— ABB MEASUREMENT & ANALYTICS | DATA SHEET
266CSH / CST Multivariable pressure transmitter with Modbus® communication
2 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A
— Measurement made easy Pressure transmitters – 2600T series. Technical solutions for any application
— Base accuracy • 0.075 % of calibrated span (266CSH) • 0.04 % of calibrated span (266CST)
— 266CSH/CST mass flow measurement with compensation, level measurement with compensation for gases, steam, and liquids • Dynamic compensation of pressure and temperature
changes
— Proven sensor technology together with state-of-the-art digital technology • Large turn down ratio of up to 100:1
— Flexible configuration options • Local configuration via buttons on LCD indicator • TTG (Through-The-Glass) keypad technology
— 10-year stability • 0.15 % of URL
— Comprehensive range of functions • Integrated counting function
266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 3
Change from one to two columns
— Introduction
266CSH / 266CST
Thanks to their multisensor technology, these transmitters are capable of measuring three separate process variables at the same time and offer the option of calculating the following values:
• Mass flow for gases, steam, and liquids by means of dynamic compensation
• Standard volume flow for gases by means of dynamic compensation
• Heat flow for water and steam • Drum water level and level measurement with density
compensation of liquids The differential pressure and absolute pressure are measured by two integrated sensors. The process temperature is measured by an external standard Pt100 resistance thermometer. Flow calculation The flow calculation carried out by these transmitters includes compensation of pressure and / or temperature as well as more complex variables such as discharge coefficient, thermal expansion, Reynolds number, and compressibility factor. The 266CXX pressure transmitters include flow equations for superheated steam, saturated steam, gases, and liquids - so you only need one device for your system. Multivariable transmitters represent a more economical solution than the designs that have been used for this type of measuring point up to now, in which three different transmitters for differential pressure, absolute pressure, and temperature report their values to a DCS, PLC, or flow computer.
M10143
dp
p
T
Qm
Qv
T
Flo
w
Flo
w
FDP
P
Past Present
Figure 1: Flow measurement - past and present
The dynamic mass flow of the 266CXX is calculated using the following equation:
dpρdεβ1
CQm 1
2
4
Qm Mass flow C Discharge coefficient
Diameter ratio Gas expansion factor
d Inside diameter of the differential flow sensor dp Differential pressure
Density The flow calculation process is based on the following standards:
• AGA 3 • DIN EN ISO 5167
4 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A
— … Introduction Flow coefficient The discharge coefficient is defined as the actual flow divided by the theoretical flow. It corrects the theoretical equation for the effect on the velocity profile (Reynolds number), assuming that no energy is lost between the pressure taps and pressure tap location. It is dependent on the differential flow sensor, the diameter ratio, and the Reynolds number. Compensation for the discharge coefficient ensures a high level of measuring accuracy for flow measurement with primary elements. Gas expansion factor The gas expansion factor corrects for density differences between pressure taps due to expansion of compressible media. It does not apply to liquids which are essentially non-compressible. The gas expansion factor is dependent on the diameter ratio, the isentropic exponent, the differential pressure, and the static pressure of the medium. Diameter ratio The diameter ratio is dependent on the inside diameter of the differential flow sensor and the pipe diameter, which in turn are subject to temperature functions. If the temperature of the medium being measured changes, the material of the process pipe and differential flow sensor expands or contracts. The thermal expansion coefficients are dependent on the material of the pipe and differential flow sensor, and are used for calculating the change in diameters. This ensures a high level of flow accuracy in applications with low and high temperatures.
Medium density The medium density has a direct effect on the flow calculation. The 266CXX pressure transmitters compensate for the medium density resulting from changes in temperature and / or pressure as follows:
• Gases as a function of p and T based on gas laws, taking compressibility factors into account; for natural gas, based on AGA 8 or SGERG
• Superheated steam as a function of p and T based on steam tables
• Saturated steam as a function of p based on steam tables
• Liquids as a function of T Mass flow calculations With the 266CXX pressure transmitters, mass flow calculations can be configured for the following differential flow sensors:
• Orifice corner pressure taps, ISO • Orifice flange pressure taps, ISO • Orifice D and D/2 pressure taps, ISO • Orifice corner pressure taps, ASME • Orifice flange pressure taps, ASME • Orifice D and D/2 pressure taps, ASME • Orifice flange pressure taps, AGA 3 • Orifice 2.5D and 8D pressure taps • Small bore orifice, flange pressure taps • Small bore orifice, corner pressure taps • ISA 1932 nozzle • Long radius nozzle wall pressure taps, ISO • Long radius nozzle wall pressure taps, ASME • Standard Venturi pipe, rough-cast inlet, ISO • Standard Venturi pipe, machined inlet, ISO • Standard Venturi pipe, welded inlet, ISO • Standard Venturi pipe, rough-cast inlet, ASME • Standard Venturi pipe, machined inlet, ASME • Standard Venturi pipe, welded inlet, ASME • Venturi, nozzle, ISO • Pitot tube • Wedge element • Plus all non-standard flow sensors
266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 5
ABB offers a complete range of differential flow sensors. We provide the full testing and documentation that your application needs. Whether the requirement is a single orifice plate with a simple Certificate of Conformity or a project requiring full material inspection, traceability, third-party verification, calibration and comprehensive data dossiers – ABB can satisfy all of the requirements. In addition compact solutions are available, OriMaster, a compact orifice flowmeter, and PitoMaster, a compact pitot flowmeter. Level measurement The following functions are available for level measurement with pressure and temperature compensation:
• Level measurement with temperature compensation, on open tank
• Level measurement with pressure and temperature compensation, on closed tank, with and without diaphragm seal
• Fill volume measurement by means of tank shape specification
• Drum water level measurement All of the functionality, including all the data required for compensated mass flow or for level measurement, is configured entirely using the PC-based DTM 266-MV. A simplified setting method, which uses the (optional) LCD indicator, is available for flow and level calculation.
Change from two to one column
6 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A
—
Functional specification
Measuring range limits and span limits
Differential pressure sensor
Sensor code Measuring range upper limit (URL) Lower range limit (LRL) Minimum measuring span
A 1 kPa
10 mbar
4 in H2O
1 kPa
10 mbar
4 in H2O
0.05 kPa
0.5 mbar
0.2 in H2O
C 6 kPa
60 mbar
24 in H2O
6 kPa
60 mbar
24 in H2O
0.2 kPa
2 mbar
0.8 in H2O
F 40 kPa
400 mbar
160 in H2O
40 kPa
400 mbar
160 in H2O
0.4 kPa
4 mbar
1.6 in H2O
L 250 kPa
2500 mbar
1000 in H2O
250 kPa
2500 mbar
1000 in H2O
2.5 kPa
25 mbar
10 in H2O
N 2000 kPa
20 bar
290 psi
2000 kPa
20 bar
290 psi
20 kPa
0.2 bar
2.9 psi
Absolute pressure sensor (second sensor)
Sensor code Measuring range upper limit (URL) Lower range limit (LRL) Minimum measuring span
1 600 kPa
6 bar
87 psi
0 abs 6 kPa
0.06 bar
0.87 psi
2 2000 kPa
20 bar
290 psi
0 abs 20 kPa
0.2 bar
2.9 psi
3 10000 kPa
100 bar
1450 psi
0 abs 100 kPa
1 bar
14.5 psi
4 41000 kPa
410 bar
5945 psi
0 abs 410 kPa
4.1 bar
59.5 psi
Change from one to two columns
266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 7
Span limits
Maximum measuring span = Measuring range upper limit (URL). For differential pressure measurements, can be adjusted up to ± URL (TD = 0.5) within the measuring range limits. Note To optimize performance characteristics, it is recommended that you select the transmitter sensor code with the lowest turn down ratio.
Recommendation for square root function
At least 10 % of measuring range upper limit (URL)
Zero position suppression and elevation
The zero position and span can be set to any value within the measuring range limits listed in the table if:
• already set span minimum span
Temperature input
Process temperature range 200 to 850 °C ( 328 to 1562 °F) with external resistance thermometer (Pt100) in four-wire circuit.
Damping
Configurable time constant between 0 and 60 s. This is in addition to the sensor response time.
Warm-up time
Ready for operation as per specifications in less than 10 s with minimum damping.
Insulation resistance
> 100 M at 500 V DC (between terminals and ground)
8 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A
—
Operating limits
Pressure limits
Gauge pressure limits The transmitter models 266CSX can operate without damage within the following overpressure limits:
Sensors Filling fluid Gauge pressure limits
A Silicone oil 0.5 kPa abs., 5 mbar abs., 0.07 psia
and 0.6 MPa, 6 bar, 87 psi
or 2 MPa, 20 bar, 290 psi
depending on code variant selected*
A Fluorocarbon
(Galden™)
17.5 kPa abs., 175 mbar abs., 2.5 psia
and 0.6 MPa, 6 bar, 87 psi
or 2 MPa, 20 bar, 290 psi
depending on code variant selected*
C to N Silicone oil 0.5 kPa abs., 5 mbar abs., 0.07 psia
and 2 MPa, 20 bar, 290 psi
or 10 MPa, 100 bar, 1450 psi
or 41 MPa, 410 bar, 5945 psi
depending on code variant selected*
C to N Fluorocarbon
(Galden™)
17.5 kPa abs., 175 mbar abs., 2.5 psia
and 2 MPa, 20 bar, 290 psi
or 10 MPa, 100 bar, 1450 psi
or 41 MPa, 410 bar, 5945 psi
depending on code variant selected*
* 1 MPa, 10 bar, 145 psi for Kynar-PVDF
Static pressure limits The transmitter models 266CSX can operate within the specifications with the following limits:
Sensors Filling fluid Static pressure limits
A Silicone oil 3.5 kPa abs., 35 mbar abs., 0.5 psia
and 0.6 MPa, 6 bar, 87 psi
or 2 MPa, 20 bar, 290 psi
depending on code variant selected*
A Fluorocarbon
(Galden™)
17.5 kPa abs., 175 mbar abs., 2.5 psia
and 0.6 MPa, 6 bar, 87 psi
or 2 MPa, 20 bar, 290 psi
depending on code variant selected*
C to N Silicone oil 3.5 kPa abs., 35 mbar abs., 0.5 psia
and 2 MPa, 20 bar, 290 psi
or 10 MPa, 100 bar, 1450 psi
or 41 MPa, 410 bar, 5945 psi
depending on code variant selected*
C to N Fluorocarbon
(Galden™)
17.5 kPa abs., 175 mbar abs., 2.5 psia
and 2 MPa, 20 bar, 290 psi
or 10 MPa, 100 bar, 1450 psi
or 41 MPa, 410 bar, 5945 psi
depending on code variant selected*
* 1 MPa, 10 bar, 145 psi for Kynar-PVDF
Test pressure The transmitters can withstand a pressure test with the following line pressure without leaking:
Model Test pressure
266CSX 1.5 × nominal pressure (static
pressure limit) simultaneously on
both sides*
* Meets hydrostatic test requirements of ANSI/ISA-S 82.03.
266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 9
Temperature limits °C (°F)
Environment This is the operating temperature.
All models Ambient temperature limits
Silicone oil 40 and 85 °C ( 40 and 185 °F)
Fluorocarbon (Galden™) 40 and 85 °C ( 40 and 185 °F)
All models Ambient temperature limits
Integrated digital display (LCD)* 40 and 85 °C ( 40 and 185 °F)
Viton™ gasket 20 and 85 °C ( 4 and 185 °F)
PTFE gasket 20 and 85 °C ( 4 and 185 °F)
* If may no longer be possible to read the digital display (LCD) clearly
below 20 °C ( 4 °F) and above 70 °C (158 °F).
Note For applications in potentially explosive environments, the temperature specified on the certificate / approval which depends upon the type of protection sought shall apply. Process
All models Process temperature limits
Silicone oil 40 and 121 °C ( 40 and 250 °F)*
Fluorocarbon (Galden™) 40 and 121 °C ( 40 and 250 °F)**
Viton™ gasket 20 and 121 °C ( 4 and 250 °F)
PTFE gasket 20 and 85 °C ( 4 and 185 °F)
* 85 °C (185 °F) for applications under 10 kPa, 100 mbar abs., 1.45 psia up
to 3.5 kPa abs., 35 mbar abs., 0.5 psia
** 85 °C (185 °F) for applications below atmospheric pressure up to
17.5 kPa abs., 175 mbar abs., 2.5 psia
Transport and storage
Models 266Cxx – Transport and storage
Ambient temperature range 50 to 85 °C ( 58 to 185 °F)
With integrated digital display (LCD):
40 to 85 °C ( 40 to 185 °F)
Relative humidity Up to 75 %
—
Environmental limits Electromagnetic compatibility (EMC)
In accordance with EN 61326 Overvoltage strength (with overvoltage protection): 4 kV (in accordance with IEC 1000-4-5 EN 61000-4-5)
Pressure Equipment Directive (PED)
Instruments with a maximum operating pressure of 41 MPa, 410 bar, 5,945 psi comply with Directive 2014/68/EU category III, module H.
Humidity
Relative humidity: up to 100 %. Condensation, icing: permitted.
Vibration resistance
Acceleration up to 2 g at frequencies of up to 1000 Hz (in accordance with IEC 60068-2-6).
Shock resistance
Acceleration: 50 g Duration: 11 ms (in accordance with IEC 60068-2-27).
Humid and dusty atmospheres (IP rating)
The transmitter is dust and sand-proof and protected against immersion effects in accordance with EN 60529 (2001) with IP 67 (IP 68 on request), by NEMA 4X, or by JIS C0920.
Change from two to one column
10 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A
— Use in potentially explosive atmospheres Change from one to two columns
Ex marking
Devices in hazardous atmospheres with or without integrated digital display. For ambient temperatures 40 to 85 °C ( 40 to 185 °F) the information based on the temperature classes in the associated certificates, must be complied with. The temperature sensor circuit (Pt100) and the digital output (pulse / limit value output) must be connected in accordance with the requirements of the Ex certificate. ATEX / IECEx
Ex-marking
Type of protection ‘Ex d’ – flameproof (enclosure)
ATEX (Code E2)
II 1/2 G Ex db IIC T6 Ga/Gb Ta = 50 °C to +75 °C – IP67
II 1/2 D Ex tb IIIC T85°C Db Ta = 50 °C to +75 °C – IP67
IECEx (Code E9)
Ex db IIC T6 Ga/Gb Ta = 50 °C to +75 °C – IP67
Ex tb IIIC T85°C Db Ta = 50 °C to +75 °C – IP67
Type examination
certificate
ATEX (Code E2)
FM09AATEX0023X
IECEx (Code E9)
IECEx FME 16.0002X
Ex-marking
Type of protection ‘Ex n’ – non-sparking and ‘Ex t’ – enclosure
ATEX (Code E3)
II 3 G Ex nA nC IIC T6/T5/T4 nA Gc – IP67
II 3 D Ex tc IIIC T85°C Dc – IP67
IECEx (Code ER)
Ex nA nC IIC T6/T5/T4 nA Gc – IP67
Ex tc IIIC T85°C Dc IP67
Type examination
certificate
ATEX (Code E3 )
FM09AATEX0025X
IECEx (Code ER)
IECEx FME 16.0004X
FM (USA and Canada)
Ex-marking
Type of protection Explosion proof
Explosion proof (US):
Class I, Div. 1, Groups A, B, C, D Ta = 50 to 85 °C
Explosion proof (Canada):
Class I, Div. 1, Groups A, B, C, D / T5 Ta = 50 to 85 °C
Dust Ignition Proof:
Class II/III, Div. 1, Groups E, F, G D Ta = 50 to 85 °C
Type of protection Non-Incendive
Class II/III, Div. 1, Groups E, F, G / T5 Ta = 50 to 85 °C
Type of protection Energy limited
Energy limited (US):
Class I Zone 2, AEx nA nC IIC T6…T4 Ta = 50 to 85 °C
Energy limited (Canada):
Class I Zone 2, Ex nA nC IIC T6…T4 Ta = 50 to 85 °C
FM approvals USA (code ET)
FM16US0066X
Canada (code ET)
FM16CA0036X
Type 4X, IP67 for all above markings.
Combined ATEX, FM and IECEx approvals
Code EN = E2+E9+E3+ER+ET
266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 11
— Electrical data and options
Power supply
Devices with Modbus communication
Terminals PWR + / PWR
Supply voltage 10.5 to 30 V DC
The transmitter operates on terminal voltage of 10.5 to 30 V DC. The quiescent supply current is 10 mA typically. The transmitting supply current does not exceed 25 mA.
Output signal
Modbus® RS 485 with 8 bit Remote Terminal Unit (RTU) data transmission.
Modbus® interface
Configuration
(HART®-RS485)
Via an RS485 interface in connection with
Asset Vision Basic (DAT200) a HART®
communication DTM and a corresponding
Device Type Manager (DTM)
Operating
(Modbus® communication)
Modbus RTU – 2-wire half-duplex RS485 serial
connection
Baud rate 1200, 2400, 4800, 9600
Factory setting: 9600 bps
Parity None, even, odd
Factory setting: none
Typical response time < 100 milliseconds
Response delay time 0 to 200 milliseconds
Factory setting: 50 milliseconds
Device address 1 to 247
Factory setting: 247
Register address offset One base
LCD display
M10142 Figure 2: LCD display (example)
Integral LCD display (code L1) • Wide screen LCD display, 128 × 64 pixel, 52.5 × 27.2 mm
(2.06 × 1.07 in), dot matrix, multilingual. • Four buttons for device configuration and management. • Easy setup for quick commissioning. • Customized visualizations which the user can select. • Total value and actual value flow indication. The display can also be used to show static pressure, sensor temperature, and diagnosis notice, as well as make configuration settings. Integral LCD display with TTG-(Through-The-Glass) operation (code L5) As with the integral LCD display above, but featuring an innovative TTG (Through-The-Glass) button technology which can be used to activate the device's configuration and management menus without having to remove the transmitter housing cover. The TTG (Through-The-Glass) buttons are protected against accidental activation.
12 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A
— Measuring accuracy
Reference conditions according to IEC 60770: • Ambient temperature 20 C (68 F), rel. humidity 65 %,
atmospheric pressure 1.013 hPa (1.013 mbar). • Position of measuring cell (separating diaphragm
areas) vertical. • Measuring span based on zero point. • Separating diaphragms made from stainless steel
AISI 316 L or Hastelloy, gasket Viton / Perbunan, silicone oil filling fluid
• Digital trim values equal to the span end points. Unless otherwise stated, errors are specified as a % of the measuring span value. Some measuring accuracy levels relating to the upper measuring range limit (URL) are affected by the current turn down (TD); i.e., the ratio of the upper measuring range limit to the already set span. Note FOR OPTIMUM MEASURING ACCURACY, IT IS RECOMMENDED THAT YOU SELECT THE SENSOR CODE WHICH WILL PROVIDE THE LOWEST TD VALUE.
Dynamic response
In accordance with IEC 61298-1
Sensors Time constant
(63.2 % of total step response)
Sensors F to R 150 ms
Sensor C 400 ms
Sensor A 1000 ms
266CXX: Delay time for all sensors 70 ms
Response time (total) = delay time + time constant
Measuring error
In % of calibrated span, consisting of terminal-based non-linearity, hysteresis, and non-repeatability.
Model DP-Sensor For TD range Measuring error
266CSH A to N From 1:1 to 10:1 ±0.075 %
A From 10:1 to 20:1 ±(0.075 + 0.005 × TD 0.05) %
C From 10:1 to 30:1 ±(0.075 + 0.005 × TD 0.05) %
F to N From 10:1 to 100:1 ±(0.075 + 0.005 × TD 0.05) %
266CST A to N From 1:1 to 10:1 ±0.04 %
A From 10:1 to 20:1 ±(0.04 + 0.005 × TD 0.05) %
C From 10:1 to 30:1 ±(0.04 + 0.005 × TD 0.05) %
F to N From 10:1 to 100:1 ±(0.04 + 0.005 × TD 0.05) %
Recommendation for square root function At least 10 % of upper measuring range limit (URL)
Model Pabs sensor (second sensor) Measuring error
266CXX 1 to 3 ±0.05 %
4 ±0.075 %
Model Process temperature measurement
(Pt100) in acc. with IEC 60751
Measuring error -
transmitter part
266CXX 200 to 850 °C ( 328 to 1562 °F) ±0.3 K (0.54 °F)
266CXX: The accuracy of the mass or standard volume flow is not affected by the accuracy of the dp, p, and T measurement alone; rather, it also depends upon the primary device used (flow coefficient), the pressure and temperature range to be compensated, as well as other parameters. In typical applications, the flow measurement accuracy (without the primary device accuracy) is ±0.7 to 0.9 % of the mass flow.
266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 13
Ambient temperature Per 20 K change within the limits of 40 to 85 °C (per 36 °F change within the limits of 40 to 185 °F):
Model Sensor For TD
range
266CSH A 10:1 ±(0.08 % URL + 0.06 % measuring span)
C to N 10:1 ±(0.04 % URL + 0.06 % measuring span)
266CST A 10:1 ±(0.06 % URL + 0.045 % measuring span)
C to N 10:1 ±(0.03 % URL + 0.045 % measuring span)
In the event of a change to the ambient temperature of
10 °C to 60 °C (14 to 140 °F):
Model Sensor For TD
range
266CSH A 10:1 ±(0.16 % URL + 0.065 % measuring span)
C to N 10:1 ±(0.08 % URL + 0.065 % measuring span)
266CST A 10:1 ±(0.12 % URL + 0.05 % measuring span)
C to N 10:1 ±(0.06 % URL + 0.05 % measuring span)
Per 10 K change within the limits of 40 to 10 °C or 60 to 85 °C (per 18 °F change within the limits of 40 to 14 °F or 140 to 185 °F):
Model Sensor For TD
range
266CSH A 10:1 ±(0.066 % URL + 0.04 % measuring span)
C to N 10:1 ±(0.033 % URL + 0.04 % measuring span)
266CST A 10:1 ±(0.05 % URL + 0.03 % measuring span)
C to N 10:1 ±(0.025 % URL + 0.03 % measuring span)
Absolute pressure sensor Per 20 K change between the limits of 40 to 85 °C ( 40 to 185 °F):
±(0.08 % URL + 0.08 % measuring span) Limited to ±(0.1 % URL + 0.1 % measuring span) for the entire temperature range of 125 K within the limits of 40 to 85 °C ( 40 to 185 °F). Static pressure
Zero signal errors may be calibrated out at operating pressure.
Measuring range Sensor A Sensors C, F, L, N
Zero signal error Up to 2 bar:
0.05 % URL
Up to 100 bar:
0.05 % URL
> 2 bar: 0.05 % URL/bar > 100 bar: 0.05 %
URL/100 bar
Span error Up to 2 bar:
0.05 % measuring span
Up to 100 bar:
0.05 % measuring span
> 2 bar: 0.05 %
Measuring span / bar
> 100 bar: 0.05 %
Measuring span / 100 bar
14 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A
— … Measuring accuracy Electromagnetic field Meets all requirements of EN 61326 Mounting position Rotations in the plane of the diaphragm have a negligible effect. A tilt from the vertical of up to 90° causes a zero [point] shift of up to 0.35 kPa (3.5 mbar, 1.4 in H2O), which can be corrected by making an appropriate zero position adjustment. There is no effect on the measuring span. Long-term stability Sensors C to N:
±0.15 % of URL over a period of 10 years (±0.05 % URL/year)
Sensor A: ±0.3 % of URL over a period of 10 years (±0.2 % URL/year)
Total performance Only for differential pressure measurement; similar to DIN 16086. Within an ambient temperature change range of
10 to 60 °C (14 to 140 °F), up to 10 MPa, 100 bar, 1450 psi static pressure.
Model Sensor For TD range Total performance (DP)
266CSH C to N 1:1 ±0.17 % of calibrated span
266CST C to N 1:1 ±0.14 % of calibrated span
The total performance includes the measuring error (non-linearity including hysteresis and non-repeatability), the thermal change in the ambient temperature as regards the zero signal and measuring span, as well as the effect of the static pressure on the zero signal and measuring span.
Eperf Total Performance
E TZ Effect of the ambient temperature on the zero signal
E TS Effect of the ambient temperature on the measuring span
E PZ Effect of the static pressure on the zero signal
E PS Effect of the static pressure on the measuring span
Elin Measuring error
— Technical specification Note Please refer to the order information to check the availability of different versions of the relevant model.
Materials
Process separating diaphragms* Stainless steel 1.4435 (AISI 316L); Hastelloy C276®; Monel 400®; Monel 400®, gold-plated; Tantalum
Process flanges, adapters, screw plugs, and vent / drain valves*
Stainless steel 1.4404 / 1.4408 (AISI 316L); Hastelloy C276®; Monel 400®; Kynar (flange made from stainless steel AISI 316L with PVDF insert)
Sensor filling fluid
Silicone oil; Fluorocarbon (Galden™) Mounting bracket**
Galvanized C steel with chromium passivation; Stainless steel AISI 316, AISI 316 L
Seals*
Viton™ (FPM); Buna® (NBR); EPDM; PTFE or FEP-coated Viton™ (only for PVDF Kynar process connection); Graphite
Pressure sensor housing
Stainless steel 1.4404 (AISI 316L) Screws and nuts
Screws and nuts made from stainless steel AISI 316, class A4-70 as per UNI 7323 (ISO 3506) in compliance with NACE MR0175 Class II
Electronics housing and cover
Aluminum alloy (copper content 0.3 %) with baked epoxy finish (color RAL9002); Stainless steel AISI 316L.
Cover O-ring
Buna N® (Perbunan) * Wetted parts of the transmitter. ** U-bolt material: Stainless steel AISI 400;
Screw material: High-strength alloy steel or stainless steel AISI 316
2lin
2PSΔ
2PZΔ
2TSΔTZΔperf EEE)EE(E
266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 15
Local zero point, measuring span, and write protection settings
Fiber glass-reinforced polyphenylene oxide (removable) Plates
Stainless steel AISI 316 for transmitter name plate, certification plate, optional measuring point tag plate. Settings plate attached to electronics housing, and optional tag plate with customer data. All plates laser-labeled.
Calibration
Standard: 0 to measuring range upper limit, for ambient temperature and atmospheric pressure
Optional: To specified measuring span
Surge protection
The 266 Modbus multivariable pressure transmitter comes standard with a surge / transient suppression scheme build into the termination block. • Up to 4 kV on power supply • Up to 2 kV on I/O • Voltage: 1.2 s rise time / 50 s delay time at half value
Optional accessories Mounting bracket
For vertical and horizontal 60 mm (2 in) pipes or wall mounting
LCD display
Can be rotated in 90° increments into 4 positions Additional tag plates
Code I2: For measuring point tag (up to 30 characters) and calibration specifications (up to 30 characters: lower and upper value plus unit), attached to transmitter housing. Code I1: For customer data (4 lines with 30 characters each), attached to transmitter housing with wire.
Cleaning stage for oxygen applications (O2)
Refer to Ordering Information on page 23. Certificates
Test, design, characteristics, material traceability. Refer to Ordering Information on page 23.
Name plate and operating instruction language
Refer to Ordering Information on page 23.
Process connections
Flanges
¼-18 NPT on the process axis Adapters
½-14 NPT on the process axis Center distance
54 mm (2.13 in) between flanges; 51 mm, 54 mm, or 57 mm (2.01 in, 2.13 in, or 2.24 in) between adapters
Fastening screw threads
-20 UNF with 41.3 mm center distance Or with process flange code C: • M10 with operating pressures of up to 10 MPa,
100 bar, 1450 psi • M12 with higher operating pressures of up to 41 MPa,
410 bar, 5945 psi
16 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A
— … Technical specification
Electrical connections
Cable entry
Two ½-14 NPT or M20 × 1.5 threaded bores for cable glands, directly on housing.
Terminals • Two terminal for power (+ and ). • Two terminals for RS485 communication. • Four terminals for a Pt100 resistance thermometer with
four-wire technology. For wire cross sections of up to 2.5 mm2 (14 AWG) and connection points for testing and communication purposes. Grounding
Internal and external ground terminals are provided for 6 mm2 (10 AWG) wire cross sections.
Mounting position
The transmitters can be installed in any position. The electronic housing can be rotated into any position. A stop is provided to prevent overturning.
Weight
Pressure transmitter without options
Approximately 3.8 kg (8.4 lb); Add 1.5 kg (3.3 lb) for housings made from stainless steel.
Packaging
Add 650 g (1.5 lb) for packaging
Packaging
Carton with dimensions of approx. 28 × 23 × 24 cm (11 × 9 × 9 in)
— Configuration Standard configuration Transmitters are calibrated at the factory to the customer's specified measuring range. The calibrated range and measuring point number are specified on a tag plate. If this data has not been specified, the transmitter will be delivered with the plate left blank and the following configuration.
Parameter Value
Device mode Operate (Modbus)
Device address 247
Multivariable calculation No calculation
Software tag (max. 8 characters) blank
Optional LCD display PV (DP) in kPa; output in percent as
bargraph display
(DP) Physical unit kPa
(DP) Output scale 0% 0 (LRL)
(DP) Output scale 100% Upper Range Limit (URL)
Output Linear
Damping 0.125 s
(PS) Physical unit MPa
(PS) Output scale 0% 0 (LRL)
(PS) Output scale 100% Upper Range Limit (URL)
Damping 0.125 s
(T) Physical unit °C
(T) Output scale 0% 200 (LRL)
(T) Output scale 100% +850 Upper Range Limit (URL)
Damping 10 s
Any or all of the configurable parameters listed above – including the lower and upper range values (with the same unit of measurement) – can easily be changed using a PC running the configuration software with the DTM for 266Cxx-Modbus. Specifications concerning the flange type and materials, O-ring and vent / drain valve materials, and additional device options are stored in the transmitter database. Note For device functionality and simulation purpose a 178 resistor (206 °C [402.8 °F]) and 2 jumpers are installed in the PT100 connection
Change from two to one column
266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 17
—
Mounting dimensions Transmitter with barrel housing – Horizontal flanges
M10019-02
29 (1.14)
18 (0.71)18 (0.71)
210
(8
.28
)
60 (2.36)**72 (2.83)***
56 (2.21) 53 (2.09)
12 (
0.4
7)
90 (3.54) 33 (1.30)
65
(2
.53
)
41
3 (
1.6
3)
,
9 (0.35)
*
142 (5.59)
179
(7.
02
)
91 (3.58)
145
(5
.70
)
1 2
3
4
5
10
6
7
8
9
1 Push buttons
2 Name plate
3 Certification plate
4 Vent / drain valve
5 Process connection
6 Terminal side
7 LCD display housing cover
8 Electronics side
9 Process flange adapter
0 Space for removing the cover
* 54 mm (2.13 in) via ¼-18 NPT process flanges; 51 mm (2.01 in), 54 mm (2.13 in), or 57 mm (2.24 in) via ½-14 NPT adapter flanges.
Note Process connection and seal groove satisfy IEC 161518. Thread for attaching adapter flanges or other components (for example manifold) on the process flange: -20 UNF.
** With screw plug
*** With vent / drain valve
Figure 3: Barrel housing – horizontal flanges, Dimensions in mm (in)
18 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A
— … Mounting dimensions Transmitter with barrel housing – Vertical flanges
M10139-01
142 (5.59)
54 (2.13)
91 (3.58)
31
(1.2
2)
25
1 (9
.88
)
216
(8
.50
)
18 (0.71)
28 (1.10) LCD (L1)24 (0.95) TTG-LCD (L5)
53 (2.09)
9 (0.35)
110 (4.33)
18 (0.71)
41,3 (1.63)
1 2
3
4
5
6
9
8
0
7
1 Pusch buttons
2 Name plate
3 Certification plate
4 Vent / drain valve
5 Process connection
6 Terminal side
7 LCD display housing cover
8 Electronics side
9 Process flange adapter
0 Space for removing the cover
Figure 4: Barrel housing - vertical flanges, Dimensions in mm (in)
266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 19
Transmitter with mounting bracket, for vertical or horizontal mounting on 60 mm (2 in) pipe pipe
M10020-01
89
(3
.48
)
142 (5.59)
¹�
179
(7.
02)
91 (3.58)
116 (4.57)
179
(7.
02)
91 (3.58)
123 (4.86)
*
142 (5.59)
72 (2.83)
210
(8
.28
)
107 (4.21)
53 (2.09)
45 (1.77) 33 (1.30)
56 (2.21)
29 (1.14)
18 (0.71)18 (0.71)
12 (
0.4
7)60 (2.36)**72 (2.83)***
29 (1.14)
18 (0.71)18 (0.71)
210
(8
.28
)
107 (4.21)
72 (2.83)
56 (2.21) 53 (2.09)
12 (
0.4
7)
45 (1.77) 33 (1.30)
60 (2.36)²�
72 (2.83)³�
* 54 mm (2,13 in) via ¼-18 NPT process flanges;
51 mm (2,01 in), 54 mm (2,13 in), or 57 mm (2.24 in) via ½-14 NPT adapter flanges.
Note Process connection and seal groove satisfy IEC 161518. Thread for attaching adapter flanges or other components (for example manifold) on the process flange: -20 UNF.
** With screw plug
*** With vent / drain valve
Figure 5: Pipe mounting – barrel housing, Dimensions in mm (in)
20 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A
— … Mounting dimensions Transmitter with DIN aluminum housing – horizontal flanges with mounting bracket for vertical or horizontal mounting on 60 mm (2 in) pipe
M10021-01
65
(2
.54
)8
3 (
3.2
8)
136 (5.35)
116 (4.57)*
185 (7.25)
29 (1.14)
18 (0.71)
53 (2.09)
18 (
0.7
1)
86 (3.40)
15 (
0.5
7)
129
(5
.06
)
72 (2.83)
116 (4.57)
178
(6
.99
)
180
(7.
08
)
142 (5.59)185 (7.25)
29 (1.14)
18 (0.71)
53 (2.09)
18 (
0.7
1)
107
(4.2
1)
86 (3.40)
*
* 54 mm (2.13 in) via ¼-18 NPT process flanges;
51 mm (2.01 in), 54 mm (2.13 in), or 57 mm (2.24 in) via ½-14 NPT adapter flanges.
Note Process connection and seal groove satisfy IEC 161518. Thread for attaching adapter flanges or other components (for example manifold) on the process flange: -20 UNF.
Figure 6: Pipe mounting – DIN housing, Dimensions in mm (in)
266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 21
Transmitter with flat bracket, for vertical or horizontal mounting on 60 mm (2 in) pipe
M10022-01
70 (2.75)
70 (
2.7
5)
179
(7.
02
)
91 (3.58)
142 (5.59)
49
(1.
93
)
29 (1.14)
18 (0.71)18 (0.71)
210
(8
.28
)
56 (2.21) 53 (2.09)
45 (1.77) 33 (1.30)12
(0
.47
)
60 (2.36)*72 (2.83)**
25 (0.98)
44 (1.71)
89 (3.48)
118
(4
.63
)
*
* With screw plug
** With vent / drain valve
Figure 7: Flat bracket for pipe mounting – barrel housing, Dimensions in mm (in)
22 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A
—
Electrical connections
M11189
COMM.A(+)
B(-)
SURGEINSIDE
RTD
Modbus9...30 V DC
PE
1 3
4
2
5
1 Terminals for Modbus® interface
2 Terminal for PE / Cable Shield
3 Terminals for power supply
4 Terminals for Pt100 resistance thermometer
5 Ground terminal PE Potential equalization
Figure 8: Connection on the device (example)
266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 23
—
Ordering Information
Model 266CSH and 266CST
Base model
Multivariable transmitter for mass flow and level, base accuracy 0.075 % 266CSH X X X X X X X
Multivariable transmitter for mass flow and level base accuracy 0.04 % 266CST X X X X X X X
Sensor Span Limits
0.05 and 1 kPa (0.5 and 10 mbar 0.2 and 4 in H2O) A*
0.2 and 6 kPa (2 and 60 mbar / 0.8 and 24 in H2O) C
0.4 and 40 kPa (4 and 400 mbar / 1.6 and 160 in H2O) F
2.5 and 250 kPa (25 and 2500 mbar / 10 and 1000 in H2O) L
20 and 2000 kPa (0.2 and 20 bar / 2.9 and 290 psi) N
Maximum Working Pressure
0 and 0.6 MPa / 0 and 6 bar / 0 and 87 psi (only with Sensor Span Limits code A) 1
0 and 2 MPa / 0 and 20 bar / 0 and 290 psi 2
0 and 10 MPa / 0 and 100 bar / 0 and 1450 psi / (not with Sensor Span Limits code A) 3
0 and 41 MPa / 0 and 410 bar / 0 and 5945 psi / (not with Sensor Span Limits code A) 4
Diaphragm Material / Fill Fluid
AISI 316L SST (1.4435) / Silicone oil (NACE) S
Hastelloy C-276 / Silicone oil (NACE) K
Monel 400 / Silicone oil (NACE) M
Monel 400 gold-plated / Silicone oil (NACE) V
Tantalum / Silicone oil (NACE) T
AISI 316L SST (1.4435) / Inert fluid - Galden (Suitable for oxygen applications) (NACE) A**
Hastelloy C-276 / Inert fluid - Galden (Suitable for oxygen applications) (NACE) F**
Monel 400 / Inert fluid - Galden (Suitable for oxygen applications) (NACE) C**
Monel 400 gold-plated / Inert fluid - Galden (Suitable for oxygen applications) (NACE) Y**
Tantalum / Inert fluid - Galden (Suitable for oxygen applications) (NACE) D**
Process Flanges and Adapters Material / Connection
AISI 316L SST (1.4404 / 1.4408) / ¼-18 NPT female direct / (horizontal connection) (NACE) A
AISI 316L SST (1.4404 / 1.4408) / ½-14 NPT female through adapter / (horizontal connection) (NACE) B
AISI 316L SST (1.4404 / 1.4408) / ¼-18 NPT female direct (DIN 19213) / (horizontal connection) (NACE) C
Hastelloy C-276 / ¼-18 NPT female direct / (horizontal connection) (NACE) D
Hastelloy C-276 / ½-14 NPT female through adapter / (horizontal connection) (NACE) E
Monel 400 / ¼-18 NPT female direct / (horizontal connection) (NACE) G
Monel 400 / ½-14 NPT female through adapter / (horizontal connection) (NACE) H
Kynar (PVDF) / ¼-18 NPT female direct (MWP = 1 MPa / 10 bar / 145 psi) / (insert on side of flange) P
AISI 316L SST (1.4404 / 1.4408) / ¼-18 NPT female direct / (vertical connection) (NACE) Q
* Not available with Diaphragm Material code M, V, T, C, Y, D
** Suitable for Oxygen service
Continued see next page
24 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A
— … Ordering Information Base model
Multivariable transmitter for mass flow and level, base accuracy 0.075 % 266CSH X X X
Multivariable transmitter for mass flow and level base accuracy 0.04 % 266CST X X X
Bolts Material / Gaskets Material
AISI 316L SST (NACE - non exposed) / Viton (Suitable for oxygen applications) 3*
AISI 316L SST (NACE - non exposed) / PTFE (Max. 25 MPa / 250 bar / 3625 psi) 4
AISI 316L SST (NACE - non exposed) / EPDM 5
AISI 316L SST (NACE - non exposed) / Perbunan 6
AISI 316L SST (NACE - non exposed) / Graphite 7
AISI 316L SST (NACE - non exposed) / FEP (only available with Kynar [PVDF] process connection) T
Housing Material / Electrical Connection
Aluminium alloy (Barrel type) / ½-14 NPT A
Aluminium alloy (Barrel type) / M20 × 1.5 B
AISI 316L SST (Barrel type) / ½-14 NPT S
AISI 316L SST (Barrel type) / M20 × 1.5 T
Output
Modbus RS 485 / No additional options N
Modbus RS 485 / Options requested (to be ordered by Additional ordering code) 6
* Suitable for Oxygen service
Additional ordering information
Additional ordering information
Multivariable transmitter for mass flow and level, base accuracy 0.075 % 266CSH XX XX
Multivariable transmitter for mass flow and level base accuracy 0.04 % 266CST XX XX
Vent and Drain Valve Material / Position
AISI 316L SST (1.4404) / On process axis (NACE) V1
AISI 316L SST (1.4404) / On flanges side top (NACE) V2
AISI 316L SST (1.4404) / On flanges side bottom (NACE) V3
Hastelloy C-276 / On process axis (NACE) V4
Hastelloy C-276 / On flanges side top (NACE) V5
Hastelloy C-276 / On flanges side bottom (NACE) V6
Monel 400 / On process axis (NACE) V7
Monel 400 / On flanges side top (NACE) V8
Monel 400 / On flanges side bottom (NACE) V9
Explosion Protection Certification
ATEX Group II Category 1/2 GD – Flameproof Ex d E2
ATEX Group II Category 3 GD – Type of protection "N" Ex nL design compliance E3
FM Approvals (USA and Canada) Explosion proof and Type „n“ ET
Combined ATEX, IECEx, FM Approvals (USA and Canada) EN
IEC Approval Group II Category 1/2 GD – Flameproof Ex d E9
IEC Approval Group II Category 3 GD – Type of protection "N" Ex nL design compliance ER
Continued see next page
266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 25
Additional ordering information
Multivariable transmitter for mass flow and level, base accuracy 0.075 % 266CSH XX XX XX XX XX XX
Multivariable transmitter for mass flow and level base accuracy 0.04 % 266CST XX XX XX XX XX XX
Integral LCD
With integral LCD display L1
TTG (Through The Glass) integral digital LCD display L5
Mounting Bracket Shape / Material
For pipe mounting / Carbon steel (not suitable for AISI housing) B1
For pipe mounting / AISI 316 SST (1.4401) (not suitable for AISI housing) B2
For wall mounting / Carbon steel (not suitable for AISI housing) B3
For wall mounting / AISI 316 SST (1.4401) (not suitable for AISI housing) B4
Flat type bracket / AISI 316 SST (1.4401) (suitable for AISI housing) B5
Operating Instruction Language
English M5
Label and Tag Language
German T1
Italian T2
Spanish T3
French T4
Additional Tag Plate
Supplemental wired-on stainless steel plate (4 lines, 32 characters each) I1
Laser printing of tag on stainless steel plate I2
Stainless steel tag, certification and wire-on plates I3
Configuration
Standard pressure = in H2O / psi at 68 °F N2
Standard pressure = in H2O / psi at 39.2 °F N3
Standard pressure = in H2O / psi at 20 °C N4
Standard pressure = in H2O / psi at 4 °C N5
Custom N6
Continued see next page
26 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A
— … Ordering Information Additional ordering information for model 266CSH
Multivariable transmitter for mass flow and level, base accuracy 0.075 % 266CSH XX XX XX XX XX
Multivariable transmitter for mass flow and level base accuracy 0.04 % 266CST XX XX XX XX XX
Preparation Procedure
Oxygen service cleaning, Pmax = 12 MPa (120 bar, 1740 psi) or maximum working pressure (lower value),
Tmax = 60 °C / 140 °F (only available with inert fill and Viton gasket)
P1
Hydrogen service preparation (Fluid film) P2
Certificates
Inspection certificate 3.1 acc. EN 10204 of calibration C1
Inspection certificate 3.1 acc. EN 10204 of cleanliness stage C3
Inspection certificate 3.1 acc. EN 10204 of helium leakage test of the sensor module C4
Inspection certificate 3.1 acc. EN 10204 of pressure test C5
Declaration of compliance with the order 2.1 acc. EN 10204 for instrument design C6
Separate calibration record CC
PMI test on wetted parts CT
Material Traceability
Inspection certificate 3.1 acc. EN 10204 of pressure-bearing and process wetted parts with analysis certificates as
material verification
H3*
Material certificate 2.2 acc. EN 10204 of the pressure bearing and process wetted parts H4
Connector
With cable gland M20 × 1.5 U8
Housing Accessories
Integral mount manifold (price adder just for assembling, not for manifold) A1
* Minor Parts with Factory Certificate acc. to EN 10204
266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 27
Standard delivery scope (changes possible with additional ordering code)
• Adapters supplied loose • Sealing plugs for horizontal connection flanges on the process axis; not for PVDF Kynar insert or for vertical connection
flanges (no vent / drain valves) • For standard applications (without explosion protection) • No display, no mounting bracket, no surge protector • Operating instruction and English labelling • Configuration with kPa and °C units • No test, inspection, or material certificates
Important remark for all models
The selection of suitable wetted parts and filling fluid for compatibility with the process media is a customers responsibility, if not otherwise notified before manufacturing.
NACE compliance information
1 The materials of constructions comply with metallurgical recommendations of NACE MR0175/ISO 15156 for sour oil field production environments. As specific environmental limits may apply to certain materials, please consult latest standard for further details. Materials AISI 316 / AISI 316L, Hastelloy C-276, Monel 400 also conform to NACE MR0103 for sour refining environments.
2 NACE MR0175 addresses bolting requirements in two classes: • Exposed bolts:
Bolts directly exposed to the sour environment or buried, encapsulated or anyway not exposed to atmosphere • Non exposed bolts:
The bolting must not be directly exposed to sour environments, and must be directly exposed to the atmosphere at all times.
266CSH, 266CST bolting identified by “NACE” are in compliance to the requirements of NACE MR0175 when considered “non exposed bolting” Change from one to two columns
—
Trademarks
Buna-N is a registered trademark of DuPont Dow Elastomers.
Hastelloy is a registered trademark of Haynes International, Inc.
Monel is a registered trademark of Special Metals Corporation
Modbus is a registered trademark of the Modbus Organization
Galden is a Montefluos trademark
Kynar is an Elf Atochem North America Inc. trademark
Viton is a DuPont de Nemours trademark
Sales Service
— ABB Limited Measurement & Analytics Howard Road, St. Neots Cambridgeshire, PE19 8EU UK Tel: +44 (0)870 600 6122 Fax: +44 (0)1480 213 339 Email: [email protected] ABB Automation Products GmbH Measurement & Analytics Schillerstr. 72 32425 Minden Germany Tel: +49 571 830-0 Fax: +49 571 830-1806 abb.com/pressure
ABB Inc. Measurement & Analytics 125 E. County Line Road Warminster, PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183 ABB S.p.A. Measurement & Analytics Via Luigi Vaccani 4 22016 Tremezzina (CO) Italy Tel: +39 0344 58111 Email: [email protected]
DS/
266C
SH/C
ST/M
OD
BU
S-EN
Rev
. A
06.
2018
— We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB. Copyright© 2018 ABB All rights reserved 3KXP400011R1001
/ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages false /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 240 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages false /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects true /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly true /PDFXNoTrimBoxError false /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier (FOGRA27) /PDFXOutputCondition () /PDFXRegistryName (http://www.color.org) /PDFXTrapped /False
/CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure false /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MarksOffset 6 /MarksWeight 0.250000 /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /DocumentCMYK /PageMarksFile /RomanDefault /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /UseDocumentProfile /UseDocumentBleed false >> > ]>> setdistillerparams> setpagedevice