Rev. 042010 AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information)

NAC Power Extender Installation Guide · 2020-02-13 · AL802ULADA - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NAC Power Extender Installation Guide · 2020-02-13 · AL802ULADA - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit

Rev. 042010

AL802ULADANAC Power Extender

Installation Guide(See Application Guide for additional information)

Page 2: NAC Power Extender Installation Guide · 2020-02-13 · AL802ULADA - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit

- 2 - AL802ULADA

Agency Listings:• ULListedControlUnitsforFireProtective SignalingSystems(UL864).• MEA-NYCDepartmentofBuildingsApproved.• CSFM-CaliforniaStateFireMarshalApproved.• FM-FactoryMutualApproved.• NFPA72Compliant.Input:• Powerinput120VAC60Hz,5amp.• Two(2)ClassA,StyleZortwo(2)ClassB, StyleW,X,YFACPinputs.• Two(2)NCdrycontacttriggerinputs.Output:• Class2Ratedpowerlimitedoutputs.• 24VDC@8ampmaxtotalalarmcurrent.• 2.5ampmaxcurrentperoutput.• Separate1.0ampauxiliaryoutput.• Two(2)outputsmaybeparalleledformorepoweronan indicatingcircuit(see Application Guide).• Programmablesupervisedindicatingcircuitoutputs: Four(4)ClassB,StyleW,X,YorTwo(2)ClassA, StyleZorOne(1)ClassA,StyleZandTwo(2) ClassB,StyleW,X,Y(see Application Guide).•Thermalandshortcircuitprotectionwithautoreset.Battery Backup:•Built-inchargerforsealedleadacidorgeltypebatteries.•Automaticswitchovertostand-bybatterywhen ACFails.• Zerovoltagedropwhenswitchingoverto batterybackup.

Supervision:•ACfailsupervision(form“C”contact,1amp/28VDC). Factorysetfor30secondswithoptional2.5to3hour delaysetting(fieldselectable).• InstantlocalACtroublereportingrelay (form“C”contact,1amp/28VDC).•Batterypresenceandlowbatterysupervision (form“C”contact,1amp/28VDC).Visual Indicators:•InputandoutputstatusLEDindicators.Special Features:• 2-wirehorn/strobeSyncmodeallowsaudible notificationappliances(horns)tobesilenced whilevisualnotificationappliances(strobes) continuetooperate.• TemporalCode3,SteadyMode,InputtoOutput FollowerMode(maintainssynchronizationof notificationappliancescircuit).• Compatiblewith12VDCor24VDCfirepanels.•Outputloopsupervisionsteeredtoinput1orinput2.• Signalcircuittroublememory(helpsidentify intermittentloopproblems).• Commontroubleinputandoutput.• Groundfaultdetection.Added Features:•Unitincludespowersupply,redenclosure,camlock, andbatteryleads.Enclosure Dimensions and Descriptions:AL802ULADA15.5”Hx12.23”Wx4.5”DProduct Weight:17lbs.

Overview:TheAltronixAL802ULADAisanextremelycosteffective8ampremotepowersupply/batterycharger.Itmaybecon-nectedtoany12or24voltFireAlarmControlPanel(FACP).PrimaryapplicationsincludeNotificationApplianceCircuit(NACsuchasstrobesandhorns)expansionsupporttomeetADArequirements.Italsoprovidesauxiliarypowertosupportsystemaccessories.Theunitdeliverselectronicallyregulatedandfiltered24voltpowertoClassB,StyleW,X,YorClassA,StyleZNACloopcircuits.Additionally,aseparate1.0Aauxiliaryoutputforfour(4)-wiresmokedetectorsisavail-able.The8ampmax.alarmcurrentcanbedividedbetweenthefour(4)outputsforpoweringNACdevices.Eachoutputisratedat2.5ampmax.,andcanbeindependentlyprogrammedforSteady,TemporalCode3orStrobeSynchronization.AlloutputsmaybeprogrammedforInputtoOutputFollowerMode(outputwillfollowinput).Anindividualoutputof4ampisachievedbyparalleling2outputs.Innon-alarmconditionindependentloopsupervisionforClassA,StyleZand/orClassB,StyleW,X,YFACPNACcircuitsisprovided.Intheeventofalooptrouble,theFACPwillbenotifiedviathesteeredinput(input1orinput2).Inaddition,therearecommontroubleoutputterminals(NC,C,NO)whichareusedtoindicategeneralloop/systemtrouble.AcommontroubleinputisprovidedforoptionalNC(normallyclosed)devicestoreporttroubletotheFACP.Two(2)FACPsignalingoutputscanbeemployedanddirectedtocontrolsupervisionandpowerdeliverytoanycombinationofthefour(4)outputs.

Specifications:

AL802ULADA - NAC Power Extender

Page 3: NAC Power Extender Installation Guide · 2020-02-13 · AL802ULADA - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit

AL802ULADA - 3 -

Power Supply Specifications:AC Input: 120VAC60Hz,5amp,suppliedbyamaximum15ampdedicatedbranchcircuit.

Output: Four(4)regulatedsupervisedNACoutputcircuits,24VDC,2.5ampmaximumcurrent.One(1)aux.specialapplication24VDCpoweroutputcircuit1amp,non-supervisedtotaloutputcurrentmustnotexceedcurrent8ampinAlarmCondition.

Battery: Usetwo(2)12VDC/12AHortwo(2)12VDC/7AHbatteriesconnectedinseries.

Stand-by/Alarm Current Consumption:

90mA/175mA

EOL Resistor (end of line):

2.2K(2200ohm),AltronixModel#AL-EOL22(included).

Ground fault maximumtest impedance:

1000ohm.

Stand-by Specifications:Stand-by Batteries Stand-by Time Total Amp/Minutes Alarm Output Current Aux. Output

24VDC/7AH 24Hours 8amp/5minutes ---

24VDC/12AH(usetwo(2)12VDCbatteriesinseries)

24Hours 8amp/5minutes 50mA

24VDC/36AH 24Hours 8amp/5minutes 1amp

Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power outage. For loads connected to “AUX” please, refer to battery “Stand-by Specifications” above for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may, not exceed 8 amp total alarm current (example: AUX = 1 amp, outputs up to 7 amp).

Installation Instructions:WiringmethodsshallbeinaccordancewiththeNationalElectricalCode/NFPA70/NFPA72/ANSI,andwithalllocalcodesandauthoritieshavingjurisdiction.Productisintendedforindooruseonly. Carefully review: Application Guide for AL602ULADA, AL802ULADA, AL1002ULADA Power Supply Specifications (pg. 3) Stand-by Specifications (pg. 3) Output Programming Selection Table (pg. 4) Sync Mode Selection Table (pg. 4) Terminal Identification Table (pgs. 5-6) LED Status Indication Table (pg. 6)1.Mounttheunitindesiredlocation.Markandpredrillholesinthewalltolineupwiththetoptwokeyholesinthe enclosure.Installtwoupperfastenersandscrewsinthewallwiththescrewheadsprotruding.Placetheenclosure’s upperkeyholesoverthetwoupperscrews,levelandsecure. Markthepositionofthelowertwoholes.Removetheenclosure.Drillthelowerholesandinstallthetwofasteners. Placetheenclosure’supperkeyholesoverthetwoupperscrews.Installthetwolowerscrewsandmakesuretotighten allscrews(Enclosure Dimensions, pg. 12).Secureenclosuretoearthground(Fig. 1, pg. 3).2.Connecttheline(L),ground(G),andneutral(N),terminalstoaseparateunswitchedACcircuit(120VAC,60Hz) dedicatedtotheFireAlarmSystem.3.Measureoutputvoltagebeforeconnectingdevices.Thishelpsavoidpotentialdamage.4.Connectbatterytoterminalsmarked[+BAT--]onthePowerSupplyBoard(batteryleadsincluded). Usetwo(2)12VDCbatteriesconnectedinseries.5.Setoutputselectionswitchesmarked[OUT1throughOUT4]tofollowcorrespondinginput[IN1&IN2]and desiredoutputsignaltype (Output Programming Selection Table, pg. 4).6.ConnectFACPoutputtodesiredAL800LGK9Elogicboardinputs,andnotificationappliancestodesired AL800LGK9Elogicboardoutputs(see Application Guide). Note:The2-wirehorn/strobesyncmodewillonlysynchronizehorns,horn/strobes,strobeswith synchronizationcapability.

L G Nline

groundneutral

Fig. 1

Page 4: NAC Power Extender Installation Guide · 2020-02-13 · AL802ULADA - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit

- 4 - AL802ULADA

7.Forconnectionofsmokedetectors,digitaldialer(Optional Hookup Diagram, pg. 7).

Class A, Style Z Class B, Style W, X, Y, SW1 & SW2 Settings:• ForallClassB,StyleW,X,Y,hookupsSW1&SW2ontheAL800LGKlogicboardmustbeopen. ForallClassA,StyleZhookupsSW1&SW2ontheAL800LGKlogicboardmustbeclosed.

Output Programming Selection Table: Outputs must be programmed independently (OUT1 - OUT4)

Function Switch Positions Descriptions

ON OFF

InputtoOutputFollowerMode

1 2,3 Outputfollowssignalitreceivesfromthecorrespondinginput(i.e.FACPSyncmodule-maintainssynchronizationofnotificationappliancecircuit).

TemporalCode3Mode 3 1,2 EnablesTemporalCode3signalgenerationoutput.Thismodewillacceptasteadyorapulsinginput.

SteadyMode 1,2,3 Asteadyoutputsignalwillbegenerated.Thismodewillacceptsteadyorpulsinginput.

For the above modes Dip Switch 4 determines which Input controls the corresponding output:Switch 4 in the ON position causes output(s) to be controlled by input 1.Switch 4 in the OFF position causes output(s) to be controlled by input 2.

Sync Mode Selection Table:

FunctionSwitch Positions

DescriptionsON OFF

AmsecoSyncMode*

1,3,4

2

ThismodeisdesignedtoworkwiththeAmsecoseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

FaradaySyncMode* 2,4 1,3

ThismodeisdesignedtoworkwiththeFaradayseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchro-nizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

Gentex®

SyncMode*GentexisaregisteredtrademarkofGentexCorporation.

1,2,3,4

ThismodeisdesignedtoworkwiththeGentex®seriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchro-nizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

SystemSensor®SyncMode*SystemSensorisaregisteredtrademarkofHoneywell.

1,2,4 3

ThismodeisdesignedtoworkwiththeSystemSensor®seriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

CooperWheelock®

SyncMode*CooperWheelockisaregisteredtrademarkofCooperWheelock.

2,3,4 1

ThismodeisdesignedtoworkwiththeCooperWheelockseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.

*Note:TheAL802ULADAwillonlysynchronizehorns,horn/strobesandstrobesthatcontainsynchronizationcapability.Contactsignalmanufacturerformoredetailedinfo.Thesamesynchronizationmodemustbeselectedforalloutputs

Note: It is required to control visual notification appliances (strobes) via input 1 (IN1) and audible notification appliances (horns) via input 2 (IN2). This allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate.

(AL800LGK Board)Output Dip Switches

INPUT SELECTTEMPORAL

STROBE SYNCIN>OUT SYNC

Page 5: NAC Power Extender Installation Guide · 2020-02-13 · AL802ULADA - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit

AL802ULADA - 5 -

Amount of Notification Appliances per NAC:Amseco 27perNAC* SystemSensor® 32perNAC*

Faraday 39perNAC* CooperWheelock® 32perNAC*

Gentex® 32perNAC*

*Not to exceed a maximum of 2.5 amp per NAC.

Terminal Identification Table:AL800LGK9E - Logic BoardTerminalLegend Function/Description

IN1+,IN1-IN2+,IN2-(Supervised)

Theseterminalsconnecttothe12VDCor24VDCFACPnotificationappliancecircuitoutputs.(ClassA,StyleZorClassB,StyleW,X,Y)Inputtriggervoltageis8-33VDC@5mAmin.Terminalpolarityisshowninalarmcondition.Duringanalarmconditiontheseinputswillcausetheselectedoutputschosentodrivenotificationappliances.Thedesignatedoutputsaresetbyoutputswitches[OUT1throughOUT4](Output Programming Selection Table, pg. 4). AtroubleconditiononanoutputloopwillcausethecorrespondinginputtotriptheFACPbyopeningtheFACPloop.Analarmconditionwillalwaysoverridetroubletodrivenotificationappliances.

RET1+,RET1-RET2+,RET2-(Supervised)

For(ClassA,StyleZhookupstheseterminalpairsreturntoFACPNAC1and/orNAC2.ForClassB,StyleW,X,YhookupstheFACPEOLresistorfromtheNAC1and/orNAC2outputsareterminatedattheseterminals.

C“DRY1”NCC“DRY2”NC(Dryinputtrigger)

Anopenacrosstheseinputs,willcausetheselectedoutputschosentodrivenotificationappli-ances.Thedesignatedoutputsaresetbyoutputswitches[OUT1throughOUT4](Output Programming Selection Table, pg. 4).NotetheseinputsareunidirectionalandwillnotreportatroubleconditiontotheFACP.

+OUT1--+OUT2--+OUT3--+OUT4--(Supervised)

Notificationappliancesareconnectedtotheseregulatedoutputs (see Application Guide pg. 2-4). Eachpower-limitedoutputwillsupply2.5amp.Two(2)outputsmaybeconnectedinparallelforamaximumNACoutputcapabilityof4amp.Totalsupplycurrentis8amp(see note below).Outputsarecontrolledbydesignatedinput1[IN1]orinput2[IN2](Output Programming Selection Table, pg. 4). Maximumlinelossorvoltagedrop(testedwith2.5V).

C“FAULT”NC(Commontroubleinput)

Anopencircuitacrossthispairofterminalswillcause[IN1andIN2]tosimultaneouslysignalatroubleconditionbacktotheFACP(TypicallyusedtoreportACorBATFail).(form“C”contact1amp/28VDC)(Fig. 2, pg. 7).

NC,C,NO(Commontroubleoutput)

Thesearedrycontacttroubleoutputsthatfollowanygeneralloop/systemtroubleconditions.(Typicallyusedtotriggeradigitalcommunicatororotherreportingdevice).(form“C”contact1amp/28VDC0.35PowerFactor)(Fig. 2, pg. 7) .

--AUX+Thisseparate1ampmaxauxiliarySpecialApplicationPoweroutputcircuitistypicallyusedto power4-wiresmokedetectors.Seeattachedlistofdevices(Appendix A, pgs. 10-12).

+DC-- 24VDCfrompowersupply.

Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power outage. For loads connected to “AUX” please, refer to battery “Stand-by Specifications” above for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may, not exceed 8 amp total alarm current (example: AUX = 1 amp, outputs up to 7 amp).

Page 6: NAC Power Extender Installation Guide · 2020-02-13 · AL802ULADA - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit

- 6 - AL802ULADA

Terminal Identification Table:AL800ADA Power Supply Board*Terminal Legend Function/Description

L,G,N Connect120VACtotheseterminals:Ltohot,Ntoneutral,Gtoground.

-DC+ 24VDC@8ampinalarmnon-powerlimitedoutput.

ACFAILNO,C,NC

Form“C”drycontactsusedtoinstantaneouslysignalthelossACtolocalannunciationdevices,withACpresentterminalsmarkedNOandCareopen,NCandCareclosed.WhenlossofACoccursterminalsmarkedNOandCareclosed,NCandCareopen.

ACLOCALNC,NO,C

Form“C”drycontactsusedtoinstantaneouslysignalthelossACtolocalannunciationdevices,withACpresentterminalsmarkedNOandCareopen,NCandCareclosed.WhenlossofACoccursterminalsmarkedNOandCareclosed,NCandCareopen.

BATFAILNO,C,NC

Form“C”drycontactsusedtosignallowbatteryvoltageorlossofbatteryvoltage.UndernormalconditionsterminalsmarkedNOandCareopen,NCandCareclosed.DuringatroubleconditionterminalsmarkedNOandCareclosed,andNCandCareopen(Fig. 2, pg. 7).

+BAT- Stand-bybatteryinput(leadsprovided)(Fig. 2, pg. 7).

*Power Board Parameter Specifications:• ACFailconditionwillreportapproximately30secondsafterlossofAC.Todelayreportfor2.5to3hourscut jumperACDELAYonthePowerSupplyBoard(ACtroubleoutputdelayoption).IfthismodeisselectedthePower SupplyBoardmustberesetbyremovingallpowertoitfor30seconds.• Lowbatteryconditionwillreportatapproximately21VDC.• Batterypresencedetectionwillreportwithin180secondsafterbatteryremainsundetected(missingorremoved). Arestoredbatterywillreportwithin30seconds.

LED Diagnostics:AL800ADA - Power Supply BoardRed (DC) Green (AC) Power Supply Status

ON ON Normaloperatingcondition.

ON OFF LossofAC,Stand-bybatterysupplyingpower.

OFF ON NoDCoutput.

OFF OFF LossofAC.Dischargedornostand-bybattery.NoDCoutput.

AL800LGK9E - Logic BoardLED OFF ON BLINK (LONG)* BLINK (SHORT)**

ON Normal AlarmCondition TroubleCondition TroubleConditionMemory

ON Normal AlarmCondition TroubleCondition TroubleConditionMemory

OFF Normal AlarmCondition TroubleCondition TroubleConditionMemory

OFF Normal AlarmCondition TroubleCondition TroubleConditionMemory

Input1 Normal AlarmCondition TroubleCondition ---

Input2 Normal AlarmCondition TroubleCondition ---

Fault Normal AlarmCondition --- ---

* Indicatescurrenttroublecondition.Whentrouble(open,shortorground)occursonaspecificoutput,the correspondingredoutputLED,[OUT1-OUT4]willblink.ThecorrespondinggreeninputLEDwill blinkaswell.Looptroublewillreportwithin30seconds.

**Indicatestroubleconditionmemory.Whenatroubleconditionrestores,theunitsredoutputLED,[OUT1-OUT4] willblinkwithashorteranddistinctlyadifferentduration.ThegreeninputLEDswillbeoff(normalcondition). Toresetthememorydepresstheresetbutton(Fig. 2c, pg. 7).TheLED(s)willextinguish.

Note:Ifindicatingcircuitshavebeenrestored,memoryresetisnotrequiredfornormaloperationoftheunit.

Page 7: NAC Power Extender Installation Guide · 2020-02-13 · AL802ULADA - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit

AL802ULADA - 7 -

These circuits are used tomonitor AC and Bat Fail andwill cause a simultaneous trouble condition to the FACP's IN1 and IN2

Digital Communicator orLocal Annunciator Dry output Contact(Form "C" contacts)

4-wire SmokeDetector

+

--

+

--

4-wire SmokeDetector

FireAlarmControlPanel(FACP)

EOL PowerSupervision Relay

(Not Supplied)

EOLResistor

fromFACP

SW1

-- DC +

SW2

+ OUT1 --

OUT1 OUT2 OUT3 OUT4

INP1 INP2

FAULT

NCC

NOC

"FA

ULT"

NC

OUT1 OUT3

OUT2 OUT4INPUT SELECT

TEMPORALSTROBE SYNC

IN > OUT SYNC

IN1+ IN1-- IN2--IN2+ C "DRY1" NCRET1+ RET1-- RET2--RET2+ C "DRY2" NC

+ OUT2 -- + OUT3 -- + OUT4 --

INPUT SELECTTEMPORAL

STROBE SYNCIN > OUT SYNC

-- AUX +

UPPER TERMINALSLOWER TERMINALS

AddressableControl ModuleTrigger OutputSee Note 2

lineground

neutralGreenLead

Use separate knockout. Keep 1/4" spacing from non power limited wiring

Power-LimitedOutputs2.5ampperoutputinalarm(total=8amp)(Supervised)

Supervised Non-Supervised

Non-Supervised

Non-Supervised

RESET

unswitched 120VACpower mains

(non-power limited) NC C NO NC C NO NC C NO

AC Local AC D

ELAY

BAT FAIL AC FAIL

AC LED

VR1

Fig. 2

These circuits are used tomonitor AC and Bat Fail andwill cause a simultaneous trouble condition to the FACP's IN1 and IN2

Digital Communicator orLocal Annunciator Dry output Contact(Form "C" contacts)

4-wire SmokeDetector

+

--

+

--

4-wire SmokeDetector

FireAlarmControlPanel(FACP)

EOL PowerSupervision Relay

(Not Supplied)

EOLResistor

fromFACP

SW1

-- DC +

SW2

+ OUT1 --

OUT1 OUT2 OUT3 OUT4

INP1 INP2

FAULT

NCC

NOC

"FA

ULT"

NC

OUT1 OUT3

OUT2 OUT4INPUT SELECT

TEMPORALSTROBE SYNC

IN > OUT SYNC

IN1+ IN1-- IN2--IN2+ C "DRY1" NCRET1+ RET1-- RET2--RET2+ C "DRY2" NC

+ OUT2 -- + OUT3 -- + OUT4 --

INPUT SELECTTEMPORAL

STROBE SYNCIN > OUT SYNC

-- AUX +

UPPER TERMINALSLOWER TERMINALS

AddressableControl ModuleTrigger OutputSee Note 2

lineground

neutralGreenLead

Use separate knockout. Keep 1/4" spacing from non power limited wiring

Power-LimitedOutputs2.5ampperoutputinalarm(total=8amp)(Supervised)

Supervised Non-Supervised

Non-Supervised

Non-Supervised

RESET

unswitched 120VACpower mains

(non-power limited) NC C NO NC C NO NC C NO

AC Local AC D

ELAY

BAT FAIL AC FAIL

AC LED

VR1

NC

CN

OC

"FA

ULT

" N

C

Fig. 2b

Fig. 2a

These circuits are used tomonitor AC and Bat Fail andwill cause a simultaneous trouble condition to the FACP's IN1 and IN2

Digital Communicator orLocal Annunciator Dry output Contact(Form "C" contacts)

4-wire SmokeDetector

+

--

+

--

4-wire SmokeDetector

FireAlarmControlPanel(FACP)

EOL PowerSupervision Relay

(Not Supplied)

EOLResistor

fromFACP

SW1

-- DC +

SW2

+ OUT1 --

OUT1 OUT2 OUT3 OUT4

INP1 INP2

FAULT

NCC

NOC

"FA

ULT"

NC

OUT1 OUT3

OUT2 OUT4INPUT SELECT

TEMPORALSTROBE SYNC

IN > OUT SYNC

IN1+ IN1-- IN2--IN2+ C "DRY1" NCRET1+ RET1-- RET2--RET2+ C "DRY2" NC

+ OUT2 -- + OUT3 -- + OUT4 --

INPUT SELECTTEMPORAL

STROBE SYNCIN > OUT SYNC

-- AUX +

UPPER TERMINALSLOWER TERMINALS

AddressableControl ModuleTrigger OutputSee Note 2

lineground

neutralGreenLead

Use separate knockout. Keep 1/4" spacing from non power limited wiring

Power-LimitedOutputs2.5ampperoutputinalarm(total=8amp)(Supervised)

Supervised Non-Supervised

Non-Supervised

Non-Supervised

RESET

unswitched 120VACpower mains

(non-power limited) NC C NO NC C NO NC C NO

AC Local AC D

ELAY

BAT FAIL AC FAIL

AC LED

VR1

Fig. 2cTroubleMemoryResetButton

CommontroubleInput/Output

Optional Hookup Diagram:

Page 8: NAC Power Extender Installation Guide · 2020-02-13 · AL802ULADA - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit

- 8 - AL802ULADA

Optional hookups:1- BatteryandACmonitoring:ACorBatteryFailconditionwillcausethecommontroubleinput[C“FAULT”NC]toreportbacktotheFACPviainput1andinput2.Thecommontroubleinputmayalsobeusedforotheroptional supervisorymonitoring.

ToreportACandBatteryTroubleconnectthebatteryandACFailrelayoutputshownin(Fig. 2a)tothe commontroubleinput.

2- Drycontactinput(C“DRY1”NC)(C“DRY2”NC)canbeusedtoalarmoutputfroman addressablemodule(theseinputsareunidirectionandcannotreportbacktotriggermodule).

Connection to triggering devices must be made within 20ft of distance and using conduit for wiring.

3- Auxiliaryoutput(-AUX+)24VDCat1ampmax.

4- ACLocal[NC,C,NO]shouldconnecttothehostcontrolpanelforlocalannunciationof thetroublecondition.

Note: Ifcommontroubleinput,terminalsmarked[C“FAULT”NC]arenotused,theseterminalsmustbe shorted(connectjumper)toremaininactive.Foroptionalhookups(Fig. 2b).

Maintenance:Unitshouldbetestedatleastonceayearfortheproperoperationasfollows:

Output Voltage Test:Undernormalloadconditions,theDCoutputvoltageshouldbecheckedforpropervoltagelevel(26.2-26.4VDC recommended range).Battery Test:Undernormalloadconditionscheckthatthebatteryisfullycharged.Checkspecifiedvoltagebothatbatteryterminalandattheboardterminalsmarked[+BAT--]toinsurethereisnobreakinthebatteryconnectionwires.Fuses:Checkinputandoutputfusesonthepowersupplyboard,[email protected]:Maximumchargingcurrentis3.2amp.Note:Expectedbatterylifeis5years,howeveritisrecommendedchangingbatteriesin4yearsorlessifneeded.

Page 9: NAC Power Extender Installation Guide · 2020-02-13 · AL802ULADA - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit

AL802ULADA - 9 -

Battery Calculation Worksheet

Unitsarecapableofrecharging40AHbatterymax.Iftotalampere-hourrequiredexceeds40AH,decreaseAUXcurrenttoprovideenoughstand-bytimefortheapplication.

DeviceNumber of Devices

Current per DeviceStand-by Current

Alarm Current

Foreachdeviceusethisformula: Thiscolumn x Thiscolumn = Equals Currentpernumberofdevices.

AL802ULADA(Currentdrawfrombattery)

1Stand-by: 90mA 90mA

Alarm: 175mA 175mA

A AL802 Current 90mA 175mA

AuxiliaryDevices Refertodevicemanualforcurrentratings.

Alarm/Stand-by mA mA mA

Alarm/Stand-bymA

mA mA

Alarm/Stand-by mA mA mA

B Auxiliary Devices Current (must not exceed 1 amp)

Refertodevicemanualforcurrentratings.

Alarm: mA 0mA mA

Alarm:mA

0mA mA

Alarm: mA 0mA mA

Alarm: mA 0mA mA

C NotificationAppliancesCurrent must notexceed8amp(8000mA) 0mA mA

D Totalalarmcurrent mA mA

E Totalcurrentratingsconvertedtoamperes(lineDx.001) A A

F Numberofstandbyhours(24forNFPA72,Chapter1,1-5.2.5). H

G MultiplylinesEandF. Totalstand-byAH AH

HAlarmsoundingperiodinhours.(Forexample,5minutes=.0833hours.)

H

I MultiplylinesEandH. TotalalarmAH AH

J AddlinesGandI. Totalstand-byandalarmAH AH

KMultiplylineJby1.30.(30%extrainsurancetomeetdesiredperformance)Totalampere-hoursrequired

AH

Page 10: NAC Power Extender Installation Guide · 2020-02-13 · AL802ULADA - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit

- 10 - AL802ULADA

Appendix A - UL Listed Compatible Devices

A.1 Four (4) Wire Smoke Detectors

TableA-1belowlistsfour(4)wiresmokedetectorscompatiblewithAL802ULADAAUXoutput.

Smoke Detector/Base Detector TypeMax StandbyCurrent (mA)

AlarmCurrent (mA)

SystemSensorB112LP Base 0.12 36

SystemSensorB114LP Base * *

SystemSensorB404B Base * *

SystemSensorDH100ACDC Photoelectric 0.15 0.70

SystemSensorDH100ACDCLP Photoelectric 0.15 0.70

SystemSensorDH100ACDCLPW Photoelectric 0.15 0.70

SystemSensorDH400ACDCI IonizationDuct 25 95

SystemSensorDH400ACDCP PhotoelectricDuct 25 95

SystemSensor1112/24/D Ionization 0.05 50

SystemSensor1424 Ionization 0.10 41

SystemSensor1451(w/B402BBase) Ionization 0.10 39

SystemSensor2112/24ATR Photoelectric 0.50 60/70

SystemSensor2112/24AITR Photoelectric 0.50 60/70

SystemSensor2112/24/D Photoelectric 0.05 50

SystemSensor2112/24R Photoelectric 0.50 60/70

SystemSensor2112/24TR Photoelectric 0.50 60/70

SystemSensor2112/24T/D Photoelectricw/135oThermal 0.05 50

SystemSensor2112/24TSRBPhotoelectricw/135o

ThermalSupervisoryRelay15 45

SystemSensor2312/24TB Photoelectric 0.12 50

SystemSensor2412(12volt) Photoelectric 0.12 77

SystemSensor2412AT(12volt) Photoelectric 0.12 58

SystemSensor2412TH(12volt) Photoelectric 0.12 77

SystemSensor2424 Photoelectric 0.10 41

SystemSensor2424TH Photoelectric 0.10 41

SystemSensor2451 Photoelectric 0.10 39

SystemSensor2451TH(with/B402BBase) Photoelectric 0.10 39

SystemSensor2W-MOD LoopTest/MaintenanceMod. 30 50

Page 11: NAC Power Extender Installation Guide · 2020-02-13 · AL802ULADA - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit

AL802ULADA - 11 -

A.1 Four (4) Wire Smoke Detectors (cont.)

Smoke Detector/Base Detector TypeMax StandbyCurrent (mA)

AlarmCurrent (mA)

SystemSensor4W-B(12/24volt) PhotoelectricI3 .05 23

SystemSensor4WT-B(12/24volt) PhotoelectricI3w/Therm .05 23

SystemSensor4WTA-B(12/24volt) I3Photow/Therm/Sounder .05 35

SystemSensor4WTR-B(12/24volt) I3Photow/Therm/Relay .05 35

SystemSensor4WTR-B(12/24volt)I3Photow/Therm/Sounder/Relay

.05 50

SystemSensor4WITAR-B(12/24volt)I3Photow/IsolatedTherm/

Sounder/Relay.05 50

SystemSensor2W-MOD2I3LoopTest/Maintenance

Mod..05 *

SystemSensorRRS-MODI3ReversingRelay/Sync

Module.05 *

SystemSensor6424 ProjectedBeam 10 28.4

SystemSensorBeam1224(S) ProjectedBeam 17 38.5

*Contactmanufacturerforcurrentdraws

A.2 Relays

TableA-3belowlistsrelayscompatiblewithAL802ULADAAUXoutput.

Manufacturer Model Current (mA)

SystemSensor

PR-1 PR-2 PR-3 EOLR-1 R-10T R-14T R-20T R-24T R-10E R-14E R-20ER-24E

15 30 30 30 23 23 40 40 23 23 40 40

Page 12: NAC Power Extender Installation Guide · 2020-02-13 · AL802ULADA - 3 - Power Supply Specifications: AC Input: 120VAC 60Hz, 5 amp, supplied by a maximum 15 amp dedicated branch circuit

- 12 - AL802ULADA

12.230"

15.500"

1.100"

0.910"

1.100"

0.910"

0.790"

1.100"

1.500"

1.250"

5.000"

1.250"

1.500"4.615"4.615"1.500"

1.750"

1.500"4.615"4.615"1.500"

1.750"

4.500"4.500"1.250"

1.500"

5.000"

2.000"

2.000"

1.250"

1.375"

1.125"

Enclosure Dimensions:15.5”Hx12.23”Wx4.5”D

MEMBER

Altronixisnotresponsibleforanytypographicalerrors.

14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056website:www.altronix.com,e-mail:[email protected],LifetimeWarranty,MadeinU.S.A.IIAL802ULADA L27K