2 41 CS 30 - - - - -
175 4" CRUDE OIL CRUDE FROM CRUDE TEST TANK 4"-PL-20-1382-AC01 4"-PL-20-1380-AC01 17039-EK-P-DW-0202-14 - - 0 2 108 50 50 2 41 CS 30 - - - - -
176 4" CRUDE OIL 4"-PL-20-1380-AC01 N1 NOZZLE OF EK-PBA-1112A 4"-PL-20-1382-AC01 17039-EK-P-DW-0202-14 - - 1 9 108 50 50 2 41 CS 30 - - - - -
177 4" CRUDE OIL 4"-PL-20-1380-AC01 N1 NOZZLE OF EK-PBA-1112B 4"-PL-20-1381-AC01 17039-EK-P-DW-0202-14 - - 1 9 108 50 50 2 41 CS 30 - - - - -
178 3" CRUDE OIL N2 NOZZLE OF EK-PBA-1112B 20-BL-1460B 3"-PL-20-1384-BC01 17039-EK-P-DW-0202-14 - - 1 7 108 50 50 2 41 CS 30 - - - - -
179 3" CRUDE OIL N2 NOZZLE OF EK-PBA-1112A 20-BL-1460B 3"-PL-20-1381-BC01 17039-EK-P-DW-0202-14 - - 1 7 108 50 50 2 41 CS 30 - - - - -
180 2" CRUDE OIL 3"-PL-20-0881-BC01 FV1391 2"-PL-20-0882-BC01 17039-EK-P-DW-0202-14 - - 1 3 108 50 50 2 41 CS 30 - - - - -
181 2" CRUDE OIL 2"-PL-20-0882-BC01 20-GL-1409 BY PASS LINE OF FV 1391 17039-EK-P-DW-0202-14 - - 1 2 108 50 50 2 41 CS 30 - - - - -
182 2" CRUDE OIL FV1391MINIMUM RECYCLE TO CRUDE OIL
TEST TANK2"-PL-20-1387-AC01 17039-EK-P-DW-0202-14 - - 1 5 108 50 50 2 41 CS 30 - - - - -
183 2" CRUDE OIL 4"-PT-13-0015-FC01 13-GL-0066 2"-PT-13-8603-FC01 17039-EK-P-DW-0202-06 - - 2 5 108 50 50 2 41 CS 30 - - - - -
184 2" CRUDE OIL 4"-PT-13-0016-FC01 13-GL-0077 2"-PT-13-0022-FC01 17039-EK-P-DW-0202-06 - - 2 5 108 50 50 2 41 CS 30 - - - - -
185 4" CRUDE OIL 4"-PT-13-0014-FC01 8"-PT-13-0168-FC01 4"-PT-13-0017-FC0117039-EK-P-DW-0202-06 TO 17039-EK-P-DW-
0202-09- - 2 4 108 50 50 2 41 CS 30 - - - - -
186 4" CRUDE OIL 4"-PT-13-0015-FC01 8"-PT-13-0168-FC01 4"-PT-13-8604-FC0117039-EK-P-DW-0202-06 TO 17039-EK-P-DW-
0202-09- - 2 4 108 50 50 2 41 CS 30 - - - - -
187 4" CRUDE OIL 4"-PT-13-0016-FC01 8"-PT-13-0168-FC01 4"-PT-13-8605-FC0117039-EK-P-DW-0202-06 TO 17039-EK-P-DW-
0202-09- - 2 4 108 50 50 2 41 CS 30 - - - - -
188 2" CRUDE OIL 4"-PT-13-0017-FC01 13-GL-8172 2"-PT-13-7733-FC01 17039-EK-P-DW-0202-06 - - 2 5 108 50 50 2 41 CS 30 - - - - -
189 2" CRUDE OIL 4"-PT-13-0016-FC01 13-GL-8182 2"-PT-13-7738-FC01 17039-EK-P-DW-0202-06 - - 2 5 108 50 50 2 41 CS 30 - - - - -
Page 5 of 5
MIN MAX
Temp. °C Temp. °C
1 10" WELL FLUID 10"-PT-13-0158-FC01 N1NOZZLE OF ND-HBG-1470 10"-PT-13-0192-FC0117039-ND-P-DW-0202-15 TO 17039-ND-P-DW-
0203-01- - 5 16 250 50 50 2 41 CS 30 - - - - -
2 2" WELL FLUIDWELL FLUID FROM TEST
SEPERATOR10"-PT-13-0192-FC01 2"-PT-13-0205-FC01
17039-ND-P-DW-0202-20 TO 17039-ND-P-DW-
0203-01- - 2 8 250 50 50 2 41 CS 30 - - - - -
3 10" WELL FLUID 10"-PT-13-0192-FC01 10"-PT-20-0350-DC01 10"-PT-20-0352-DC01 17039-ND-P-DW-0203-01 - - 2 4 250 50 50 2 41 CS 30 - - - - -
4 10" WELL FLUID N2NOZZLE OF ND-HBG-1470 N1NOZZLE OF ND-HBG-1470 10"-PT-20-0350-DC0117039-ND-P-DW-0203-01 TO 17039-ND-P-DW-
0203-02- - 2 9 250 50 50 2 41 CS 30 - - - - -
5 10" WELL FLUID 10"-PT-20-0350-DC01 10"-PT-20-4175A-DC01 10"-PT-13-0350A-DC0117039-ND-P-DW-0203-01 TO 17039-ND-P-DW-
0203-04- - 2 6 250 50 50 2 41 CS 30 - - - - -
6 - CRUDE OIL K3B NOZZLE OF ND-MBD-1020 24"MW1 ND-MBD-1020 17039-ND-P-DW-0203-02 - - 0 1 80 50 50 2 41 CS - - - - - -
7 - CRUDE OIL K3B NOZZLE OF ND-MBD-1020 K3A NOZZLE OF ND-MBD-1020 LT 0404 17039-ND-P-DW-0203-02 - - 2 4 80 50 50 2 41 CS 3 - - - - -
8 - CRUDE OIL K4A NOZZLE OF ND-MBD-1020 K4B NOZZLE OF ND-MBD-1020 LG 1068 17039-ND-P-DW-0203-02 - - 0 4 80 50 50 2 41 CS 3 - - - - -
9 - CRUDE OIL K1A NOZZLE OF ND-MBD-1020 K1B NOZZLE OF ND-MBD-1020 ILT 4502 17039-ND-P-DW-0203-02 - - 0 3 80 50 50 2 41 CS 3 - - - - -
10 - CRUDE OIL K1A NOZZLE OF ND-MBD-1020 K1B NOZZLE OF ND-MBD-1020 ILT 0402 17039-ND-P-DW-0203-02 - - 0 2 80 50 50 2 41 CS 3 - - - - -
11 - CRUDE OIL K8 NOZZLE OF ND-MBD-1340 PT 0405 - 17039-ND-P-DW-0203-02 - - 0 1 80 50 50 2 41 CS 3 - - - - -
12 - CRUDE OIL K6 NOZZLE OF ND-MBD-1020 PT 0406 - 17039-ND-P-DW-0203-02 - - 0 1 80 50 50 2 41 CS 3 - - - - -
13 - CRUDE OIL K5 NOZZLE OF ND-MBD-1020 PT 1067 - 17039-ND-P-DW-0203-02 - - 0 1 80 50 50 2 41 CS 3 - - - - -
14 4" CRUDE OIL N3 NOZZLE OF ND-MDB-1020 LV 1068 4"-PL-20-0357-BC01 17039-ND-P-DW-0203-02 - - 3 10 80 50 50 2 41 CS 30 - - - - -
15 4" CRUDE OIL LV 1068 FV 0200B 4"-PT-20-0358-AC01 17039-ND-P-DW-0203-02 - - 2 7 80 50 50 2 41 CS 30 - - - - -
16 - CRUDE OIL 4"-PL-20-0357-BC01 4"-PL-20-0358-AC01 BY PASS LINE OF LV 1068 17039-ND-P-DW-0203-02 - - 1 2 80 50 50 2 41 CS 30 - - - - -
17 12" CRUDE OIL/HOT OILWELL FLUID FROMLP
PRODUCTION HEADERN1 NOZZLE OF ND-HBG-1480 12"-PT-13-0182-FC01
17039-ND-P-DW-0202-18 TO 17039-ND-P-
DW-0203-03- - 3 11 250 50 50 2 41 CS 30 - - - - -
18 10" CRUDE OIL/HOT OIL 12"-PT-13-0182-FC01 10"-PT-20-0366-BC01 10"-PT-20-7818-BC01 17039-ND-P-DW-0203-03 - - 2 4 250 50 50 2 41 CS 30 - - - - -
19 10" CRUDE OIL/HOT OIL 10"-PT-20-0366-BC01 CRUDE TO INLET SEPERATOR-C 10"-PT-20-0366A-BC01 17039-ND-P-DW-0203-03 TO 17039-ND-P-
DW-0203-05- - 0 0 250 50 50 2 41 CS 30 - - - - -
20 10" CRUDE OIL/HOT OIL N2 NOZZLE OF ND-HBG-1480 N1 NOZZLE OF ND-MBD-1340 10"-PT-20-0366-BC01 17039-ND-P-DW-0203-03 TO 17039-ND-P-
DW-0203-04- - 2 9 250 50 50 2 41 CS 30 - - - - -
21 3"CRUDE
OIL/WATER/HC GAS
WELL FLUID FROM TEST
TRANSFER PUMPS10"-PT-20-0366-BC01 3"-PT-20-2861-BC01
17039-ND-P-DW-0202-22 TO 17039-ND-P-
DW-0203-04- - 2 6 80 50 50 2 41 CS 30 - - - - -
22 3"CRUDE
OIL/WATER/HC GAS6"-PL-20-0393-AC01 10"-PT-20-0366-BC01 3"-PL-20-0393-BC01
17039-ND-P-DW-0203-15 TO 17039-ND-P-
DW-0203-04- - 2 7 80 50 50 2 41 CS 30 - - - - -
23 -CRUDE
OIL/WATER/HC GASK3B NOZZLE OF ND-MBD1340 NITROGEN PURGE CONNECTION INLET SEPERATOR-B 17039-ND-P-DW-0203-04 - - 0 1 80 50 50 2 41 CS 30 - - - - -
24 -CRUDE
OIL/WATER/HC GASN7 NOZZLE OF ND-MBD-1340 NITROGEN PURGE CONNECTION - 17039-ND-P-DW-0203-04 - - 1 5 80 50 50 2 41 CS 3 - - - - -
25 -CRUDE
OIL/WATER/HC GASK1A NOZZLE OF ND-MBD-1340 K1B NOZZLE OF ND-MBD-1340 ILIT 0466 17039-ND-P-DW-0203-04 - - 0 2 80 50 50 2 41 CS 3 - - - - -
26 -CRUDE
OIL/WATER/HC GASK4A NOZZLE OF ND-MBD-1340 K4B NOZZLE OF ND-MBD-1340 LG 0463 17039-ND-P-DW-0203-04 - - 0 4 80 50 50 2 41 CS 3 - - - - -
27 -CRUDE
OIL/WATER/HC GASK9A NOZZLE OF ND-MBD-1340 K9B NOZZLE OF ND-MBD-1340 ILIT 0464 17039-ND-P-DW-0203-04 - - 0 2 80 50 50 2 41 CS 3 - - - - -
28 -CRUDE
OIL/WATER/HC GASK8 NOZZLE OF ND-MBD-1340 PIT0454 - 17039-ND-P-DW-0203-04 - - 0 1 80 50 50 2 41 CS 3 - - - - -
29 -CRUDE
OIL/WATER/HC GASK6 NOZZLE OF ND-MBD-1340 PIT0455 - 17039-ND-P-DW-0203-04 - - 0 1 80 50 50 2 41 CS 3 - - - - -
30 -CRUDE
OIL/WATER/HC GASK5 NOZZLE OF ND-MBD-1340 PIT0456 - 17039-ND-P-DW-0203-04 - - 0 1 80 50 50 2 41 CS 3 - - - - -
31 4"CRUDE
OIL/WATER/HC GASN3 NOZZLE OF ND-MBD-1340 LV0463 4"-PL-20-0369-AC01 17039-ND-P-DW-0203-04 - - 3 10 80 50 50 2 41 CS 30 - - - - -
32 4"CRUDE
OIL/WATER/HC GASLV0463A 6"-PT-20-0396-AC01 4"-PL-20-0370-AC02 17039-ND-P-DW-0203-04 - - 1 5 80 50 50 2 41 CS 30 - - - - -
33 -CRUDE
OIL/WATER/HC GAS4"-PL-20-0369-AC01 4"-PL-20-0370-AC02 BYE PASS LINE OF LV0463 17039-ND-P-DW-0203-04 - - 1 2 80 50 50 2 41 CS 30 - - - - -
34 10"CRUDE
OIL/WATER/HC GAS10"-PT-20-0366A-BC01 10"-PT-20-4175A-DC01 10"-PT-20-0360A-DC01
17039-ND-P-DW-0203-03 TO 17039-ND-P-
DW-0203-05- - 2 6 80 50 50 2 41 CS 30 - - - - -
35 10"CRUDE
OIL/WATER/HC GAS
WELL FLUID FROM HP INLET
HEATER-A10"-PT-20-4175A-DC01 10"-PT-13-0350-DC01 17039-ND-P-DW-0203-05 - - 2 6 80 50 50 2 41 CS 30 - - - - -
36 -CRUDE
OIL/WATER/HC GASK3B NOZZLE OF ND-MBD-1500 24" MW1 ND-MBD-1500 17039-ND-P-DW-0203-05 - - 0 0 80 50 50 2 41 CS - - - - - -
37 -CRUDE
OIL/WATER/HC GASK8 NOZZLE OF ND-MBD-1500 PIT 0454A - 17039-ND-P-DW-0203-05 - - 0 1 80 50 50 2 41 CS 30 - - - - -
38 -CRUDE
OIL/WATER/HC GASK6 NOZZLE OF ND-MBD-1500 PIT 0455A - 17039-ND-P-DW-0203-05 - - 0 1 80 50 50 2 41 CS 30 - - - - -
(NOTE-4)
HEAT TRACING LINE LIST
PIPING /
EQUIPMENT
DIA(inch)
PIPE
MATERIAL
HEAT TRACING PIPE CABLE
LENGTH (M)
NO. OF CRK.
REQ
MATERIAL
SL.NO
INSULATION
THICKNESS. (mm)
MAINTAINED
Temp. °C
No's FLANGES
INSULATION VALVE / FLANGE Q'TY
PIPE / EQUIPMENT
LENGTH (M)
OPERATING
Temp. °C DESIGN TEMP. °C
No's VALVES
(NOTE-4)
P&ID NUMBERSERVICE LINE No. / EQUIPMENT FROM LINE No. /
EQUIPMENT TO LINE No. / EQUIPMENT
AMBIENT Temp. °C
TRAID
CABLE
POWER CABLE
LENGTH
POWER CABLE
SIZE
Page 1 of 6
Annexure- 5
MIN MAX
Temp. °C Temp. °C
(NOTE-4)
HEAT TRACING LINE LIST
PIPING /
EQUIPMENT
DIA(inch)
PIPE
MATERIAL
HEAT TRACING PIPE CABLE
LENGTH (M)
NO. OF CRK.
REQ
MATERIAL
SL.NO
INSULATION
THICKNESS. (mm)
MAINTAINED
Temp. °C
No's FLANGES
INSULATION VALVE / FLANGE Q'TY
PIPE / EQUIPMENT
LENGTH (M)
OPERATING
Temp. °C DESIGN TEMP. °C
No's VALVES
(NOTE-4)
P&ID NUMBERSERVICE LINE No. / EQUIPMENT FROM LINE No. /
EQUIPMENT TO LINE No. / EQUIPMENT
AMBIENT Temp. °C
TRAID
CABLE
POWER CABLE
LENGTH
POWER CABLE
SIZE
39 -CRUDE
OIL/WATER/HC GASK5 ND-MBD-1500 PIT 0456A - 17039-ND-P-DW-0203-05 - - 0 1 80 50 50 2 41 CS 30 - - - - -
40 4"CRUDE
OIL/WATER/HC GASN3 NOZZLE OF ND-MBD-1500 LV 0463A 4"-PL-20-0369A-BC01 17039-ND-P-DW-0203-05 - - 3 10 80 50 50 2 41 CS 30 - - - - -
41 4"CRUDE
OIL/WATER/HC GASLV 0463A 6"-PT-20-0396-AC01 4"-PT-20-0890-AC01
17039-ND-P-DW-0203-05 TO 17039-ND-P-DW-
0203-06- - 2 7 80 50 50 2 41 CS 30 - - - - -
42 -CRUDE
OIL/WATER/HC GAS4"-PL-20-0369A-BC01 4"-PT-20-0890-AC01 BYEPASS LINE OF LV 0463A 17039-ND-P-DW-0203-05 - - 1 2 80 50 50 2 41 CS 30 - - - - -
43 4"CRUDE
OIL/WATER/HC GAS4"-PT-20-0358-AC01 N3 NOZZLE OF ND-HBG-B-1030 4"-PT-0396B-AC01
17039-ND-P-DW-0203-17 TO 17039-ND-P-DW-
0203-066 14 80 50 50 2 41 CS 30
44 -CRUDE
OIL/WATER/HC GAS4"-PT-20-0358-AC01 4"-PT-0396B-AC01 BY PASS LINE OF FV0200B 17039-ND-P-DW-0203-06 1 2 80 50 50 2 41 CS 30
45 6" CRUDE OIL 4"-PT-20-0370-AC01 4"-PT-20-0370-AC01 6"-PT-20-0396-AC0117039-ND-P-DW-0203-04 TO 17039-ND-P-DW-
0203-06- - 1 4 150 50 50 2 41 CS 30 - - - - -
46 4" CRUDE OIL 4"-PT-20-0890-AC01 6"-PT-20-0396-AC01 4"-PT-20-0367D-AC0117039-ND-P-DW-0203-05 TO 17039-ND-P-DW-
0203-06- - 1 4 150 50 50 2 41 CS 30 - - - - -
47 - CRUDE OIL 6"-PT-20-0396-AC01 4"-PT-20-0358-AC01 BYPASS LINE OF FV 0200B 17039-ND-P-DW-0203-06 - - 1 2 150 50 50 2 41 CS 30 - - - - -
48 - CRUDE OIL N8 NOZZLE OF ND-MBD-A-1050 64-BL-17-1791A ND-MBD-A-1050 - - 0 0 150 50 50 2 41 CS - - - - - -
49 3" CRUDE OIL N1 NOZZLE OF ND-HBG-A-1030 LV 0476 3"-PL-20-0374-AC01 17039-ND-P-DW-0203-06 - - 1 5 150 50 50 2 41 CS 30 - - - - -
50 3" CRUDE OIL LV 0476 4"-PL-20-0823-AC01 3"-PL-20-0376-AC0117039-ND-P-DW-0203-06 TO 17039-ND-P-DW-
0203-10- - 3 5 150 50 50 2 41 CS 30 - - - - -
51 4" CRUDE OIL 3"-PL-20-0376-AC01 6"-PL-20-0440-AC01 4"-PL-20-0375-AC0117039-ND-P-DW-0203-06 TO 17039-ND-P-DW-
0203-14- - 1 2 150 50 50 2 41 CS 30 - - - - -
52 - CRUDE OIL 20-BL-1256 20-BL-1270 PDIT0470 17039-ND-P-DW-0203-06 - - 0 2 150 50 50 2 41 CS 3 - - - - -
53 - CRUDE OIL 3"-PL-20-0374-AC01 3"-PL-20-0376-AC01 BYPASS LINE OF LV 0476 17039-ND-P-DW-0203-06 - - 1 2 150 50 50 2 41 CS 30 - - - - -
54 4" CRUDE OIL N4 NOZZLE OF ND-HBG-A-1030 N1 NOZZLE OF ND-HBG-A-1040 4"-PT-20-0377-AC0117039-ND-P-DW-0203-06 TO 17039-ND-P-DW-
0203-06- - 3 9 150 50 50 2 41 CS 30 - - - - -
55 3" CRUDE OIL 3"-PL-20-0453-AC01 N2 NOZZLE OF ND-HBG-A-1030 3"-PL-20-0457-AC0117039-ND-P-DW-0203-09 TO 17039-ND-P-DW-
0203-07- - 0 5 150 50 50 2 41 CS 30 - - - - -
56 6" CRUDE OIL N2 NOZZLE OF ND-HBG-A-1040 N1 NOZZLE OF ND-MBD-A-1050 6"-PT-20-0384-AC0117039-ND-P-DW-0203-07 TO 17039-ND-P-DW-
0203-08- - 2 7 250 50 50 2 41 CS 30 - - - - -
57 - CRUDE OIL 20-BL-1281 20-BL-1283 PDIT3605 17039-ND-P-DW-0203-07 - - 0 2 250 50 50 2 41 CS 3 - - - - -
58 3" CRUDE OIL ND-MBD-A-1050 ND-MBM-A-1060 3"-PL-20-0359-AC01 17039-ND-P-DW-0203-08 - - 0 0 150 50 50 2 41 CS 30 - - - - -
59 - CRUDE OIL N4 NOZZLE OF ND-MBM-A-1060 N3 NOZZLE OF ND-MBM-A-1060 ND-MBM-A-1060 17039-ND-P-DW-0203-08 - - 0 0 150 50 50 2 41 CS - - - - - -
60 2" CRUDE OILHC COCNDENSATE FROM LP
GAS COMPRESSION PACKAGE6"-PT-20-0384-AC01 2"-PL-20-0470-AC01
17039-ND-P-DW-0204-01 TO 17039-ND-P-DW-
0203-08- - 1 6 150 50 50 2 41 CS 30 - - - - -
61 4" CRUDE OIL N2 NOZZLE OF ND-MBM-A-1060 4"-PL-20-0452-AC01 4"-PL-20-0360-AC0117039-ND-P-DW-0203-08 TO 17039-ND-P-DW-
0203-09- - 0 1 150 50 50 2 41 CS 30 - - - - -
62 4" CRUDE OIL 4"-PL-20-0360-AC01 NI NOZZLE OF ND-PBA-A-1070B 4"-PL-20-0452-AC01 17039-ND-P-DW-0203-09 1 6 150 50 50 2 41 CS 30
63 4" CRUDE OIL 4"-PL-20-0360-AC01 NI NOZZLE OF ND-PBA-A-1070A 4"-PL-20-0451-AC01 17039-ND-P-DW-0203-09 0 1 150 50 50 2 41 CS 30
64 3" CRUDE OIL N2 NOZZLE OF ND-PBA-A-1070A 3"-PL-20-0457-AC01 3"-PL-20-0454-AC01 17039-ND-P-DW-0203-09 - - 1 6 150 50 50 2 41 CS 30 - - - - -
65 3" CRUDE OIL N2 NOZZLE OF ND-PBA-A-1070B 3"-PL-20-0457-AC01 3"-PL-20-0453-AC01 17039-ND-P-DW-0203-09 - - 1 6 150 50 50 2 41 CS 30 - - - - -
66 4" CRUDE OIL 4"-PL-20-0823-AC01 N1 NOZZLE OF ND-BBJ-1120B 4"-PL-20-0818-AC0117039-ND-P-DW-0203-10 TO 17039-ND-P-DW-
0203-11- - 2 5 90 50 50 2 41 CS 30 - - - - -
67 4" CRUDE OIL 4"-PL-20-0823-AC01 4"-PL-20-0818-AC01 4"-PL-20-0820-AC0117039-ND-P-DW-0203-10 TO 17039-ND-P-DW-
0203-11- - 1 2 90 50 50 2 41 CS 30 - - - - -
68 4" CRUDE OIL 4"-PL-20-0823-AC01 N1 NOZZLE OF ND-BBJ-1120A 4"-PL-20-0816-AC01 17039-ND-P-DW-0203-10 - - 2 5 90 50 50 2 41 CS 30 - - - - -
69 4" CRUDE OIL 4"-PL-20-0823-AC01 4"-PL-20-0816-AC01 4"-PL-20-0817-AC01 17039-ND-P-DW-0203-10 - - 0 2 90 50 50 2 41 CS 30 - - - - -
70 4" CRUDE OIL N2 NOZZLE OF ND-BBJ-1120A 10"-PL-20-0833-AC01 4"-PL-20-0822-AC0117039-ND-P-DW-0203-10 TO 17039-ND-P-DW-
0203-12- - 2 5 90 50 50 2 41 CS 30 - - - - -
71 - CRUDE OIL N8 NOZZLE OF ND-MBD-B-1050 64-BL-1793 ND-MBD-B-1050 17039-ND-P-DW-0203-19 - - 0 0 90 50 50 2 41 CS -
72 8" CRUDE OIL ND-MBD-B-1050 ND-MBM-B-1060 8"-PL-20-0359B-AC01 17039-ND-P-DW-0203-19 - - 0 0 90 50 50 2 41 CS 30
73 - CRUDE OIL N3 NOZZLE OF ND-MBM-B-1060 N4 NOZZLE OF ND-MBM-B-1060 ND-MBM-B-1060 17039-ND-P-DW-0203-19 - - 0 0 90 50 50 2 41 CS 30
74 4" CRUDE OIL N2 NOZZLE OF ND-BBJ-1120B 10"-PL-20-0833-AC01 4"-PL-20-0825-AC0117039-ND-P-DW-0203-11 TO 17039-ND-P-DW-
0203-12- - 2 5 90 50 50 2 41 CS 30 - - - - -
75 2" CRUDE OIL 4"-PL-20-8639-AC01 FV 1012C 2"-PL-20-0841C-AC01 17039-ND-P-DW-0203-12 - - 2 3 90 50 50 2 41 CS 30
76 2" CRUDE OIL FV 1012CMINIMUM RECYCLE FLOW TO
CRUDE STORAGE TANK2"-PL-20-0827-AC01
17039-ND-P-DW-0203-12 TO 17039-ND-P-DW-
0203-10- - 2 5 90 50 50 2 41 CS 30
77 - CRUDE OIL 2"-PL-20-0841C-AC01 2"-PL-20-0827-AC01 BYPASS LINE OF FV 1012C 17039-ND-P-DW-0203-12 - - 1 2 90 50 50 2 41 CS 30
Page 2 of 6
MIN MAX
Temp. °C Temp. °C
(NOTE-4)
HEAT TRACING LINE LIST
PIPING /
EQUIPMENT
DIA(inch)
PIPE
MATERIAL
HEAT TRACING PIPE CABLE
LENGTH (M)
NO. OF CRK.
REQ
MATERIAL
SL.NO
INSULATION
THICKNESS. (mm)
MAINTAINED
Temp. °C
No's FLANGES
INSULATION VALVE / FLANGE Q'TY
PIPE / EQUIPMENT
LENGTH (M)
OPERATING
Temp. °C DESIGN TEMP. °C
No's VALVES
(NOTE-4)
P&ID NUMBERSERVICE LINE No. / EQUIPMENT FROM LINE No. /
EQUIPMENT TO LINE No. / EQUIPMENT
AMBIENT Temp. °C
TRAID
CABLE
POWER CABLE
LENGTH
POWER CABLE
SIZE
78 4" CRUDE OIL 3"-PL-20-8640-AC01 FV 1012D 4"-PL-20-0841D-AC01 17039-ND-P-DW-0203-12 - - 2 5 90 50 50 2 41 CS 30
79 - CRUDE OIL 4"-PL-20-0841D-AC01 2"-PL-20-0827-AC01 BYPASS LINE OF FV 1012D 17039-ND-P-DW-0203-12 - - 1 2 90 50 50 2 41 CS 30
80 2" CRUDE OIL 3"-PL-20-0839-AC01 FV 1012B 2"-PL-20-0841A-AC0117039-ND-P-DW-0203-12 TO 17039-ND-P-DW-
0203-10- - 1 3 90 50 50 2 41 CS 30 - - - - -
81 - CRUDE OIL 2"-PL-20-0841A-AC01 4"-PL-20-0827-AC01 BY PASS LINE OF FV 1012B 17039-ND-P-DW-0203-12 - - 1 2 90 50 50 2 41 CS 30 - - - - -
82 - CRUDE OIL 2"-PL-20-0841A-AC01 2"-PL-20-0827-AC01 BYPASS LINE OF FV 1012A 17039-ND-P-DW-0203-12 - - 1 2 90 50 50 2 41 CS 30 - - - - -
83 4" CRUDE OIL 10"-PL-20-0833-AC01 20-BL-9000 4"-PL-20-8637-AC01 17039-ND-P-DW-0203-12 - - 0 0 90 50 50 2 41 CS 30 - - - - -
84 4" CRUDE OIL 10"-PL-20-0833-AC01 20-BL-9001 4"-PL-20-2638-AC01 17039-ND-P-DW-0203-12 - - 0 0 90 50 50 2 41 CS 30 - - - - -
85 4" CRUDE OIL 20-BL-9000 NI NOZZLE OF ND-PBA-1130C 4"-PL-20-8636-AC01 17039-ND-P-DW-0203-12 - - 0 0 90 50 50 2 41 CS 30 - - - - -
86 3" CRUDE OIL N2 NOZZLE OF ND-PBA-1130C - 3"-PL-20-8639-AC01 17039-ND-P-DW-0203-12 2 9 90 50 50 2 41 CS 30
87 4" CRUDE OIL 20-BL-9001 NI NOZZLE OF ND-PBA-1130D 4"-PL-20-8638-AC01 17039-ND-P-DW-0203-12 - - 0 0 90 50 50 2 41 CS 30 - - - - -
88 3" CRUDE OIL N2 NOZZLE OF ND-PBA-1130D - 3"-PL-20-8638-AC01 17039-ND-P-DW-0203-12 2 9 90 50 50 2 41 CS 30
89 6" CRUDE OIL - 6"-PL-20-0840-AC01 6"-PL-20-0840-AC0117039-ND-P-DW-0203-12 TO 17039-ND-P-DW-
0203-130 0 90 50 50 2 41 CS 30
90 4" CRUDE OIL 10"-PL-20-0833-AC01 N1 NOZZLE OF ND-PM-1130A 4"-PL-20-0836-AC01 17039-ND-P-DW-0203-12 - - 1 6 90 50 50 2 41 CS 30 - - - - -
91 4" CRUDE OIL 10"-PL-20-0833-AC01 N1 NOZZLE OF ND-PM-1130B 4"-PL-20-0837-AC01 17039-ND-P-DW-0203-12 - - 1 6 90 50 50 2 41 CS 30 - - - - -
92 6" CRUDE OIL 6"-PL-20-0840-AC01 N1 NOZZLE OF ND-PBA-1140A 6"-PL-20-0842-AC0117039-ND-P-DW-0203-12 TO 17039-ND-P-DW-
0203-13- - 2 8 90 50 50 2 41 CS 30 - - - - -
93 4" CRUDE OIL N2 NOZZLE OF ND-PBA-1140A 6"-PL-20-0848-DC01 4"-PL-20-0845-DC01 17039-ND-P-DW-0203-13 - - 2 7 90 50 50 2 41 CS 30 - - - - -
94 6" CRUDE OIL 6"-PL-20-0840-AC01 N1 NOZZLE OF ND-PBA-1140B 6"-PL-20-0843-AC0117039-ND-P-DW-0203-12 TO 17039-ND-P-DW-
0203-13- - 2 8 90 50 50 2 41 CS 30 - - - - -
95 4" CRUDE OIL N2 NOZZLE OF ND-PBA-1140B 6"-PL-20-0848-DC01 4"-PL-20-0846-DC01 17039-ND-P-DW-0203-13 - - 2 7 90 50 50 2 41 CS 30 - - - - -
96 6" CRUDE OIL 6"-PL-20-0840-AC01 N1 NOZZLE OF ND-PBA-1140C 6"-PL-20-0844-AC0117039-ND-P-DW-0203-12 TO 17039-ND-P-DW-
0203-13- - 2 8 90 50 50 2 41 CS 30 - - - - -
97 4" CRUDE OIL N12 NOZZLE OF ND-PBA-1140C 6"-PL-20-0848-DC01 4"-PL-20-0847-DC01 17039-ND-P-DW-0203-13 - - 2 7 90 50 50 2 41 CS 30 - - - - -
98 6" CRUDE OIL 6"-PL-20-0840-AC01 N1 NOZZLE OF ND-PBA-1140D 6"-PL-20-8641-AC0117039-ND-P-DW-0203-12 TO 17039-ND-P-DW-
0203-13- - 2 8 90 50 50 2 41 CS 30 - - - - -
99 4" CRUDE OIL N2 NOZZLE OF ND-PBA-1140D 6"-PL-20-0848-DC01 4"-PL-20-8642-DC01 17039-ND-P-DW-0203-13 - - 2 7 90 50 50 2 41 CS 30 - - - - -
100 6" CRUDE OIL 6"-PL-20-0848-DC01 6"-PL-20-0855-DC01 6"-PL-20-0849-DC0117039-ND-P-DW-0203-13 TO 17039-ND-P-DW-
0203-16- - 0 3 90 50 50 2 41 CS 30 - - - - -
101 6" CRUDE OIL 6"-PL-20-0393-AC01 6"-PL-20-0840-AC01 6"-PL-20-0393-AC0117039-ND-P-DW-0203-15 TO 17039-ND-P-DW-
0203-16- - 1 6 90 50 50 2 41 CS 30 - - - - -
102 4" CRUDE OIL N1 NOZZLE OF ND-BBJ-1090 6"-PL-20-0440-AC01 4"-PL-20-0458-DC0117039-ND-P-DW-0203-06 TO 17039-ND-P-DW-
0203-14- - 1 3 90 50 50 2 41 CS 30 - - - - -
103 8" CRUDE OIL N2 NOZZLE OF ND-BBJ-1090 8"-PL-20-0386-AC01 8"-PL-20-0459-AC0117039-ND-P-DW-0203-14 TO 17039-ND-P-DW-
0203-15- - 3 6 90 50 50 2 41 CS 30 - - - - -
104 2" CRUDE OILCLOSED DRAIN FROM CLOSED
DRAIN TRANSFER PUMPS6"-PL-20-0440-AC01 2"-DC-57-6210-AC01
17039-ND-P-DW-0203-02 TO 17039-ND-P-DW-
0203-14- - 0 0 90 50 50 2 41 CS 30 - - - - -
105 3" CRUDE OIL
OFF SPEC CRUDE FROM
CRUDE/CRUDE EXCHANGER
OUTLET
6"-PL-20-0440-AC01 3"-PL-20-0375-AC0117039-ND-P-DW-0203-06 TO 17039-ND-P-DW-
0203-14- - 0 0 90 50 50 2 41 CS 30 - - - - -
106 8" CRUDE OIL 8"-PL-20-0459-AC01 N1 NOZZLE OF ND-PBA-1100A 8"-PL-20-0386-AC0117039-ND-P-DW-0203-14 TO 17039-ND-P-DW-
0203-15- - 1 6 90 50 50 2 41 CS 30 - - - - -
107 6" CRUDE OIL N2 NOZZLE OF ND-PBA-1100A 6"-PL-20-0393-AC01 6"-PL-20-0388-AC0117039-ND-P-DW-0203-14 TO 17039-ND-P-DW-
0203-15- - 1 7 90 50 50 2 41 CS 30 - - - - -
108 8" CRUDE OIL 8"-PL-20-0459-AC01 N1 NOZZLE OF ND-PBA-1100B 8"-PL-20-0387-AC0717039-ND-P-DW-0203-14 TO 17039-ND-P-DW-
0203-15- - 1 6 90 50 50 2 41 CS 30 - - - - -
109 3" CRUDE OIL N2 NOZZLE OF ND-PBA-1100B 6"-PL-20-0393-AC01 3"-PL-20-0389-AC0117039-ND-P-DW-0203-14 TO 17039-ND-P-DW-
0203-15- - 1 7 90 50 50 2 41 CS 30 - - - - -
110 3" CRUDE OIL 6"-PL-20-0393-AC01 FV 0475 3"-PL-20-0390-AC01 17039-ND-P-DW-0203-15 - - 1 3 90 50 50 2 41 CS 30 - - - - -
111 - CRUDE OIL 3"-PL-20-0390-AC01 6"-PL-20-0393-AC01 BYPASS LINE OF FV 0475 17039-ND-P-DW-0203-15 - - 1 2 90 50 50 2 41 CS 30 - - - - -
112 3" CRUDE OIL FV 0475 N7 NOZZLE OF ND-BBJ-1090 3"-PL-20-0391-AC0117039-ND-P-DW-0203-15 TO 17039-ND-P-DW-
0203-14- - 2 6 90 50 50 2 41 CS 30 - - - - -
113 6" CRUDE OIL 6"-PL-20-0855-DC01 MOV 1024 6"-PL-20-0856-DC01 17039-ND-P-DW-0203-16 - - 1 6 90 50 50 2 41 CS 30 - - - - -
114 6" CRUDE OIL 6"-PL-20-0855-DC01 MOV 1036 6"-PL-20-0857-DC01 17039-ND-P-DW-0203-16 - - 1 6 90 50 50 2 41 CS 30 - - - - -
115 6" CRUDE OIL MOV 1024 6"-PL-20-0860-DC01 6"-PL-20-0858-DC01 17039-ND-P-DW-0203-16 - - 5 9 90 50 50 2 41 CS 30 - - - - -
116 6" CRUDE OIL MOV 1036 6"-PL-20-0860-DC01 6"-PL-20-0859-DC01 17039-ND-P-DW-0203-16 - - 5 9 90 50 50 2 41 CS 30 - - - - -
117 6" CRUDE OIL 6"-PL-20-0860-DC01TREATED CRUDE TO NHK
CTF/STF PIPE LINE6"-PL-20-0861-DC01 17039-ND-P-DW-0203-16 - - 1 9 90 50 50 2 41 CS 30 - - - - -
Page 3 of 6
MIN MAX
Temp. °C Temp. °C
(NOTE-4)
HEAT TRACING LINE LIST
PIPING /
EQUIPMENT
DIA(inch)
PIPE
MATERIAL
HEAT TRACING PIPE CABLE
LENGTH (M)
NO. OF CRK.
REQ
MATERIAL
SL.NO
INSULATION
THICKNESS. (mm)
MAINTAINED
Temp. °C
No's FLANGES
INSULATION VALVE / FLANGE Q'TY
PIPE / EQUIPMENT
LENGTH (M)
OPERATING
Temp. °C DESIGN TEMP. °C
No's VALVES
(NOTE-4)
P&ID NUMBERSERVICE LINE No. / EQUIPMENT FROM LINE No. /
EQUIPMENT TO LINE No. / EQUIPMENT
AMBIENT Temp. °C
TRAID
CABLE
POWER CABLE
LENGTH
POWER CABLE
SIZE
118 3" CRUDE OIL 3"-PL-20-0457B-AC01 N2 NOZZLE OF ND-HBG-B-1030 3"-PL-20-0457-AC0117039-ND-P-DW-0203-06 TO 17039-ND-P-DW-
0203-17- - 0 4 150 50 50 2 41 CS 30 - - - - -
119 4" CRUDE OIL N1 NOZZLE OF ND-HBG-B-1030 LV 0476B 4"-PT-20-03764B-AC01 17039-ND-P-DW-0203-17 - - 4 7 150 50 50 2 41 CS 30
120 3" CRUDE OIL LV 0476B 4"-PT-20-0824-AC01 3"-PL-20-0379A-AC0117039-ND-P-DW-0203-17 TO 17039-ND-P-DW-
0203-10- - 2 3 150 50 50 2 41 CS 30
121 3" CRUDE OIL 4"-PT-20-03764B-AC01 3"-PL-20-0379A-AC01 BYPASS LINE OF LV 0476B 17039-ND-P-DW-0203-17 - - 1 2 150 50 50 2 41 CS 30
122 4" CRUDE OIL N4 NOZZLE OF ND-HBG-B-1030 N1 NOZZLE HBG-B-1040 4"-PT-20-0377B-AC0117039-ND-P-DW-0203-17 TO 17039-ND-P-DW-
0203-18- - 3 10 150 50 50 2 41 CS 30 - - - - -
123 6" CRUDE OIL N2 NOZZLE OF ND-HBG-1040 N1 NOZZLE OF ND-MBD-B-1050 6"-PT-20-0384B-AC0117039-ND-P-DW-0203-19 TO 17039-ND-P-DW-
0203-19- - 2 7 150 50 50 2 41 CS 30 - - - - -
124 - CRUDE OIL 20-BL-1281B 20-BL-1283B PDIT3605B 17039-ND-P-DW-0203-18 - - 0 2 250 50 50 2 41 CS 30 - - - - -
125 - CRUDE OIL 20-BL-1069B 20-BL-1070B LG0476 17039-ND-P-DW-0203-19 - - 0 2 150 50 50 2 41 CS 30 - - - - -
126 - CRUDE OIL 20-BL-1074B 20-BL-1073B LIT0416 17039-ND-P-DW-0203-19 - - 0 2 150 50 50 2 41 CS 30 - - - - -
127 4" CRUDE OIL N2 NOZZLE OF ND-MBM-B-1060 4"-PL-20-0452-AC01 4"-PL-20-0360B-AC01 17039-ND-P-DW-0203-19 - - 0 1 150 50 50 2 41 CS 30 - - - - -
128 4" CRUDE OIL 4"-PL-20-0360B-AC01 N1 NOZZLE OF ND-PBA-B-1070A 4"-PL-20-0451B-AC0117039-ND-P-DW-0203-19 TO 17039-ND-P-DW-
0203-20- - 1 7 150 50 50 2 41 CS 30 - - - - -
129 3" CRUDE OIL N2 NOZZLE OF ND-PBA-B-1070A 3"-PL-20-0457B-AC01 3"-PL-20-0454B-AC01 17039-ND-P-DW-0203-20 - - 1 6 150 50 50 2 41 CS 30 - - - - -
130 4" CRUDE OIL 4"-PL-20-0360B-AC01 N1 NOZZLE OF ND-PBA-B-1070B 3"-PL-20-0453B-AC0117039-ND-P-DW-0203-19 TO 17039-ND-P-DW-
0203-20- - 1 7 150 50 50 2 41 CS 30 - - - - -
131 3" CRUDE OIL N2 NOZZLE OF ND-PBA-B-1070B 3"-PL-20-0454B-AC01 3"-PL-20-0457B-AC0117039-ND-P-DW-0203-20 TO 17039-ND-P-DW-
0203-17- - 1 6 150 50 50 2 41 CS 30 - - - - -
132 4" CRUDE OIL 4"-PT-13-0157-FC01 N1 NOZZLE OF ND-MBD-1110 4"-PT-13-0196-FC0117039-ND-P-DW-0202-18 TO 17039-ND-P-DW-
0202-19- - 1 3 108 50 50 2 41 CS 30 - - - - -
133 6" CRUDE OIL N3 NOZZLE OF ND-MBD-1110 LV 0216 6"-PL-13-0204-DC01 17039-ND-P-DW-0202-19 - - 2 12 108 50 50 2 41 CS 30 - - - - -
134 2" CRUDE OIL LV 0216 TO HP INLET HEATER A TRAIN A 2"-PT-13-0205A-FC0117039-ND-P-DW-0202-19 TO 17039-ND-P-DW-
0202-21- - 7 15 108 50 50 2 41 CS 30 - - - - -
135 2" CRUDE OIL LV 0216 TO CRUDE OIL TEST TANK 2"-PT-13-0205B-FC0117039-ND-P-DW-0202-19 TO 17039-ND-P-DW-
0203-01- - 2 8 108 50 50 2 41 CS 30 - - - - -
136 2" CRUDE OIL 2"-PT-13-0205-FC01 12"-PT-13-0182-FC01 2"-PT-13-0206-FC0117039-ND-P-DW-0202-19 TO 17039-ND-P-DW-
0202-03- - 4 10 108 50 50 2 41 CS 30 - - - - -
137 4" CRUDE OIL WELL FLUID FROM HP WELL-1 TO TEST HEADER 4"-PT-13-0001-FC0117039-ND-P-DW-0202-05 TO 17039-ND-P-DW-
0202-18- - 2 7 108 50 50 2 41 CS 30 - - - - -
138 4" CRUDE OIL WELL FLUID FROM HP WELL-2 TO TEST HEADER 4"-PT-13-0002-FC0117039-ND-P-DW-0202-05 TO 17039-ND-P-DW-
0202-18- - 2 7 108 50 50 2 41 CS 30 - - - - -
139 4" CRUDE OIL WELL FLUID FROM HP WELL-3 TO TEST HEADER 4"-PT-13-0003-FC0117039-ND-P-DW-0202-05 TO 17039-ND-P-DW-
0202-18- - 2 7 108 50 50 2 41 CS 30 - - - - -
140 4" CRUDE OIL WELL FLUID FROM HP WELL-4 10"-PT-13-0158-FC01 4"-PT-13-0014-FC0117039-ND-P-DW-0202-06 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
141 4" CRUDE OIL WELL FLUID FROM HP WELL-5 10"-PT-13-0158-FC01 4"-PT-13-0015-FC0117039-ND-P-DW-0202-06 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
142 4" CRUDE OIL WELL FLUID FROM HP WELL-6 10"-PT-13-0158-FC01 4"-PT-13-0016-FC0117039-ND-P-DW-0202-06 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
143 4" CRUDE OIL WELL FLUID FROM LP WELL -13 12"-PT-13-0184-FC01 4"-PT-13-0969-FC0117039-ND-P-DW-0202-14 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
144 4" CRUDE OIL WELL FLUID FROM LP WELL -14 12"-PT-13-0184-FC01 4"-PT-13-0970-FC0117039-ND-P-DW-0202-14 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
145 4" CRUDE OIL WELL FLUID FROM LP WELL -15 12"-PT-13-0184-FC01 4"-PT-13-0971-FC0117039-ND-P-DW-0202-14 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
146 2" CRUDE OIL 4"-PT-13-0969-FC01 13-GL-0357 2"-PT-13-0977-FC01 17039-ND-P-DW-0202-14 - - 2 4 108 50 50 2 41 CS 30 - - - - -
147 2" CRUDE OIL 4"-PT-13-0970-FC01 13-GL-0322 2"-PT-13-0976-FC01 17039-ND-P-DW-0202-14 - - 2 4 108 50 50 2 41 CS 30 - - - - -
148 2" CRUDE OIL 4"-PT-13-0971-FC01 13-GL-0355 2"-PT-13-0975-FC01 17039-ND-P-DW-0202-14 - - 2 4 108 50 50 2 41 CS 30 - - - - -
149 4" CRUDE OIL WELL FLUID FROM LP WELL -10 12"-PT-13-0184-FC01 4"-PT-13-0134-FC0117039-ND-P-DW-0202-13 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
150 4" CRUDE OIL WELL FLUID FROM LP WELL -11 12"-PT-13-0184-FC01 4"-PT-13-0961-FC0117039-ND-P-DW-0202-13 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
151 4" CRUDE OIL WELL FLUID FROM LP WELL -12 12"-PT-13-0184-FC01 4"-PT-13-0965-FC0117039-ND-P-DW-0202-13 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
152 2" CRUDE OIL 4"-PT-13-0134-FC01 13-GL-0357 2"-PT-13-0136-FC01 17039-ND-P-DW-0202-13 - - 2 4 108 50 50 2 41 CS 30 - - - - -
153 2" CRUDE OIL 4"-PT-13-0961-FC01 13-GL-0322 2"-PT-13-0964-FC01 17039-ND-P-DW-0202-13 - - 2 4 108 50 50 2 41 CS 30 - - - - -
154 2" CRUDE OIL 4"-PT-13-0965-FC01 13-GL-0355 2"-PT-13-0967-FC01 17039-ND-P-DW-0202-13 - - 2 4 108 50 50 2 41 CS 30 - - - - -
155 4" CRUDE OIL WELL FLUID FROM LP WELL -7 12"-PT-13-0184-FC01 4"-PT-13-0127-FC0117039-ND-P-DW-0202-12 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
156 4" CRUDE OIL WELL FLUID FROM LP WELL -8 12"-PT-13-0184-FC01 4"-PT-13-0128-FC0117039-ND-P-DW-0202-12 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
157 4" CRUDE OIL WELL FLUID FROM LP WELL -9 12"-PT-13-0184-FC01 4"-PT-13-0133-FC0117039-ND-P-DW-0202-12 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
Page 4 of 6
MIN MAX
Temp. °C Temp. °C
(NOTE-4)
HEAT TRACING LINE LIST
PIPING /
EQUIPMENT
DIA(inch)
PIPE
MATERIAL
HEAT TRACING PIPE CABLE
LENGTH (M)
NO. OF CRK.
REQ
MATERIAL
SL.NO
INSULATION
THICKNESS. (mm)
MAINTAINED
Temp. °C
No's FLANGES
INSULATION VALVE / FLANGE Q'TY
PIPE / EQUIPMENT
LENGTH (M)
OPERATING
Temp. °C DESIGN TEMP. °C
No's VALVES
(NOTE-4)
P&ID NUMBERSERVICE LINE No. / EQUIPMENT FROM LINE No. /
EQUIPMENT TO LINE No. / EQUIPMENT
AMBIENT Temp. °C
TRAID
CABLE
POWER CABLE
LENGTH
POWER CABLE
SIZE
158 2" CRUDE OIL 4"-PT-13-0127-FC01 13-GL-0305 2"-PT-13-0131-FC01 17039-ND-P-DW-0202-12 - - 2 4 109 50 50 2 41 CS 30 - - - - -
159 2" CRUDE OIL 4"-PT-13-0128-FC01 13-GL-0322 2"-PT-13-0132-FC01 17039-ND-P-DW-0202-12 - - 2 4 110 50 50 2 41 CS 30 - - - - -
160 2" CRUDE OIL 4"-PT-13-0133-FC01 13-GL-0326 2"-PT-13-0135-FC01 17039-ND-P-DW-0202-12 - - 2 4 108 50 50 2 41 CS 30 - - - - -
161 4" CRUDE OIL WELL FLUID FROM LP WELL -4 12"-PT-13-0184-FC01 4"-PT-13-0118-FC0117039-ND-P-DW-0202-11 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
162 4" CRUDE OIL WELL FLUID FROM LP WELL -5 12"-PT-13-0184-FC01 4"-PT-13-0119-FC0117039-ND-P-DW-0202-11 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
163 4" CRUDE OIL WELL FLUID FROM LP WELL -6 12"-PT-13-0184-FC01 4"-PT-13-0120-FC0117039-ND-P-DW-0202-11 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
164 2" CRUDE OIL 4"-PT-13-0118-FC01 13-GL-0357 2"-PT-12-0121-FC01 17039-ND-P-DW-0202-11 - - 2 4 108 50 50 2 41 CS 30 - - - - -
165 2" CRUDE OIL 4"-PT-13-0119-FC01 13-GL-0322 2"-PT-12-0122-FC01 17039-ND-P-DW-0202-11 - - 2 4 108 50 50 2 41 CS 30 - - - - -
166 2" CRUDE OIL 4"-PT-13-0120-FC01 13-GL-0355 2"-PT-12-0123-FC01 17039-ND-P-DW-0202-11 - - 2 4 108 50 50 2 41 CS 30 - - - - -
167 4" CRUDE OIL WELL FLUID FROM LP WELL -1 12"-PT-13-0184-FC01 4"-PT-13-0109-FC0117039-ND-P-DW-0202-10 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
168 4" CRUDE OIL WELL FLUID FROM LP WELL -2 12"-PT-13-0184-FC01 4"-PT-13-0110-FC0117039-ND-P-DW-0202-10 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
169 4" CRUDE OIL WELL FLUID FROM LP WELL -3 12"-PT-13-0184-FC01 4"-PT-13-0111-FC0117039-ND-P-DW-0202-10 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
170 2" CRUDE OIL 4"-PT-13-0109-FC01 13-GL-0305 2"-PT-13-0112-FC01 17039-ND-P-DW-0202-10 - - 2 4 108 50 50 2 41 CS 30 - - - - -
171 2" CRUDE OIL 4"-PT-13-0110-FC01 13-GL-0322 2"-PT-13-0113-FC01 17039-ND-P-DW-0202-10 - - 2 4 108 50 50 2 41 CS 30 - - - - -
172 2" CRUDE OIL 4"-PT-13-0114-FC01 13-GL-0326 2"-PT-13-0114-FC01 17039-ND-P-DW-0202-10 - - 2 4 108 50 50 2 41 CS 30 - - - - -
173 4" CRUDE OIL WELL FLUID FROM HP WELL -13 10'-PT-0158-FC01 4"-PT-13-0053-FC0117039-ND-P-DW-0202-09 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
174 4" CRUDE OIL WELL FLUID FROM HP WELL -14 10'-PT-0158-FC01 4"-PT-13-0054-FC0117039-ND-P-DW-0202-09 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
175 4" CRUDE OIL WELL FLUID FROM HP WELL -15 10'-PT-0158-FC01 4"-PT-13-0120A-FC0117039-ND-P-DW-0202-09 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
176 4" CRUDE OIL 4"-PT-13-0053-FC01 10"-PT-13-0068-FC01 4"-PT-13-0055-FC0117039-ND-P-DW-0202-09 TO 17039-ND-P-DW-
0202-18- - 5 8 108 50 50 2 41 CS 30 - - - - -
177 4" CRUDE OIL 4"-PT-13-0002-FC01 10"-PT-13-0068-FC01 4"-PT-13-0056-FC0117039-ND-P-DW-0202-09 TO 17039-ND-P-DW-
0202-18- - 5 8 108 50 50 2 41 CS 30 - - - - -
178 4" CRUDE OIL 4"-PT-13-0120-FC01 10"-PT-13-0068-FC01 4"-PT-13-0122-FC0117039-ND-P-DW-0202-09 TO 17039-ND-P-DW-
0202-18- - 5 8 108 50 50 2 41 CS 30 - - - - -
179 2" CRUDE OIL 4"-PT-13-0053-FC01 13-GL-0020 2"-PT-13-0061-FC01 17039-ND-P-DW-0202-09 - - 2 5 108 50 50 2 41 CS 30 - - - - -
180 2" CRUDE OIL 4"-PT-13-0002-FC01 13-GL-0022 2"-PT-13-0012-FC01 17039-ND-P-DW-0202-09 - - 2 5 108 50 50 2 41 CS 30 - - - - -
181 2" CRUDE OIL 4"-PT-13-0120-FC01 13-GL-0024 2"-PT-13-0123-FC01 17039-ND-P-DW-0202-09 - - 2 5 108 50 50 2 41 CS 30 - - - - -
182 2" CRUDE OIL 4"-PT-13-0055-FC01 13-GL-8015 2"-PT-13-7778-FC01 17039-ND-P-DW-0202-09 - - 2 5 108 50 50 2 41 CS 30 - - - - -
183 2" CRUDE OIL 4"-PT-13-0056-FC01 13-GL-8020 2"-PT-13-7782-FC01 17039-ND-P-DW-0202-09 - - 2 5 108 50 50 2 41 CS 30 - - - - -
184 4" CRUDE OIL WELL FLUID FROM HP WELL -10 10'-PT-0158-FC01 4"-PT-13-0040-FC0117039-ND-P-DW-0202-08 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
185 4" CRUDE OIL WELL FLUID FROM HP WELL -11 10'-PT-0158-FC01 4"-PT-13-0041-FC0117039-ND-P-DW-0202-08 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
186 4" CRUDE OIL WELL FLUID FROM HP WELL -12 10'-PT-0158-FC01 4"-PT-13-0042-FC0117039-ND-P-DW-0202-08 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
187 2" CRUDE OIL 4"-PT-13-0040-FC01 13-GL-0130 2"-PT-13-0046-FC01 17039-ND-P-DW-0202-08 - - 2 5 108 50 50 2 41 CS 30 - - - - -
188 2" CRUDE OIL 4"-PT-13-0041-FC01 13-GL-0149 2"-PT-13-0047-FC01 17039-ND-P-DW-0202-08 - - 2 5 108 50 50 2 41 CS 30 - - - - -
189 2" CRUDE OIL 4"-PT-13-0042-FC01 13-GL-0024 2"-PT-13-0048-FC01 17039-ND-P-DW-0202-08 - - 2 5 108 50 50 2 41 CS 30 - - - - -
190 4" CRUDE OIL 4"-PT-13-0040-FC01 10"-PT-13-0068-FC01 4"-PT-13-0043-FC0117039-ND-P-DW-0202-08 TO 17039-ND-P-DW-
0202-09- - 1 2 108 50 50 2 41 CS 30 - - - - -
191 4" CRUDE OIL 4"-PT-13-0041-FC01 10"-PT-13-0068-FC01 4"-PT-13-0044-FC0117039-ND-P-DW-0202-08 TO 17039-ND-P-DW-
0202-09- - 2 4 108 50 50 2 41 CS 30 - - - - -
192 4" CRUDE OIL 4"-PT-13-0042-FC01 10"-PT-13-0068-FC01 4"-PT-13-0045-FC0117039-ND-P-DW-0202-08 TO 17039-ND-P-DW-
0202-09- - 2 4 108 50 50 2 41 CS 30 - - - - -
193 2" CRUDE OIL 4"-PT-13-0043-FC01 13-GL-8246 2"-PT-13-7758-FC01 17039-ND-P-DW-0202-08 - - 2 5 108 50 50 2 41 CS 30 - - - - -
194 2" CRUDE OIL 4"-PT-13-0044-FC01 13-GL-8279 2"-PT-13-7770-FC01 17039-ND-P-DW-0202-08 - - 2 5 108 50 50 2 41 CS 30 - - - - -
195 4" CRUDE OIL WELL FLUID FROM HP WELL -7 10"-PT-13-0158-FC01 4"-PT-13-0027-FC0117039-ND-P-DW-0202-07 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
196 4" CRUDE OIL WELL FLUID FROM HP WELL -8 10"-PT-13-0158-FC01 4"-PT-13-0028-FC0117039-ND-P-DW-0202-07 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
197 4" CRUDE OIL WELL FLUID FROM HP WELL -9 10"-PT-13-0158-FC01 4"-PT-13-0029-FC0117039-ND-P-DW-0202-07 TO 17039-ND-P-DW-
0202-18- - 3 10 108 50 50 2 41 CS 30 - - - - -
Page 5 of 6
MIN MAX
Temp. °C Temp. °C
(NOTE-4)
HEAT TRACING LINE LIST
PIPING /
EQUIPMENT
DIA(inch)
PIPE
MATERIAL
HEAT TRACING PIPE CABLE
LENGTH (M)
NO. OF CRK.
REQ
MATERIAL
SL.NO
INSULATION
THICKNESS. (mm)
MAINTAINED
Temp. °C
No's FLANGES
INSULATION VALVE / FLANGE Q'TY
PIPE / EQUIPMENT
LENGTH (M)
OPERATING
Temp. °C DESIGN TEMP. °C
No's VALVES
(NOTE-4)
P&ID NUMBERSERVICE LINE No. / EQUIPMENT FROM LINE No. /
EQUIPMENT TO LINE No. / EQUIPMENT
AMBIENT Temp. °C
TRAID
CABLE
POWER CABLE
LENGTH
POWER CABLE
SIZE
198 2" CRUDE OIL 4"-PT-13-0027-FC01 13-GL-0090 2"-PT-13-0034-FC01 17039-ND-P-DW-0202-07 - - 2 5 108 50 50 2 41 CS 30 - - - - -
199 2" CRUDE OIL 4"-PT-13-0028-FC01 13-GL-7936 2"-PT-13-0035-FC01 17039-ND-P-DW-0202-07 - - 2 5 108 50 50 2 41 CS 30 - - - - -
200 2" CRUDE OIL 4"-PT-13-0029-FC01 13-GL-0119 2"-PT-13-0036-FC01 17039-ND-P-DW-0202-07 - - 2 5 108 50 50 2 41 CS 30 - - - - -
201 4" CRUDE OIL 4"-PT-13-0027-FC01 10"-PT-13-0068-FC01 4"-PT-13-0030-FC0117039-ND-P-DW-0202-07 TO 17039-ND-P-DW-
0202-08- - 2 4 108 50 50 2 41 CS 30 - - - - -
202 4" CRUDE OIL 4"-PT-13-0028-FC01 10"-PT-13-0068-FC01 4"-PT-13-0031-FC0117039-ND-P-DW-0202-07 TO 17039-ND-P-DW-
0202-08- - 2 4 108 50 50 2 41 CS 30 - - - - -
203 4" CRUDE OIL 4"-PT-13-0029-FC01 10"-PT-13-0068-FC01 4"-PT-13-0032-FC0117039-ND-P-DW-0202-07 TO 17039-ND-P-DW-
0202-08- - 2 4 108 50 50 2 41 CS 30 - - - - -
204 2" CRUDE OIL 4"-PT-13-0030-FC01 13-GL-8211 2"-PT-13-7746-FC01 17039-ND-P-DW-0202-07 - - 2 5 108 50 50 2 41 CS 30 - - - - -
205 2" CRUDE OIL 4"-PT-13-0031-FC01 13-GL-8222 2"-PT-13-7750-FC01 17039-ND-P-DW-0202-07 - - 2 5 108 50 50 2 41 CS 30 - - - - -
206 2" CRUDE OIL 4"-PT-13-0014-FC01 13-GL-0050 2"-PT-13-8602-FC01 17039-ND-P-DW-0202-07 - - 2 5 108 50 50 2 41 CS 30 - - - - -
207 2" CRUDE OIL 4"-PT-13-0015-FC01 13-GL-0066 2"-PT-13-8603-FC01 17039-ND-P-DW-0202-06 - - 2 5 108 50 50 2 41 CS 30 - - - - -
208 2" CRUDE OIL 4"-PT-13-0016-FC01 13-GL-0077 2"-PT-13-0022-FC01 17039-ND-P-DW-0202-06 - - 2 5 108 50 50 2 41 CS 30 - - - - -
209 4" CRUDE OIL 4"-PT-13-0014-FC01 10"-PT-13-0068-FC01 4"-PT-13-0017-FC0117039-ND-P-DW-0202-06 TO 17039-ND-P-DW-
0202-15- - 2 4 108 50 50 2 41 CS 30 - - - - -
210 4" CRUDE OIL 4"-PT-13-0015-FC01 10"-PT-13-0068-FC01 4"-PT-13-8604-FC0117039-ND-P-DW-0202-06 TO 17039-ND-P-DW-
0202-15- - 2 4 108 50 50 2 41 CS 30 - - - - -
211 4" CRUDE OIL 4"-PT-13-0016-FC01 10"-PT-13-0068-FC01 4"-PT-13-8605-FC0117039-ND-P-DW-0202-06 TO 17039-ND-P-DW-
0202-15- - 2 4 108 50 50 2 41 CS 30 - - - - -
212 2" CRUDE OIL 4"-PT-13-0017-FC01 13-GL-8172 2"-PT-13-7733-FC01 17039-ND-P-DW-0202-06 - - 2 5 108 50 50 2 41 CS 30 - - - - -
213 2" CRUDE OIL 4"-PT-13-0016-FC01 13-GL-8182 2"-PT-13-7738-FC01 17039-ND-P-DW-0202-06 - - 2 5 108 50 50 2 41 CS 30 - - - - -
214 2" CRUDE OILWELL FLUID FROM TEST
SEPEARTORN1 NOZZLE OF ND-BBJ-1111 2"-PT-13-0205C-FC01 17039-ND-P-DW-0202-20 - - 0 1 108 50 50 2 41 CS 30 - - - - -
215 2" CRUDE OIL
MINIMUM RECIRCULATION LINE
FROM TEST TANK TRANSFER
PUMP
N9 NOZZLE OF ND-BBJ-1111 2"-PL-20-1387-AC01 17039-ND-P-DW-0202-20 - - 2 5 108 50 50 2 41 CS 30 - - - - -
216 4" CRUDE OIL N9 NOZZLE OF ND-BBJ-1111CRUDE OIL TO TEST TANK
TRANSFER PUMP4"-PL-44-1380-AC01 17039-ND-P-DW-0202-20 - - 0 1 108 50 50 2 41 CS 30 - - - - -
217 12" CRUDE OIL 12"-PT-13-0184-FC01 WELL FLUID TO INLET HEATER-B 12"-PT-13-0182-FC0117039-ND-P-DW-0202-18 TO 17039-ND-P-DW-
0203-03- - 10 4 108 50 50 2 41 CS 30 - - - - -
Page 6 of 6
A 22-Nov-18 PGB DS/AD MSR
REV. DATE BY CHECKED APPROVED
DOCUMENT TITLE : DATA SHEET FOR CAPACITOR BANK
CREATION OF SURFACE PRODUCTION FACILITY (OCS & GGS) AT NADUA AND EAST KHAGORIJAN, ASSAM
PROJECT DOCUMENTS ARE CONTROLLED DOCUMENTS.
REVISIONS ARE DENOTED Δ IN RIGHT HAND MARGIN
DOCUMENT NO : 17039-EK-E-DS-9011
ISSUED FOR REVIEW
DESCRIPTION
CLIENT:
OIL INDIA LIMITED
CLIENT REF:
IFB No: CPI4540P18
EPMC:
KAVIN ENGINEERING AND SERVICES PRIVATE LIMITED
KAVIN REF:
KIP-17039
Annexure- 6
REV.
2 of 8 A
REV. NO. BY DATE CHECKED DATE APPROV. DATE
A PGB 22-Nov-2018 DS/AD 22-Nov-2018 MSR 22-Nov-2018
ORG. ORG. DATE
PGB 8-Oct-2018
REV. NO.
A
DOCUMENT TITLE: ITEM/TAG NO.: DATASHEET NO.:
DATA SHEET FOR CAPACITOR BANK - 17039-EK-E-DS-9011
PROJECT DESCRIPTION:
OIL INDIA LIMITED - - 17039-EK-E-DB-9001
EPCM DESCRIPTION
PROJECT NO.: SHEET NO.:
CREATION OF SURFACE PRODUCTION FACILITY (OCS & GGS) AT NADUA AND EAST
KHAGORIJAN, ASSAMKIP-17039
CLIENT NAME: CLIENT DOCUMENT NO.: REQUISITION NO.: SPECIFICATION NO.:
REVISION RECOED SHEET
REVISION DESCRIPTION LIST OF PAGES OF MODIFIED SECTIONS, IF ANY
ISSUED FOR REVIEW
KAVIN ISSUED FOR REVIEW
PURCHASE ORDER NO.:
-
REV.
3 of 8 A
Rev. No. By Date Checked Date Approved Date
A PGB 22-Nov-2018 DS/AD 22-Nov-2018 MSR 22-Nov-2018
ORG. ORG. DATE
PGB 8-Oct-2018
PAGE NO. A
1 22-Nov-2018
2 22-Nov-2018
3 22-Nov-2018
4 22-Nov-2018
5 - 8 22-Nov-2018
DOCUMENT TITLE: ITEM/TAG NO.: DATASHEET NO.:
DATA SHEET FOR CAPACITOR BANK - 17039-EK-E-DS-9011
PROJECT DESCRIPTION:
OIL INDIA LIMITED - - 17039-EK-E-DB-9001
EPCM Description
PROJECT NO.: SHEET NO.:
CREATION OF SURFACE PRODUCTION FACILITY (OCS & GGS) AT NADUA AND EAST
KHAGORIJAN, ASSAMKIP-17039
CLIENT NAME: CLIENT DOCUMENT NO.: REQUISITION NO.: SPECIFICATION NO.:
REVISION INDEX SHEET
PAGE DESCRIPTION
Cover Sheet
KAVIN ISSUED FOR REVIEW
PURCHASE ORDER NO.:
-
Capacitor Bank Data Sheet
Revision Record Sheet
Revision Index Sheet
Notes sheet
REV.
4 of 8 A
Rev. No. By Date Checked Date Approved Date
A PGB 8-Oct-18 DS/AD 8-Oct-18 MSR 8-Oct-18
ORG. ORG. DATE
PGB 8-Oct-18
8. A continuously rated voltage transformer shall be provided for voltage monitoring and unbalance protection with primary connected in star and two
secondary windings connected in star and open delta connection respectively.
10. Manufacturer can submit certificates that the equipment complies with all type tests as prescribed by IEC/IS Standard specifying the test requirements for
that equipment. Type test performed beyond 5 years are not acceptable. In case type test certificate for the equipment as required above is not available, the
VENDOR shall perform type test free of charge to prove the design to the satisfaction of the Company
11. Capacitor shall comply with the general safety regulations for power installation prescribed in the relevant standard. Capacitor units shall have overload
capacity as per IS 13925
12. Capacitor unit shall be suitable for operation at R.M.S voltage between terminals not exceeding 1.1 times of the rated voltage,elcuding transients.
HOLD:
1. Capacitor bank rating is preliminary only, same shall be confirmed later.
4. The automatic power factor relay shall provide output signals in multiple stages to enable achieve the set power factor at all possible loading conditions.
5. The control panel shall have digital display of the set and achieved power factors and analog display of current in all the three phases of the line to the
capacitor bank.
6. Capacitor banks shall comprise an appropriate number of basic single-phase units (minimum 4 nos. basic units in parallel per phase), which shall be
connected in star formation
7. Dielectric used in the capacitors shall be all polypropylene or mixed dielectric with low watt loss
VENDOR NAME Description
3. The selected basic unit size shall be 25kVAr or any lower rating and the same shall be justified by design calculation.
The built-up unit sizes shall be multiplication of the single unit i.e. 25kVAr, 50kVAr and 100kVAr. The total capacitor bank shall comprise a number of the built-
up units of different ratings.
KAVIN ISSUED FOR REVIEW
PURCHASE ORDER NO.:
-
NOTES SHEETS:
1. VTA - Vendor to advise, VTC- Vendor to confirm
2. TBC - To be Confirmed
REQUISITION NO.: SPECIFICATION NO.:
OIL INDIA LIMITED - - 17039-EK-E-DB-9001
DOCUMENT TITLE: ITEM/TAG NO.: DATASHEET NO.:
DATA SHEET FOR CAPACITOR BANK - 17039-EK-E-DS-9011
PROJECT DESCRIPTION: PROJECT NO. SHEET NO.:
CREATION OF SURFACE PRODUCTION FACILITY (OCS & GGS) AT NADUA AND EAST
KHAGORIJAN, ASSAMKIP-17039
CLIENT NAME CLIENT DOC. NO:
REFERENCE DOCUMENTS:
1. 17039-EK-E-DB-9001 - Electrical Design Basis
5 of 8
1 No
DATA SHEET FOR CAPACITOR BANK
SPECIFICATION REF.: 17039-EK-E-DB-9001 MANUFACTURER: -
DOCUMENT No.:
SERVICE:
TAG Nos. : -
PAGE No.:
No. OF UNITS:
17039-EK-E-DS-9011
CAPACITOR BANK
ENVIRONMENTAL CONDITIONS
Project location : ASSAM, INDIA System voltage : 415V +6/-10%
POWER SUPPLY SYSTEM
Relative humidity (Min/Max) 36/ 98%
Hazardous area classification : (if
applicable)Safe Area
Sl.No.
50kA, 1Sec
50Hz ±3%
Resistance Earthed
Site Ambient temperature : 2° C/ 41°C System frequency :
Ambient temperature for design of
electrical equipment :45°C System earthing :
Atmosphere : Corrosive & Dust Environment System fault level :
PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE Rev. No.
Altitude 121m above MSL
4 Enclosure details:
1 Rating of APFC Panel kVAr 850
2 Rated Voltage of the Panel V 415V +6/-10%
5.1 Material CRCA Sheet Steel
3 Frequency Hz 50Hz ±3%
5.3 Protection IP 42
5 ConstructionFree Standing, Floor mounted,
Compartmentalized Design.
5.5 Cable Entry TBC
5.2 Thickness of Sheet SteelFrames and doors shall not less than 2
mm
6 Bus bar Detail:
5.4 Dimensions VTA
6.2 Cross Section VTA
5.6 Painting RAL 7032 as per IS-5
7 Capacitors:
6.1 Material Copper
7.2 No.of Steps 12
6.3 Bus bar support VTA
7.1 Type APP
7.3 Configuration VTC
MCCB with Capacitor Duty Contactor
3 Standard Followed IS: 13585 (Part 1),IEC 60931
4 PurposePower Factor Improvement & Harmonic
Filtering
5 Location Indoor
Technical Details of APFC Panel
8
8.1
8.2
1
2
Cubical Details:
Steps Outgoing
APFC Relays
Manufacturer's Name
Maker's Type Designation
Technical Details of Capacitor Bank
Micro processor based relay
VTA
All polypropylene
Sl.No.
6.0
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.8.1
6.8.2
7
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.7.1
7.8
7.8.1
7.8.2
7.8.3
7.9
7.9.1
7.10
1
2
3
4
5
6
7
8
9
10
11
12
13
DATA SHEET FOR CAPACITOR BANK
SPECIFICATION REF.: 17039-EK-E-DB-9001 MANUFACTURER: -
TAG Nos. : -
DOCUMENT No.: 17039-EK-E-DS-9011 PAGE No.: 6 of 8
SERVICE: CAPACITOR BANK No. OF UNITS: 1 No
i) Lengthwise VTA
ii) Cross wise VTA
a) Nominal thickness of poly propylene VTA
b) Tensile strength of poly propylene
Impulse withstand voltage
Physical and electrical properties of capacitor
W/kVAr VTA
Temperature rise under max. voltage °C VTA
°C 50°CLimiting ambient temperature
Watt loss (maximum) per phase
V for Sec VTA
kV VTA
VTA
KVAr (at rated voltage and frequency of each unit) kVAr VTA
V VTA
Delta/Star Star
No. of phases and No. of terminals in each unit
Connection of capacitor units
Maximum permissible over voltage and duration corresponding to
the same
Maximum permissible operative over voltage (continuous)
Rated frequency Hz
V 525
Type & make of Capacitors
Rated voltage of each capacitor units
Technical Details of Individual Capacitor Unit
VTA
Creepage distances (mm/KV) mm VTA
50
Voltage V VTA
Directly connected internal discharge resistor Yes/No VTA
Current A VTA
Output kVAr VTA
Discharge device to discharge capacitor to 50Vor less in 300 secs
after disconnection from supply
Losses (watts / kVAr) W/kVAr VTA
Permissible load
Insulation level
Power Frequency Withstand Voltage KV (RMS) kV VTA
Unit Protection MCCB + Capacitor duty Contactor
Dielectric type VTA
Rated Voltage (V) V 525
Rated Current (A) A VTA
Capacitor Unit
Rated Output (kVAr) kVAr VTA
Incoming VTA
Outgoing VTA
Type of mounting VTA
Terminal Arrangement
Three
Impulse withstand Voltage (PEAK) Kv VTA
Nos. VTA
No of Phases
Type of Connection
No of Units per bank
Delta/Star Star
Rated Output (Effective) kVAr
PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
Rated Voltage (Effective) V 525
Rated Voltage V 525
Rev. No.
Capacitor Bank
Rated Output (Installed) kVAr VTA
VTA
DATA SHEET FOR CAPACITOR BANK
SPECIFICATION REF.: 17039-EK-E-DB-9001 MANUFACTURER: -
TAG Nos. : -
DOCUMENT No.: 17039-EK-E-DS-9011 PAGE No.: 7 of 8
SERVICE: CAPACITOR BANK No. OF UNITS: 1 No
Rated short time current and specified duration kA/s VTA
Number of phases 3
Total weight / weight of coil and assembly unit Kg VTA
Dimensions (Overall) mm VTA
Compensation percent of series reactors % 7
Rated frequency Hz 50
Rated capacity / inductance kVAr / mH VTA
Rated current and voltage A &V VTA
Insulation Level kV VTA
Type and Make VTA
21Whether tcc curve is attached and if so, how it is coordinated
with capacitor bank protection.Required
Technical Details of Series Reactor
20 Maximum ambient temperature capacitor can withstand °C VTA
19Percentage of over voltage due to failure of each bank for
different ratingsVTA
18 Voltage and current rating of capacitor bushing ( of units)
%
VTA
17 Whether the neutral capacitor bank floated or earthed
V & A
VTA
e) Output of capacitor if one element fails, 2 elements fails
etc.kVAr VTA
d) Units in parallel per series group Nos. VTA
c) bank capacitance µF VTA
b) Capacitance of each phase of each star µF VTA
a) Rated output of capacitor unit and voltage V VTA
16 Capacitor bank output
15Maximum difference of capacitance between capacitor units
in bankµF VTA
d) Minimum and maximum voltage and PF setting V & % VTA
c) Schematic drawing Yes/No Required
b) Earth fault Required
a) Whether timer required for switching operation Required
14 Protection schemes for capacitor bank (recommended)
e) Dielectric breakdown voltage kV VTA
ii) Crosswise VTA
i) Lengthwise VTA
d) Shrinkage
ii) Crosswise VTA
i) Lengthwise VTA
VENDOR'S RESPONSE Rev. No.Sl.No. PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS
c) Percentage elongation
-
DOCUMENT No.: 17039-EK-E-DS-9011 PAGE No.: 8 of 8
SERVICE: CAPACITOR BANK No. OF UNITS: 1 No
DATA SHEET FOR CAPACITOR BANK
SPECIFICATION REF.: 17039-EK-E-DB-9001 MANUFACTURER: -
TAG Nos. :
b) Inrush current Yes
21 Type of Shielding adopted in the reactor VTA
20 Whether reactor designed for
a) Harmonics Yes
18 Maximum system voltage for which reactor is designed V VTA
19 Conforming to IS Required
16 Rated KVAR kVAr VTA
17 Terminal arrangement Top/Sides VTA
14 Winding resistance (cold /hot) Ω VTA
15 Voltage and current rating of reactor bushing V & A VTA
12 Type of cooling VTA
13 Load losses W/kVAr VTA
11 Reactance at rated current mH VTA
VENDOR'S RESPONSE Rev. No.Sl.No. PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS
A 22-Nov-18 PGB DS/AD MSR
REV. DATE BY CHECKED APPROVED
DOCUMENT TITLE : DATA SHEET FOR CAPACITOR BANK
CREATION OF SURFACE PRODUCTION FACILITY (OCS & GGS) AT NADUA AND EAST KHAGORIJAN, ASSAM
PROJECT DOCUMENTS ARE CONTROLLED DOCUMENTS.
REVISIONS ARE DENOTED Δ IN RIGHT HAND MARGIN
DOCUMENT NO : 17039-ND-E-DS-9011
ISSUED FOR REVIEW
DESCRIPTION
CLIENT:
OIL INDIA LIMITED
CLIENT REF:
IFB No: CPI4540P18
EPMC:
KAVIN ENGINEERING AND SERVICES PRIVATE LIMITED
KAVIN REF:
KIP-17039
Annexure- 7
REV.
2 of 8 A
REV. NO. BY DATE CHECKED DATE APPROV. DATE
A PGB 22-Nov-2018 DS/AD 22-Nov-2018 MSR 22-Nov-2018
ORG. ORG. DATE
PGB 8-Oct-2018
REV. NO.
A
DOCUMENT TITLE: ITEM/TAG NO.: DATASHEET NO.:
DATA SHEET FOR CAPACITOR BANK - 17039-ND-E-DS-9011
PROJECT DESCRIPTION:
OIL INDIA LIMITED - - 17039-ND-E-DB-9001
EPCM DESCRIPTION
PROJECT NO.: SHEET NO.:
CREATION OF SURFACE PRODUCTION FACILITY (OCS & GGS) AT NADUA AND EAST
KHAGORIJAN, ASSAMKIP-17039
CLIENT NAME: CLIENT DOCUMENT NO.: REQUISITION NO.: SPECIFICATION NO.:
REVISION RECOED SHEET
REVISION DESCRIPTION LIST OF PAGES OF MODIFIED SECTIONS, IF ANY
ISSUED FOR REVIEW
KAVIN ISSUED FOR REVIEW
PURCHASE ORDER NO.:
-
REV.
3 of 8 A
Rev. No. By Date Checked Date Approved Date
A PGB 22-Nov-2018 DS/AD 22-Nov-2018 MSR 22-Nov-2018
ORG. ORG. DATE
PGB 8-Oct-2018
PAGE NO. A
1 22-Nov-2018
2 22-Nov-2018
3 22-Nov-2018
4 22-Nov-2018
5 - 8 22-Nov-2018
DOCUMENT TITLE: ITEM/TAG NO.: DATASHEET NO.:
DATA SHEET FOR CAPACITOR BANK - 17039-ND-E-DS-9011
PROJECT DESCRIPTION:
OIL INDIA LIMITED - - 17039-ND-E-DB-9001
EPCM Description
PROJECT NO.: SHEET NO.:
CREATION OF SURFACE PRODUCTION FACILITY (OCS & GGS) AT NADUA AND EAST
KHAGORIJAN, ASSAMKIP-17039
CLIENT NAME: CLIENT DOCUMENT NO.: REQUISITION NO.: SPECIFICATION NO.:
REVISION INDEX SHEET
PAGE DESCRIPTION
Cover Sheet
KAVIN ISSUED FOR REVIEW
PURCHASE ORDER NO.:
-
Capacitor Bank Data Sheet
Revision Record Sheet
Revision Index Sheet
Notes sheet
REV.
4 of 8 A
Rev. No. By Date Checked Date Approved Date
A PGB 8-Oct-18 DS/AD 8-Oct-18 MSR 8-Oct-18
ORG. ORG. DATE
PGB 8-Oct-18
8. A continuously rated voltage transformer shall be provided for voltage monitoring and unbalance protection with primary connected in star and two
secondary windings connected in star and open delta connection respectively.
10. Manufacturer can submit certificates that the equipment complies with all type tests as prescribed by IEC/IS Standard specifying the test requirements for
that equipment. Type test performed beyond 5 years are not acceptable. In case type test certificate for the equipment as required above is not available, the
VENDOR shall perform type test free of charge to prove the design to the satisfaction of the Company
11. Capacitor shall comply with the general safety regulations for power installation prescribed in the relevant standard. Capacitor units shall have overload
capacity as per IS 13925
12. Capacitor unit shall be suitable for operation at R.M.S voltage between terminals not exceeding 1.1 times of the rated voltage,elcuding transients.
REFERENCE DOCUMENTS:
1. 17039-ND-E-DB-9001 - Electrical Design Basis
HOLD:
1. Capacitor bank rating is preliminary only, same shall be confirmed later.
4. The automatic power factor relay shall provide output signals in multiple stages to enable achieve the set power factor at all possible loading conditions.
5. The control panel shall have digital display of the set and achieved power factors and analog display of current in all the three phases of the line to the
capacitor bank.
6. Capacitor banks shall comprise an appropriate number of basic single-phase units (minimum 4 nos. basic units in parallel per phase), which shall be
connected in star formation
7. Dielectric used in the capacitors shall be all polypropylene or mixed dielectric with low watt loss
VENDOR NAME Description
3. The selected basic unit size shall be 25kVAr or any lower rating and the same shall be justified by design calculation.
The built-up unit sizes shall be multiplication of the single unit i.e. 25kVAr, 50kVAr and 100kVAr. The total capacitor bank shall comprise a number of the built-
up units of different ratings.
KAVIN ISSUED FOR REVIEW
PURCHASE ORDER NO.:
-
NOTES SHEETS:
1. VTA - Vendor to advise, VTC- Vendor to confirm
2. TBC - To be Confirmed
REQUISITION NO.: SPECIFICATION NO.:
OIL INDIA LIMITED - - 17039-ND-E-DB-9001
DOCUMENT TITLE: ITEM/TAG NO.: DATASHEET NO.:
DATA SHEET FOR CAPACITOR BANK - 17039-ND-E-DS-9011
PROJECT DESCRIPTION: PROJECT NO. SHEET NO.:
CREATION OF SURFACE PRODUCTION FACILITY (OCS & GGS) AT NADUA AND EAST
KHAGORIJAN, ASSAMKIP-17039
CLIENT NAME CLIENT DOC. NO:
5 of 8
1 No
DATA SHEET FOR CAPACITOR BANK
SPECIFICATION REF.: 17039-ND-E-DB-9001 MANUFACTURER: -
DOCUMENT No.:
SERVICE:
TAG Nos. : -
PAGE No.:
No. OF UNITS:
17039-ND-E-DS-9011
CAPACITOR BANK
ENVIRONMENTAL CONDITIONS
Project location : ASSAM, INDIA System voltage : 415V +6/-10%
POWER SUPPLY SYSTEM
Relative humidity (Min/Max) 36/ 98%
Hazardous area classification : (if
applicable)Safe Area
Sl.No.
50kA, 1Sec
50Hz ±3%
Resistance Earthed
Site Ambient temperature : 2° C/ 41°C System frequency :
Ambient temperature for design of
electrical equipment :45°C System earthing :
Atmosphere : Corrosive & Dust Environment System fault level :
PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE Rev. No.
Altitude 121m above MSL
4 Enclosure details:
1 Rating of APFC Panel kVAr 850
2 Rated Voltage of the Panel V 415V +6/-10%
5.1 Material CRCA Sheet Steel
3 Frequency Hz 50Hz ±3%
5.3 Protection IP 42
5 ConstructionFree Standing, Floor mounted,
Compartmentalized Design.
5.5 Cable Entry TBC
5.2 Thickness of Sheet SteelFrames and doors shall not less than 2
mm
6 Bus bar Detail:
5.4 Dimensions VTA
6.2 Cross Section VTA
5.6 Painting RAL 7032 as per IS-5
7 Capacitors:
6.1 Material Copper
7.2 No.of Steps 12
6.3 Bus bar support VTA
7.1 Type APP
7.3 Configuration VTC
MCCB with Capacitor Duty Contactor
3 Standard Followed IS: 13585 (Part 1),IEC 60931
4 PurposePower Factor Improvement & Harmonic
Filtering
5 Location Indoor
Technical Details of APFC Panel
8
8.1
8.2
1
2
Cubical Details:
Steps Outgoing
APFC Relays
Manufacturer's Name
Maker's Type Designation
Technical Details of Capacitor Bank
Micro processor based relay
VTA
All polypropylene
Sl.No.
6.0
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.8.1
6.8.2
7
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.7.1
7.8
7.8.1
7.8.2
7.8.3
7.9
7.9.1
7.10
1
2
3
4
5
6
7
8
9
10
11
12
13
DATA SHEET FOR CAPACITOR BANK
SPECIFICATION REF.: 17039-ND-E-DB-9001 MANUFACTURER: -
TAG Nos. : -
DOCUMENT No.: 17039-ND-E-DS-9011 PAGE No.: 6 of 8
SERVICE: CAPACITOR BANK No. OF UNITS: 1 No
i) Lengthwise VTA
ii) Cross wise VTA
a) Nominal thickness of poly propylene VTA
b) Tensile strength of poly propylene
Impulse withstand voltage
Physical and electrical properties of capacitor
W/kVAr VTA
Temperature rise under max. voltage °C VTA
°C 50°CLimiting ambient temperature
Watt loss (maximum) per phase
V for Sec VTA
kV VTA
VTA
KVAr (at rated voltage and frequency of each unit) kVAr VTA
V VTA
Delta/Star Star
No. of phases and No. of terminals in each unit
Connection of capacitor units
Maximum permissible over voltage and duration corresponding to
the same
Maximum permissible operative over voltage (continuous)
Rated frequency Hz
V 525
Type & make of Capacitors
Rated voltage of each capacitor units
Technical Details of Individual Capacitor Unit
VTA
Creepage distances (mm/KV) mm VTA
50
Voltage V VTA
Directly connected internal discharge resistor Yes/No VTA
Current A VTA
Output kVAr VTA
Discharge device to discharge capacitor to 50Vor less in 300 secs
after disconnection from supply
Losses (watts / kVAr) W/kVAr VTA
Permissible load
Insulation level
Power Frequency Withstand Voltage KV (RMS) kV VTA
Unit Protection MCCB + Capacitor duty Contactor
Dielectric type VTA
Rated Voltage (V) V 525
Rated Current (A) A VTA
Capacitor Unit
Rated Output (kVAr) kVAr VTA
Incoming VTA
Outgoing VTA
Type of mounting VTA
Terminal Arrangement
Three
Impulse withstand Voltage (PEAK) Kv VTA
Nos. VTA
No of Phases
Type of Connection
No of Units per bank
Delta/Star Star
Rated Output (Effective) kVAr
PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
Rated Voltage (Effective) V 525
Rated Voltage V 525
Rev. No.
Capacitor Bank
Rated Output (Installed) kVAr VTA
VTA
DATA SHEET FOR CAPACITOR BANK
SPECIFICATION REF.: 17039-ND-E-DB-9001 MANUFACTURER: -
TAG Nos. : -
DOCUMENT No.: 17039-ND-E-DS-9011 PAGE No.: 7 of 8
SERVICE: CAPACITOR BANK No. OF UNITS: 1 No
Rated short time current and specified duration kA/s VTA
Number of phases 3
Total weight / weight of coil and assembly unit Kg VTA
Dimensions (Overall) mm VTA
Compensation percent of series reactors % 7
Rated frequency Hz 50
Rated capacity / inductance kVAr / mH VTA
Rated current and voltage A &V VTA
Insulation Level kV VTA
Type and Make VTA
21Whether tcc curve is attached and if so, how it is coordinated
with capacitor bank protection.Required
Technical Details of Series Reactor
20 Maximum ambient temperature capacitor can withstand °C VTA
19Percentage of over voltage due to failure of each bank for
different ratingsVTA
18 Voltage and current rating of capacitor bushing ( of units)
%
VTA
17 Whether the neutral capacitor bank floated or earthed
V & A
VTA
e) Output of capacitor if one element fails, 2 elements fails
etc.kVAr VTA
d) Units in parallel per series group Nos. VTA
c) bank capacitance µF VTA
b) Capacitance of each phase of each star µF VTA
a) Rated output of capacitor unit and voltage V VTA
16 Capacitor bank output
15Maximum difference of capacitance between capacitor units
in bankµF VTA
d) Minimum and maximum voltage and PF setting V & % VTA
c) Schematic drawing Yes/No Required
b) Earth fault Required
a) Whether timer required for switching operation Required
14 Protection schemes for capacitor bank (recommended)
e) Dielectric breakdown voltage kV VTA
ii) Crosswise VTA
i) Lengthwise VTA
d) Shrinkage
ii) Crosswise VTA
i) Lengthwise VTA
VENDOR'S RESPONSE Rev. No.Sl.No. PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS
c) Percentage elongation
-
DOCUMENT No.: 17039-ND-E-DS-9011 PAGE No.: 8 of 8
SERVICE: CAPACITOR BANK No. OF UNITS: 1 No
DATA SHEET FOR CAPACITOR BANK
SPECIFICATION REF.: 17039-ND-E-DB-9001 MANUFACTURER: -
TAG Nos. :
b) Inrush current Yes
21 Type of Shielding adopted in the reactor VTA
20 Whether reactor designed for
a) Harmonics Yes
18 Maximum system voltage for which reactor is designed V VTA
19 Conforming to IS Required
16 Rated KVAR kVAr VTA
17 Terminal arrangement Top/Sides VTA
14 Winding resistance (cold /hot) Ω VTA
15 Voltage and current rating of reactor bushing V & A VTA
12 Type of cooling VTA
13 Load losses W/kVAr VTA
11 Reactance at rated current mH VTA
VENDOR'S RESPONSE Rev. No.Sl.No. PARTICULARS OF EQUIPMENT UNITS PURCHASER'S REQUIREMENTS