WSAA Product Appraisal 14/13 1 COPYRIGHT NUPIGECO SpA Italy PRODUCT APPRAISAL REPORT 14/13 EloFIT Electrofusion and butt welding fittings and EloPRESS Compression fittings for PE pipe AS/NZS 4129:2008 - Fittings for polyethylene (PE) pipes for pressure applications Publication Date: 28 November 2014

NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

  • Upload
    dokhue

  • View
    224

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 1

COPYRIGHT

NUPIGECO SpA Italy PRODUCT APPRAISAL REPORT 14/13 EloFIT Electrofusion and butt welding fittings and EloPRESS Compression fittings for PE pipe

AS/NZS 4129:2008 - Fittings for polyethylene (PE) pipes for pressure applications Publication Date: 28 November 2014

Page 2: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 2

COPYRIGHT

Document History

The following information indicates the changes made to this document.

Date Version File Location

24 October 2014 Peer Review Draft

U:\PP1 Industry Performance and Regulation\PP1-012 Product Appraisals\Civil Asset Infrastructure\2014\PA 1413 Nupigeco EF Elofit Elopress and Niron\Peer review\PA 14_13_Nupigeco SpA EF and butt welding fittings-final 24-10-14.docx

28 November 2014 Publication Date

U:\PP1 Industry Performance and Regulation\PP1-012 Product Appraisals\Civil Asset Infrastructure\2014\PA 1413 Nupigeco EF Elofit Elopress and Niron\Peer review\PA 14_13_Nupigeco SpA EF and butt welding fittings Publication Version.docx

Peer Reviewers

Name/Title Organisation Date

Infrastructure Product and Materials Expert Panel IPAM CoP 14/11/2014

Carl Radford, Product Appraisal Manager WSAA 28/11/2014

Approvals

Name/Title Signature Date

Carl Radford, Product Appraisal Manager, WSAA Carl Radford 28/11/2014

Page 3: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 3

Overview of WSAA The Water Services Association of Australia (WSAA) is the peak industry body that supports the Australian Urban Water Industry. Its members and associate members provide water and sewerage services to approximately 20 million Australians and many of Australia's largest industrial and commercial enterprises.

The Association facilitates collaboration, knowledge sharing, networking and cooperation within the urban water industry. It is proud of the collegiate attitude of its members which has led to industry-wide approaches to national water issues.

WSAA can demonstrate success in the standardisation of industry performance monitoring and benchmarking, as well as many research outcomes of national significance. The WSAA Executive retains strong links with policy makers and legislative bodies and their influencers, to monitor emerging issues of importance to the urban water industry. WSAA is regularly consulted and its advice sought by decision makers when developing strategic directions for the water industry.

WSAA was formed in 1995 as a non-profit organisation to foster the exchange of information relating to the provision of urban water services between industry, government and the community, and to promote sustainable water resource management.

The Association’s main activities focus on four areas:

1 .influencing national and state policies on the provision of urban water services and sustainable water resource management

2. promoting debate on environmentally sustainable development and management of water resources and the community health requirements of public water supplies

3. improving industry performance and establishing benchmarks and industry leading practices for water service processes; and

4. fostering the exchange of information on education, training, research, water and wastewater management and treatment and other matters of common interest.

Copyright

This document is copyrighted. Apart from any use as permitted under the Copyright Act 1968, no part of this document may be reproduced or transmitted in any form or by any means, electronically or mechanical, for any purpose, without the express written permission of Water Services Association of Australia Limited.

© Copyright 2014 by WATER SERVICES ASSOCIATION of Australia Limited All rights reserved.

Page 4: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 4

CONTENTS

1 EXECUTIVE SUMMARY ............................................................................................................................................... 6 1.1 Report Recommendation....................................................................................................................................... 7

2 THE APPLICANT ........................................................................................................................................................... 7 3 THE PRODUCT ............................................................................................................................................................. 7

3.2 EloFIT Electrofusion, elongated and short spigot fittings for butt fusion and for use with electrofusion socketed fittings ............................................................................................................................................................................ 7

3.2.1 EloFIT elongated and short spigot fittings for butt fusion and for use with electrofusion socketed fittings ........ 8 3.2.2 EloFIT Electrofusion Tapping and Branch Saddles .......................................................................................... 9

3.2.2.1 EloFIT Electrofusion Tapping Tee ............................................................................................................ 9 3.2.2.2 EloFIT Electrofusion Branch Saddles ..................................................................................................... 10

3.3 EloPRESS Compression fittings ............................................................................................................................ 10 3.4 EloPRESS Mechanical Saddles Clamp ................................................................................................................. 13 3.5 EloPRESS Poly to Copper transition fittings.......................................................................................................... 14

4 SCOPE OF THE APPRAISAL ..................................................................................................................................... 15 5 APPRAISAL CRITERIA ............................................................................................................................................... 19

5.1 Quality Assurance Requirements .......................................................................................................................... 19 5.2 Performance Requirements................................................................................................................................... 19 5.3 Compliance with Appraisal Criteria ........................................................................................................................ 19

5.3.1 Compliance with Quality Assurance Requirements ........................................................................................ 19 5.3.2 Compliance with Performance Requirements ................................................................................................. 20 5.3.3 Testing of electrofusion and compression fittings ........................................................................................... 21

5.4 Use in contact with drinking water ......................................................................................................................... 22 5.5 Compliance with Material Requirements ............................................................................................................... 22

5.5.1 Body................................................................................................................................................................ 22 5.5.2 Split ring .......................................................................................................................................................... 22 5.5.3 Thrust ring ....................................................................................................................................................... 22 5.5.4 Gasket O-ring made of NBR ........................................................................................................................... 23 5.5.5 Stainless steel inserts ..................................................................................................................................... 23 5.5.6 Zinc plated steel inserts .................................................................................................................................. 23 5.5.7 Brass inserts ................................................................................................................................................... 23 5.5.8 Screw Threads ................................................................................................................................................ 23 5.5.9 Reinforcement ring (for female thread) ........................................................................................................... 23

6 FITTING INSTRUCTIONS, TRAINING AND INSTALLATION ..................................................................................... 24 7 PRODUCT MARKING ................................................................................................................................................. 24 8 PACKAGING AND TRANSPORTATION ..................................................................................................................... 24 9 PRODUCT WARRANTY .............................................................................................................................................. 25 10 WATER AGENCY EXPERIENCE WITH THE PRODUCT OR FIELD TESTING REPORT ....................................... 25 11 DISCUSSION ............................................................................................................................................................. 26 12 OUTCOMES OF EXPERT PANEL PRODUCT REVIEW................................ ERROR! BOOKMARK NOT DEFINED. 13 LIFE EXPECTANCY .................................................................................................................................................. 27 14 FUTURE WORKS ...................................................................................................................................................... 27 15 REPORT RECOMMENDATION ................................................................................................................................ 27 16 DISCLAIMER ............................................................................................................................................................. 27

16.1 Issue of Report .................................................................................................................................................... 28 16.2 Limits on Reliance on Information and Recommendations.................................................................................. 28

16.2.1 Disclaimer of liability ..................................................................................................................................... 28

Page 5: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 5

16.2.2 Need for independent assessment ............................................................................................................... 28 16.3 No Updating ........................................................................................................................................................ 29 16.4 No Warranty ........................................................................................................................................................ 29

APPENDIX A – TECHNICAL MANUAL .......................................................................................................................... 30 APPENDIX B - QUALITY CERTIFICATIONS ................................................................................................................. 33 APPENDIX C – GASKET O-RING TECHNICAL DATA SHEET ..................................................................................... 37 APPENDIX D - WSAA PRODUCT SPECIFICATION ..................................................................................................... 38 APPENDIX E – PRODUCT MARKING ........................................................................................................................... 42 APPENDIX F - SUPPLIER CONTACTS ......................................................................................................................... 44 APPENDIX G – TYPE AND PERFORMANCE TESTING ............................................................................................... 45

Page 6: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 6

1 EXECUTIVE SUMMARY

NUPIGECO SpA’s EloFIT and EloPRESS range of plastics moulded fittings can be categorised as follows: (a) EloFIT electrofusion fittings; (b) EloFIT elongated spigot fittings for butt fusion and for use with electrofusion socketed

fittings and EloFIT short spigot fittings for butt fusion only; (c) EloPRESS compression fittings; and (d) EloPRESS Poly to Copper transition kit.

EloFIT electrofusion socketed, short and elongated spigot fittings and EloPRESS compression fittings are suitable for use with polyethylene (PE) pipes manufactured in accordance with AS/NZS 4130 - Polyethylene (PE) pipes for pressure applications, for conveyance of drinking water, recycled water and sewerage, in aboveground and below ground applications.

EloFIT electrofusion socketed, short and elongated spigot fittings and EloPRESS compression fitting are manufactured by NUPIGECO SpA in Busto Arsizio, close to Milan, Italy. EloFIT and EloPRESS fittings are distributed in Australia by NUPIGECO’s Brisbane Office (Pacific, Middle East & African branch) in Ashgrove, QLD 4060.

EloFIT and EloPRESS range of plastics moulded fittings were appraised for compliance with AS/NZS 4129:2008 Fittings for polyethylene (PE) pipes for pressure applications. The appraised fittings are Watermark Level 1 product certified, by SAI Global. The WaterMark certificate is shown in Appendix B. A copy of the schedule is available for downloading from the WSAA ‘Members Only’ IPAM Portal Website.

The EloFIT system is assembled through either the electrofusion or butt fusion process.

EloFIT electrofusion range of fittings includes straight coupler, end cap, 30⁰, 45° and 90° elbow, branch saddles, tapping tee, reducers, equal tee, reducing tee in sizes from DN 20 to DN 630 (product dependent). Refer to Table 1, in Section 4 for a complete range of appraised fittings.

EloFIT short and elongated spigot range of fittings includes 45° and 90° elbow long spigot, Cap long spigot, stub end, reducer long spigot, reducer short spigot, 90 Tee long spigot, and reducing tee spigot in sizes from DN 20 to DN 630 (product dependent). Refer to Table 1, in Section 3 for a complete range of appraised fittings.

The EloFIT electrofusion fittings, elongated and short spigot fittings are manufactured from black PE 100 resin and available in different pressures classes i.e. SDR 17 for PN 10, SDR 11 for PN 16, SDR 9 for PN 20 and SDR 7.4 for PN 25 at 20⁰C (size dependent).

Plastics moulded material of the fitting body for the EloFIT range of fittings complies with Table 1.1 of AS/NZS 4129:2008.

The EloPRESS compression fitting range includes 90° elbow, 90° elbow Poly to female/male thread, coupler, reducing coupler, flange adaptor, end connection male/female, end piece, 90° equal tee, reducing tee and Equal tee with male/female thread offtake in sizes from DN 20 to DN 110 (product dependent). The female threaded outlets have a Grade 316 stainless steel reinforcing ring (see Section 12 Discussion). Sizes suitable for the water industry include; DN’s 25, 32, 50, 63, 90 and larger if appropriate. Refer to Table 1, in Section 3 for a complete range of appraised fittings.

EloPRESS fitting is manufactured from compounds that meet the requirements of AS/NZS 4129:2008. The fitting body and locking nut is moulded from UV stabilised polypropylene copolymer (PP-B) black. The polypropylene copolymer (PP-B) black material is listed in Table 1.1 in AS/NZS 4129.

A tabular and diagrammatic summary of the product range is shown in Section 3.

The appraisal concludes that:

Page 7: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 7

• The NUPIGECO’s EloFIT electrofusion and butt welding fittings and EloPRESS compression fittings are ‘fit for purpose’ and suitable for use in water supply1 and sewer gravity, pressure and vacuum systems.

• The EloFIT electrofusion and butt welding fittings and EloPRESS compression fittings are suitable for use with PE pipe conforming to AS/NZS 4130.

• ISO Type 5 product certification of the EloFIT electrofusion and butt welding fittings and EloPRESS compression fittings has been adequately addressed to the satisfaction of WSAA Appraisal Network.

Note: 1 includes drinking and recycled water supply. 1.1 Report Recommendation It is recommended that WSAA members and associates accept/authorise the EloFIT electrofusion and butt welding fittings and EloPRESS compression fittings supplied by NUPIGECO SpA as listed in Section 4 - Scope of this report and in the Product Certification Schedules. This recommendation is subject to the pipelines / fittings being designed, installed and commissioned in accordance with NUPIGECO SpA recommendations, appropriate WSAA Codes and nominated Standards.

2 THE APPLICANT NUPIGECO SpA is a manufacturer and supplier of polyethylene pipe and fittings used for jointing PE pressure pipes. Nupigeco was founded in 2008 by the merger of NUPI SpA and GECO System SpA, two companies with over 30 years of experience in the field.

EloFIT electrofusion socketed, short and elongated spigot fittings and EloPRESS compression fitting are manufactured by NUPIGECO SpA in Busto Arsizio, close to Milan, Italy.

In Australia the EloFIT and EloPRESS fittings are distributed by NUPIGECO’s Brisbane Office in Ashgrove, QLD 4060.

3 THE PRODUCT NUPIGECO SpA product range consists of the following fittings: (a) EloFIT electrofusion fittings; (b) EloFIT elongated spigot fittings for butt fusion and for use with electrofusion socketed

fittings and EloFIT short spigot fittings for butt fusion only; (c) EloPRESS compression fittings; and (d) EloPRESS Poly to Copper transition kit.

EloFIT electrofusion socketed, short and elongated spigot fittings and EloPRESS compression fittings are suitable for use with polyethylene (PE) pipes manufactured in accordance with AS/NZS 4130 - Polyethylene (PE) pipes for pressure applications, for conveyance of drinking water, recycled water and sewerage, in above ground and below ground applications.

EloFIT and EloPRESS range of plastics moulded fittings were appraised for compliance with AS/NZS 4129:2008 Fittings for polyethylene (PE) pipes for pressure applications. The appraised fittings are Watermark Level 1 product certified, by SAI Global. The WaterMark Level 1 Certificate is shown in Appendix B. A copy of the Schedule is available for downloading from the WSAA ‘Members Only’ IPAM Portal Website.

3.1 EloFIT Electrofusion, elongated and short spigot fittings for butt fusion and for use with electrofusion socketed fittings The EloFIT electrofusion fittings, elongated and short spigot fittings are manufactured from black PE 100 resin and available in different pressures classes i.e. SDR 17 for PN 10, SDR 11 for PN 16, SDR 9 for PN 20 and SDR 7.4 for PN 25 at 20⁰C (size dependent).

Page 8: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 8

The black PE 100 resin used to manufacture these fittings is in accordance with approved resins listed in Table 1.1 of AS/NZS 4129.

EloFIT electrofusion range of fittings includes straight coupler, end cap, 30⁰, 45° and 90° elbow, branch saddles, tapping tee, reducers, equal tee, reducing tee in sizes from DN 20 to DN 630 (product dependent). Refer to Table 1, in Section 4 for a complete range of appraised fittings.

The range of EloFIT electrofusion and butt welding fittings are shown in Figure 1. The complete range in the scope of this appraisal is covered in Section 4.

EF Straight Coupler;

EF Straight coupler long;

EF End Cap;

EF 30 o 45 o 90o Elbow;

EF 90o Elbow w/support;

EF Reducer

EF Equal Tee w/Spigot

EF Reducing Tee w/Spigot

FIGURE 1: RANGE OF ELOFIT - ELECTROFUSION SOCKETED FITTINGS

3.1.1 EloFIT elongated and short spigot fittings for butt fusion and for use with electrofusion socketed fittings NUPIGECO SpA’s EloFIT elongated spigot fittings for butt fusion and for use with electrofusion socketed fittings and short spigot fittings for butt fusion only.

NUPIGECO SpA’s EloFIT with short spigots (for butt welding), and elongated fittings (for butt- and electrofusion welding) are made from the same PE 100 resin. The dimensional requirements for the EloFIT elongated spigot fittings complies with AS/NZS 4129 and the dimensional requirements for the short spigots comply with EN 12201-3.

Page 9: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 9

The range of EloFIT elongated and short spigot fittings for butt fusion and for use with electrofusion socketed fittings are shown in Figure 2. The complete range in the scope of this appraisal is covered in Section 4.

Long Spigot Elbow

Long Spigot 90° Tee

Long Spigot Cap

Spigot Reducer

Spigot Stub

FIGURE 2: RANGE OF ELOFIT ELONGATED AND SHORT SPIGOT FITTINGS FOR BUTT FUSION AND FOR USE WITH ELECTROFUSION SOCKETED FITTINGS

3.1.2 EloFIT Electrofusion Tapping and Branch Saddles 3.1.2.1 EloFIT Electrofusion Tapping Tee

The EloFIT EF Tapping Tee is a mechanical “self” tapping tee for property service connections from PE pipe and sealed using electrofusion. The EloFIT EF Tapping Tee is available in various sizes from DN 40 to DN 630 (with outlet from dn 20 to dn 63) at a maximum allowable operating pressure of 16 bar (PN 16, SDR 11) at 20⁰C.

There are three types available in this range.

Page 10: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 10

(a) EloFIT EF Tapping Tee with belt – from DN 140 / dn 20 to DN 315 / dn 63 (all size inclusive).

(b) EloFIT EF Top Load tapping Tee – from DN 355 - 630 / with only dn 63 outlet (c) EloFIT EF Tapping Tee with a rigid under clamp – from DN 40 / dn 20 to DN 180 / dn

32 (all size inclusive); DN 63 / dn 40-50-63; and DN 75 / dn63.

The ranges of EloFIT EF Tapping Tees are shown in Figure 3. The complete range in the scope of this appraisal is covered in Section 4.

EF Tapping Tee with belt EF Tapping Tee with a rigid under clamp

EF Top Load tapping Tee

FIGURE 3: ELOFIT - ELECTROFUSION TAPPING TEES 3.1.2.2 EloFIT Electrofusion Branch Saddles

The EloFIT EF branch saddle is a for property service connections from PE pipe and also sealed using electrofusion. A drilling machine is used on branch saddles fused on PE pipe.

The EloFIT EF branch saddle is available in various sizes from DN 40 to DN 315 (with outlet from dn 20 to dn 63) at a maximum allowable operating pressure of 16 bar (PN 16, SDR 11) at 20⁰C.

There are two types available in this range. (a) EloFIT EF Branch Saddle with belt – from DN 90 / dn 20 to DN 315 / dn 63 (all size

inclusive). (b) EloFIT EF Branch Saddle with a rigid under clamp – from DN 40 / dn 20 to DN 90 / dn

32 (all size inclusive); DN 40-75 / dn 40; and DN 63 / dn 50-63

The range of EloFIT EF Branch Saddles is shown in Figure 4. The complete range in the scope of this appraisal is covered in Section 4.

EF Branch Saddle with a rigid under clamp EF Branch Saddle with belt

FIGURE 4: ELOFIT - ELECTROFUSION BRANCH SADDLES 3.2 EloPRESS Compression fittings EloPRESS compression fittings in size range DN 20 to DN 63, manufactured from black copolymer polypropylene PP-B (Type 2) are rated to PN 16 (16 bars) and fittings in size range DN 75 to DN 110 are rated to PN 10 (10 bars) at 20⁰C.

Page 11: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 11

EloPRESS compression fitting range includes 90° elbow, 90° elbow Poly to female/male thread, coupler, reducing coupler, flange adaptor, end connection male/female, end piece, 90° equal tee, reducing tee and Equal tee with male/female thread offtake in sizes from DN 20 to DN 110 (product dependent). The female threaded outlets have a Grade 316 stainless steel reinforcing ring (see Section 5.5.9). Sizes suitable for the water industry include; DN’s 25, 32, 50, 63, 90 and 110.

Refer to Table 1, in Section 3 for a complete range of appraised fittings.

EloPRESS fitting is manufactured from compounds that meet the requirements of AS/NZS 4129:2008. The fitting body and locking nut are moulded from UV stabilised polypropylene copolymer (PP-B) black. The thrust ring is moulded from polypropylene copolymer (PP-B). The polypropylene copolymer (PP-B) material is listed in Table 1.1 in AS/NZS 4129.

The split ring is moulded from polyacetal resin. The O-ring seal is made of nitrile butadiene rubber (NBR), hardness 70sh, and black in colour.

Refer to Figure 5 for the material components of the EloPRESS compression system.

1 (body) and 5 (nut) – made of Black copolymer polypropylene PP-B (Type 2)

3 Thrust Ring – made of copolymer polypropylene PP-B

2 Gasket (O Ring) – made of 75 Shore nitrile rubber (NBR)

4 Split Ring – made of White polyacetal (Its conic shape ensures a perfect mechanical seal to the piping system when the nut is tightened to the fitting body)

FIGURE 5: COMPONENTS OF ELOPRESS COMPRESSION FITTINGS The range of EloPRESS Compression fittings are shown in Figure 6. The complete range in the scope of this appraisal is covered in Section 4.

Adapter Male thread;

Adapter Female thread;

Page 12: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 12

Elbow 90º;

Elbow 90⁰ Poly to Female thread;

Elbow 90⁰ Poly to Male thread;

Straight Coupler;

Reducing coupler;

Flange adaptor;

End connection Female;

90º Equal Tee;

Equal Tee with Female Thread Offtake;

Page 13: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 13

Equal Tee with Male Thread Offtake;

Reducing Tee;

FIGURE 6: RANGE OF ELOPRESS COMPRESSION FITTINGS 3.3 EloPRESS Mechanical Saddles Clamp The EloPRESS saddle clamps provides a means for the connection of property services to PE80 or PE100 polyethylene pipes in sizes DN 25 to DN 160 at a maximum allowable operating pressure of 10 bar (PN 10) at 20⁰C.

The EloPRESS saddle clamp is available both in standard version and with stainless steel 316 metal stiffening ring. The clamp saddles are composed of two black copolymer polypropylene PP-B (Type 2) parts, held together by AISI 316” stainless steel bolts, nuts and washers and 2 nitrile NBR rubber gaskets that ensure a leak tight seal. The number of bolts depends on the diameters: 2 bolts for DN 25 to DN 50, 4 bolts for DN 63 to DN 90 and 6 bolts for ø DN 110 to DN 160.

A watertight connection is achieved through the use of a combination hydrostatic lip / compression seal around the connection into the pipeline.

The nitrile rubber seal, that is fully compliant with the requirements of AS 1646:2007 Elastomeric seals for waterworks purposes also provide resistants to contaminants such as oils, diesel and other hydrocarbons.

EloPRESS fittings’ pressure rating differs as per size range; PN 16 for DN 16 to DN 63; PN 10 for DN 75 to DN 110 and PN 10 for clamp saddles.

1 Bolts and nuts – Stainless Steel 316 to EN ISO 4017

3 Gasket (O Ring) – made of 75 Shore nitrile rubber (NBR)

2 & 4 Body made of Black copolymer polypropylene PP-B (Type 2).

5 Reinforced ring –made of “AISI 316” stainless steel

FIGURE 7: COMPONENTS OF ELOPRESS SADDLE CLAMPS

A range of EloPRESS Saddle clamps are shown in Figure 8. The list of NUPIGECO EloPRESS Saddle clamps, included in the scope of this appraisal, is specified in Section 4.

Page 14: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 14

FIGURE 8: COMPONENTS OF ELOPRESS SADDLE CLAMP 3.4 EloPRESS Poly to Copper transition fittings The EloPRESS Poly to copper transition fittings can be used to join Polyethylene and copper pipes.

The EloPRESS Poly to copper transition fittings includes straight joiners, tees and elbows pre-assembled. Connection kits are also available for joining ½”, ¾” and 1” copper to 16mm, 25mm and 32mm PE pipe.

The stainless steel Grip Ring (Jaw) of the EloPRESS Poly to Copper connection is made from Stainless Steel 304 which provides the required axial restraint for the PE - Copper pipe joint. Grade 304 Stainless Steel is normal for these fittings and not recommended for water industry buried applications. Refer to Clause 11.

The water tight seal is created by the 'top hat' seals on the pipe (black and brown colour) and the captive O-ring inside the fitting body.

Refer to Figure 9 for the assembly of poly copper connector.

FIGURE 9: ASSEMBLY OF ELOPRESS POLY TO COPPER CONNECTOR A range of EloPRESS Transition (Poly to Copper) fittings are shown in Figure 10. The list of NUPIGECO EloPRESS Transition (Poly to Copper) fittings as listed as Item Nos. 16, 17 and 18 of Table 1 are excluded in this appraisal, and not specified in Section 4.

Page 15: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 15

Transition Coupler

Transition Elbow

Transitions Tee

FIGURE 10: ELOPRESS POLY TO COPPER TRANSITION FITTINGS

4 SCOPE OF THE APPRAISAL The scope of the appraisal is generally described in Section 3 above and Table 1 below: The SAI Global Schedule to WaterMark Licence No. WMKA21296 also provides a complete product listing including model identification, model name and product description including size.

To view the complete Licence and Schedule refer to the SAI Global web site at:

http://register.saiglobal.com/client/schedule.aspx?setID=SF01&custID=AS059993&appCertNo=WMKA21296. A copy of this 54 page list is available from the WSAA ‘Members Only’ IPAM Portal.

Page 16: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 16

COPYRIGHT

TABLE 1: NUPIGECO PRODUCTS LISTED IN THE WATERMARK SCHEDULE WMKA21296

Item WaterMark

Schedule Page Nos.

Product Description Pressure Class and SDR Rating Brand

1 2 Elbow 90 deg – 16, 20, 25, 32, 40, 50, 63, 75, 90, 110mm DN 16-63 (PN 10); DN 75-110 (PN 16)

Elopress Compression No SDR rating for compression fittings and mechanical tapping saddle as the material of make is PP-B (Type 2)

2 2 Elbow 90 deg Poly to Copper – 20, 25, 32mm DN 16-63 (PN 10)

3 3, 4 Elbow 90 deg Poly to Female thread – 16mm x ½” up to 110mm x 4”

DN 16-63 (PN 10); DN 75-110 (PN 16) 4 4, 5, 6 Elbow 90 deg Poly to Male thread – 16mm x ½” up to 110mm x 4”

5 6 Joiner (coupling) – 16mm x 16mm to 110mm x 110mm

6 6, 7, 8, 9 Mechanical Tapping Saddle – 20mm (½”), 25mm (½”, ¾”), 32mm (½”, ¾”, 1”), ….up to 110mm (½”, ¾”, 1”, 1¼” 1½”, 2”, 2½”, 3”)

PN 10

7 9, 10 Reducing Joiner/coupling – 20mm x 16mm to 110mm x 90mm

DN 16-63 (PN 10); DN 75-110 (PN 16)

8 10, 11, 12 End connection Female – 16mm x ½” to 110mm x 4”

9 12, 13 Flange adaptor – 50mm x 2” to 160mm x 6”

10 13, 14 End connection Male – 16mm x ½” to 110mm x 4”

11 14, 15 90 deg Equal Tee – 16 x 16 x 16mm to 110 x 110 x 110mm

12 15 End piece – 16mm to 110mm

13 15, 16, 17 Equal Tee with Female Thread Offtake – 20mm x ½” x 20mm to 110mm x 4” x 110mm

14 17, 18, 19 Equal Tee with Male Thread Offtake – 20mm x ½” x 20mm to 110mm x 4” x 110mm

15 19 Reducing Tee – 20 x 20 x 16mm to 110 x 100 x 90mm

16 1 Transition Elbow 90 deg Poly to Copper – From DN 16 x ½” to DN 25 x ¾”

DN 16-63 (PN 10)

EloPRESS Compression Transition Fittings Poly to Copper

17 5 Transition Coupler Poly to Copper – From DN 16 x ½” to DN 32 x ¾”

18 14 Transition 90 deg Tee Poly to Copper – From DN 20 x ½” to DN 25 x ¾”

Page 17: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 17

Item WaterMark

Schedule Page Nos.

Product Description Pressure Class and SDR Rating Brand

19 19, 27 45 deg Elbow long spigot – 32 mm to 400 mm DN 63-400 (PN 10, SDR 17); DN 25-400 (PN 16, SDR 11)

EloFIT butt welding

20 20, 27, 28 Cap long spigot - 20mm to 400mm

21 20, 21, 35, 36 Stub end – 20mm to 630mm DN 63-630 (PN 10, SDR 17); DN 25-630 (PN 16, SDR 11)

22 21, 36 Stub end short spigot – 63mm to 630mm DN 63-630 (PN 10, SDR 17); DN 25-630 (PN 16, SDR 11)

23 21, 22, 36, 37 90 deg Elbow Long Spigot - 25mm to 400mm

DN 63-400 (PN 10, SDR 17); DN 25-400 (PN 16, SDR 11)

24 21, 22, 23, 24, 46, 47, 48

Reducer long spigot – 32 x 25mm to 400-355mm

25 24, 25, 48, 49 Reducer short spigot – 250-200mm to 400-355mm

26 25, 51, 52 90 deg Tee long spigot – 25mm to 400mm

27 25, 26, 52, 53 Reducing Tee long spigot – 63-32mm to 225-160/125/110mm

28 22, 37, 38, 54 EF Coupling – 20mm to 710mm DN 20-710 (PN 16, SDR 11); DN 110-710 (PN 10, SDR 17); DN 63-450 (PN 25, SDR 7.4)

EloFIT Electrofusion

29 28, 29 EF End Cap – 20mm to 315mm

PN 16, SDR 11

30 29 EF 45 deg Elbow – 32 to 180mm

31 29 EF 30 deg Elbow – 90, 110 & 125mm

32 29, 30, 31, 32 Branch Saddle – 40 x (20, 25, 32, 40mm) to 315 x (20, 25, 32, 40, 50, 63mm)

33 30, 31 Branch Saddle D x D – 90 x 90mm to 125 x 125mm

34 31, 32, 33, 34 Branch Saddle High Volume – 110 x 75mm to 315 x 125mm

35 35 Branch Saddle Top Load – 355 x 160mm; 400 x 90/110/160mm; 630 x 63mm

36 37 EF 90 deg Elbow – 20mm to 180mm

37 37 EF 90 deg Elbow w/support – 90, 110 and 125mm

38 38 EF coupling long – 32, 40, 50, 63mm

39 38, 39, 40, 41, 42

Tapping Tee – 40 x 20/25/32mm to 315 x 20/25/32/40/50/63mm

Page 18: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 18

Item WaterMark

Schedule Page Nos.

Product Description Pressure Class and SDR Rating Brand

40 42, 43 Tapping Tee Medium Volume – 63-32mm to 180-20/25/32mm

PN 16, SDR 11 EloFIT Electrofusion

41 43 Tapping Tee Top Load 63-63mm

42 43, 44 Tapping Tee Zero Leakage – 90 x 32/40/50/63mm to 200/32/40/50/63mm

43 49, 50 EF Reducer – 32 x 25/20mm to 225 x 160mm

44 52 EF Equal Tee w/Spigot – 20mm to 180mm

45 52 EF Reducing Tee w/Spigot – 110-63mm to 125-90mm

46 53, 54 EF Sewage Coupling – 110mm to 710mm PN 10, SDR 17

Page 19: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 19

COPYRIGHT

5 APPRAISAL CRITERIA 5.1 Quality Assurance Requirements The WSAA product appraisal network accepts polyethylene Electrofusion and butt welding fittings and polypropylene compression fittings for pressure applications manufactured in compliance with AS/NZS 4129:2008 Fittings for polyethylene (PE) pipes for pressure applications and duly certified by means of an ISO Type 5 product certification scheme undertaken by a JAS-ANZ accredited Certification Assessment Body (CAB) or by an international accreditation system recognised by JAS-ANZ.

The manufacturer is generally expected to have a production management and control system that has been duly accredited in accordance with AS/NZS ISO 9001 as a prerequisite to undergoing a product certification audit.

5.2 Performance Requirements NUPIGECO’s EloFIT electrofusion and butt welding fittings and EloPRESS compression fittings have been appraised for compliance with AS/NZS 4129:2008 Fittings for polyethylene (PE) pipes for pressure applications.

Appraisal criteria is also determined by the WSAA Infrastructure Products and Materials Network and regularly reviewed to ensure that the criteria reflect the requirements of WSAA members.

The following Product Specifications are also relevant to this application.

WSA PS–207 Polyethylene (PE) Pipe for Pressure Applications - Water Supply and Sewerage

WSA PS–208 Polyethylene (PE) Moulded Pressure Fittings for Pressure Applications - Water Supply and Sewerage

WSA PS–312 Flange Gaskets and O-Rings

WSA PS–327 Tapping Saddles, Mechanical, for Use with Polyethylene (PE) Mains for Pressure Applications - Water Supply

WSA PS–329 Tapping Saddles, Electrofusion, for Use with Polyethylene (PE) Mains for Pressure Applications - Water Supply.

NOTE: Product Specifications are listed on the WSAA website. Additional specifications may at times be added and existing specifications may at times be changed. Water Agencies may have additional, fewer or modified specifications listed on their websites that take precedence.

A copy of the above Product Specifications can be found in Appendix D or downloaded from the WSAA website.

Note: 1 includes drinking and recycled water supply. 5.3 Compliance with Appraisal Criteria 5.3.1 Compliance with Quality Assurance Requirements NUPIGECO SpA in Busto Arsizio (Varese), Italy has been issued with Certificate of Registration No. KI-083608 by Kiwa Italia S.p.A to certify their Quality Management System as compliant with UNI EN ISO 9001:2008 for design and production by injection moulding of plastic fittings and valves for piping systems for the transport and distribution of liquid and gaseous fluids; design and production by extrusion of plastic and metalloplastic mono and multi-layer pipes for the transport of liquid and gaseous fluids under pressure; marketing of relative accessories.

Page 20: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 20

Kiwa is an independent highly qualified organization having certification as its core activity. Kiwa wants to be a Partner for progress on the basis of its qualities as a recognised and renowned certification company, relying on testing, inspection, training, technology and data services. Kiwa works for clients in many sectors with an emphasis on water, energy, construction, infrastructure, automotive & transport, agro, feed & food, safety & security, health & care and the environment. Clients come from manufacturing and process industries, (business) services, public and private utilities, (local) government agencies and international institutions.

Kiwa is globally active in over forty countries with offices in the Netherlands, Germany, Belgium, Italy, Scandinavia, Spain, the United Kingdom, Turkey, Taiwan, Peru and China which offer all of Kiwa's services. In over thirty countries additionally, Kiwa has established a reliable network of partners and colleagues in the field of certification.

In addition to the above certificates NUPIGECO SpA has also submitted the following Environmental Management System certificates:

a) Quality Italy (IQNet) and its partner CISQ / IIP S.r.l - Environmental Management System UNI EN ISO 14001:2004 - Certificate of Registration No. 116

b) Quality Italy (IQNet) - Environmental Management System ISO 14001:2004 - Certificate of Registration No. IT-58341

Refer to Appendix B for copies of the certificates.

5.3.2 Compliance with Performance Requirements ISO Type 5 Product Certification provides some on-going assurance that the product is manufactured and tested to comply with AS/NZS 4129:2008 and any amendments and revisions issued while the license is current.

NUPIGECO’s EloFIT electrofusion and butt welding fittings and EloPRESS compression fittings are ISO Type 5 Product Certified by SAI Global with License No. WMKA21296 to demonstrate ongoing compliance with the requirements specified in AS/NZS 4129:2008.

To view the complete Licence and Schedule refer to the SAI Global web site at:

http://register.saiglobal.com/client/schedule.aspx?setID=SF01&custID=AS059993&appCertNo=WMKA21296

NUPIGECO’s EloFIT electrofusion and butt welding system and EloPRESS compression system also have many international approvals:

a) UNI EN ISO 15494 Plastic piping systems for industrial applications - Polyethylene (PE100)

b) UNI EN 1555-3 Plastic piping systems for the supply of gaseous fuels - Polyethylene (PE80-PE100) - Part 3: Fittings

c) UNI EN 12201-3 Plastic piping systems for water supply - Polyethylene (PE80-PE100) - Part 3: Fittings

d) UNI 9561:2006 (Italy) - Pipes and fittings of plastic-compression fittings for mechanical splice for use with polyethylene pressure pipes for water distribution

e) GW 335-B3 P (09/2011) (Germany) - Plastics piping systems for gas and water distribution - Part B3 : Mechanical fasteners of plastics ( POM , PP ) for water distribution

Page 21: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 21

5.3.3 Testing of electrofusion and compression fittings AS/NZS 4129 calls up for a range of type tests in the following Sections: (a) Section 2 – Mechanical compression joint fittings

Clause 2.4.2 Assembled joint leaktightness

Clause 2.4.3 Liquid infiltration

Clause 2.4.4 Leaktightness when subjected to bending

Clause 2.4.5 Pull-out resistance (b) Section 3 – Electrofusion fittings

Table 3.2 Hydrostatic strength

Table 3.2 Decohesive strength

Table 3.2 Tapping tees impact resistance

Table 3.4 Short-term internal pressure

Table 3.4 Tensile load

Table 3.5 Melt flow rate

Table 3.5 Thermal stability (c) Section 4 – Mechanical Tapping Saddles

Clause 4.4.2 Liquid infiltration resistance

Clause 4.4.3 Leak resistance under pressure when subjected to bending

Clause 4.4.4 Resistance to internal pressure

Clause 4.4.5 Resistance to internal pressure with application of bending moment to outlet

Clause 4.4.6 Resistance to rotational and axial sliding

The type test and production test results have been confirmed to meet the requirements of AS/NZS 4129 by SAI Global WaterMark certification.

Type Tests have been carried out by Plumbing Testing Laboratory (PTL) QLD, TTR Institute Srl, Italy and NG Institute Srl, Italy. Refer to Appendix G for test results.

Process Verification and Batch Release Tests have been carried out “In-House” in NUPIGECO SpA Quality Control Laboratory in Busto Arsizo (VA) Italy using appropriate specialist testing equipment.

Refer to Appendix G for test results.

To demonstrate type testing compliance, WSAA requests appraisal applicants to submit typical type test and batch release test reports as per AS/NZS 4129:2008. NUPIGECO has submitted the

• Plumbing Testing Laboratory Report TT2086 dated 11 December 2008 for EloFIT electrofusion and EloPRESS compression fittings (previously known as GECO fittings) manufactured from HDPE (PE100) and Polypropylene PP-B (Type 2) respectively.

• Other type test reports conducted in Italy by NUPIGECO’s nominated laboratories TTR Institute Srl and NG Institute Srl

• Process Verification Test and Batch Release Test results carried out by NUPIGECO’s In-House Quality Control Laboratory.

Page 22: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 22

5.4 Use in contact with drinking water NUPIGECO SpA has submitted two Certificates of Analysis for polyethylene and polypropylene resins for compliance with AS/NZS 4020:2005. Both reports are prepared by NATA Accredited (No. 15773) AMS Laboratories Pty Ltd located in Silverwater NSW 2128. The reports concluded as follows:

a) Report No. 1211030 dated 11/10/2012 represents EloPRESS Polypropylene compression fitting sample 90o Elbow DN 16, model no. 10KG16.

Based on completion and evaluation of all tests on 11/10/2012, the product, 10KG16 EloPRESS Elbow 90o DN16; fully complies with the test requirements of AS/NZS 4020:2005 to cover a cold water application up to <40°C, at the recommended 0.1 (1/10) of 'in-the-product' exposure at (20 ± 2)°C. This testing exposure will cover the product range with lower or equivalent wetted surface area.

b) Report No. 1406838 dated 13/06/2014 represents EloFIT PE100 HDPE Electrofusion 90o Elbow DN 20, model no. 12EGEM020.

Based on completion and evaluation of all tests on 11/10/2012, the product, 10EGEM020 PE100 HDPE EloFIT Electrofusion Elbow 90o DN20; fully complies with the test requirements of AS/NZS 4020:2005 to cover a cold water application up to <40°C, at the recommended 0.1 (1/10) of 'in-the-product' exposure at (20 ± 2)°C. This testing exposure will cover the product range with lower or equivalent wetted surface area.

c) Report No. 1406838 covers EloFIT butt welding fittings as the material of make (i.e. HDPE PE100) is same as that of EloFIT electrofusion fittings.

The full test reports are being held on file by WSAA.

5.5 Compliance with Material Requirements Refer Clause 1.13 & 1.14, AS/NZS 4129

5.5.1 Body NUPIGECO SpA states that they only use PE 100 resins approved to PIPA and Australian standards sourced from consistent proven suppliers.

NUPIGECO has submitted an Inspection Certificates 3.1 according to EN 10204:2004 listing PE compound HE3490-LS-H which is listed in PIPA Industry Guideline POP004 – Polyethylene pipe compounds. The Certificate 3.1 (10AO-03098 dated 10.05.2010) has been issued by Borealis AG, Vienna Austria to NUPIGECO SpA.

EloPRESS fitting is manufactured from compounds that meet the material requirements listed in Table 1.1 in AS/NZS 4129-2008.

NUPIGECO uses black copolymer polypropylene PP-B (Type 2) for the EloPRESS body and locking nut.

5.5.2 Split ring The split ring is a material component of the EloPRESS compression fittings as shown in Figure 6. The split ring is moulded from Polyacetal (POM) listed in Table 1.1 in AS/NZS 4129.

5.5.3 Thrust ring The Thrust ring is a material component of the EloPRESS compression fittings as shown in Figure 6.

NUPIGECO uses copolymer polypropylene PP-B for the EloPRESS thrust ring.

Page 23: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 23

5.5.4 Gasket O-ring made of NBR The Gasket O-ring is a material component of the EloPRESS compression fittings. The Gasket O-ring is made of 75 Shore nitrile rubber (NBR).

EloPRESS compression fittings including Mechanical Clamp Saddle as shown in Figures 6 & 7. This NBR O- O-ring is manufactured by LAVEL GOMMA Rubber Specialist using compound code 01/AA70NBR in compliance with AS 1646.1, DVGW E70NBR in compliance with AS 1646.1, DVGW EN 681-1 and DVGW DIN EN 682 Type GBL and certified for use in contact with potable water according to DVGW-Arbeitsblatt W 270 - Testing and assessment of enhancement of microbial growth on non-metallic materials in contact with drinking water. Refer to Appendix D.

5.5.5 Stainless steel inserts The EloFIT transition fittings are made of Galvanised Iron, Stainless Steel or Copper and are assembled through threaded or push-fit joints. EloFIT transition fittings are excluded from the scope of appraisal. So none of the EloFIT electrofusion fittings included in the appraisal contains Stainless Steel inserts.

The EloPRESS Poly to Copper transition fittings as shown in figure 10 has a Stainless Steel 304 Grip Ring (Jaw) which provides the required axial restraint for the PE-Copper pipe joint.

Grade 304 Stainless Steel is normal for these fittings and not recommended for water industry buried applications. Refer to Clause 11.

The water tight seal is created by the 'top hat' seals on the pipe (black and brown colour) and the captive O-ring inside the fitting body.

See Figure 9 for the assembly of EloPRESS Poly to Copper connector.

5.5.6 Zinc plated steel inserts EloFIT transition fittings are excluded from the scope of approval. So none of the EloFIT electrofusion fittings included in the appraisal contains Zinc plated Steel inserts.

5.5.7 Brass inserts EloFIT transition fittings are excluded from the scope of approval. So none of the EloFIT electrofusion fittings included in the appraisal contains Brass inserts.

5.5.8 Screw Threads NUPIGECO’s EloPRESS compression fittings with screw threads (male or female) such as adaptors have pipe threads in compliance with EN 10226-1 which is compatible with the WSAA requirement of ISO 7.1. TTR Institute Srl, Italy Test Report No. 1103417-001 dated 26/08/2014 conforms that male thread is in line with ISO 7.1 and EN 10226.

The ISO 7.1 specification for sealing pipe threads requires male threads to be tapered and female threads to be parallel and EN 10226-1 carries the same specification.

5.5.9 Reinforcement ring (for female thread) The reinforcement ring for the female threaded fittings is Grade 316 stainless steel.

The purpose of the SS reinforcement ring is to increase hydraulic and mechanical strength of the thread, particularly in presence of high pressure and mechanical stress of the outlet, for example continuous vibration to the threaded connection or an oversized male thread connection. SS reinforcement rings are not required for compression fittings for female threads ½”-1¼” because the plastic thickness of the outlet has the hydraulic and mechanical strength to resist the pressure and mechanical stress. For thread sizes 1 ½”-4” a SS reinforcement ring is important as the plastic thickness is proportionally smaller while the integral pressure stress applied to the thread is greater than the smaller sizes (½”-1 ¼”).

Page 24: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 24

6 FITTING INSTRUCTIONS, TRAINING AND INSTALLATION For product information, PE pipeline design and other welding installation instructions, refer to Appendix A for list of NUPIGECO Technical Manual and how to access them.

WSAA has published the Polyethylene Pipeline Code - WSA 01 with significant input and peer review of the Plastics Industry Pipe Association of Australia (PIPA). WSAA recommend for overall design, installation, pipeline testing and installer training requirements for PE pipeline systems agencies refer to the WSAA Polyethylene Pipeline Code - WSA 01 available from the bookshop at the WSAA web site www.wsaa.asn.au.

Satisfactory completion of a recognised PE pipeline installation training program is a recommended pre-requisite for all PE pipeline installers and supervisors.

7 PRODUCT MARKING NUPIGECO EloFIT electrofusion and butt welding fittings and EloPRESS compression fittings are product certified to AS/NZS 4129 and the minimum marking is:

a) Manufacturer’s name or registered trademark (EloFIT or EloPRESS)

b) Date or batch code (e.g. 30/04/2014 or LOT: S-018850)

c) Nominal size (DN) of the pipe to which the fitting is suited (e.g. 63 mm)

d) Material identification – (grade, type etc. abbreviated in accordance with nominated standards such as AS/NZS 4131) (e.g. PE100)

e) Classification for which the fitting is to be used (e.g. PN16, SDR 11)

f) The number of this Standard i.e. AS/NZS 4129.

g) Additional information related to the fusion-jointing conditions shall be provided (e.g. temperature range and time)

The information of Items (b), (c), (d), (e), (f) and (g) may be provided on the body of the fitting, or provided using a label, pressure sensitive tape, or other suitable means on the product marking; however, the fitting body is the preferred labelling location.

Refer to Appendix E for Product Marking.

8 PACKAGING AND TRANSPORTATION NUPIGECO fittings are single bagged in a PE-foil for dust protection. In addition the fittings are multi-packaged in a cardboard box. Packaging lists are available on request. See Figure 11.

Page 25: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 25

FIGURE 11: NUPIGECO ELOFIT ELECTROFUSION FITTING PACKAGING AND

TRANSPORTATION

9 PRODUCT WARRANTY

Nupigeco Spa declares for EloFIT and EloPRESS fittings a warranty time of 36 months after delivery.

Nupigeco Spa guarantees the quality EloFIT and EloPRESS fittings when stocked for a maximum of 10 years (i.e. shelf life) at the following storage conditions:

a) Store in a dry, covered place, with temperature in the range -20°C to +50°C

b) Avoid exposure to direct sun and/or heating sources

c) Avoid stresses and shocks

d) Avoid contamination with water and/or chemicals

e) Remove the fitting from its plastic bag only immediately before installation

Nupigeco Spa declares for EloFIT and EloPRESS fittings a service life of minimum 50 years, under hydrostatic stress of 10 MPa at 20°C, provided the above conditions for storage are respected and manufacturer’s installation instructions are followed.

10 WATER AGENCY EXPERIENCE WITH THE PRODUCT OR FIELD TESTING REPORT

A field testing report of the NUPIGECO EloFIT electrofusion and butt welding fittings and EloPRESS compression fittings has not been submitted at this time.

While electrofusion, butt welding and compression fittings are a mature and widely installed product, the Australian water industry has had varied experience with the performance of these fittings. They are approved by many Water Agencies simply based on product certification and the knowledge that they are capable of performing well provided the installation is carried out correctly by competent well-trained installers.

Many Water Agencies are cautious particularly about the use of electrofusion fittings due to the lack of confidence in the installers. Because of the history of erratic installation quality, it is imperative that satisfactory completion of a recognised PE pipeline installation training program be a minimum pre-requisite for all PE pipeline installers. In addition it is recommended that for PE pipelines where electrofusion fittings are being used, an

Page 26: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 26

attentive site supervision regime be adopted using qualified, experienced supervisors until the individual installer or contractor can demonstrate competence in all aspects of installation.

11 DISCUSSION Where stainless steel is to be buried, 316 as a minimum is recommended. Performance of 316 can still vary greatly depending on the soil conditions. Well-drained soils with high resistivity (some sands) give far better results than waterlogged soil of low resistivity (such as wet clay or estuarine swamps where 316 is not recommended). Stainless steel should be buried in a drained trench that has been backfilled with sand or crushed aggregate. Additional corrosion protection is not normally recommended for buried stainless steel as a product such as petrolatum tape can induce crevice corrosion unless it is applied with great care.

Compression fittings rely on interface pressure being maintained between the elastomeric seal and the PE pipe surface to maintain a sealed connection. Mechanical fittings, including compression fittings are normally used on PE pipe ≤ DN 90. Mechanical fittings are also normally used for repairs or changes to the pipeline as the pipe surface preparation requirements are less stringent than electrofusion.

Some water agencies consider the smaller PE pipe and compression fittings used for main to meter property services as plumbing products and they are not included in Water Agency infrastructure. Many agencies use minor size PE mains in ‘Cul-De-Sac’ installations and find PP compression fittings adequate and ‘fit for purpose’.

For information on quality polyethylene pipeline design, installation and testing processes refer to the WSAA Polyethylene Pipeline Code - WSA 01.

For pipe sizes up to and including DN 90, joints shall be the compression or electrofusion type complying with AS/NZS 4129. For new installations of pipe in diameters greater than DN 90, butt welding or electrofusion coupling jointing shall be used. Only trained and certified welders shall perform weld jointing of pipelines. Spigot and socket fusion welding shall not be permitted. Electrofusion systems shall permit manual operation and be limited to the long bodied, 4.0/4.7 mm diameter single pin connections conforming to the requirements of AS/NZS 4129.

The use of mechanically bolted jointing systems with elastomeric seals to joint PE pressure pipelines exceeding DN 63 in diameter has generally been limited to applications where pipeline fusion jointing proves impracticable and shall be subject to acceptance by the Water Agency.

Mechanical jointing systems for PE pressure pipe shall be configured to incorporate elastomeric seals and pipe gripping joint components that are specifically designed to restrain PE pipe ends from axial movement relative to the joint and to retain joint seal notwithstanding internal positive and negative service pressure fluctuations. Mechanical jointing systems to be installed on PE pressure pipelines shall, for acceptance, incorporate a 316 stainless steel ring stiffening insert that is designed to provide internal support for and tightly fit the nominated PE pipe internal bore.

Mechanical compression and thread jointed pipe fittings not exceeding DN 63 in diameter (usually in property service and cul-de-sac applications) and fusion jointed fittings in pressure applications shall comply with the requirements of AS/NZS 4129. Mechanical tapping bands for reticulation (diameter < DN 315) PE pipelines shall comply with AS/NZS 4129 Section 4.

The jointing and seal configuration systems of AS/NZS 5065 PE and PP pipes and fittings for non-pressure applications shall be designed to provide pipeline joint structural and dimensional integrity and stability during handling, installation, hydrostatic testing, burial and subsequent long term service.

Page 27: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 27

Electrofusion jointing of PE pipelines offers a permanently sealed and jointed system provided the electrofusion process is carried out correctly. The electrofusion jointed PE pipeline has the potential to have life expectancy equal to and in some cases well beyond other pipeline materials and jointing systems. The PE material is corrosion resistant and correctly made joints are permanently fused to provide a high level of joint integrity against leakage and/or infiltration over the long-term. Similar to other plastic pipe systems, PE is susceptible to fatigue from cyclic pressure changes and additional design considerations must be made if used in a pumped pipeline. Refer to WSAA Technical Note TN4, plus design material information available from Nupigeco Australia.

PE pipelines are susceptible to permeation of specific organic chemicals (as are other pipeline systems) and care must be exercised if designing for installation in contaminated ground and/or brownfield sites. Seek further advice from Nupigeco Australia regarding such installations.

The appraisal concludes that:

• The NUPIGECO EloFIT electrofusion and butt welding fittings and EloPRESS compression fittings are ‘fit for purpose’ and suitable for use in water supply and sewer pressure and vacuum systems.

• The NUPIGECO EloFIT electrofusion and butt welding fittings and EloPRESS compression fittings are suitable for use with PE pipe conforming to AS/NZS 4130.

• The ISO Type 5 WaterMark Licence for the NUPIGECO range of fittings (i.e. EloFIT electrofusion and butt welding fittings and EloPRESS compression fittings) has been addressed to the satisfaction of WSAA Appraisal Network

12 LIFE EXPECTANCY Based on product certification to the nominated standard the NUPIGECO SpA EloFIT electrofusion and butt welding fittings and EloPRESS compression fittings have been rated ‘B’ – Life expectancy in excess of 50 years before replacement. This rating is only a general guide to life expectancy and may increase or decrease as a result of the quality of installation, system operating conditions, operating environment and other geographical and site specific factors.

13 FUTURE WORKS There are no outstanding future work items.

14 REPORT RECOMMENDATION It is recommended that WSAA members and associates accept/authorise the EloFIT electrofusion and butt welding fittings and EloPRESS compression fittings supplied by NUPIGECO SpA as listed in Section 4 – Scope of this report and in the WaterMark Product Certification Schedules as ‘fit for purpose’ in water supply and sewer pressure and vacuum applications. This recommendation is subject to the pipelines / fittings being designed, installed and commissioned in accordance with NUPIGECO Australia recommendations, appropriate WSAA Codes, including WSAA member integrated Codes and supplementary and nominated Standards.

15 DISCLAIMER This Product Appraisal Report (Report) is issued by the Water Services Association of Australia Limited on the understanding that:

This Report applies to the product(s) as submitted. Any changes to the product(s) either minor or major shall void this Report.

To maintain the recommendations of this Report any such changes shall be detailed and notified to the Product Appraisal Manager for consideration and review of the Report and

Page 28: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 28

appropriate action. Appraisals and their recommendations will be the subject of continuous review dependent upon the satisfactory performance of products.

WSAA reserves the right to undertake random audits of product manufacture and installation. Where products fail to maintain appraised performance requirements the appraisal and its recommendations may be modified and reissued. Appraisal reports will be reviewed and reissued at regular intervals not exceeding five (5) years.

The following information explains a number of very important limits on your ability to rely on the information in this Report. Please read it carefully and take it into account when considering the contents of this Report.

Any enquiries regarding this report should be directed to the Program Manager, Carl Radford, Phone: 03 8605 7601 email [email protected].

15.1 Issue of Report This Report has been published and/or prepared by the Water Services Association of Australia Limited and nominated Project Manager and peer group of technical specialists (the Publishers).

The Report has been prepared for use within Australia only by technical specialists that have expertise in the function of products such as those appraised in the Report (the Recipients).

By accepting this Report, the Recipient acknowledges and represents to the Publisher(s) and each person involved in the preparation of the Report that the Recipient has understood and accepted the terms of this Disclaimer.

15.2 Limits on Reliance on Information and Recommendations 15.2.1 Disclaimer of liability Neither the Publisher(s) nor any person involved in the preparation of the Report accept(s) any liability for any loss or damage suffered by any person however caused (including negligence or the omission by any person to do anything) relating in any way to the Report or the product appraisal criteria underlying it. This includes (without limitation) any liability for any recommendation or information in the Report or any errors or omissions.

15.2.2 Need for independent assessment The information and any recommendation contained (expressly or by implication) in this Report are provided in good faith. However, you should treat the information as indicative only. You should not rely on that information or any such recommendation except to the extent that you reach an agreement to the contrary with the Publisher(s).

This Report does not contain all information that a person might require for the purposes of assessing any product discussed or appraised within it (Product). The product appraisal criteria used in preparing this Report may not address all relevant aspects of the Product.

Recipients should seek independent evidence of any matter which is material to their decisions in connection with an assessment of the Product and consult their own advisers for any technical information required. Any decision to use the Product should take into account the reliability of that independent evidence obtained by the Recipient regarding the Product.

Recipients should also independently verify and assess the appropriateness of any recommendation in the Report, especially given that any recommendation will not take into account a Recipient’s particular needs or circumstances.

WSAA has not evaluated the extent of the product liability and professional indemnify insurance that the provider of the product maintains. Recipients should ensure that they evaluate the allocation of liability for product defects and any professional advice obtained

Page 29: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 29

in relation to the product or its specification including the requirements for product liability and professional indemnity insurance.

15.3 No Updating Neither the Publisher(s) nor any person involved in the preparation of this Report [has] [have] any obligation to notify you of any change in the information contained in this Report or of any new information concerning the Publisher(s) or the Product or any other matter.

15.4 No Warranty The Publisher(s) do[es] not, in any way, warrant that steps have been taken to verify or audit the accuracy or completeness of the information in this Report, or the accuracy, completeness or reasonableness of any recommendation in this Report.

Page 30: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 30

APPENDIX A – TECHNICAL MANUAL

The following technical literatures are available from the NUPIGECO Website:

1. NUPIGECO polyethylene fittings for water and gas under pressure 2011

2. EloFIT Instructions Manual 2011

3. EloFIT equipment 2011

4. EloFIT electrofusion fittings 2011

5. EloFIT butt welding fittings 2011

6. Nupigeco EloPRESS compression fittings 2012

You have to first register on the website with a username and password and then login to download the above documents listed under “Gas and Water distribution”. http://www.nupigeco.com/en/documentazione-en

Page 31: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 31

1. NUPIGECO Elofit Depl4ante 2011_GB-w.pdf

2. Elofit Instructions Manual 02-2013.pdf

3. Elofit List_Attrezzatura_Equipment_2011

4. Elofit List_Racc Elettrofusione_Electrofusion fittings_2011.pdf

Page 32: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 32

5. Elofit List_Raccordi a Codolo_Butt Welding Fittings_2011.pdf

6. NUPIGECO Elopress Depl4ante 2012_en_w.pdf

Page 33: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 33

APPENDIX B - QUALITY CERTIFICATIONS

TABLE B1: NUPIGECO SPA - QUALITY MANAGEMENT SYSTEM

Applicant’s Business: Via Stefano Ferrario, Zona Industriale Sud-Ovest, 21052 Busto Arsizio (Va), Italy

Quality System Standard UNI EN ISO 9001:2008

Registration No. KI-083608

Certifying agency Kiwa Italia S.p.A

First date of certification 1 October 1991

Current date of certification 14 July 2014

Expiry date of certification 13 July 2017

TABLE B2: NUPIGECO SPA - ENVIRONMENTAL MANAGEMENT SYSTEM

Applicant’s Business: Via Stefano Ferrario, Zona Industriale Sud-Ovest, 21052 Busto Arsizio (Va), Italy

Quality System Standard ISO 14001:2008

Registration No. IT 58341

Certifying agency IQNET The International Certification Network

First date of certification 26 September 2009

Current date of certification 13 September 2013

Expiry date of certification 12 September 2016

TABLE B3: NUPIGECO SPA - ENVIRONMENTAL MANAGEMENT SYSTEM

Applicant’s Business: Via Stefano Ferrario, Zona Industriale Sud-Ovest, 21052 Busto Arsizio (Va), Italy

Quality System Standard ISO 14001:2008

Registration No. IT 58341

Certifying agency IQNET The International Certification Network

First date of certification 26 September 2009

Current date of certification 13 September 2013

Expiry date of certification 12 September 2016

Page 34: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 34

TABLE B4: NUPIGECO SPA - HEALTH AND SAFETY MANAGEMENT SYSTEM

Applicant’s Business: Via Stefano Ferrario, Zona Industriale Sud-Ovest, 21052 Busto Arsizio (Va), Italy

Quality System Standard OHAS 18001:2007

Certificate No. KI 082350

Certifying agency Kiwa Italia S.p.A

First date of certification 29 April 2014

Current date of certification 29 April 2014

Expiry date of certification 28 April 2017

TABLE B5: NUPIGECO SPA - PRODUCT CERTIFICATION (WATERMARK)

Applicant’s Business: Via Stefano Ferrario, Zona Industriale Sud-Ovest, 21052 Busto Arsizio (Va), Italy

Product Standard/Spec. AS/NZS 4129:2008 - Fittings for polyethylene (PE) pipes for pressure applications

Certificate No. WMKA 21296

Certifying agency SAI Global

First date of certification 13 May 2009

Current date of certification 22 April 2014

Expiry date of certification 12 May 2019

Page 35: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 35

Page 36: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 36

Page 37: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 37

APPENDIX C – GASKET O-RING TECHNICAL DATA SHEET

Page 38: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 38

APPENDIX D - WSAA PRODUCT SPECIFICATION

Page 39: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 39

Page 40: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 40

Page 41: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 41

Page 42: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 42

APPENDIX E – PRODUCT MARKING

Page 43: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 43

Page 44: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 44

APPENDIX F - SUPPLIER CONTACTS

Jeffrey Booth

Manager – Pacific, Middle East & Africa

NUPIGECO SpA Italy

PO Box 47, Ashgrove QLD 4060

Brisbane Office, Australia

Mob: 0448 044 815

Email: [email protected]

Web: www.nupigeco.com

Page 45: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 45

COPYRIGHT

APPENDIX G – TYPE AND PERFORMANCE TESTING Type Tests and Batch Release Tests for NUPIGECO’s EloFIT and EloPRESS fittings – AS/NZS 4129:2008

Type tests (TT) Characteristics Clause,

Table Requirements Test Method Frequency WSAA Comments

Dimensions 1.8 Threaded end connections on fittings

AS ISO 7.1 or AS 1722.2

At change in joint design Nupigeco has submitted the below four reports to demonstrate the type tests: • TTR Institute Srl, Italy’s test report No. 1102194-001 dated

25/09/2013 and test report No. 1103417-001 dated 26/08/2014

• NG Institute Srl, Italy’s test report No. 1101414-001 dated 14/11/2011 and test report No. 1101385-001 dated 04/11/2011.

Complies.

1.9 General dimensions for ends suitable for connection to other pipe systems

As appropriate At change in joint design

1.10 Flanged ends ISO 3126 At change in joint design

3.4.2 Electrofusion sockets ISO 3126 At any change in design

3.4.3 Electrofusion spigots ISO 3126 At any change in design

3.4.4 Tapping tees ISO 3126 At any change in design

Material Properties - General

1.12 Effect on water AS/NZS 4020 At any change in material, formulation or design or every five years whichever occurs first

NUPIGECO SpA has submitted two Certificates of Analysis for polyethylene and polypropylene resins for compliance with AS/NZS 4020:2005. Both reports are prepared by NATA Accredited (No. 15773) AMS Laboratories Pty Ltd located in Silverwater NSW 2128. The reports concluded as follows: • Report No. 1211030 dated 11/10/2012 represents

EloPRESS Polypropylene compression fitting sample 90o Elbow DN 16, model no. 10KG16.

Based on completion and evaluation of all tests on 11/10/2012, the product, 10KG16 EloPRESS Elbow 90o DN16; fully complies with the test requirements of AS/NZS 4020:2005 to cover a cold water application up to <40°C, at the recommended 0.1 (1/10) of 'in-the-product' exposure at (20 ± 2)°C. This testing exposure will cover the product range with lower or equivalent wetted surface area. • Report No. 1406838 dated 13/06/2014 represents EloFIT

PE100 HDPE Electrofusion 90o Elbow DN 20, model no.

Page 46: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 46

12EGEM020. Based on completion and evaluation of all tests on 11/10/2012, the product, 10EGEM020 PE100 HDPE EloFIT Electrofusion Elbow 90o DN20; fully complies with the test requirements of AS/NZS 4020:2005 to cover a cold water application up to <40°C, at the recommended 0.1 (1/10) of 'in-the-product' exposure at (20 ± 2)°C. This testing exposure will cover the product range with lower or equivalent wetted surface area. Report No. 1406838 covers EloFIT butt welding fittings as the material of make (i.e. HDPE PE100) is same as that of EloFIT electrofusion fittings. Complies.

Material Properties - Plastics

1.13.1 Long-term behaviour ISO 1167 and ISO 9080

At any change in material

Nupigeco Spa Italy Test Reports. Complies.

1.13.2 Resistance to internal pressure ISO 1167 At any change in design At any change in material

1.13.3 Light transmission ISO 7686 At any change in materials other than black materials

1.13.4 Chemical resistance for fuel gas applications

AS/NZS 4131 At any change in material Not applicable for water supply (potable and recycled) applications

Page 47: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 47

Characteristics Clause, Table Requirements Test Method Frequency WSAA Comments

Mechanical compression joint fittings

2.4.2 Assembled joint leaktightness ISO 1167 At any change in design Plumbing Testing Laboratory (PTL) QLD Test Report TT2086 dated 17/12/2008. The specimens (63mm compression coupler) were subject to hydrostatic pressures of 960 kPa at 20° ± 2°C for 1000 hours and 960 kPa at 40° ± 2°C for 1000 hours. No leakages or other failure occurred. Complies

2.4.3 Liquid infiltration ISO 3459 At any change in design Plumbing Testing Laboratory (PTL) QLD Test Report TT2086 dated 17/12/2008. The specimen ((63mm compression coupler) was tested generally in accordance with ISO 3459:1976, except that the test was carried out by applying a vacuum while submerged in a water bath. The specimen was subjected to vacuums of -10 +5, -0 kPa and -80 ± 5kPa for 1 hour each. No leakage occurred. Complies.

2.4.4 Leaktightness when subjected to bending

ISO 3503 At any change in design Plumbing Testing Laboratory (PTL) QLD Test Report TT2086 dated 17/12/2008. The specimen (32mm compression tee) subjected to a hydrostatic pressure of 2.88 MPa for 1 hour. No leakage occurred. Complies.

2.4.5 Pull-out resistance ISO 3501 At any change in design Plumbing Testing Laboratory (PTL) QLD Test Report TT2086 dated 17/12/2008. The specimen (63mm compression tee) was subjected to a longitudinal pull-out force of 1094 N for 1 hour. No separation, slippage, or other failure occurred. Complies.

Page 48: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 48

Characteristics Clause, Table Requirements Test Method Frequency WSAA Comments

Electrofusion fittings

Table 3.2 Hydrostatic strength ISO 1167 At any change in design TTR Institute Srl, Italy Test Report No. 1102194-009 dated 25/09/13 and 1102194-010 dated 25/09/13 conducted on three samples of 63mm, PE100, SDR11, PN16 EloFIT EF coupler has been submitted. Test temp 80 deg C, sample tested in water at 10 Bar for 6 hr conditioning, test period 1050 hr. No failure was reported. Complies.

Table 3.2 Decohesive strength ISO 13954 ISO 13955

At any change in material At any change in material

TTR Institute Srl, Italy Test Report No. 1102194-004 dated 25/09/2013 conducted on a 63mm, PE100, SDR11, EloFIT electrofusion coupling has been submitted. At 23 deg C test temperature, percentage brittle failure decohesion < 33.3%. Nupigeco has also submitted additional test report No. 1102194-005 dated 17/08/13, 1102194-006 dated 25/09/13, 1102194-007 dated 25/09/13 and 1102194-008 dated 25/09/13 in support of this type test. Actual % brittle failure = 0. Complies.

Table 3.2 Tapping tees impact resistance ISO 13957 At any change in material TTR Institute Srl, Italy Test Report No. 1101860-003 dated 10/04/13 conducted on an Electrofusion tapping tee DN110 x DN63PE, PE100, SDR11 has been submitted as per UNI EN 1716:1998 which is equivalent to ISO 13957:1997. Pre-test temperature 0 deg C, Drop height 2m, Striker Mass 2.5 kg; Sample was hitted on two opposite sides, tested with air pressure of 26.71 mbar at 23.8 deg C. No leakage. Complies.

Table 3.4 Short-term internal pressure Appendix E At any change in material Plumbing Testing Laboratory (PTL) QLD Test Report TT2086 dated 17/12/2008. Complies. This type test was satisfied under Clause 3.5.2*

Table 3.4 Tensile load Appendix F At any change in material GECO System SpA, Italy Test Report No. MOD M1351 ed.1 rev. 1 dated 22/01/2009 has been submitted. Test was conducted on three samples ‘Fitting Code EME040, Batch W000923 under test conditions 5mm/min at 23 Deg C. Minimum elongation 25% before pipe yields. Test elongation value 30%, No leak was observed after maximum elongation. Complies.

Page 49: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 49

Characteristics Clause, Table Requirements Test Method Frequency WSAA Comments

Electrofusion fittings

Table 3.5 Melt flow rate ISO 1133 At any change in material TTR Institute Srl, Italy Test Report No. 1102194-003 dated 25/09/13 conducted on a 63mm, PE100, SDR11, EloFIT electrofusion coupling has been submitted. Sample raw material: HE3490 IM 20B09727 (MFR 5kg, 190 deg C, 0.5 gram/10 min). Test temp 190 deg C, Pre heating time 5 min, test load 5 kg, cut-off time interval 240 Sec, three samples have undergone through type test. (Tested MFR of 3 samples – 0.496, 0.499 and 0.498 g/10 min); Average MFR 0.5 gram/10 min, sample deviation – none. Complies.

Table 3.5 Thermal stability (or Oxidation Induction Time – OIT as per ISO11357-6:2008 or EN12201 or EN1555

ISO/TR 10837 At any change in material TTR Institute Srl, Italy Test Report No. 1102194-002 dated 25/09/13 conducted on three samples of 63mm, PE100, SDR11, EloFIT electrofusion coupling has been submitted. Test temp 210 deg C, sample mass 23.9 gram, tested sample surface – external, sample position – internal. OIT for three samples – 32.1 min, 31.4 min and 32.6 min, all of them are > 20 min. Complies.

*3.5.2 Relationship between fitting and pipe wall thickness (Table 3.4 – Short-term internal pressure resistance). Failure pressure shall be greater than pressure equivalent of 2.00 x MRS calculated for thickest walled pipe for which fitting has been designed.

Appendix E of AS/NZS 4129 (ISO 1167)

At any change in material The 50mm electrofusion tee was tested at 80°C for 165 hours at 960 kPa (9.6 MPa), the sample was also submitted to a 100 hour test at 20°C. The test pressure applied is 9.6 MPa (8 MPa); MRS for PE100, PN16, SDR11 pipe is 4 MPa, so 2.00 x 4 = 8 MPa. There was no leakage observed at both testing. Complies.

Mechanical tapping saddles

4.4.2 Liquid infiltration resistance ISO 3459 At any change in design Plumbing Testing Laboratory (PTL) QLD Test Report TT2086 dated 17/12/2008. The specimen (140mm x 75mm tapping saddle) was tested generally in accordance with ISO 3459:1976, except that the test was carried out by applying a vacuum while submerged in a water bath. The specimen was subjected to a vacuum of -10 +5, -0 kPa and -80 ± 5 kPa for 1 hour each. No leakage occurred. Complies.

Page 50: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 50

Characteristics Clause, Table Requirements Test Method Frequency WSAA Comments

Mechanical tapping saddles

4.4.3 Leak resistance under pressure when subjected to bending

ISO 3503 At any change in design Plumbing Testing Laboratory (PTL) QLD Test Report TT2086 dated 17/12/2008. The specimen (140mm x 75mm tapping saddle) was tested in accordance with ISO 3503:1976. The specimen was subjected to a hydrostatic pressure of 2.88 MPa for 1 hour. No leakage occurred. Complies.

4.4.4 Resistance to internal pressure ISO 1167 At any change in design Plumbing Testing Laboratory (PTL) QLD Test Report TT2086 dated 17/12/2008. The specimens (75mm x 25mm tapping saddle) were tested in accordance with ISO 1167:1996. The specimens were subjected to hydrostatic pressures of 960 ± 0.04 MPa at 20° ± 2°C for 1007 hours and at 40° ± 2°C for 1010 hours. No leakage or other failure occurred. Complies.

4.4.5 Resistance to internal pressure with application of bending moment to outlet

ISO 1167 and Clause 4.4.5 of this Standard (i.e. AS/NZS 4129)

At any change in design Plumbing Testing Laboratory (PTL) QLD Test Report TT2086 dated 17/12/2008. The specimen (125mm tapping saddle) was tested generally in accordance with Clause 4.4.5, except for the following variations to the test method: • The test was carried out on PN16 pipe, subjected to the test

pressure for PN16. • The centre section of the test pipe was prevented from

buckling under pressure by two guide plates. A bending moment of 50 Nm was applied to the specimen. No leakage, fracture, cracks or other failure occurred. Complies.

4.4.6 Resistance to rotational and axial sliding

Clauses 4.4.6.2 and 4.4.6.3 of this Standard (i.e. AS/NZS 4129)

At any change in design Plumbing Testing Laboratory (PTL) QLD Test Report TT2086 dated 17/12/2008. The specimen (125mm tapping saddle) was tested generally in accordance with Clause 4.4.6. Test was carried out on PN16 pipe. A rotational moment of 50N.m and a sliding force of 125 N were applied to the specimen for 1 minute each. No movement occurred during either test. Complies.

Page 51: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 51

Batch release tests (BRT)

Characteristics Clause, Table Requirements Test Method Frequency Comments

Material properties - Metallic

1.14.1.2 Corrosion resistance of deemed corrosion resistance of metallic materials

Composition to relevant standard

Each batch

Not applicable as EloPRESS Transition compression fittings are excluded.

1.14.1.3 Corrosion protection of other metallic materials

AS/NZS 4158 Each batch

1.14.2 Resistance to internal pressure and freedom from defects

Watertightness test of AS 3688

Each batch

1.14.3 Dezincification AS 2345 Each batch

Mechanical compression joint fittings

1.8 Dimensions AS ISO 7.1 AS 1722.2

As per factory quality system

TTR Institute Srl, Italy Test Report No. 1103417-001 dated 26/08/2014 conforms that male thread is in line with ISO 7.1 and EN 10226. Complies.

1.11 Freedom from defects Visual As per factory quality system

Three samples of 32mm compression fittings have been tested by Nupigeco Spa Italy Test Report No. MOD. M350 ed.0 rev.o dated 29/01/14. Complies.

1.15 Marking Visual As per factory quality system

Same report as above. Fitting code: KCMAN32, Branch No. R002065. Complies.

Electrofusion fittings

1.11 Freedom from defects Visual As per factory quality system

Three samples of 63mm EF fittings have been tested by Nupigeco Spa Italy Test Report No. MOD. M135AG ed.1 rev.1 dated 15/07/14. Complies. Same report as above. Fitting code: EME063, Batch: R014996, Raw Batch No. E435945. Complies.

1.15 Marking Visual As per factory quality system

3.4.1 Dimensions ISO 3126 As per factory quality system

Table 3.2 Hydrostatic strength 80o C > 165 h ISO 1167 As per factory quality system

Three samples of 63mm EF fittings have been tested by Nupigeco Spa Italy Test Report No. MOD. M135AG ed.1 rev.1 dated 15/07/14. Complies.

Table 3.4 Short-term internal pressure Appendix E As per factory quality system

63mm EF fittings have been tested by Nupigeco Spa Italy Test Report No. MOD. M120B ed.III rev.2 dated 24/07/14. Complies.

Table 3.4 Tensile load Appendix F As per factory quality system

Three samples of 63mm EF fittings have been tested by Nupigeco Spa Italy Test Report No. MOD. M135D ed.1 rev.2 dated 15/07/14996. Complies.

Page 52: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 52

Characteristics Clause, Table Requirements Test Method Frequency Comments

Table 3.5 Melt flow rate ISO 1133 As per factory quality system (Note 1)

Nupigeco Spa Test Report No. MOD. M135B ed.1 rev.2 dated 29/01/2014. Fitting code KCMAN32. Complies.

Table 3.5 Thermal stability ISO TR 10837 As per factory quality system (Note 1)

Three samples of 63mm EF fittings have been tested by Nupigeco Spa Italy Test Report No. MOD. M135E2 ed.01 rev.2 dated 15/07/14, as per EN 728 / EN 11357. Batch R04996 Min request period at 200 deg C > 20 min – Pass; Min request period at 210 deg C > 9 min. Isotherm 210 deg C 35 min. Complies.

- Electrical resistance Refer to manufacturer

Each fitting Three samples of 63mm EF fittings have been tested by Nupigeco Spa Italy Test Report No. MOD. M135E1 ed.0 rev.3 dated 15/07/14, Batch R014996. Welding safety coefficient NF T54-969. Welding condition: 40V, t = 108s, E = 47.51 kJ. Welding and Electrical Test ISO 11413 / UNI10521. Complies.

Mechanical tapping saddles

1.8 Dimensions AS ISO 7.1 AS 1722.2

As per factory quality system

Nupigeco Spa Italy has submitted relevant Test Report. Complies.

1.11 Freedom from defects Visual As per factory quality system

Nupigeco Spa Italy has submitted relevant Test Report. Complies.

Page 53: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 53

Process verification tests (PVT) Characteristics Clause,

Table Requirements Test Method Frequency Comments

Mechanical compression joint fittings

1.13.2 Resistance to internal pressure > 1000 h

ISO 1167 Min. one/size group/year (Note 2)

Nupigeco Spa Italy has submitted relevant Test Reports. Complies.

2.4.2 Assembled joint leaktightness at 40o C

ISO 1167 Min. one/size group/year (Note 2)

2.4.5 Pull-out resistance ISO 3501 Min. one/size group/year (Note 2)

Electrofusion fittings

Table 3.2 Hydrostatic strength at 20oC > 100h ISO 1167 Min. one/size group/year (Note 2)

Table 3.2 Hydrostatic strength at 80oC > 1000h

ISO 1167 Min. one/size group/year (Note 2)

Table 3.4 Short-term internal pressure Appendix E Min. one/size group/year (Note 2)

Table 3.4 Tensile load Appendix F Min. one/size group/year (Note 2)

Mechanical tapping saddles

4.4.4 Assembled saddle leaktightness at 40oC

ISO 1167 Min. one/size group/year (Note 2)

NOTES: 1. Tests to be carried out where reprocessed materials are used. 2. The whole range of products to be tested over 5 years (20% each year). Rotate sizes and compounds each year. Size groups: (a) < 63mm, (b) 75 to 225 mm, (c) > 250 mm.

Page 54: NUPIGECO SpA Italy - Water Services Association of … SpA EF and butt welding fittings-final 24- ... GASKET O-RING TECHNICAL DATA SHEET ... elbow, branch saddles, tapping tee, reducers,

WSAA Product Appraisal 14/13 54

COPYRIGHT

Melbourne Office Level 8, 469 Latrobe Street Melbourne VIC 3000 PO Box 13172 Law Courts Post Office Melbourne VIC 8010 Phone: (03) 9606 0678 Fax: (03) 9606 0376 Sydney Office Level 11, 39 Martin Place, Sydney, NSW 2000 GPO Box 915 Sydney NSW 2001 P +61 (0) 3 8605 7666 +61 (0) 3 8605 7666 | F +61 (0)2 9221 5977