    Modulex3 Line MX3IPG2ANumerical integrated generator protection(Rotor and auxiliary protection): 64R - 27 d.c. - 59 d.c.

    0

    Protection functions• Rotor earth fault detection based on

    injection of a.c. low voltage(accessory X2/IPG2A) between therotor winding of the protectedsynchronous machine and ground.

    • Two independent time thresholdsmeasuring the resistance of the earthfault (R

  • 8/19/2019 Mx3ipg2a en Td

    2/2

    13

    Characteristics• Generator rated excitation voltage

    1000 V d.c.

    • Excitation circuit to groundcapacitance 5µF

    • Injected voltage (X2/IPG2A)40 V

    • Rated frequency fn50/60 Hz

    • R< 200 to 4000ΩIndependent time

    0.05 to 600 s

    • R 10 to 100 mAIndependent time

    0.05 to 600 s

    • D.C. voltage measurement rangesselectable by internal bridges.

    • Input resistance

    • U-< 0.5 to 1.2 UnIndependent time

    0.02 to 600 s

    • U- 0.5 to 1.2 UnIndependent time

    0.02 to 600 s

    • U->> 0.5 to 1.2 UnIndependent time

    0.02 to 600 s

    • Auxiliary supply of MX3IPG2A

    Uaux: 19 to 100 Vd.c.or: 19 to 72 Va.c.

    Uaux: 64 to 300 Vd.c.or: 64 to 275 Va.c.

    Burden: 5 W / 10 W d.c.

    10VA / 20VA a.c.

    • Auxiliary supply of X2/IPG2A

    Uaux: 24 to 240 Va.c.

    Frequency: 45 to 65 Hz

    Burden: