ABB MEASUREMENT & ANALYTICS | DATA SHEET 266CSH / CST Multivariable pressure transmitter with Modbus® communication

Multivariable pressure transmitter with Modbus® communication · Flow coefficient The discharge coefficient is defined as the actual flow divided by the theoretical flow. It corrects

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

  • — ABB MEASUREMENT & ANALYTICS | DATA SHEET

    266CSH / CST Multivariable pressure transmitter with Modbus® communication

  • 2 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A

    — Measurement made easy Pressure transmitters – 2600T series. Technical solutions for any application

    — Base accuracy • 0.075 % of calibrated span (266CSH) • 0.04 % of calibrated span (266CST)

    — 266CSH/CST mass flow measurement with compensation, level measurement with compensation for gases, steam, and liquids • Dynamic compensation of pressure and temperature

    changes

    — Proven sensor technology together with state-of-the-art digital technology • Large turn down ratio of up to 100:1

    — Flexible configuration options • Local configuration via buttons on LCD indicator • TTG (Through-The-Glass) keypad technology

    — 10-year stability • 0.15 % of URL

    — Comprehensive range of functions • Integrated counting function

  • 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 3

    Change from one to two columns

    — Introduction

    266CSH / 266CST

    Thanks to their multisensor technology, these transmitters are capable of measuring three separate process variables at the same time and offer the option of calculating the following values:

    • Mass flow for gases, steam, and liquids by means of dynamic compensation

    • Standard volume flow for gases by means of dynamic compensation

    • Heat flow for water and steam • Drum water level and level measurement with density

    compensation of liquids The differential pressure and absolute pressure are measured by two integrated sensors. The process temperature is measured by an external standard Pt100 resistance thermometer. Flow calculation The flow calculation carried out by these transmitters includes compensation of pressure and / or temperature as well as more complex variables such as discharge coefficient, thermal expansion, Reynolds number, and compressibility factor. The 266CXX pressure transmitters include flow equations for superheated steam, saturated steam, gases, and liquids - so you only need one device for your system. Multivariable transmitters represent a more economical solution than the designs that have been used for this type of measuring point up to now, in which three different transmitters for differential pressure, absolute pressure, and temperature report their values to a DCS, PLC, or flow computer.

    M10143

    dp

    p

    T

    Qm

    Qv

    T

    Flo

    w

    Flo

    w

    FDP

    P

    Past Present

    Figure 1: Flow measurement - past and present

    The dynamic mass flow of the 266CXX is calculated using the following equation:

    dpρdεβ1

    CQm 1

    2

    4

    Qm Mass flow C Discharge coefficient

    Diameter ratio Gas expansion factor

    d Inside diameter of the differential flow sensor dp Differential pressure

    Density The flow calculation process is based on the following standards:

    • AGA 3 • DIN EN ISO 5167

  • 4 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A

    — … Introduction Flow coefficient The discharge coefficient is defined as the actual flow divided by the theoretical flow. It corrects the theoretical equation for the effect on the velocity profile (Reynolds number), assuming that no energy is lost between the pressure taps and pressure tap location. It is dependent on the differential flow sensor, the diameter ratio, and the Reynolds number. Compensation for the discharge coefficient ensures a high level of measuring accuracy for flow measurement with primary elements. Gas expansion factor The gas expansion factor corrects for density differences between pressure taps due to expansion of compressible media. It does not apply to liquids which are essentially non-compressible. The gas expansion factor is dependent on the diameter ratio, the isentropic exponent, the differential pressure, and the static pressure of the medium. Diameter ratio The diameter ratio is dependent on the inside diameter of the differential flow sensor and the pipe diameter, which in turn are subject to temperature functions. If the temperature of the medium being measured changes, the material of the process pipe and differential flow sensor expands or contracts. The thermal expansion coefficients are dependent on the material of the pipe and differential flow sensor, and are used for calculating the change in diameters. This ensures a high level of flow accuracy in applications with low and high temperatures.

    Medium density The medium density has a direct effect on the flow calculation. The 266CXX pressure transmitters compensate for the medium density resulting from changes in temperature and / or pressure as follows:

    • Gases as a function of p and T based on gas laws, taking compressibility factors into account; for natural gas, based on AGA 8 or SGERG

    • Superheated steam as a function of p and T based on steam tables

    • Saturated steam as a function of p based on steam tables

    • Liquids as a function of T Mass flow calculations With the 266CXX pressure transmitters, mass flow calculations can be configured for the following differential flow sensors:

    • Orifice corner pressure taps, ISO • Orifice flange pressure taps, ISO • Orifice D and D/2 pressure taps, ISO • Orifice corner pressure taps, ASME • Orifice flange pressure taps, ASME • Orifice D and D/2 pressure taps, ASME • Orifice flange pressure taps, AGA 3 • Orifice 2.5D and 8D pressure taps • Small bore orifice, flange pressure taps • Small bore orifice, corner pressure taps • ISA 1932 nozzle • Long radius nozzle wall pressure taps, ISO • Long radius nozzle wall pressure taps, ASME • Standard Venturi pipe, rough-cast inlet, ISO • Standard Venturi pipe, machined inlet, ISO • Standard Venturi pipe, welded inlet, ISO • Standard Venturi pipe, rough-cast inlet, ASME • Standard Venturi pipe, machined inlet, ASME • Standard Venturi pipe, welded inlet, ASME • Venturi, nozzle, ISO • Pitot tube • Wedge element • Plus all non-standard flow sensors

  • 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 5

    ABB offers a complete range of differential flow sensors. We provide the full testing and documentation that your application needs. Whether the requirement is a single orifice plate with a simple Certificate of Conformity or a project requiring full material inspection, traceability, third-party verification, calibration and comprehensive data dossiers – ABB can satisfy all of the requirements. In addition compact solutions are available, OriMaster, a compact orifice flowmeter, and PitoMaster, a compact pitot flowmeter. Level measurement The following functions are available for level measurement with pressure and temperature compensation:

    • Level measurement with temperature compensation, on open tank

    • Level measurement with pressure and temperature compensation, on closed tank, with and without diaphragm seal

    • Fill volume measurement by means of tank shape specification

    • Drum water level measurement All of the functionality, including all the data required for compensated mass flow or for level measurement, is configured entirely using the PC-based DTM 266-MV. A simplified setting method, which uses the (optional) LCD indicator, is available for flow and level calculation.

    Change from two to one column

  • 6 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A

    Functional specification

    Measuring range limits and span limits

    Differential pressure sensor

    Sensor code Measuring range upper limit (URL) Lower range limit (LRL) Minimum measuring span

    A 1 kPa

    10 mbar

    4 in H2O

    1 kPa

    10 mbar

    4 in H2O

    0.05 kPa

    0.5 mbar

    0.2 in H2O

    C 6 kPa

    60 mbar

    24 in H2O

    6 kPa

    60 mbar

    24 in H2O

    0.2 kPa

    2 mbar

    0.8 in H2O

    F 40 kPa

    400 mbar

    160 in H2O

    40 kPa

    400 mbar

    160 in H2O

    0.4 kPa

    4 mbar

    1.6 in H2O

    L 250 kPa

    2500 mbar

    1000 in H2O

    250 kPa

    2500 mbar

    1000 in H2O

    2.5 kPa

    25 mbar

    10 in H2O

    N 2000 kPa

    20 bar

    290 psi

    2000 kPa

    20 bar

    290 psi

    20 kPa

    0.2 bar

    2.9 psi

    Absolute pressure sensor (second sensor)

    Sensor code Measuring range upper limit (URL) Lower range limit (LRL) Minimum measuring span

    1 600 kPa

    6 bar

    87 psi

    0 abs 6 kPa

    0.06 bar

    0.87 psi

    2 2000 kPa

    20 bar

    290 psi

    0 abs 20 kPa

    0.2 bar

    2.9 psi

    3 10000 kPa

    100 bar

    1450 psi

    0 abs 100 kPa

    1 bar

    14.5 psi

    4 41000 kPa

    410 bar

    5945 psi

    0 abs 410 kPa

    4.1 bar

    59.5 psi

    Change from one to two columns

  • 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 7

    Span limits

    Maximum measuring span = Measuring range upper limit (URL). For differential pressure measurements, can be adjusted up to ± URL (TD = 0.5) within the measuring range limits. Note To optimize performance characteristics, it is recommended that you select the transmitter sensor code with the lowest turn down ratio.

    Recommendation for square root function

    At least 10 % of measuring range upper limit (URL)

    Zero position suppression and elevation

    The zero position and span can be set to any value within the measuring range limits listed in the table if:

    • already set span minimum span

    Temperature input

    Process temperature range 200 to 850 °C ( 328 to 1562 °F) with external resistance thermometer (Pt100) in four-wire circuit.

    Damping

    Configurable time constant between 0 and 60 s. This is in addition to the sensor response time.

    Warm-up time

    Ready for operation as per specifications in less than 10 s with minimum damping.

    Insulation resistance

    > 100 M at 500 V DC (between terminals and ground)

  • 8 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A

    Operating limits

    Pressure limits

    Gauge pressure limits The transmitter models 266CSX can operate without damage within the following overpressure limits:

    Sensors Filling fluid Gauge pressure limits

    A Silicone oil 0.5 kPa abs., 5 mbar abs., 0.07 psia

    and 0.6 MPa, 6 bar, 87 psi

    or 2 MPa, 20 bar, 290 psi

    depending on code variant selected*

    A Fluorocarbon

    (Galden™)

    17.5 kPa abs., 175 mbar abs., 2.5 psia

    and 0.6 MPa, 6 bar, 87 psi

    or 2 MPa, 20 bar, 290 psi

    depending on code variant selected*

    C to N Silicone oil 0.5 kPa abs., 5 mbar abs., 0.07 psia

    and 2 MPa, 20 bar, 290 psi

    or 10 MPa, 100 bar, 1450 psi

    or 41 MPa, 410 bar, 5945 psi

    depending on code variant selected*

    C to N Fluorocarbon

    (Galden™)

    17.5 kPa abs., 175 mbar abs., 2.5 psia

    and 2 MPa, 20 bar, 290 psi

    or 10 MPa, 100 bar, 1450 psi

    or 41 MPa, 410 bar, 5945 psi

    depending on code variant selected*

    * 1 MPa, 10 bar, 145 psi for Kynar-PVDF

    Static pressure limits The transmitter models 266CSX can operate within the specifications with the following limits:

    Sensors Filling fluid Static pressure limits

    A Silicone oil 3.5 kPa abs., 35 mbar abs., 0.5 psia

    and 0.6 MPa, 6 bar, 87 psi

    or 2 MPa, 20 bar, 290 psi

    depending on code variant selected*

    A Fluorocarbon

    (Galden™)

    17.5 kPa abs., 175 mbar abs., 2.5 psia

    and 0.6 MPa, 6 bar, 87 psi

    or 2 MPa, 20 bar, 290 psi

    depending on code variant selected*

    C to N Silicone oil 3.5 kPa abs., 35 mbar abs., 0.5 psia

    and 2 MPa, 20 bar, 290 psi

    or 10 MPa, 100 bar, 1450 psi

    or 41 MPa, 410 bar, 5945 psi

    depending on code variant selected*

    C to N Fluorocarbon

    (Galden™)

    17.5 kPa abs., 175 mbar abs., 2.5 psia

    and 2 MPa, 20 bar, 290 psi

    or 10 MPa, 100 bar, 1450 psi

    or 41 MPa, 410 bar, 5945 psi

    depending on code variant selected*

    * 1 MPa, 10 bar, 145 psi for Kynar-PVDF

    Test pressure The transmitters can withstand a pressure test with the following line pressure without leaking:

    Model Test pressure

    266CSX 1.5 × nominal pressure (static

    pressure limit) simultaneously on

    both sides*

    * Meets hydrostatic test requirements of ANSI/ISA-S 82.03.

  • 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 9

    Temperature limits °C (°F)

    Environment This is the operating temperature.

    All models Ambient temperature limits

    Silicone oil 40 and 85 °C ( 40 and 185 °F)

    Fluorocarbon (Galden™) 40 and 85 °C ( 40 and 185 °F)

    All models Ambient temperature limits

    Integrated digital display (LCD)* 40 and 85 °C ( 40 and 185 °F)

    Viton™ gasket 20 and 85 °C ( 4 and 185 °F)

    PTFE gasket 20 and 85 °C ( 4 and 185 °F)

    * If may no longer be possible to read the digital display (LCD) clearly

    below 20 °C ( 4 °F) and above 70 °C (158 °F).

    Note For applications in potentially explosive environments, the temperature specified on the certificate / approval which depends upon the type of protection sought shall apply. Process

    All models Process temperature limits

    Silicone oil 40 and 121 °C ( 40 and 250 °F)*

    Fluorocarbon (Galden™) 40 and 121 °C ( 40 and 250 °F)**

    Viton™ gasket 20 and 121 °C ( 4 and 250 °F)

    PTFE gasket 20 and 85 °C ( 4 and 185 °F)

    * 85 °C (185 °F) for applications under 10 kPa, 100 mbar abs., 1.45 psia up

    to 3.5 kPa abs., 35 mbar abs., 0.5 psia

    ** 85 °C (185 °F) for applications below atmospheric pressure up to

    17.5 kPa abs., 175 mbar abs., 2.5 psia

    Transport and storage

    Models 266Cxx – Transport and storage

    Ambient temperature range 50 to 85 °C ( 58 to 185 °F)

    With integrated digital display (LCD):

    40 to 85 °C ( 40 to 185 °F)

    Relative humidity Up to 75 %

    Environmental limits Electromagnetic compatibility (EMC)

    In accordance with EN 61326 Overvoltage strength (with overvoltage protection): 4 kV (in accordance with IEC 1000-4-5 EN 61000-4-5)

    Pressure Equipment Directive (PED)

    Instruments with a maximum operating pressure of 41 MPa, 410 bar, 5,945 psi comply with Directive 2014/68/EU category III, module H.

    Humidity

    Relative humidity: up to 100 %. Condensation, icing: permitted.

    Vibration resistance

    Acceleration up to 2 g at frequencies of up to 1000 Hz (in accordance with IEC 60068-2-6).

    Shock resistance

    Acceleration: 50 g Duration: 11 ms (in accordance with IEC 60068-2-27).

    Humid and dusty atmospheres (IP rating)

    The transmitter is dust and sand-proof and protected against immersion effects in accordance with EN 60529 (2001) with IP 67 (IP 68 on request), by NEMA 4X, or by JIS C0920.

    Change from two to one column

  • 10 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A

    — Use in potentially explosive atmospheres Change from one to two columns

    Ex marking

    Devices in hazardous atmospheres with or without integrated digital display. For ambient temperatures 40 to 85 °C ( 40 to 185 °F) the information based on the temperature classes in the associated certificates, must be complied with. The temperature sensor circuit (Pt100) and the digital output (pulse / limit value output) must be connected in accordance with the requirements of the Ex certificate. ATEX / IECEx

    Ex-marking

    Type of protection ‘Ex d’ – flameproof (enclosure)

    ATEX (Code E2)

    II 1/2 G Ex db IIC T6 Ga/Gb Ta = 50 °C to +75 °C – IP67

    II 1/2 D Ex tb IIIC T85°C Db Ta = 50 °C to +75 °C – IP67

    IECEx (Code E9)

    Ex db IIC T6 Ga/Gb Ta = 50 °C to +75 °C – IP67

    Ex tb IIIC T85°C Db Ta = 50 °C to +75 °C – IP67

    Type examination

    certificate

    ATEX (Code E2)

    FM09AATEX0023X

    IECEx (Code E9)

    IECEx FME 16.0002X

    Ex-marking

    Type of protection ‘Ex n’ – non-sparking and ‘Ex t’ – enclosure

    ATEX (Code E3)

    II 3 G Ex nA nC IIC T6/T5/T4 nA Gc – IP67

    II 3 D Ex tc IIIC T85°C Dc – IP67

    IECEx (Code ER)

    Ex nA nC IIC T6/T5/T4 nA Gc – IP67

    Ex tc IIIC T85°C Dc IP67

    Type examination

    certificate

    ATEX (Code E3 )

    FM09AATEX0025X

    IECEx (Code ER)

    IECEx FME 16.0004X

    FM (USA and Canada)

    Ex-marking

    Type of protection Explosion proof

    Explosion proof (US):

    Class I, Div. 1, Groups A, B, C, D Ta = 50 to 85 °C

    Explosion proof (Canada):

    Class I, Div. 1, Groups A, B, C, D / T5 Ta = 50 to 85 °C

    Dust Ignition Proof:

    Class II/III, Div. 1, Groups E, F, G D Ta = 50 to 85 °C

    Type of protection Non-Incendive

    Class II/III, Div. 1, Groups E, F, G / T5 Ta = 50 to 85 °C

    Type of protection Energy limited

    Energy limited (US):

    Class I Zone 2, AEx nA nC IIC T6…T4 Ta = 50 to 85 °C

    Energy limited (Canada):

    Class I Zone 2, Ex nA nC IIC T6…T4 Ta = 50 to 85 °C

    FM approvals USA (code ET)

    FM16US0066X

    Canada (code ET)

    FM16CA0036X

    Type 4X, IP67 for all above markings.

    Combined ATEX, FM and IECEx approvals

    Code EN = E2+E9+E3+ER+ET

  • 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 11

    — Electrical data and options

    Power supply

    Devices with Modbus communication

    Terminals PWR + / PWR

    Supply voltage 10.5 to 30 V DC

    The transmitter operates on terminal voltage of 10.5 to 30 V DC. The quiescent supply current is 10 mA typically. The transmitting supply current does not exceed 25 mA.

    Output signal

    Modbus® RS 485 with 8 bit Remote Terminal Unit (RTU) data transmission.

    Modbus® interface

    Configuration

    (HART®-RS485)

    Via an RS485 interface in connection with

    Asset Vision Basic (DAT200) a HART®

    communication DTM and a corresponding

    Device Type Manager (DTM)

    Operating

    (Modbus® communication)

    Modbus RTU – 2-wire half-duplex RS485 serial

    connection

    Baud rate 1200, 2400, 4800, 9600

    Factory setting: 9600 bps

    Parity None, even, odd

    Factory setting: none

    Typical response time < 100 milliseconds

    Response delay time 0 to 200 milliseconds

    Factory setting: 50 milliseconds

    Device address 1 to 247

    Factory setting: 247

    Register address offset One base

    LCD display

    M10142 Figure 2: LCD display (example)

    Integral LCD display (code L1) • Wide screen LCD display, 128 × 64 pixel, 52.5 × 27.2 mm

    (2.06 × 1.07 in), dot matrix, multilingual. • Four buttons for device configuration and management. • Easy setup for quick commissioning. • Customized visualizations which the user can select. • Total value and actual value flow indication. The display can also be used to show static pressure, sensor temperature, and diagnosis notice, as well as make configuration settings. Integral LCD display with TTG-(Through-The-Glass) operation (code L5) As with the integral LCD display above, but featuring an innovative TTG (Through-The-Glass) button technology which can be used to activate the device's configuration and management menus without having to remove the transmitter housing cover. The TTG (Through-The-Glass) buttons are protected against accidental activation.

  • 12 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A

    — Measuring accuracy

    Reference conditions according to IEC 60770: • Ambient temperature 20 C (68 F), rel. humidity 65 %,

    atmospheric pressure 1.013 hPa (1.013 mbar). • Position of measuring cell (separating diaphragm

    areas) vertical. • Measuring span based on zero point. • Separating diaphragms made from stainless steel

    AISI 316 L or Hastelloy, gasket Viton / Perbunan, silicone oil filling fluid

    • Digital trim values equal to the span end points. Unless otherwise stated, errors are specified as a % of the measuring span value. Some measuring accuracy levels relating to the upper measuring range limit (URL) are affected by the current turn down (TD); i.e., the ratio of the upper measuring range limit to the already set span. Note FOR OPTIMUM MEASURING ACCURACY, IT IS RECOMMENDED THAT YOU SELECT THE SENSOR CODE WHICH WILL PROVIDE THE LOWEST TD VALUE.

    Dynamic response

    In accordance with IEC 61298-1

    Sensors Time constant

    (63.2 % of total step response)

    Sensors F to R 150 ms

    Sensor C 400 ms

    Sensor A 1000 ms

    266CXX: Delay time for all sensors 70 ms

    Response time (total) = delay time + time constant

    Measuring error

    In % of calibrated span, consisting of terminal-based non-linearity, hysteresis, and non-repeatability.

    Model DP-Sensor For TD range Measuring error

    266CSH A to N From 1:1 to 10:1 ±0.075 %

    A From 10:1 to 20:1 ±(0.075 + 0.005 × TD 0.05) %

    C From 10:1 to 30:1 ±(0.075 + 0.005 × TD 0.05) %

    F to N From 10:1 to 100:1 ±(0.075 + 0.005 × TD 0.05) %

    266CST A to N From 1:1 to 10:1 ±0.04 %

    A From 10:1 to 20:1 ±(0.04 + 0.005 × TD 0.05) %

    C From 10:1 to 30:1 ±(0.04 + 0.005 × TD 0.05) %

    F to N From 10:1 to 100:1 ±(0.04 + 0.005 × TD 0.05) %

    Recommendation for square root function At least 10 % of upper measuring range limit (URL)

    Model Pabs sensor (second sensor) Measuring error

    266CXX 1 to 3 ±0.05 %

    4 ±0.075 %

    Model Process temperature measurement

    (Pt100) in acc. with IEC 60751

    Measuring error -

    transmitter part

    266CXX 200 to 850 °C ( 328 to 1562 °F) ±0.3 K (0.54 °F)

    266CXX: The accuracy of the mass or standard volume flow is not affected by the accuracy of the dp, p, and T measurement alone; rather, it also depends upon the primary device used (flow coefficient), the pressure and temperature range to be compensated, as well as other parameters. In typical applications, the flow measurement accuracy (without the primary device accuracy) is ±0.7 to 0.9 % of the mass flow.

  • 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 13

    Ambient temperature Per 20 K change within the limits of 40 to 85 °C (per 36 °F change within the limits of 40 to 185 °F):

    Model Sensor For TD

    range

    266CSH A 10:1 ±(0.08 % URL + 0.06 % measuring span)

    C to N 10:1 ±(0.04 % URL + 0.06 % measuring span)

    266CST A 10:1 ±(0.06 % URL + 0.045 % measuring span)

    C to N 10:1 ±(0.03 % URL + 0.045 % measuring span)

    In the event of a change to the ambient temperature of

    10 °C to 60 °C (14 to 140 °F):

    Model Sensor For TD

    range

    266CSH A 10:1 ±(0.16 % URL + 0.065 % measuring span)

    C to N 10:1 ±(0.08 % URL + 0.065 % measuring span)

    266CST A 10:1 ±(0.12 % URL + 0.05 % measuring span)

    C to N 10:1 ±(0.06 % URL + 0.05 % measuring span)

    Per 10 K change within the limits of 40 to 10 °C or 60 to 85 °C (per 18 °F change within the limits of 40 to 14 °F or 140 to 185 °F):

    Model Sensor For TD

    range

    266CSH A 10:1 ±(0.066 % URL + 0.04 % measuring span)

    C to N 10:1 ±(0.033 % URL + 0.04 % measuring span)

    266CST A 10:1 ±(0.05 % URL + 0.03 % measuring span)

    C to N 10:1 ±(0.025 % URL + 0.03 % measuring span)

    Absolute pressure sensor Per 20 K change between the limits of 40 to 85 °C ( 40 to 185 °F):

    ±(0.08 % URL + 0.08 % measuring span) Limited to ±(0.1 % URL + 0.1 % measuring span) for the entire temperature range of 125 K within the limits of 40 to 85 °C ( 40 to 185 °F). Static pressure

    Zero signal errors may be calibrated out at operating pressure.

    Measuring range Sensor A Sensors C, F, L, N

    Zero signal error Up to 2 bar:

    0.05 % URL

    Up to 100 bar:

    0.05 % URL

    > 2 bar: 0.05 % URL/bar > 100 bar: 0.05 %

    URL/100 bar

    Span error Up to 2 bar:

    0.05 % measuring span

    Up to 100 bar:

    0.05 % measuring span

    > 2 bar: 0.05 %

    Measuring span / bar

    > 100 bar: 0.05 %

    Measuring span / 100 bar

  • 14 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A

    — … Measuring accuracy Electromagnetic field Meets all requirements of EN 61326 Mounting position Rotations in the plane of the diaphragm have a negligible effect. A tilt from the vertical of up to 90° causes a zero [point] shift of up to 0.35 kPa (3.5 mbar, 1.4 in H2O), which can be corrected by making an appropriate zero position adjustment. There is no effect on the measuring span. Long-term stability Sensors C to N:

    ±0.15 % of URL over a period of 10 years (±0.05 % URL/year)

    Sensor A: ±0.3 % of URL over a period of 10 years (±0.2 % URL/year)

    Total performance Only for differential pressure measurement; similar to DIN 16086. Within an ambient temperature change range of

    10 to 60 °C (14 to 140 °F), up to 10 MPa, 100 bar, 1450 psi static pressure.

    Model Sensor For TD range Total performance (DP)

    266CSH C to N 1:1 ±0.17 % of calibrated span

    266CST C to N 1:1 ±0.14 % of calibrated span

    The total performance includes the measuring error (non-linearity including hysteresis and non-repeatability), the thermal change in the ambient temperature as regards the zero signal and measuring span, as well as the effect of the static pressure on the zero signal and measuring span.

    Eperf Total Performance

    E TZ Effect of the ambient temperature on the zero signal

    E TS Effect of the ambient temperature on the measuring span

    E PZ Effect of the static pressure on the zero signal

    E PS Effect of the static pressure on the measuring span

    Elin Measuring error

    — Technical specification Note Please refer to the order information to check the availability of different versions of the relevant model.

    Materials

    Process separating diaphragms* Stainless steel 1.4435 (AISI 316L); Hastelloy C276®; Monel 400®; Monel 400®, gold-plated; Tantalum

    Process flanges, adapters, screw plugs, and vent / drain valves*

    Stainless steel 1.4404 / 1.4408 (AISI 316L); Hastelloy C276®; Monel 400®; Kynar (flange made from stainless steel AISI 316L with PVDF insert)

    Sensor filling fluid

    Silicone oil; Fluorocarbon (Galden™) Mounting bracket**

    Galvanized C steel with chromium passivation; Stainless steel AISI 316, AISI 316 L

    Seals*

    Viton™ (FPM); Buna® (NBR); EPDM; PTFE or FEP-coated Viton™ (only for PVDF Kynar process connection); Graphite

    Pressure sensor housing

    Stainless steel 1.4404 (AISI 316L) Screws and nuts

    Screws and nuts made from stainless steel AISI 316, class A4-70 as per UNI 7323 (ISO 3506) in compliance with NACE MR0175 Class II

    Electronics housing and cover

    Aluminum alloy (copper content 0.3 %) with baked epoxy finish (color RAL9002); Stainless steel AISI 316L.

    Cover O-ring

    Buna N® (Perbunan) * Wetted parts of the transmitter. ** U-bolt material: Stainless steel AISI 400;

    Screw material: High-strength alloy steel or stainless steel AISI 316

    2lin

    2PSΔ

    2PZΔ

    2TSΔTZΔperf EEE)EE(E

  • 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 15

    Local zero point, measuring span, and write protection settings

    Fiber glass-reinforced polyphenylene oxide (removable) Plates

    Stainless steel AISI 316 for transmitter name plate, certification plate, optional measuring point tag plate. Settings plate attached to electronics housing, and optional tag plate with customer data. All plates laser-labeled.

    Calibration

    Standard: 0 to measuring range upper limit, for ambient temperature and atmospheric pressure

    Optional: To specified measuring span

    Surge protection

    The 266 Modbus multivariable pressure transmitter comes standard with a surge / transient suppression scheme build into the termination block. • Up to 4 kV on power supply • Up to 2 kV on I/O • Voltage: 1.2 s rise time / 50 s delay time at half value

    Optional accessories Mounting bracket

    For vertical and horizontal 60 mm (2 in) pipes or wall mounting

    LCD display

    Can be rotated in 90° increments into 4 positions Additional tag plates

    Code I2: For measuring point tag (up to 30 characters) and calibration specifications (up to 30 characters: lower and upper value plus unit), attached to transmitter housing. Code I1: For customer data (4 lines with 30 characters each), attached to transmitter housing with wire.

    Cleaning stage for oxygen applications (O2)

    Refer to Ordering Information on page 23. Certificates

    Test, design, characteristics, material traceability. Refer to Ordering Information on page 23.

    Name plate and operating instruction language

    Refer to Ordering Information on page 23.

    Process connections

    Flanges

    ¼-18 NPT on the process axis Adapters

    ½-14 NPT on the process axis Center distance

    54 mm (2.13 in) between flanges; 51 mm, 54 mm, or 57 mm (2.01 in, 2.13 in, or 2.24 in) between adapters

    Fastening screw threads

    -20 UNF with 41.3 mm center distance Or with process flange code C: • M10 with operating pressures of up to 10 MPa,

    100 bar, 1450 psi • M12 with higher operating pressures of up to 41 MPa,

    410 bar, 5945 psi

  • 16 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A

    — … Technical specification

    Electrical connections

    Cable entry

    Two ½-14 NPT or M20 × 1.5 threaded bores for cable glands, directly on housing.

    Terminals • Two terminal for power (+ and ). • Two terminals for RS485 communication. • Four terminals for a Pt100 resistance thermometer with

    four-wire technology. For wire cross sections of up to 2.5 mm2 (14 AWG) and connection points for testing and communication purposes. Grounding

    Internal and external ground terminals are provided for 6 mm2 (10 AWG) wire cross sections.

    Mounting position

    The transmitters can be installed in any position. The electronic housing can be rotated into any position. A stop is provided to prevent overturning.

    Weight

    Pressure transmitter without options

    Approximately 3.8 kg (8.4 lb); Add 1.5 kg (3.3 lb) for housings made from stainless steel.

    Packaging

    Add 650 g (1.5 lb) for packaging

    Packaging

    Carton with dimensions of approx. 28 × 23 × 24 cm (11 × 9 × 9 in)

    — Configuration Standard configuration Transmitters are calibrated at the factory to the customer's specified measuring range. The calibrated range and measuring point number are specified on a tag plate. If this data has not been specified, the transmitter will be delivered with the plate left blank and the following configuration.

    Parameter Value

    Device mode Operate (Modbus)

    Device address 247

    Multivariable calculation No calculation

    Software tag (max. 8 characters) blank

    Optional LCD display PV (DP) in kPa; output in percent as

    bargraph display

    (DP) Physical unit kPa

    (DP) Output scale 0% 0 (LRL)

    (DP) Output scale 100% Upper Range Limit (URL)

    Output Linear

    Damping 0.125 s

    (PS) Physical unit MPa

    (PS) Output scale 0% 0 (LRL)

    (PS) Output scale 100% Upper Range Limit (URL)

    Damping 0.125 s

    (T) Physical unit °C

    (T) Output scale 0% 200 (LRL)

    (T) Output scale 100% +850 Upper Range Limit (URL)

    Damping 10 s

    Any or all of the configurable parameters listed above – including the lower and upper range values (with the same unit of measurement) – can easily be changed using a PC running the configuration software with the DTM for 266Cxx-Modbus. Specifications concerning the flange type and materials, O-ring and vent / drain valve materials, and additional device options are stored in the transmitter database. Note For device functionality and simulation purpose a 178 resistor (206 °C [402.8 °F]) and 2 jumpers are installed in the PT100 connection

    Change from two to one column

  • 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 17

    Mounting dimensions Transmitter with barrel housing – Horizontal flanges

    M10019-02

    29 (1.14)

    18 (0.71)18 (0.71)

    210

    (8

    .28

    )

    60 (2.36)**72 (2.83)***

    56 (2.21) 53 (2.09)

    12 (

    0.4

    7)

    90 (3.54) 33 (1.30)

    65

    (2

    .53

    )

    41

    3 (

    1.6

    3)

    ,

    9 (0.35)

    *

    142 (5.59)

    179

    (7.

    02

    )

    91 (3.58)

    145

    (5

    .70

    )

    1 2

    3

    4

    5

    10

    6

    7

    8

    9

    1 Push buttons

    2 Name plate

    3 Certification plate

    4 Vent / drain valve

    5 Process connection

    6 Terminal side

    7 LCD display housing cover

    8 Electronics side

    9 Process flange adapter

    0 Space for removing the cover

    * 54 mm (2.13 in) via ¼-18 NPT process flanges; 51 mm (2.01 in), 54 mm (2.13 in), or 57 mm (2.24 in) via ½-14 NPT adapter flanges.

    Note Process connection and seal groove satisfy IEC 161518. Thread for attaching adapter flanges or other components (for example manifold) on the process flange: -20 UNF.

    ** With screw plug

    *** With vent / drain valve

    Figure 3: Barrel housing – horizontal flanges, Dimensions in mm (in)

  • 18 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A

    — … Mounting dimensions Transmitter with barrel housing – Vertical flanges

    M10139-01

    142 (5.59)

    54 (2.13)

    91 (3.58)

    31

    (1.2

    2)

    25

    1 (9

    .88

    )

    216

    (8

    .50

    )

    18 (0.71)

    28 (1.10) LCD (L1)24 (0.95) TTG-LCD (L5)

    53 (2.09)

    9 (0.35)

    110 (4.33)

    18 (0.71)

    41,3 (1.63)

    1 2

    3

    4

    5

    6

    9

    8

    0

    7

    1 Pusch buttons

    2 Name plate

    3 Certification plate

    4 Vent / drain valve

    5 Process connection

    6 Terminal side

    7 LCD display housing cover

    8 Electronics side

    9 Process flange adapter

    0 Space for removing the cover

    Figure 4: Barrel housing - vertical flanges, Dimensions in mm (in)

  • 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 19

    Transmitter with mounting bracket, for vertical or horizontal mounting on 60 mm (2 in) pipe pipe

    M10020-01

    89

    (3

    .48

    )

    142 (5.59)

    ¹�

    179

    (7.

    02)

    91 (3.58)

    116 (4.57)

    179

    (7.

    02)

    91 (3.58)

    123 (4.86)

    *

    142 (5.59)

    72 (2.83)

    210

    (8

    .28

    )

    107 (4.21)

    53 (2.09)

    45 (1.77) 33 (1.30)

    56 (2.21)

    29 (1.14)

    18 (0.71)18 (0.71)

    12 (

    0.4

    7)60 (2.36)**72 (2.83)***

    29 (1.14)

    18 (0.71)18 (0.71)

    210

    (8

    .28

    )

    107 (4.21)

    72 (2.83)

    56 (2.21) 53 (2.09)

    12 (

    0.4

    7)

    45 (1.77) 33 (1.30)

    60 (2.36)²�

    72 (2.83)³�

    * 54 mm (2,13 in) via ¼-18 NPT process flanges;

    51 mm (2,01 in), 54 mm (2,13 in), or 57 mm (2.24 in) via ½-14 NPT adapter flanges.

    Note Process connection and seal groove satisfy IEC 161518. Thread for attaching adapter flanges or other components (for example manifold) on the process flange: -20 UNF.

    ** With screw plug

    *** With vent / drain valve

    Figure 5: Pipe mounting – barrel housing, Dimensions in mm (in)

  • 20 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A

    — … Mounting dimensions Transmitter with DIN aluminum housing – horizontal flanges with mounting bracket for vertical or horizontal mounting on 60 mm (2 in) pipe

    M10021-01

    65

    (2

    .54

    )8

    3 (

    3.2

    8)

    136 (5.35)

    116 (4.57)*

    185 (7.25)

    29 (1.14)

    18 (0.71)

    53 (2.09)

    18 (

    0.7

    1)

    86 (3.40)

    15 (

    0.5

    7)

    129

    (5

    .06

    )

    72 (2.83)

    116 (4.57)

    178

    (6

    .99

    )

    180

    (7.

    08

    )

    142 (5.59)185 (7.25)

    29 (1.14)

    18 (0.71)

    53 (2.09)

    18 (

    0.7

    1)

    107

    (4.2

    1)

    86 (3.40)

    *

    * 54 mm (2.13 in) via ¼-18 NPT process flanges;

    51 mm (2.01 in), 54 mm (2.13 in), or 57 mm (2.24 in) via ½-14 NPT adapter flanges.

    Note Process connection and seal groove satisfy IEC 161518. Thread for attaching adapter flanges or other components (for example manifold) on the process flange: -20 UNF.

    Figure 6: Pipe mounting – DIN housing, Dimensions in mm (in)

  • 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 21

    Transmitter with flat bracket, for vertical or horizontal mounting on 60 mm (2 in) pipe

    M10022-01

    70 (2.75)

    70 (

    2.7

    5)

    179

    (7.

    02

    )

    91 (3.58)

    142 (5.59)

    49

    (1.

    93

    )

    29 (1.14)

    18 (0.71)18 (0.71)

    210

    (8

    .28

    )

    56 (2.21) 53 (2.09)

    45 (1.77) 33 (1.30)12

    (0

    .47

    )

    60 (2.36)*72 (2.83)**

    25 (0.98)

    44 (1.71)

    89 (3.48)

    118

    (4

    .63

    )

    *

    * With screw plug

    ** With vent / drain valve

    Figure 7: Flat bracket for pipe mounting – barrel housing, Dimensions in mm (in)

  • 22 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A

    Electrical connections

    M11189

    COMM.A(+)

    B(-)

    SURGEINSIDE

    RTD

    Modbus9...30 V DC

    PE

    1 3

    4

    2

    5

    1 Terminals for Modbus® interface

    2 Terminal for PE / Cable Shield

    3 Terminals for power supply

    4 Terminals for Pt100 resistance thermometer

    5 Ground terminal PE Potential equalization

    Figure 8: Connection on the device (example)

  • 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 23

    Ordering Information

    Model 266CSH and 266CST

    Base model

    Multivariable transmitter for mass flow and level, base accuracy 0.075 % 266CSH X X X X X X X

    Multivariable transmitter for mass flow and level base accuracy 0.04 % 266CST X X X X X X X

    Sensor Span Limits

    0.05 and 1 kPa (0.5 and 10 mbar 0.2 and 4 in H2O) A*

    0.2 and 6 kPa (2 and 60 mbar / 0.8 and 24 in H2O) C

    0.4 and 40 kPa (4 and 400 mbar / 1.6 and 160 in H2O) F

    2.5 and 250 kPa (25 and 2500 mbar / 10 and 1000 in H2O) L

    20 and 2000 kPa (0.2 and 20 bar / 2.9 and 290 psi) N

    Maximum Working Pressure

    0 and 0.6 MPa / 0 and 6 bar / 0 and 87 psi (only with Sensor Span Limits code A) 1

    0 and 2 MPa / 0 and 20 bar / 0 and 290 psi 2

    0 and 10 MPa / 0 and 100 bar / 0 and 1450 psi / (not with Sensor Span Limits code A) 3

    0 and 41 MPa / 0 and 410 bar / 0 and 5945 psi / (not with Sensor Span Limits code A) 4

    Diaphragm Material / Fill Fluid

    AISI 316L SST (1.4435) / Silicone oil (NACE) S

    Hastelloy C-276 / Silicone oil (NACE) K

    Monel 400 / Silicone oil (NACE) M

    Monel 400 gold-plated / Silicone oil (NACE) V

    Tantalum / Silicone oil (NACE) T

    AISI 316L SST (1.4435) / Inert fluid - Galden (Suitable for oxygen applications) (NACE) A**

    Hastelloy C-276 / Inert fluid - Galden (Suitable for oxygen applications) (NACE) F**

    Monel 400 / Inert fluid - Galden (Suitable for oxygen applications) (NACE) C**

    Monel 400 gold-plated / Inert fluid - Galden (Suitable for oxygen applications) (NACE) Y**

    Tantalum / Inert fluid - Galden (Suitable for oxygen applications) (NACE) D**

    Process Flanges and Adapters Material / Connection

    AISI 316L SST (1.4404 / 1.4408) / ¼-18 NPT female direct / (horizontal connection) (NACE) A

    AISI 316L SST (1.4404 / 1.4408) / ½-14 NPT female through adapter / (horizontal connection) (NACE) B

    AISI 316L SST (1.4404 / 1.4408) / ¼-18 NPT female direct (DIN 19213) / (horizontal connection) (NACE) C

    Hastelloy C-276 / ¼-18 NPT female direct / (horizontal connection) (NACE) D

    Hastelloy C-276 / ½-14 NPT female through adapter / (horizontal connection) (NACE) E

    Monel 400 / ¼-18 NPT female direct / (horizontal connection) (NACE) G

    Monel 400 / ½-14 NPT female through adapter / (horizontal connection) (NACE) H

    Kynar (PVDF) / ¼-18 NPT female direct (MWP = 1 MPa / 10 bar / 145 psi) / (insert on side of flange) P

    AISI 316L SST (1.4404 / 1.4408) / ¼-18 NPT female direct / (vertical connection) (NACE) Q

    * Not available with Diaphragm Material code M, V, T, C, Y, D

    ** Suitable for Oxygen service

    Continued see next page

  • 24 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A

    — … Ordering Information Base model

    Multivariable transmitter for mass flow and level, base accuracy 0.075 % 266CSH X X X

    Multivariable transmitter for mass flow and level base accuracy 0.04 % 266CST X X X

    Bolts Material / Gaskets Material

    AISI 316L SST (NACE - non exposed) / Viton (Suitable for oxygen applications) 3*

    AISI 316L SST (NACE - non exposed) / PTFE (Max. 25 MPa / 250 bar / 3625 psi) 4

    AISI 316L SST (NACE - non exposed) / EPDM 5

    AISI 316L SST (NACE - non exposed) / Perbunan 6

    AISI 316L SST (NACE - non exposed) / Graphite 7

    AISI 316L SST (NACE - non exposed) / FEP (only available with Kynar [PVDF] process connection) T

    Housing Material / Electrical Connection

    Aluminium alloy (Barrel type) / ½-14 NPT A

    Aluminium alloy (Barrel type) / M20 × 1.5 B

    AISI 316L SST (Barrel type) / ½-14 NPT S

    AISI 316L SST (Barrel type) / M20 × 1.5 T

    Output

    Modbus RS 485 / No additional options N

    Modbus RS 485 / Options requested (to be ordered by Additional ordering code) 6

    * Suitable for Oxygen service

    Additional ordering information

    Additional ordering information

    Multivariable transmitter for mass flow and level, base accuracy 0.075 % 266CSH XX XX

    Multivariable transmitter for mass flow and level base accuracy 0.04 % 266CST XX XX

    Vent and Drain Valve Material / Position

    AISI 316L SST (1.4404) / On process axis (NACE) V1

    AISI 316L SST (1.4404) / On flanges side top (NACE) V2

    AISI 316L SST (1.4404) / On flanges side bottom (NACE) V3

    Hastelloy C-276 / On process axis (NACE) V4

    Hastelloy C-276 / On flanges side top (NACE) V5

    Hastelloy C-276 / On flanges side bottom (NACE) V6

    Monel 400 / On process axis (NACE) V7

    Monel 400 / On flanges side top (NACE) V8

    Monel 400 / On flanges side bottom (NACE) V9

    Explosion Protection Certification

    ATEX Group II Category 1/2 GD – Flameproof Ex d E2

    ATEX Group II Category 3 GD – Type of protection "N" Ex nL design compliance E3

    FM Approvals (USA and Canada) Explosion proof and Type „n“ ET

    Combined ATEX, IECEx, FM Approvals (USA and Canada) EN

    IEC Approval Group II Category 1/2 GD – Flameproof Ex d E9

    IEC Approval Group II Category 3 GD – Type of protection "N" Ex nL design compliance ER

    Continued see next page

  • 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 25

    Additional ordering information

    Multivariable transmitter for mass flow and level, base accuracy 0.075 % 266CSH XX XX XX XX XX XX

    Multivariable transmitter for mass flow and level base accuracy 0.04 % 266CST XX XX XX XX XX XX

    Integral LCD

    With integral LCD display L1

    TTG (Through The Glass) integral digital LCD display L5

    Mounting Bracket Shape / Material

    For pipe mounting / Carbon steel (not suitable for AISI housing) B1

    For pipe mounting / AISI 316 SST (1.4401) (not suitable for AISI housing) B2

    For wall mounting / Carbon steel (not suitable for AISI housing) B3

    For wall mounting / AISI 316 SST (1.4401) (not suitable for AISI housing) B4

    Flat type bracket / AISI 316 SST (1.4401) (suitable for AISI housing) B5

    Operating Instruction Language

    English M5

    Label and Tag Language

    German T1

    Italian T2

    Spanish T3

    French T4

    Additional Tag Plate

    Supplemental wired-on stainless steel plate (4 lines, 32 characters each) I1

    Laser printing of tag on stainless steel plate I2

    Stainless steel tag, certification and wire-on plates I3

    Configuration

    Standard pressure = in H2O / psi at 68 °F N2

    Standard pressure = in H2O / psi at 39.2 °F N3

    Standard pressure = in H2O / psi at 20 °C N4

    Standard pressure = in H2O / psi at 4 °C N5

    Custom N6

    Continued see next page

  • 26 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A

    — … Ordering Information Additional ordering information for model 266CSH

    Multivariable transmitter for mass flow and level, base accuracy 0.075 % 266CSH XX XX XX XX XX

    Multivariable transmitter for mass flow and level base accuracy 0.04 % 266CST XX XX XX XX XX

    Preparation Procedure

    Oxygen service cleaning, Pmax = 12 MPa (120 bar, 1740 psi) or maximum working pressure (lower value),

    Tmax = 60 °C / 140 °F (only available with inert fill and Viton gasket)

    P1

    Hydrogen service preparation (Fluid film) P2

    Certificates

    Inspection certificate 3.1 acc. EN 10204 of calibration C1

    Inspection certificate 3.1 acc. EN 10204 of cleanliness stage C3

    Inspection certificate 3.1 acc. EN 10204 of helium leakage test of the sensor module C4

    Inspection certificate 3.1 acc. EN 10204 of pressure test C5

    Declaration of compliance with the order 2.1 acc. EN 10204 for instrument design C6

    Separate calibration record CC

    PMI test on wetted parts CT

    Material Traceability

    Inspection certificate 3.1 acc. EN 10204 of pressure-bearing and process wetted parts with analysis certificates as

    material verification

    H3*

    Material certificate 2.2 acc. EN 10204 of the pressure bearing and process wetted parts H4

    Connector

    With cable gland M20 × 1.5 U8

    Housing Accessories

    Integral mount manifold (price adder just for assembling, not for manifold) A1

    * Minor Parts with Factory Certificate acc. to EN 10204

  • 266CSH / CST MULTIVARIABLE PRESSURE TRANSMITTER | DS/266CSH/CST/MODBUS-EN REV. A 27

    Standard delivery scope (changes possible with additional ordering code)

    • Adapters supplied loose • Sealing plugs for horizontal connection flanges on the process axis; not for PVDF Kynar insert or for vertical connection

    flanges (no vent / drain valves) • For standard applications (without explosion protection) • No display, no mounting bracket, no surge protector • Operating instruction and English labelling • Configuration with kPa and °C units • No test, inspection, or material certificates

    Important remark for all models

    The selection of suitable wetted parts and filling fluid for compatibility with the process media is a customers responsibility, if not otherwise notified before manufacturing.

    NACE compliance information

    1 The materials of constructions comply with metallurgical recommendations of NACE MR0175/ISO 15156 for sour oil field production environments. As specific environmental limits may apply to certain materials, please consult latest standard for further details. Materials AISI 316 / AISI 316L, Hastelloy C-276, Monel 400 also conform to NACE MR0103 for sour refining environments.

    2 NACE MR0175 addresses bolting requirements in two classes: • Exposed bolts:

    Bolts directly exposed to the sour environment or buried, encapsulated or anyway not exposed to atmosphere • Non exposed bolts:

    The bolting must not be directly exposed to sour environments, and must be directly exposed to the atmosphere at all times.

    266CSH, 266CST bolting identified by “NACE” are in compliance to the requirements of NACE MR0175 when considered “non exposed bolting” Change from one to two columns

    Trademarks

    Buna-N is a registered trademark of DuPont Dow Elastomers.

    Hastelloy is a registered trademark of Haynes International, Inc.

    Monel is a registered trademark of Special Metals Corporation

    Modbus is a registered trademark of the Modbus Organization

    Galden is a Montefluos trademark

    Kynar is an Elf Atochem North America Inc. trademark

    Viton is a DuPont de Nemours trademark

    Sales Service

  • — ABB Limited Measurement & Analytics Howard Road, St. Neots Cambridgeshire, PE19 8EU UK Tel: +44 (0)870 600 6122 Fax: +44 (0)1480 213 339 Email: [email protected] ABB Automation Products GmbH Measurement & Analytics Schillerstr. 72 32425 Minden Germany Tel: +49 571 830-0 Fax: +49 571 830-1806 abb.com/pressure

    ABB Inc. Measurement & Analytics 125 E. County Line Road Warminster, PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183 ABB S.p.A. Measurement & Analytics Via Luigi Vaccani 4 22016 Tremezzina (CO) Italy Tel: +39 0344 58111 Email: [email protected]

    DS/

    266C

    SH/C

    ST/M

    OD

    BU

    S-EN

    Rev

    . A

    06.

    2018

    — We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB. Copyright© 2018 ABB All rights reserved 3KXP400011R1001

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages false /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 240 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages false /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects true /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly true /PDFXNoTrimBoxError false /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier (FOGRA27) /PDFXOutputCondition () /PDFXRegistryName (http://www.color.org) /PDFXTrapped /False

    /CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure false /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MarksOffset 6 /MarksWeight 0.250000 /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /DocumentCMYK /PageMarksFile /RomanDefault /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /UseDocumentProfile /UseDocumentBleed false >> > ]>> setdistillerparams> setpagedevice