THE EFFECT OF THERMAL AGEING ON LOW VOLTAGE CROSS-LINKED POLYETHYLENE INSULATED CABLE NOOR FAEZAH BINTI HAMDI A project report submitted in partial fulfilment of the requirements for the award of the degree of Master of Forensic Engineering. School of Civil Engineering Faculty of Engineering Universiti Teknologi Malaysia JANUARY 2019

NOOR FAEZAH BINTI HAMDI

  • Upload
    others

  • View
    19

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NOOR FAEZAH BINTI HAMDI

THE EFFECT OF THERMAL AGEING ON LOW VOLTAGE CROSS-LINKED

POLYETHYLENE INSULATED CABLE

NOOR FAEZAH BINTI HAMDI

A project report submitted in partial fulfilment of the

requirements for the award of the degree of

Master of Forensic Engineering.

School of Civil Engineering

Faculty of Engineering

Universiti Teknologi Malaysia

JANUARY 2019

Page 2: NOOR FAEZAH BINTI HAMDI

iii

DEDICATION

This thesis is dedicated to my parents

for their love , endless support

and encouragement.

Page 3: NOOR FAEZAH BINTI HAMDI

iv

ACKNOWLEDGEMENT

"In The Name Of Allah, The Most Beneficient,The Most Merciful"

I would first like to thank my main supervisor, Dr. Mohd Azreen bin Mohd

Ariffin for his continuous support, motivation and encouragement. I am forever

grateful for his kind advice and guidance in helping me for the completion of this

thesis.

My research would have been impossible without the aid and support of Ir.

Dr. Lau Kwan Yiew from School of Electical Engineering. His guidance and

immerse knowledge helped me in all the time of research experiment.

My sincere thanks also goes to the Jabatan Perkhidmatan Awam for the study

opportunity and providing the financial support for me to further my studies at the

Universiti Teknologi Malaysia, Johor. Not to forget, my current employer, Jabatan

Kerja Raya Malaysia for the opportunities and providing me the access, data and

sample for the this research. Financial assistance from the Universiti Teknologi

Malaysia for my research work is highly appreciated.

Finally, to my families and friends, thanks you for being there with your

unconditional love and continuous support.

Page 4: NOOR FAEZAH BINTI HAMDI

v

ABSTRACT

This research presents some results and discusses the investigation on thermal

ageing of low voltage cross-linked polyethylene (XLPE) insulated cable rated at

0.6/1(1.2) kV. This type of cable was found to experience premature degradation

within three to five years of service. The objective of this investigation is to study the

characteristic of XLPE insulated cable under thermal conditions. A number of tests

were conducted to investigate the chemical properties, electrical properties and

mechanical properties of unaged and aged XLPE insulated cable. Samples were

thermally aged using air ventilated oven at temperature of 90 oC. The breakdown

strength of XLPE materials were measured for each samples. The structural changes

due to the formation of carbonyl groups were observed using Fourier Transform

Infrared (FTIR) spectroscopy. The application of Differential Scanning Calorimetry

(DSC) revealed the effect of thermal ageing on the crystallinity variation on XLPE

insulated cable. Mechanical properties were observed through tensile strength test.

Experimental findings in this study suggests that thermal ageing induces significant

degradation on XLPE insulated cable.

Page 5: NOOR FAEZAH BINTI HAMDI

vi

ABSTRAK

Kajian ini menerangkan hasil siasatan dan ujian terhadap kabel voltan rendah

jenis cross-linked polyethylene (XLPE) dengan kadaran penebat pada 0.6 / 1 (1.2)

kilo volts. Kabel jenis ini didapati semakin kerap mengalami kerosakan akibat

pereputan awal dalam tempoh operasi antara tiga hingga lima tahun. Objektif

siasatan ini adalah untuk mengkaji ciri-ciri kabel jenis XLPE apabila diletakkan

dalam keadaan berhaba tinggi. Beberapa siri ujian telah dibuat untuk mengkaji sifat

kimia, elektrikal dan mekanikal kabel jenis XLPE dalam keadaan baru dan lama.

Kabel dipanaskan pada suhu 90 OC di dalam ketuhar sebagai kaedah penghasilan

kabel lama / tua. Kekuatan dielektrik untuk setiap sampel XLPE diukur. Perubahan

struktur bahan akibat pembentukan kumpulan karbonil turut diteliti menggunakan

teknik spektroskopi Fourier Transform Infrared (FTIR). Penggunaan teknik

Differential Scanning Calorimetry (DSC) membolehkan kesan penuaan haba

terhadap perubahan pada penghabluran bahan XLPE. Ciri mekanikal bahan diuji

melalui ujian kekuatan tegangan bahan. Hasil dari kajian ini mendapati bahawa

kesan penuaan haba telah menyebabkan kemerosotan jangka hayat kabel jenis voltan

rendah XLPE.

Page 6: NOOR FAEZAH BINTI HAMDI

vii

TABLE OF CONTENTS

TITLE PAGE

DECLARATION ii

DEDICATION iii

ACKNOWLEDGEMENT iv

ABSTRACT v

ABSTRAK vi

TABLE OF CONTENTS vii

LIST OF TABLES x

LIST OF FIGURES xi

LIST OF ABBREVIATIONS xiii

LIST OF SYMBOLS xiv

LIST OF APPENDICES xv

CHAPTER 1 INTRODUCTION 1

1.1 Problem Background 6

1.2 Problem Statement 6

1.3 Research Objectives 7

1.4 Research Scope 7

1.5 Significance of the Study 5

CHAPTER 2 LITERATURE REVIEW 7

2.1 Introduction 7

Page 7: NOOR FAEZAH BINTI HAMDI

viii

2.2 Characteristics of XLPE Material 9

2.3 Thermal Ageing of the XLPE Material 9

2.4 Oxidation in XLPE Insulation 11

2.5 Electrical Properties of XLPE Insulation 12

2.6 Mechanical Properties of XLPE Insulation 13

2.7 Crystallinity of XLPE Insulation 13

CHAPTER 3 RESEARCH METHODOLOGY 15

3.1 Overview of Research Design 15

3.2 Materials and Preparation 16

3.2.1 Materials 16

3.2.2 Preparation of Materials 19

3.2.3 Thermal Ageing Procedure 19

3.3 Experimental Techniques 20

3.3.1 Breakdown Strength Test 20

3.3.2 Fourier Transform Infrared Spectroscopy 23

3.3.3 Tensile Strength Test 24

3.3.4 Differential Scanning Calorimetry 26

CHAPTER 4 RESULT 29

4.1 Breakdown Strength Test 29

4.2 Fourier Transform Infrared Spectroscopy 33

4.3 Tensile Strength Test 37

4.4 Differential Scanning Calorimetry 42

Page 8: NOOR FAEZAH BINTI HAMDI

ix

CHAPTER 5 DISCUSSION AND CONCLUSION 45

5.1 Discussion of the Results 45

5.1.1 Breakdown Strength Test 45

5.1.2 Fourier Transform Infrared Spectroscopy 46

5.1.3 Tensile Strength Test 51

5.1.4 Differential Scanning Calorimetry 52

5.2 Conclusion 54

REFERENCES 57

APPENDICES 61

Page 9: NOOR FAEZAH BINTI HAMDI

x

LIST OF TABLES

TABLE NO. TITLE PAGE

Table 4.1 Breakdown strength data of cable A and cable C. 23

Table 4.2 Breakdown strength data of cable B and cable C. 24

Table 5.1 Carbonyl compound group frequencies 42

Table 5.2 Functional group found in XLPE Fresh A1 43

Table 5.3 Functional group found in XLPE Fresh B1 44

Table 5.4 Functional group found in XLPE Aged A2 45

Table 5.5 Functional group found in XLPE Aged B2 46

Table 5.6 Functional group found in XLPE Degraded 47

Table 5.7 Crystallinity variation from DSC measurement

(cooling) for XLPE material of cable A and cable C.

51

Table 5.8 Crystallinity variation from DSC measurement

(cooling) for XLPE material of cable B and cable C.

51

Page 10: NOOR FAEZAH BINTI HAMDI

xi

LIST OF FIGURES

FIGURE NO. TITLE PAGE

Figure 1.1 A single core low voltage XLPE insulated cable. 2

Figure 1.2 A multi-core low voltage XLPE insulated cable. 3

Figure 1.3 Degraded red core XLPE cable found in switchboard. 4

Figure 1.4 Degraded XLPE insulated underground cable. 5

Figure 2.1 The ATR principle 9

Figure 3.1 Experimental works 13

Figure 3.2 25 mm2 low voltage XLPE insulated cable from

manufacturer A.

14

Figure 3.3 25 mm2 low voltage XLPE insulated cable from

manufacturer B.

14

Figure 3.4 25 mm2 low voltage XLPE insulated cable from

manufacturer C.

15

Figure 3.5 Oven (Constance Model FC-9023A) for heating

process.

16

Figure 3.6 Breakdown strength test configuration. 17

Figure 3.7 Sample immersed in transformer oil. 18

Figure 3.8 Damaged surface on sample due to breakdown voltage

at 38 kilovolts.

20

Figure 3.8 Shimadzu FTIR Spectrophotometer Model IRTRacer-

100

20

Figure 3.9 LRX 2.5kN Lloyd Tensile Tester. 21

Figure 3.10 Dumb-bell shaped sample piece for tensile test. 21

Figure 3.11 DSC 1 STAR System equipment. 22

Figure 4.1 Weibull plots comparing the AC breakdown strength 24

Page 11: NOOR FAEZAH BINTI HAMDI

xii

of XLPE insulation layer of fresh and aged for cable

by Manufacturer A, and degraded cable.

Figure 4.2 Weibull plots comparing the AC breakdown strength

of XLPE insulation layer of fresh and aged for cable

by Manufacturer B, and degraded cable.

25

Figure 4.3 ATR spectrum for sample XLPE Fresh A1. 26

Figure 4.4 ATR spectrum for sample XLPE Fresh B1. 27

Figure 4.5 ATR spectrum for sample XLPE Fresh A2. 28

Figure 4.6 ATR spectrum for sample XLPE Fresh B2. 29

Figure 4.7 ATR spectrum for sample XLPE Degraded. 30

Figure 4.8 The stress-strain curve of sample XLPE Fresh A1

(kept at room temperature).

31

Figure 4.9 The stress-strain curve of sample XLPE Fresh B1

(kept at room temperature).

32

Figure 4.10 The stress-strain curve of sample XLPE Aged A2

(after heated at temperature 90 OC for 50 hours )

33

Figure 4.11 The stress-strain curve of sample XLPE Aged B2

(after heated at temperature 90 OC for 50 hours)

34

Figure 4.12 DSC thermogram for sample XLPE Fresh A1. 36

Figure 4.13 DSC thermogram for sample XLPE Fresh B1. 37

Figure 4.14 DSC thermogram for sample XLPE Fresh A2. 38

Figure 4.15 DSC thermogram for sample XLPE Fresh B2. 39

Figure 4.16 DSC thermogram for sample XLPE Degraded. 40

Page 12: NOOR FAEZAH BINTI HAMDI

xiii

LIST OF ABBREVIATIONS

XLPE - Cross-linked polyethylene

PVC - Polyvinyl chloride

EPR - Ethylene propylene rubber

IEC - International Electrotechnical Commission

JKR - Jabatan Kerja Raya

EMAL - Electrical Material Approved List

FTIR - Fourier transform infrared

DSC - Differential scanning calorimetry

DCP - Dicumyl peroxide

ATR - Attenuated total reflectance

AC - Alternating current

Hz - Hertz

C-H - Carbon-hydrogen

OH - Oxygen hydrogen (Hydroxy)

Page 13: NOOR FAEZAH BINTI HAMDI

xiv

LIST OF SYMBOLS

EB - Breakdown field

VB - Breakdown voltage

d - sample thickness

F(x) - Cummulative probability of failure

exp - exponential

x - Breakdown voltage

α - Scale parameter

β - Shape parameter

χc - Crystallinity

ΔH0 - Enthalpy corresponding to the melting of 100% crystalline

material

ΔH - Heat of fusion

Page 14: NOOR FAEZAH BINTI HAMDI

xv

LIST OF APPENDICES

APPENDIX TITLE PAGE

APPENDIX A IEC 50602-1 (2004) 61

Page 15: NOOR FAEZAH BINTI HAMDI
Page 16: NOOR FAEZAH BINTI HAMDI

1

CHAPTER 1

INTRODUCTION

1.1 Problem Background

Cross-linked polyethylene (XLPE) is manufactured from polyethylene (PE)

plastic with a three-dimensional molecular bond that is created within a structure of a

plastic. Manufacturing process of XLPE is done by adding small amounts of

chemical additives (such as antioxidants) to the polymer. Additives help improve the

flow properties of a polymer that will be moulded. This process allows the molecular

chains to form a lattice formation by cross-linking the polymer under appropriate

treatment after extrusion (Reeves and Heathcote, 2003).

The process of cross-linking changes its original state from thermoplastic to

thermoset (Tamboli et al, 2004). As a thermoset polymer, it consists of long chain of

molecules that form bonds between the chains during polymerisation. This forms a

single network of polymer chains that are generally not straight, but a tangled mass.

XLPE is commonly used in electrical cable construction for a wide range of

voltage. A study by Dilip K and Das Gupt (1997) had shown the benefis of using

XLPE as insulation material in general are due to their great physical, chemical and

dielectric properties. XLPE is favoured over other insulation material, such as

polyvinyl chloride (PVC), ethylene propylene rubber (EPR) and silicone rubber due

to its toughness against high temperature. This material also has high insulation

resistance, excellent dielectric strength and a low dissipation factor at all frequencies.

Low voltage is a voltage between the range of 50 volts and 1,000 volts

alternating current, as defined by the International Electrotechnical Commission

(IEC). Low voltage XLPE insulated cable are used in low voltage (600/1000 volts)

applications. In Malaysia, this type of cable is designated for general use and for

Page 17: NOOR FAEZAH BINTI HAMDI

2

underground cabling, where lightness and convenience of terminating are major

considerations. XLPE insulated cable also withstands smaller radius bending,

allowing for easy and reliable installation.

The design of low voltage XLPE insulated cable must conform to IEC 60502

(2004) and rated at 600/1000 (1,200) kilovolts. It has plan circular conductors made

of compacted stranded copper or stranded aluminium. The XLPE insulation layer is

rated at temperature of 90 OC. A typical construction of a low voltage XLPE

insulated cable is illustrated in figure 1.1 and figure 1.2.

Figure 1.1 A single core low voltage XLPE insulated cable.

Page 18: NOOR FAEZAH BINTI HAMDI

3

Figure 1.2 A multi-core low voltage XLPE insulated cable.

1.1 Problem Background

Previous studies and researches showed that XLPE cable has a great

performance over high temperature and could last 40 years or more (Anwar ul-

Hamid et al, 2015). However, there are increments in the number of complaints for

insulation failure in low voltage XLPE insulated cable within 5 years of service. This

leads to a temporary suspension in the usage of XLPE insulated cable. The approval

for this type of cable from sizes between 1.5 mm2 up to 25 mm2 has been withdrawn

from the Jabatan Kerja Raya (JKR) Electrical Material Approved List (EMAL).

During installation, cables are subjected to repeated bending or random

flexing causing its copper conductors to be stressed. Mechanical stresses during

installation are generally more severe than those encountered while in service.

Physical damage caused by mishandling of the cables may cause injury to the

Page 19: NOOR FAEZAH BINTI HAMDI

4

insulation layer. Degraded cable can often be found in the electrical switch board is

as shown in figure 1.3

Figure 1.3 Degraded red core XLPE cable found in switchboard.

Page 20: NOOR FAEZAH BINTI HAMDI

5

In the operating environment, constant abrasion of the cable by other cables

could cause failure in cable insulation. Environmental factors such as high humidity

and elevated temperatures can also degrade XLPE insulation layer. Moisture may

exist in cable surroundings and it could affect the basic characteristics of the XLPE

insulation and the realibility of XLPE insulated cables (Mecheri et al, 2010).

According to Jong-Il Weon (2009), the degradation of XLPE is also caused by

exposure to heat, ultraviolet radiation, discolouration among others. Figure 1.4 shows

the degraded XLPE insulated underground cable.

Figure 1.4 Degraded XLPE insulated underground cable.

Page 21: NOOR FAEZAH BINTI HAMDI

6

1.2 Problem Statement

A reliable study on understanding how the degradation mechanism especially

on low voltage system is still lacking although there area high numbers of published

papers related to degradation of XLPE material. A reliable method of investigating

the insulation failure, failure analysis and failure origin must be studied. The

degradation on low voltage XLPE insulated cable is investigated using several

methods comprise of the study of chemical, electrical and mechanical properties of

the XLPE material.

1.3 Research Objectives

This work aims to fabricate a forensic investigation process for cable

insulation failure. Therefore, there is a potential for improvement in identifying the

cause that made the material fails to perform its intended function. The specific

research objectives are as follow;

i) To identify the primary degradation and failure mechanism of

low voltage XLPE insulated cable.

ii) To characterize and compare the properties of the XLPE materials

under different thermal conditions.

iii) To provide thermal ageing analysis for cable failure.

Page 22: NOOR FAEZAH BINTI HAMDI

7

1.4 Research Scope

The scope of research for this experimental study includes;

i) Insulation layer of low voltage XLPE insulated cable was used in this

experiment to study the electrical, mechanical and chemical properties

for both fresh and aged conditions.

ii) Insulation layer of low voltage XLPE insulated cable that had

experienced degradation was also used in this study for reference and

comparison purposes.

iii) The properties and behaviour of each samples were compared and

characterized using breakdown strength test, tensile strength test,

Fourier infrated (FTIR) spectroscopy and differential scanning

calorimetry (DSC).

1.5 Significance of the Study

Eventhough many experimental works have been done to investigate the

degradation of XLPE insulated cable, not much research and publication have been

done particularly for cable degradation in the low voltage cable. Therefore, the

benefits expected from this research are;

i) To determine the condition of low voltage cable failure with the

application of forensic engineering in the investigation.

ii) The use of research information helps to provide forensic engineers

a proper method of doing forensic investigation on cable failure.

Page 23: NOOR FAEZAH BINTI HAMDI

57

REFERENCES

E.A Reeves and Martin J. Heathcote (2003) Newnes electrical pocket book. (ed.)

Britain: Newnes Publication

S M Tamboli, S T Mhaske and D D Kale (2004) 'Crosslinked polyethylene', Indian

Journal of Chemical Technology, (11), 853-864

Dilip K. and Das-Gupta (1997) 'Conduction mechanisms and high-field effects in

synthetic insulating polymers', IEEE Transactions on Dielectrics and Electrical

Insulation, 4(2), 149-156

Ul-Hamid, A., Soufi, K. Y., Al-Hadhrami, L. M., and Shemsi, A. M. (2015). 'Failure

investigation of an underground low voltage XLPE insulated cable', Anti-

Corrosion Methods and Materials, 62(5), 281–287.

https://doi.org/10.1108/ACMM-02-2014-1352

International Electrotechnical Commission (2004) IEC 60502-1. Switzerland:

International Electrotechnical Commission

Y. Mecheri, M. Nedjar, A. Lamure, M. Aufray., and C. Drouet (2010), 'Influence of

moisture on the electrical properties of XLPE insulation'. 2010 Annual Report

Conference on Electrical Insulation and Dielectric Phenomena (CEIDP), pp. 1-

4. http://dx.doi.org/10.1109/CEIDP.2010.5724017

Weon, J. Il. (2010). 'Effects of thermal ageing on mechanical and thermal behaviors

of linear low density polyethylene pipe'. Polymer Degradation and Stability,

95(1), 14–20. https://doi.org/10.1016/j.polymdegradstab.2009.10.016

Page 24: NOOR FAEZAH BINTI HAMDI

58

Mo Shan-jun, Zhang Jun, Liang Dong and Chen Hong-yin (2013), 'Study on

pyrolisis characteristics of cross-linked polyethylene material cable'. Procedia

Engineering 52 (2013), 588-592. doi:10.1016/j.proeng.2013.02.190

Tetiana Salivon and Xavier Colin (2015), 'Degradatio of XLPE and PVC cable

insulators', 2015 Annual Report Conference on Electrical Insulation and

Dielectric Phenomena 18-21 October. Ann Arbor, Michigan: IEEE 656-659

L. Boukezzi, A. Boubakeur, and M. Lallouani (2010),'Oxidation evaluation of cross-

linked polyethylene under thermal degradation : FTIR study', 5th International

Symposium on Hydrocarbons and Chemistry (ISHC5). 23-25 May, Sidi Fredj,

Algiers:

M. Muhr, E. Neges, R. Woschitz, and Ch. Sumereder (2004), 'Aging behaviour of

cross-linked polyethylene (XLPE) as an insulating material for high (HV) and

extra-high voltage cables (EHV). 2004 Annual Report Conference on Electrical

Insulation and Dielectric Phenomena, Boulder, Colorado:

Nobrega, A. M., Martinez, M. L. B., & De Queiroz, A. A. A. (2013), 'Investigation

and analysis of electrical aging of XLPE insulation for medium voltage covered

conductors manufactured in Brazil'. IEEE Transactions on Dielectrics and

Electrical Insulation, 20 (2), 628–640.

https://doi.org/10.1109/TDEI.2013.6508767

L. Boukezzi, M. Nedjar, L. Mokhnache, M. Lallouani, and A. Boubakeur (2006).

'Thermal aging of cross-linked polyethylene'. Annales de Chimie: Science Des

Materiaux, 31(5), 561 – 569. https://doi.org/10.3166/acsm.31.561-569

Page 25: NOOR FAEZAH BINTI HAMDI

59

Emna Khouildi, Rabah Attia, and Rafik Cherni (2017), 'Investigating thermal affect

on a cross-linked polyethylene power cable', Indonesian Journal of Electrical

Engineering and Computer Science, 5(1), 33-40.

https://doi.org/10.11591/ijeecs.v5.i1.pp33-40

Y. Mecheri, S. Bouazabia, and A. Boubakeur, and M.Lallouani (2013). Effect of

thermal Ageing on the Properties of XLPE as an Insulating Material for HV

Cables. International Electrical Insulation Conference, May 2013, Birmingham,

United Kingdom:

C.P Martin, A.S Vaughan and S.J Sutton (2003), 'The thermomechanical behaviour

of crosslinked polyethylene cable insulation material' 2003 Annual Report

Conference on Electrical Insulation and Dielectric Phenomena 88-91. 19-22

Oct, Alburquerque, New Mexico

Kwan Yiew Lau Structure and electrical properties of silica-based polyethylene

nanocomposites, PhD Thesis Universiti of Southampton, 2013

Weon, J. Il. (2010). 'Effects of thermal ageing on mechanical and thermal behaviors

of linear low density polyethylene pipe'. Polymer Degradation and Stability,

95(1), 14–20. https://doi.org/10.1016/j.polymdegradstab.2009.10.016

Geng, P., Song, J., Tian, M., Lei, Z., & Du, Y. (2018). Influence of thermal aging on

AC leakage current in XLPE insulation. AIP Advances, 8(2).

https://doi.org/10.1063/1.5017297

M. Blazso, B.Zelei, and E. Jakab (1995),'Thermal decomposition of low-density

polyethylene in the presence of chlorine-containing polymers', Journal of