DS0.72"DS
Layer 1: AGC ComfortSelect 36 (e=0.036*, #2)ZF-S: Super Spacer Premium
NFRC 102-2010 THERMAL PERFORMANCETEST REPORT
Rendered to:
EARTHWISE GROUP, LLC
SERIES/MODEL: 623.620 Patio Door
90% Argon*
TYPE: Sliding Patio Door
0.27
Reference must be made to Report No. D7298.03-116-46, dated 03/27/15 for complete testspecimen description and data.
Summary of ResultsStandardized Thermal Transmittance (U-Factor)
Gap 1:Clear
Unit Size: 78-3/4" x 78-3/4" (2000 mm x 2000 mm) (Model Size)
Layer 2:
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Report Number:Test Date:
Report Date:
78-3/4" x 78-3/4" (2000 mm x 2000 mm) (Model Size)
NFRC 102-2010 THERMAL PERFORMANCE TEST REPORT
5796 Cedarview Court
Series/Model:
Overall Size:
Test Sample Identification:
Sliding Patio Door
D7298.03-116-46
623.620 Patio Door
Type:
Test Procedure: U-factor tests were performed in a Guarded Hot Box in accordance withNFRC 102-2010, Procedure for Measuring the Steady-State Thermal Transmittance ofFenestration Systems .
Btu/hr·ft2·F (CTS Method)Standardized U-factor (Ust):
This report is a reissue of the original Report No. D7298.01-116-46. This report is reissued inthe name of Earthwise Group, LLC through written authorization of Deceuninck NorthAmerica, LLC.
Test Results Summary:
The Energex Winodw Alliance - Bensalem, Pennsylvania
0.27
NFRC Standard Size:
Test Sample Submitted by:
Test Sample Submitted for: Validation for Recertification (Production Line Unit) no Plant Qualification
Liberty Township, Ohio 45044
Rendered to:
EARTHWISE GROUP, LLC
03/27/1503/19/15
78.7" x 78.7" (2000 mm wide x 2000 mm high)
130 Derry CourtYork, PA 17406
p. 717.764.7700f. 717.764.4129
www.archtest.com www.intertek.com/building
Test Sample Description:
*Stated per Client/Manufacturer N/A Non-Applicable
VinylMitered / Welds / Unsealed
N/AGlazing Method:Exterior Finish:
White Interior Finish:
White
Vinyl
AGC ComfortSelect 36 (e=0.036*, #2)90% Argon*
Single-Probe Method*
Gap 1:DS
0.72"DS
Gas Fill Method:
Daylight Opening:
Active Panel:
VinylExterior Finish:
Material:
Glazing Method:
White
Material:
31-3/4" x 67-3/4"White
Exterior39-7/8" x 75-7/8"
Page 2 of 8
78-3/4" x 78-3/4" (Model Size)
Frame:VY: Vinyl
D7298.03-116-46
Daylight Opening:
31-3/4" x 67-3/4"
WhiteWhite
39-7/8" x 75-7/8"Material:
Daylight Opening:Vinyl
Interior Finish:
*EPS foam located in all panel cavities
Size:
VI: Vinyl with Reinforcement - Interlock (Aluminum)*
ExteriorSize:
Corner Joinery:
Exterior Color:Interior Color:
Vinyl
Exterior Color:Interior Color:Corner Joinery:
Interior Finish:
Mitered / Welds / Unsealed
VP: Vinyl with Reinforcement - Partial*Size:
Exterior Color:
ZF-S: Super Spacer PremiumClear
Exterior Finish:
Corner Joinery:
Layer 1:
Glazing Method:
Vinyl
N/A
Coped / Screws / Sealed
Fixed Panel:
Glazing Information:
Layer 2:
Interior Color:
*Aluminum reinforcement in stiles and bottom rail*EPS foam located in all panel cavities
Test Sample Description: (Continued)
Weatherstripping:
Hardware:
Drainage:
Weepslot
Polypile with center fin
2 Screen track
4
Roller assembly
Metal handle lock assembly
0.50" x 0.50" 4
LocationDrainage Method
Bottom corners of each panel
Fixed panel track sill
Inactive jambs and fixed panel track head3
1 set
Metal keeper
Weep notch 1.00" x 0.13"
1.00" x 0.25"
Size
Sill face and active panel track sill
1Aluminum threshold
Weephole
Aluminum snubber 1
Vinyl insert
Quantity
Polypile with center fin 2 rows Jambs
Lock jamb
Polypile pad
Description
1 Lock stile
1
Bottom corners of active panel
1 row Fixed and active meeting stile
2 Fixed meeting stile
Quantity Location
Quantity
Polypile with center fin
D7298.03-116-46Page 3 of 8
3 rows
LocationDescription
Head and sill
2 Fixed and active meeting stile
Fixed panel track jamb
Fixed panel retainer clip 2 Top and bottom of fixed meeting stile
Fixed panel riser 1 Fixed panel track sill
Vinyl interlock
Measured Test Data
Heat Flows1. Total Measured Input into Metering Box (Qtotal) Btu/hr 2. Surround Panel Heat Flow (Qsp) Btu/hr 3. inches4.5. Metering Box Wall Heat Flow (Qmb) Btu/hr 6. EMF vs Heat Flow Equation (equivalent information) 0.0115*EMF + -0.0177. Flanking Loss Heat Flow (Qfl) Btu/hr 8. Net Specimen Heat Loss (Qs) Btu/hr
Areas1. Test Specimen Projected Area (As) ft2
2. Test Specimen Interior Total (3-D) Surface Area (Ah) ft2
3. Test Specimen Exterior Total (3-D) Surface Area (Ac) ft2
4. Metering Box Opening Area (Amb) ft2
5. Metering Box Baffle Area (Ab1) ft2
6. Surround Panel Interior Exposed Area (Asp) ft2
Test Conditions1. Average Metering Room Air Temperature (th) F2. Average Cold Side Air Temperature (tc) F3. Average Guard/Environmental Air Temperature F4. Metering Room Average Relative Humidity %5. Metering Room Maximum Relative Humidity %6. Metering Room Minimum Relative Humidity %7. Measured Cold Side Wind Velocity (Perpendicular Flow) mph8. Measured Warm Side Wind Velocity (Parallel Flow) mph9. Measured Static Pressure Difference Across Test Specimen 0.00" ± 0.04"H2O
Average Surface Temperatures1. Metering Room Surround Panel F2. Cold Side Surround Panel F
Results
Thermal Transmittance (U-factor)
899.16
Btu/hr·ft2·F0.0236
75.1170.84
10.05
69.80
32.04
Thermal Transmittance of Test Specimen (Us)0.27
68.19-0.22
9.66
1.
71.26
12.66
9.86
-0.38
51.688.00
10.41
NA
50.11
829.47
43.0748.77
7.59
Surround Panel ConductanceSurround Panel Thickness
Page 4 of 8D7298.03-116-46
Btu/hr·ft2·F0.272. Standardized Thermal Transmittance of Test Specimen (Ust) Btu/hr·ft2·F
Calculated Test Data
CTS Method1. Warm Side Emittance of Glass (e1)2. Cold Side Emittance of Glass3. Warm Side Frame Emittance*4. Cold Side Frame Emittance*5. Warm Side Sash/Panel/Vent Emittance*6. Cold Side Sash/Panel/Vent Emittance*7. Warm Side Baffle Emittance (eb1)8. Cold Side Baffle Emittance (eb2)9. Equivalent Warm Side Surface Temperature F
10. Equivalent Cold Side Surface Temperature F11. Warm Side Baffle Surface Temperature F12. Cold Side Baffle Surface Temperature F13. Measured Warm Side Surface Conductance (hh)14. Measured Cold Side Surface Conductance (hc)15. Test Specimen Thermal Conductance (Cs)16. Convection Coefficient (Kc) Btu/(hr·ft2·F1.25)17. Radiative Test Specimen Heat Flow (Qr1) Btu/hr18. Conductive Test Specimen Heat Flow (Qc1) Btu/hr19. Radiative Heat Flux of Test Specimen (qr1)20. Convective Heat Flux of Test Specimen (qc1)21. Standardized Warm Side Surface Conductance (hsth)22. Standardized Cold Side Surface Conductance (hstc)23. Standardized Thermal Transmittance (Ust)
Test Duration1.2.
*Stated per NFRC 101
9.1810.08
Btu/hr·ft2·F
N/A
3.49
395.30Btu/hr·ft2·F
Btu/hr·ft2·F
0.92
55.55
N/A
Page 5 of 8
The thermal performance test results were derived from 02:03 hours, 03/19/15 to 06:03hours, 03/19/15.
Btu/hr·ft2·F4.970.37
0.27
The environmental systems were started at 17:13 hours, 03/18/15.
Btu/hr·ft2·FBtu/hr·ft2·F
5.28
Thermal Transmittance (U-factor)
The test parameters were considered stable for two consecutive four hour test periodsfrom 22:03 hours, 03/18/15 to 06:03 hours, 03/19/15.
1.18 Btu/hr·ft2·F
68.78
434.17
0.900.90
1.35
The reported Standardized Thermal Transmittance (Ust) was determined using CTS Method,per Section 8.2(A) of NFRC 102.
3.
Btu/hr·ft2·F
0.84
D7298.03-116-46
0.84
0.900.90
0.33
Glass collapse determined using a digital glass and air space meter
ANSI/NCSL Z540-2-1997 type B uncertainty for this test was 1.62%.
The test sample was installed in a vertical orientation, the exterior of the specimen was exposedto the cold side. The direction of heat transfer was from the interior (warm side) to the exterior(cold side) of the specimen. The ratings were rounded in accordance to NFRC 601, NFRC Unitand Measurement Policy. The data acquisition frequency is 5 minutes.
“This test method does not include procedures to determine the heat flow due to either airmovement through the specimen or solar radiation effects. As a consequence, the thermaltransmittance results obtained do not reflect performances which are expected from fieldinstallations due to not accounting for solar radiation, air leakage effects, and the thermal bridgeeffects that have the potential to occur due to the specific design and construction of thefenestration system opening. The latter can only be determined by in-situ measurements.Therefore, it is important to recognize that the thermal transmittance results obtained from thistest method are for ideal laboratory conditions and should only be used for fenestration productcomparisons and as input to thermal performance analyses which also include solar, air leakageand thermal bridge effects.”
0.78"0.84"
Page 6 of 8
Glazing Deflection:
D7298.03-116-46
Fixed Panel
Center gap width at laboratory ambientconditions on day of testing
The sample was inspected for the formation of frost or condensation, which may influence thesurface temperature measurements. The sample showed no evidence of condensation/frost atthe conclusion of the test.
Active Panel
Estimated center gap width upon receipt ofspecimen in laboratory (after stabilization)
Edge Gap Width
0.78"
0.72" 0.72"
0.84"
0.72" 0.66"Center gap width at test conditions
Required annual calibrations for the Architectural Testing Inc. 'thermal test chamber' (ICN000001) in York, Pennsylvania were last conducted in May 2014 in accordance withArchitectural Testing Inc. calibration procedure. A CTS Calibration verification was performedDecember 2014. A Metering Box Wall Transducer and Surround Panel Flanking LossCharacterization was performed December 2014.
For ARCHITECTURAL TESTING, INC.
Tested By: Reviewed By:
Ryan P. Moser Shon W. EinsigSenior Technician Senior Technician
Individual-In-Responsible-Charge
RPM:klbD7298.03-116-46
Attachments (pages): This report is complete only when all attachments listed are included.
Submittal Form and Drawings (15)Baffle Wiring Diagram (1)
D7298.03-116-46
"Ratings included in this report are for submittal to an NFRC licensed IA for certificationpurposes and are not meant to be used for labeling purposes. Only those values identified on avalid Certification Authorization Report (CAR) are to be used for labeling purposes."
Page 7 of 8
Architectural Testing, Inc. will service this report for the entire test record retention period. Testrecords that are retained such as detailed drawings, datasheets, representative samples of testspecimens, or other pertinent project documentation will be retained by Architectural Testing,Inc. for the entire test record retention period. The test record retention end date for this reportis March 19, 2019.
This report is a reissue of the original Report No. D7298.01-116-46. This report is reissued inthe name of Earthwise Group, LLC through written authorization of Deceuninck NorthAmerica, LLC.
Appendix-A: Appendix-B:
Architectural Testing, Inc. is accredited by the International Accreditation Service (IAS) under thespecific test methods listed under lab code TL-144, in accordance with the recognizedInternational Standard ISO/IEC 17025:2005. The laboratory’s accreditation or test report in noway constitutes or implies product certification, approval, or endorsement by IAS.
CTS Calibration Data (1)
This report does not constitute certification of this product nor an opinion or endorsement bythis laboratory. It is the exclusive property of the client so named herein and relates only to thespecimen tested. This report may not be reproduced, except in full, without the writtenapproval of Architectural Testing, Inc.
Appendix-D:
Surround Panel Wiring Diagram (1)Appendix-C:
Page 8 of 8
.03R0
Revision(s)
Revision Log
03/27/15
Rev. #
Original Report Issue - Reissue of Report No.D7298.01-116-46 in the name of EarthwiseGroup, LLC.
Date
D7298.03-116-46
Page(s)
All
This report produced from controlled document template ATI 00025(a), revised 03/14/2013.
CTS Test DateCTS Size ft2
CTS Glass/Core ConductanceWarm Side Air Temperature FCold Side Air Temperature FWarm Side Average Surface Temperature FCold Side Average Surface Temperature FConvection Coefficient (Kc)Measured Cold Side Surface Conductance (hc)Measured Thermal Transmittance
4.
1.2. 43.06
05/11/14
69.803. 0.42
D7298.03-116-46Appendix A: CTS Calibration Data
Btu/hr·ft2·F
8. 0.33
5. -0.396. 54.35
Btu/hr·ft2·F
3.88
9. 4.9710. 0.30 Btu/hr·ft2·F
7.Btu/(hr·ft2·F1.25)
+1 +2 +3
+4 +5
+6 +7 +8
D7298.03-116-46Appendix B: Surround Panel Wiring Diagram
+1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30
Appendix C: Baffle Wiring DiagramD7298.03-116-46
Appendix D: Submittal Form and DrawingsD7298.03-116-46
ITEM NO. DESCRIPTION QUANTITY FAB DWG. NO SOURCE
1 HEAD 1 10001100-F-01 A2 JAMB 2 10001100-F-05 A3 EXTERIOR FRAME COVER 1 10001104-F-01 A4 INTERIOR FRAME COVER 2 STRAIGHT CUT A5 SILL 1 10001101-F-01 A6 SILL THRESHOLD 1 10300171-F-01 PPPP7 SILL RISER 1 10001105-F-01 A8 WEATHER-STRIPPING - .270 x .250 AS REQ'D HHHH9
10 MISC SNUBBER 2 10300148-F-01 PPPP11 ROLLER TRACK CAP 1 STRAIGHT CUT N12 L - BRACKET 2 LLLL13 SILL FRAME GASKET 2 CC1415 KEEPER 1 F16 2778 KEEPER - YZD MILD STEEL17 2778 KEEPER - STAINLESS STEEL18 SCREEN KEEPER 1 MMMM19 BUMPER STOP 2 F2021 SCREWS SNUBBER 1622 L - BRACKET - HEAD & SASH 823 L - BRACKET - HEAD & SASH 424 KEEPER (INSTALLATION) 225 SILL RISER 426 FRAME ASSEMBLY 1227 SCREEN KEEPER 2282930
REV DATE DESCRIPTION BY
NAME:
CONFIDENTIAL DWN BY: JGMUNPUBLISHED WORK © 2008 CHKD BY:
DECEUNINCK NORTH AMERICA DWG NO:
QUAS CANLK
DECU-2808-00
#8 x 1.25" PFH - ZINC#8A x 1" PFH - ZINC
DECU-2808-84011H0402152.525
10001105W21255MW
1030014816719-01011H027
623.000 PD - 005
623000PD-005
623.000 PD - 005 - BILL OF MATERIALS 2 LITE
100011001000110010001104
PART NO.
100011041000110110300171
#8 x 2.5" PFH - ZINC#8 x 2.5" PFH - ZINC
#8 x 1.25" PFH - ZINC
THIS DOCUMENT CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION. DO NOT COPY OR DISCLOSE THIS INFORMATION WITHOUT THE EXPRESS WRITTEN CONSENT OF DECEUNINCK NORTH AMERICA. DECEUNINCK NORTH AMERICA RESERVES THE RIGHT TO CHANGE THIS DRAWING AND ANY ASSOCIATED DOCUMENTS.
#8 x 3" PPH - ZINC#6 x .375" PPH
MONROE, OH COPYRIGHT 2008
ITEM NO. DESCRIPTION QUANTITY FAB DWG. NO SOURCE
1 FXD PNL TOP RAIL 1 10001102-F-01 A2 STILE 2 10001102-F-01 A3 BOTTOM RAIL 1 10001102-F-02 A4 INTERLOCK 1 10001117-F-04 A5 SCREW COVER 1 STRAIGHT CUT A6 GLAZING BEAD 4 10001111-F-01 A7 STILE REINFORCEMENT - JAMB 1 STRAIGHT CUT PPPP8 STILE REINFORCEMENT - INTERLOCK 1 STRAIGHT CUT PPPP9 WEATHER-STRIPPING - .270 x .250 AS REQ'D HHHH1011 OPR PNL RAIL - TOP 1 10001102-F-01 A12 STILE - INTERLOCK 1 10001102-F-03 A13 STILE - LOCK 1 10001102-F-04 A14 RAIL - BOTTOM 1 10001102-F-05 A15 INTERLOCK 1 10001117-F-02 A16 SCREW COVER 1 STRAIGHT CUT A17 GLAZING BEAD 4 10001111-F-01 A18 STILE REINFORCEMENT - INTERLOCK 1 STRAIGHT CUT PPPP19 STILE REINFORCEMENT - LOCK 1 10300150-F-01 PPPP20 RAIL REINFORCEMENT - BOTTOM 1 10300150-F-01 PPPP21 WEATHER-STRIPPING - .270 x .250 AS REQ'D HHHH2223 MISC LOCK SET ASSEMBLY - 2817 LOCK W/ TRIMPLATE 1 AMESBURY F24 HANDLE SET ASSEMBLY 1 AMESBURY F25 HANDLE SET - INTERIOR SWITCH AMESBURY26 HANDLE SET - INTERIOR SWITCH / KEY27 HANDLE SET - BLANK28 ROLLER ASSEMBLY - PRECISION 1.66" WHEEL 2 F29 DRAFT PLUG - .810 DIA. 2 HHHH30 3/8" HOLE PLUG 2 D31 IMPACT BRACKET 2 MMMM32 1" INSULATED GLASS - NOTE 233 SETTING BLOCKS (REFER TO IG SUPPLIER GUIDELINES) AS REQ'D34 GLAZING COMPOUND AS REQ'D VENTURE TAPE3536 SCREWS LOCK SET 237 ROLLER ASSEMBLY 438 FIXED PANEL TO JAMB 1039 REINFORCMENT TO PANEL AS REQ'D40 INTERLOCK AS REQ'D41 IMPACT BRACKET 642
NOTE LAMINATED GLASS UTILIZES .090" SOLUTIA PVBREV DATE DESCRIPTION BY
NAME:
CONFIDENTIAL DWN BY: JGMUNPUBLISHED WORK © 2008 CHKD BY:
DECEUNINCK NORTH AMERICA DWG NO:
000.620 PD - 006
000620PD-006
10300151
#8 x 1" PFH - ZINC
9946011H055-D
REFER TO APPLICABLE TEST REPORT
#8 x 1" PPH - ZINC#8 x .75" PFH - PAINTED
1000111710001118
DECU-XXX3
W21255MW
2806/2957-01DECU-XXX1DECU-XXX2
W21255MW
10001102
1000111110300150
10001102
1939-6011-TRUTH
10001102
1000111810001111
THIS DOCUMENT CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION. DO NOT COPY OR DISCLOSE THIS INFORMATION WITHOUT THE EXPRESS WRITTEN CONSENT OF DECEUNINCK NORTH AMERICA. DECEUNINCK NORTH AMERICA RESERVES THE RIGHT TO CHANGE THIS DRAWING AND ANY ASSOCIATED DOCUMENTS.
#8 x .75" PPH - ZINC
DECU-XXX4 ADH-3006
REFER TO APPLICABLE TEST REPORT
MONROE, OH COPYRIGHT 2008
REFER TO APPLICABLE TEST REPORT
#8 x 3" PFH - PAINTED
#8 x 1.5" PFH - ZINC
000.620 PD - 006 - BILL OF MATERIALS 2 LITE
103001501030015010300150
1000110210001117
PART NO.
100011021000110210001102