Occupancy Sensor AutoON/Override Power PackCat. No. LCA2292

Load Ratings: 20A, 2400W @ 120V, 60Hz - Incandescent / 20A, 2400VA @ 120V, 60Hz - Fluorescent20A, 5540VA @ 277V, 60Hz - Fluorescent / 1/2 HP @ 120V - Motor Load / 2 HP @ 240/277V, 60Hz - Motor Load / 0.5A 120V, 1A 30VDC - HVAC Relay

For use with LRM2250, LRM2255, LRM2260, LRM2265, LRM2270,LRM2275, LRM2280 Low Voltage SensorsINSTALLATION INSTRUCTIONSWARNINGS AND CAUTIONS:

• TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at circuit breaker or fuse and test that power is off before wiring!• Tobeinstalledand/orusedinaccordancewithappropriateelectricalcodesandregulations.• Ifyouareunsureaboutanypartoftheseinstructions,consultanelectrician.• Usethisdevicewithcopper or copper clad wire only.• Disconnect powerwhenservicingfixtureorchanginglamps.

• LightsFlickering - Lamphasabadconnection. - Wiresnotsecuredfirmlywithwireconnectors.

• LightsdidnotturnON - Circuit breaker or fuse has tripped. - Lampisburnedout. - LampNeutralconnectionisnotwired. - HoldOFForManualONinputisactive. - LowVoltagemisswired.Verifywiringpreappropriatediagram. - LineVoltagemisswired.Verifywiringpreappropriatediagram.

• LightsstayON - Constantmotion.To Test:adjustsensor;removemotionsource(HVAC,Mask,or

movesensor).

• LightsturnONtoolong - Adjust sensor settings.

• LightscameONduringpresentation - AutoONmodeisconnectedandthetimedelayexpired. - Increasethesensortimedelayorgeneratemoremotionduringthepresentation.

• LightsdonotturnOFFwithtimedelay

- HoldONinputisactive.

FEATURES

• Title24Compliant• HoldOn/HoldOffcapabilities• Regulated24VDC,150mAoutputcurrent• MountsinsideFluorescentBallastcavity• MountsinsideoroutsideJunctionBox• RatedforPlenumspaces

RATINGS

PartNumber HVAC Relay Power Input1 Power Output2

LCA2292 Yes 120-277VAC,50/60Hz 24VDC,150mA3.6W1Inputvoltagetolerance10%,Frequencytolerance5%.2Outputvoltagetolerance15%,Outputvoltagelistedatnominal.

DESCRIPTION

Thepowerpackcontainsapowersupply,aloadswitchingrelayandanHVACrelay.ThepowersupplyprovidesClass2low-voltagepowerforLRM2250,LRM2255,LRM2260, LRM 2265, LRM2270, LRM2275, and LRM2280 Series Occupancy Sensors.Therelayinthepowerpackiscontrolledbytheoccupancysensorsconnectedviathe22GaugeBlue"occupancy"wire.Multipleoccupancysensorscanbeconnectedtoasinglepowerpackinordertofullycoveranarea.Thepowerpacksincludezerocrossswitchingcircuitrytominimizeinrushcurrentassociatedwithincandescentandelectronicballasts.Thisreduceswearandtearontherelaycontactsmakingthepowerpacklastlonger.Application Notes:1.Whenalightingloadexceedsasinglepowerpack’srating,theloadcanbesplitbetweenmultiplepowerpacks.Thelowvoltageoccupancyinput(Bluewire)andDCreturn(Blackwires)ofthepowerpacksmustbeconnectedtogetherforallpowerpackstooperatetogetherasone.ConnecttheBlue(occupancy)wiresofallpowerpacksandsensorstogether.ConnecttheBlack(return)wiresofallpowerpacksandsensorstogether.ConnecttheRed(+24VDC)wiresofthesensorstotheRedwiresofonlyonepowerpack.NeverconnecttheRed(+24VDC)wiresoftwodifferentpower packs together.

2.Whenmoresensorsarerequiredthanonepowerpackcansupply,multiplepowerpacks can be used to supply power to the occupancy sensor, but not switch any load.Theprimarypowerpackisthepowerpackswitchingtheload.Thesecondarypowerpacksonlyprovidelowvoltagepowertotheoccupancysensor(s).Connectasmanysensorstotheprimarypowerpackaspossible(seecurrentcapacitysectionbelow),byconnectingtheRedwiresofthesensorstotheRedwire(+24VDC)oftheprimarypowerpack.ConnecttheRedwires(+24VDC)oftheremainingsensorstotheRedwiresofthesecondarypowerpack.ConnecttheBlack(return)wiresofallpowerpacksandallsensorstogether.ConnecttheBlue(occupancy)wireofallsensorstogethertotheBluewire(occupancy)oftheprimarypowerpack.NeverconnecttheRed(+24VDC)wiresoftwodifferentpowerpackstogether.

FCC COMPLIANCE STATEMENT (LCA2292)ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassAdigitaldevice,pursuanttopart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainstharmfulinterferencewhentheequipmentisoperatedinacommercialenvironment.Thisequipmentgenerates,uses,andcanradiateradiofrequencyenergyand,ifnotinstalledandusedinaccordancewiththeinstructionmanual,maycauseharmfulinterferencetoradiocommunications.Operationofthisequipmentinaresidentialareaislikelytocauseharmfulinterferenceinwhichcasetheuserwillberequiredtocorrecttheinterferenceathisownexpense.

LOW-VOLTAGE CURRENT CAPACITY

INSTALLATION

LCA2292 TotalNumberofSensors ≤ 150mA

1. WARNING:TOAVOIDFIRE,SHOCK,ORDEATH;TURN OFF POWERATCIRCUITBREAKERORFUSEANDTESTTHATPOWERISOFFBEFOREWIRING!

2. Mount power pack per desired application: A. Tomountoutside4"x4"junctionboxusing2"EMTnipple,refertoFigure 1. Wire

per instructions Step 3A and 3B. B. Tomountinside4"x4"junctionbox,refertoFigure 2. Wire per instructions Step

3A and 3B. •Ensurethatconduit/cableentryclampislocatedincornerofjunctionbox. •Dresswirestoprovideenoughclearancewhendeviceisinstalled. CAUTION:Low-voltagewiresmustalsobedressedsotheyareseparate

fromthehighvoltage(ClassI)conductors.Refertolocalbuildingcodesfortheappropriateinstallationrequirementsforthelowvoltagewiring.Jacketingoverthelow-voltagewiresmayberequiredtoprovideappropriateinsulationfromthehigh-voltagewiring.

C. Tomountinsideballastcavityoflightfixture,refertoFigure 3A. Wire per instructions Step 3A and 3B.

CAUTION:Low-voltagewiresmustalsobedressedsotheyareseparatefromthehighvoltage(ClassI)conductors.Refertolocalbuildingcodesfortheappropriateinstallationrequirementsforthelowvoltagewiring.Jacketingoverthelow-voltagewiresmayberequiredtoprovideappropriateinsulationfromthehigh-voltagewiring.

D. Tomountoutsideballastcavityoflightfixture,refertoFigure 3B. Wire per instructions Step 3A and 3B.

3A. Line Voltage Wiring:Remove5/8"(1.6cm)ofinsulationfromeachcircuitconductor.Makesurethatendsofconductorsarestraight.ConnectleadwiresfromPowerPacktoLINEcircuitperappropriateWIRINGDIAGRAMasfollows:Twiststrandsofeachleadtightlyand,withcircuitconductorspushfirmlyintoappropriatewireconnector.Screwconnectorsonclockwisemakingsurethatnobareconductorshowsbelowthewire connectors. Secure each connector with electrical tape.

3B. Class 2 and HVAC Wiring:ConnectLow-VoltagewiresfromPowerPacktoSensorperappropriateWIRINGDIAGRAMasfollows:Twiststrandsofeachleadtightlyand,withcircuitconductors,pushfirmlyintoappropriatewireconnector.Screwconnectorsonclockwisemakingsurethatnobareconductorshowsbelowthewireconnectors.Secure each connector with electrical tape.

4. Refer to sensor Installation Instructions for further details.5. Restore power at circuit breaker or fuse. INSTALLATION IS COMPLETE.

Mounts outsidejunction box

Figure 1

Line Voltage Wires

Class 2 Wires

Figure 2

Mounts insidejunction box

Line Voltage Wires

Class 2 Wires

OPERATION

TheAutoOn/OverridePowerPackcanbeturnedONandOFFautomaticallyusinganoccupancysensorinput,atimer,panelorBASinput,andmanuallyfromanoptionallowvoltagemomentaryswitch.

AUTOON(SeeWiringDiagram):Theoccupancysensorinput,HoldONinputandtheoptionalmomentaryswitchinputcanall be used to turn the load ON.WhentheloadisturnedOFFusingthemomentaryswitch,thepowerpackdoesnotturnitONautomaticallyuntilafterthesensortimedelayexpires(e.g.,presentationmode).PressingthemomentaryswitchbeforethesensortimedelayexpiresturnstheloadON.Whentheoccupancysensor’stimedelayexpires,thepowerpackrevertstoAutoONmodeanditturnstheloadONwiththenextinputfromtheoccupancysensor.

MANUALON(SeeWiringDiagram):OccupantsmustpressthelowvoltagemomentaryswitchtoturntheloadON.When the occupancy sensor is the only input keeping the load ON, the load turns OFF whenthesensortimedelayexpires.Ifthesensorinputre-triggerswithin30secondsaftertheloadturnsOFF,theloadturnsONagain.Afterthe30secondsexpirewithnosensorinputpressthemomentaryswitchtoturntheloadON.

LOW VOLTAGE INPUTS24VDCinputwiresareprovidedtocontroltheloadrelay.Theinputsmaybeusedincombinationorindividually,dependingontheapplication(s).Seewiringdiagramsforconnections.

MAINTAINED INPUTSOccupancy Sensor (Blue)-ThisinputisforoccupancysensorAutoON/AutoOFF.Applying24vclosestherelay(Occupied).Removethevoltageandtherelayopens(Vacant).

Occupancy Sensor (Blue/White)-ThisinputisforoccupancysensorManualON/AutoOFF.Whentheattachedoccupancysensordetectsmotion,noactionoccurs.AlocalmomentaryswitchisrequiredtomanuallyturntheloadON.ThenthesensorwillturntheloadOFFwhenthetimedelayexpires.

Hold ON (Yellow)-Thisinputisintendedfortimerorpanelinput.Applying24VDCclosestherelay and disables other inputs.

Itcan be overridden by the HoldOFFinput.Hold OFF (Orange)–Thisinputisusedfortimer,panel,BASorloadshedinput.Applying24VDCopenstherelay.Removethevoltageandtherelaycanacceptanyotherinput.ItoverridestheControlONandHoldONinputs.

Local Switch (Yellow/Orange)–Thisinputisforalowvoltagemomentaryswitch.Applying24VDCmomentaryinputchangestherelaytotheoppositestate.ItoverridestheControl ON, Hold ON and Hold OFF inputs.

• All wires rated at 105o C, 600V insulation.• Class 2 wires are Teflon coated, for plenum applications.• HVAC wiring is Class 1 and Class 2 rated.

Line Voltage Wires

Class 2 Wires

Line 120-277V

Neutral

Load

Load

Power (24 VDC)

DC Return

Occupancy Auto ON

HVAC Wires

HVAC Common

HVAC NO (Normally Open)

HVAC NC (Normally Closed)

Occupancy Manual ON

Hold ON

Hold OFF

Local Switch Input

Signal Name

Black

White

Blue

Blue

Red

Black

Blue

Green

Brown/White

Brown

Blue/White

Yellow

Orange

Yellow/Orange

Color

18 AWG

18 AWG

14 AWG

14 AWG

22 AWG

22 AWG

22 AWG

22 AWG

22 AWG

22 AWG

22 AWG

22 AWG

22 AWG

22 AWG

Gauge

Wire Designations

TROUBLESHOTING

Page 2: Occupancy Sensor AutoON/Override Power Pack Cat. No ... Controls... · Occupancy Sensor AutoON/Override Power Pack Cat. No. LCA2292 Load Ratings: 20A, 2400W @ 120V, 60Hz - Incandescent

Auto ON/Auto OFF, Manual OFF

Occupancy Sensor

Switch

N HOrange

Green

Brown

Brown/White

Orange/Yellow

Blue

Yellow

Black

Red

Blue/White

NH

Blue

Blue

White

Black

LOAD

LOAD

Manual ON, Light Hold OFF, Auto OFF

Occupancy Sensor

Switch

Dry Contacts

N HOrange

Green

Brown

Brown/White

Orange/Yellow

Blue

Yellow

Black

Red

Blue/White

NH

Blue

Blue

White

Black

LOAD

LOAD

Auto ON, Auto OFF, Light Hold ON

Occupancy Sensor

Dry Contacts

N HOrange

Green

Brown

Brown/White

Orange/Yellow

Blue

Yellow

Black

Red

Blue/White

NH

Blue

Blue

White

Black

LOAD

LOAD

HVAC

N H

ComNO InputNC Input

Orange

Green

Brown

Brown/White

Orange/Yellow

Blue

Yellow

Black

Red

Blue/White

NH

Blue

Blue

White

Black

LOAD

LOAD

HVAC

Local Switch

Switch

N HOrange

Green

Brown

Brown/White

Orange/Yellow

Blue

Yellow

Black

Red

Blue/White

NH

Blue

Blue

White

Black

LOAD

LOAD

Multiple Occupancy Sensors Exceed Power Supply Ratings

Occupancy Sensor

N HOrange

Green

Brown

Brown/White

Orange/Yellow

Blue

Yellow

Black

Red

Blue/White

Yellow

Orange

Orange/Yellow

Blue/White

Green

Brown

Brown/White

Blue

Red

Black

NH

White

Black

N H

Blue

Blue

White

Black

LOAD

LOAD

Blue

Blue

Multiple Loads Exceed Single Power Pack Ratings

N H

Occupancy Sensor

Orange

Green

Brown

Brown/White

Orange/Yellow

Blue

Yellow

Black

Red

Blue/White

Yellow

Orange

Orange/Yellow

Blue/White

Green

Brown

Brown/White

Blue

Red

Black

NH

NH

White

Black

LOAD

N H

Blue

Blue

White

Black

LOAD

LOAD

Blue

Blue

LCA

2292

Inst

ruct

ions

EN

.PD

F

Manual ON, Auto OFF

N HOrange

Green

Brown

Brown/White

Orange/Yellow

Blue

Yellow

Black

Red

Blue/White

NH

Blue

Blue

White

Black

LOAD

LOAD

LCA2292 Bi-Level Switching

Occupancy Sensor

Zone 1 - Auto ON

Zone 2 - Manual ON

Momentaryor Maintained

Switches

N H

Green

Brown

Brown/White

Yellow

White/Blue

Blue

Blue

White

Black

LOAD 1

LOAD 2

Yellow

Orange

Green

Brown

Brown/White

Blue

Red

White

Blue

Blue

Black

Orange/Yellow

White/Blue

Black

Red

Orange

Orange/Yellow

Blue

Zone 1

Zone 2

Local SW 1

Auto ON

+24VDC

Com

Local SW 2

Manual ON

Black Com

PRODUCT WARRANTY

Philips Lighting Standard two (2) year warrantyContactInformation:PhilipsLighting,10275HigginsRoad,Rosemont,IL60018USACustomerCare/TechnicalService: 1 800-372-3331 E-Mail:[email protected] Website:www.usa.lighting.philips.com