Asset: P.S. 131 - BROOKLYN, 4305 FT HAMILTON PKWY, New York, 11219 Inspection Id Inspection Type Time In Last Edited SA : K131 Architectural - Senior 2019-10-04 8:20 AM 2019-10-04 6:19 PM AA : K131 Architectural - Associate 2019-10-04 8:51 AM 2019-10-04 3:21 PM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment Areaways 2-5, cornice, louvers, leaders/gutters/downspouts/scuppers, exterior guards, window lintels, security lights, drainage for asphalt, fences, student non-use asphalt and concrete, student use asphalt and concrete, retaining walls, seating benches metal/wood/plastic, playing surface-schoolyard, playgrounds southeast and southwest were inaccessible due to scaffolding and netting at all facades. Heating and ventilating units in the penthouses (North, South MERs) were inaccessible due to construction materials stored on top of the roof hatches Principal(s) Information Principal Name Stamatina Hatzimichalis Organization P.S. 131 - Brooklyn Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal's comments are as follows: 1. Student and Staff Toilet Rooms are in need of an upgrade. 2. Additional electrical power is needed in Room 412 to support window a/c units. 3. Exterior stairs are in poor condition and need to be upgraded. Custodian Peter Foti Fireman Was not present Building Square Footage 86,000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4+B+PH+Attic Comments on the Number of Classrooms 48 Comments on the Year Built 1901 Student Population 853 Staff Population 115 Weather Fair Facade Photo Corner of Fort Hamilton Parkway and 44th Street - East view NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2019 - 2020 K131 PB/A&W Print Date: 9/14/2020 Page 1 of 52

NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Asset: P.S. 131 - BROOKLYN, 4305 FT HAMILTON PKWY, New York, 11219

Inspection Id Inspection Type Time In Last Edited

SA : K131 Architectural - Senior 2019-10-04 8:20 AM 2019-10-04 6:19 PM

AA : K131 Architectural - Associate 2019-10-04 8:51 AM 2019-10-04 3:21 PM

Asset Data

Question Answer

Was the building fully accessible for inspection No

Inspection Access Comment Areaways 2-5, cornice, louvers, leaders/gutters/downspouts/scuppers,exterior guards, window lintels, security lights, drainage for asphalt,fences, student non-use asphalt and concrete, student use asphalt andconcrete, retaining walls, seating benches metal/wood/plastic, playingsurface-schoolyard, playgrounds southeast and southwest wereinaccessible due to scaffolding and netting at all facades.

Heating and ventilating units in the penthouses (North, South MERs)were inaccessible due to construction materials stored on top of theroof hatches

Principal(s) Information

Principal Name Stamatina Hatzimichalis

Organization P.S. 131 - Brooklyn

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal's comments are as follows: 1. Student and Staff ToiletRooms are in need of an upgrade. 2. Additional electrical power isneeded in Room 412 to support window a/c units. 3. Exterior stairs arein poor condition and need to be upgraded.

Custodian Peter Foti

Fireman Was not present

Building Square Footage 86,000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 4+B+PH+Attic

Comments on the Number of Classrooms 48

Comments on the Year Built 1901

Student Population 853

Staff Population 115

Weather Fair

Facade Photo

Corner of Fort Hamilton Parkway and 44thStreet - East view

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 1 of 52

Page 2: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Main Entrance Photo

Facade A - Fort Hamilton Parkway

Roof Photo

Roof 4 - Southwest view

Have any Systems/Major Building Components been upgraded? Yes

Systems: Coping, Exterior Wall, Chimney, Bulkhead and Parapetmasonry, Roofing, Flashing, Roof Drains, Roof Barriers,Skylight/Roof Vent

Year: Under Construction

Systems: Exterior Stair repairs (main entrance)

Year: 2017

Systems: Exterior Stair repairs, Limited Coping replacement

Year: 2012

Systems: Exterior Stair replacement (Original Building), LimitedParapet repairs

Year: 2010

Systems: Slate Roofing replacement, Limited Foundation Wallwaterproofing (1938 building)

Year: 2007

Systems: Aluminum Double-hung Windows and Exterior Guardsreplacement

Year: 1994

Systems: Complete Roofing replacement except Slate Roof

Year: 1991

Have there been any New Building Additions? Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 2 of 52

Page 3: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Comments on New Building Additions 1938 (+43,000 SF)

Tandem Schools? No

Leased Space? No

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are all floors of the building accessible through compliant means? No

Are SOME floors other than the 1st floor and basement accessible through compliantmeans?

No

Do any of the following spaces exist on the First floor? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs

No

Do any of the following spaces exist in the Basement? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs

Yes

For the rooms that do exist, are SOME of them accessible in the Basement? Yes

Boys and Girls or Unisex accessible toilets exist in the Basement? No

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings Yes Yes

Interior Routes

Corridor and Lobby H/C Lifts No Yes

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies No Change in Elevation

Interior Elevators No

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms Room 221 Yes No Not on Accessible Route

Auditorium 1st Floor Yes No Not on Accessible RouteNo Stage Access

No No

Cafeteria Basement Yes Yes Yes No

Classrooms None on Accessible Route Yes No Not on Accessible Route

Computer Rooms Room 202 Yes No Not on Accessible Route

Gymnasium 3rd Floor Yes No Not on Accessible Route Yes No

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 3 of 52

Page 4: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

Rooms & Spaces

Library Room 212 Yes No Not on Accessible Route

Main Office Room 106 Yes No Not on Accessible Route

Multi-purpose Room No

Nurse's Room Room 201A Yes No Not on Accessible Route

Pool No

Science Lab No

Toilet Rooms (Boys) Basement Yes No Water ClosetArrangementTurning RadiusSink ArrangementNo Lever-type Hardware

Toilet Rooms (Girls) Basement Yes No No Lever-type HardwareWater ClosetArrangementTurning RadiusSink Arrangement

Toilet Rooms (Staff) Basement Yes No Water ClosetArrangementSink Arrangement

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Inspected

InaccessibleInstance on AW2-AW5

Instance Quantity 4

Instance Quantity Uom EACH

InspectedInstance on AW1, AW6

Instance Condition 3 - Fair

Instance Quantity 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 4 of 52

Page 5: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

AREAWAY

Instance Quantity Uom EACH

Deficiency AREAWAY STAIRS: DETERIORATEDTREADS/RISERS/NOSINGS

Roof Plan reference

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

AW1

Violations No violations recorded.

Deficiency AREAWAY DRAINS: DETERIORATED

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 5 of 52

Page 6: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

AREAWAY

Deficiency Photo1

AW1

Violations No violations recorded.

Deficiency AREAWAY SLAB: CRACKS AND SPALLING

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

AW6

Violations No violations recorded.

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Under Construction

COPING Under Construction

CORNICE Inaccessible

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 4 - Between Fair and Poor

Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MINORDETERIORATION

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 6 of 52

Page 7: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Roof Plan reference

Deficiency Quantity 3

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade G

Violations No violations recorded.

Deficiency METAL: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 7 of 52

Page 8: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Deficiency Photo1

Facade C

Violations No violations recorded.

Deficiency METAL CLAD: DETERIORATED DOOR - MAJORDETERIORATION

Roof Plan reference

Deficiency Quantity 3

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade L

Violations No violations recorded.

Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 8 of 52

Page 9: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade K

Violations No violations recorded.

DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Does not Exist

EXTERIOR WALLS Inspected

Material Type(s) Masonry

Replacement Quantity 50,000

Replacement Uom S.F.

Under ConstructionInstance on All Facades

Instance Quantity 50,000

Instance Quantity Uom S.F.

EXTERIOR SOFFITS Does not Exist

LOADING DOCK Does not Exist

LOUVER Inaccessible

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 11,000

Replacement Uom C.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 9 of 52

Page 10: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

PARAPETS Inspected

Under ConstructionInstance on All Facades

Instance Quantity 11,000

Instance Quantity Uom C.F.

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 24,000

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inaccessible

ROOF BARRIER Under Construction

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

Under ConstructionInstance on Slate Roof: Roof 1

Instance Quantity 4,000

Instance Quantity Uom S.F.

Under ConstructionInstance on Built-Up: Roofs 2-6

Instance Quantity 19,000

Instance Quantity Uom S.F.

Under ConstructionInstance on Metal: Roof 7

Instance Quantity 1,000

Instance Quantity Uom S.F.

ROOFING DRAINS Under Construction

Specialties Inspected

BULKHEAD/PENTHOUSE Inspected

Condition 4 - Between Fair and Poor

Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED LINTELS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 10 of 52

Page 11: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Deficiency Photo1

Roof 5 BH2

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOORAND FRAME

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE DOOR AND FRAME

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 5 BH2

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: GLAZED BLOCKOPEN JOINTS

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 11 of 52

Page 12: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Roof Plan reference

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE WALLS/INTERIOR: PLASTERCRACKS/SPALLING

Roof Plan reference

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 4 BH1

Violations No violations recorded.

Deficiency BULKHEAD/PENTHOUSE DOORS: DETERIORATED DOOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 12 of 52

Page 13: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

ROOF

Specialties

BULKHEAD/PENTHOUSE

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE DOOR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 4 BH1

Violations No violations recorded.

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Does not Exist

SKYLIGHT/ROOF VENT Under Construction

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Inspected

Condition 5 - Poor

Deficiency STONE: CRACKS/SPALLING - MINOR

Roof Plan reference

Deficiency Quantity 20

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 13 of 52

Page 14: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B

Violations No violations recorded.

Deficiency CAST IN PLACE CONCRETE: DETERIORATED EXPANSIONJOINT

Roof Plan reference

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade C1

Violations No violations recorded.

Deficiency STONE: BULGING/DISPLACED

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 14 of 52

Page 15: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

Deficiency STONE: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 15 of 52

Page 16: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency STONE: CRACKS/SPALLING - MAJOR

Roof Plan reference

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency STONE: DETERIORATED JOINTS AT COPING STONES

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 16 of 52

Page 17: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Roof Plan reference

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

RAILINGS Inspected

Condition 5 - Poor

Deficiency BROKEN BRACKET

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 17 of 52

Page 18: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

RAILINGS

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency DAMAGED

Roof Plan reference

Deficiency Quantity 40

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency RUST - MINOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 18 of 52

Page 19: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

RAILINGS

Roof Plan reference

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade C1

Violations No violations recorded.

STAIRS/RAMPS Inspected

Condition 5 - Poor

Deficiency STONE: DETERIORATED SUBSTRATE

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE SUBSTRATE AND RESET

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 19 of 52

Page 20: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Deficiency Photo1

Facade B

Violations No violations recorded.

Deficiency CONCRETE: CRACKS/SPALLING - MAJOR

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B

Violations No violations recorded.

Deficiency STONE: CRACKS, SPALLING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 20 of 52

Page 21: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade K

Violations No violations recorded.

Deficiency STONE: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 50

Quantity Uom L.F.

Potential Action REPOINT

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 21 of 52

Page 22: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Deficiency Photo1

Facade D

Violations No violations recorded.

Deficiency STONE: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 50

Quantity Uom L.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

WINDOWS Inspected

Replacement Quantity 12,000

Replacement Uom S.F.

EXTERIOR GUARDS Inaccessible

LINTELS Inaccessible

WINDOWS Inspected

Material Type(s) Aluminum, Steel, Solid Wood

InspectedInstance on Aluminum - Double Hung: All Facades

Instance Condition 3 - Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 22 of 52

Page 23: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

WINDOWS

WINDOWS

Instance Quantity 11,800

Instance Quantity Uom S.F.

Installation Year 1994

Source of Installation Custodial Staff

Deficiency ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE

Roof Plan reference

Elevation

Deficiency Quantity 80

Quantity Uom EACH

Potential Action REPLACE BALANCES

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

InspectedInstance on Steel: Facade C

Instance Condition 5 - Poor

Instance Quantity 100

Instance Quantity Uom S.F.

Installation Year 1920

Source of Installation Inspector Estimate

Deficiency STEEL: DETERIORATED

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 23 of 52

Page 24: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

WINDOWS

WINDOWS

Roof Plan reference

Elevation

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPLACE WINDOW

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade C

Violations No violations recorded.

InspectedInstance on Wood: Facades B, D

Instance Condition 5 - Poor

Instance Quantity 100

Instance Quantity Uom S.F.

Installation Year 1901

Source of Installation Inspector Estimate

Deficiency WOOD: DETERIORATED

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 24 of 52

Page 25: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

WINDOWS

WINDOWS

Roof Plan reference

Elevation

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPLACE WINDOW

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

Deficiency WOOD: BROKEN PANE

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 25 of 52

Page 26: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

EXTERIOR

WINDOWS

WINDOWS

Elevation

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 3 - Fair

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED MASONRYFIREPROOFING

Deficiency Location/Instance Basement Tunnel below connector wing, Kitchen Storage Room 1901building

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 26 of 52

Page 27: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

STRUCTURAL

COLUMNS/BEAMS/BEARING WALLS

Deficiency Photo1

Tunnel

Violations No violations recorded.

Deficiency CONCRETE COLUMNS/BEAMS:CRACKED/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Basement

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Header beam at the Ash Hoist Vault

Violations No violations recorded.

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING

Deficiency Location/Instance Basement Crawlspace, Boiler Room

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Crawlspace

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 27 of 52

Page 28: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

STRUCTURAL

COLUMNS/BEAMS/BEARING WALLS Inspected

Violations No violations recorded.

FLOOR STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Gymnasium Shower Room, Basement Boiler Room

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete, Masonry

Condition 3 - Fair

Deficiency BRICK: CRACKED/SPALLED

Deficiency Location/Instance Basement

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action RESTITCH

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Kitchen Storage Room

Violations No violations recorded.

Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED

Deficiency Location/Instance Basement

Deficiency Quantity 80

Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 28 of 52

Page 29: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Inspected

Foundation Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Slab Structure Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Vault/Ash Hoist Doors and Framing Inspected

Condition 5 - Poor

Deficiency WATER INFILTRATION

Deficiency Location/Instance Basement

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Ash Hoist Vault

Violations No violations recorded.

Deficiency DETERIORATED/DAMAGED VAULT/ASH HOIST DOORS ANDFRAMING

Deficiency Location/Instance Basement

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 29 of 52

Page 30: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

STRUCTURAL

VAULTS-BUNKERS

Vault/Ash Hoist Doors and Framing

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade L

Violations No violations recorded.

AUDITORIUM Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed H/C Lift

Does not ExistInstance on 1st Floor

Fixed Seating

InspectedInstance on 1st Floor

Condition 1 - Good

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor

Stage

InspectedInstance on 1st Floor

Stage Inspected

InspectedInstance on 1st Floor

Condition 1 - Good

Deficiency No deficiencies recorded

Stage Curtain Rigging Inspected

InspectedInstance on 1st Floor

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 30 of 52

Page 31: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

AUDITORIUM

Stage

Stage Curtain Rigging Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtains Inspected

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CAFETERIA Inspected

InspectedInstance on Basement

Ceiling

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

Does not ExistInstance on Basement

Floor Finish

InspectedInstance on Basement

Condition 4 - Between Fair and Poor

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Near windows, Center

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near windows

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 31 of 52

Page 32: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

CAFETERIA

Floor Finish

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Center, near Stairs

Deficiency Quantity 300

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Center

Violations No violations recorded.

Sliding-folding Partition

Does not ExistInstance on Basement

Stage

Does not ExistInstance on Basement

Walls

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on Basement

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance 4th Floor bridge

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 32 of 52

Page 33: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling Inspected

Deficiency Photo1

4th Floor bridge

Violations No violations recorded.

Door(s) Inspected

Condition 4 - Between Fair and Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Rooms 107,214, Main Entrance Vestibule (2), Exit Vestibule by Stair A

Deficiency Quantity 5

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 214

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Rooms 105,107,202,208, Corridor near Room 204, and others

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 33 of 52

Page 34: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency Photo1

Room 208

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Rooms 203,204,211,304,308, and others

Deficiency Quantity 800

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 203

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GLAZED BLOCK: CRACKS/SPALLING

Deficiency Location/Instance 2nd Floor bridge

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 34 of 52

Page 35: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

2nd Floor bridge

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Corridor near Rooms 201,426

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 201

Violations No violations recorded.

Specialties Does not Exist

GYMNASIUM Inspected

InspectedInstance on 3rd Floor

Ceiling

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 3rd Floor

Condition 3 - Fair

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Storage Room

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Storage Room

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 35 of 52

Page 36: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

GYMNASIUM

Door(s)

Violations No violations recorded.

Fixed Equipment

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Seating

InspectedInstance on 3rd Floor

Condition 3 - Fair

Deficiency DAMAGED FIXED SEATING

Deficiency Location/Instance Right Side

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Right Side

Violations No violations recorded.

Sliding-folding Partition

Does not ExistInstance on 3rd Floor

Stage

Does not ExistInstance on 3rd Floor

Walls

InspectedInstance on 3rd Floor

Condition 3 - Fair

Deficiency SALT GLAZED BRICK: CRACKS/SPALLING

Deficiency Location/Instance Near windows

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 36 of 52

Page 37: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

GYMNASIUM

Walls

Deficiency Photo1

Near windows

Violations No violations recorded.

Window Curtains/Shades/Blinds

Does not ExistInstance on 3rd Floor

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency DETERIORATED/TORN-OUT/MISSING

Deficiency Location/Instance Auditorium to Gymnasium Stair

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Auditorium to Gymnasium Stair

Violations No violations recorded.

KITCHEN Inspected

InspectedInstance on Basement

Ceiling

InspectedInstance on Basement

Condition 3 - Fair

Deficiency METAL PAN: DAMAGED/MISSING

Deficiency Location/Instance Near windows

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 37 of 52

Page 38: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

KITCHEN

Ceiling

Purpose of Action LEVEL 2

Deficiency Photo1

Near windows

Violations No violations recorded.

Door(s)

InspectedInstance on Basement

Condition 5 - Poor

Deficiency METAL: DETERIORATED DOOR

Deficiency Location/Instance Storage Room

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Storage Room

Violations No violations recorded.

Deficiency METAL: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Entrance, Mop Room

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 38 of 52

Page 39: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

KITCHEN

Door(s)

Deficiency Photo1

Entrance

Violations No violations recorded.

Floor Finish

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Storage Room

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Storage Room

Violations No violations recorded.

Walls

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Near windows

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 39 of 52

Page 40: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

KITCHEN

Walls

Deficiency Photo1

Near windows

Violations No violations recorded.

LIBRARY Inspected

InspectedInstance on Room 212

Built-in Furnishing

InspectedInstance on Room 212

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Ceiling

InspectedInstance on Room 212

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Room 212

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Room 212

Condition 3 - Fair

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Near circulation desk

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near circulation desk

Violations No violations recorded.

Walls

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 40 of 52

Page 41: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

LIBRARY Inspected

Walls

InspectedInstance on Room 212

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOCKER ROOM Inspected

InspectedInstance on 3rd Floor

Alternative use Yes

Ceiling

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 3rd Floor

Condition 3 - Fair

Deficiency WOOD: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Entrance

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Entrance

Violations No violations recorded.

Floor Finish

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Locker Room Lockers

Does not ExistInstance on 3rd Floor

Walls

InspectedInstance on 3rd Floor

Condition 4 - Between Fair and Poor

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Near windows

Deficiency Quantity 180

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 41 of 52

Page 42: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

LOCKER ROOM Inspected

Walls

Deficiency Photo1

Near windows

Violations No violations recorded.

MULTI-PURPOSE ROOM Does not Exist

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Inspected

InspectedInstance on 3rd Floor

Alternative use Yes

Ceiling

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

Does not ExistInstance on 3rd Floor

Floor Finish

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Partially

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Stairs A/4,B/4, Auditorium to Gymnasium Stair

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 42 of 52

Page 43: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Ceiling

Deficiency Photo1

Stair A/4

Violations No violations recorded.

Door(s) Inspected

Condition 5 - Poor

Deficiency METAL CLAD WOOD: DETERIORATED DOOR

Deficiency Location/Instance Stairs A/3,C/Basement,D/Basement (2),1

Deficiency Quantity 4

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair D/Basement

Violations No violations recorded.

Partition Inspected

Condition 2 - Between Good and Fair

Deficiency GLASS PANEL: DAMAGED/DETERIORATED

Deficiency Location/Instance Stair A/1,B/1,C/2,E/Basement

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 43 of 52

Page 44: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Partition

Deficiency Photo1

Stair E/Basement

Violations No violations recorded.

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs and Landings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GLAZED BLOCK: CRACKS/SPALLING

Deficiency Location/Instance Stairs B/2,3, Auditorium to Gymnasium/2,3

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair B/2

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Stair C/3

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 44 of 52

Page 45: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Walls

Deficiency Photo1

Stair C/3

Violations No violations recorded.

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Room 426

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 426

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance 1st Floor by Stair E

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 45 of 52

Page 46: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

TOILET ROOMS - STAFF

Floor Finish

Deficiency Photo1

1st Floor by Stair E

Violations No violations recorded.

Stalls Inspected

Condition 5 - Poor

Deficiency RUST - MAJOR

Deficiency Location/Instance Rooms 226,426

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 426

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Room 226

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 46 of 52

Page 47: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

TOILET ROOMS - STAFF

Walls

Deficiency Photo1

Room 226

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Room 307B

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 307B

Violations No violations recorded.

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Rooms 125,325

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 47 of 52

Page 48: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Door(s)

Deficiency Photo1

Room 125

Violations No violations recorded.

Floor Finish Inspected

Condition 3 - Fair

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance Rooms B10,108,208,225,308, and others

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room B10

Violations No violations recorded.

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Rooms 325,425

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 48 of 52

Page 49: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Walls

Deficiency Photo1

Room 425

Violations No violations recorded.

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Does not Exist

Drainage System for Asphalt Inspected

Catch Basins/Manhole - Surrounded by asphalt Inaccessible

Culverts - Asphalt Covering Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED COVER

Deficiency Location/Instance Exit 10 Walkway

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Exit 10 Walkway

Violations No violations recorded.

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Does not Exist

DRINKING FOUNTAINS Does not Exist

FENCES Inaccessible

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 49 of 52

Page 50: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

SITE

PAVING

Student Non-Use Inspected

Gravel Exists? No

Asphalt Inaccessible

Concrete Inaccessible

Pavers Does not Exist

Student Use Inspected

Gravel Exists? No

Asphalt Inaccessible

Concrete Inaccessible

Pavers Does not Exist

Site Sidewalks & Walkways Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance 44th Street

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

44th Street

Violations No violations recorded.

Pavers Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 4 - Between Fair and Poor

Deficiency DAMAGED CURBS

Deficiency Location/Instance 43rd Street, 44th Street, Fort Hamilton Parkway

Deficiency Quantity 50

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 50 of 52

Page 51: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Deficiency Photo1

43rd Street

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance 43rd Street, 44th Street, Fort Hamilton Parkway

Deficiency Quantity 1,300

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

43rd Street

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Inspected

InaccessibleInstance on Southeast

InaccessibleInstance on Southwest

PLAYING SURFACE Inspected

Playing Field Inspected

InaccessibleInstance on Schoolyard

Running Track Does not Exist

RETAINING WALLS Inaccessible

SEATING Inspected

Benches Inspected

Concrete Does not Exist

Metal/Wood/Plastic Inaccessible

Bleachers Does not Exist

SITE WALLS (NOT RETAINING WALLS) Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 51 of 52

Page 52: NYC Department of Educationclassrooms. 2. Some of the Toilet Room toilets have flushing issues (no deficiencies observed). 3. Due to construction all playground areas are inaccessible

Question Response

SITE

STAIRS/RAMPS: EXTERIOR

Railings Inspected

Condition 3 - Fair

Deficiency MISSING

Deficiency Location/Instance 43rd Street

Deficiency Quantity 8

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

43rd Street

Violations No violations recorded.

Site Cheek/flank Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs/ramps Inspected

Condition 2 - Between Good and Fair

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance 43rd Street

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

43rd Street

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

K131

PB/A&W Print Date: 9/14/2020Page 52 of 52