NOTES: 1. ALL DIMENSION ARE IN mm UNLESS OTHERWISE STATED. 2. THIS DRAWING TO BE READ IN CONJUNCTION WITH SPECIFICATIONS. 3. ALL ARCHITECTURE DETAILS TO ARCH’S APPROVAL. 4. CONTRACTOR SHOULD DO A SITE SURVEY BEFORE WORK COMMENCEMENT. 5. SINGLE LINE DIAGRAMS SHALL BE SUBMITTED TO THE S.O. FOR APPROVAL PRIOR TO COMMENCEMENT OF INSTALLATION. 6. ALTERNATE CIRCUITING SHALL BE PROVIDED FOR ALL LIGHTING. 7. CONTRACTOR TO DESIGN THE ELECTRICAL INSTALLATION IN ACCORDANCE WITH THE LATEST SS CP5. 8. OUTGOING CONTACTOR SHALL BE RATED APPROPRIATELY. 9. OUTGOING LIGHTING CIRCUIT BREAKER SHALL BE APPROPRIATELY DESIGN WITH MINIMUM RATING OF 10A SPN MCB 10KA. 1 1 DOUBLE POLE DP MCB RESIDUAL CURRENT CIRCUIT BREAKER RCCB ISOLATOR T C 2A LEGEND: C/W BYPASS SWITCH (SETTING 7pm TO 7am) PROGRAMMABLE TIMER WITH RS 232 INTERFACE UNIT S MOTION SENSOR MINIATURE CIRCUIT BREAKER NTS L/ROAD/MES/SD/1002 LROADMES-SD1002A.dgn Description Rev. Date By App’d Chk’d MELVYN THONG A DEC 2010 1. REVISED LIGHT FITTING DESCRIPTION 2. INCLUDE LEGEND AND REVISED NOTES. 3. REVISED POB /LINKWAY INCOMMING ISOLATOR RATING TO 32A AND SPPG DP MCB FROM 63A TO 32A. JULI JULY 2007 NURLY TAY K.C. TYPICAL SINGLE LINE DIAGRAM FOR NEW OG BOX (POB/LINKWAY/TAXI STAND/BUS SHELTER) LIGHTNING SURGE ARRESTOR BI TERMINAL ADRIAN CHEONG/ HADI WIJAYA WEATHERPROOF JUNCTION BOX Drawing No. : Scale Designed Drawn Checked of Sheet A3 Date Approved Rev. Project Title : CAD File Name: Drawing Title : LTA Endorsement : MELVYN THONG A MALVIN HO NURLY STANDARD INSTALLATION DETAILS SCALE NTS TYPICAL SINGLE LINE DIAGRAM - FOR NEW OG-BOX (POB/LINKWAY/TAXI STAND/BUS SHELTER) C S C C LSA LSA LSA BI BI BI TERMINAL BI BI TERMINAL (LTA COMPARTMENT) (LTA COMPARTMENT) kwh METER (PG COMPARTMENT) BI BI SUPPLIED AND INSTALLED BY PG FROM POWERGRID POWER GRID NEW OG-BOX METER POWER GRID 32A 40A DP RCCB (100mA) 2A T (10 KA) SPARE SPARE LI GHT FI TTI NG FOR COVERED POB W I TH COVERED RAMPS DP MCB (TYPE B) 32A DP CONTACTOR 7pm TO 7am MIDNIGHT TO 7am PROGRAMMABLE TIMER 40A DP RCCB (100mA) 2A T 32A DP CONTACTOR 7pm TO 7am PROGRAMMABLE TIMER DP MCB 32A (10 KA) DP MCB (TYPE B) DP MCB LI GHT FI TTI NG FOR COVERED POB W I TH COVERED RAMPS/LI NKW AY CONTACTOR *SEE NOTE NO. 9 *SEE NOTE NO. 9 *SEE NOTE NO. 9 *SEE NOTE NO. 8 32A COMB BUSBAR 32A COMB BUSBAR 32A COMB BUSBAR INTELLIGENT LIGHTING CONTROL BOX kwh 32A (PROVIDED BY PG) DP MCB (TYPE C) 32A (PROVIDED BY PG) DP MCB (TYPE C) 32A DP ISOLATOR 32A DP ISOLATOR NEW DB POB/LINKWAY NEW DB BUS SHELTER/ TAXI STAND LI GHT FI TTI NG TO TECHNI CAL SPECI FI CATI ON PERFORMANCE ARMOURED CABLE IN HEAVY DUTY UPVC PIPES PVC CABLES IN HEAVY DUTY UPVC PIPES PVC CABLES IN HEAVY DUTY UPVC PIPES ARMOURED CABLE IN HEAVY DUTY UPVC PIPES E RING CIRCUIT SHALL BE LESS THAN 1 ohm

NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

NOTES:1. ALL DIMENSION ARE IN mm UNLESS OTHERWISE STATED.

2. THIS DRAWING TO BE READ IN CONJUNCTION

WITH SPECIFICATIONS.

3. ALL ARCHITECTURE DETAILS TO ARCH’S APPROVAL.

4. CONTRACTOR SHOULD DO A SITE SURVEY BEFORE WORK COMMENCEMENT.

5. SINGLE LINE DIAGRAMS SHALL BE SUBMITTED

TO THE S.O. FOR APPROVAL PRIOR TO

COMMENCEMENT OF INSTALLATION.

6. ALTERNATE CIRCUITING SHALL BE PROVIDED

FOR ALL LIGHTING.

7. CONTRACTOR TO DESIGN THE ELECTRICAL

INSTALLATION IN ACCORDANCE WITH THE

LATEST SS CP5.

8. OUTGOING CONTACTOR SHALL BE RATED

APPROPRIATELY.

9. OUTGOING LIGHTING CIRCUIT BREAKER

SHALL BE APPROPRIATELY DESIGN WITH

MINIMUM RATING OF 10A SPN MCB 10KA.

1 1

DOUBLE POLEDP

MCB

RESIDUAL CURRENT CIRCUIT BREAKERRCCB

ISOLATOR

T

C

2A

LEGEND:

C/W BYPASS SWITCH (SETTING 7pm TO 7am)

PROGRAMMABLE TIMER WITH RS 232 INTERFACE UNIT

S MOTION SENSOR

MINIATURE CIRCUIT BREAKER

NTS

L/ROAD/MES/SD/1002

LROADMES-SD1002A.dgnDescriptionRev. Date By App’dChk’d

MELVYNTHONGA DEC 2010

1. REVISED LIGHT FITTING DESCRIPTION

2. INCLUDE LEGEND AND REVISED NOTES.

3. REVISED POB /LINKWAY INCOMMING ISOLATOR RATING TO 32A AND SPPG DP MCB FROM 63A TO 32A.

JULI JULY 2007

NURLY

TAY K.C.

TYPICAL SINGLE LINE DIAGRAM FOR NEW OG BOX

(POB/LINKWAY/TAXI STAND/BUS SHELTER)

LIGHTNING SURGE ARRESTOR

BI TERMINAL

ADRIAN CHEONG/HADI WIJAYA

WEATHERPROOF JUNCTION BOX

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet A3

Date

Approved

Rev.

Project Title :

CAD File Name:

Drawing Title :

LTA Endorsement :

MELVYN THONG

A

MALVIN HONURLY

STANDARD INSTALLATION DETAILS

SCALE NTS

TYPICAL SINGLE LINE DIAGRAM - FOR NEW OG-BOX (POB/LINKWAY/TAXI STAND/BUS SHELTER)

C

S

C

C

LSA LSA

LSA

BI

BI BI TERMINAL BI BI TERMINAL

(LTA COMPARTMENT) (LTA COMPARTMENT)

kwh

METER

(PG COMPARTMENT)

BI

BI SUPPLIED AND

INSTALLED BY PG

FROM POWERGRID

POWER GRID

NEW

OG-BOX

METERPOWER GRID

32A

40A DPRCCB(100mA)

2A

T

(10 KA)

SP

AR

E

SP

AR

E

LIG

HT

FIT

TIN

G

FO

R

CO

VE

RE

D

PO

B

WIT

H

CO

VE

RE

D

RA

MP

S

DP MCB

(TYPE B)

32A DP

CONTACTOR

7pm

TO 7am

MIDNIGHT

TO 7am

PROGRAMMABLE

TIMER

40A DPRCCB(100mA)

2A

T

32A DP

CONTACTOR

7pm

TO 7am

PROGRAMMABLE

TIMER

DP MCB

32A

(10 KA)

DP MCB

(TYPE B)

DP MCB

LIG

HT

FIT

TIN

G

FO

R

CO

VE

RE

D

PO

B

WIT

H

CO

VE

RE

D

RA

MP

S/

LIN

KW

AY

CONTACTOR

*SEE

NOTE

NO. 9

*SEE

NOTE

NO. 9

*SEE

NOTE

NO. 9

*SEE

NOTE

NO. 8

32A COMB BUSBAR32A COMB BUSBAR

32A COMB BUSBAR

INTELLIGENT

LIGHTING

CONTROL BOX

kwh

32A

(PROVIDED BY PG)DP MCB (TYPE C)

32A

(PROVIDED BY PG)DP MCB (TYPE C)

32A DPISOLATOR

32A DP

ISOLATOR

NEW DB

POB/LINKWAY

NEW DB

BUS SHELTER/

TAXI STAND

LIG

HT

FIT

TIN

G

TO

TE

CH

NIC

AL

SP

ECIFIC

ATIO

N

PE

RF

OR

MA

NC

E

ARMOURED CABLE IN

HEAVY DUTY UPVC PIPES

PVC CABLES IN

HEAVY DUTY UPVC PIPES

PVC CABLES IN

HEAVY DUTY UPVC PIPES

ARMOURED CABLE IN

HEAVY DUTY UPVC PIPES

E

RING CIRCUIT

SHALL BE LESS

THAN 1 ohm

Page 2: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

NOTES:

OTHERWISE STATED.1. ALL DIMENSION ARE IN mm UNLESS

WITH SPECIFICATIONS.

2. THIS DRAWING TO BE READ IN CONJUNCTION

APPROVAL.3. ALL ARCHITECTURE DETAILS TO ARCH’S

BEFORE WORK COMMENCEMENT.4. CONTRACTOR SHOULD DO A SITE SURVEY

COMMENCEMENT OF INSTALLATION.

TO THE S.O. FOR APPROVAL PRIOR TO

5. SINGLE LINE DIAGRAMS SHALL BE SUBMITTED

DOUBLE POLEDP

MCB

RESIDUAL CURRENT CIRCUIT BREAKERRCCB

ISOLATOR

T

C

2A

LEGEND:

C/W BYPASS SWITCH (SETTING 7pm TO 7am)

PROGRAMMABLE TIMER WITH RS 232 INTERFACE UNIT

S MOTION SENSOR

MINIATURE CIRCUIT BREAKER

FOR ALL LIGHTING.

6. ALTERNATE CIRCUITING SHALL BE PROVIDED

LATEST SS CP5.

INSTALLATION IN ACCORDANCE WITH THE

7. CONTRACTOR TO DESIGN THE ELECTRICAL

LIGHTNING SURGE ARRESTOR

BI TERMINAL

WEATHERPROOF JUNCTION BOX

(BUS SHELTER/TAXI STAND)

TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX

L/ROAD/MES/SD/1003

1 1LROADMES-SD1003A.dgn

SCALE: NTS

TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX (BUS SHELTER / TAXI STAND )

METERPOWER GRID

32ADP MCB (TYPE C)

(PROVIDED BY PG)

3. INCLUSION OF TAXI STAND REQUIREMENT.

1. REVISED LIGHT FITTING DESCRIPTION

2. INCLUDE LEGEND AND REVISED NOTES.TAY K.CJUNE 2010A

NTS

NO. 8

NOTE

*SEE

MINIMUM RATING OF 10A SPN MCB 10KA.

SHALL BE APPROPRIATELY DESIGN WITH

8. OUTGOING LIGHTING CIRCUIT BREAKER

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet A3

Date

Approved

Rev.

Project Title :

CAD File Name:

Drawing Title :

LTA Endorsement :

MELVYN THONG

JULI

A

DescriptionRev. Date By App’dChk’d

THONG

MELVYN

MALVIN HO

JULY 2007

NURLY

HADI WIJAYAADRIAN CHEONG/

STANDARD INSTALLATION DETAILS

LSA

32A COMB BUSBAR

E

kwh METER kwh

(PG COMPARTMENT)

BI

INSTALLED BY PG

BI SUPPLIED AND

THAN 1 ohm

SHALL BE LESS

RING CIRCUIT

(PROVIDED BY PG)

(10KA)

FROM POWERGRID

OG-BOX

NEW

POWER GRID

40A DP

RCCB(100mA)

2A

T

C

CONTACTOR

32A DP

TIMERS

PROGRAMMABLE

7am

7pm TO

(10KA)

DP MCB (TYPE B)

32A

DP MCB (TYPE C)

DP ISOLATOR

TAXI STAND

BUS SHELTER/

NEW DB

SPARE COMPARTMENT

DP MCB

PE

RF

OR

MA

NC

E

TE

CH

NIC

AL

SP

ECIFIC

ATIO

N

LIG

HT

FIT

TIN

G

TO

63A

63A

SPARE COMPARTMENTFOR INTELLIGENT LIGHTING CONTROL BOX

HEAVY DUTY UPVC PIPES

PVC CABLES IN

HEAVY DUTY UPVC PIPES

ARMOURED CABLE IN

LSA

BI

BI

Page 3: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

NOTES:

HEAVY DUTY UPVC PIPES

PVC CABLES IN

HEAVY DUTY UPVC PIPES

ARMOURED CABLE IN

OTHERWISE STATED.1. ALL DIMENSION ARE IN mm UNLESS

WITH SPECIFICATIONS.

2. THIS DRAWING TO BE READ IN CONJUNCTION

APPROVAL.3. ALL ARCHITECTURE DETAILS TO ARCH’S

BEFORE WORK COMMENCEMENT.4. CONTRACTOR SHOULD DO A SITE SURVEY

COMMENCEMENT OF INSTALLATION.

TO THE S.O. FOR APPROVAL PRIOR TO

5. SINGLE LINE DIAGRAMS SHALL BE SUBMITTED

FOR ALL LIGHTING.

6. ALTERNATE CIRCUITING SHALL BE PROVIDED

LATEST SS CP5.

INSTALLATION IN ACCORDANCE WITH THE

7. CONTRACTOR TO DESIGN THE ELECTRICAL

ITEM MARKED * TO 32A RATING.

8. CONTRACTOR IS RESPONSIBLE TO REPLACE

APPROPRIATELY.

9. OUTGOING CONTACTOR SHALL BE RATED

MINIMUM RATING OF 10A SPN MCB 10KA.

SHALL BE APPROPRIATELY DESIGN WITH

10. OUTGOING LIGHTING CIRCUIT BREAKER

DOUBLE POLEDP

MCB

RESIDUAL CURRENT CIRCUIT BREAKERRCCB

ISOLATOR

T

C

2A

LEGEND:

C/W BYPASS SWITCH (SETTING 7pm TO 7am)

PROGRAMMABLE TIMER WITH RS 232 INTERFACE UNIT

S MOTION SENSOR

MINIATURE CIRCUIT BREAKER

LIGHTNING SURGE ARRESTOR

BI TERMINAL

WEATHERPROOF JUNCTION BOX

1. REVISED LIGHT FITTING DESCRIPTION

2. INCLUDE LEGEND AND REVISED NOTES.

32A AND SPPG DP MCB FROM 63A TO 32A.3. REVISED POB /LINKWAY INCOMMING ISOLATOR RATING TO

(DBO BUS SHELTER/POB/LINKWAY)

TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX

JUNE 2010

NO. 10

NOTE

*SEE

NO. 10

NOTE

*SEE

NO. 9

NOTE

*SEE

NO. 10

NOTE

*SEE

TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX (DBO BUS SHELTER /POB /LINKWAY) SCALE: NTS

A TAY K.CDrawing No. :

Scale

Designed

Drawn

Checked

ofSheet A3

Date

Approved

Rev.

Project Title :

CAD File Name:

Drawing Title :

LTA Endorsement :

MELVYN THONG

JULI

A

DescriptionRev. Date By App’dChk’d

THONG

MELVYN

MALVIN HO

JULY 2007

NURLY

HADI WIJAYAADRIAN CHEONG/

STANDARD INSTALLATION DETAILS

L/ROAD/MES/SD/1004

LROADMES-SD1004A.dgn

C

S

C

LSA

BI BI TERMINAL

DP MCB (TYPE C)

kwh METER

(PG COMPARTMENT)

BI

INSTALLED BY PG

BI SUPPLIED AND

(PROVIDED BY PG)

(10KA)

FROM POWERGRID

POWER GRID

OG-BOX

EXISTING

DBO BUS SHELTER

EXISTING

63A * (SEE NOTE 8)

32A

40A DPRCCB(100mA)

2A

T

(10 KA)

SP

AR

E

(TYPE B)

DP MCB

CONTACTOR

32A DPTO 7am

7pm

TIMER

PROGRAMMABLE

DP MCB

PO

B

WIT

H

CO

VE

RE

D

RA

MP

S/

LIN

KW

AY

LIG

HT

FIT

TIN

G

FO

R

CO

VE

RE

D

SP

AR

E

PO

B

WIT

H

CO

VE

RE

D

RA

MP

S

LIG

HT

FIT

TIN

G

FO

R

CO

VE

RE

D

TO 7am

MIDNIGHT

CONTACTOR

32A COMB BUSBAR

32A COMB BUSBAR

CONTROL BOX

LIGHTING

INTELLIGENT

kwh METERPOWER GRID

32ADP MCB (TYPE C)

(PROVIDED BY PG)

DP ISOLATOR63A * (SEE NOTE 8)

POB/LINKWAY

NEW OG-BOX

32A DP

ISOLATOR

HEAVY DUTY UPVC PIPES

PVC CABLES IN

HEAVY DUTY UPVC PIPES

ARMOURED CABLE IN

E THAN 1 ohm

SHALL BE LESS

RING CIRCUIT

LSA

BI

Page 4: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

A

-

B

- 1

-

2

-

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

MELVYN THONG

N.T.S. JULI JULY 2007

L/ROAD/MES/SD/1006

LROADMES-SD1006A.dgn

NURLY

STANDARD INSTALLATION DETAILS

MALVIN HO

A

TYPICAL DETAIL OF POB/LINKWAY/

BUS SHELTER/TAXI STAND/OG-BOX

DescriptionRev. Date App’dChk’dDesigned

By

Drawn

By

A JUNE 2012 CHING ANGELINEHADI

WIJAYAADRIAN

CHEONG

1.

2.

3.

INCLUSION OF TAXI STAND OG-BOX REQUIREMENT.

ADD SPACE TO HOUSE INTELLIGENT LIGHTING DETECTION

SYSTEM CONTROLLER INSIDE OG-BOX.

ADD PROVISION OF Ø50mm HEAVY DUTY UPVC PIPE FOR

INTELLIGENT LIGHTING DETECTION SYSTEM.

TYPICAL DETAIL OF POB / LINKWAY / BUS SHELTER / TAXI STAND / OG-BOXSCALE: NTS

UV STABILISEDPOLYCARBONATE

UV STABILISEDPOLYCARBONATE

REMOVABLE PLATE

3273-A

ABLOY

FIX PLATE

REMOVABLE PLATE

27.5

280

82.5

REMOVABLE PLATE

27.5

280

1Ø KWH

METER

POWER

GRID

T’wood= 230

70

Std= 235

T’wood= 230

Std= 235

188

138

188

138

T’wood= 230 T’wood= 230

560

1Ø KWH

METER

POWER

GRID

BI Supply

and Installed

By PG

T’w

ood

=300

T’w

ood

=300

3273-A

ABLOY

3273-A

ABLOY

Depth

=

mm

450

100

EXTERNAL FRONT DOOR

FIX PLATE

Front

Back

Front

Back

Std

Casing

=560

EXTERNAL BACK DOOR

GLASS

EXTERNAL VIEW INTERNAL FRONT VIEW

PLAN VIEW

EXTERNAL BACK VIEW

Front

Back

SUPPORT FOR BREAKER

PARTITION

SUPPORTFOR BREAKER

EXTERNALFRONTDOOR

PARTITION

EXTERNAL FRONT DOOR

2 NOS Ø100mm HEAVY DUTY UPVCLEAD IN C/W 90^ LONG BEND PIPESFOR POWER GRID INCOMING CABLING

2 NOS Ø100mm HEAVY DUTY UPVCLEAD IN C/W 90^ LONG BEND PIPESFOR POWER GRID INCOMING CABLING

PLINTH C/W OPENINGFOR CABLE ENTRY

Lock

Lock

Lock

min

Overall Length = min 1320mmOverall Length = min 1320mm

420

Overall H

eig

ht =

min 1300

mm

Overall H

eig

ht =

min 1300

mm

Ø50mm HEAVY DUTY UPVC PIPEFOR BUS SHELTER ADVERTISING PANEL

Ø50mm HEAVY DUTY UPVC PIPE FOR BUS SHELTER ADVERTISING PANEL

Ø100mm HEAVY DUTY UPVC PIPE FOR BUS SHELTER/TAXI STANDELECTRICAL DISTRIBUTION

BUS SHELTER/TAXI STAND

Ø100mm HEAVY DUTY UPVC PIPEFOR BUS SHELTER/TAXI STAND ELECTRICAL DISTRIBUTION

Depth = min 450mm

Depth = min 450mm

Back

Depth = min 450mm

Front

REMOVABLEPLATE

3273-A

ABLOY

Lock

ELEVATION 1 ELEVATION 2

INTERNAL SIDE VIEW

SECTION A-A

20070

PARTITION

SUPPORT FOR INTELLIGENTLIGHTING DETECTION SYSTEMCONTROLLER

EXTERNAL FRONT DOOR

EXTERNALFRONTDOOR

PARTITION

SUPPORT FORINTELLIGENTLIGHTINGDETECTIONSYSTEMCONTROLLER

SECTION B-B

70200 70

INTELLIGENTLIGHTINGDETECTIONSYSTEMCONTROLLERFOR POB

Ø100mm HEAVY DUTY UPVC PIPEFOR POB/LINKWAY ELECTRICAL DISTRIBUTION

INTELLIGENTLIGHTINGDETECTIONSYSTEMCONTROLLERFOR POB

POB/LINKWAY

Ø100mm HEAVY DUTY UPVC PIPEFOR POB/LINKWAY ELECTRICAL DISTRIBUTION

Page 5: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

SYSTEM FOR BUS SHELTER

TYPICAL LIGHTING AND LIGHTNING PROTECTION

LROADMES-SD1007A.dgn

L/ROAD/MES/SD/1007

TO M&E SPECIFICATIONPROPOSED LIGHT FITTING (IP65)

TO M&E SPECIFICATIONPROPOSED LIGHT FITTING (IP65)

1 1

ON SITE & TO SO APPROVAL)(LOCATION TO BE DETERMINEDON SITE & TO SO APPROVAL)

(LOCATION TO BE DETERMINED

0 0.5 1 1.5 2 2.5 Metres

Scale 1:50

TYPICAL LIGHTING LAYOUT PLAN

1:50

REVISED DETAILS

UPVC PIPE 1 NO. Ø100mm HEAVY DUTY ARMOURED CABLE IN

UPVC PIPE 1 NO. Ø100mm HEAVY DUTY ARMOURED CABLE IN

UPVC PIPE 1 NO. Ø100mm HEAVY DUTY ARMOURED CABLE IN

A

A

FA

LL

FA

LL

ROOF EAVES ABOVE

MIN.

600

3000

FA

LL

1 2 3

1 2 3

7500

A-

75030003000750

FA

LL

200

125

27

00

300

THERMOPLASTIC ROAD MARKING MATERIALS

200 WIDE YELLOW LINE IN HOT APPLIED

3

2

1

3

LINE OF ROAD KERB OR ROAD RESERVE LINE

4mm THK. TEMPERED GLASS

NOTICE BOARD WITH ALUM. FRAME C/W

MS ANGLE ROOF FASCIA TO ENGR’S DTL

MFR’S DTL

ROOF CAPPING @ 1500mm C/C TO

2

7500

75030003000750

1500150015001500

3000

27

00

300

L/ER373/AR/TD/5003

L/ER373/AR/TD/5003

L/ER373/AR/TD/5003

L/ER373/AR/TD/5003

L/ER373/AR/TD/5003

AL/ER373/AR/TD/5003

AL/ER373/AR/TD/5003

LATEST REVISION

DRAWING NO. L/CFADC/AR/BS/0005

LTA ARCHITECTURAL DESIGN CRITERIA

ONCOMING TRAFFIC IN ACCORDANCE TO

BUS SHELTER ADDRESS PLATE TO FACE

M.S. RHS POST BELOW (C1)

M.S. RHS POST (C1)

1400

75

0 (C

LE

AR)

300

GRANOLITHIC FINISHES TO SO’S APPROVAL

CONC. SLAB COMPLETE WITH 25mm THK

ALUM. BENCH ALUM. BENCH

POWDER COATED ALUM. ’F’ TYPE CAPPING

PANEL TO SO’S APPROVAL

TOP PANEL AND 0.7mm THK UNDERSIDE

ROOF PANEL COMPLETE WITH MIN. 1mm THK

MIN. 10mm THK. ALUM. HONEY COMB

LITTER BIN BY OTHERS

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet A3

Date

Approved

Rev.

Project Title :

CAD File Name:

Drawing Title :

LTA Endorsement :

MELVYN THONG

JULI

A

DescriptionRev. Date By App’dChk’d

THONG

MELVYNA DEC 2010

MALVIN HO

JULY 2007

NURLY

TAY K.CHADI WIJAYA

ADRIAN CHEONG/

STANDARD INSTALLATION DETAILS

HEAVY DUTY UPVC PIPEPVC CABLE IN Ø25mm

(TOTAL RESISTANCE < 10ohm)EARTH PIT(TOTAL RESISTANCE < 10ohm)

EARTH PIT

OG BOXNEW

FROM 0G-BOX TO ADVERTISING PANELUPVC PIPE C/W PULL WIRES 1 NO. Ø50mm HEAVY DUTY

INCOMING CABLEPIPES FOR SP POWERGRID’S UPVC HEAD-IN 90° LONG BEND 2 NOS. Ø100mm HEAVY DUTY

(SEE DETAIL "1")DOWNSTREAM EDGE OF BUS SHELTERPANEL TO BE LOCATED AT THE DRAW WIRES FOR ADVERTISEMENT1 NO. ELECTRICAL PIPE WITH

DOWN CONDUCTOR

UPVC PIPE 1 NO. Ø100mm HEAVY DUTY ARMOURED CABLE IN

SCALE 1:50

SITE

PANEL TO BE DETERMINED ON

LOCATION OF ADVERTISEMENT

DETAIL "1"NTS

AND POWERGRID’S APPROVAL

TO SITE CONDITIONS

SHALL BE SUBJECTED

(IP55) LOCATION

NEW OG BOX

PANEL

FROM OG-BOX TO ADVERTISING

UPVC PIPE C/W PULL WIRES

1NO. Ø50mm HEAVY DUTY

PANEL

ADVERTISEMENT

TYPICAL LIGHTNING PROTECTION SYSTEM (ROOF PLAN)

Page 6: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

EARTH ROD

GROUND LEVEL

PROTECTION EARTH LABELINCLUSIVE OF LIGHTNINGEARTH ROD CLAMP

16mm DIA COPPER)(min. 2 Nos. 1.8m LENGTH,

COUPLING

COPPER CONDUCTOR TAPEPIPE C/W 25mm X 3mmØ50mm HEAVY DUTY UPVC

GALVANISED COVERHOT DIP

ALL AROUNDCONCRETE HAUNCH

50

LROADMES-SD1008A.dgn

L/ROAD/MES/SD/1008

Scale: N.T.S.

Scale: N.T.S.

BONDING TO STEEL SUPPORT POSTTYPE 1 - ELEVATION OF LIGHTNING

DETAIL 2

Scale: N.T.S.

SECTION H-H

25mm x 3mm COPPER TAPE

STEEL SUPPORT POST

ALUMINIUM OR

TO STEEL SUPPORT POST

M8 ALUMINIUM COPPER BOLT

B-BOND

(IP65) TO M&E SPECIFICATIONPROPOSED LIGHT FITTING

UPVC PIPEHEAVY DUTYIN Ø25mm PVC CABLECONCEALED

M&E SPECIFICATIONFITTING (IP65) TO PROPOSED LIGHT

M&E SPECIFICATIONFITTING (IP65) TO PROPOSED LIGHT

M&E SPECIFICATIONFITTING (IP65) TO PROPOSED LIGHT

UPVC PIPE 1 NO. Ø100mm HEAVY DUTY ARMOURED CABLE IN

JUNCTION BOXCONCEALED

PITEARTH

EARTH PIT

REQUIREMENTSROOF SPECIALIST’S BONDING DETAILS TO

FOR SP POWERGRID INCOMING CABLINGPIPES LEAD IN 90° LONG BEND PIPES2 NOS Ø100mm HEAVY DUTY UPVC

EARTH PIT

UPVC PIPEIN Ø25mm HEAVY DUTYCONCEALED PVC CABLE

POWERGRID’S APPROVALTO SITE CONDITIONS AND SP

LOCATION SHALL BE SUBJECTED NEW OG BOX (IP54)

SEE DETAIL ’3’

SEE DETAIL ’2’GROUND)150mm ABOVE COLUMN (MIN. STRUCTUREBONDING TO

SEE DETAIL ’3’

CABLE CONNECTIONCONCEALED JUNCTION BOX FOR

CABLE CONNECTIONCONCEALED JUNCTION BOX FOR

FOR CABLE CONNECTION CONCEALED JUNCTION BOX

REQUIREMENTSROOF SPECIALIST’S BONDING DETAILS TO

1:50

11

0 0.5 1 1.5 2 2.5 Metres

Scale 1:50

BUS SHELTER

TYPICAL ELECTRICAL INSTALLATION DETAILS FOR

REVISED DETAILS

SECTION PLAN

ELEVATION PLANSEE DETAIL ’3’ABOVE GROUND)COLUMN (MIN. 150mm BONDING TO STRUCTURE

SEE DETAIL ’3’

GROUND)SEE DETAIL ’2’COLUMN (MIN. 150mm ABOVE BONDING TO STRUCTURE

UPVC PIPE 1 NO. Ø100mm HEAVY DUTY ARMOURED CABLE IN

LATEST REVISION

DRAWING NO. L/CFADC/AR/BS/0005

LTA ARCHITECTURAL DESIGN CRITERIA

ONCOMING TRAFFIC IN ACCORDANCE TO

BUS SHELTER ADDRESS PLATE TO FACE

GLASS PANEL OF 900 X 900)

VIEW THROUGH THE FRONT

TO BE IN FULL UNOBSTRUCTED

OF POSTERS OF SIZE 940 X 940,

(SHALL ALLOW CLEAR MOUNTING

C/W 4mm THK. TEMPERED GLASS

NOTICE BOARD WITH ALUM. FRAME

A

ROAD

450

300

MIN. 6003000

2700300

–2

692

2300

–2388

–25

34

200 (

MIN.)

FFL

1 2 3

45

0 (B

EN

CH)

7500

75030003000750

23

00

–2

38

8

–2

692

1000 1000

97

01000

200

15

0

217

0

1500150015001500

ALUM. BENCH

ALUM. BENCH

GRANOLITHIC FINISHES TO SO’S APPROVAL

CONC. SLAB COMPLETE WITH 25mm THK

45

0

MS ANGLE ROOF FASCIA (T1)

M.S. SHS (R2)

M.S. ’C’ CHANNEL RAFTER (R1)

LIGHT FITTING TO M&E SPECS

M.S. RHS POST (C1)

POWDER COATED ALUM. ’F’ TYPE CAPPING

LITTER BIN BY OTHERS

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet A3

Date

Approved

Rev.

Project Title :

CAD File Name:

Drawing Title :

LTA Endorsement :

MELVYN THONG

JULI

A

DescriptionRev. Date By App’dChk’d

THONG

MELVYNA DEC 2010

MALVIN HO

JULY 2007

NURLY

TAY K.CHADI WIJAYA

ADRIAN CHEONG/

STANDARD INSTALLATION DETAILS

H-

H

-

SCALE NTS

SCALE 1:50

DETAIL 3

Page 7: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

L/ROAD/MES/SD/1009

1 1LROADMES-SD1009A.dgn

FOR BUS SHELTER

TYPICAL EQUIPOTENTIAL BONDING DETAILS

REVISED DETAIL

1:50

IN Ø25mm HEAVY DUTY UPVC PIPE

6mÀ PVC EARTH BONDING CABLE

AND POWERGRID’S APPROVAL

TO SITE CONDITIONS

SHALL BE SUBJECTED

(IP55) LOCATION

NEW OG BOX

CABLING

POWERGRID INCOMING

BEND PIPES FOR

LEAD IN 90° LONG

DUTY UPVC PIPES

2 NOS Ø100mm HEAVY

DUTY UPVC PIPE

Ø25mm HEAVY

BONDING CABLE IN

6mÀ PVC EARTH

Scale 1:50

FOR BUS SHELTERTYPICAL EQUIPOTENTIAL BONDING DETAILS

LATEST REVISION

DRAWING NO. L/CFADC/AR/BS/0005

LTA ARCHITECTURAL DESIGN CRITERIA

ONCOMING TRAFFIC IN ACCORDANCE TO

BUS SHELTER ADDRESS PLATE TO FACE

GLASS PANEL OF 900 X 900)

VIEW THROUGH THE FRONT

TO BE IN FULL UNOBSTRUCTED

OF POSTERS OF SIZE 940 X 940,

(SHALL ALLOW CLEAR MOUNTING

C/W 4mm THK. TEMPERED GLASS

NOTICE BOARD WITH ALUM. FRAME

FFL

1 2 3

45

0 (B

EN

CH)

7500

75030003000750

23

00

–2

38

8

–2

692

1000 1000

97

01000

200

15

0

217

0

1500150015001500

ALUM. BENCH

ALUM. BENCH

GRANOLITHIC FINISHES TO SO’S APPROVAL

CONC. SLAB COMPLETE WITH 25mm THK

45

0

MS ANGLE ROOF FASCIA (T1)

M.S. SHS (R2)

M.S. ’C’ CHANNEL RAFTER (R1)

LIGHT FITTING TO M&E SPECS

M.S. RHS POST (C1)

POWDER COATED ALUM. ’F’ TYPE CAPPING

LITTER BIN BY OTHERS

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet A3

Date

Approved

Rev.

Project Title :

CAD File Name:

Drawing Title :

LTA Endorsement :

MELVYN THONG

JULI

A

DescriptionRev. Date By App’dChk’d

THONG

MELVYNA DEC 2010

MALVIN HO

JULY 2007

NURLY

TAY K.CHADI WIJAYA

ADRIAN CHEONG/

STANDARD INSTALLATION DETAILS

Page 8: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

WATER INGRESS

SEALANT TO PREVENT

WITH APPROVED

UPVC PIPE SEALED

WITH CONCRETE SURFACE

TO HAVE DIRECT CONTACT

TO PREVENT ALUMINIUM TAPE

CONCRETE SURFACE PAINTED OVER

BOLTED ON BEARING PLATE.

ALUMINIUM CONDUCTOR TAPE

BI-METALLIC BOND/CLAMP AND

(SEE DETAIL X)

TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE

PAINTED OVER TO PREVENT ALUMINIUM TAPE

BOLTED ON BEARING PLATE CONCRETE SURFACE

BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE

(SEE DETAIL X)

TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE

PAINTED OVER TO PREVENT ALUMINIUM TAPE

BOLTED ON BEARING PLATE CONCRETE SURFACE

BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE

1 1

STANDARD INSTALLATION DETAILS

JULI JULY 2007

Drawing No. :

Drawn

Checked

ofSheet

Date

Approved

Rev.

Project Title :

CAD File Name:

Drawing Title :

LTA Endorsement :

MELVYN THONG

A

MALVIN HONURLY

Scale

Designed

NTS

L/ROAD/MES/SD/1010

LROADMES-SD1010A.dgnDescriptionRev. Date App’dChk’d

Designed

By

Drawn

By

A JUNE 2012 CHINGWIJAYA

HADICHEONGADRIAN

TAY K.C.

A4

10x10mm CHAMFER

TO ROADSIDE DRAIN

12°

PILE CAP TO ENGR’S DETAIL

R.C. GRATING

2800

–3

84

22

00

–2

58

4

1100

100

85

514

5

370 2060 370

1800

MIN. 40 MIN. 40

EQEQ

FALL

75

0

75

67

5

7002200

75

675

625

15°

AND ROOF

´ OF POB DECK

EQ

EQ

25

25

25

17

00

TO ENGR’S DETAIL

TYPICAL CROSS BEAM

CHIPPING FINISHED TO S.O’S APPROVAL

20mm THK PRECASTED GRANOLITHIC

RC COLUMN TO ENGR’S DETAIL WITH

200

600

10x10mm CHAMFER

TO ROADSIDE DRAIN

12°

PILE CAP TO ENGR’S DETAIL

2800

–3

84

22

00

–2

58

4

1100

100

85

514

5

370 2060 370

1800

MIN. 40 MIN. 40

EQEQ

FALL

75

0

75

67

5

7002200

75

675

625

15°

TO ENGR’S DETAIL

TYPICAL CROSS BEAM

CHIPPING FINISHED TO S.O’S APPROVAL

20mm THK PRECASTED GRANOLITHIC

RC COLUMN TO ENGR’S DETAIL WITH

200

600

17

00

EQ

EQ

25

25

25

15

0

15

0

Ø45mm S.S. RAILING Ø45mm S.S. RAILING

COATING FINISH TO SO’S APPROVAL

TO ENGR’S DETAIL COMPLETE WITH SPRAY

CHS HOT-DIPPED GALVANISED M.S. POST

COATING FINISH TO SO’S APPROVAL

TO ENGR’S DETAIL COMPLETE WITH SPRAY

CHS HOT-DIPPED GALVANISED M.S. MEMBER

AND ROOF

´ OF POB DECK

COATING FINISH TO SO’S APPROVAL

TO ENGR’S DETAIL COMPLETE WITH SPRAY

CHS HOT-DIPPED GALVANISED M.S. POST

COATING FINISH TO SO’S APPROVAL

TO ENGR’S DETAIL COMPLETE WITH SPRAY

CHS HOT-DIPPED GALVANISED M.S. MEMBER

57

00 (

MIN.)

1000 (V

ARIE

S)

54

00 (

MIN.)

1000 (V

ARIE

S)

FALL FALL

CHIPPING FINISHED TO S.O’S APPROVAL

20mm THK PRECASTED GRANOLITHIC

MEMBRANE TO SO’S APPROVAL

PLANTING TROUGH WITH WATERPROOFING

MEMBRANE TO SO’S APPROVAL

PLANTING TROUGH WITH WATERPROOFING

CHIPPING FINISHED TO S.O’S APPROVAL

20mm THK PRECASTED GRANOLITHIC

R.C. GRATING

TO OG BOX TO M&E SPECIFICATIONS

Ø50mm PVC PIPE FOR LIGHTING CIRCUITS

POB DECK

FFL OF

Ø15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR Ø15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR

POB DECK

FFL OF

FOOTPATH LEVEL

ROAD LEVEL

FOOTPATH LEVEL

ROAD LEVEL

WITH MIN. 1mm THK. TOP PANEL TO SO’S APPROVAL

MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL COMPLETE

WITH MIN. 1mm THK. TOP PANEL TO SO’S APPROVAL

MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL COMPLETE

SYSTEM AND REVISED DETAILS.

TO AMEND TO LATEST STANDARD FOR LIGHTNING PROTECTION

FOR COVERED PEDESTRIAN OVERHEAD BRIDGE

TYPICAL LIGHTNING PROTECTION SYSTEMFOR COVERED POB (EXPRESSWAY)

FOR COVERED POB (NON-EXPRESSWAY)

DETAIL X

EARTH ROD

ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE

25mm x 3mm ALUMINIUM CONDUCTOR TAPE

ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE

25mm x 3mm COPPER CONDUCTOR TAPE

EARTH ROD

ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE

25mm x 3mm ALUMINIUM CONDUCTOR TAPE

ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE

25mm x 3mm COPPER CONDUCTOR TAPE

(TOTAL EARTH RESISTANCE 10ohms)

EARTH PIT

(TOTAL EARTH RESISTANCE 10ohms)

EARTH PIT

1500

1500

IN ACCORDANCE TO SS 555 REQUIREMENTS

CONTRACTOR TO ENSURE THAT BONDED

PURPOSE MADE BOND

TEST BOX AT POB)

(SEE TYPICAL LIGHTNING PROTECTION

IN ACCORDANCE TO SS 555 REQUIREMENTS

GROUND LEVEL (SURFACE MOUNT)

AT 1500mm HEIGHT FROM

150mm x 150mm TEST LINK BOX

IN ACCORDANCE TO SS 555 REQUIREMENTS

CONTRACTOR TO ENSURE THAT BONDED

PURPOSE MADE BOND

TEST BOX AT POB)

(SEE TYPICAL LIGHTNING PROTECTION

IN ACCORDANCE TO SS 555 REQUIREMENTS

GROUND LEVEL (SURFACE MOUNT)

AT 1500mm HEIGHT FROM

150mm x 150mm TEST LINK BOX

PROTECTION

TEST

BOX

LIGHTNING

NUT INSERTM5 COUNTERSUNK BOLT

SECTION Y-Y

TEST BOX AT POBTYPICAL LIGHTNING PROTECTION

(WITH COVER)ELEVATION VIEW

(WITHOUT COVER)ELEVATION VIEW

DUTY UPVC PIPES

ENCASED HEAVY

COVER PLATE

STAINLESS STEEL

DUTY UPVC PIPES

ENCASED HEAVY

R.C. COLUMNCOPPER TAPE

25mm x 3mm

CONNECTOR

BI-METALLIC

COVER PLATE

STAINLESS STEEL

ALUMINIUM TAPE

25mm x 3mm

CONNECTOR

BI-METALLIC

COPPER TAPE

25mm x 3mm

ALUMINIUM TAPE

25mm x 3mm

Y-

Y-

Page 9: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

EARTH ROD

GROUND LEVEL

PROTECTION EARTH LABELINCLUSIVE OF LIGHTNINGEARTH ROD CLAMP

16mm DIA COPPER)(min. 2 Nos. 1.8m LENGTH,

COUPLING

COPPER CONDUCTOR TAPEPIPE C/W 25mm X 3mmØ50mm HEAVY DUTY UPVC

GALVANISED COVERHOT DIP

ALL AROUNDCONCRETE HAUNCH

50

DescriptionRev. Date App’dChk’dDesigned

By

Drawn

By

A JUNE 2012 CHINGWIJAYA

HADICHEONGADRIAN

TAY K.C.SYSTEM.

TO AMEND TO LATEST STANDARD FOR LIGHTNING PROTECTION

1 1

NTS

EARTHING ROD

25 x 3mm ALUMINIUM TAPE

GROUND LEVEL

HEAVY DUTY UPVC PIPE

Ø50mm HEAVY DUTY UPVC PIPE25 x 3mm COPPER TAPE ENCASED IN

BOND TO SUPPORT POST.25 x 3mm ALUMINIUM TAPE

L/ROAD/MES/SD/1011

LROADMES-SD1011A.dgn

(TOTAL EARTH RESISTANCE <10ohms>EARTH PIT REFER TO DETAIL ’3’

REFER TO DETAIL ’2’

(REFER TO DETAIL 1)ELECTRICALLY CONTINUOUS.THE NEW COVERED POB AND RAILING ARE LIGHTNING PROTECTION SYSTEM FORCONTRACTOR TO ENSURE THAT THE NEW

OVERHEAD BRIDGE

FOR NEW ROOF OVER EXISTING PEDESTRIAN

TYPICAL LIGHTNING PROTECTION SYSTEM

THAT BONDED IN ACCORDANCE TO LATEST SS 555.REQUIREMENT. CONTRACTOR TO ENSURE BONDING DETAILS TO NEW ROOF SPECIALIST

(LATEST SS 555)GROUND LEVEL (SURFACE MOUNT)AT 1500mm HEIGHT FROM 150mm x 150mm TEST LINK BOX

SCALE 1 : 50

OVERHEAD BRIDGE

FOR NEW ROOF OVER EXISTING PEDESTRIAN

TYPICAL LIGHTNING PROTECTION SYSTEM

ENGR’S DETAIL

WITH BOLTS/NUTS TO

PLATE WITH 90° ANGLE

12mm THK MS BEARING

ALUMINIUM TAPE

NEW 25mm x 3 mm

WITH CONCRETE SURFACE

TO HAVE DIRECT CONTACT

TO PREVENT ALUMINIUM TAPE

CONCRETE SURFACE PAINTED OVER

BOLTED ON BEARING PLATE.

ALUMINIUM CONDUCTOR TAPE

BI-METALLIC BOND/CLAMP AND

ENGR’S DETAIL

RAILING TO

DETAIL 1N.T.S.

COVER PLATE

STAINLESS STEEL

COPPER TAPE

25mm x 3mm

CONNECTOR

BI-METALLIC

DUTY UPVC PIPES

ENCASED Ø50mm HEAVY

ALUMINIUM TAPE

25mm x 3mm

DUTY UPVC PIPES

Ø50mm HEAVY

DETAIL 2N.T.S.

DETAIL 3N.T.S.

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet

Date

Approved

Rev.

Project Title :

CAD File Name:

Drawing Title :

LTA Endorsement :

MELVYN THONG

JULI

A

DescriptionRev. Date By App’dChk’d

THONG

MELVYNA DEC 2010

MALVIN HO

JULY 2007

NURLY

TAY K.CHADI WIJAYA

ADRIAN CHEONG/

STANDARD INSTALLATION DETAILS

A4

FFL

EXISTING POB DECK EQEQ EQEQ

EXISTING PLANTING TROUGHS

TYPICAL SECTION OF POB DECK

FFL

TYPICAL SECTION OF POB STAIRCASE

SCALE 1:20

TO VERIFY ON SITE FOR ACTUAL WIDTH OF POB DECK

ROOF EAVE TO EXTEND AT NOT MORE THAN HALF THE WIDTH OF PLANTING TROUGH

SCALE 1:20

REFER TO SECTION OF POB DECK FOR ANNOTATION

TO VERIFY ON SITE FOR ACTUAL WIDTH OF STAIRCASE

& COLUMN

EXISTING POB STAIRCASE

1100

100

855

100

45

6mm THK S.S. FLAT BAR

6mm THK S.S. FLAT BAR

FFL

Ø45mm S.S. RAILING

MORE THAN 100mm CLEAR

Ø15mm S.S. ROD AT NOT

MOUNTING DETAILS

REFER TO ENGR’S DWG. FOR

TYPICAL ELEVATION OF RAILING ON POB DECKSCALE 1:20

SPACING OF POSTS AT REGULAR INTERVAL TO ENGR’S DETAIL

EQEQEQEQ

TO SO’S APPROVAL

Ø45mm S.S. HANDRAIL

TO SO’S APPROVAL

Ø45mm S.S. RAILING

TO S.S. PLATE TO ENGR’S DETAIL

6mm THK. S.S. FLAT BAR TO BE WELDED

100mm CLEAR TO SO’S APPROVAL

Ø15mm S.S. ROD AT NOT MORE THAN

6mm THK S.S. FLAT BAR TO SO’S APPROVAL

SCALE 1:20

TYPICAL ELEVATION OF RAILING ON POB STAIRCASE

800

1100

30

TOP PANEL TO SO’S APPROVAL

PANEL COMPLETE WITH MIN. 1 mm THK

MIN. 10mm THK. ALUM. HONEYCOMB ROOF

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

300VARIES DEPEND ON SITE300

M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL

M.S. SUPPORT POST TO ENGR’S DETAILMIN.

2100

FLEXIBLE CONDUIT IN SUPPORT POST

ELECTRICAL CABLE CONCEALED IN PVC

MIN.40

1100

S.S. ROD AT NOT MORE THAN 100mm CLEAR

S.S. FLAT BAR AT REGULAR INTERVAL AND

NEW Ø45mm S.S. RAILNG COMPLETE WITH

VARIES DEPEND ON SITE

300VARIES DEPEND ON SITE300

TO SO’S APPROVAL

WITH MIN. 1mm THK. TOP PANEL

COMB ROOF PANEL COMPLETE

MIN. 10mm THK. ALUM. HONEY

NOT MORE THAN 100mm CLEAR

INTERVAL AND S.S. ROD AT

S.S. FLAT BAR AT REGULAR

HARDRAIL COMPLETE WITH

NEW Ø45mm S.S. RAILNG AND

MIN.

2100

1100

800

M.S. SUPPORT POST TO ENGR’S DETAIL

TO ENGR’S DETAIL

M.S. SUPPORT POST

APPLICABLE RANGE 2700 TO 3600

TO SPECIFICATION

CONVENTIONAL BALLAST

SPECIFICATIONS

WITH THE AUTHORITY’S

LIGHT FITTING TO COMPLY

Page 10: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A4

Date

Approved

Rev.

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

MELVYN THONG

N.T.S. JULI JAN 2010

L/ROAD/MES/SD/1012

LROADMES-SD1012A.dgn

SALIM

STANDARD INSTALLATION DETAILS

MALVIN HOADRIAN CHEONG/

A

FOR SINGLE POST COVERED LINKWAY

LIGHTNING PROTECTION SYSTEM

TYPICAL CABLE ENTRY DETAIL AND

DescriptionRev. Date App’dChk’dDesigned

By

Drawn

By

A JUNE 2012 CHING ANGELINEWIJAYA

HADICHEONGADRIAN

INCLUSION OF TAXI STAND OG-BOX REQUIREMENT.

AMENDMENT TO LIGHTNING PROTECTION SYSTEM.2.

1.

TEAKWOOD FOR MOUNTING

CABLE GLAND FOR ARMOURED CABLE

300x300x20 THK MS PLATE

C1 WELDED ALL-ROUND TO

10mm THK NON SHRINK GROUT

MOUNTED ON TEAKWOOD BLOCK

TERMINAL BLOCK CONNECTOR

FLAT BAR TO SUPPORT TEAKWOOD BLOCK

FROM OG BOX TO FIRST LIGHTING POINT

ARMOURED CABLE IN Ø100mm HEAVY DUTY UPVC PIPE

UPVC PIPE

IN Ø50mm HEAVY DUTY

COPPER TAPE

25mm x 3mm

IN PVC COATED FLEXIBLE STEEL CONDUIT

PVC CABLE + 2.5mÀ EARTH CABLE

<10 ohms)

RESISTANCE

(TOTAL EARTH

PROTECTION SYSTEM

FOR LIGHTNING

EARTH PIT

500

DETAIL 1

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /

FLEXIBLE STEEL CONDUIT TO M&E DWG. & SPEC.

PVC CABLE CONCEALED IN PVC COATED

FOR PVC CABLES TO M&E DWG. & SPEC.

G.I. CONDUIT ALONG BACK OF M.S. FASCIA

FOR INCOMING CABLES TO M&E DETAIL

PVC COATED FLEXIBLE STEEL CONDUIT

FOR PVC CABLES TO M&E DWG. & SPEC.

G.I. CONDUIT ALONG BACK OF M.S. FASCIA

FLEXIBLE STEEL CONDUIT IN SUPPORT POST

PVC CABLE CONCEALED IN PVC COATED

ROOF SPECIALIST’S REQUIREMENTS.

BONDING DETAILS TO

´

A

GASKET

S/S SCREW

´

3° FALL

S/S SCREW

ALUM. ROOF FRAME & M.S. MEMBER

ISOLATOR / BONDING TAPE BETWEENALUM. ROOF FRAME & M.S. MEMBER

ISOLATOR / BONDING TAPE BETWEEN

1500

TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE

SECTION J-J

ALUM. ROOF FRAME & M.S. MEMBER

ISOLATOR / BONDING TAPE BETWEEN

M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL

TO ENGR’S DETAIL

M.S. ANGLE ROOF FASCIA

TO ENGR’S DETAIL

M.S. ANGLE ROOF FASCIA

40

40

FFL

B-

B-

´

´

MS BASE PLATE TO ENGR’S DETAIL

(TO BE PROVIDED AT 1ST & LAST POST ONLY)

BY POST CAPPING

OPENING FOR INCOMING CABLES COVERED

20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL

CONC. SLAB TO ENGR’S DTL COMPLETE WITH

RC FOOTING TO ENGR’S DETAIL

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

50 x 50 x 3 ALUM ANGLE PLATE

MS RHS TO ENGR’S DETAIL

100 100

10

750

REF. DWG. NO. L/STLLW/AR/STD/1002

Scale 1:5

300 TOP PANEL TO SO’S APPROVAL

PANEL COMPLETE WITH MIN. 1mm THK.

MIN. 10mm THK. ALUM. HONEYCOMB ROOF

WITH MIN. 1mm THK.TOP PANEL TO SO’S APPROVAL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL COMPLETE

TO SO’S APPROVAL

COMPLETE WITH MIN. 1mm THK. TOP PANEL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL

TO SO’S APPROVAL

COMPLETE WITH MIN. 1mm THK. TOP PANEL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL

750

–81

750

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

ALUM FLASHING PIECE BOLTED AT BOTH END

(TO BE PROVIDED AT 1ST & LAST POST ONLY)

BY POST CAPPING

OPENING FOR INCOMING CABLES COVERED

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

15

0

C-

C-

SECTION C-C

M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL

TO SO’S APPROVAL

COMPLETE WITH MIN. 1mm THK. TOP PANEL

MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL

ALUM. ROOF CAPPING FOR ROOF PANEL TO MFR’S DETAIL

TO MFR’S DETAIL

ALUM. ROOF CAPPING FOR ROOF PANEL

M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL

M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL

TO MFR’S DETAIL

ALUM. ROOF CAPPING FOR ROOF PANEL

K-

K-

M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL

2100 (

MIN.) (N

TS)

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

LIGHT FITTING TO M&E SPEC. & SHALL NOT PROTRUDE FROM M.S. RAFTER /

LIGHT FITTING MOUNTING BRACKET TO CONTRACTOR PROPOSAL

CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING

LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /

(DESIGN TO REFER TO ARCH DWG)

LIGHT FITTING TO M&E SPEC

FLEXIBLE STEEL CONDUIT IN SUPPORT POST

PVC CABLE CONCEALED IN PVC COATED

SEE DETAIL X

SECTION K-K

SECTION B-B

SECTION C-C

DETAIL X

TYPICAL CROSS SECTION FOR SINGLE POST COVERED LINKWAY

TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE

SECTION Y-Y

25mm x 3mm COPPER TAPE

STEEL SUPPORT POST

TO STEEL SUPPORT POSTM8 COPPER BOLT

Y-

Y-

Page 11: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

EARTH ROD

GROUND LEVEL

PROTECTION EARTH LABELINCLUSIVE OF LIGHTNINGEARTH ROD CLAMP

16mm DIA COPPER)(min. 2 Nos. 1.8m LENGTH,

COUPLING

COPPER CONDUCTOR TAPEPIPE C/W 25mm X 3mmØ50mm HEAVY DUTY UPVC

GALVANISED COVERHOT DIP

ALL AROUNDCONCRETE HAUNCH

50

SECTION E-E

ALUMINIUM TAPE

SUPPORT POST

ALUMINIUM OR STEEL

Scale: N.T.S.

B-BOND

COPPER TAPE

Scale: N.T.S.

M8 STAINLESS STELL BOLT

M8 COPPER BOLT

CONNECTOR

BI-METALLIC

E-

E

-

SECTION H-HScale: N.T.S.

Scale: N.T.S.

BONDING TO STEEL SUPPORT POSTTYPE 1 - ELEVATION OF LIGHTNING

DETAIL 2

25mm x 3mm COPPER TAPE

STEEL SUPPORT POST

ALUMINIUM OR

TO STEEL SUPPORT POST

M8 ALUMINIUM COPPER BOLT

B-BOND

FOR COVERED LINKWAY

TYPICAL LIGHTNING PROTECTION SYSTEM

H

-

H-

ROOF TO STEEL SUPPORT POSTELEVATION OF BONDING FROM

DETAIL 1

0 2 3 4 5 Metres0.5

Scale 1:100

1.51

A

1:100

REVISED DETAILS L/ROAD/MES/SD/1014

LROADMES-SD1014A.dgn 1 1

Scale: N.T.S.

DETAIL 3

LIGHTNING PROTECTION SYSTEM LAYOUT PLAN

FRONT ELEVATION (LIGHTNING PROTECTION SYSTEM SHALL BE APPLIED FOR ALL TYPE OF LINKWAY)

FRONT ELEVATION 1

Scale 1:50

STRUCTUREEXISTING BONDED TO

PITEARTH

PITEARTH

PITEARTH

PITEARTH

SEE DETAIL 2(MIN 150mm ABOVE FLOOR LEVEL)BONDING TO STRUCTURE COLUMN

SEE DETAIL 2(MIN 150mm ABOVE FLOOR LEVEL)BONDING TO STRUCTURE COLUMN

Scale 1:100

Scale 1:100

SEE DETAIL 2ABOVE FLOOR LEVEL)COLUMN (MIN 150mm BONDING TO STRUCTURE

SEE DETAIL 3

SEE DETAIL 3

SEE DETAIL 1REQUIREMENTSROOF SPECIALIST’S BONDING DETAILS TO

SEE DETAIL 1SPECIALIST’S REQUIREMENTS)(BONDING DETAILS TO ROOFLIGHTNING PROTECTION SYSTEMBONDING TO UPPER ROOF

SEE DETAIL 1REQUIREMENTSROOF SPECIALIST’S BONDING DETAILS TO

SEE DETAIL 1REQUIREMENTSROOF SPECIALIST’S BONDING DETAILS TO

SEE DETAIL 1REQUIREMENTSROOF SPECIALIST’S BONDING DETAILS TO

SEE DETAIL 3

SEE DETAIL 2

PITEARTH

SEE DETAIL 3

SEE DETAIL 2FLOOR LEVEL)(MIN 150mm ABOVE STRUCTURE COLUMN BONDING TO

Scale 1:50

Scale 1:50

1 2 3 4 5 6 7

1 2 4 5 7

FRONT ELEVATION 1 (WITHOUT LEVEL DIFFERENCE)

FRONT ELEVATION WITH LEVEL DIFFERENCE

3 86 9 10

FFL

(CLEAR)

TO POWERGRID’S APPROVAL)

(LOCATION TO BE DETERMINED ON SITE &

OG BOX ON CONC. PLINTH TO M&E DTLS

TO ENGR’S DETAIL

M.S. ANGLE ROOF FASCIA

PANEL TO MFR’S DETAIL

ALUM. ROOF CAPPING FOR ROOF

TOP PANEL TO SO’S APPROVAL

PANEL COMPLETE WITH MIN. 1mm THK.

MIN. 10mm THK. ALUM. HONEY COMB ROOF

M.S. RHS POST TO ENGR’S DETAIL

15001500 15001500 15001500 15001500 1500150015001500

750300030003000300030003000750

820

12

00

15

0

200

2100 (

MIN.)

–2

35

2

–2

107 (

MIN.

2100

CL

EA

R)

–2

45

OG BOX

OG BOX

FFL

FFL

ALUM FLASHING PIECE

FFL(CLEAR)

TO POWERGRID’S APPROVAL)

(LOCATION TO BE DETERMINED ON SITE &

OG BOX ON CONC. PLINTH TO M&E DTLS

TO ENGR’S DETAIL

M.S. ANGLE ROOF FASCIA

PANEL TO MFR’S DETAIL

ALUM. ROOF CAPPING FOR ROOF

TOP PANEL TO SO’S APPROVAL

PANEL COMPLETE WITH MIN. 1mm THK.

MIN. 10mm THK. ALUM. HONEY COMB ROOF

TO ENGR’S DETAIL

M.S. ANGLE ROOF FASCIA

75030003000750

1500 1500 1500 1500750 3000 3000 750

1500150015001500750 3000 3000 3000 750

150015001500150015001500 –81

–81

–2

107 (

MIN.

2100

CL

EA

R)

2100 (

MIN.)

–2

35

2

–2

107 (

MIN.

2100

CL

EA

R)

–2

45

M.S. RHS POST TO ENGR’S DETAIL

M.S. RHS POST TO ENGR’S DETAIL

82012

00

15

0200

2100

–2

35

2

–2

107 (

MIN.

2100

CL

EA

R)

–2

45

EL/ER187/AR/TD/3006

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet A3

Date

Approved

Rev.

Project Title :

CAD File Name:

Drawing Title :

LTA Endorsement :

MELVYN THONG

JULI

A

DescriptionRev. Date By App’dChk’d

THONG

MELVYNA DEC 2010

MALVIN HO

JULY 2007

NURLY

TAY K.CHADI WIJAYA

ADRIAN CHEONG/

STANDARD INSTALLATION DETAILS

Page 12: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

0 0.5 1 1.5 2 2.5 Metres

Scale 1:501 1

LIGHT FIXTURE TO M&E SPECIFICATION

SCALE 1 : 501:50

L/ROAD/MES/SD/1015

LROADMES-SD1015-.dgn

-

SCALE 1 : 50

LIGHT FIXTURE TO M&E SPECIFICATION

AND NEW ROOF OVER EXISTING POB

TYPICAL LIGHTING SYSTEM FOR NEW POB

TAY K.C HADI WIJAYAADRIAN CHEONG/

CNV NOV 2010

H.D uPVC PIPE FROM OG BOXARMOURED CABLE IN Ø100mm

FLEXIBLE CONDUIT FOR LIGHTINGPVC CABLE IN PVC COATED

FLEXIBLE CONDUIT FOR LIGHTINGPVC CABLE IN PVC COATED

ENCASED IN COLUMNØ100mm HD uPVC PIPE PVC CABLE IN

H.D uPVC PIPE FROM OG BOXARMOURED CABLE IN Ø100mm

TYPICAL LIGHTING SYSTEM

FOR NEW COVERED POB

TYPICAL LIGHTING SYSTEM

FOR NEW ROOF OVER EXISTING POB

CABLES IN PIPE SLEEVE

END OF POB

IN GI CONDUIT PVC CABLE

JUNCTION BOXWEATHERPROOF

JUNCTION BOXWEATHERPROOF

JUNCTION BOXWEATHERPROOF

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet A3

Date

Approved

Rev.

Project Title :

CAD File Name:

Drawing Title :

LTA Endorsement :

MELVYN THONG

DescriptionRev. Date By App’dChk’d

STANDARD INSTALLATION DETAILS

1000

1500

200600

17

00

EQ

EQ

25

25

25

FOOTPATH LEVEL

ROAD LEVEL

5680 (

MIN.

54

00)

900 (V

ARIE

S)

2800

–384

2200

–2584

1100

100

855

14

5

370 2060 370

1800MIN. 40 MIN. 40

EQEQ

750

75

67

5

7002200

75

675

625

150

15°

12°

MIN.

300

1000

1500

200600

17

00

EQ

EQ

25

25

25

FOOTPATH LEVEL

ROAD LEVEL

5680 (

MIN.

54

00)

900 (V

ARIE

S)

2800

–384

2200

–2584

1100

100

855

14

5

370 2060 370

1800MIN. 40 MIN. 40

EQEQ

750

75

67

5

7002200

75

675

625

150

15°

12°

MIN.

300

Page 13: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

LEGEND:

1 1

MIN.

54

00

A-

PROPOSED HIGH COVERED LINKWAY

ALUM WEATHER SHIELDPROPOSED LOCATION OF

THE 2.4m WIDE COVERED LINKWAYROOF TO HAVE THE SAME RADIUS AS PROPOSED HIGH COVER LINWAY CURVED

END OF HIGH COVER LINKWAYPROPOSED ALUM WEATHER SHIELD AT BOTH

PROPOSED 2.4m WIDE COVERED LINKWAY34

00

NTS

LIGHT FITTINGCOLUMN MOUNTED

LIGHT FITTINGCOLUMN MOUNTED

LIGHT FITTINGCOLUMN MOUNTED

LIGHT FITTINGCOLUMN MOUNTED

LIGHT FITTINGCOLUMN MOUNTED

LIGHT FITTINGCOLUMN MOUNTED

LIGHTINGSLINKWAY

CONNECT TO

LIGHTINGSLINKWAYCONNECT TO

24

00

54

00

600

4200

600

5400

6004200600

2400

16200

L/ROAD/MES/SD/1016

LROADMES-SD1016-.dgn

LIGHT FITTINGCOLUMN MOUNTED

-

HIGH COVERED LINKWAY

TYPICAL LIGHTING SYSTEM FOR

HADI WIJAYAADRIAN CHEONG/

NOV 2010CNV

TAY K.C

JUNCTION BOX

ENCASED IN COLUMNØ100mm HD uPVC PIPE PVC CABLE IN

ENCASED IN COLUMNØ100mm HD uPVC PIPE

PVC CABLE IN

JUNCTION BOX

H.D uPVC PIPE FROM OG BOXARMOURED CABLE IN Ø100mm

ENCASED IN COLUMNØ100mm HD uPVC PIPE PVC CABLE IN

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet A3

Date

Approved

Rev.

Project Title :

CAD File Name:

Drawing Title :

LTA Endorsement :

MELVYN THONG

JULI

DescriptionRev. Date By App’dChk’d

HADI WIJAYAADRIAN CHEONG/

STANDARD INSTALLATION DETAILS

Scale: N.T.S.

Scale: N.T.S.

Scale: N.T.S.

SECTION A-A

ROOF PLAN (HIGH COVERED LINKWAY)

TYPICAL COLUMN MOUNTED LIGHT FITTING

FRONT VIEW SIDE VIEW

ISOMETRIC VIEW

SPECIFICATIONLIGHT FITTING TO M&E COLUMN MOUNTED

Page 14: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

EARTH ROD

GROUND LEVEL

EARTH ROD CLAMPINCLUSIVE OF LIGHTNINGPROTECTION EARTH LABEL

(min. 2 Nos. 1.8m LENGTH,16mm DIA COPPER)

COUPLINGØ50mm HEAVY DUTY UPVCPIPE C/W 25mm X 3mmCOPPER CONDUCTOR TAPE

HOT DIP GALVANISED COVER

CONCRETE HAUNCH ALL AROUND

50

TAY K.C

CNV NOV 2010

EARTH PIT(TOTAL RESISTANCE < 10ohm)

(LOCATION TO BE DETERMINEDON SITE & TO SO APPROVAL)

EARTH PIT(TOTAL RESISTANCE < 10ohm)

(LOCATION TO BE DETERMINEDON SITE & TO SO APPROVAL)

LEGEND:

SECTION E-E

SECTION H-H

25mm x 3mm COPPER TAPE

ALUMINIUM OR

STEEL SUPPORT POST

M8 ALUMINIUM COPPER BOLT

TO STEEL SUPPORT POST

ALUMINIUM TAPE

ALUMINIUM OR STEEL

SUPPORT POST

Scale: N.T.S.

Scale: N.T.S.

Scale: N.T.S.

DC BONDING

BONDING

DETAIL 2TYPE 1 - ELEVATION OF LIGHTNING

BONDING TO STEEL SUPPORT POST

B-BOND

COPPER TAPE

Scale: N.T.S.

B-BOND

M8 STAINLESS STELL BOLT

M8 COPPER BOLT

BI-METALLIC

CONNECTOR

DC

1 1

MIN.

54

00

A-

PROPOSED HIGH COVERED LINKWAY

PROPOSED LOCATION OFALUM WEATHER SHIELD

PROPOSED HIGH COVER LINWAY CURVED ROOF TO HAVE THE SAME RADIUS AS THE 2.4m WIDE COVERED LINKWAY

PROPOSED ALUM WEATHER SHIELD AT BOTHEND OF HIGH COVER LINKWAY

PROPOSED 2.4m WIDE COVERED LINKWAY

NTS

BONDING DETAILS TO ROOF SPECIALIST’S REQUIREMENT

SEE DETAIL 1

EARTH PIT

SEE DETAIL 3

SEE DETAIL 2

BONDING DETAILS TO ROOF SPECIALIST’S REQUIREMENT

SEE DETAIL 1

600

54

00

42

00

600

24

00

16200

5400

6004200600

2400

TYPICAL LIGHTNING PROTECTION SYSTEM FOR

HIGH COVERED LINKWAY

L/ROAD/MES/SD/1017

LROADMES-SD1017-.dgn

STANDARD INSTALLATION DETAILS

-

ADRIAN CHEONG/HADI WIJAYA

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet A3

Date

Approved

Rev.

Project Title :

CAD File Name:

Drawing Title :

LTA Endorsement :

MELVYN THONG

DescriptionRev. Date By App’dChk’d

THONG

E-

H

-

H-

E

-

EARTH PIT

BONDING

DOWN CONDUCTORDC

SECTION A-A

ROOF PLAN (HIGH COVERED LINKWAY)

DETAIL 1ELEVATION OF BONDING FROM ROOF TO

STEEL SUPPORT POST

Scale: N.T.S.

Scale: N.T.S.

Scale: N.T.S.

DETAIL 3

Page 15: NOTES: LEGEND · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator rating to 32a and sppg dp mcb from 63a to 32a. juli july 2007 nurly tay k.c. typical

Ø 32mm STAINLESS STEEL PIPE

R.C. COLUMN

EXISTING GROUND LEVEL

EXISTING ROAD LEVEL

FACING PAVEMENT FACING ROAD

COUPLING INLET

TYPICAL LAYOUT COUPLING INLET AT 1000mm ABOVE GROUND

1. NUMBER OF HOLES SHOWN ARE INDICATIVE ONLY (NOT ACTUAL NUMBER).

NOTE:

OF LAYBY SUBJECT TO APPROVAL BY NATIONAL PARKS BOARD

NOTE : FOR LESS THAN 8m RADIUS FROM COLUMN OF POB TO THE MIDPOINT

SCALE NTS

OF LAYBY SUBJECT TO APPROVAL BY NATIONAL PARKS BOARD

NOTE : FOR MORE THAN 8m RADIUS FROM COLUMN AT POB TO THE MIDPOINT

SCALE 1 : 20

1000

ABOVE GROUND

ISOLATION VALVE AT 1500mm

CAD File Name :

Drawing No. :

Scale

Designed

Drawn

Checked

ofSheet 1 1 A1

Date

Approved

Rev.

-

Drawing Title :

Project Title :

LTA Endorsement :

Qualified Person Endorsement :

DescriptionRev. Date By App’dChk’d

MELVYN THONG

AS SHOWN JAN 2011CNV

L/ROAD/MES/SD/2001

LROADMES-SD2001-.dgn

TAN BOON TONGLIM KWEE CHEW /

VERON

FOR INFORMATION ONLY

STANDARD INSTALLATION DETAILS

AND SECTIONS FOR NEW POB

TYPICAL IRRIGATION INSTALLATION DETAILS

B

-

PLATFORM AND ABOVE THE SOIL LEVELTHE PLANTER TROUGH THAT ABUT THEBE FIXED TO THE INNER WALL OFBOTTOM OF THE PIPE AND SHOULDCENTRE TO CENTRE ALONG THE *3mm HOLES AT 400mm APART*25mm STAINLESS STEEL PIPE WITH

SECTION A - A

TYPICAL SECTION OF PEDESTRIAN OVERHEAD BRIDGE

1500mm ABOVE GROUNDSTAINLESS STEEL PIPE AT FOR 2 NOS. OF EXPOSED *32mm 2 NOS. OF ISOLATION VALVE

PIPE BURIED UNDERGROUND*32mm STAINLESS STEEL

STEEL PIPE SLEEVE*50mm GALVANISED

SEE DETAIL A

STEEL PIPE RISER*32mm STAINLESS

600

250 x 250 HANDICAPPED SIGN

1000

1500

200600

17

00

EQ

EQ

25

25

25

FOOTPATH LEVEL

ROAD LEVEL

5680 (

MIN.

54

00)

900 (V

ARIE

S)

2800

–384

2200

–2584

1100

100

855

14

5

370 2060 370

1800MIN. 40 MIN. 40

EQEQ

750

75

67

5

7002200

75

675

625

150

15°

12°

MIN.

300

DescriptionRev. Date By Chk’d

FOR INFORMATION ONLY

SECTION B-BSCALE 1:20

STEEL PIPE RISER2 NOS. *32mm STAINLESS

50

200

150

80

200

2000

2000

SCALE NTS

SCALE NTS

SCALE NTS

400mm

5030050

50

300

50

COUPLING INLET

GROUND LEVEL

1000

400

SECTION X-X DETAIL ASCALE NTS

Ø3mm HOLE

END CAP

END CAP

STEEL PIPE

*32mm STAINLESS

*32mm STAINLESS STEEL PIPE RISER

BURIED UNDERGROUND

Ø32mm STAINLESS STEEL PIPE

CONCRETE FILLED

NEAREST OPEN DRAIN

OVERFLOW PIPE TO WITH HAUNCH END

UNDERGROUND PIPE

WATER WAGON CONNECTION

QUICK RELEASE COUPLING FOR

Ø38mm (1�INCH)

PIPING SUPPORTS

HOT-DIPPED GALVANISED

STAINLESS STEEL OR

WITH RETRACTABLE HANDLE

4.5mm ALUMINIUM CHEQUERED PLATE

Ø32mm STAINLESS STEEL PIPE

1500mm ABOVE GROUND

ISOLATION VALVE AT

AND ABOVE THE SOIL LEVEL

THAT ABUTS THE PLATFORM

INNER WALL OF THE TROUGH

SHOULD BE FIXED TO THE

THE BOTTOM OF THE PIPE

400mm APART C/C ALONG

WITH Ø3mm HOLES AT

Ø25mm STAINLESS STEEL PIPE

(UNDERGROUND)

CONNECTION

FOR WATER WAGON

QUICK RELEASE COUPLING

Ø38mm (1�INCH)

400mm

1500mm ABOVE GROUND

ISOLATION VALVE AT

AND ABOVE THE SOIL LEVEL

THAT ABUTS THE PLATFORM

INNER WALL OF THE TROUGH

SHOULD BE FIXED TO THE

THE BOTTOM OF THE PIPE

400mm APART C/C ALONG

WITH Ø3mm HOLES AT

Ø25mm STAINLESS STEEL PIPE

Ø3mm HOLE

END CAP

END CAP

STEEL PIPE

*32mm STAINLESS

*32mm STAINLESS STEEL PIPE RISER

UNDERGROUND COUPLING INLETISOMETRIC DIAGRAM WITH

SURFACE COUPLING INLETISOMETRIC DIAGRAM WITH

NEAREST OPEN DRAIN

OVERFLOW PIPE TO

WITH HAUNCH END

UNDERGROUND PIPE

CONCRETE FILLED

ABOVE GROUND

AT 1000mm

CONNECTION

FOR WATER WAGON

QUICK RELEASE COUPLING

Ø38mm (1 1/2 INCH)

X

-