Rev. 042010 AL842ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Altronix Corp.

NAC Power Extender Installation Guide · 24VDC/7AH 24 Hours 6.5 amp/5 minutes ---24VDC/12AH (use two (2) 12VDC batteriesin series) 24 Hours 6.5 amp/5 minutes 50mA 24VDC/36AH 24 Hours

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NAC Power Extender Installation Guide · 24VDC/7AH 24 Hours 6.5 amp/5 minutes ---24VDC/12AH (use two (2) 12VDC batteriesin series) 24 Hours 6.5 amp/5 minutes 50mA 24VDC/36AH 24 Hours

Rev. 042010

AL842ULADANAC Power Extender

Installation Guide(See Application Guide for additional information)

Altronix Corp.140 58th St. Brooklyn, NY

Page 2: NAC Power Extender Installation Guide · 24VDC/7AH 24 Hours 6.5 amp/5 minutes ---24VDC/12AH (use two (2) 12VDC batteriesin series) 24 Hours 6.5 amp/5 minutes 50mA 24VDC/36AH 24 Hours

- 2 - AL842ULADA

Agency Listings:• ULListedforControlUnitsforFireProtective SignalingSystems(UL864).• MEA-NYCDepartmentofBuildingsApproved.• CSFM-CaliforniaStateFireMarshalApproved.• FM-FactoryMutualApproved.• NFPA72Compliant.Input:• Powerinput120VAC/60Hz,5amp.• Two(2)ClassA,StyleZortwo(2)ClassB, StyleW,YFACPinputs.• Two(2)NCdrycontacttriggerinputs.Output:• Class2Ratedpowerlimitedoutputs.• 24VDCvoltageregulatedpowerlimitedoutputs.• 8ampmaxtotalalarmcurrent.• 2.5Amaxcurrentperoutput.• Twoauxiliaryoutputsratedat1ampeach (1ampcontinuous,1ampACdisconnect).• Programmablesupervisedindicatingcircuitoutputs: Four(4)ClassB,StyleW,YorFour(4)ClassA, StyleZorTwo(2)ClassA,StyleZandTwo(2)ClassB, StyleW,Y(see Application Guide).•Thermalandshortcircuitprotectionwithautoreset.Battery Backup:•Built-inchargerforsealedleadacidorgeltypebatteries.•Automaticswitchovertostand-bybatterywhen ACfails.• Zerovoltagedropwhenswitchingoverto batterybackup.

Supervision:•ACfailsupervision(form“C”contact,1amp/28VDC). Factorysetfor30secondswithoptional2.5to3hour delaysetting(fieldselectable).• InstantlocalACtroublereportingrelay (form“C”contact,1amp/28VDC).•Batterypresenceandlowbatterysupervision (form“C”contact,1amp/28VDC).Visual Indicators:•InputandoutputstatusLEDindicators.Special Features:• 2-wirehorn/strobeSyncmodeallowsaudible notificationappliances(horns)tobesilenced whilevisualnotificationappliances(strobes) continuetooperate.• SyncprotocolsincludePotter/Amseco,Faraday, Gentex®,SystemSensor®,andCooperWheelock®.• TemporalCode3,SteadyMode,InputtoOutput FollowerMode(maintainssynchronizationof notificationappliancescircuit).• Compatiblewith12VDCor24VDCfirepanels.•Outputloopsupervisiondirectedtoinput1orinput2.•SignalCircuitTroubleMemory-facilitatesquick identificationofanintermittent/fault(shortcircuit,openorground)whichhaspreviouslyoccurredononeor moresignalingcircuitoutputs.LEDsindicate/identifywhichoutputthefaulthasoccurred.• Commontroubleinputandoutput.• Groundfaultdetection.•Unitincludespowersupply,logicboardenclosure, camlock,andbatteryleads.Enclosure Dimensions (approx. H x W x D):18”x14.5”x4.625”(457.2mmx368.3mmx117.48mm)

Overview:TheAltronixAL842ULADAisanextremelycosteffective8ampremotepowersupply/batterycharger.Itmaybecon-nectedtoany24voltFireAlarmControlPanel(FACP).PrimaryapplicationsincludeNotificationApplianceCircuit(NACsuchasstrobesandhorns)expansionsupporttomeetADArequirements.Italsoprovidesauxiliarypowertosupportsystemaccessories.Theunitdeliverselectronicallyregulatedandfiltered24voltpowertoClassB,StyleW,YorClassA,StyleZNACloopcircuits.Additionally,aseparate1ampauxiliaryoutputfor4-wiresmokedetectorsisavailable.The8ampmax.alarmcurrentcanbedividedbetweenthefour(4)outputsforpoweringNACdevices.Eachoutputisratedat2.5ampmax.,andcanbeindependentlyprogrammedforSteady,TemporalCode3orStrobeSynchronization.AlloutputsmaybeprogrammedforInputtoOutputFollowerMode(outputwillfollowinput).Innon-alarmconditionindependentloopsupervisionforClassA,StyleZand/orClassB,StyleW,YFACPNACcircuitsisprovided.Intheeventofalooptrouble,theFACPwillbenotifiedviathesteeredinput(input1orinput2).Inaddition,therearecommontroubleoutputterminals[NC,C,NO]whichareusedtoindicategeneralloop/systemtrouble.Acommontroubleinputisprovidedforoptional[NC](normallyclosed)devicestoreporttroubletotheFACP.Two(2)FACPsignalingoutputscanbeemployedanddirectedtocontrolsupervisionandpowerdeliverytoanycombinationofthefour(4)outputs.

Specifications:

AL842ULADA - NAC Power Extender

Page 3: NAC Power Extender Installation Guide · 24VDC/7AH 24 Hours 6.5 amp/5 minutes ---24VDC/12AH (use two (2) 12VDC batteriesin series) 24 Hours 6.5 amp/5 minutes 50mA 24VDC/36AH 24 Hours

AL842ULADA - 3 -

Power Supply Specifications:AC Input: 120VAC60Hz,5ampsuppliedbyamaximum15ampdedicatedbranchcircuit.

Output:Four(4)regulatedsupervisedNACoutputcircuits,24VDC,2.5ampmaximumcurrent.One(1)aux.specialapplication24VDCpoweroutputcircuit1amp,non-supervisedtotaloutputcurrentmustnotexceedcurrent8ampinAlarmCondition.

Battery: Usetwo(2)12VDC/12AHortwo(2)12VDC/7AHbatteriesconnectedinseries.

Stand-by/Alarm Current Consumption:

90mA/175mA

EOL Resistor (end of line): 2.2K(2200ohm),AltronixModel#AL-EOL22(included).

Ground fault maximumtest impedance:

1000ohm.

Stand-by Specifications:Stand-by Batteries Stand-by Time Total Amp/Minutes Alarm Output Current Aux. Output

24VDC/7AH 24Hours 6.5amp/5minutes ---

24VDC/12AH(usetwo(2)12VDCbatteriesinseries)

24Hours 6.5amp/5minutes 50mA

24VDC/36AH 24Hours 6.5amp/5minutes 1amp

Note: Unit is equipped with two (2) 1 amp max. auxiliary outputs: “AUX1” will automatically disconnect whenAC is lost. “AUX2” will remain battery backed up during power outage. For loads connected to “AUX2” please, refer to battery “Stand-by Specifications” above for ratings. When loads are connected to the “AUX1” and or “AUX2” outputs during alarm condition, the remaining outputs may not exceed 8 amp total alarm current. (example: AUX1 = 1 amp, AUX2 = 1 amp, outputs up to 7 amp).

Installation Instructions:WiringmethodsshallbeinaccordancewiththeNationalElectricalCode/NFPA70/NFPA72/ANSI,andwithalllocalcodesandauthoritieshavingjurisdiction.Productisintendedforindooruseonly.Carefully review: Application Guide for AL642ULADA, AL842ULADA, AL1042ULADA Power Supply Output Specifications (pg. 3) Stand-by Specifications (pg. 3) Output Programming Selection Table (pg. 4) Sync Mode Selection Table (pg. 4) Terminal Identification Table (pgs. 5-6) LED Diagnostics (pg. 6)1.Mounttheunitinthedesiredlocation.Markandpredrillholesinthewalltolineupwiththetoptwokeyholesinthe enclosure.Installtwoupperfastenersandscrewsinthewallwiththescrewheadsprotruding.Placetheenclosure’s upperkeyholesoverthetwoupperscrews;levelandsecure.Markthepositionofthelowertwoholes.Removethe enclosure.Drillthelowerholesandinstalltwofasteners.Placetheenclosure’supperkeyholesoverthetwoupper screws.Installthetwolowerscrewsandmakesuretotightenallscrews(Enclosure Dimensions, pg. 8). Secureenclosuretoearthground(Fig. 1, pg. 3).2.Connecttheline(L)andneutral(N)terminalstoaseparateunswitchedACcircuit(120VAC,60Hz) dedicatedtotheFireAlarmSystem.3.Measureoutputvoltagebeforeconnectingdevices.Thishelpsavoidingpotentialdamage.4.Connectbatterytotheterminalsmarked[+BAT--]onthePowerSupplyBoard(batteryleadsincluded). Usetwo(2)12VDCbatteriesconnectedinseries.5.Setoutputselectionswitchesmarked[OUT1throughOUT4]tofollowcorrespondinginput[IN1&IN2] anddesiredoutputsignaltype (Output Programming Selection Table, pg. 4).6.ConnectFACPoutputtothedesiredAL842LGKlogicboardinputs,andnotificationappliancestothedesired AL842LGKlogicboardoutputs(see Application Guide).Note:The2-wirehorn/strobesyncmodewillonlysynchronizehorns,horn/strobes,strobeswith synchronizationcapability.7.Forconnectionofsmokedetectors,digitaldialer(Optional Hookup Diagram, pg. 7).

Fig. 1

L Nline

ground

neutral

Page 4: NAC Power Extender Installation Guide · 24VDC/7AH 24 Hours 6.5 amp/5 minutes ---24VDC/12AH (use two (2) 12VDC batteriesin series) 24 Hours 6.5 amp/5 minutes 50mA 24VDC/36AH 24 Hours

- 4 - AL842ULADA

Output Programming Selection Table:Outputs must be programmed independently (OUT1 - OUT4)

Function Switch Positions Descriptions

ON OFF

InputtoOutputFollowerMode

1 2,3 Outputfollowssignalitreceivesfromthecorrespondinginput(i.e.FACPSyncmodule-maintainssynchronizationofnotificationappliancecircuit).

TemporalCode3Mode 3 1,2 EnablesTemporalCode3signalgenerationoutput.Thismodewillacceptasteadyorapulsinginput.

SteadyMode 1,2,3 Asteadyoutputsignalwillbegenerated.Thismodewillacceptsteadyorpulsinginput.

For the above modes Dip Switch 4 determines which Input controls the corresponding output:Switch 4 in the ON position causes output(s) to be controlled by input 1.Switch 4 in the OFF position causes output(s) to be controlled by input 2.

Sync Mode Selection Table:

FunctionSwitch Positions

DescriptionsON OFF

AmsecoSyncMode*

1,3,4

2

ThismodeisdesignedtoworkwiththeAmsecoseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

FaradaySyncMode*

2,4 1,3

ThismodeisdesignedtoworkwiththeFaradayseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchro-nizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

Gentex®SyncMode*GentexisaregisteredtrademarkofGentexCorporation.

1,2,3,4

ThismodeisdesignedtoworkwiththeGentex®seriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchro-nizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

SystemSensor®SyncMode*SystemSensorisaregisteredtrademarkofHoneywell.

1,2,4 3

ThismodeisdesignedtoworkwiththeSystemSensor®seriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

CooperWheelock®

SyncMode*CooperWheelockisaregisteredtrademarkofCooperWheelock.

2,3,4 1

ThismodeisdesignedtoworkwiththeCooperWheelockseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

Note:TheAL842ULADAwillonlysynchronizehorns,horn/strobesandstrobesthatcontainsynchronizationcapability.Contactsignalmanufacturerformoredetailedinfo.Thesamesynchronizationmodemustbeselectedforalloutputs.

Note: It is required to control visual notification appliances (strobes) via input 1 [IN1] and audible notification appliances (horns) via input 2 [IN2]. This allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate.

Amount of Notification Appliances per NAC:Amseco 27perNAC* SystemSensor® 32perNAC*

Faraday 39perNAC* CooperWheelock® 32perNAC*

Gentex® 32perNAC**Not to exceed a maximum of 2.5 amp per NAC.

AL842LGK Board(Output Dip Switches)

INPUT SELECTTEMPORAL

STROBE SYNCIN>OUT SYNC

Page 5: NAC Power Extender Installation Guide · 24VDC/7AH 24 Hours 6.5 amp/5 minutes ---24VDC/12AH (use two (2) 12VDC batteriesin series) 24 Hours 6.5 amp/5 minutes 50mA 24VDC/36AH 24 Hours

AL842ULADA - 5 -

Terminal Identification Table:AL842LGK - Logic Board Terminal Legend Function/Description

IN1+,IN1-IN2+,IN2-(Supervised)

Theseterminalsconnecttothe24VDCFACPnotificationappliancecircuitoutputs.(ClassA,StyleZorClassB,StyleW,Y)Inputtriggervoltageis8-33VDC@5mAmin.Terminalpolar-ityisshowninalarmcondition.Duringanalarmconditiontheseinputswillcausetheselectedoutputschosentodrivenotificationappliances.Thedesignatedoutputsaresetbyoutputswitches[OUT1throughOUT4](Output Programming Selection Table, pg. 4).AtroublconditiononanoutputloopwillcausethecorrespondinginputtotriptheFACPbyopeningtheFACPloop.Analarmconditionwillalwaysoverridetroubletodrivenotificationappliances.

RET1+,RET1-RET2+,RET2-(Supervised)

ForClassA,StyleZhookupstheseterminalpairsreturntoFACPNAC1and/orNAC2.ForClassB,StyleW,YhookupstheFACPEOLresistorfromtheNAC1and/orNAC2outputsareterminatedattheseterminals.Optionally,othernotificationappliancesoradditionalsignalingcircuitpowersuppliesmaybeconnectedtotheseterminals.IfthisoptionischosentheEOLresistormustbeterminatedatthelastdevice.

C“DRY1”NCC“DRY2”NC(Dryinputtrigger)

Anopenacrosstheseinputs,willcausetheselectedoutputschosentodrivenotificationappli-ances.Thedesignatedoutputsaresetbyoutputswitches[OUT1throughOUT4](Output Programming Selection Table, pg. 4).NotetheseinputsareunidirectionalandwillnotreportatroubleconditiontotheFACP.

+OUT1--+OUT2--+OUT3--+OUT4--(Supervised)

Notificationappliancesareconnectedtotheseregulatedoutputs(see Application Guide, pgs. 2-4).Eachpowerlimitedoutputwillsupply2amp.Totalsupplycurrentis8amp(see note below).Outputsarecontrolledbydesignatedinput1[IN1]orinput2[IN2] (Output Programming Selection Table, pg. 4).Maximumlinelossorvoltagedrop(testedwith2.5V).

+Loop1--+Loop2--+Loop3--+Loop4--

UsedforClassA,StyleZhook-upstoterminateloopsoriginatingon[OUT1],[OUT2],[OUT3],and[OUT4]respectively.

C“FAULT”NC(Commontroubleinput)

Anopencircuitacrossthispairofterminalswillcause[INP1andINP2]LEDstosimultaneouslysignalatroubleconditionbacktotheFACP(TypicallyusedtoreportACorBATFail).(Fig. 2e, pg. 7).

NC,C,NO(Commontroubleoutput)

Thesearedrycontacttroubleoutputsthatreportanygeneralloop/systemtroubleconditions.(Typicallyusedtotriggeradigitalcommunicatororotherreportingdevices).(form“C”contact1amp/28VDC0.35PowerFactor)(Fig. 2, pg. 7).

--AUX+Thisseparate1ampmax.auxiliaryspecialapplicationpoweroutputcircuitistypicallyusedtopowerelectromagneticdoorholdersthatkeepfireandsmokedoorsopenundernormalconditions.

--AUX2+

Thisseparateauxiliaryregulatedpoweroutputcircuitsuppliesupto1ampduringstand-byandalarmconditiontoauxiliaryspecialapplicationpoweroutputcircuitistypicallyusedtopower4-wiresmokedetectors.Seeattachedlistofdevices(Appendix A, pgs. 10-12).SincethisoutputisnotdisconnectedfromitsloadduringACpowerfailureusethe(Battery Calculation Worksheet, pg. 9)todeterminebatterysizeand/orallowablestand-byandalarmcurrent.

+DC-- 24VDCfrompowersupply.

Note: Unit is equipped with two (2) 1 amp max. auxiliary outputs: “AUX1” will automatically disconnect when AC is lost. “AUX2” will remain battery backed up during the power outage. For loads connected to “AUX2” please refer to battery “Stand-by Specifications” above for ratings. When loads are connected to the “AUX1” and/or “AUX2” outputs during alarm condition, the remaining outputs may not exceed 8 amp total alarm current. (example: AUX1 = 1 amp, AUX2 = 1 amp, outputs up to 7 amp).

Page 6: NAC Power Extender Installation Guide · 24VDC/7AH 24 Hours 6.5 amp/5 minutes ---24VDC/12AH (use two (2) 12VDC batteriesin series) 24 Hours 6.5 amp/5 minutes 50mA 24VDC/36AH 24 Hours

- 6 - AL842ULADA

Terminal Identification Table:AL800ADA - Power Supply BoardTerminal Legend Function/Description

L,G,N Connect120VACtotheseterminals:Ltohot,Ntoneutral.

-DC+ 24VDC@8ampinalarmnon-powerlimitedoutput.

ACFAILNO,C,NC

Form“C”drycontactsindicatethelossofAC,withACpresentterminalsmarked[NOandC]areopen,[NCandC]areclosed.WhenlossofACoccursterminalsmarked[NOandC]areclosed,[NCandC]areopen.

ACLOCALNC,NO,C

Form“C”drycontactsusedtoinstantaneouslysignalthelossACtolocalannunciationdevices,withACpresentterminalsmarked[NOandC]areopen,[NCandC]areclosed.WhenlossofACoccursterminalsmarked[NOandC]areclosed,[NCandC]areopen.

BATFAILNO,C,NC

Form“C”drycontactsindicatelowbatteryvoltageorlossofbatteryvoltage.Undernormalconditionsterminalsmarked[NOandC]areopen,[NCandC]areclosed.Duringatroubleconditionterminalsmarked[NOandC]areclosed,and[NCandC]areopen(Fig. 2, pg. 7).

+BAT- Stand-bybatteryinput(leadsprovided)(Fig. 2, pg. 7).

*Power Board Parameter Specifications:• ACFailconditionwillreportapproximately30secondsafterlossofAC.Todelayreportfor2.5to3hourscut jumperACDELAYonthePowerSupplyBoard(ACtroubleoutputdelayoption).IfthismodeisselectedthePower SupplyBoardmustberesetbyremovingallpowertoitfor30seconds.• Lowbatteryconditionwillreportatapproximately21VDC.• Batterypresencedetectionwillreportwithin180secondsafterbatteryremainsundetected(missingorremoved). Arestoredbatterywillreportwithin30seconds.

LED Diagnostics:AL800ADA - Power Supply BoardRed (DC) Green (AC) Power Supply Status

ON ON Normaloperatingcondition.

ON OFF LossofAC,Stand-bybatterysupplyingpower.

OFF ON NoDCoutput.

OFF OFF LossofAC.Dischargedornostand-bybattery.NoDCoutput.

AL842LGK - Logic Board

LED OFF ON BLINK (LONG)* BLINK (SHORT)**

ON Normal AlarmCondition TroubleCondition TroubleConditionMemory

ON Normal AlarmCondition TroubleCondition TroubleConditionMemory

OFF Normal AlarmCondition TroubleCondition TroubleConditionMemory

OFF Normal AlarmCondition TroubleCondition TroubleConditionMemory

Input1 Normal AlarmCondition TroubleCondition ---

Input2 Normal AlarmCondition TroubleCondition ---

Fault Normal AlarmCondition --- ---

* Indicatesexistingtroublecondition.Whenatroublecondition(open,shortorground)occursonaspecificoutput,the correspondingredoutputLED,[OUT1-OUT4]willblink.ThecorrespondinggreeninputLEDwillblinkaswell.

**Indicatestroubleconditionmemory.Whenatroubleconditionrestores,theunitsredoutputLEDs[OUT1-OUT4] willblinkwithashorteranddistinctlydifferentduration.ThegreeninputLEDswillbeoff(normalcondition). ToresetthememorydepresstheresetbuttonlocatedontheAL842LGKlogicboard(Fig. 2c, pg. 7). TheLED(s)willextinguish.

Note: Whenindicatingcircuitshaverestored,troublememoryresetisnotrequiredfornormaloperation.

Page 7: NAC Power Extender Installation Guide · 24VDC/7AH 24 Hours 6.5 amp/5 minutes ---24VDC/12AH (use two (2) 12VDC batteriesin series) 24 Hours 6.5 amp/5 minutes 50mA 24VDC/36AH 24 Hours

AL842ULADA - 7 -

Fig. 2

Optional Hookup Diagram:

Fig. 2b

Fig. 2a

NC NO C

NC C NO NC

C NO

AC Local

AC DELAY

BAT FAILAC FAIL

AC LED

VR1

OUT1 OUT2 OUT3 OUT4

INP2 INP1 FAULT

RESET

OUT1 OUT3

OUT2 OUT4IN>OUT SYNCSTROBE SYNC

TEMPORALINPUT SELECT

IN>OUT SYNCSTROBE SYNC

TEMPORALINPUT SELECT

NC

C N

O C

"FA

ULT

" NC

+ DC ---

-- AUX2 + -- LOOP4 + -- OUT4 +-- OUT3 +

-- LOOP3 + -- LOOP1 + -- OUT1 + -- OUT2 +

-- LOOP2 +-- IN1 +

-- RET1 +-- IN2 +

-- RET2 + NC "DRY1" C

NC "DRY2" C-- AUX1 +

Green Lead

Addressablecontrolmoduletriggeroutput

(See Typical Application Diagram for device hookup)

Power-Limited Outputs 2.5 amp per output max. (total = 8 amp)

(Supervised)

+ --4-wire Smoke

Detector

+ --4-wire Smoke

Detector

FireAlarmControlPanel(FACP)

EOL PowerSupervision Relay

(Not Supplied)

EOL Resistorfrom FACP

Digi

tal C

omm

unic

ator

or

Loca

l Ann

unci

ator

Dry

ou

tput

Con

tact

(For

m "

C" c

onta

cts)

These circuits are used to monitor AC and Bat Fail

and will cause a simultaneous

trouble condition to the FACP's IN1 and IN2

(Non-Supervised)

Factory InstalledBoard Interface

Cable

AC

MagneticDoor Holder

lineground

neutral

unswitched 120VACpower mains

(non-power limited)

SupervisedNon-Supervised Non-Supervised

Non-

Supe

rvis

ed

NC NO C

NC C NO NC

C NO

AC Local

AC DELAY

BAT FAILAC FAIL

AC LED

VR1

OUT1 OUT2 OUT3 OUT4

INP2 INP1 FAULT

RESET

OUT1 OUT3

OUT2 OUT4IN>OUT SYNCSTROBE SYNC

TEMPORALINPUT SELECT

IN>OUT SYNCSTROBE SYNC

TEMPORALINPUT SELECT

NC

C N

O C

"FA

ULT

" NC

+ DC ---

-- AUX2 + -- LOOP4 + -- OUT4 +-- OUT3 +

-- LOOP3 + -- LOOP1 + -- OUT1 + -- OUT2 +

-- LOOP2 +-- IN1 +

-- RET1 +-- IN2 +

-- RET2 + NC "DRY1" C

NC "DRY2" C-- AUX1 +

Green Lead

Addressablecontrolmoduletriggeroutput

(See Typical Application Diagram for device hookup)

Power-Limited Outputs 2.5 amp per output max. (total = 8 amp)

(Supervised)

+ --4-wire Smoke

Detector

+ --4-wire Smoke

Detector

FireAlarmControlPanel(FACP)

EOL PowerSupervision Relay

(Not Supplied)

EOL Resistorfrom FACP

Digi

tal C

omm

unic

ator

or

Loca

l Ann

unci

ator

Dry

ou

tput

Con

tact

(For

m "

C" c

onta

cts)

These circuits are used to monitor AC and Bat Fail

and will cause a simultaneous

trouble condition to the FACP's IN1 and IN2

(Non-Supervised)

Factory InstalledBoard Interface

Cable

AC

MagneticDoor Holder

lineground

neutral

unswitched 120VACpower mains

(non-power limited)

SupervisedNon-Supervised Non-Supervised

Non-

Supe

rvis

ed

NC

C

N

O

C "

FAU

LT"

NC

Fig. 2c

TroubleMemoryResetButton

+ D

C ---

BA

T FA

ILN

O C

NC

NO

C N

C

+ B

AT

---

L G

N

DC

AC

FAIL

AC

15A

32V

10A

250V

OUT1 OUT2 OUT3 OUT4

INP2 INP1 FAULT

RESET

OUT1 OUT3

OUT2 OUT4IN>OUT SYNCSTROBE SYNC

TEMPORALINPUT SELECT

IN>OUT SYNCSTROBE SYNC

TEMPORALINPUT SELECT

NC

C N

O C

"FA

ULT

" NC

+ DC ---

-- AUX2 + -- LOOP4 + -- OUT4 +-- OUT3 +

-- LOOP3 + -- LOOP1 + -- OUT1 + -- OUT2 +

-- LOOP2 +-- IN1 +

-- RET1 +-- IN2 +

-- RET2 + NC "DRY1" C

NC "DRY2" C-- AUX1 +

Green Lead

Addressablecontrolmoduletriggeroutput

(See Typical Application Diagram for device hookup)

Power-Limited Outputs 2.5 amp per output max. (total = 10 amp)

+ --4-wire Smoke

Detector

+ --4-wire Smoke

Detector

FireAlarmControlPanel(FACP)

EOL PowerSupervision Relay

(Not Supplied)

EOL Resistorfrom FACP

Digi

tal C

omm

unic

ator

or

Loca

l Ann

unci

ator

Dry

ou

tput

Con

tact

(For

m "

C" c

onta

cts)

These circuits are used to monitorAC and Bat Fail and will cause asimultaneous trouble conditionto the FACP's IN1 and IN2(Non-Supervised)

Factory InstalledBoard Interface

Cable

ACFuseCover

unswitched 115VAC 50/60Hz, 4.4 amp

power mains(non power-limited)

MagneticDoor Holder

Page 8: NAC Power Extender Installation Guide · 24VDC/7AH 24 Hours 6.5 amp/5 minutes ---24VDC/12AH (use two (2) 12VDC batteriesin series) 24 Hours 6.5 amp/5 minutes 50mA 24VDC/36AH 24 Hours

- 8 - AL842ULADA

Optional hookups:1- BatteryandACmonitoring:ACorBatteryFailconditionwillcausethecommontroubleinput[C“FAULT”NC]to reportbacktotheFACPviainput1andinput2.Thecommontroubleinputmayalsobeusedforotheroptional supervisorymonitoring.

ToreportACandBatteryTroubleconnectthebatteryandACFailrelayoutputshownin(Fig. 2a)tothe commontroubleinput.

2- Drycontactinput(C“DRY1”NC)(C“DRY2”NC)canbeusedtoalarmoutputfroman addressablemodule(theseinputsareunidirectionandcannotreportbacktotriggermodule).

Connection to triggering devices must be made within 20ft of distance and using conduit for wiring.

3- Auxiliaryoutput(-AUX+)24VDCat1ampmax.

4- ACLocal[NC,C,NO]shouldconnecttothehostcontrolpanelforlocalannunciationof thetroublecondition.

Note: Ifcommontroubleinput,terminalsmarked[C“FAULT”NC]arenotused,theseterminalsmustbe shorted(connectjumper)toremaininactive.Foroptionalhookups(Fig. 2b).

Maintenance:Unitshouldbetestedatleastonceayearfortheproperoperationasfollows:

Output Voltage Test:Undernormalloadconditions,theDCoutputvoltageshouldbecheckedforpropervoltagelevel(26.2-26.4VDC recommended range).Battery Test:Undernormalloadconditionscheckthatthebatteryisfullycharged.Checkspecifiedvoltagebothatthebatteryterminalandattheboardterminalsmarked[+BAT--]toensurethatthereisnobreakinthebatteryconnectionwires.Fuses:Checkinputandoutputfusesonthepowersupplyboard,replaceifnecessary.Inputfuseratingis10amp@250V,[email protected]:Maximumchargingcurrentis3.2amp.Note:Expectedbatterylifeis5years;however,itisrecommendedchangingbatteriesin4yearsorlessifneeded.

Page 9: NAC Power Extender Installation Guide · 24VDC/7AH 24 Hours 6.5 amp/5 minutes ---24VDC/12AH (use two (2) 12VDC batteriesin series) 24 Hours 6.5 amp/5 minutes 50mA 24VDC/36AH 24 Hours

AL842ULADA - 9 -

Battery Calculation Worksheet

Unitsarecapableofrecharging40AHbatterymax.Iftotalampere-hourrequiredexceeds40AH,decreaseAUXcurrenttoprovideenoughstand-bytimefortheapplication.

DeviceNumber of Devices

Current per DeviceStand-by Current

Alarm Current

Foreachdeviceusethisformula: Thiscolumn x Thiscolumn = Equals Currentpernumberofdevices.

AL842ULADA(Currentdrawfrombattery)

1Stand-by: 90mA 90mA

Alarm: 175mA 175mA

A AL842 Current 90mA 175mA

AuxiliaryDevices Refertodevicemanualforcurrentratings.

Alarm/Stand-by mA mA mA

Alarm/Stand-bymA

mA mA

Alarm/Stand-by mA mA mA

B Auxiliary Devices Current (must not exceed 1 amp)

Refertodevicemanualforcurrentratings.

Alarm: mA 0mA mA

Alarm:mA

0mA mA

Alarm: mA 0mA mAAlarm:

mA 0mA mA

C NotificationAppliancesCurrent must notexceed8amp(8000mA) 0mA mA

D Totalalarmcurrent mA mA

E Totalcurrentratingsconvertedtoamperes(lineDx.001) A A

F Numberofstandbyhours(24forNFPA72,Chapter1,1-5.2.5). H

G MultiplylinesEandF. Totalstand-byAH AH

HAlarmsoundingperiodinhours.(Forexample,5minutes=.0833hours.)

H

I MultiplylinesEandH. TotalalarmAH AH

J AddlinesGandI. Totalstand-byandalarmAH AH

KMultiplylineJby1.30.(30%extrainsurancetomeetdesiredperformance)Totalampere-hoursrequired

AH

Page 10: NAC Power Extender Installation Guide · 24VDC/7AH 24 Hours 6.5 amp/5 minutes ---24VDC/12AH (use two (2) 12VDC batteriesin series) 24 Hours 6.5 amp/5 minutes 50mA 24VDC/36AH 24 Hours

- 10 - AL842ULADA

Appendix A - UL Listed Compatible Devices

A.1 Four (4) Wire Smoke Detectors

TableA-1belowlistsfour(4)wiresmokedetectorscompatiblewithAL842ULADAAUXoutput.

Smoke Detector/Base Detector TypeMax StandbyCurrent (mA)

AlarmCurrent (mA)

SystemSensorB112LP Base 0.12 36

SystemSensorB114LP Base * *

SystemSensorB404B Base * *

SystemSensorDH100ACDC Photoelectric 0.15 0.70

SystemSensorDH100ACDCLP Photoelectric 0.15 0.70

SystemSensorDH100ACDCLPW Photoelectric 0.15 0.70

SystemSensorDH400ACDCI IonizationDuct 25 95

SystemSensorDH400ACDCP PhotoelectricDuct 25 95

SystemSensor1112/24/D Ionization 0.05 50

SystemSensor1424 Ionization 0.10 41

SystemSensor1451(w/B402BBase) Ionization 0.10 39

SystemSensor2112/24ATR Photoelectric 0.50 60/70

SystemSensor2112/24AITR Photoelectric 0.50 60/70

SystemSensor2112/24/D Photoelectric 0.05 50

SystemSensor2112/24R Photoelectric 0.50 60/70

SystemSensor2112/24TR Photoelectric 0.50 60/70

SystemSensor2112/24T/D Photoelectricw/135oThermal 0.05 50

SystemSensor2112/24TSRBPhotoelectricw/135o

ThermalSupervisoryRelay15 45

SystemSensor2312/24TB Photoelectric 0.12 50

SystemSensor2412(12volt) Photoelectric 0.12 77

SystemSensor2412AT(12volt) Photoelectric 0.12 58

SystemSensor2412TH(12volt) Photoelectric 0.12 77

SystemSensor2424 Photoelectric 0.10 41

SystemSensor2424TH Photoelectric 0.10 41

SystemSensor2451 Photoelectric 0.10 39

SystemSensor2451TH(with/B402BBase) Photoelectric 0.10 39

SystemSensor2W-MOD LoopTest/MaintenceMod. 30 50

Page 11: NAC Power Extender Installation Guide · 24VDC/7AH 24 Hours 6.5 amp/5 minutes ---24VDC/12AH (use two (2) 12VDC batteriesin series) 24 Hours 6.5 amp/5 minutes 50mA 24VDC/36AH 24 Hours

AL842ULADA - 11 -

A.1 Four (4) Wire Smoke Detectors (cont.)

Smoke Detector/Base Detector TypeMax StandbyCurrent (mA)

AlarmCurrent (mA)

SystemSensor4W-B(12/24volt) PhotoelectricI3 .05 23

SystemSensor4WT-B(12/24volt) PhotoelectricI3w/Therm .05 23

SystemSensor4WTA-B(12/24volt) I3Photow/Therm/Sounder .05 35

SystemSensor4WTR-B(12/24volt) I3Photow/Therm/Relay .05 35

SystemSensor4WTR-B(12/24volt)I3Photow/Therm/Sounder/Relay

.05 50

SystemSensor4WITAR-B(12/24volt)I3Photow/IsolatedTherm/

Sounder/Relay.05 50

SystemSensor2W-MOD2I3LoopTest/Maintence

Mod..05 *

SystemSensorRRS-MODI3ReversingRelay/Sync

Module.05 *

SystemSensor6424 ProjectedBeam 10 28.4

SystemSensorBeam1224(S) ProjectedBeam 17 38.5

*Contactmanufacturerforcurrentdraws

A.2 Relays

TableA-3belowlistsrelayscompatiblewithAL842ULADAAUXoutput.

Manufacturer Model Current (mA)

SystemSensor

PR-1 PR-2 PR-3 EOLR-1 R-10T R-14T R-20T R-24T R-10E R-14E R-20ER-24E

15 30 30 30 23 23 40 40 23 23 40 40

Page 12: NAC Power Extender Installation Guide · 24VDC/7AH 24 Hours 6.5 amp/5 minutes ---24VDC/12AH (use two (2) 12VDC batteriesin series) 24 Hours 6.5 amp/5 minutes 50mA 24VDC/36AH 24 Hours

Altronixisnotresponsibleforanytypographicalerrors.

14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056website:www.altronix.com,e-mail:[email protected],LifetimeWarranty,MadeinU.S.A.IIAL842ULADA I04M

- 12 - AL842ULADAMEMBER

1.5”(38.1mm)

1.0”(25.4mm)

4.5”(114.3mm)

1.0”(25.4mm)

1.0”(25.4mm)

1.25”(31.75mm)

1.25”(31.75mm)

1.0”(25.4mm)

1.5”(38.1mm)

1.5”(38.1mm)

1.5”(38.1mm)

1.5”(38.1mm)

8.5”(215.9mm)

18.0”(457.2mm)

18.0”(457.2mm)

18.0”(457.2mm)

6.0”(152.4mm)

2.5”(63.5mm)

2.75”(69.85mm)

2.75”(69.85mm)

4.5”(114.3mm)

4.5”(114.3mm)

14.5”(368.3mm)

14.5”(368.3mm)

1.0”(25.4mm)

1.0”(25.4mm)

14.5”(368.3mm)

2.5”(63.5mm)

1.5”(38.1mm)

2.5”(63.5mm)

Enclosure Dimensions (H x W x D approximate):18”x14.5”x4.625”(457.2mmx368.3mmx117.48mm)