1| February 3, 2016 | © 2014 Curtiss-Wright Nuclear Division Establishing a Heat Exchanger Test Plan Authored and Presented By: Edward Plansky and Steven Schaefer Presented to: FSRUG JANUARY 26, 2016

Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

1 | February 3, 2016 | © 2014 Curtiss-Wright

Nuclear Division

Establishing a Heat

Exchanger Test Plan

Authored and Presented

By:

Edward Plansky

and

Steven Schaefer

Presented to:

FSRUGJANUARY 26, 2016

Page 2: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

2 | February 3, 2016 | © Curtiss-Wright

INTRODUCTION

What are some of the determining factors in establishing a HX inspection test plan?

• Criticality of the HX

• Suspected or known leaks

• Limited window of access

• Identical HX has known issues

• HX Program identifies plan %

• Prior history or lack of

• Schedule

• Budget

• License extension

• Regulatory compliance or commitment

Page 3: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

3 | February 3, 2016 | © Curtiss-Wright

INTRODUCTION

What are some of the different sample plans?

• All open/accessible tubes or 100% sample

• Identified leakers and the bounding tubes

• All tubes with historical damage, bounding prior plugged tubes and

tubes within potential damage prone areas, usually totaling a

predetermined percentage of tubes

• All tubes with historical damage, bounding prior plugged tubes and

tubes within potential damage prone areas plus a predetermined

percentage of tubes that have not been inspected previously

• If multiple HX’s, like WB’s, then a 100% sample in one or more and

a sample like the 3rd one above in the remaining HX’s. Rotating the

plans until all HX’s have been inspected 100%.

Page 4: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

4 | February 3, 2016 | © Curtiss-Wright

Basic 100% Straight Length Sample Plan

A plan of all accessible

tubes was selected.

This is a Spent Fuel

Pool Cooler with U-

Bend tubes. The

sample plan was 100%

of the straight lengths.

The plan was based on

historical vibrational

damage and limited

access to the HX.

Page 5: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

5 | February 3, 2016 | © Curtiss-Wright

Basic 100% St. Lgth. & Accessible U-Bend Sample Plan

All accessible tubes were inspected. This was a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths plus as many U-Bends as possible. The U-bends were added because of OE at a site with a similar RHR that had vibrational damage in the U-Bends.

The black fill shows the U-Bends that were inspected.

Page 6: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

6 | February 3, 2016 | © Curtiss-Wright

Basic 100% Sample Plan – Damage Driven

All accessible tubes

were inspected. This

is a copper alloy

tubed HX with ID

pitting. The sample

plan was 100%

because pitting is a

random damage

mechanism.

Page 7: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

7 | February 3, 2016 | © Curtiss-Wright

Varible 100% / >50% Sample Plan – Schedule Driven

This inspection sample plan varies between 100% and >50% depending on LCO window. This is one of four CCW HX’s which have 304 Stainless Steel tubes with no service related damage to date. When schedule allows the sample plan is 100% but when time is limited scope is reduced to include all perimeter tubes and every other row. Then the next inspection the sample can be the perimeter again and the opposite rows. This way tubes with the highest potential for damage (perimeter) are inspected every time and after two inspections 100% coverage is completed on the Safety Related HX.

Page 8: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

8 | February 3, 2016 | © Curtiss-Wright

Expanded Sample Plan – Leaker & Damage Driven

If a FWH the with a

drain cooler is

scoped for a sample

of tubes it is very

important to inspect

tubes with the

highest potential for

damage. This would

include perimeter

tubes (filled) and

tubes along the baffle

overlap (half filled) in

the drain cooler.

Page 9: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

9 | February 3, 2016 | © Curtiss-Wright

Expanded Sample Plan – Leaker & Damage Driven

A relatively new fossil plant HP FWH with leaks in less than a year. So a sample of the perimeter and cross section to determine the extent and severity of the damage was selected. Once the damage was located that area was expanded to encompass the effected tubes.

Page 10: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

10 | February 3, 2016 | © Curtiss-Wright

Expanded Sample Plan – Leaker & Damage Driven

A relatively new fossil

plant IP FWH which

experienced leaks

multiple times from

IGSCC in the de-

superheater zone.

That area is

inspected 100% and

the perimeter and

selected rows in the

Inlet pass were

added to monitor for

possible damage.

Page 11: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

11 | February 3, 2016 | © Curtiss-Wright

Selected 15% Sample Plan – Main Condenser

This shows a basic ~15% sample plan consisting of all perimeter tubes, selected tubes across the bundle and potential FM collection areas. Areas can be expanded when things occur like bellows failures or dropped objects.

In recent years all 4 WB’s were inspected 100% in both Units for the 1st time since retube in 1988.

Page 12: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

12 | February 3, 2016 | © Curtiss-Wright

Selected 15% Sample Plan – Main Condenser

This shows a basic

~15% sample plan of

all perimeter tubes,

selected tubes across

the bundle and

potential FM collection

areas. Areas can be

expanded when things

occur like bellows

failures or dropped

objects.

In recent years all 4

WB’s were inspected

100% in both Units for

the 1st time since

original install in 1973.

Page 13: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

13 | February 3, 2016 | © Curtiss-Wright

Selected 10% Sample Plan – Main Condenser – Multi BWG

This shows how sometimes the sample plan needs to be divided into two separate plans. One plan for thicker wall perimeter tubes (dark tubes) and another plan for thinner wall main body tubes (red tubes).

Page 14: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

14 | February 3, 2016 | © Curtiss-Wright

Selected 10% Sample Plan – Main Condenser

This shows the

combined sample plans

for approximately 10%

of the total tubes.

Again, the highest

damage potential being

the perimeter, bounding

prior plugs and

selected rows for

randomly occurring

damage.

Page 15: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

15 | February 3, 2016 | © Curtiss-Wright

Selected 10%+ Sample Plan – Main Condenser

This shows how the original sample plan was expanded as time permitted to included tubes that had not been previously inspected. This way over time 100% of the tubes will be inspected without leaving out high potential tubes.

Page 16: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

16 | February 3, 2016 | © Curtiss-Wright

Tools for Assisting in Sample Selection – Tubesheet Maps

OEM Tubesheets

maps can also be

helpful in identifying

features of the HX like

cross over U-Tubes

and blanks where tie

rods attach to the

tubesheet and tube

supports holding them

in place.

Page 17: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

17 | February 3, 2016 | © Curtiss-Wright

Tools for Assisting in Sample Selection – Internals Drawing

As built drawings

can be used to

identify the internal

structures like tube

supports and

baffles as well as

identify the cut-out

patterns. They

also show inlets

and outlets which

are areas with

higher potential for

damage.

Page 18: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

18 | February 3, 2016 | © Curtiss-Wright

Tools for Assisting in Sample Selection – Externals Drawing

As built drawings

can be used to

identify the shell

inlets and outlets

which are areas

with higher

potential for

damage.

Page 19: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

19 | February 3, 2016 | © Curtiss-Wright

Tools for Assisting in Sample Selection – Plan Views

This shows a side view of the HP & LP steam boxes of a main condenser.

The tubes directly under the turbine discharges are prone to steam erosion &

vibrational damage and should get extra attention.

Page 20: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

20 | February 3, 2016 | © Curtiss-Wright

SUMMARY

What are some of the determining factors in establishing a HX inspection test plan?

• Criticality of the HX

• Suspected or known leaks

• Limited window of access

• Identical HX has known issues

• HX Program identifies plan %

• Prior history or lack of

• Schedule

• Budget

• License extension

• Regulatory compliance or commitment

Page 21: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

21 | February 3, 2016 | © Curtiss-Wright

SUMMARY

What are some of the different sample plans?

• All open/accessible tubes or 100% sample

• Identified leakers and the bounding tubes

• All tubes with historical damage, bounding prior plugged tubes and

tubes within potential damage prone areas, usually totaling a

predetermined percentage of tubes

• All tubes with historical damage, bounding prior plugged tubes and

tubes within potential damage prone areas plus a predetermined

percentage of tubes that have not been inspected previously

• If multiple HX’s, like WB’s, then a 100% sample in one or more and

a sample like the 3rd one above in the remaining HX’s. Rotating the

plans until all HX’s have been inspected 100%.

Page 22: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

22 | February 3, 2016 | © Curtiss-Wright

For More Information

Darren HoweManager, AnatecET Level III QDA

AnatecPhone: 949-271-7520Mobile: 949-300-2173

[email protected]

Edward PlanskyManager, Mid-West Office

ET Level III QDAAnatec

Phone: 920-657-1350Mobile: 920-374-0093

[email protected]

Nuclear Division

Page 23: Nuclear Division Establishing a Heat Exchanger …fsrug.org/Presentations2016/8.pdfwas a Residual Heat Removal HX with U-Bend tubes. The sample plan was 100% of the straight lengths

23 | February 3, 2016 | © Curtiss-Wright

http://www.curtisswright.com/

Steven Schaefer

Manager, BOP Services

ET Level III QDA, ASNT Level III ET

Anatec

Mobile: 860-885-4695

[email protected]

Nuclear Division