Asset: P.S. 136 - QUEENS, 201-15 115 AVENUE, New York, 11412 Inspection Id Inspection Type Time In Last Edited SA : Q136 Architectural - Senior 2020-08-21 7:21 AM 2020-08-27 9:34 AM AA : Q136 Architectural - Associate 2020-08-21 7:14 AM 2020-09-03 2:58 PM Asset Data Question Answer Was the building fully accessible for inspection Yes Principal(s) Information Principal Name Dr. Tanya Walker Organization P.S. 136 - Queens Did you meet with this Principal? No Did this Principal provide feedback? Yes Summary of Principal's Feedback A Principal questionnaire form was returned with concerns about additional ventilation on the 2nd and 3rd Floors for the upcoming school year. Custodian Stephen McPartland Fireman Joseph Barbieri Building Square Footage 87000 Comments on the Area None Comments on the Stories (Floors) plus Basements 3+B Comments on the Number of Classrooms 38 Comments on the Year Built 1928 Student Population 640 Staff Population 80 Weather Fair Facade Photo Corner of 115th Avenue and 221st Street - Northeast View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2019 - 2020 Q136 PB/A&W Print Date: 9/13/2020 Page 1 of 45

NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Asset: P.S. 136 - QUEENS, 201-15 115 AVENUE, New York, 11412

Inspection Id Inspection Type Time In Last Edited

SA : Q136 Architectural - Senior 2020-08-21 7:21 AM 2020-08-27 9:34 AM

AA : Q136 Architectural - Associate 2020-08-21 7:14 AM 2020-09-03 2:58 PM

Asset Data

Question Answer

Was the building fully accessible for inspection Yes

Principal(s) Information

Principal Name Dr. Tanya Walker

Organization P.S. 136 - Queens

Did you meet with this Principal? No

Did this Principal provide feedback? Yes

Summary of Principal's Feedback A Principal questionnaire form was returned with concerns aboutadditional ventilation on the 2nd and 3rd Floors for the upcomingschool year.

Custodian Stephen McPartland

Fireman Joseph Barbieri

Building Square Footage 87000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 3+B

Comments on the Number of Classrooms 38

Comments on the Year Built 1928

Student Population 640

Staff Population 80

Weather Fair

Facade Photo

Corner of 115th Avenue and 221st Street -Northeast View

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 1 of 45

Page 2: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Main Entrance Photo

Facade A - 115th Avenue

Roof Photo

Roof 1 - Northeast View

Have any Systems/Major Building Components been upgraded? Yes

Systems: 1st Floor Student Toilet Rooms converted HC compliance.

Year: 2018

Systems: Loading Dock repairs.

Year: 2017

Systems: Exterior Modernization Program including Roofing andFlashing replacement; Parapets and Coping replacement;Roof Drains replacement; Bulkhead Exterior Wallsrepairs; Windows and Window Guards replacement(Partial 1st Floor and entire 2nd and 3rd Floor); PartialExterior Walls Brick Veneer replacement at 2nd Floor;Partial Foundation Walls waterproofing at Facade A .

Year: 2015

Systems: Exterior Walls repairs.

Year: 2012

Systems: Partial Basement waterproofing; Areaway Walls repairs;Exterior Doors repairs; Stairs repairs.

Year: 2010

Systems: Exterior Walls, Bulkhead and Structural repairs.

Year: 2009

Have there been any New Building Additions? Yes

Comments on New Building Additions 1937 + 29,000 S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 2 of 45

Page 3: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Tandem Schools? No

Leased Space? No

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No Damaged/Deteriorated Railings

Damaged railingwith exposedsharp edges is apotential safetyhazard.

EXTERIOR |STAIRS/RAMPS: EXTERIOR |RAILINGS

Southwest Exitstair facing115th Avenue.

Joseph Barbieri Fireman

No Other Broken treebranch that issemi-attached tothe tree is aPotential SafetyHazard

DOT Sidewalk 202nd Street StephenMcPartland

Custodian

No Potential FallingDebris

Broken andloose stone wallis a PotentialSafety Hazard

INTERIOR |AUDITORIUM| Walls

Auditorium -Near ExitVestibule 9A

Joseph Barbieri Fireman

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? No

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits No Saddle height > 1/2"

Exterior H/C Lifts No No

Exterior Ramps and Railings No Yes

Interior Routes

Corridor and Lobby H/C Lifts No No

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies Yes

Interior Elevators No

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 3 of 45

Page 4: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

Rooms & Spaces

Art Rooms No

Auditorium 1st Floor Yes No No Stage AccessNot on Accessible Route

Yes No

Cafeteria 1st Floor Yes No Not on Accessible Route Yes No

Classrooms None on Accessible Route Yes No Not on Accessible Route

Computer Rooms Room 321 Yes No Not on Accessible Route

Gymnasium 3rd Floor Yes No Not on Accessible Route Yes No

Library Room 211 Yes No Not on Accessible Route

Main Office Room 255 Yes No Not on Accessible Route

Multi-purpose Room No

Nurse's Room Room 263 Yes No Not on Accessible Route

Pool No

Science Lab No

Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route

Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route

Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Inspected

InspectedInstance on AW1-AW10

Instance Condition 3 - Fair

Instance Quantity 10

Instance Quantity Uom EACH

Deficiency AREAWAY WALLS: CRACKS AND SPALLING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 4 of 45

Page 5: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

EXTERIOR

AREAWAY

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A - AW1

Violations No violations recorded.

Deficiency AREAWAY GRATINGS: MINOR RUSTING

Roof Plan reference

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Inspected

Material Type(s) Masonry

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 5 of 45

Page 6: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

EXTERIOR

CHIMNEY Inspected

Deficiency No deficiencies recorded

COPING Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

CORNICE Does not Exist

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

EXTERIOR WALLS Inspected

Material Type(s) Masonry

Replacement Quantity 40,500

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 2 - Between Good and Fair

Instance Quantity 40,500

Instance Quantity Uom S.F.

Deficiency No deficiencies recorded

EXTERIOR SOFFITS Does not Exist

LOADING DOCK Inspected

Condition 4 - Between Fair and Poor

Deficiency CHEEK WALL/CRACKS, SPALLING - MAJOR

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 6 of 45

Page 7: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

EXTERIOR

LOADING DOCK

Deficiency Photo1

Facade C

Violations No violations recorded.

LOUVER Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 4,000

Replacement Uom C.F.

InspectedInstance on All Facades

Instance Condition 3 - Fair

Instance Quantity 4,000

Instance Quantity Uom C.F.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 4

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 7 of 45

Page 8: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

EXTERIOR

PARAPETS Inspected

Violations No violations recorded.

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 26,000

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF BARRIER Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Modified Bitumen: All Roofs

Instance Condition 1 - Good

Instance Quantity 26,000

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2015

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

ROOFING DRAINS Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Specialties Inspected

BULKHEAD/PENTHOUSE Inspected

Condition 3 - Fair

Deficiency BULKHEAD/PENTHOUSE WALLS/EXTERIOR:CRACKS/SPALLING - MINOR

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 8 of 45

Page 9: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

EXTERIOR

ROOF Inspected

Specialties

BULKHEAD/PENTHOUSE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 - Roof Vent

Violations No violations recorded.

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Does not Exist

SKYLIGHT/ROOF VENT Inspected

Material Type(s) Glass

Condition 3 - Fair

Deficiency SHAFT VENTS DAMAGED

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 9 of 45

Page 10: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

EXTERIOR

ROOF

Specialties

SKYLIGHT/ROOF VENT

Deficiency DAMAGED GUARDS

Roof Plan reference

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

Deficiency BROKEN GLASS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 10 of 45

Page 11: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

EXTERIOR

ROOF

Specialties

SKYLIGHT/ROOF VENT

Deficiency Photo1

Roof 1

Violations No violations recorded.

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Inspected

Condition 3 - Fair

Deficiency STONE: CRACKS/SPALLING - MINOR

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency STONE: OPEN JOINTS

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 11 of 45

Page 12: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade H

Violations No violations recorded.

RAILINGS Inspected

Condition 3 - Fair

Deficiency RUST - MAJOR

Roof Plan reference

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 12 of 45

Page 13: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

RAILINGS

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency RUST - MINOR

Roof Plan reference

Deficiency Quantity 40

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

STAIRS/RAMPS Inspected

Condition 3 - Fair

Deficiency STONE: WORN-OUT TREAD/RISER/NOSING

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 13 of 45

Page 14: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Deficiency Photo1

Facade F

Violations No violations recorded.

Deficiency CONCRETE: CRACKS/SPALLING - MINOR

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

WINDOWS Inspected

Replacement Quantity 11,030

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 3 - Fair

Deficiency RUST - MINOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 14 of 45

Page 15: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

EXTERIOR

WINDOWS

EXTERIOR GUARDS

Roof Plan reference

Elevation

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency STEEL: MINOR RUSTING

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 15 of 45

Page 16: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

EXTERIOR

WINDOWS

LINTELS

Elevation

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

WINDOWS Inspected

Material Type(s) Aluminum, Solid Wood

InspectedInstance on Aluminum - Double Hung: All Facades (Basement, Partial 1stFloor)

Instance Condition 3 - Fair

Instance Quantity 4,700

Instance Quantity Uom S.F.

Installation Year 2000

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

InspectedInstance on Aluminum - Double Hung: All Facades (Partial 1st Floor, Entire2nd and 3rd Floor)

Instance Condition 1 - Good

Instance Quantity 6,300

Instance Quantity Uom S.F.

Installation Year 2013

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

InspectedInstance on Wood: AW1, AW2

Instance Condition 5 - Poor

Instance Quantity 30

Instance Quantity Uom S.F.

Installation Year 1939

Source of Installation Custodial Staff

Deficiency WOOD: DETERIORATED

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 16 of 45

Page 17: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

EXTERIOR

WINDOWS

WINDOWS

Roof Plan reference

Elevation

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE WINDOW

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A - AW1

Violations No violations recorded.

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 3 - Fair

Deficiency CONCRETE COLUMNS/BEAMS:CRACKED/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Basement - Boiler Room, Fan Area

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 17 of 45

Page 18: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

STRUCTURAL

COLUMNS/BEAMS/BEARING WALLS

Purpose of Action LEVEL 5

Deficiency Photo1

Basement - Boiler Room

Violations No violations recorded.

FLOOR STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS

Deficiency Location/Instance Basement - Boiler Room

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Basement - Boiler Room

Violations No violations recorded.

Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance 1st Floor - Facade E - East Vestibule, Basement - Storage

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 18 of 45

Page 19: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE Inspected

Deficiency Photo1

1st Floor - Facade E - East Vestibule

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete

Condition 4 - Between Fair and Poor

Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED

Deficiency Location/Instance Basement - Boiler Room

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Basement - Boiler Room

Violations No violations recorded.

Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE

Deficiency Location/Instance Basement - Glass Storage

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 19 of 45

Page 20: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS Inspected

Deficiency Photo1

Basement - Glass Storage

Violations No violations recorded.

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Inspected

Foundation Walls Inspected

Condition 3 - Fair

Deficiency CRACKS, SPALLING

Deficiency Location/Instance Basement - Ash Hoist Vault

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Basement - Ash Hoist Vault

Violations No violations recorded.

Slab Structure Inspected

Condition 3 - Fair

Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE

Deficiency Location/Instance Basement - Ash Hoist Vault

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 20 of 45

Page 21: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

STRUCTURAL

VAULTS-BUNKERS

Slab Structure

Deficiency Photo1

Basement - Ash Hoist Vault

Violations No violations recorded.

Vault/Ash Hoist Doors and Framing Inspected

Condition 5 - Poor

Deficiency WATER INFILTRATION

Deficiency Location/Instance Basement - Ash Hoist Vault

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Basement - Ash Hoist Vault

Violations No violations recorded.

Deficiency MINOR RUSTING

Deficiency Location/Instance Basement - Ash Hoist Vault

Deficiency Quantity 3

Quantity Uom EACH

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 21 of 45

Page 22: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

STRUCTURAL Inspected

VAULTS-BUNKERS

Vault/Ash Hoist Doors and Framing

Deficiency Photo1

Basement - Ash Hoist Vault

Violations No violations recorded.

AUDITORIUM Inspected

InspectedInstance on 1st Floor (540 Seats)

Ceiling

InspectedInstance on 1st Floor (540 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor (540 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed H/C Lift

Does not ExistInstance on 1st Floor (540 Seats)

Fixed Seating

InspectedInstance on 1st Floor (540 Seats)

Condition 2 - Between Good and Fair

Deficiency DAMAGED/BROKEN/INOPERABLE

Deficiency Location/Instance Seats B/2, H/1, L/13, 15, 17, and others

Deficiency Quantity 11

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Seat H/1

Violations No violations recorded.

Floor Finish

InspectedInstance on 1st Floor (540 Seats)

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 22 of 45

Page 23: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

AUDITORIUM Inspected

Floor Finish

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor (540 Seats)

Stage

InspectedInstance on 1st Floor (540 Seats)

Stage Inspected

InspectedInstance on 1st Floor (540 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtain Rigging Inspected

InspectedInstance on 1st Floor (540 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtains Inspected

InspectedInstance on 1st Floor (540 Seats)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on 1st Floor (540 Seats)

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Exit Vestibule 9A

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Exit Vestibule 9A

Violations No violations recorded.

Deficiency STONE MOLDINGS: CRACKS/SPALLING

Deficiency Location/Instance Near Exit Vestibule 9A

Deficiency Quantity 5

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 23 of 45

Page 24: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

AUDITORIUM

Walls

Deficiency Photo1

Near Exit Vestibule 9A

Violations No violations recorded.

Deficiency STONE: CRACKS/SPALLING

Deficiency Location/Instance Auditorium - Near Exit Vestibule 9A

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Auditorium - Near Exit Vestibule 9A

Violations No violations recorded.

Window Curtains/Shades/Blinds

InspectedInstance on 1st Floor (540 Seats)

Condition 5 - Poor

Deficiency INOPERABLE CURTAINS

Deficiency Location/Instance Near windows at Left and right sides

Deficiency Quantity 3

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

CAFETERIA Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 24 of 45

Page 25: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

CAFETERIA

Door(s)

InspectedInstance on 1st Floor

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Main Entrance, rear corridor Entrance

Deficiency Quantity 3

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance

Rear corridor Entrance

Violations No violations recorded.

Fixed Equipment

Does not ExistInstance on 1st Floor

Floor Finish

InspectedInstance on 1st Floor

Condition 3 - Fair

Deficiency CONCRETE: CRACKS

Deficiency Location/Instance Near Toilet Room , Center, Near Exit 2, Near Serving Area

Deficiency Quantity 250

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 25 of 45

Page 26: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

CAFETERIA

Floor Finish

Deficiency Photo1

Near Toilet Room

Violations No violations recorded.

Sliding-folding Partition

Does not ExistInstance on 1st Floor

Stage

Does not ExistInstance on 1st Floor

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency SALT GLAZED BRICK: CRACKS/SPALLING

Deficiency Location/Instance Near Toilet Room , Near Serving Area

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Toilet Room

Violations No violations recorded.

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Rooms 222, 231, 313, 320, 321, Exit Vestibule 10, and others

Deficiency Quantity 17

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 26 of 45

Page 27: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s)

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 321

Violations No violations recorded.

Deficiency WOOD: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Main Entrance Vestibule

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance Vestibule

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET

Deficiency Location/Instance Room 321

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 27 of 45

Page 28: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency Photo1

Room 321

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Room 207

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 207

Violations No violations recorded.

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Rooms 101, 321

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 321

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 28 of 45

Page 29: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency STONE: CRACKS/SPALLING

Deficiency Location/Instance Main Entrance Vestibule, Corridor near Auditorium

Deficiency Quantity 75

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Auditorium

Violations No violations recorded.

Deficiency STONE MOLDINGS: CRACKS/SPALLING

Deficiency Location/Instance Main Entrance Vestibule, Corridor near Auditorium

Deficiency Quantity 25

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance Vestibule

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Main Entrance Vestibule

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 29 of 45

Page 30: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Deficiency Photo1

Main Entrance Vestibule

Violations No violations recorded.

Specialties Does not Exist

GYMNASIUM Inspected

InspectedInstance on 3rd Floor

Ceiling

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 3rd Floor

Condition 3 - Fair

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Office

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Office

Violations No violations recorded.

Fixed Equipment

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 30 of 45

Page 31: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

GYMNASIUM

Seating

InspectedInstance on 3rd Floor

Condition 3 - Fair

Deficiency DAMAGED FIXED SEATING

Deficiency Location/Instance Near Office

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Office

Violations No violations recorded.

Sliding-folding Partition

Does not ExistInstance on 3rd Floor

Stage

Does not ExistInstance on 3rd Floor

Walls

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency SALT GLAZED BRICK: CRACKS/SPALLING

Deficiency Location/Instance Near Stair 9, North side, South side, East side, West side

Deficiency Quantity 120

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Stair 9

Violations No violations recorded.

Window Curtains/Shades/Blinds

Does not ExistInstance on 3rd Floor

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 31 of 45

Page 32: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

KITCHEN Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor

Condition 3 - Fair

Deficiency METAL: DAMAGED LOUVER

Deficiency Location/Instance Serving Area

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Serving Area

Violations No violations recorded.

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIBRARY Inspected

InspectedInstance on Room 211

Built-in Furnishing

InspectedInstance on Room 211

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Ceiling

Does not ExistInstance on Room 211

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 32 of 45

Page 33: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

LIBRARY

Door(s)

InspectedInstance on Room 211

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Room 211

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on Room 211

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Near windows

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near windows

Violations No violations recorded.

LOCKER ROOM Does not Exist

MULTI-PURPOSE ROOM Does not Exist

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Does not Exist

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Partially

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Stairs AB/1, EF/1

Deficiency Quantity 6

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 33 of 45

Page 34: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Door(s)

Purpose of Action LEVEL 2

Deficiency Photo1

Stair AB/1

Violations No violations recorded.

Partition Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Railings Inspected

Condition 4 - Between Fair and Poor

Deficiency METAL: MISSING

Deficiency Location/Instance Cafeteria Exit 2 Vestibule, Exit Vestibule Near Auditorium MainEntrance, Exit Vestibule 9A

Deficiency Quantity 18

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Exit Vestibule Near Auditorium Main Entrance

Violations No violations recorded.

Stairs and Landings Inspected

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Stairs EF/2, 3

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 34 of 45

Page 35: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Stairs and Landings

Deficiency Photo1

Stair EF/2

Violations No violations recorded.

Deficiency STONE: BROKEN/MISSING

Deficiency Location/Instance Main Entrance Vestibule

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance Vestibule

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Stair 9/3

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 35 of 45

Page 36: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR Inspected

Walls Inspected

Stair 9/3

Violations No violations recorded.

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Rooms 229, 257,

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 229

Violations No violations recorded.

Floor Finish Inspected

Condition 3 - Fair

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance Room 229

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 229

Violations No violations recorded.

Stalls Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 36 of 45

Page 37: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

TOILET ROOMS - STAFF Inspected

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Rooms 258, 260, 357, 358

Deficiency Quantity 4

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 358

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance Rooms 258, 260

Deficiency Quantity 45

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 37 of 45

Page 38: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Floor Finish Inspected

Room 260

Violations No violations recorded.

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Rooms 258, 357

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 357

Violations No violations recorded.

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Inspected

Condition 5 - Poor

Deficiency FENCING DAMAGED

Deficiency Location/Instance 202nd Street

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 38 of 45

Page 39: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

SITE

CONTAINERIZATION

202nd Street

Violations No violations recorded.

Deficiency CONCRETE PAD DAMAGED

Deficiency Location/Instance 202nd Street

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

202nd Street

Violations No violations recorded.

Deficiency CONTAINER DAMAGED

Deficiency Location/Instance 202nd Street

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

202nd Street

Violations No violations recorded.

Drainage System for Asphalt Inspected

Catch Basins/Manhole - Surrounded by asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Asphalt Covering Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 39 of 45

Page 40: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

SITE

Drainage System for Concrete Inspected

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Inspected

Catch Basins/Manhole - Surrounded by Soil Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Soil Covering Inspected

Condition 4 - Between Fair and Poor

Deficiency DAMAGED

Deficiency Location/Instance 201st Street (3 locations)

Deficiency Quantity 18

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

201st Street

Violations No violations recorded.

DRINKING FOUNTAINS Does not Exist

FENCES Inspected

Condition 4 - Between Fair and Poor

Deficiency CHAIN LINK: DAMAGED POST/RAIL

Deficiency Location/Instance 201st Street

Deficiency Quantity 30

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

201st Street

Violations No violations recorded.

Deficiency WROUGHT IRON: DAMAGED/DETERIORATED

Deficiency Location/Instance Exit 2 Walkway, 115th Avenue , 202nd Street

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 40 of 45

Page 41: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

SITE

FENCES

Deficiency Quantity 640

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

202nd Street

Violations No violations recorded.

Deficiency CONCRETE CURB: DAMAGED/DETERIORATED

Deficiency Location/Instance 202nd Street, 115th Avenue , 201st Street

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

202nd Street

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Behind Mini Building

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 41 of 45

Page 42: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

SITE

PAVING

Student Non-Use

Asphalt

Deficiency Photo1

Behind Mini Building

Violations No violations recorded.

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance 115th Avenue, 202nd Street, 201st Street

Deficiency Quantity 350

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

201st Street

Violations No violations recorded.

Pavers Does not Exist

Student Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 4 - Between Fair and Poor

Deficiency POTHOLES

Deficiency Location/Instance Near Mini Building, Courtyard

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 42 of 45

Page 43: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

SITE

PAVING

Student Use

Asphalt

Deficiency Photo1

Courtyard

Violations No violations recorded.

Deficiency CRACKS - MINOR

Deficiency Location/Instance Schoolyard

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Schoolyard

Deficiency Quantity 1,200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Schoolyard

Violations No violations recorded.

Concrete Does not Exist

Pavers Does not Exist

Site Sidewalks & Walkways Inspected

Asphalt Inspected

Condition 3 - Fair

Deficiency HEAVING

Deficiency Location/Instance 201st Street Near Loading Area

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 43 of 45

Page 44: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

SITE

PAVING

Site Sidewalks & Walkways

Asphalt

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

201st Street Near Loading Area

Violations No violations recorded.

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED CURBS

Deficiency Location/Instance 201st Street, 202nd Street, 115th Avenue

Deficiency Quantity 85

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 4

Deficiency Photo1

115th Avenue

Violations 85691

Pavers Does not Exist

PLAYGROUNDS Inspected

InspectedInstance on Schoolyard

Benches

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 44 of 45

Page 45: NYC Department of Education - NYCSCASA : Q136 Architectural - Senior 2018-10-31 8:42 AM 2019-06-05 5:34 PM AA : Q136 Architectural - Associate 2018-10-31 9:09 AM 2018-11-15 3:04 PM

Question Response

SITE

PLAYGROUNDS

Benches

Does not ExistInstance on Schoolyard

Fence

Does not ExistInstance on Schoolyard

Pavement

Does not ExistInstance on Schoolyard

Play Equipment

InspectedInstance on Schoolyard

Condition 1 - Good

Deficiency No deficiencies recorded

Safety Surfacing

InspectedInstance on Schoolyard

Condition 1 - Good

Deficiency No deficiencies recorded

Unpaved Area

Does not ExistInstance on Schoolyard

PLAYING SURFACE Does not Exist

RETAINING WALLS Does not Exist

SEATING Does not Exist

SITE WALLS (NOT RETAINING WALLS) Does not Exist

STAIRS/RAMPS: EXTERIOR Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q136

PB/A&W Print Date: 9/13/2020Page 45 of 45