Modulex3 Line MX3IPG2ANumerical integrated generator protection(Rotor and auxiliary protection): 64R - 27 d.c. - 59 d.c.
0
Protection functions• Rotor earth fault detection based on
injection of a.c. low voltage(accessory X2/IPG2A) between therotor winding of the protectedsynchronous machine and ground.
• Two independent time thresholdsmeasuring the resistance of the earthfault (R
8/19/2019 Mx3ipg2a en Td
2/2
13
Characteristics• Generator rated excitation voltage
1000 V d.c.
• Excitation circuit to groundcapacitance 5µF
• Injected voltage (X2/IPG2A)40 V
• Rated frequency fn50/60 Hz
• R< 200 to 4000ΩIndependent time
0.05 to 600 s
• R 10 to 100 mAIndependent time
0.05 to 600 s
• D.C. voltage measurement rangesselectable by internal bridges.
• Input resistance
• U-< 0.5 to 1.2 UnIndependent time
0.02 to 600 s
• U- 0.5 to 1.2 UnIndependent time
0.02 to 600 s
• U->> 0.5 to 1.2 UnIndependent time
0.02 to 600 s
• Auxiliary supply of MX3IPG2A
Uaux: 19 to 100 Vd.c.or: 19 to 72 Va.c.
Uaux: 64 to 300 Vd.c.or: 64 to 275 Va.c.
Burden: 5 W / 10 W d.c.
10VA / 20VA a.c.
• Auxiliary supply of X2/IPG2A
Uaux: 24 to 240 Va.c.
Frequency: 45 to 65 Hz
Burden: