35
N Surge Protection FAIL-SAFE OVERVOLTAGE PROTECTION IN A FULL RANGE OF OPTIONS • Surge-Trap® STZ Series N2 • Surge-Trap® STZ-R Series N5 • Surge-Trap® STXH Series N8 • Surge-Trap® STXR Series N10 • Surge-Trap® STXP Series N12 • Surge-Trap® STXT Series N14 • Surge-Trap® STT Series N16 • Surge-Trap® STP Series Pluggable SPD N19 • Surge-Trap® ST Series Modular SPD N22 • Surge-Trap® STPT2-PV Series for Photovoltaic N25 • Surge-Trap® STMT23 Slim Series (IEC only) N26 • Surge-Trap® STET23 Series with EMI Filter (IEC only) N27 • STLB Series N28 • TPMOV® Technology N30 • VSP MOV Protector Fuse N32 • Surge-Rated Disconnect Switch N34 Your problem: Power-related problems cost US companies more than $80 billion dollars a year Most transients originate from within a facility and nearly 80% of today’s overvoltage problems are caused by equipment and power disturbances within the plant These inner-facility transients are caused, for example, by light load panels switching on and off, motors starting and stopping, and close conductor proximity Less than 20% of the transient problems originate outside the facility due to lightning strikes, utility grid switching, switching capacitor banks, and electrical accidents Our solution: You need fail-safe surge suppression, and the reliability and cost savings of Mersen’s Surge-Trap® Surge Protective Devices with patented TPMOV® Technology inside Surge-Trap SPDs provide a compact, space saving solution Plus, unlike other SPDs on the market, they do not require additional overcurrent protection, thus offering reduced installation costs Want more information fast? For more technical or application-specific information, please call our overvoltage protection experts at 978-462-6662; 416-252-9371 in Canada; or visit our website at ep.mersen.com.

N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

  • Upload
    vodang

  • View
    227

  • Download
    5

Embed Size (px)

Citation preview

Page 1: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

NSurge ProtectionFa i l- S a F e ov e r vo ltag e P r ot e c t i o N i N a F u l l r a N g e o F o P t i o N S

•Surge-Trap®STZSeries . . . . . . N2

•Surge-Trap®STZ-RSeries . . . . N5

•Surge-Trap®STXHSeries . . . . . N8

•Surge-Trap®STXRSeries . . . . N10

•Surge-Trap®STXPSeries . . . . N12

•Surge-Trap®STXTSeries . . . . N14

•Surge-Trap®STTSeries . . . . . . N16

•Surge-Trap®STPSeriesPluggableSPD . . . . . . . . . . . . . N19

•Surge-Trap®STSeriesModularSPD . . . . . . . . . . . . . . . N22

•Surge-Trap®STPT2-PVSeriesforPhotovoltaic . . . . . . . . . . . N25

•Surge-Trap®STMT23SlimSeries(IEConly) . . . . . . . . . . . . . . . . . N26

•Surge-Trap®STET23SerieswithEMIFilter(IEConly) . . . . N27

•STLBSeries . . . . . . . . . . . . . . . . N28

•TPMOV®Technology . . . . . . . .N30

•VSPMOVProtectorFuse . . . . N32

•Surge-RatedDisconnectSwitch . . . . . . . . . .N34

Your problem:Power-relatedproblemscostU .S .companiesmorethan$80billion

dollarsayear .Mosttransientsoriginate

fromwithinafacilityandnearly80%of

today’sovervoltageproblemsarecaused

byequipmentandpowerdisturbances

withintheplant .Theseinner-facility

transientsarecaused,forexample,by

lightloadpanelsswitchingonandoff,

motorsstartingandstopping,andclose

conductorproximity .Lessthan20%ofthe

transientproblemsoriginateoutsidethe

facilityduetolightningstrikes,utilitygrid

switching,switchingcapacitorbanks,and

electricalaccidents .

Our solution:Youneedfail-safesurgesuppression,andthereliabilityand

costsavingsofMersen’sSurge-Trap®

SurgeProtectiveDeviceswithpatented

TPMOV®Technologyinside .Surge-Trap

SPDsprovideacompact,spacesaving

solution .Plus,unlikeotherSPDsonthe

market,theydonotrequireadditional

overcurrentprotection,thusoffering

reducedinstallationcosts .

Want more information fast?Formoretechnicalorapplication-specific

information,pleasecallourovervoltage

protectionexpertsat978-462-6662;

416-252-9371inCanada;orvisitour

websiteatep.mersen.com.

Page 2: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.comN2

N

Surge Protective device

NEMADEVICESFORANSI/UL 1449TYPE 1 AND2APPL ICATIONS

SURgE-TRAP® STZ SERIESEXTERNALSPD

TheMersenflagshipforfacility-wideprotection,TheSurge-Trap®

Type1STZSeriesfeaturessurgecapacitiesupto450kAdesigned

withMersen’sindustryleadingTPMOV®technologyinsidemakingit

thesafestandmostreliableproductonthemarket .Optionsinclude

surgecounter,through-the-doordisconnectswitch,audiblealarm,dry

contact,andEMI/RFIfiltering .ThisexternalSPDcanbeinstalledon

thelineorloadsideoftheserviceentrance .

F EATURES AND BENEF I TS :• Idealfornewconstructionbidprojectsandspecificationaswellas

existingfacilityretrofit

• AvailablewithaccessoryOption Aforbasicfeatures(LEDstatusindicators)andOption Bforstandardfeatures(EMI/RFIfilter,surgecounter,Audiblealarmanddrycontacts)

• ReplaceableSPDModulewhichcanberotated90degrees

dependingondesiredcableentrylocation

• Upto10ModesofProtection(L-N,L-L,L-g,N-g)

• 15-yearwarranty

RAT INgS :

• Volts (Un):120-480VAC

• Nominal Discharge Current Rating (In):20kA

• Surge Capacity (per phase):100,150,200,300,450kA

• Short-Circuit Current Rating (SCCR):200kA

• Optional EMI/RFI Filter:Upto-50dBfrom10kHzto100MHz

APPROVALS :

• ANSI/UL14494thEdition,

Type1SPD,FileE210793

• CSAC22 .2,Type1SPD

• ANSI/IEEEC62 .41 .1,C62 .41 .2,

C62 .45

• UL96ALightningProtection

• RoHSCompliant

Page 3: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N3

Surge ProtectioNSURgE-TRAP® STZSERIES

GENERAl PRODUCt SPECIFICAtIONS

CAtAlOG NUMBER (INClUDES SUFFIxES*)

SYStEM VOltAGE AND CONFIGURAtION

In MAxIMUM CONtINUOUS OPERAtING VOltAGE (MCOV, Uc)

VOltAGE PROtECtION RAtING (VPR) (Ul 1449, 6kA, 3kV)

l-N l-G l-l N-G* l-N l-G l-l N-G*STZ240S… 240/120V Split Phase 20kA 150 150 300 150 700 700 1000 700

STZ120D… 120V 3-Phase DELTA 20kA - 150 300 - - 700 1000 -

STZ208Y… 208/120V 3-Phase WYE 20kA 150 150 300 150 700 700 1000 700

STZ480Y… 480/277V 3-Phase WYE 20kA 320 320 640 150 1200 1200 2000 700

STZ240D… 240V 3-Phase DELTA 20kA - 320 640 - - 1200 2000 -

STZ480D… 480V 3-Phase DELTA & HRG WYE 20kA - 550 1100 - - 1800 3000 -

*Part Number Selector (Don’t see what you need? Please contact the factory)

STZModel Series

STZ

480YVoltage and System

Configuration

240S: 240/120V Split120D: 120V DELTA208Y: 208/120V WYE480Y: 480/277V WYE240D: 240V DELTA480D: 480V DELTA & HRG WYE

30Surge Capacity

10: 100kA15: 150kA20: 200kA30: 300kA45: 450kA

BPackage

A: Basic LED Status Indicators Phase Loss IndicationB: Standard LED Status Indicators Phase Loss Indication Audible Alarm Form C Dry Contacts EMI/RFI Filter Surge Counter

1Enclosure

1: NEMA 1/12/3R/4X: NEMA 4X

TDisconnect

T: UL98 Switch thru the door handleBLANK: None

Human-Machine Interface (HMI)

Option A: Basic Option B: Standard

Note: Images above show HMI mounted on Internal SPD (STZ-R Series). For the STZ External SPD, HMI will be mounted on the enclosure door.

Mounting: Mounting feetWiring: Wire Lugs for 6-10 AWG copperEnclosure: NEMA 4 or NEMA 4X stainless steelFlammability: UL94-5VA Operating & Storage Temperature: -40°C to +85°C

Relative Humidity Range: 0 to 95% non-condensingVisual LED End-of-Life Indicator: Green = 67 to 100% Life Yellow = 34 to 66% Life Red = 0 to 33% LifeFrequency: 50-60Hz

Page 4: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N4

Surge ProtectioN

Optional Form C Dry Contact and Audible Alarm (Included with Option B)

Form C Dry Contact 125VAC, 1A Resistive 30VDC, 2A General Purpose __________________________________________________

NC = Normally Closed COM = Common NO = Normally Open

Audible Alarm Alarm sounds when any protection is lost.

Dimensions and Mounting Configurations

Without Disconnect Switch 12x12 Enclosure

With Disconnect Switch16x12 Enclosure

DIMENSIONS IN [ ] ARE MILLIMETERS

6.29 12.98

13.52

10.00

12.77

4X .31 THRU

REV. DATE ECO DESCRIPTION BY CK APP- 3/2/2016 N/A INITIAL RELEASE JRB N/A N/A

CONTROL No:____________1773

STZ SeriesExternal SPD Type 1

NEMA 4/4X450kA max Surge Capacity

C. MCKENZIE

3/2/16

R. LYONS

OUTLINE DIMENSIONSNOT TO BE USED FOR PRODUCTION

SIGN:

DATE:

DESIGN ENGINEERPRODUCT MANAGERSIGN:

DATE:

MERSEN USA NEWBURYPORT-MA, LLC374 MERRIMAC STREETNEWBURYPORT,MA 01950

SHEET 1 OF 1

7021143/2/16

DIMENSIONS IN [ ] ARE MILLIMETERS

12.98

17.52

8.06 12.00

16.77

4X .31 THRU

REV. DATE ECO DESCRIPTION BY CK APP- 3/2/2016 N/A INITIAL RELEASE JRB N/A N/A

CONTROL No:____________1773

STZ SeriesExternal SPD Type 1

NEMA 4/4X with Disconnect Switch450kA max Surge Capacity

C. MCKENZIE

3/2/16

R. LYONS

OUTLINE DIMENSIONSNOT TO BE USED FOR PRODUCTION

SIGN:

DATE:

DESIGN ENGINEERPRODUCT MANAGERSIGN:

DATE:

MERSEN USA NEWBURYPORT-MA, LLC374 MERRIMAC STREETNEWBURYPORT,MA 01950

SHEET 1 OF 1

7021153/2/16

SURgE-TRAP® STZSERIES

Page 5: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com N5

NSurge Protective device

NEMADEVICESFORANSI/UL 1449TYPE 1 AND2APPL ICATIONS

SURgE-TRAP® STZ-R SERIESINTERNALSPD

Forfacility-widesurgeprotectioninternaltoexistingequipmentsuch

asswitchgear,panelboards,ormotorcontrolcenters,theSurge-Trap®

Type1STZ-RSeriesistheobviouschoice .TheSTZ-Rseriesfeatures

surgecapacitiesupto450kAdesignedwithMersen’sindustry-leading

TPMOV®technologyinsidemakingitthesafestandmostreliable

productonthemarket .IdealforOEMsandpanelbuilders,thisinternal

SPDcanbeinstalledonthelineorloadsideoftheserviceentrance .

F EATURES AND BENEF I TS :• SPDintendedtobeinstalledinternaltoexistingswitchgear,

panelboards,motorcontrolcenters,etc .

• AvailablewithaccessoryOption Aforbasicfeatures(LEDstatusindicators)andOption Bforstandardfeatures(EMI/RFIfilter,surgecounter,Audiblealarmanddrycontacts)

• Localorremotehumanmachineinterface(HMI)whichcanbe

rotated90degreesdependingondesiredcableentrylocation

• Upto10ModesofProtection(L-N,L-L,L-g,N-g)

• 15-yearwarranty

RAT INgS :

• Volts (Un):120-480VAC

• Nominal Discharge Current Rating (In):20kA

• Surge Capacity (per phase):100,150,200,300,450kA

• Short-Circuit Current Rating (SCCR):200kA

• Optional EMI/RFI Filter:Upto-50dBfrom10kHzto100MHz

APPROVALS :

• ANSI/UL14494thEdition,

Type1SPD,FileE210793

• CSAC22 .2,Type1SPD

• ANSI/IEEEC62 .41 .1,C62 .41 .2,

C62 .45

• UL96ALightningProtection

• RoHSCompliant

Page 6: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N6

Surge ProtectioN SURgE-TRAP® STZ-R SERIES

GENERAl PRODUCt SPECIFICAtIONS

CAtAlOG NUMBER (INClUDES SUFFIxES*)

SYStEM VOltAGE AND CONFIGURAtION

In MAxIMUM CONtINUOUS OPERAtING VOltAGE (MCOV, Uc)

VOltAGE PROtECtION RAtING (VPR) (Ul 1449, 6kA, 3kV)

l-N l-G l-l N-G* l-N l-G l-l N-G*STZ240S… 240/120V Split Phase 20kA 150 150 300 150 700 700 1000 700

STZ120D... 120V 3-Phase DELTA 20kA - 150 300 - - 700 1000 -

STZ208Y… 208/120V 3-Phase WYE 20kA 150 150 300 150 700 700 1000 700

STZ480Y… 480/277V 3-Phase WYE 20kA 320 320 640 150 1200 1200 2000 700

STZ240D… 240V 3-Phase DELTA 20kA - 320 640 - - 1200 2000 -

STZ480D… 480V 3-Phase DELTA & HRG WYE 20kA - 550 1100 - - 1800 3000 -

*Part Number Selector (Don’t see what you need? Please contact the factory.)

STZModel Series

STZ

480YVoltage and System

Configuration

240S: 240/120V Split120D: 120V DELTA208Y: 208/120V WYE480Y: 480/277V WYE240D: 240V DELTA480D: 480V DELTA & HRG WYE

30Surge Capacity

10: 100kA15: 150kA20: 200kA30: 300kA45: 450kA

BPackage

A: Basic LED Status Indicators Phase Loss IndicationB: Standard LED Status Indicators Phase Loss Indication Audible Alarm Form C Dry Contacts EMI/RFI Filter Surge Counter

REnclosure

Q: Internal SPD without HMIR: Internal SPD with HMI

UDisconnect

U: UL98 SwitchBLANK: None

Human-Machine Interface (HMI)

Option A: Basic Option B: Standard

Mounting: Mounting feetWiring: Wire Lugs for 6-10 AWG copperFlammability: UL94-5VA Operating & Storage Temperature: -40°C to +85°C

Relative Humidity Range: 0 to 95% non-condensingVisual LED End-of-Life Indicator: Green = 67 to 100% Life Yellow = 34 to 66% Life Red = 0 to 33% LifeFrequency: 50-60Hz

Page 7: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N7

Surge ProtectioN

Optional Form C Dry Contact and Audible Alarm (Included with Option B)

Form C Dry Contact 125VAC, 1A Resistive 30VDC, 2A General Purpose __________________________________________________

NC = Normally Closed COM = Common NO = Normally Open

Audible Alarm Alarm sounds when any protection is lost.

Dimensions and Mounting Configurations

Without Disconnect Switch With Disconnect Switch12x12 Enclosure 16x12 Enclosure

DIMENSIONS IN [ ] ARE MILLIMETERS

2.49

4.83

3.98

.70

TYP. .900

TYP. .500

TYP. .080

8.47 5.50 2.00

8.31

7.75

8X .25 THRU

REV. DATE ECO DESCRIPTION BY CK APP- 3/1/2016 N/A INITIAL RELEASE JRB N/A N/A

CONTROL No:____________1773

STZ-R SeriesInternal SPD Type 1

450kA max Surge CapacityC. MCKENZIE

3/2/16

R. LYONS

OUTLINE DIMENSIONSNOT TO BE USED FOR PRODUCTION

SIGN:

DATE:

DESIGN ENGINEERPRODUCT MANAGERSIGN:

DATE:

MERSEN USA NEWBURYPORT-MA, LLC374 MERRIMAC STREETNEWBURYPORT,MA 01950

SHEET 1 OF 1

7021133/2/16

DIMENSIONS IN [ ] ARE MILLIMETERS

10.88

10.25

5.60

14.75 14.25

4.45

4X .25 THRU

11.01

4.98

4.05

REV. DATE ECO DESCRIPTION BY CK APP- 3/2/2016 N/A INITIAL RELEASE JRB N/A N/A

CONTROL No:____________1773

STZ-R SeriesInternal SPD Type 1 with Disconnect Switch

450kA max Surge CapacityC. MCKENZIE

3/2/16

R. LYONS

OUTLINE DIMENSIONSNOT TO BE USED FOR PRODUCTION

SIGN:

DATE:

DESIGN ENGINEERPRODUCT MANAGERSIGN:

DATE:

MERSEN USA NEWBURYPORT-MA, LLC374 MERRIMAC STREETNEWBURYPORT,MA 01950

SHEET 1 OF 1

7021163/2/16

DIMENSIONS IN [ ] ARE MILLIMETERS

10.88

10.25

5.60

14.75 14.25

4.45

4X .25 THRU

11.01

4.98

4.05

REV. DATE ECO DESCRIPTION BY CK APP- 3/2/2016 N/A INITIAL RELEASE JRB N/A N/A

CONTROL No:____________1773

STZ-R SeriesInternal SPD Type 1 with Disconnect Switch

450kA max Surge CapacityC. MCKENZIE

3/2/16

R. LYONS

OUTLINE DIMENSIONSNOT TO BE USED FOR PRODUCTION

SIGN:

DATE:

DESIGN ENGINEERPRODUCT MANAGERSIGN:

DATE:

MERSEN USA NEWBURYPORT-MA, LLC374 MERRIMAC STREETNEWBURYPORT,MA 01950

SHEET 1 OF 1

7021163/2/16

DIMENSIONS IN [ ] ARE MILLIMETERS

2.49

4.83

3.98

.70

TYP. .900

TYP. .500

TYP. .080

8.47 5.50 2.00

8.31

7.75

8X .25 THRU

REV. DATE ECO DESCRIPTION BY CK APP- 3/1/2016 N/A INITIAL RELEASE JRB N/A N/A

CONTROL No:____________1773

STZ-R SeriesInternal SPD Type 1

450kA max Surge CapacityC. MCKENZIE

3/2/16

R. LYONS

OUTLINE DIMENSIONSNOT TO BE USED FOR PRODUCTION

SIGN:

DATE:

DESIGN ENGINEERPRODUCT MANAGERSIGN:

DATE:

MERSEN USA NEWBURYPORT-MA, LLC374 MERRIMAC STREETNEWBURYPORT,MA 01950

SHEET 1 OF 1

7021133/2/16

DIMENSIONS IN [ ] ARE MILLIMETERS

10.88

10.25

5.60

14.75 14.25

4.45

4X .25 THRU

11.01

4.98

4.05

REV. DATE ECO DESCRIPTION BY CK APP- 3/2/2016 N/A INITIAL RELEASE JRB N/A N/A

CONTROL No:____________1773

STZ-R SeriesInternal SPD Type 1 with Disconnect Switch

450kA max Surge CapacityC. MCKENZIE

3/2/16

R. LYONS

OUTLINE DIMENSIONSNOT TO BE USED FOR PRODUCTION

SIGN:

DATE:

DESIGN ENGINEERPRODUCT MANAGERSIGN:

DATE:

MERSEN USA NEWBURYPORT-MA, LLC374 MERRIMAC STREETNEWBURYPORT,MA 01950

SHEET 1 OF 1

7021163/2/16

SURgE-TRAP® STZ-R SERIES

Page 8: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.comN8

NSurge Protective device

NEMADEVICESFORANSI/UL 1449TYPE 1 AND2APPL ICATIONS

SURgE-TRAP® STXHSERIES

ThemostcompactoftheSTXseriesoffering,theSurge-Trap®Type1

STXHmeetsrequirementsforUL14494thEditionandissuitable

forany120/240VACsplitphaseapplication .TheSTXHSeriesSPD

featuresTPMOV®technologyinsidemakingitthesafestproduct

availableinitscategory .Itscompactsize,performance,andreliability

areespeciallyidealforHVACapplicationsanddirectmountingtoair

conditiondisconnectswitches .

F EATURES AND BENEF I TS :

• DesignedwiththeindustryleadingMersenTPMOV®Technology

• CompactfootprintdesignedtomatewithACDisconnectSwitches

• LEDstatusindicator(ON=good,OFF=Replace)

• NEMA4Xenclosureforoutdoororindooruse

• Fits1/2”knockoutswith18”leadsforeasyinstallation

• ForuseinANSI/ULType1or2SPDinstallations

• 3ModesofProtection(L-N,L-L)

• 3-yearwarranty

RAT INgS :

• Volts (Un):120/240VACSplitPhase

• Nominal Discharge Current Rating (In):20kA

• Surge Capacity (per phase and per mode):50kA

• Short-Circuit Current Rating (SCCR):200kA

APPROVALS :

• ANSI/UL14494thEdition,

Type1SPD,FileE210793

• CSAC22 .2,Type1SPD

• ANSI/IEEEC62 .41 .1,C62 .41 .2,

C62 .45

• UL96ALightningProtection

• RoHSCompliant

Page 9: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N9

Surge ProtectioNSURgE-TRAP® STXHSERIES

GENERAl PRODUCt SPECIFICAtIONS

CAtAlOG NUMBER (INClUDES SUFFIxES*)

SYStEM VOltAGE AND CONFIGURAtION

In MAxIMUM CONtINUOUS OPERAtING VOltAGE (MCOV, Uc)

VOltAGE PROtECtION RAtING (VPR) (Ul 1449, 6kA, 3kV)

l-N l-l l-N l-lSTXH120P05 120V Single Phase 20kA 150 - 600 -

STXH240S05 240/120V Split Phase 20kA 150 300 600 1000

LED Status Indicator 1/2"-14 Mounting Hub

Dimensions and Mounting Configurations Ideal for Air Conditioning Disconnect Applications

Mounting: 1/2" – 14 threaded hub Includes sealing locking washerWiring: Pre-wired 18" 10AWGEnclosure: NEMA 4X Non-metallicFlammability: UL94-5VA

Operating & Storage Temperature: -40°C to +85°CRelative Humidity Range: 0 to 95% non-condensingVisual End-of-Life Indicator: GREEN = OK, OUT = REPLACEFrequency: 50-60Hz

Visible from side profile through light tube in cover

DIMENSIONS IN [ ] ARE MILLIMETERS

3.07 21.00±2.00

.88

.13

1/2 NPSM

1/2 SEALING LOCKNUT

10 AWG WIRES

1.85

3.22

REV. DATE ECO DESCRIPTION BY CK APP- 2/29/2016 N/A INITIAL RELEASE JRB N/A N/A

CONTROL No:____________1773

STXH SeriesSurge-Trap® SPD Type 1

3/2/16

C. MCKENZIE

3/2/16

R. LYONS

OUTLINE DIMENSIONSNOT TO BE USED FOR PRODUCTION

SIGN:

DATE:

DESIGN ENGINEERPRODUCT MANAGERSIGN:

DATE:

MERSEN USA NEWBURYPORT-MA, LLC374 MERRIMAC STREETNEWBURYPORT,MA 01950

SHEET 1 OF 1

702103

DIMENSIONS IN [ ] ARE MILLIMETERS

3.07 21.00±2.00

.88

.13

1/2 NPSM

1/2 SEALING LOCKNUT

10 AWG WIRES

1.85

3.22

REV. DATE ECO DESCRIPTION BY CK APP- 2/29/2016 N/A INITIAL RELEASE JRB N/A N/A

CONTROL No:____________1773

STXH SeriesSurge-Trap® SPD Type 1

3/2/16

C. MCKENZIE

3/2/16

R. LYONS

OUTLINE DIMENSIONSNOT TO BE USED FOR PRODUCTION

SIGN:

DATE:

DESIGN ENGINEERPRODUCT MANAGERSIGN:

DATE:

MERSEN USA NEWBURYPORT-MA, LLC374 MERRIMAC STREETNEWBURYPORT,MA 01950

SHEET 1 OF 1

702103

Page 10: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.comN10

NSurge Protective device

NEMADEVICESFORANSI/UL 1449TYPE 1 AND2APPL ICATIONS

SURgE-TRAP® STXRSERIES

ThemostpopularrangeintheSTXseriesoffering,theSurge-Trap®Type

1STXRmeetsrequirementsforUL14494thEditionandisidealforthe

replacementofobsoletesurgearrestors .TheSTXRSeriesSPDsfeature

TPMOV®technologyinside,makingthemthesafestproductavailable .

Withasmall,compactdesignandlineorloadinstallationflexibility,

theSTXRseriesistheperfectfitforbranchpaneland/orindividual

equipmentprotection .

F EATURES AND BENEF I TS :

• DesignedwiththeindustryleadingMersenTPMOV®Technology• LEDstatusindicator(ON=good,OFF=Replace)• NEMA4Xenclosureforoutdoororindooruse• Fits3/4"knockoutswith3'leadsforeasyinstallation• Optionalmountingbracketforsurfacemountapplications• Optionalaudiblealarmandremotedrycontacts• ForuseinANSI/ULType1or2SPDinstallations• Upto10modesofProtection(L-N,L-L,L-goptional,N-goptional)

• 5-yearwarranty

RAT INgS :

• Volts (Un):120-600VAC

• Nominal Discharge Current Rating (In):10-20kA

• Surge Capacity (per phase and per mode):50kA

• Short-Circuit Current Rating (SCCR):200kA

APPROVALS :

• ANSI/UL14494thEdition,

Type1SPD,FileE210793

• CSAC22 .2,Type1SPD

• ANSI/IEEEC62 .41 .1,C62 .41 .2,

C62 .45

• UL96ALightningProtection

• RoHSCompliant

Page 11: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N11

Surge ProtectioN

61-600A

SURgE-TRAP® STXRSERIES

GENERAl PRODUCt SPECIFICAtIONS

CAtAlOG NUMBER (INClUDES SUFFIxES*)

SYStEM VOltAGE AND CONFIGURAtION

In MAxIMUM CONtINUOUS OPERAtING VOltAGE (MCOV, Uc)

VOltAGE PROtECtION RAtING (VPR) (Ul 1449, 6kA, 3kV)

l-N l-G l-l N-G* l-N l-G l-l N-G*STXR120P05 120V Single Phase 20kA 150 300 - 150 700 1200 - 600

STXR240P05 240V Single Phase 20kA 320 640 - 320 1200 1800 - 1000

STXR240S05 240/120V Split Phase 20kA 150 300 300 150 700 1200 1200 600

STXR480S05 480/240V Split Phase 20kA 320 640 640 320 1200 1800 2000 1000

STXR208Y05 208/120V 3-Phase WYE 20kA 150 300 300 150 700 1200 1200 600

STXR380Y05 380/220V 3-Phase WYE 20kA 320 640 640 320 1200 1800 2000 1000

STXR480Y05 480/277V 3-Phase WYE 20kA 320 470 640 150 1200 1800 2000 700

STXR600Y05 600/347V 3-Phase WYE 20kA 420 690 840 270 1500 2500 2500 1000

STXR240D05 240V 3-Phase DELTA 20kA - 320 640 - - 1200 2000 -

STXR480D05 480V 3-Phase DELTA & HRG WYE 10kA - 550 1100 - - 1800 3000 -

STXR600D05 600V 3-Phase DELTA 20kA - 690 840 - - 2000 2500 -

l-N/Hl-N

l-G/Hl-G

l-l/Hl-l

N-G* l-N/Hl-N

l-G/Hl-G

l-l/Hl-l

N-G*

STXR240H05 240/120V Hi-Leg DELTA 20kA 150/270 300/420 300/420 150 700/1.2k 1.2k/1.2k 2k/2k 600

STXR480H05 480/240V Hi-Leg DELTA 10kA 320/550 320/550 640/870 320 1.2/1.8k 1.2/1.8k 2k/2.5k 1000

*Suffixes: Add Suffix “N” for N-G protection. Example: STXR208Y05N

Add Suffix “A” for Audible Alarm and Dry Contact. Example: STXR208Y05A

For both options, Example: STXR208Y05AN

CAtAlOG NUMBER

ACCESSORY DESCRIPtION

STXRMBK STXR Mounting Bracket Kit. Includes (1) 90 degree bracket and (2) mounting screws

Optional Form C Dry Contact and Audible Alarm (Suffix “A”)

Form C Dry Contact (Pre-wired 3' 18AWG) 125VAC, 1A Resistive 30VDC, 2A General Purpose __________________________________________________

Gray = Normally Closed Blue = Common Red = Normally Open

Audible AlarmAlarm sounds when any protection is lost

3/4"-14 Mounting Hub

Dimensions and Mounting Configurations Bracket Mount Option

Mounting: 3/4" – 14 threaded hub Includes locking washerWiring: Pre-wired 3' (1m) 10AWGEnclosure: NEMA 4X Non-metallicFlammability: UL94-5VA

Operating & Storage Temperature: -40°C to +85°CRelative Humidity Range: 0 to 95% non-condensingVisual End-of-Life Indicator: GREEN = OK, OUT = REPLACEFrequency: 50-60Hz

Page 12: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.comN12

NSurge Protective device

NEMADEVICESFORANSI/UL 1449TYPE 1 AND2APPL ICATIONS

SURgE-TRAP® STXPSERIES

TheSurge-Trap®Type1STXPSeriesoffersadvancedperformanceand

featuresovertheSTXRseriesincludinghighersurgecapacityand

phaseLEDstatusindicators .TheSTXPmeetsrequirementsforUL1449

4thEditionandhasbeendesignedforadditionalmountingflexibility

includingmountingfeetandflush-mountcapability .TheSTXPfeatures

TPMOV®technologyinsidemakingitthesafestproductavailable .

Installationcanbedoneonthelineorloadsideofapanel .TheSTXPis

theperfectfitfromserviceentranceallthewaydowntoanimportant

machinespecificcontrolpanel .

F EATURES AND BENEF I TS :• DesignedwiththeindustryleadingMersenTPMOV®Technology

(internallyfused)

• Enhanced100kAsurgecapacityforlongerlifeandhighersingle

impulsewithstand

• Pre-wiredwith3'leadsforeasyinstallation

• Upto10ModesofProtection(L-N,L-L,L-g,N-g)

• 10-yearwarranty

RAT INgS :

• Volts (Un):120-600VAC

• Nominal Discharge Current Rating (In):20kA

• Surge Capacity (per phase):100kA

• Short-Circuit Current Rating (SCCR):200kA

APPROVALS :

• ANSI/UL14494thEdition,

Type1SPD,FileE210793

• CSAC22 .2,Type1SPD

• ANSI/IEEEC62 .41 .1,C62 .41 .2,

C62 .45

• UL96ALightningProtection

• RoHSCompliant

Page 13: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N13

Surge ProtectioNSURgE-TRAP® STXPSERIES

GENERAl PRODUCt SPECIFICAtIONS

CAtAlOG NUMBER (INClUDES SUFFIxES*)

SYStEM VOltAGE AND CONFIGURAtION

In MAxIMUM CONtINUOUS OPERAtING VOltAGE (MCOV, Uc)

VOltAGE PROtECtION RAtING (VPR) (Ul 1449, 6kA, 3kV)

l-N l-G l-l N-G* l-N l-G l-l N-G*STXP120P10 120V Single Phase 20kA 150 150 - 150 700 700 - 600

STXP240S10 240/120V Split Phase 20kA 150 150 300 150 700 700 1000 600

STXP480S10 480/240V Split Phase 20kA 320 320 640 150 1200 1200 2000 600

STXP208Y10 208/120V 3-Phase WYE 20kA 150 150 300 150 700 700 1000 600

STXP380Y10 380/220V 3-Phase WYE 20kA 320 320 640 150 1200 1200 2000 600

STXP480Y10 480/277V 3-Phase WYE 20kA 320 320 640 150 1200 1200 2000 600

STXP600Y10 600/347V 3-Phase WYE 20kA 420 420 840 275 1200 1500 2000 1000

STXP240D10 240V 3-Phase DELTA 20kA - 320 640 - - 1200 2000 -

STXP480D10 480V 3-Phase DELTA & HRG WYE 20kA - 550 1100 - - 1800 3000 -

STXP600D05 (50kA) 600V 3-Phase DELTA 20kA - 690 695 - - 2000 2500 -

l-N/Hl-N

l-G/Hl-G

l-l/Hl-l

N-G* l-N/Hl-N

l-G/Hl-G

l-l/Hl-l

N-G*

STXP240H10 240/120V Hi-Leg DELTA 20kA 150/275 150/275 300/425 150 700/1.2k 700/1.2k 1.0k/2000 600

STXP480H10 480/240V Hi-Leg DELTA 20kA 320/550 320/550 640/870 320 1.2k/1.8k 1.2k/1.8k 1.8k/2.5k 1000

*Suffixes: Add Suffix “A” for Audible Alarm and Dry Contact. Example: STXP208Y10A

CAtAlOG NUMBER

ACCESSORY DESCRIPtION

STXPFMK STXP Flush Mount Kit. Includes (1) mounting plate and (3) mounting screws

Optional Form C Dry Contact and Audible Alarm (Suffix “A”)

Form C Dry Contact (Pre-wired 3' 18AWG) 125VAC, 1A Resistive 30VDC, 2A General Purpose __________________________________________________

Gray = Normally Closed Blue = Common Red = Normally Open

Audible AlarmAlarm sounds when anyprotection is lost

Dimensions and Mounting Configurations Flush Mount Option

Mounting: Female 3/4" – 14 threaded hub Mounting feet with 0.125" diameter holesWiring: Pre-wired 3' (1m) 10AWGEnclosure: NEMA 4X Non-metallicFlammability: UL94-5VA

Operating & Storage Temperature: -40°C to +85°CRelative Humidity Range: 0 to 95% non-condensingVisual End-of-Life Indicator: GREEN = OK, OUT = REPLACEFrequency: 50-60Hz

3/4"-14 Female Mounting Hub

Page 14: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.comN14

NSurge Protective device

NEMADEVICESFORANSI/UL 1449TYPE 1 AND2APPL ICATIONS

SURgE-TRAP® STXTSERIES

ThemostadvancedoftheSTXseries,theSurge-Trap®Type1STXT

SeriescomesstandardwithEMI/RFIFilteringandsurgecapacitiesup

to200kA .TheSTXTfeaturesTPMOV®technologyinside,makingitthe

safestproductavailable .Withlineorloadsideinstallationflexibility,

thisunitisagreatfitfromtheserviceentranceallthewaydownto

eachdistributionand/orbranchpanel .

F EATURES AND BENEF I TS :• Premium200kAsurgecapacityforlongerlifeandhighersingle

impulsewithstand

• IncludesEMI/RFIfilterforcleanerattenuation

• Mountinghubandmountingfeetforinstallationflexibility

• Optionalaudiblealarmandremotedrycontacts

• Upto10ModesofProtection(L-N,L-L,L-g,N-g)

• 10-yearwarranty

RAT INgS :

• Volts (Un):120-600VAC

• Nominal Discharge Current Rating (In):20kA

• Surge Capacity (per phase):100kAor200kA

• Short-Circuit Current Rating (SCCR):200kA

• EMI/RFI Filter:Upto-50dBfrom10kHzto100MHz

APPROVALS :

• ANSI/UL14494thEdition,

Type1SPD,FileE210793

• CSAC22 .2,Type1SPD

• ANSI/IEEEC62 .41 .1,C62 .41 .2,

C62 .45

• UL96ALightningProtection

• RoHSCompliant

Page 15: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N15

Surge ProtectioNSURgE-TRAP® STXTSERIES

GENERAl PRODUCt SPECIFICAtIONS

CAtAlOG NUMBER (INClUDES SUFFIxES*)

SYStEM VOltAGE AND CONFIGURAtION

In MAxIMUM CONtINUOUS OPERAtING VOltAGE (MCOV, Uc)

VOltAGE PROtECtION RAtING (VPR) (Ul 1449, 6kA, 3kV)

l-N l-G l-l N-G* l-N l-G l-l N-G*STXT120P20 120V Single Phase 20kA 150 150 - 150 700 700 - 700

STXT240S20 240/120V Split Phase 20kA 150 150 300 150 700 700 1000 700

STXT480S20 480/240V Split Phase 20kA 320 320 640 150 1200 1200 2000 700

STXT208Y20 208/120V 3-Phase WYE 20kA 150 150 300 150 700 700 1000 700

STXT380Y20 380/220V 3-Phase WYE 20kA 320 320 640 150 1200 1200 2000 700

STXT480Y20 480/277V 3-Phase WYE 20kA 320 320 640 150 1200 1200 2000 700

STXT600Y20 600/347V 3-Phase WYE 20kA 420 420 840 275 1500 1500 2500 1200

STXT240D20 240V 3-Phase DELTA 20kA - 320 640 - - 1200 2000 -

STXT480D20 480V 3-Phase DELTA & HRG WYE 20kA - 550 1100 - - 1800 3000 -

STXT600D10 600V 3-Phase DELTA 20kA - 695 840 - - 2500 2500 -

l-N/Hl-N

l-G/Hl-G

l-l/Hl-l

N-G* l-N/Hl-N

l-G/Hl-G

l-l/Hl-l

N-G*

STXT240H20 240/120V Hi-Leg DELTA 20kA 150/275 150/275 300/425 150 700/1.2k 700/1.2k 1.0k/2000 700

STXT480H20 480/240V Hi-Leg DELTA 20kA 320/550 320/550 640/870 320 1.2k/1.8k 1.2k/1.8k 2.0k/2.5k 1200

*Suffixes: Add Suffix “A” for Audible Alarm and Dry Contact. Example: STXP208Y10A For 100kA Surge Capacity models, substitute “10” for “20.” Example: STXT208Y10

Optional Form C Dry Contact and Audible Alarm (Suffix “A”)

Form C Dry Contact 125VAC, 1A Resistive 30VDC, 2A General Purpose __________________________________________________

COM = Common NO = Normally Open

Audible AlarmAlarm sounds when anyprotection is lost

3/4"-14 Female Mounting Hub

Dimensions and Mounting Configurations

Mounting: Female 3/4" – 14 threaded hub Mounting feet with 0.25" diameter holesWiring: Wire Lugs for 8 AWG copperEnclosure: NEMA 4X Non-metallicFlammability: UL94-5VA

Operating & Storage Temperature: -40°C to +85°CRelative Humidity Range: 0 to 95% non-condensingVisual End-of-Life Indicator: GREEN = OK, OUT = REPLACEFrequency: 50-60Hz

DIMENSIONS IN [ ] ARE MILLIMETERS

7.08

7.40

3.50

6.70

4X .30THRU

3/4 NPSMTHRU

3.68

1.25

REV. DATE ECO DESCRIPTION BY CK APP- 2/29/2016 N/A INITIAL RELEASE JRB N/A N/A

CONTROL No:____________1773

STXT SeriesSurge-Trap® SPD Type 1

3/2/16

C. MCKENZIE

3/2/16

R. LYONS

OUTLINE DIMENSIONSNOT TO BE USED FOR PRODUCTION

SIGN:

DATE:

DESIGN ENGINEERPRODUCT MANAGERSIGN:

DATE:

MERSEN USA NEWBURYPORT-MA, LLC374 MERRIMAC STREETNEWBURYPORT,MA 01950

SHEET 1 OF 1

702104

DIMENSIONS IN [ ] ARE MILLIMETERS

7.08

7.40

3.50

6.70

4X .30THRU

3/4 NPSMTHRU

3.68

1.25

REV. DATE ECO DESCRIPTION BY CK APP- 2/29/2016 N/A INITIAL RELEASE JRB N/A N/A

CONTROL No:____________1773

STXT SeriesSurge-Trap® SPD Type 1

3/2/16

C. MCKENZIE

3/2/16

R. LYONS

OUTLINE DIMENSIONSNOT TO BE USED FOR PRODUCTION

SIGN:

DATE:

DESIGN ENGINEERPRODUCT MANAGERSIGN:

DATE:

MERSEN USA NEWBURYPORT-MA, LLC374 MERRIMAC STREETNEWBURYPORT,MA 01950

SHEET 1 OF 1

702104

DIMENSIONS IN [ ] ARE MILLIMETERS

7.08

7.40

3.50

6.70

4X .30THRU

3/4 NPSMTHRU

3.68

1.25

REV. DATE ECO DESCRIPTION BY CK APP- 2/29/2016 N/A INITIAL RELEASE JRB N/A N/A

CONTROL No:____________1773

STXT SeriesSurge-Trap® SPD Type 1

3/2/16

C. MCKENZIE

3/2/16

R. LYONS

OUTLINE DIMENSIONSNOT TO BE USED FOR PRODUCTION

SIGN:

DATE:

DESIGN ENGINEERPRODUCT MANAGERSIGN:

DATE:

MERSEN USA NEWBURYPORT-MA, LLC374 MERRIMAC STREETNEWBURYPORT,MA 01950

SHEET 1 OF 1

702104

Page 16: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.comN16

NSurge Protective device

NEMADEVICESFORANSI/UL 1449TYPE 1 AND2APPL ICATIONS

SURgE-TRAP® STT SERIES

TheSurge-Trap®STTSeriesmeetsrequirementsforUL14494th

Edition .Itprovidesatwo-yearwarrantyandoffersaneconomical

replacementfortheformersurgearrestorcategory .TheSurge-Trap

Type1SPDfeaturesTPMOV®technologyinsidemakingita“no-fuse”

surgesuppressorthatdoesn’trequiretheuseofadditionalovercurrent

protection .Itcanbeinstalledupstreamordownstreamofthemain

disconnect .

F EATURES AND BENEF I TS :

• DesignedwiththeindustryleadingMersenTPMOV®Technology

• LEDstatusindicatorbyphase(ON=good,Red=Replace)

• OptionforNEMA2orNEMA4Xenclosureforindoororoutdooruse

• NEMA2optionfits1/2"knockoutsforpanelmount

• NEMA4Xsuitableforpanelmountandwallmount

• ForuseinANSI/ULType1or2SPDinstallations

• Upto6modesofProtection(L-N,L-L)

• 2-yearwarranty

RAT INgS :

• Volts (Un):120-600AC

• Nominal discharge current Rating (In):10-20kA

• Surge Capacity:50kAperphase

• Short-Circuit Current Rating (SCCR):200kA

APPROVALS :

• ANSI/UL14494thEdition,

FileE210793

• Type1ListedforUnitedStates

• Type2ListedforCanada

• RoHSCompliant

• ANSI/IEEEC62 .41 .1,C62 .41 .2,

C62 .45

• UL96ALightningProtection

Page 17: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N17

Surge ProtectioNSURgE-TRAP® STT SERIES

GENERAl PRODUCt SPECIFICAtIONS

CATALog No. NEMA 2 ENCLoSURE

CATALog No. NEMA 4X ENCLoSURE

NoMiNAL VoLTAgE (VAC)

SYSTEM TYPE

FREQ (HZ)

MCoV (L-N)

NoMiNAL DiSCHARgE CURRENT (iN, KA)

VoLTAgE PRoTECTioN RATiNg (VPR, VAC) CiRCUiT CoNNECTioN WiRiNg DiAgRAMS

L-N L-g N-g L-L

STT21201PG STT4X1201PG 120 1 50/60 180 20 700 1200 600 - A

STT2240SPG STT4X240SPG 120/240 1S 50/60 180 20 700 - - 1200 B

STT22401PG STT4X2401PG 240 1 50/60 270 20 1000 1500 700 - A

STT22083PYG STT4X2083PYG 120/208 3Y 50/60 180 20 700 - - 1200 D

STT24803PYG STT4X4803PYG 277/480 3Y 50/60 320 10 1200 - - 2000 D

STT26003PYG STT4X6003PYG 347/600 3Y 50/60 420 10 1500 - - 2500 D

STT22403PDG STT4X2403PDG 240 3D 50/60 270 (L-G) 20 - 1000 - 1800 C

STT24803PDG STT4X4803PDG 480 3D 50/60 550 (L-G) 10 - 1800 - 3000 C

DIMENSIONS: STT2

THREE PHASE SINGLE/SPLIT PHASE

DIMENSIONS: STT4X

Wiring: Pre-wired with 16" (0.4m) 12 AWG conductorsFlammability: UL94 V0Operating & Storage Temperature: -40ºC to + 85ºC

Visual End of Life Indicator: GREEN = OK RED = REPLACEFrequency: 50-60 HzResponse Time: <25 ns

3.750

4.7254.050

2.370

3.700

3.7023.002

2.370

3.750

4.7254.050

2.370

3.700

3.7023.002

2.370

4.4500.84

5.710

2.250

4.500

3.6002.43

Page 18: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N18

Surge ProtectioN

Wiring Diagrams: STT2 and STT4X

Single/Split Phase

Wiring Diagrams: STT2 and STT4X

Three Phase Delta & Wye

Installation Diagram: STT2 Installation Diagram: STT4X

SURgE-TRAP® STT SERIES

A B

C D

Note: Must be installed on a solidly grounded system.

D

C

B

AA

B

C

D

12345678

8 7 6 5 4 3 2 1

REV. DESCRIPTION DATE APPROVED

NUT

¾" close nipple

¾" steel conduit locking nut

nut

Page 19: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com N19

N

Surge-Trap®PluggableSurgeProtectiveDevice(SPD)isano-fuse,fail-

safesurgesuppressorfeaturingMersen’spatentedTPMOV®technology

inside .UL14494thEditionapproved,itisDIN-railmountablefeaturing

afail-safeself-protecteddesign,visualindicator,andasmallfootprint .

Aremoteindicatoroptionprovidesstatustocriticalcontrolcircuitry .

TheSurge-TrapPluggableSPDhasahighshortcircuitratinganda

thermallyprotectedMOV,whicheliminatestheneedforadditional

overcurrentprotectiondevices .

F EATURES AND BENEF I TS :

• Easyinstallationorretrofit

• DIN-railmountable

• Fail-safe,self-protecteddesign

• Remoteindicator

• Visualindicator

• IP20finger-safedesign

Surge Protective device

DIN-RAILPLUggABLE SPDFOR ANSI/UL 1449TYPE 1 AND2APPL ICATIONS

SURgE-TRAP® PLUggABLE

• Smallfootprint

• Noadditionalovercurrent

protectiondevicesrequired

• Easytoreplacemodules

• 2-yearwarranty

RAT INgS :

• Volts (Un):120-690VAC

• Nominal Discharge Current Rating (In):10-20kA

• Surge Capacity:50kA

• Short-Circuit Current Rating (SCCR):200kA

APPROVALS :

• ANSI/UL14494thEdition,

Type1ComponentAssembly

SPD,FileE210793

• ANSI/IEEEC62 .41 .1,C62 .41 .2,

C62 .45

• RoHSCompliant

Page 20: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N20

Surge ProtectioN SURgE-TRAP® PLUggABLE

GENERAl PRODUCt SPECIFICAtIONS

1-POlE, SINGlE-PHASE, 2-WIRECATALog NUMBER

NoMiNAL VoLTAgE (VAC)

MAXiMUM CoNTiNUoUS oPERATiNg VoLTAgE (MCoV, VAC) VoLTAgE PRoTECTioN RATiNg (VPR, VAC) REPLACEMENT PLUg in (kA)

L-N L-g N-g L-L L-N L-g N-g L-L L-1

STP1201PGM 120 180 180 - - 600 600 - - SP180U 20STP2301PGM 240 275 275 - - 900 900 - - SP275U 20STP2771PGM 277 320 320 - - 1000 1000 - - SP320U 20STP3471PGM 347 420 420 - - 1500 1500 - - SP420U 10STP6001PGM* 600 650 650 - - 2000 2000 - - SP660U 10*SCCR = 42kA

2-POlE, SPlIt-PHASE, 3-WIRECATALog NUMBER

NoMiNAL VoLTAgE (VAC)

MAXiMUM CoNTiNUoUS oPERATiNg VoLTAgE (MCoV, VAC) VoLTAgE PRoTECTioN RATiNg (VPR, VAC) REPLACEMENT PLUg in (kA)

L-N L-g N-g L-L L-N L-g N-g L-L L1, L2

STP240SPGM 120/240 180 180 - 360 600 600 - 1200 SP180U 20STP480SPGM 240/480 275 275 - 550 900 900 - 1800 SP275U 20

3-POlE, 3-PHASE DEltA, 4-WIRECATALog NUMBER

NoMiNAL VoLTAgE (VAC)

MAXiMUM CoNTiNUoUS oPERATiNg VoLTAgE (MCoV, VAC) VoLTAgE PRoTECTioN RATiNg (VPR, VAC) REPLACEMENT PLUg in (kA)

L-N L-g N-g L-L L-N L-g N-g L-L L1, L2, L3

STP2403PDGM 240 275 275 - 550 900 900 - 1800 SP275U 20STP4803PDGM 480 550 550 - 1100 1800 1800 - 3000 SP550U 10

3-POlE, 3-PHASE WYE, 4-WIRECATALog NUMBER

NoMiNAL VoLTAgE (VAC)

MAXiMUM CoNTiNUoUS oPERATiNg VoLTAgE (MCoV, VAC) VoLTAgE PRoTECTioN RATiNg (VPR, VAC) REPLACEMENT PLUg in (kA)

L-N L-g N-g L-L L-N L-g N-g L-L L1, L2, L3

STP2083PYGM 120/208 180 180 - 360 600 600 - 1200 SP180U 20STP4803PYGM 277/480 320 320 - 640 1000 1000 - 1800 SP320U 20STP6003PYGM 347/600 420 420 - 840 1500 1500 - 2500 SP420U 10STP6903PYGM 400/690 440 440 - 880 1500 1500 - 2500 SP440U 20

4-POlE, 3-PHASE WYE, 5-WIRE, INClUDING N-G MODECATALog NUMBER

NoMiNAL VoLTAgE (VAC)

MAXiMUM CoNTiNUoUS oPERATiNg VoLTAgE (MCoV, VAC) VoLTAgE PRoTECTioN RATiNg (VPR, VAC) REPLACEMENT PLUg in (kA)

L-N L-g N-g L-L L-N L-g N-g L-L L1, L2, L3 N-g

STP2083PYM 120/208 180 180 180 360 600 1200 600 1200 SP180U SP180U 20STP4803PYM 277/480 320 500 180 640 1000 1500 600 1800 SP320U SP180U 20STP6003PYM 347/600 420 695 275 840 1500 2000 600 2500 SP420U SP275U 10STP6903PYM 400/690 440 760 320 880 1500 2000 1000 2500 SP440U SP320U 20

4-POlE, 3-PHASE DEltA HIGH-lEG, 5-WIRE, INClUDING N-G MODECATALog NUMBER

NoMiNAL VoLTAgE (VAC)

MAXiMUM CoNTiNUoUS oPERATiNg VoLTAgE (MCoV, VAC) VoLTAgE PRoTECTioN RATiNg (VPR, VAC) REPLACEMENT PLUg in (kA)

L-N L-g N-g L-L L-N L-g N-g L-L L1, L3 L2 N-g

STP2403PHM 120/240 360 180 455 275 1200 600 1500 900 SP180U SP275U SP180U 20STP4803PHM 240/480 550/455 275/180 825/730 550 1.8k/1.5k 900/600 2.5k/2.0k 1800 SP275U SP550U SP180U 10

Mounting: 35mm DIN-RailWire Range: 6-14AWG Solid / Stranded CUTerminal Torque: 14.75 lbs-inDegree of Protection: IP 20Flammability: UL94 V0

Operating & Storage Temperature: -40ºC to + 85ºCVisual End of Life Indicator: RED = End of LifeRemote End of Life Indicator: NO/NC Dry ContactFrequency: 50-60 Hz

Page 21: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N21

Surge ProtectioNSURgE-TRAP® PLUggABLE

DIMENSIONS - StP SERIESPoLES A

iN MM

1 Pole 0.71 18.03

2 Pole 1.42 36.06

3 Pole 2.13 54.1

4 Pole 2.84 72.13

DIMENSIONS - St SERIES

PoLES A

iN MM

1 Pole 0.7 17.8

2 Pole 1.39 35.5

3 Pole 2.1 53.3

4 Pole 2.8 71

WIRING DIAGRAMS

1-POLE, SINGLE-PHASE, 2-WIRE

2-POLE, SPLIT-PHASE, 3-WIRE

3-POLE, 3-PHASE DELTA, 3-WIRE

3-POLE, 3-PHASE DELTA, 3-PHASE WYE, 4-WIRE

4-POLE, 3-PHASE WYE,5-WIRE

4-POLE, 3-PHASE DELTA HIGH-LEG, 5-WIRE

SINGLE PHASE 2 WIRE + GROUND

SPLIT PHASE3 WIRE + GROUND

3 PHASE DELTA3 WIRE + GROUND

3 PHASE WYE4 WIRE + GROUND

REMOtE StAtUS INDICAtOR

Signal Wire Range #16 to #30 AWG

Terminal Torque 2.2 lb-in

Cont. between Comm + NO Product Offline, Not Protected

Cont. between Comm + NC Product Online, Protected

ST AND STP SERiES: FOR REMOTE INDICATION, ADD “M” TO THE END OF THE CATALOG NUMBER. FOR EXAMPLE, ST4803PYGM.

NO 1

Common 2

NC

Subminiature Switch

125 VAC-3A max

G/N

L2

G/NG/N

G

L2 High Leg

G

L3 L1 L2

B B B

Page 22: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.comN22

NSurge Protective device

DIN-RAILMODULAR SPDFOR ANSI/UL 1449TYPE 1 AND2APPL ICATIONS

SURgE-TRAP® MODULAR

Surge-Trap®ModularSurgeProtectiveDevice(SPD)isano-fuse,fail-

safesurgesuppressorfeaturingMersen’spatentedTPMOV®technology

inside .UL14494thEditionapproved,itisDIN-railmountablefeaturing

afail-safeself-protecteddesign,visualindicator,andasmallfootprint .

Aremoteindicatoroptionprovidesstatustocriticalcontrolcircuitry .

TheSurge-TrapModularSPDhasahighshortcircuitratinganda

thermallyprotectedMOV,whicheliminatestheneedforadditional

overcurrentprotectiondevices .

F EATURES AND BENEF I TS :

• Easyinstallationorretrofit

• DIN-railmountable

• Fail-safe,self-protecteddesign

• Remoteindicator(optional)

• Visualindicator

• IP20finger-safedesign

• Smallfootprint

• Noadditionalovercurrent

protectiondevicesrequired

• 2-yearwarranty

RAT INgS :

• Volts (Un):120-690VAC

• Nominal Discharge Current Rating (In):20kA

• Surge Capacity (per phase and per mode):50kA

• Short-Circuit Current Rating (SCCR):200kA

APPROVALS :

• ANSI/UL14494thEdition,

Type1ComponentAssembly

SPD,FileE210793

• ANSI/IEEEC62 .41 .1,C62 .41 .2,

C62 .45

• RoHSCompliant

Page 23: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N23

Surge ProtectioNSURgE-TRAP® MODULAR

GENERAl PRODUCt SPECIFICAtIONS

1-POlE, SINGlE-PHASE, 2-WIRECATALog NUMBER

NoMiNAL VoLTAgE (VAC)

MAXiMUM CoNTiNUoUS oPERATiNg VoLTAgE (MCoV, VAC) VoLTAgE PRoTECTioN RATiNg (VPR, VAC) in (kA)

L-N L-g N-g L-L L-N L-g N-g L-L

ST1201PG(M) 120 180 180 - - 500 500 - - 20ST2301PG(M) 240 270 270 - - 800 800 - - 20ST2771PG(M) 277 320 320 - - 900 900 - - 20

2-POlE, SPlIt-PHASE, 3-WIRECATALog NUMBER

NoMiNAL VoLTAgE (VAC)

MAXiMUM CoNTiNUoUS oPERATiNg VoLTAgE (MCoV, VAC) VoLTAgE PRoTECTioN RATiNg (VPR, VAC) in (kA)

L-N L-g N-g L-L L-N L-g N-g L-L

ST208SPG(M) 120/208 180 180 - 360 500 500 - 900 20ST240SPG(M) 120/240 180 180 - 360 500 500 - 900 20ST480SPG(M) 240/480 270 270 - 540 800 800 - 1500 20

3-POlE, 3-PHASE DEltA, 3-WIRECATALog NUMBER

NoMiNAL VoLTAgE (VAC)

MAXiMUM CoNTiNUoUS oPERATiNg VoLTAgE (MCoV, VAC) VoLTAgE PRoTECTioN RATiNg (VPR, VAC) in (kA)

L-N L-g N-g L-L L-N L-g N-g L-L

ST2403PD(M) 240 - - - 270 - - - 1000 20ST4803PD(M) 480 - - - 550 - - - 3000 20

3-POlE, 3-PHASE DEltA, 4-WIRECATALog NUMBER

NoMiNAL VoLTAgE (VAC)

MAXiMUM CoNTiNUoUS oPERATiNg VoLTAgE (MCoV, VAC) VoLTAgE PRoTECTioN RATiNg (VPR, VAC) in (kA)

L-N L-g N-g L-L L-N L-g N-g L-L

ST2403PDG(M) 240 270 270 - 540 800 800 - 1500 20ST4803PDG(M) 480 550 550 - 1100 1500 1500 - 3000 20

3-POlE, 3-PHASE WYE, 4-WIRECATALog NUMBER

NoMiNAL VoLTAgE (VAC)

MAXiMUM CoNTiNUoUS oPERATiNg VoLTAgE (MCoV, VAC) VoLTAgE PRoTECTioN RATiNg (VPR, VAC) in (kA)

L-N L-g N-g L-L L-N L-g N-g L-L

ST2083PYG(M) 120/208 180 180 - 360 500 500 - 900 20ST4803PYG(M) 277/480 320 320 - 640 900 900 - 1800 20ST6003PYG(M) 347/600 420 420 - 840 1200 1200 - 2000 20ST6903PYG(M) 400/690 510 510 - 1020 1500 1500 - 3000 20

4-POlE, 3-PHASE WYE, 5-WIRE, INClUDING N-G MODECATALog NUMBER

NoMiNAL VoLTAgE (VAC)

MAXiMUM CoNTiNUoUS oPERATiNg VoLTAgE (MCoV, VAC) VoLTAgE PRoTECTioN RATiNg (VPR, VAC) in (kA)

L-N L-g N-g L-L L-N L-g N-g L-L

ST2083PY(M) 120/208 180 360 180 360 500 900 500 900 20ST4803PY(M) 277/480 320 470 150 640 1000 1500 500 1800 20ST6003PY(M) 347/600 420 690 270 840 1500 2500 800 2500 20ST6903PY(M) 400/690 1020 510 510 1020 3000 1500 1500 3000 20FOR REMOTE INDICTATION, ADD “M” TO THE END OF THE PART NUMBER. EXAMPLE, ST4803PYM. OMIT “M” TO ORDER WITHOUT REMOTE INDICATION. EXAMPLE, ST4803PY.

Mounting: 35mm DIN-RailWire Range: 6-14AWG Solid / Stranded CUTerminal Torque: 14.75 lbs-inDegree of Protection: IP 20Flammability: UL94 V0

Operating & Storage Temperature: -40ºC to + 85ºCVisual End of Life Indicator: Visual TabRemote End of Life Indicator: NO/NC Dry ContactFrequency: 50-60 HzResponse Time: <25 ns

Page 24: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N24

Surge ProtectioN SURgE-TRAP® MODULAR

DIMENSIONS - StP SERIESPoLES A

iN MM

1 Pole 0.71 18.03

2 Pole 1.42 36.06

3 Pole 2.13 54.1

4 Pole 2.84 72.13

DIMENSIONS - St SERIES

PoLES A

iN MM

1 Pole 0.7 17.8

2 Pole 1.39 35.5

3 Pole 2.1 53.3

4 Pole 2.8 71

WIRING DIAGRAMS

1-POLE, SINGLE-PHASE, 2-WIRE

2-POLE, SPLIT-PHASE, 3-WIRE

3-POLE, 3-PHASE DELTA, 3-WIRE

3-POLE, 3-PHASE DELTA, 3-PHASE WYE, 4-WIRE

4-POLE, 3-PHASE WYE,5-WIRE

4-POLE, 3-PHASE DELTA HIGH-LEG, 5-WIRE

SINGLE PHASE 2 WIRE + GROUND

SPLIT PHASE3 WIRE + GROUND

3 PHASE DELTA3 WIRE + GROUND

3 PHASE WYE4 WIRE + GROUND

REMOtE StAtUS INDICAtOR

Signal Wire Range #16 to #30 AWG

Terminal Torque 2.2 lb-in

Cont. between Comm + NO Product Offline, Not Protected

Cont. between Comm + NC Product Online, Protected

ST AND STP SERiES: FOR REMOTE INDICATION, ADD “M” TO THE END OF THE CATALOG NUMBER. FOR EXAMPLE, ST4803PYGM.

NO 1

Common 2

NC

Subminiature Switch

125 VAC-3A max

G/N

L2

G/NG/N

G

L2 High Leg

G

L3 L1 L2

B B B

Page 25: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com N25

NSurge Protective device

DIN-RAILPLUggABLESPDFORPHOTOVOLTAICAPPL ICATIONS

SURgE-TRAP®STPT2-PV SERIES FOR PHOTOVOLTAIC

STPT240PVistheseriesofdevices

thatprovideadvancedovervoltage

protectiontophotovoltaicsystemsby

utilizingMersen’soptimizeddynamic

thermaldisconnectionsystem,which

doesnotrequire additionalovercurrent

protection(back-upfuse)duetoits

highshort-circuitwithstandrating .

Thesesurgeprotectivedevicesare

suitablefor all PV applications:large-

scale,rooftop,andself-consumption

(off-grid)DCinstallations .

REFERENCE NUMBER

CAtAlOG NUMBER

UCPV [VDC]

Up@In (8/20) [kV]

In (8/20) [kA]

SCCR [kA]

CARtRIDGE ID (l)

83020138 STPT2-40K600V-YPV 660 ≤2.6 20 100 C40

83020139 STPT2-40K600V-YPVM 660 ≤2.6 20 100 C40

83020140 STPT2-40K1000V-YPV 1060 ≤4 20 50 C41

83020141 STPT2-40K1000V-YPVM 1060 ≤4 20 50 C41

83020158 STPT2-40K1500V-YPV 1500 ≤5 10 65 C42

83020159 STPT2-40K1500V-YPVM 1500 ≤5 10 65 C42

DIMENSIONS ElECtRICAl DIAGRAM MICROSWItCH DIAGRAM

RAT INgS :

• Volts (Ucpv):600-1500VDC

• Nominal Discharge Current Rating (In):10-20kA

• Surge Capacity (per phase and per mode):40kA

• Short-Circuit Current Rating (SCCR):50-100kA

APPROVALS :

• ANSI/UL14494thEdition,

Type2ComponentAssembly,

File E468946

• EN50539-11

• UTEC61740-51

rePlacemeNt cartridgeSNetwork ucPv

[vdc]

imax (8/20) [ka]

in(8/20)

@uP [ka]

up@in (8/20)[kv]

cartridge id.reF. No. catalog No.

83020005 SP2-40K600V-PV PV 330 40 20 ≤1.3 C40

83020006 SP2-40K1000V-PV PV 530 40 20 ≤2 C41

83020010 SP2-40K1500V-PV PV 750 40 10 ≤2,5 C42

Page 26: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.comN26

N

eP.merSeN.com

Surge Protective device

DIN-RAILMODULARSPDFOR IECTYPE2 + 3APPL ICATIONS

SURgE-TRAP®STMT23 SL IMSERIES

STMT2320SistheseriesofcombinedType

2+3/ClassII+IIIdevicesfordischargingvoltage

surgeswhileprovidingaveryfinevoltage

protectionlevel,inaccordancewithIEC/EN

61643-11 .

Suitableasthefinalstageofprotectionin

panelswithType2protectiondevicesinstalled

upstream .TheseSPDsshouldbeinstalled

ascloseaspossibletotheequipmentbeing

protected .Idealforlimitedspaces .Widerange

ofvoltageratings .

reF. Number

catalog Number without/with remote moNit.

un [vac]

uc [v]

up@in (8/20)[kv]

imax (8/20) [ka]

i (8/20) [ka]

83230500 83230501

STMT23-6K20V-SP-SSTMT23-6K20V-SP-SM 12 20 ≤0.22 (L1-L2) 0.7 (L1/L2-PE) 6 3

83230504 83230505

STMT23-6K30V-SP-SSTMT23-6K30V-SP-SM 24 30 ≤0.22 (L1-L2) 0.7 (L1/L2-PE) 6 3

83230506 83230507

STMT23-6K60V-SP-SSTMT23-6K60V-SP-SM 48 60 ≤0.33 (L1-L2) 0.7 (L1/L2-PE) 6 3

83230508 83230509

STMT23-6K75V-SP-SSTMT23-6K75V-SP-SM 60 75 ≤0.5 (L1-L2) 0.9 (L1/L2-PE) 6 3

83230502 83230503

STMT23-6K150V-SP-S STMT23-6K150V-SP-SM 120 150 ≤0.7 (L1-L2) 0.9 (L1/L2-PE) 6 3

83230510 83230511

STMT23-20K275V-SP-SSTMT23-20K275V-SP-SM 230 275 ≤1.4 (L1-L2) 1.4 (L1/L2-PE) 20 10

DIMENSIONS ElECtRICAl DIAGRAM MICROSWItCH DIAGRAM

RAT INgS :

• Volts (Un):12-230VAC

• Nominal Discharge Current Rating (In):3-10kA

• Surge Capacity (per phase and per mode):6-20kA

• Short-Circuit Current Rating (SCCR):10kA

APPROVALS :

• IEC/EN61643-11

Page 27: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com N27

NSurge Protective device

DIN-RAILMODULARSPDFOR IECTYPE2 + 3APPL ICATIONS

SURgE-TRAP®STET23 SERIES

reFereNce Number

catalogNumber

un [vac]

uc [v]

up@in [kv]

in (8/20) [ka] il [a] remote

(m)

83230401 STET23-20K150V-SPM 120 150 ≤0.8 10 20 √

83230403 STET23-20K275V-SPM 230 275 ≤1.2 10 20 √

DIMENSIONS ElECtRICAl DIAGRAM MICROSWItCH DIAGRAM

STET2320istheseriesofcombinedType2+3/ClassII+III

devicesfordischargingvoltagesurgeswhile providingavery

finevoltageprotectionlevel,in accordancewithIEC/EN61643-11 .

Complete with a built-inpowerfulEMIfilter .Suitableasthefinal

stageofprotectionininstallationswithelectromagneticdisturbances

whichmightinterrupt,degrade,orlimitsystemperformance .Series

connectionforapplicationsupto20Arated current .

RAT INgS :

• Volts (Un):120-230VAC

• Nominal Discharge Current Rating (In):10kA

• Surge Capacity (per phase and per mode):20kA

• load Current Rating (Il):20A

• EMI Filter:Upto82dB

APPROVALS :

• IEC/EN61643-11

Page 28: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.comN28

NSurge Protective device

IN-L INESPD FORLEDL IgHTINgAPPL ICATIONS

SURgE-TRAP® STLBSERIES

Mersen’sSPDforLEDlightingapplications,theSTLBseriesisa

universalsolutionwithenhancedsafetydeliveringpeace-of-mind

tousersandinstallers .Asingledeviceissuitableforsingle,split,or

three-phaseapplications;canbeinstalledinseriesorparallelwiththe

luminaire;featuresleakagecurrentfreetechnologyandvisualend-of-

lifeindication .ItisalsoULRecognized(cURus)andIECcertified .

FEATURES AND BENEF I TS :• Universal,certifiedSPDswhichcanbesafelyusedinanyluminaire

andanyinstallation• Commonapplications:RoadwayLighting,ParkingLot/garage

Lighting,indoor/outdoorLEDsignage,industrialmanufacturingfacilities,allcritical24/7applications

• Parallelorseriesconnecteddevice• End-of-lifeindicationviaLEDorseriesdisconnection• LeakageCurrentFree• globalCompliancetoANSI/UL/CSAandIEC• Versatilemountingdesignaccomodatesverticalorhorizontal

mounting• 2-yearwarranty

RAT INgS :

• Volts (Un):100-277VAC

• Nominal Discharge Current Rating (In):3kA

• Surge Capacity:10kA

• Short-Circuit Current Rating (SCCR):10kA

• load Current Rating (Il):2 .5A

• IEEE C62.41.2 location Category:C-High10kV/10kA

APPROVALS :

• ANSI/UL14494thEdition,Type

4SPD,FileE468946

• EN61643-11Type2+3SPD

• RoHSCompliant

Page 29: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N29

Surge ProtectioNSURgE-TRAP® STLBSERIES

geNeral Product SPeciFicatioNS

reFereNce Number

catalog Number SyStem voltage aNd coNFiguratioN

in maximum coNtiNuouS oPeratiNg voltage (mcov, uc)

meaSured limitiNg voltageS (mlv)

l-g l-l l-g l-l

83230320 STLBT23-10K320V-C3U-DD 120V Single Phase240V Single Phase240/120V Split Phase208Y/120V 3-Ph WYE480Y/277V 3-Ph WYE240V 3-Ph DELTA

3kA 320 320 1020 1340

Dimensions Wiring Diagram: Series

Wiring Diagram: ParallelElectrical Diagram

Mounting: 5.5mm Diameter Mounting HoleWiring: Screw Terminals (0.7 Nm)Wire Range: 14-18 AWG Solid/Stranded CuConnection: Series or ParallelEnclosure: IP20Flammability: UL94-V0

Operating & Storage Temperature: -40°C to +85°CRelative Humidity Range: 5 to 95% Visual End-of-Life Indicator: GREEN = OK, OUT = REPLACEFrequency: 50-60HzMaximum Back-up Fuse: Mersen AJT25Response Time (L-L, L-G): 25ns, 100ns

Page 30: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.comN30

N

Mersen’spatentedTPMOV®technologyeliminatescommonfailure

modesthatoccurinthefieldwithstandardmetaloxidevaristors .

InternallytheTPMOViscomprisedofavoltageclampingdevice

andadisconnectingapparatusthatmonitorsthestatusofthemetal

oxidedisk,makingtheTPMOVafail-safedevice .Intheeventofan

overvoltagebreakdown,themetaloxidediskissecurelydisconnected

fromthesystempowerbyanarcshield .Uponfailure,theTPMOVis

alsoequippedwithavisualpinindicatoraswellasanormallyopen

micro-switch,providingremoteindicationifapplicable .

F EATURES AND BENEF I TS :

• Highenergycapacity

• Consistentfootprintwith25–40mmMOVs

• Built-invisual/remoteindication

• Wavesolderable

• Noadditionalovercurrentprotectiondevice(fuses)required

Surge Protective device

COMPONENTSPDFOROEMDESIgNANDBUILD

TPMOV® TECHNOLOgY

RAT INgS :

• Volts (Un):150-550VAC

• Nominal Discharge Current Rating (In):20kA

• Surge Capacity:50kA

• Short-Circuit Current Rating (SCCR):200kA

APPROVALS :

• ANSI/UL14494thEdition,

Type1ComponentAssembly

SPD,FileE210793

• RoHSCompliant

Page 31: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N31

Surge ProtectioN

CAtAlOG NUMBER (INClUDES SUFFIxES*)

MAxIMUM CONtINUOUS OPERAtING VOltAGE (MCOV, VAC)

VOltAGE PROtECtION RAtING (VPR)

NOMINAl DISCHARGE CURRENt (kA)

OPERAtING tEMPERAtURE

DIMENSION A (INCHES)

150TPMOV 150 700 20 -40°C to +85°C 0.485

180TPMOV 180 800 20 -40°C to +85°C 0.485

270TPMOV 275 800 20 -40°C to +85°C 0.495

320TPMOV 320 1000 20 -40°C to +85°C 0.51

420TPMOV 420 1500 20 -40°C to +85°C 0.54

510TPMOV 510 1500 20 -40°C to +85°C 0.54

550TPMOV 550 1500 20 -40°C to +85°C 0.545

CAtAlOG - ORDERING SYStEM

150Maximum Continuous

operating Voltage(MCoV)

150: 150VAC180: 180VAC270: 275VAC320: 320VAC420: 420VAC510: 510VAC550: 550VAC

TPMoVModel Series

TPMoV: Thermally Protected MOV

SLMechanical options

* For details regarding HV microswitch please consult factory

Dimensional Drawing of TPMOV Board Layout Dimensions

VOLTAGE A DiMENSioN

550 0.545

420/510 0.54

320 0.51

270 0.495

150/180 0.485

.407

1.375

.146

A.627

1.687

2X .325

2X .037

.231.197

2X Ø .039

.844

SWITCH LEADS

CONTACT LEAD

MOV LEAD

SCALE: 2:1TOLERANCES: ± .005

.407

1.375

.146

A.627

1.687

2X .325

2X .037

.231.197

2X Ø .039

.844

SWITCH LEADS

CONTACT LEAD

MOV LEAD

SCALE: 2:1TOLERANCES: ± .005

Suffix PCB Leads Tact Switch Visual Tabs Pkg Qty

Blank No Yes Yes 10

S Yes Yes No 10

SL Yes Yes No 500

ST Yes Yes Yes 10

SLT Yes Yes Yes 500

HV No Yes-HV Yes 10

S-HV Yes Yes-HV Yes 10

SL-HV Yes Yes-HV Yes 500

TPMOV® TECHNOLOgY

Page 32: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.comN32

NSurge Protective device

COMPONENTDEVICEFOR OEMDESIgN ANDBUILD

VSPMOVPROTECTORFUSE

RAT INgS :

• Volts:600VAC

• Surge Rating:5-100kA8/20μSec

• Interrupting Rating (IR):200kA

APPROVALS :

• ANSI/UL248SpecialPurpose

MOVFuse,FileE60314Mersensurgesuppressionfusesarespeciallydesignedtoaddress

theprotectionofSPDsystems .Oursurgesuppressionfuseshave

beenspeciallydesignedtowithstand8/20μSecsurgepulseswithout

opening,allowingtheSPDsystemtoreacttothesurge .Allsurge

suppressionfuseshavea8/20μSecsurgerating,notacontinuous

currentrating .UnderACshortcircuitconditionsthesesurge

suppressionfusesareverycurrentlimiting .

F EATURES AND BENEF I TS :

• VSPfusesrated600VAC,200kAI .R .

• Surgeratingsof5-100kA8/20μSeccapacity

• Variousmountingconfigurationsferrules,blade,bolt-in,pcboard

mount

Page 33: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N33

Surge ProtectioN

PRODUCt PERFORMANCE DAtA VSP (5-20)-2,R,H,S

CATALog No. (CoNNECTioN SUFFiX)

VoLTAgE RATiNg (AC)

8X20 µSEC SURgE RATiNg

MELTiNg i2T (A2S)

CLEARiNg i2T (A2S)

iPEAK@ 100KA 60 HZ (A)

VSP5-2,-R,-H,-S 600V 5,000 341 936 3,652

VSP10-2,-R,-H,-S 600V 10,000 1,541 3,744 5,794

VSP15-2,-R,-H,-S 600V 15,000 3,072 8,424 7,591

VSP20-2,-R,-H,-S 600V 20,000 4,992 14,400 9,194

VSP30, -2 600V 30,000 12,507 33,696 12,044

VSP40, -2 600V 40,000 19,543 59,904 14,588 VSP (30-100)-2

VSP50, -2 600V 50,000 32,020 93,600 16,925

VSP60, -2 600V 60,000 42,808 134,784 19,110

VSP70, -2 600V 70,000 61,152 183,456 21,176

VSP80, -2 600V 80,000 79,872 239,616 23,146

VSP90, -2 600V 90,000 99,000 303,264 25,034

VSP100, -2 480V 100,000 121,500 374,400 26,854

VSP100-XL 600V 100,000 121,500 374,400 26,854

RECOMMENDED FUSE BlOCkS FOR VSP FUSES VSP30-100

VSP(5-20)-2

NUMBER oF PoLES SCREW WiTH DoUBLE QUiCK CoNNECTS

PRESSURE PLATE WiTH DoUBLE QUiCK CoNNECTS

CoPPER BoX CoNNECToR

ADDER 30310 30320 30350

1 30311 30321 30351

2 30312 30322 30352

3 30313 30323 30353 VSP100-XL

VSP(30-100)-2

NUMBER oF PoLES CATALog NUMBER

ADDER 60305J 60315J 60325J

1 60306J 60316J 60326J

2 60307J 60317J 60327J

3 60308J 60318J 60328J

MOUNtING OPtIONS

DOUBLE HOLE MOUNT (ROUND HOLES)

-H

PC BOARD MOUNTING

-R

SURFACE SCREW MOUNT

-S

VSPMOVPROTECTORFUSE

Page 34: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.comN34

NSurge Protective device

COMPONENTDEVICEFOR OEMDESIgN ANDBUILD

SURgE-RATEDDISCONNECTSWITCH

TheSurgeSwitchisanextremelycompact,highperformance,

manuallyoperated,non-fusedswitch .Itisspecificallydesignedto

withstandthehighsurgecurrentof200kAwithan8x20µswaveform

seenintoday’stransientvoltagesurgeprotectiondevice(SPD)

applications .Mersen’sSurgeSwitchutilizesauniquecontactdesign

thatactuallyclampcontactstighterduringasurge .

F EATURES AND BENEF I TS :

• Onlysurgeratedswitchavailabletoday

• Compactfootprint

• Extremelyreliable

• Defeatablepistolhandlesautomaticallyrelatchwhenpaneldooris

closed,notoolnecessarytoresetlatch

• Directmounthandleoption

RAT INgS :

• Volts:600VAC

• Amps:600A

• Surge Rating:200kA8x20µswaveform

APPROVALS :

• ULListedguideNRNT,File

E224922

Page 35: N Surge Protection - Gescan Surge Protection Fail-S aFe overvoltage ... (per phase): 100, 150, 200, 300, 450kA ... *Part Number Selector

eP.merSeN.com

N

N35

Surge ProtectioNSURgE-RATEDDISCONNECTSWITCH

CAtAlOG NUMBER DESCRIPtION

SS200 3-pole, surge switch, 200kA 8x20 µs

SS200-4 4-pole, surge switch, 200kA 8x20 µs

HADSS200 Direct mount black handle

HGPB External black handle, NEMA 1,3R, 12 (IEC IP 54), defeatable

HGPR External red handle, NEMA 1,3R,12 (IEC IP 54), defeatable

HGPB4 External black handle, NEMA 1,3R,124,4X (IEC IP 65), defeatable

HGPR4 External red handle, NEMA 1,3R,12,4,4X (IEC IP 65), defeatable

SG200-10 Shaft, 7.9 in (200 mm)

SG320-10 Shaft, 12.6 in (320 mm)

SG400-10 Shaft, 15.7 in (400 mm)

TS200SS Terminal Shield, 3-pole

TS2004SS Terminal Shield, 4-pole

DIMENSIONS (dual dimensions: in/mm) SS200 DIMENSIONS (dual dimensions: in/mm) SS200-4

DIMENSIONS: HADSS200 DIMENSIONS: PISTOL HANDLE TYPE G

HGPB

HGPR

HGPB4

HGPR4

DIMENSIONS: PISTOL HANDLE TYPE G

SS200/SS200-4

SHAFT LENgTH H MiNiMUM DiMENSioN H MAXiMUM DiMENSioN

iN MM iN MM iN MM

7.9 200 4.88 124 9.29 236

12.6 320 4.88 124 14.01 356

15.7 400 4.88 124 17.16 436

O - OFF

I - ON

90°

3.15 80

652.56

0.6717

4.73120

2.8773

2.78

70.5

2.7570

50

90°

o2"502"

ø 3111 4"

4 ø 4.51 8"

-ON

-OFF

DOOR DRILLING