Occupancy Sensor AutoON/Override Power PackCat. No. LCA2292
Load Ratings: 20A, 2400W @ 120V, 60Hz - Incandescent / 20A, 2400VA @ 120V, 60Hz - Fluorescent20A, 5540VA @ 277V, 60Hz - Fluorescent / 1/2 HP @ 120V - Motor Load / 2 HP @ 240/277V, 60Hz - Motor Load / 0.5A 120V, 1A 30VDC - HVAC Relay
For use with LRM2250, LRM2255, LRM2260, LRM2265, LRM2270,LRM2275, LRM2280 Low Voltage SensorsINSTALLATION INSTRUCTIONSWARNINGS AND CAUTIONS:
• TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at circuit breaker or fuse and test that power is off before wiring!• Tobeinstalledand/orusedinaccordancewithappropriateelectricalcodesandregulations.• Ifyouareunsureaboutanypartoftheseinstructions,consultanelectrician.• Usethisdevicewithcopper or copper clad wire only.• Disconnect powerwhenservicingfixtureorchanginglamps.
• LightsFlickering - Lamphasabadconnection. - Wiresnotsecuredfirmlywithwireconnectors.
• LightsdidnotturnON - Circuit breaker or fuse has tripped. - Lampisburnedout. - LampNeutralconnectionisnotwired. - HoldOFForManualONinputisactive. - LowVoltagemisswired.Verifywiringpreappropriatediagram. - LineVoltagemisswired.Verifywiringpreappropriatediagram.
• LightsstayON - Constantmotion.To Test:adjustsensor;removemotionsource(HVAC,Mask,or
movesensor).
• LightsturnONtoolong - Adjust sensor settings.
• LightscameONduringpresentation - AutoONmodeisconnectedandthetimedelayexpired. - Increasethesensortimedelayorgeneratemoremotionduringthepresentation.
• LightsdonotturnOFFwithtimedelay
- HoldONinputisactive.
FEATURES
• Title24Compliant• HoldOn/HoldOffcapabilities• Regulated24VDC,150mAoutputcurrent• MountsinsideFluorescentBallastcavity• MountsinsideoroutsideJunctionBox• RatedforPlenumspaces
RATINGS
PartNumber HVAC Relay Power Input1 Power Output2
LCA2292 Yes 120-277VAC,50/60Hz 24VDC,150mA3.6W1Inputvoltagetolerance10%,Frequencytolerance5%.2Outputvoltagetolerance15%,Outputvoltagelistedatnominal.
DESCRIPTION
Thepowerpackcontainsapowersupply,aloadswitchingrelayandanHVACrelay.ThepowersupplyprovidesClass2low-voltagepowerforLRM2250,LRM2255,LRM2260, LRM 2265, LRM2270, LRM2275, and LRM2280 Series Occupancy Sensors.Therelayinthepowerpackiscontrolledbytheoccupancysensorsconnectedviathe22GaugeBlue"occupancy"wire.Multipleoccupancysensorscanbeconnectedtoasinglepowerpackinordertofullycoveranarea.Thepowerpacksincludezerocrossswitchingcircuitrytominimizeinrushcurrentassociatedwithincandescentandelectronicballasts.Thisreduceswearandtearontherelaycontactsmakingthepowerpacklastlonger.Application Notes:1.Whenalightingloadexceedsasinglepowerpack’srating,theloadcanbesplitbetweenmultiplepowerpacks.Thelowvoltageoccupancyinput(Bluewire)andDCreturn(Blackwires)ofthepowerpacksmustbeconnectedtogetherforallpowerpackstooperatetogetherasone.ConnecttheBlue(occupancy)wiresofallpowerpacksandsensorstogether.ConnecttheBlack(return)wiresofallpowerpacksandsensorstogether.ConnecttheRed(+24VDC)wiresofthesensorstotheRedwiresofonlyonepowerpack.NeverconnecttheRed(+24VDC)wiresoftwodifferentpower packs together.
2.Whenmoresensorsarerequiredthanonepowerpackcansupply,multiplepowerpacks can be used to supply power to the occupancy sensor, but not switch any load.Theprimarypowerpackisthepowerpackswitchingtheload.Thesecondarypowerpacksonlyprovidelowvoltagepowertotheoccupancysensor(s).Connectasmanysensorstotheprimarypowerpackaspossible(seecurrentcapacitysectionbelow),byconnectingtheRedwiresofthesensorstotheRedwire(+24VDC)oftheprimarypowerpack.ConnecttheRedwires(+24VDC)oftheremainingsensorstotheRedwiresofthesecondarypowerpack.ConnecttheBlack(return)wiresofallpowerpacksandallsensorstogether.ConnecttheBlue(occupancy)wireofallsensorstogethertotheBluewire(occupancy)oftheprimarypowerpack.NeverconnecttheRed(+24VDC)wiresoftwodifferentpowerpackstogether.
FCC COMPLIANCE STATEMENT (LCA2292)ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassAdigitaldevice,pursuanttopart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainstharmfulinterferencewhentheequipmentisoperatedinacommercialenvironment.Thisequipmentgenerates,uses,andcanradiateradiofrequencyenergyand,ifnotinstalledandusedinaccordancewiththeinstructionmanual,maycauseharmfulinterferencetoradiocommunications.Operationofthisequipmentinaresidentialareaislikelytocauseharmfulinterferenceinwhichcasetheuserwillberequiredtocorrecttheinterferenceathisownexpense.
LOW-VOLTAGE CURRENT CAPACITY
INSTALLATION
LCA2292 TotalNumberofSensors ≤ 150mA
1. WARNING:TOAVOIDFIRE,SHOCK,ORDEATH;TURN OFF POWERATCIRCUITBREAKERORFUSEANDTESTTHATPOWERISOFFBEFOREWIRING!
2. Mount power pack per desired application: A. Tomountoutside4"x4"junctionboxusing2"EMTnipple,refertoFigure 1. Wire
per instructions Step 3A and 3B. B. Tomountinside4"x4"junctionbox,refertoFigure 2. Wire per instructions Step
3A and 3B. •Ensurethatconduit/cableentryclampislocatedincornerofjunctionbox. •Dresswirestoprovideenoughclearancewhendeviceisinstalled. CAUTION:Low-voltagewiresmustalsobedressedsotheyareseparate
fromthehighvoltage(ClassI)conductors.Refertolocalbuildingcodesfortheappropriateinstallationrequirementsforthelowvoltagewiring.Jacketingoverthelow-voltagewiresmayberequiredtoprovideappropriateinsulationfromthehigh-voltagewiring.
C. Tomountinsideballastcavityoflightfixture,refertoFigure 3A. Wire per instructions Step 3A and 3B.
CAUTION:Low-voltagewiresmustalsobedressedsotheyareseparatefromthehighvoltage(ClassI)conductors.Refertolocalbuildingcodesfortheappropriateinstallationrequirementsforthelowvoltagewiring.Jacketingoverthelow-voltagewiresmayberequiredtoprovideappropriateinsulationfromthehigh-voltagewiring.
D. Tomountoutsideballastcavityoflightfixture,refertoFigure 3B. Wire per instructions Step 3A and 3B.
3A. Line Voltage Wiring:Remove5/8"(1.6cm)ofinsulationfromeachcircuitconductor.Makesurethatendsofconductorsarestraight.ConnectleadwiresfromPowerPacktoLINEcircuitperappropriateWIRINGDIAGRAMasfollows:Twiststrandsofeachleadtightlyand,withcircuitconductorspushfirmlyintoappropriatewireconnector.Screwconnectorsonclockwisemakingsurethatnobareconductorshowsbelowthewire connectors. Secure each connector with electrical tape.
3B. Class 2 and HVAC Wiring:ConnectLow-VoltagewiresfromPowerPacktoSensorperappropriateWIRINGDIAGRAMasfollows:Twiststrandsofeachleadtightlyand,withcircuitconductors,pushfirmlyintoappropriatewireconnector.Screwconnectorsonclockwisemakingsurethatnobareconductorshowsbelowthewireconnectors.Secure each connector with electrical tape.
4. Refer to sensor Installation Instructions for further details.5. Restore power at circuit breaker or fuse. INSTALLATION IS COMPLETE.
Mounts outsidejunction box
Figure 1
Line Voltage Wires
Class 2 Wires
Figure 2
Mounts insidejunction box
Line Voltage Wires
Class 2 Wires
OPERATION
TheAutoOn/OverridePowerPackcanbeturnedONandOFFautomaticallyusinganoccupancysensorinput,atimer,panelorBASinput,andmanuallyfromanoptionallowvoltagemomentaryswitch.
AUTOON(SeeWiringDiagram):Theoccupancysensorinput,HoldONinputandtheoptionalmomentaryswitchinputcanall be used to turn the load ON.WhentheloadisturnedOFFusingthemomentaryswitch,thepowerpackdoesnotturnitONautomaticallyuntilafterthesensortimedelayexpires(e.g.,presentationmode).PressingthemomentaryswitchbeforethesensortimedelayexpiresturnstheloadON.Whentheoccupancysensor’stimedelayexpires,thepowerpackrevertstoAutoONmodeanditturnstheloadONwiththenextinputfromtheoccupancysensor.
MANUALON(SeeWiringDiagram):OccupantsmustpressthelowvoltagemomentaryswitchtoturntheloadON.When the occupancy sensor is the only input keeping the load ON, the load turns OFF whenthesensortimedelayexpires.Ifthesensorinputre-triggerswithin30secondsaftertheloadturnsOFF,theloadturnsONagain.Afterthe30secondsexpirewithnosensorinputpressthemomentaryswitchtoturntheloadON.
LOW VOLTAGE INPUTS24VDCinputwiresareprovidedtocontroltheloadrelay.Theinputsmaybeusedincombinationorindividually,dependingontheapplication(s).Seewiringdiagramsforconnections.
MAINTAINED INPUTSOccupancy Sensor (Blue)-ThisinputisforoccupancysensorAutoON/AutoOFF.Applying24vclosestherelay(Occupied).Removethevoltageandtherelayopens(Vacant).
Occupancy Sensor (Blue/White)-ThisinputisforoccupancysensorManualON/AutoOFF.Whentheattachedoccupancysensordetectsmotion,noactionoccurs.AlocalmomentaryswitchisrequiredtomanuallyturntheloadON.ThenthesensorwillturntheloadOFFwhenthetimedelayexpires.
Hold ON (Yellow)-Thisinputisintendedfortimerorpanelinput.Applying24VDCclosestherelay and disables other inputs.
Itcan be overridden by the HoldOFFinput.Hold OFF (Orange)–Thisinputisusedfortimer,panel,BASorloadshedinput.Applying24VDCopenstherelay.Removethevoltageandtherelaycanacceptanyotherinput.ItoverridestheControlONandHoldONinputs.
Local Switch (Yellow/Orange)–Thisinputisforalowvoltagemomentaryswitch.Applying24VDCmomentaryinputchangestherelaytotheoppositestate.ItoverridestheControl ON, Hold ON and Hold OFF inputs.
• All wires rated at 105o C, 600V insulation.• Class 2 wires are Teflon coated, for plenum applications.• HVAC wiring is Class 1 and Class 2 rated.
Line Voltage Wires
Class 2 Wires
Line 120-277V
Neutral
Load
Load
Power (24 VDC)
DC Return
Occupancy Auto ON
HVAC Wires
HVAC Common
HVAC NO (Normally Open)
HVAC NC (Normally Closed)
Occupancy Manual ON
Hold ON
Hold OFF
Local Switch Input
Signal Name
Black
White
Blue
Blue
Red
Black
Blue
Green
Brown/White
Brown
Blue/White
Yellow
Orange
Yellow/Orange
Color
18 AWG
18 AWG
14 AWG
14 AWG
22 AWG
22 AWG
22 AWG
22 AWG
22 AWG
22 AWG
22 AWG
22 AWG
22 AWG
22 AWG
Gauge
Wire Designations
TROUBLESHOTING
Auto ON/Auto OFF, Manual OFF
Occupancy Sensor
Switch
N HOrange
Green
Brown
Brown/White
Orange/Yellow
Blue
Yellow
Black
Red
Blue/White
NH
Blue
Blue
White
Black
LOAD
LOAD
Manual ON, Light Hold OFF, Auto OFF
Occupancy Sensor
Switch
Dry Contacts
N HOrange
Green
Brown
Brown/White
Orange/Yellow
Blue
Yellow
Black
Red
Blue/White
NH
Blue
Blue
White
Black
LOAD
LOAD
Auto ON, Auto OFF, Light Hold ON
Occupancy Sensor
Dry Contacts
N HOrange
Green
Brown
Brown/White
Orange/Yellow
Blue
Yellow
Black
Red
Blue/White
NH
Blue
Blue
White
Black
LOAD
LOAD
HVAC
N H
ComNO InputNC Input
Orange
Green
Brown
Brown/White
Orange/Yellow
Blue
Yellow
Black
Red
Blue/White
NH
Blue
Blue
White
Black
LOAD
LOAD
HVAC
Local Switch
Switch
N HOrange
Green
Brown
Brown/White
Orange/Yellow
Blue
Yellow
Black
Red
Blue/White
NH
Blue
Blue
White
Black
LOAD
LOAD
Multiple Occupancy Sensors Exceed Power Supply Ratings
Occupancy Sensor
N HOrange
Green
Brown
Brown/White
Orange/Yellow
Blue
Yellow
Black
Red
Blue/White
Yellow
Orange
Orange/Yellow
Blue/White
Green
Brown
Brown/White
Blue
Red
Black
NH
White
Black
N H
Blue
Blue
White
Black
LOAD
LOAD
Blue
Blue
Multiple Loads Exceed Single Power Pack Ratings
N H
Occupancy Sensor
Orange
Green
Brown
Brown/White
Orange/Yellow
Blue
Yellow
Black
Red
Blue/White
Yellow
Orange
Orange/Yellow
Blue/White
Green
Brown
Brown/White
Blue
Red
Black
NH
NH
White
Black
LOAD
N H
Blue
Blue
White
Black
LOAD
LOAD
Blue
Blue
LCA
2292
Inst
ruct
ions
EN
.PD
F
Manual ON, Auto OFF
N HOrange
Green
Brown
Brown/White
Orange/Yellow
Blue
Yellow
Black
Red
Blue/White
NH
Blue
Blue
White
Black
LOAD
LOAD
LCA2292 Bi-Level Switching
Occupancy Sensor
Zone 1 - Auto ON
Zone 2 - Manual ON
Momentaryor Maintained
Switches
N H
Green
Brown
Brown/White
Yellow
White/Blue
Blue
Blue
White
Black
LOAD 1
LOAD 2
Yellow
Orange
Green
Brown
Brown/White
Blue
Red
White
Blue
Blue
Black
Orange/Yellow
White/Blue
Black
Red
Orange
Orange/Yellow
Blue
Zone 1
Zone 2
Local SW 1
Auto ON
+24VDC
Com
Local SW 2
Manual ON
Black Com
PRODUCT WARRANTY
Philips Lighting Standard two (2) year warrantyContactInformation:PhilipsLighting,10275HigginsRoad,Rosemont,IL60018USACustomerCare/TechnicalService: 1 800-372-3331 E-Mail:[email protected] Website:www.usa.lighting.philips.com