Power Plant and Transmission System Power Plant and Transmission System Protection Coordination Protection Coordination Fundamentals Fundamentals NERC Protection Coordination Webinar Series June 2, 2010 Jon Gardell

NERC Protection System Protection Fundamentals Public 060210

Embed Size (px)

Citation preview

Page 1: NERC Protection System Protection Fundamentals Public 060210

Power Plant and Transmission System Power Plant and Transmission System Protection Coordination Protection Coordination

FundamentalsFundamentals

NERC Protection Coordination Webinar Series

June 2, 2010

Jon Gardell

Page 2: NERC Protection System Protection Fundamentals Public 060210

2AgendaAgenda

Objective

Introduction to Protection

Generator and Power Plant Protection

• Generator Basics Unique Dynamic Characteristics of Generators

Generator and Auxiliary System Protection Requirements

• Generator Step-Up Transformer Basics Protection Requirements

• Breaker Failure Basics Protection Requirements

Page 3: NERC Protection System Protection Fundamentals Public 060210

3AgendaAgenda

Transmission System Protection Basics

• Step Distance Principles

• Types of Relaying and Schemes Used

• Pilot and Communications

• Infeed

• Benefit of Using Pilot Schemes and Effect on Coordination Issues

Pertinent IEEE Guides for Equipment and System Protection and References

Page 4: NERC Protection System Protection Fundamentals Public 060210

4AgendaAgenda

Summary of What is Important to Coordination

Questions and Answers

Page 5: NERC Protection System Protection Fundamentals Public 060210

5DisclaimerDisclaimer

The information from this webcast is provided for informational purposes only. An entity's adherence to the examples contained within this presentation does not constitute compliance with the NERC Compliance Monitoring and Enforcement Program ("CMEP") requirements, NERC Reliability Standards, or any other NERC rules. While the information included in this material may provide some of the methodology that NERC may use to assess compliance with the requirements of certain Reliability Standards, this material should not be treated as a substitute for the Reliability Standard or viewed as additional Reliability Standard requirements. In all cases, the entity should rely on the language contained in the Reliability Standard itself, and not on the language contained in this presentation, to determine compliance with the NERC Reliability Standards.

Page 6: NERC Protection System Protection Fundamentals Public 060210

6ObjectiveObjective

Increase knowledge of recommended protection for power plant and transmission system.

• Provide transmission protection engineers with insight into power plant protection issues.

• Provide power plant protection engineers with insight into transmission protection issues.

• Provide planning engineers with insight into how power plant and transmission protection respond to system conditions.

Facilitate improved coordination between power plant and transmission system protection.

Page 7: NERC Protection System Protection Fundamentals Public 060210

7Introduction to ProtectionIntroduction to Protection

Reliability

Security

Dependability

Coordination

Electrical Protection Definitions can be found in IEEE Dictionary Standard 100.

Page 8: NERC Protection System Protection Fundamentals Public 060210

8Generator and Power Plant BasicsGenerator and Power Plant Basics

Typical Steam Turbine Generator found in a Power

Plant

Page 9: NERC Protection System Protection Fundamentals Public 060210

9

The Role of the The Role of the Generator in the Power SystemGenerator in the Power System

Production of Electrical Energy to Meet Load Demand and System Losses

Balance of Energy and Stability

Dynamic Behavior

Voltage Support

System Frequency

Page 10: NERC Protection System Protection Fundamentals Public 060210

10Balance of Energy and StabilityBalance of Energy and Stability

Power System Stability - “If the oscillatory response of a power system during the transient period following a disturbance is damped and the system settles in a finite time to a new steady operating condition we say the system is stable. If the system is not stable, it is considered unstable.”

Page 11: NERC Protection System Protection Fundamentals Public 060210

11Dynamic Behavior of GeneratorsDynamic Behavior of Generators

Synchronous generators can adjust to changing load conditions fairly readily.

For small load changes a generator easily can adjust as long as there is a reserve capability.

Machine characteristics, excitation performance, and the severity of the disturbance will dictate a generator’s stability during large transient events.

Page 12: NERC Protection System Protection Fundamentals Public 060210

12

Synchronous Generator Synchronous Generator Equivalent CircuitEquivalent Circuit

Synchronous Generator Equivalent Circuit identifying armature reaction and armature leakage reactance and air-gap voltage

X armature leakageX armature reaction

E excitation

R armature

X synchronous

V terminalE air gap

Page 13: NERC Protection System Protection Fundamentals Public 060210

13Voltage SupportVoltage Support

Generators on the system are used to maintain voltage.

Automatic Voltage Regulators are set to meet a scheduled system voltage and provide reactive power support.

Generators provide system control by maintaining terminal voltage during real and reactive power load changes.

Page 14: NERC Protection System Protection Fundamentals Public 060210

14System FrequencySystem Frequency

Balance between generators and system loads.

System frequency is maintained through turbine speed control.

Excessive load will bog down the system frequency.

Light load conditions will increase system frequency.

Page 15: NERC Protection System Protection Fundamentals Public 060210

15

Unique Dynamic Characteristics Unique Dynamic Characteristics of Generators - Short Circuit Current of Generators - Short Circuit Current DecrementsDecrements

Time (Cycles)5 10 15 20 25

2

4

6

8

10

12

14

00

Asymmetrical RMS Current

1

3

5

7

9

11

13

DCCurrent

Symmetrical RMS Current

Cur

rent

in A

mpe

res

(x 1

000)

Reference: Fitzgerald, A. E. , Kingsley, Charles, and Umans, Stephen, Electric Machinery, fourth edition, McGraw-Hill Book Company, New York, 1983.

Page 16: NERC Protection System Protection Fundamentals Public 060210

16

Power Plant EquipmentPower Plant EquipmentProtection RequirementsProtection Requirements

51T

87G

87T

21 32 40 46 51V 78

24 27 59 81

50/27

R

51G 51TG

50BF

59GN/27TH

87U

Page 17: NERC Protection System Protection Fundamentals Public 060210

17

Generator Fault and Abnormal Generator Fault and Abnormal Operating Conditions Operating Conditions

Generator Faults• Stator Phase

• Stator and Field Ground

Generator Step-up Transformer Faults• Phase and Ground

System Back Up for Faults• Phase and Ground

Abnormal Operating Conditions

• Over/undervoltage

• Overexcitation

• Load Unbalance

• Loss-of-Field

• Loss-of-Synchronism (Out-of-Step)

• Over/underfrequency

• Loss of Prime mover (Motoring)

• Inadvertent Energizing

• Breaker Failure

Page 18: NERC Protection System Protection Fundamentals Public 060210

18

Pertinent Power Plant Protection for Pertinent Power Plant Protection for Coordination ConsiderationsCoordination Considerations

Phase Distance Protection (Function 21)

Overexcitation or V/Hz (Function 24)

Undervoltage Protection (Function 27)

• Generator Unit Protection

• High Side Protection Applied at Point of Common Coupling

• Generating Plant Auxiliary Power Supply Systems

Reverse Power Protection (Function 32)

Loss-of-Field Protection (LOF) (Function 40)

Negative Phase Sequence or Unbalanced Overcurrent Protection (Function 46)

Inadvertent Energizing Protection (Function 50/27)

Breaker Failure Protection (Function 50BF)

Page 19: NERC Protection System Protection Fundamentals Public 060210

19

Pertinent Power Plant Protection for Pertinent Power Plant Protection for Coordination ConsiderationsCoordination Considerations

Backup Phase (Function 51T) and Backup Ground Overcurrent Relay (Function 51TG)

Voltage-Controlled or -Restrained Overcurrent Relay (Function 51V)

Overvoltage Protection (Function 59)

Stator Ground Relay (Function 59GN/64G)

Out-of-Step or Loss-of-Synchronism Relay (Function 78)

Over and Underfrequency Relay (Function 81)

Transformer Differential Relay (Function 87T), Generator Differential Relay (Function 87G) Protection and Overall Differential Protection (Function 87U)

Page 20: NERC Protection System Protection Fundamentals Public 060210

20Phase Distance Protection (Function 21)Phase Distance Protection (Function 21)

Distance protection to provide back-up protection for system faults that have not been cleared by transmission system circuit breakers via their relays.

Impedance measurement derived from the quotient of generator terminal voltage divided by generator stator current.

• Machine Coverage

• System Relay Failure Coverage

Coordination Concerns – Undesired operation for system conditions; especially stressed voltage situations and power swings.

Page 21: NERC Protection System Protection Fundamentals Public 060210

21

Overexcitation or V/Hz Overexcitation or V/Hz Protection (Function 24)Protection (Function 24)

Protection measures a ratio of voltage to frequency at the generator terminals.

Provides overexcitation protection for the generator and any terminal connected transformers, i.e. GSU and auxiliaries.

Overexcited magnetic cores can lead to severe overheating and breakdown in insulation.

Coordination Concerns – Coordinate with Underfrequency Load Shedding (UFLS) programs in the system.

Page 22: NERC Protection System Protection Fundamentals Public 060210

22

Undervoltage Protection (Function 27)Undervoltage Protection (Function 27)Generator Unit ProtectionGenerator Unit Protection

Typically provides alarm and supervision for other protection using generator terminal voltage. Rarely used to trip the generator directly.

Provides detection of low voltage that may result in reduction in stability limit, excessive reactive power drawn from the system, and malfunction of voltage sensitive devices and equipment.

Coordination Concerns – Coordinate with any system undervoltage protection, system fault conditions, and stressed system voltage situations for which the system is designed to survive.

Page 23: NERC Protection System Protection Fundamentals Public 060210

23

Undervoltage Protection (Function 27) Undervoltage Protection (Function 27) High Side Protection at Point of Common High Side Protection at Point of Common CouplingCoupling

Protection measures system voltage at the point of common coupling.

Provides a trip of the distributed resource on undervoltage if it is islanded with local load or is subjected to a prolonged system fault.

Coordination Concerns – Coordinate with:

• Any system undervoltage protection,

• System fault conditions and stressed system voltage conditions for which the system is designed to survive.

Page 24: NERC Protection System Protection Fundamentals Public 060210

24

Undervoltage Protection (Function 27) Undervoltage Protection (Function 27) Generating Plant Auxiliary Power SystemsGenerating Plant Auxiliary Power Systems

Protection measures auxiliary system voltage.

Provides alarming or tripping, automatic transfer to backup supply, starting emergency generation.

Coordination Concerns – Coordinate with:

• Any system undervoltage protection,

• System fault conditions and stressed system voltage situations for which the system is designed to survive.

Page 25: NERC Protection System Protection Fundamentals Public 060210

25

Concerns with Auxiliary System Concerns with Auxiliary System Power Supply SourcePower Supply Source

GSU

G

Auxiliary

Backup Power Supply

27

Power Plant

Station Service

Trasfer Switch

System

GSU

G

Auxiliary

27

PowerPlant

StationService

TrasferSwitch

System

System

Unit Auxiliary Transformer Supplied Scheme

Transmission System Transformer Supplied Scheme

Page 26: NERC Protection System Protection Fundamentals Public 060210

26Reverse Power Protection (Function 32)Reverse Power Protection (Function 32)

Protection measures reverse power derived from the real component of generator voltage times generator stator current times the square root of three.

Provides protection of the prime mover from damage due to motoring.

Coordination Concerns - None

Page 27: NERC Protection System Protection Fundamentals Public 060210

27

Loss-of-Field (LOF) Protection Loss-of-Field (LOF) Protection (Function 40)(Function 40)

Protection measures impedance derived from the quotient of generator terminal voltage divided by generator stator current.

Provides detection and protection for complete or partial loss of the field excitation due to field winding open or shorts, tripping of the field breaker, loss of supply, or voltage regulation failure.

Coordination Concerns – Undesired operation during system disturbances and system power swings that are recoverable.

Page 28: NERC Protection System Protection Fundamentals Public 060210

28

Negative Phase Sequence or Negative Phase Sequence or Unbalanced Overcurrent Protection (Function Unbalanced Overcurrent Protection (Function 46)46)

Protection measures stator negative sequence current produced by the unbalanced conditions of the system to which the generator is connected.

Provides protection from excessive negative sequence currents due to asymmetries, unbalanced loads, unbalanced system faults, and open phases. This can cause rotor component heating damage.

Coordination Concerns – • Coordinate with system protection for unbalanced conditions.

• Awareness of continuous negative sequence level due to system conditions and coordinate the continuous negative sequence current protection or alarm such that it does not exceed the generator capability.

Page 29: NERC Protection System Protection Fundamentals Public 060210

29

Inadvertent Energizing Protection Inadvertent Energizing Protection (Function 50/27)(Function 50/27)

Protection measures both generator terminal voltage and generator stator current to detect inadvertent energizing of the generator.

Provides detection of accidental energizing of an off-line unit causing it to start-up as an induction motor. Significant damage can occur in a few seconds of machine motoring through the GSU transformer.

Coordination Concerns – • Set point of the undervoltage supervision should be below 50

percent nominal voltage with at least a two second time delay.

• Undesired tripping due to a higher set point should be avoided during stressed system conditions and disturbances that can be survived.

Page 30: NERC Protection System Protection Fundamentals Public 060210

30

Voltage-Controlled or -Restrained Voltage-Controlled or -Restrained Overcurrent Protection (Function 51V)Overcurrent Protection (Function 51V)

Protection measures generator terminal voltage and generator stator current. The current sensitivity varies as a function of the terminal voltage.

Provides back-up protection for system faults when the power system that the generator is connected to is protected by time-current coordinated protection.

Coordination Concerns –

• Coordinate with system elements for faults.

• Not recommended when system protection is distance type protection.

Page 31: NERC Protection System Protection Fundamentals Public 060210

31Overvoltage Protection (Function 59)Overvoltage Protection (Function 59)

Protection measures generator terminal voltage.

Provides protection against generator overvoltage. This prevents generator insulation breakdown for sustained overvoltage.

Coordination Concerns – Coordinate with any system overvoltage protection.

Page 32: NERC Protection System Protection Fundamentals Public 060210

32

Stator Ground Protection Stator Ground Protection (Function 59GN/64G, 27TH)(Function 59GN/64G, 27TH)

Protection measures the generator neutral zero sequence voltage.

Provides protection for generator system ground faults.

Coordination Concerns – Proper time delay is required so that the protection does not trip due to inter-winding capacitance issues for faults on the system or instrument secondary grounds.

Page 33: NERC Protection System Protection Fundamentals Public 060210

33

Out-of-Step or Loss-of-Synchronism Out-of-Step or Loss-of-Synchronism Protection (Function 78)Protection (Function 78)

Protection uses a measurement of apparent impedance derived from the quotient of generator terminal voltage divided by generator stator current.

Provides loss-of-synchronism (out-of-step) protection for system swings that have electrical centers located near the generator and its step-up transformer.

Coordination Concerns –

• Undesired operation during system disturbances.

• System power swings that are recoverable. Stability studies need to be performed.

Page 34: NERC Protection System Protection Fundamentals Public 060210

34

Over and Underfrequency Protection Over and Underfrequency Protection (Function 81)(Function 81)

Protection measures voltage frequency to detect over and underfrequency conditions.

Provides protection against sustained abnormal frequency operation for the prime mover and generator.

Coordination Concerns –

• Coordination is required with the system underfrequency load shedding (UFLS) program and stressed system frequency conditions for which the system is designed to survive.

• The UFLS needs to take action first to arrest the abnormal frequency condition.

Page 35: NERC Protection System Protection Fundamentals Public 060210

35

Generator Differential Protection (Function 87G) Generator Differential Protection (Function 87G)

and Overall Differential Protection (Function and Overall Differential Protection (Function 87U)87U)

Protection measures difference current in its associated zone.

Provides high-speed phase fault protection for the generator zone (87G) and unit overall zone (87U)

Coordination Concerns – None except to ensure overlaps are done correctly.

Page 36: NERC Protection System Protection Fundamentals Public 060210

36Generator Step-Up Transformer BasicsGenerator Step-Up Transformer Basics

GSU Transformer, Auxiliary Transformer and Isolated Phase Bus

Page 37: NERC Protection System Protection Fundamentals Public 060210

37

Backup Phase (Function 51T) and Backup Backup Phase (Function 51T) and Backup Ground Overcurrent Protection (Function 51TG)Ground Overcurrent Protection (Function 51TG)

Protection measures GSU phase and neutral ground current.

Provides back-up protection for faults in both the GSU and generator, and for system faults.

Coordination Issues –

• Coordinate with generator protection and the slowest system protection.

• Use of the backup phase protection (Function 51T) is not recommended due to the difficulty of coordinating with system protection functions and the detection of faults due to the generator fault current decrement.

Page 38: NERC Protection System Protection Fundamentals Public 060210

38

Backup Phase Overcurrent Backup Phase Overcurrent Protection (Function 51T) Protection (Function 51T)

If function 51T is applied, it must be set to the following requirements:• The 51T must have a minimum pickup of twice the generator

MVA rating at rated power factor.

• The 51T must operate slower with margin than the slowest transmission protection system that it must coordinate with based on protection design including breaker failure time.

• The 51T must sense the required fault based on the transmission protection design with the fault current available from the generator in the time frame that it is set to operate.

• The Generator Owner must determine that the setting for the 51T that coordinates with the transmission protection will also coordinate with the generator protection systems for the fault current available from the transmission system.

Page 39: NERC Protection System Protection Fundamentals Public 060210

39

Backup Ground Overcurrent Backup Ground Overcurrent Protection (Function 51TG)Protection (Function 51TG)

Function 51TG must be set to the following requirements:

• The 51TG must have a pickup with margin greater than the largest non-fault system unbalance anticipated based on system design.

• The 51TG must operate slower with margin than the slowest transmission protection system that it must coordinate with based on protection design including breaker failure time.

Page 40: NERC Protection System Protection Fundamentals Public 060210

40

Transformer Differential Protection Transformer Differential Protection (Function 87T)(Function 87T)

Protection measures difference current in its associated transformer zone.

Provides high speed phase fault protection for the transformer zone (87T).

Coordination Concerns – None except to ensure overlaps are done correctly.

Page 41: NERC Protection System Protection Fundamentals Public 060210

41Breaker Failure BasicsBreaker Failure Basics

HV Substation Breaker

Page 42: NERC Protection System Protection Fundamentals Public 060210

42

Breaker Failure Protection Breaker Failure Protection (Function 50BF)(Function 50BF)

Protection measures breaker current and monitors the breaker “a” switch.

If the generator breaker does not clear the fault or abnormal condition in a specified time, the timer will trip the necessary breakers to remove the generator from the system.

Coordination Issues – • All upstream (next level) protection settings and systems must

be considered when evaluating the performance of breaker failure functions associated with generators.

• Total clearing time, which includes breaker failure time, of each breaker in the generation station substation should coordinate with the critical clearing times associated with unit stability.

Page 43: NERC Protection System Protection Fundamentals Public 060210

43

Breaker Failure Protection Breaker Failure Protection (Function 50BF)(Function 50BF)

Page 44: NERC Protection System Protection Fundamentals Public 060210

44Transmission System BasicsTransmission System Basics

Types of Relaying and Schemes Used

Step Distance Principles

Pilot and Communications

Infeed

Benefits of Using Pilot Schemes and Effect on Coordination Issues

Page 45: NERC Protection System Protection Fundamentals Public 060210

45Types of Relaying and Schemes UsedTypes of Relaying and Schemes Used

Overcurrent (50, 51, 50N, 51N, 50G, 51G)

Directional Overcurrent (67, 67N)

Distance (21, 21N)

Differential (87)

Step Distance

Pilot (Communication-Aided) Schemes

Page 46: NERC Protection System Protection Fundamentals Public 060210

46Step Distance PrinciplesStep Distance Principles

Zones

• Zone 1

• Zone 2

• Zone 3

Page 47: NERC Protection System Protection Fundamentals Public 060210

47Pilot and CommunicationsPilot and Communications

Pilot schemes use communication channels to send data from the local protection terminal to the remote protection terminal(s).

This information allows high-speed tripping to occur for faults occurring on 100% of the protected line.

General Schemes Used:

• Transfer Trip

• Directional Comparison

• Current Differential

• Phase Comparison

Page 48: NERC Protection System Protection Fundamentals Public 060210

48InfeedInfeed

A source of fault current between a relay location and a fault location.

Infeed has the effect of causing the relay to measure a higher impedance than the actual impedance between the relay and the fault location.

The method of calculating the effect of infeed (also known as apparent impedance) is akin to a current divider relationship of two circuit paths in parallel. • The positive sequence equivalent diagram for the example is

shown on the next slide.

• The model combines impedances behind the faulted line.

• The generator impedance relay measures the quotient Vgen/Irelay

Page 49: NERC Protection System Protection Fundamentals Public 060210

49Current Infeed Example CalculationCurrent Infeed Example Calculation

Xline

(Xsys Bus A + XL1)//(Xsys Bus C + XL2)= XB

XA = X’d + XTR

Vgen = V relay

IA =Irelay

IB

IA + IB

I = IA + IB I

IB

IA

XB

XA

XLine

Restating I in terms of IA and recognizing

the current divider relationship of the impedance branches:

Re

Re

ReRe

Re

BA

A B

B AA

B

B Alay A TR A Line

B

lay A

lay B Alay TR Line

lay B

XI I

X X

X XI I

X

X XV I X I X

X

I I

V X XZ X X

I X

Page 50: NERC Protection System Protection Fundamentals Public 060210

50

Benefits of Using Pilot Schemes and Benefits of Using Pilot Schemes and Effect on Coordination IssuesEffect on Coordination Issues

Provides high-speed fault clearing.

Impacts on dependability and security are dependent on the type of Pilot Scheme implemented.

These factors are related and require a balance.

Power Plant to Transmission System Protection Coordination could benefit from the use of Pilot Schemes due to higher speed and more selective operation.

Communication back to the plant system would also benefit the coordination.

Page 51: NERC Protection System Protection Fundamentals Public 060210

51

Pertinent IEEE Guides for Pertinent IEEE Guides for Equipment and System ProtectionEquipment and System Protection

IEEE Std. C37.91-2008 – IEEE Guide for Protecting PowerTransformers

IEEE Std. C37.96-2000 – IEEE Guide for AC Motor Protection

IEEE Std. C37.101-2006 – IEEE Guide for AC Generator Ground Protection

IEEE Std. C37.102-2006 – IEEE Guide for Generator Protection

IEEE Std. C37.106-2005 – IEEE Guide for Abnormal Frequency Protection for Power Generating Plants

IEEE Std C37.113-1999(R2004) – IEEE Guide for Protective Relay Applications to Transmission Lines

IEEE Std. C37.119-2005 – Guide for Breaker Failure Protection of Power Circuit Breakers

IEEE Std. 242-2001 – IAS Buff Book – Protection and Coordination

Page 52: NERC Protection System Protection Fundamentals Public 060210

52ReferencesReferences

IEEE Press Book - Protective Relaying for Power Systems: Volume 1, 1980.

IEEE Press Book - Protective Relaying for Power Systems: Volume 2, 1992.

J. Lewis Blackburn, “Protective Relaying: Principles and Applications”, Marcel Dekker, Inc., 1987.

S. Horowitz and A. Phadke, “Power System Relaying”, John Wiley & Sons, Inc., 1992.

A. E. Fitzgerald, Charles Kingsley, Jr., Stephen D. Umans “Electric Machinery”, McGraw-Hill Book Company, 1983.

Page 53: NERC Protection System Protection Fundamentals Public 060210

53ReferencesReferences

C. R. Mason, “The Art and Science of Protective Relaying”, Wiley, 1956.

Westinghouse Electric Corporation, “Applied Protective Relaying”, Westinghouse , 1982.

IEEE/PSRC Working Group Report, “Application of Multifunction Generator Protection Systems,” IEEE Transactions on Power Delivery, Vol. 14, No. 4, Oct 1999, P 1285-94.

Patel, S. C., Chau, N. H. and Gardell, J. D., “Upgrading and Enhancing the Generator Protection System By Making Use of Digital Systems,” 24th Annual Western Protective Relay Conference Oct 21 - Oct 23, 1997.

Yalla, M.V.V.S., “A Digital Multifunction Protective Relay,” IEEE Transactions on Power Delivery, Vol. 7, No. 1, pp. 193-200, January 1992.

Page 54: NERC Protection System Protection Fundamentals Public 060210

54

What is Important to What is Important to Coordination – SummaryCoordination – Summary

Distance Protection – Time Coordination, Loadability, and Power Swings

Overcurrent Protection – Time-Current Coordination and Loadability

Voltage Protection – Time-Voltage Coordination and stressed system voltage conditions for which the system is designed to survive

Volts per Hertz and Frequency Protection – Coordinate with Underfrequency Load Shedding and stressed system frequency conditions for which the system is designed to survive

Loss of Excitation and Loss of Synchronism – Coordinate with system disturbances and system power swings that are recoverable

Generator Breaker Failure – Total and Critical Clearing Times

Page 55: NERC Protection System Protection Fundamentals Public 060210

55

Question & Answer