Recl
oser
Con
trol
ler
g Energy
Protection • ACParametersLevelTrips
-PhaseOvercurrent
-NeutralOvercurrent• Overvoltage• Undervoltage• Voltageunbalance• 3settinggroupsfordifferentdetectionapplications
Automation & Control• Auto-Recloser4ShotstoLockout• CLPColdloadpickup• Auto/Manual,Local/Remotecontrol• CustomizedautomationschemesusingFlexLogic™
Metering & Monitoring• Metering-current,voltage,power,energy,frequencyandPF• EventRecorder-Upto256timetaggedeventswith1msres• Enhancedsystemdiagnosticsandreporting
Communications• NetworkingInterface-twowireRS485
-Multipleprotocols(Modbus®,DNP3.0)-Optionalwirelesscommunications(radioorcellular)
• UserInterface
-FrontpanelUSBport-4lineHMIdisplay-20systemstatusLED’s
Security & EnerVista™ Software• 4-Leveldevicesecuritytomaintainauthorizedaccessonly• Simplifieddeviceconfigurationsoftwaretoolandindustry
leadingsuiteofsoftwaretoolstomanageandmaintainMultilindevices
Hardware• 3:CTsupportstraditionalaswellaslinepostsensors• 6:VTsupportstraditionalaswellasLEAinputs• Expandableinputsandoutputsforadvancedapplications
• 4shotauto-recloser• 3settinggroupsenabledifferentsettingselectionsbasedon
switchedconditions• AdvancedlogicengineandmultipleIOsforcreating
customizedcontrolschemes• Improveperformanceandreliabilitybyintegratingremote
feedersintoDMS/OMS/SCADA• Realtimemonitoringofenergytotracknon-technicallosses• Improvesassetmonitoringandmaintenanceschedules
basedonmeasuredenergydischarge
• Compatiblewithlowenergyanalog(0-10Vor0-1V)voltagesensors
• Enhancedtroubleshootingtoolsincludingsequenceofeventrecordsanddatalogger
• Reducessetuptimeandcommissioningtimewitheasy-to-usesoftwaretoolsandquicksetupkeysonfrontpanel
• Commonhardware,firmwareandsoftwareplatformwithotherMultilinDistributionAutomation(DA)controllers
• Ruggedconstructiondesignedforoutdooruseinharshenvironment(-40°Cto+60°C)
• AutomaticcontrolofOverHead&PadMountedReclosersforFaultdetection&Isolation.
• AutomaticcontrolofPadMountedSwitchGear
• InterfacingwithFDIR/FLISRforfaultisolationand&auto-restoration.
Recloser Controller
Multilin™
DGCR
FEAtuRES
APPliCAtionS
KEy BEnEFitS
Multilin DGCRRecloser ControllerRe
clos
er C
ontr
olle
r
www.GEDigitalEnergy.com
Reliability in networksA key driver andmeasurement of utilityeffectivenessisinthereliabilityofpowertoitscustomers.Asmanyfaultsonoverheaddistribution lines are transient in nature,reclosingatthesubstationandinstallationofmid-linereclosers./switchescanimprovea utilities SAIDI reliability index by up to24%.Whenpermanentfaultsoccuronoverheadlines, having feeders with increasingdegrees or automation can greatlyenhance distribution grid reliabilityand reduce restoration of unfaultedsegments from several hours to a fewsecondsorminutes.Akeycomponentofthese automation schemes is intelligentcontrollers that can integrate with FDIRsystemsthroughsharinglocalinformationandacceptingcontrolcommands.
Fault isolation and Restoration
With adequate deployment of Reclosersand switches, faults on distributionnetworkscanoftenbe isolated allowingunaffected parts of the system to berestored. Twomainmodesof operationof isolation and restoration commonlydeployedare:A,Manual: Fault Isolation&restorationis
donemanuallybythecrewvisitingthesite.
B.Automatic: Intelligenceattheswitchinglocations detect faults and based onthe level of automation available, thefollowingthreeoptionsarepossible.
1. localized Control: Local intelligencefor detecting and isolating a faultedsection of the feeder allowing forautomatic reclosing and restorationtounfaultedupstreamsectionsofthefeeder.
2. operator Control: Operator Controlrequires a DMS application like GE’sPowerOnorGeNesolutionsrunninginthecontrolcenter.Thisisacombinationoflocalintelligencecommunicatingtothe control center with an Operatorexecuting switching plans to isolatethe fault and restore service to non-faultedsections.
3. Automated Control: AutomatedControlrequiresaDMSapplicationlikelikeGE’sPowerOnorGeNerunninginthe control center or a decentralize
system running in the substationlikeGE’s D400-FDIR. FDIR algorithmsdetermines fault location andautomatically reconfigure the feedertoisolatethefault&restoringpowertonon-faultedsections.
overview TheMultilinDGCRisanadvancedRecloserController for detection of faults andcontrollingoverheadreclosers.TheMultilinDGCRiscompatiblewithmanytraditionaland magnetic actuator reclosers andprovides a great degree of flexibility inintegratingwithFDIRsystems.The Multilin DGCR provides integratedprotection, control, and reclosingfunctionality required for protectingfeeders and isolating faulted sections.Utilizing these features, the MultilinDGCR can greatly improve distributionreliabilitywhetheritisbeingusedworkingindependentlyor intandemwithanFDIRscheme.TheMultilinDGCRiscapableofmonitoring3currentsandup to6 voltagesallowingfor3-phasevoltagemeasurementoneachside of the recloser. The Multilin DGCRsupporttraditionalCTsandPTssensorsaswellaslinepostsensorssuchas(Lindsey,FisherPierce).Withthismeasurementcapability,Multilin’sDGCR can measure and communicatecritical information includingvoltageand
current magnitudes to SCADA and DMSsystems. The Multilin DGCR calculatespower factor, phase angle, power flowdirection, power and energy. Multilin’sDGCR performs real time tracking ofrecloser operations, parameters and therecloserweartherebyenablingtheutilityto manage their assets effectively andefficiently
Robust Design
BasedonGE’sprovencontrollerplatformwith tens of thousands of units installedglobally, the Multilin DGCR undergoesextensive Accelerated Life Testing (ALT)andHighlyAcceleratedLifeTesting(HALT)to validate accurate functionality underspecifiedconditionsandtoensureaccurateperformance in extreme operatingconditionsandharshenvironments.Asacompletepackage,theMultilinDGCRis offered in a NEMA-4 certified cabinetthat is suitable for operation of harshenvironmentswithanoperatingrangeof-40°Cto+60°C(-40°Fto+140°F).
Modes of operation
The Multilin DGCR Recloser controllerprovidestwomodesofoperation:
• Remotemode
• Localmode
The Multilin DGCR recloser controllermeasures three phase voltages andcurrents,andbasedonthemeasurements,managesautoreclosefunctionality.
typical loop Feeder Arrangement
The DGCR can play an important part of FDIR/FLISR solutions for improving distribution grid reliability.
Multilin DGCRRecloser Controller
Recl
oser
Con
trol
ler
www.GEDigitalEnergy.com
Comparison of time taken for different fault isolation and restoration options.
Detects Fault–Dispatchcrewonreceiptoffaultinformation
Restore upstream–RestorepowerbackfromS/SAtofirstswitchingdevice(SW1).Crewtraveltime,Isolatefault(OpenSW1)
Restore Downstream–RestorepowertosegmentbetweenSW2andTieSW.Crewtraveltime,Isolatefault(OpenSW2)&reroutepower(ClosetieSW)
Fix Fault –Rectifythefault&revertbacktonormal
* Actual restoration time varies based on the circuit configuration.
Automating the reconfiguration of faulted distribution circuits reduce customer outage time on unfaulted sections of the network from hours to seconds
Alert operator Restore upstream Restore Downstream Fix Fault
Alert operatorRestore upstream Restore Downstream Fix Fault
Alert operatorRestore upstream Restore Downstream Fix Fault
Alert operatorRestore upstream
Restore DownstreamFix Fault
ManualMode
AutomaticModeLocalizedControl
AutomaticModeOperatorControl
AutomaticModeAutomatedControl
5-10 min
5-10 min
<10 sec
<10 sec
0.5-1 hr
0.5-1 hr
<3 min
1-1.5 hr
0.5-5 sec*
0.5-5 sec*
0.5-5 sec*
SAiDi: TheSystemAverageInterruptionDurationIndexistheaverageoutagedurationforeachcustomerserved.
SAiFi: TheSystemAverage InterruptionFrequency Index istheaveragenumberofinterruptionsthatacustomerwouldexperience.
CAiDi: TheCustomerAverageInterruptionDurationIndex isSAIDI SAIFI.CAIDIgivestheaverageoutagedurationthatanygivencustomerwouldexperience.CAIDIcanalsobeviewedastheaveragerestorationtime.
nEtwoRK REConFiGuRAtion iMPRoVinG REliABility
Efficientfaultdetection,isolationandrestorationgreatlyenhancesdistributiongridreliability,reducingrestorationtimedrasticallyfromseveralhourstoafewsecondsorminutes.Distributionreliabilityperformancesaregreatlyenhanced,asaretheindexesofCAIDI,SAIFIandSAIDI,whicharecommonlyusedasareliabilityindicatorbyelectricpowerutilities.
Multilin DGCRRecloser ControllerRe
clos
er C
ontr
olle
r
www.GEDigitalEnergy.com
Fault ProtectionThe Multilin DGCR provides protectionfunctionalityfordownstreamOverCurrentand Earth Faults. The DGCR can beprogrammedtorecloseafaultedsegmenteitherindependentlyorfromremote.Thisis a key feature for grid reliability TheDGCRalsoofferscontrol,monitoringanddiagnostics in one integrated efficientdesign.
Cold load pickup
The Multilin DGCR can be programmedto block the instantaneous over-currentelements, and raise the pickup level ofthe time over-current elements, when acold load condition is detected. The coldload condition is detectedduring closingof thebreakerona feeder thathasbeende-energized for a long time. The feederinrushcurrentandthemotoracceleratingcurrent during breaker closing maybeabove some over-current protectionsettings.
Phase ioC
TheMultilinDGCRhasone instantaneousovercurrentdetectionfunctionPhaseIOC.Itconsistsofthreeseparateinstantaneousovercurrentelements;oneperphase,withidenticalsettings.
Phase toC
TheTOC in theMultilinDGCRcomeswiththefollowinguserselectablecurves:Extremely/Very/Moderately/NormallyInverse,DefiniteTime,IECCurveA/B/CandShortInverse,IACExtremely/Very/Inverse/Short,UserCurve,FlexCurveA,FlexCurveB.TheTOCsettingsareappliedtoeachofthethreephasestoproducepickupandalarmconditionsperphase
neutral current detection
The Multilin DGCR has one NeutralOvercurrent detection function. Thesettingsofthisfunctionareappliedtothecalculatedneutralcurrent forpickupandtripflags.
overvoltage detection
ThephaseOVprotectionprotectsvoltagesensitivefeederloadsandcircuitsagainstsustained overvoltage conditions. Thephase OV protection generates alarms
when the voltage exceeds the selectedvoltagelevelforthespecifiedtimedelay.
Phase under voltage detection
ThephaseUVprotectionprotectsvoltagesensitivefeederloadsandcircuitsagainstsustained under voltage conditions. Thephase UV protection generates alarmswhenthevoltagedropsbelowtheselectedvoltagelevelforthespecifiedtimedelay.
Voltage unbalance detection
The Voltage Unbalance feature in theMultilinDGCRdetectsvoltageunbalancesonafeeder.Voltageunbalanceisdefinedastheratioofnegative-sequencetopositive-sequencevoltage.Onunbalanceanalarmis issued so themaster station can takeactionto isolateandrepair thedamagedsection.Thiscouldprovideanindicationtothesystemoperatorofabrokenconductorcausingahighimpedancefault .Reverse Power DetectionReverse Powerdetection prevents the recloser OpencommandfrombeingexecutedduringtheAutoSectionalizingsequence.
Auto Recloser
The Auto Recloser element providesa mechanism to localize a fault bycoordinating this function with thereclosingoperationsofthefeederbreakerwithinatimingschedule.The logic implemented in this elementprovidesawaytodetectseveralreclosing
actions from the main circuit breakerandaccordinglyopenthe localswitch, inperiodswhenthevoltageisabsent.The logic uses the information of theovercurrent condition followed by a lossof voltage, loss of current , power flowdirectionandvoltagedetectionfunctionstoexecutethetransitionintointernalstates.
Automation & ControlTheMultilinDGCRofferspowerfulI/Oandprogrammablelogic(FlexLogic™)options for advanced automation andcontrol, reducing the need and costsassociatedwithadditionalprogrammablecontrollersordiscretecontroldevices.
Remote Control
For both operational efficiency andreliability reasons, the Multilin DGCRprovides remote control for operatingover-headrecloseraswellasPadmountedswitchgear. The Multilin DGCR has thecapabilitytolockremotecontroloperationslocally to prevent remote controlfunctionality.TheMultilinDGCRiscapableofprovidingbothlocalandmanualcontroloftheswitchgear.The compact size of the Multilin DGCRenables it to fit in existing out doorDistributionSubstationswithouttheneedforadditionalspace.
50P 50N 51P
27P 59PCLOSETRIP
CLP
Monitoring
METERING
AUTO-RECLOSER
Functional Block Diagram
ANSIDeviceNumbers&FunctionsDeviceNumber Function50P PhaseInstantaneousOvercurrent50N NeutralInstantaneousOvercurrent51P PhaseTimeOvercurrentCLP ColdLoadPickUp27P PhaseTimeOvercurrent59P OverVoltage
Custom FlexCurves can be constructed to coordinate with other Up/down stream protection devices on a lateral
Multilin DGCRRecloser Controller
Recl
oser
Con
trol
ler
www.GEDigitalEnergy.com
Set Point Group Control
TheMultilinDGCRhasthreeidenticalsetpointgroups.TheactivationofthegroupcanbedoneeitherfromtheHMIorviaadigitalinput.
Virtual inputs and outputs
TheMultilinDGCRprovides32virtualinputsand32virtualoutputsthatprovideuserswiththeabilitytosendcommandstothedevice.TheMultilinDGCRcanacceptcommandsfromSCADA,throughthefrontHMI,orfrontUSBporttoissuecommandssuchascloseoropen.
Command Setting
TheMultilinDGCRhastheabilitytoforcecommandsfromthemenustructure.ThiscanalsobeachievedviatheEnerVista™softwarethatrunsonaPC.ThissimulationensuresthatthecloseandopencommandscanbesafelyissuedfromadistancewithoutusingtheHMI.
Flexlogic™
FlexLogic in the Multilin DGCR providesthe ability to create customized controlschemes. This minimizes the needand costs associated with auxiliarycomponentsandwiring.SchemescanbeconfiguredwithFlexLogicspecifyingwhatactionsneedbetakenbasedonthestatusoffaultdetectionsorcontrolelements,aswellasinputsdrivenbyconnectedsensorsandequipment.
Battery Management System
TheMultilinDGCRiscapableofcontrollingthe over head recloser in differentconditionsincludingpowerloss.Thepowerlosscanoccurifthefeedercircuitbreakeropens up or there is a distribution gridblackout.Duringallpowerlossconditions,theMultilinDGCRissuppliedfromabackupbattery.Thebatteryisa24VSealedValveRegulatedLeadAcid(SVRLA)battery.ItissizedtokeeptheMultilinDGCRrunningfor8hours.During normal running conditions, thebattery is connected to the charger.SwitchingtodifferentmodesofoperationiscontrolledbytheDGCR.Thebatterymanagementsystemhasthefollowingmodesofoperations.
• Run
• Backup
• Batterytest
• Fusetest
AbatteryalarmLEDisprovidedforalarms,andtheeventwillbeloggedintotheeventrecorder.
Metering & MonitoringThe DGCR recloser controller is able tomonitor the recloser state based on theauxiliary input 52a / 52b provided bytherecloser. Itcanalsobeconfiguredforseveral external inputs for monitoringpossibleerrorsThese inputs can be used to inhibit anypossible local and remote closing andopeningcommandstotherecloserorthepadmountedswitchgear.The Multilin DGCR is able to monitorotherexternalstatessuchas lowbatteryconditions,ambienttemperature.
Power Quality Measurements
TheMultilinDGCRprovideshighaccuracymeteringandrecordingofallACsignals,measuringthefollowingkeyparameters:
• Phase-GroundVoltages(kV)
• PhasetoPhaseVoltages(kV)
• Positive,Negative,ZeroSequenceVoltage
• PhaseA,B,andCCurrents(A)
• Positive,Negative,ZeroSequenceCurrent
• GroundCurrent(A)
• 3-PhaseActivePower(KW)
• 3-PhaseReactivePower(KVar)
• 3-PhaseApparentPower(KVA)
• PowerFactor(LagorLead)
• Pos.&Neg.(Import&Export)RealEnergy(kWh)
Event record enables to analyze the sequence of events after each recloser action. Each event is stored with event number, date, time, and analog data of interest
Data logger helps in better understanding the analogue channel behavior. Sampling at a selectable time interval rate of 1 min to 60 minutes
Multilin DGCRRecloser ControllerRe
clos
er C
ontr
olle
r
www.GEDigitalEnergy.com
• Pos.&Neg.(Import&Export)ReactiveEnergy(kVarh)
• 2ndto8thHarmonicupto20%–forCurrent
• 2ndto8thHarmonicupto20%–forVoltage
• THDin20%–forCurrent
• THDin20%–forVoltage
Thesedatapointscanbeeasilyintegratedintoacustomer’sdatabaseforseamlessviewingthroughaSCADAorDMSsystemlikeGE’sPowerOnorGeNe.
Statistics & Counters
• TripCounter
• OpenCounter
• CloseCounter
• KI2TPhaseACounter
• KI2TPhaseBCounter
• KI2TPhaseCCounter
• TotalClose/OpenOperation
Maintenance Elements
Themaintenanceelements in theMultilinDGCR provides alarms to the system
basedonthemaximumnumberofclosing/openingexecutedcommandsperperiodoftimeandI2tmeasurementsperfeeder.
Event Recorder
To significantly reduce time and enablemore effective distribution, post faultanalysisandtroubleshooting, theMultilinDGCR provides an integrated eventrecorderanddetaileddiagnosticfeatures.Thesequenceofeventsrecorderoffersthefollowingfeatures:
• Upto256consecutiveeventsstored
• Enableordisable,operateanddropouteventsbysetpoints
• Phasevoltage/currentandpowermeteringshotisalsoincludedandstoredateachevent
Data Management & DiagnosticsThe Multilin DGCR provides advanceddisturbance diagnostic features thatsignificantly reduce the time and costsassociated with troubleshooting powersystem events and reconstruction.
Recording functions include enhanceddiagnosticswitha10channelRMSrecorderdatalogger.
Advanced Device Health Diagnostics
Comprehensive device health diagnostictestsareperformedbytheMultilinDGCRduringstartupandcontinuouslyatruntimetotestitsownmajorfunctionsandcriticalhardware.ThesediagnostictestsmonitorforconditionsthatcouldimpacttheMultilinDGCRController’sperformance,evaluatesthepotential impactandcriticalityofthiscondition,andpresents thedevicestatustooperatorsviaSCADAand/orthroughthefrontpaneldisplay.
CommunicationsTheMultilinDGCRutilizesindustrystandardcommunications technologies making itoneofeasiestandmostflexiblecontrollerstouseandintegrateintonewandexistingSCADAorDMS infrastructures.Supportedcommunicationprotocolsinclude:
• DNP3.0
• ModbusRTU(RS485)
Front panelDisplay: 4x20 character lCD display
Control Panel: Auto/Manual pushbuttonlocal/Remote pushbuttonManual open/Close pushbuttons
uSB 2.0 Port
Status lEDs
target Reset
Multi-functional menu navigation keypad
Quick access pushbuttons
Status lEDs
Multilin DGCRRecloser Controller
Recl
oser
Con
trol
ler
www.GEDigitalEnergy.com
Multiple communication ports andprotocolsallowforremotecontrolandeasyaccesstodeviceandsysteminformation.All communication ports are capable ofsimultaneouscommunications.TheMultilinDGCRcanalsocommunicatetoFDIR/FLISR/SCADAsystemsviawirelesscommunications media. The supportedwirelessmediaincludes:
• Wirelessradio(MDSorcustomerspecific)
• GSM/GPRS
• Pre-wiredforfutureradio
SecurityThe Multil in DGCR Controller andassociatedsoftware toolsprovideasuiteof security features that ensure onlyapprovedpersonnelcanmakechangestotheconfigurationofthesystemorexecutecommands.ThesefunctionsenableautilitytomeetNERC/CIPrequirements.
Password Security
TheMultilinDGCRoffersmultiple levelsofpasswordsecurity to limitaccesscontrolbased on settings or command levels.
Therearefourlevelsofpasswordsecurityprovided:
• Localsettingsaccess
• Localcontrolaccess
• Remotesettingsaccess
• Remotecontrolaccess
Local access refers to users makingchanges using the front USB serial portandtheHMI.RemoteaccessreferstousersmakingchangesusingtherearRS485port
one24hourdayperiod.
Software & configurationTheEnerVista™Suiteisanindustry-leadingset of software programs that simplifieseveryaspectofusingtheMultilinDGCR.EnerVistaprovidesallthetoolstomonitorthestatusoftheprotectedasset,maintainthe controller and integrate informationmeasuredbytheMultilinDGCRintoSCADAortheDMSmonitoringsystems.Theabilitytoeasilyviewsequenceofeventsisanintegralpartofthesetupsoftware,aspostmortem event analysis is critical topropersystemoperation.
EnerVista launchpad
EnerVistaLaunchpadisapowerfulsoftwarepackagethatprovidesuserswithallofthesetupandsupporttoolsneededfor configuring and maintaining GE’sMultilinproducts.ThesetupsoftwarewithinLaunchpad allows configuring devices inreal-timebycommunicatingusing serial,Ethernetormodemconnections,orofflineby creating setting files to be sent todevicesatalatertime.Included in Launchpad is a documentarchiving and management systemthat ensures critical documentation isup-to-date and available when needed.Documentsmadeavailableinclude:
• Manuals
• Applicationnotes
• Guideformspecifications
• Brochures
• Wiringdiagrams
• FAQs
• Servicebulletins
Set up with EnerVista™ Software
EnerVista setup software can reduce device set-up and configuration time with the help of easy to use drag & drop configuration menu.
Multilin DGCRRecloser ControllerRe
clos
er C
ontr
olle
r
www.GEDigitalEnergy.com
orderingDGC R E l S S A * * E * * 1 * X X X Description
Application R RecloserControllerLanguage E English(Standard)PowerSupply L Low(20to60vdc)Communication S RS485ModbusRTU/DNP3.0(Standard)Options S StandardI/O A CurrentInputCard(1A/5A)
B B VoltageInputCard(60-300VAC)J J LEAInputCard(0-12V)
E E E E Two(2)10AForm-Arelaysandsix(6)20to60VDCdigitalInputs(2xIO_EStandard),Max3xIO_E
D D Four(4)10Aform-Crelays(Optional,Max1IO_D)G G 3RTD(Optional,Max1IO_G)
WirelessRadioOption X None1 MDSTransNet2 MDSiNET-II4 Prewiredforfutureradiowith12VDCPowerSupplyinstalled5 Prewiredforfutureradiowith24VDCPowerSupplyinstalled
ConnectionType 1 14PinAmphenolconnector2 24PinAmphenolconnectorforABBRecloserwithISDModule
120221-v1
• Downloadtheinstructionmanual
• ReviewapplicationsNotesandsupportdocuments
• BuytheMultilinDGCRRecloserControlleronline
• View/downloadtheMultilinDGCRbrochure
Visit www.GEMultilin.com/DGCR to:
technical SpecificationsPowER SuPPlynominal: 24to48VDCRange: 20to60VDCPower Consumption: 16Wtypical,25W
maximumAC CuRREnt (oPtion A)input type: CombinedIA/SAFrequency: 50or60HzAC VoltAGE: (oPtion B)input type: 60to300VACnominal frequency: 50or60HzAC VoltAGE: (oPtion J)input range: 0-12VACnominal frequency: 50or60HzDiGitAl inPutS: type: opto-isolatedinputsExternal switch: wetcontactMaximum input voltage:
36VAC
DiGitAl outPutS:operate time: 10msMinimum contact load: 10mAat5VDCContinuous current: 10AMake & carry for 0.2s: 30AperANSIC37.90
CoMMuniCAtionSERiAlRS485 port: Opto-coupledBaud rates: upto115kbpsResponse time: 1mstypicalParity: None,Odd,EvenMaximum distance: 1200m(4000ft)isolation: 2kVProtocol: ModbusRTU,DNP3.0uSBStandard specification: CompliantwithUSB2.0Connector: 115kbpstEStinG AnD CERtiFiCAtioniSo: Manufacturedunderan
ISO9001registeredprogramPHySiCAl SPECiFiCAtionSEnclosure Size: 600mm(W)x600mm(H)x
350mm(D);23.6”(W)x23.6”(H)x13.8”(D)
weight (Base): 28kg(excludingbatteries)
EnViRonMEntAmbient operating temperature:
-40°Cto+60°C[-40°Fto+140°F]
Ambient storage / shipping temperature:
–40°Cto+85°C[-40°Fto+185°F]
Humidity: upto90%non-condensingPollution degree: 2installation category: ClassIovervoltage category: ClassIIIiP rating: NEMA4/IP65
ProvidesingressprotectionratingofNEMA4(andequivalentIPrating–IP65)asdefinedbyNEMAIEC60529forpoletopinstallation.
CoMPAtiBlE witH: ABB: OVR-3,
G&w: ViperS
Cooper: Kyle®Form3,3A,4,4A,4C,4D,FXA,FXB
Othertraditional14PinReclosers