7/31/2019 NZ EQ Report 001 View_file
1/5Winter 2012 |PCI Journal
Emulative design, which requires critical sections to re-
spond under load as they would or cast-in-place concrete,
together with the capacity design philosophy, was crucial
or gaining the acceptance o structural engineers in New
Zealand. In capacity design, the primary structural system
or resisting seismic orces is rst designed to have a
suitable mechanism o accommodating nonlinear lateral
deormation, with the engineer explicitly dening the loca-
tions o plastic hinges. Plastic hinge regions are designed
and detailed or strength and ductility during a severe
earthquake. Then the remainder o the structural system is
provided with sucient strength to avoid other possibleailure modes and maintain ductility ater fexural over-
strength develops at the plastic hinges.
Resisting lateral forcesfrom earthquakes
Moment-resisting rames have been the most common
seismic-orce-resisting system or tall buildings in New
Zealand. A beam sidesway mechanism, in which plas-
tic hinges orm in the beams due to strong columns and
weak beams, is the preerred nonlinear mechanism. To
ensure that fexural hinging does not occur at locations not
Preview of PCIs
New Zealand earthquake
reconnaissance team report
Robert B. Fleischman, Jos I. Restrepo, Joseph R. Maffei,and Kim Seeber
Precast concrete structuraldesign in New Zealand
recast concrete has been used in New Zealand
since the early 1960s and became widely accepted
in the 1980s as an eective construction method
or seismic resistance. Since then, precast concrete
has been extensively used there. Park described the evolution
o precast concrete design in that country.1
During the building boom o the mid- to late 1980s, the speed
o construction and high quality o precast concrete gave itsignicant advantages over cast-in-place concrete. The New
Zealand concrete design standard2 o the time included com-
prehensive provisions or the seismic design o cast-in-place
concrete structures but did not cover all aspects o precast
concrete structures. A study group o the New Zealand
Concrete Society was ormed in 1988 to summarize data on
precast concrete design and construction, recommend best
practices, and identiy areas or urther research. A 1995 revi-
sion o the New Zealand concrete design standard3 included
new provisions or precast concrete structures based on the
research o the early 1990s.1
PCI Reconnaissance Team ReportPhoto:Joseph
R.
Maffei
7/31/2019 NZ EQ Report 001 View_file
2/5 4PCI Journal|Winter 2012
designed or ductility, or that shear ailure cannot occur
anywhere in the structure, the maximum actions likely to
be imposed are calculated rom the fexural overstrengths
at the plastic hinges.1 Tall buildings in New Zealand were
typically constructed using perimeter moment rames with
relatively closely spaced sti columns and sti beams.
Interior beams and columns carried gravity load; their
contribution to seismic resistance was neglected.
Structural precast concrete walls (shear walls) have also
been used to provide seismic resistance in medium-rise
buildings in New Zealand. In some cases precast concrete
walls and rames are combined to orm dual systems.
These walls are designed to develop a plastic hinge at the
base. The most important consideration in detailing plastic
hinge regions or ductility is to provide sucient trans-
verse reinorcement, whether rectangular stirrups, hoops,
or spirals. The transverse reinorcement acts as shear rein-
orcement, connes the concrete, and prevents premature
buckling o the longitudinal reinorcement.1
Earthquakeof February 22, 2011
A magnitude 6.3 earthquake struck Christchurch, New
Zealand, at 12:51 p.m. on Tuesday, February 22, 2011. The
epicenter was located 10 km (6 mi) southeast o the city
center.4 The earthquake caused 182 deaths and damaged
thousands o buildings.5
New Zealand lies on the Pacic Rim and has a history
o strong earthquakes. However, Christchurch is about
240 km (150 mi) rom the nearest known major ault, andthus was not expected to experience a large earthquake. It
is in a moderate seismic hazard zone comparable to that o
Portland, Ore. The February earthquake, along with a less-
damaging earthquake the previous September, indicates the
existence o ault lines much closer to Christchurch.
In the February 22 earthquake, an interval o extremely
high-intensity shaking lasted approximately 8 sec. The
average response spectrum o the ground motions recorded
in the city center was approximately equivalent to the
Christchurch maximum considered earthquake and was
stronger or substantial ranges o typical building naturalrequencies. For individual records, the ground motion
contained requency ranges where it was substantially
stronger, similar to the maximum considered earthquake in
Berkeley, Cali.6 The February event was extremely strong
near the epicenter, with vertical accelerations o up to 2g.
Soil liqueaction was signicant and widespread due to the
presence o a high water table in sandy soil. Deep ounda-
tions are airly rare in Christchurch, and several buildings
and bridges showed evidence o support movement or di-
erential settlement.
Case study:PricewaterhouseCoopersoffice building
The 21-story PricewaterhouseCoopers oce building was
constructed in the 1980s (Fig. 1). It was designed with
an exterior moment-resisting rame and constructed us-
ing a detail in which the precast concrete joint (Fig. 2) is
placed over the column below. Vertical ducts in the precast
concrete joint allow the vertical reinorcement rom the
column to be threaded through and into the column above.
The ducts are grouted once the joint is in place.1
Figure 3 shows the perimeter moment-resisting rame
(background) and the interior gravity rame (oreground)
ollowing the earthquake o February 22. As can be seen,
the columns are more closely spaced in the perimeter
rame.
A visual survey o this building by the authors showed a
pattern o damage consistent with capacity design (Fig. 4).
The lowest two foors, situated above a parking garage and
undergoing less deormation, showed no plastic hinging.
The lower- to midlevel foors showed the greatest beam de-
Figure 1. PricewaterhouseCoopers building under construction in Christchurch,
New Zealand.
7/31/2019 NZ EQ Report 001 View_file
3/5Winter 2012 |PCI Journal4
ormation and damage, and the upper foors less damage.
Figure 4 shows the damage to the perimeter rame on the
interior o the 10th foor. The north-south beam exhibits
fexural-torsional cracks rom earthquake displacement
perpendicular to the rame, while the east-west beam
exhibits fexure cracks. The authors judge that the fexural
cracking observed does not reduce the strength o the
beams and does not substantially diminish their continueddeormation capacity or the ability o the structure to resist
uture earthquakes.
The exterior moment-resisting rame o the Pricewater-
houseCoopers building perormed as intended, orming the
desired fexural plastic hinges at the ends o the beams. No
structural damage was observed in the columns. Where the
damage was greatest, cracking and fexural torsion were
associated with these hinges. The extent o the damage
is not surprising given the extreme intensity o the earth-
quake motions. The authors judge the oce building to
have met or exceeded its design requirements to avoid col-
lapse in the maximum considered earthquake.
Final report
A ull report covering the perormance o a number o
other types o precast concrete structural systems during
the February 22, 2011, New Zealand earthquake, some
Figure 3. Corner joint in rst-level parking podium area ater February 22, 2011, earthquake in New Zealand. Photo courtesy o Franz Kahn.
Figure 2. Typical precast concrete corner unit being installed in perimeter
moment rame o the PricewaterhouseCoopers building.
7/31/2019 NZ EQ Report 001 View_file
4/5 4PCI Journal|Winter 2012
5. The Canterbury Earthquakes Royal Commission.canterbury.royalcommission.govt.nz.
6. Earthquake Engineering Research Institute (EERI).
2011.Learning from Earthquakes: The M 6.3 Christ-
church, New Zealand, Earthquake of February 22,
2011. EERI Special Earthquake Report. Oakland, CA:
EERI.
o which suered serious damage, will be published in auture issue o the PCI Journal.
References
1. Park, Robert. 2002. Seismic Design and Construction
o Precast Concrete Buildings in New Zealand. PCI
Journal, V. 47, No. 5 (SeptemberOctober): pp. 6075.
2. Standards Association o New Zealand. 1982. Code of
Practice for the Design of Concrete Structures. NZS
3101:1982. Wellington, New Zealand: Standards As-
sociation o New Zealand.
3. Standards Association o New Zealand. 1995. The
Design of Concrete Structures. NZS 3101:1995. Wel-
lington, New Zealand: Standards Association o New
Zealand.
4. GNS Science. 2011. The Canterbury Earthquake
Sequence and Implications or Seismic Design Levels.
Consultancy report 2011/183 to Canterbury Earth-
quakes Royal Commission. Compiler: T. H. Webb.
Figure 4. Corner joint in upper foor indicated damage suered in February 22, 2011, earthquake in New Zealand. The north-south beam (upper let) exhibits fexural-
torsional cracks, while the east-west beam (upper right) exhibits fexure cracks.
7/31/2019 NZ EQ Report 001 View_file
5/5Winter 2012 |PCI Journal6
About the authors
Robert B. Fleischman, PhD, is anassociate proessor in the Depart-
ment o Civil Engineering and
Engineering Mechanics at the
University o Arizona.
Jos I. Restrepo, PhD, is a
proessor in the Department o
Structural Engineering at the
University o Caliornia at San
Diego.
Joseph R. Maei, S.E., PhD,
LEED AP is a principal at
Rutherord & Chekene Engineers
in San Francisco, Cali.
Kim Seeber, P.E., FPCI, is a
senior vice president at Seaboard
Services o Virginia Inc. in
Taylors, S.C.