94
1 Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Application Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Automatic Smoke Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Pullstation Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Automatic Smoke Control Priorities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Manual Smoke Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Auto Command Retry Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 FSCS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Assigning the Fire Object Category to Smoke Control Objects . . . . . . . . . . . . . . . . . . . 7 Security Administration System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Roles and User Accounts Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 UUKL Smoke Control Security Administration Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Security Administration Detailed Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Creating a New Role . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Creating a New User Account . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Configuring User Profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Configuring Role Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Assigning System Access Permissions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 DX Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Smoke Control NAE Design Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 DX-9100 Multi-Story Building Smoke Control Application . . . . . . . . . . . . . . . . . . . 15 Application File Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 GX Control Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Point List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 GX Configuration Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note Code No. LIT-1201737 Release 1.2 Issued January 10, 2005

Multi-Story Building Smoke Control with FSCS Override

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Multi-Story Building Smoke Control with FSCS Override

1Multi-Story Building Smoke Control with FSCS Override - Metasys®System Extended Architecture Application Note

Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Application Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Automatic Smoke Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Pullstation Logic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Automatic Smoke Control Priorities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Manual Smoke Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Auto Command Retry Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

FSCS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Assigning the Fire Object Category to Smoke Control Objects . . . . . . . . . . . . . . . . . . . 7

Security Administration System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Roles and User Accounts Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

UUKL Smoke Control Security Administration Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Security Administration Detailed Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Creating a New Role . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Creating a New User Account . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Configuring User Profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Configuring Role Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Assigning System Access Permissions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11DX Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Smoke Control NAE Design Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

DX-9100 Multi-Story Building Smoke Control Application . . . . . . . . . . . . . . . . . . . 15Application File Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

GX Control Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Point List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

GX Configuration Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended ArchitectureApplication Note Code No. LIT-1201737

Release 1.2Issued January 10, 2005

Page 2: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

2

Smoke Control NAE Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Application File Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Metasys System Extended Architecture Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Multi-Story Building Smoke Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Floor Above/Floor Below Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

All Floors Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Lock Alarms Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Alarm Lockout Interlock Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

FSCS Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

FSCS Zone 2 IFC Zone Interlock Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

FSCS Zone 2 3rd Party Zone Interlock Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

FSCS Zone 2 Smoke Interlock Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

FSCS Zone Switch Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

FSCS Floor 2 Supply Fan 1 Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Floor 2 VMA 1 Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

FSCS Floor 2 Damper 1 Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

FSCS Floor 2 Damper 2 Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

FSCS Floor 2 Zone Smoke LED Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

FSCS Floor 2 Damper 3 Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

FSCS Floor 2 Exhaust Fan 1 Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

FSCS Stairwell Fan 1 Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

FSCS Elevator Fan Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

FSCS Firefighter Control Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

Using Multiple Smoke Control NAEs or NIEs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

Requirements for Larger Sites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

Object Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

Site Director Smoke Control NAE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

FSCS Smoke Control NAE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

Smoke Control System Connection Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

FSCS Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90

Monitoring the Site Director Smoke Control NAE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90

Monitoring a Smoke Control NIE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

Page 3: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

3

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended ArchitectureApplication Note

Document IntroductionSmoke control applications issue commands to controlled devices that pressurize or exhaust an area of a building. This document describes smoke control for a multi-story building with floor above/floor below pressurization in the Metasys® system extended architecture.

The smoke control strategy is achieved with the DX-9100 (DX) application and the smoke control Network Automation Engine (NAE) application described in this document, with manual override of the smoke control logic provided by the Fire Fighter’s Smoke Control Station (FSCS).

Note: These application notes only present an example of one smoke control strategy. Since every building is unique, the details of applying the strategy vary. These application notes can help you develop an appropriate application for your project.

Related DocumentationTable 1 lists related smoke control documentation.Table 1: Related DocumentationFor Information On Refer To LIT No./Part No.General smoke control information Metasys System Extended Architecture

Smoke Control System Technical BulletinLIT-1201684

Logic programming for the DX-9100 controller

GX-9100 Software Configuration Tool Technical Bulletin

LIT-6364060

Single story enclosed shopping mall smoke control

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note

LIT-1201736

Warehouse smoke control Warehouse Smoke Control with FSCS Override - Metasys System Extended Architecture Application Note

LIT-1201738

Weekly testing of dedicated stairwell pressurization fans

Weekly Testing of Dedicated Stairwell Pressurization Fans - Metasys System Extended Architecture Application Note

LIT-1201739

Weekly testing of dedicated smoke control dampers

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Application Note

LIT-1201743

Specific wiring requirements Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin

LIT-1201753

UL® 864 UUKL requirements MSEA UL 864 UUKL Compliance Checklist LIT-1201754

Page 4: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

4

Application OverviewThis application provides smoke control for a multi-story building. The application logic provides automatic smoke control, floor above/floor below pressurization and exhaust, stairwell and elevator pressurization, and fire fighter manual override. The DX controllers provide field connections, and the DX application provides basic HVAC and automatic smoke control for the multi-story building. The smoke control NAE provides a connection to the FSCS, and the smoke control NAE application provides automatic smoke control and fire fighter manual override for the smoke control system.

Automatic Smoke ControlAutomatic Smoke Control provides the logic for UUKL first incident rule by locking out subsequent alarms from automatic smoke control. Floor Above/Floor Below logic depressurizes the floor that goes into smoke alarm. The floor above the alarm, floor below the alarm, stairwell and elevator shaft are pressurized. Pressurize and Depressurize commands in automatic smoke control are commanded at a Priority 3. Priority 3 commands are released when the smoke alarm is reset.

If a floor, stairwell, or elevator shaft is under smoke control, the FSCS controls the Light-Emitting Diodes (LEDs) next to each FSCS switch to indicate the current status of the fans, dampers, and zone. Status LEDs for a fan show the fan status as On, Off, or in Trouble. Status LEDs for a damper show the damper status as Open, Closed or in Trouble. Status LEDs for a zone (store or mall area) show the zone status as Pressurize mode, Depressurize mode, or Purge mode. The Auto LED for each fan, damper, and zone switch remains on while the point is in automatic smoke control.

The logic to check the status of fans and dampers for trouble is initiated when a floor, stairwell, or elevator shaft goes into smoke control. If a fan does not reach its set point within 60 seconds, its Trouble LED on the FSCS is turned on. If a damper does not reach its set point within 75 seconds, its Trouble LED on the FSCS is turned on. After a commanded point goes into Trouble, the Automatic Command Retry logic repeats the command that failed every 60 seconds until the command is successful.

Pullstation LogicPullstations are not allowed to initiate automatic smoke control for individual floors. However, they are allowed to initiate smoke control pressurization for stairwells and elevators.

Page 5: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

5

Automatic Smoke Control PrioritiesAll automatic smoke control commands are commanded at a Priority 3. Fire fighter manual overrides, issued from the FSCS panel, to pressurize or depressurize zones, are commanded at a Priority 2. Fire fighter manual overrides, done from the FSCS panel, to control individual fans and dampers, are done at a Priority 1.

Manual Smoke ControlManual Smoke Control logic is initiated when a fire fighter turns the FSCS Panel Enable key from the Auto position to the Fire Fighter Control position and initiates a manual override of a fan, damper, or zone point from the Auto setting on the FSCS panel. This turns off the Panel Enable switch Auto LED, and turns on the Panel Enable switch Fire Fighter Control LED.

There are two levels of manual smoke control. A fire fighter can put a floor in manual smoke control by turning the zone knob to Pressurize, Depressurize, or Purge. The zone smoke control commands are commanded at Priority 2. Priority 2 commands are released when the fire fighter turns the zone knob back to Auto or turns the Panel Enable key back to Auto.

A fire fighter can put a point in manual smoke control by flipping a fan toggle switch to On or Off, or a damper or Variable Air Volume (VAV) toggle switch to Open or Close. Individual points are commanded at Priority 1. Priority 1 commands are released when the fire fighter flips the toggle switch to Auto or turns the Panel Enable key back to Auto.

Any point that is under manual smoke control activates the trouble checking logic. If a fan does not reach its set point within 60 seconds, its Trouble LED turns on. If a damper does not reach its set point within 75 seconds, its Trouble LED turns on. After a commanded point goes into Trouble, the Automatic Command Retry logic repeats the command that failed every 60 seconds until the command is successful.

Auto Command Retry LogicThe Auto Command Retry logic is used for fans, dampers, and VMAs. It does a comparison check between the commanded state and the actual device state, to verify that the command was successful. In the event a command to a fan, damper, or VMA fails, possibly because the MCO for the commanded device is on a remote smoke control NAE panel. The additional time required to communicate with the remote smoke control NAE might exceed the command response limit. Therefore, the command is resent every 60 seconds until the command is successful.

The Auto Command Retry logic is used when either a device MCO does not match command, a fan, damper, or VMA status does not match its commanded value, or a fan, damper, or VMA trouble input is active.

Page 6: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

6

FSCSThe FSCS panel example (Figure 1) shows the manually controlled devices for Floor 6 only, the elevator supply fan, and stairwell supply fan. The devices for Floor 6 are three dampers, a supply fan, an exhaust fan, and a VAV. The LEDs next to each dial or toggle switch (Table 2) designate the status of each device or zone. The Smoke LED indicates a smoke alarm for the zone (floor).The FSCS in this application has six floors and additional controls not shown here.

The LEDs on the FSCS panel (Figure 1) can be set to the following values.

The FSCS panel is responsible for all Sonalert® logic. A Trouble LED is lit when a fan or damper fails to achieve its commanded state, an automatic smoke detector triggers an alarm, or an AI or DI fuse on the DX fails. The LED value is set to 3 or 4, as described in Table 2, and the Sonalert sounds. Pressing the Silence button on the FSCS panel silences the Sonalert and changes the Trouble LED to a slow blink. The Trouble LED remains on slow blink until it is commanded off. The panel starts a timer and resounds the Sonalert within 24 hours if the Trouble LED is not turned off.

The Sonalert sounds if the FSCS Panel Enable key is turned from the Firefighter Control position to the Auto position and all zone knobs and point toggle switches are not set to Auto. The FSCS still goes into Auto mode, but the Sonalert reminds the firefighter to set the manual smoke control switches to the Auto position.

Table 2: FSCS LED Blink Condition FSCS LED Value LED Blink Condition0 LED is off1 LED is on continuously2 LED slow blink3 LED fast blink and Sonalert® turns on

Figure 1: FSCS Panel – Floor 6 Example

Page 7: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

7

The General Trouble LED turns on to a fast blink if the panel loses N2 communications.

Assigning the Fire Object Category to Smoke Control ObjectsYou must assign every object used specifically for smoke control as a Fire object. This limits the control of smoke control devices and points to authorized Fire operators.

Use the pull down menu to assign the Fire object category (Figure 2).

!WARNING: Risk of serious injury or death if a smoke control object is not assigned as a Fire object! In the event of a fire or smoke control event, devices or points used for smoke control that are not assigned as Fire objects allow those devices and points to be controlled by non-fire authorized operators. It is imperative that every smoke control device or point be assigned as a Fire object.

Figure 2: Assigning the Fire Object to Smoke Control Objects

Page 8: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

8

Security Administration SystemThe Security Administration system authenticates and authorizes users of Metasys® system extended architecture applications. The Security Administrator is a browser-based interface that manages all accounts.

Use the Security Administrator System to authenticate and authorize users on the Metasys system extended architecture. The Security Administrator creates User Accounts and Roles, and assigns access permissions to each user of the Metasys system extended architecture.

Roles and User Accounts OverviewSecurity is based on User Accounts and Roles. Roles are groups of users with a specific function within the Metasys system. To access the system, an individual provides a user account and the correct password. Use letters, numbers, or symbols to create user account passwords.

Use the Login button from the logon prompt to send the user’s credentials. A unique Session generates when the user’s credentials match the logon requirements.

UUKL Smoke Control Security Administration DetailsUUKL smoke control requires that only operators designated as fire operators be able to control the smoke control system. This required the creation of four new roles:

1. Administrator - This is the highest level of control and allows site control of all HVAC and Fire features.

Page 9: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

9

2. Fire Administrator - This role is a fire manager level setting. It allows for full system control, including system modification or configuration.

3. Fire User - This role is for most fire field technicians and allows system control and alarm acknowledgement, but not system modification or configuration.

Figure 3: Fire Administrator Access Permissions

Figure 4: Fire User Access Permissions

Page 10: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

10

4. Fire Limited - This is the lowest of the permissions and only allows the operator to view fire/smoke control devices and alarms.

Security Administration Detailed Procedures

Creating a New RoleTo create a new role:

1. From the Security Administration menu bar, select Insert > New Role. The New Role dialog box appears.

2. Fill in the information.

3. Click OK. The New Role appears in the tree.

Creating a New User AccountTo create a new user account:

1. From the Security Administration menu bar, select Insert > New User. The User Properties tab appears.

2. Fill in the information.

3. Click OK. The New User appears in the tree.

Configuring User ProfilesTo configure a user profile:

1. Select the user whom you wish to configure.

2. From the menu bar, select Edit > Properties. The User Properties tab appears.

3. Modify the desired user information.

4. Click OK.

Figure 5: Fire Limited Access Permissions

Page 11: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

11

Configuring Role PropertiesTo configure role properties:

1. Select the user whom you wish to configure.

2. From the menu bar, select Edit > Properties. The User Properties tab appears.

3. Select the Roles tab, then select an Available Role.

4. Click Add. The selected role appears in the Assigned Role list box.

5. Click OK.

Assigning System Access PermissionsTo assign system access permissions:

1. Select the user whom you wish to assign system access permissions.

2. From the main menu, select Edit > System Access Permissions. The System Access Permission dialog box appears.

3. Select an available privilege.

4. Click Add, then click OK to assign the user’s System Access Permissions.

Design ConsiderationsThis DX9100 and Smoke Control NAE application, as it exists in the Metasys System Extended Architecture Smoke Control Library, complies with the UL 864 UUKL Smoke Listing. However, you are responsible for ensuring that the application complies with state and local regulations, and is approved by the Authority Having Jurisdiction (AHJ). You are also responsible for configuring all of the smoke control components, as well as the programming of those components, in order to comply with the UL 864 UUKL Smoke Listing as documented herein.

DX Design ConsiderationsA DX will need to provide the following BACnet Binary Value object (BV) points:

• Zone Pressurize Command – Set to true to turn on supply fans

• Zone Depressurize Command – Set to true to turn on exhaust fans

• BV Auto point – Normally set to true. Point is false when a fire fighter turns a fan On or Off, or sets a damper to Open or Close.

• BV command point for each fan

• BV feedback point for each fan

• BV command point for each damper

• BV open feedback point for each damper

• BV close feedback point for each damper

Page 12: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

12

• BV point for an Analog Input (AI) Fuse

• BV point for a Binary Input (BI) Fuse

Use the following priorities for commands to DX points:

• Priority 3 – commands from automatic smoke control

• Priority 2 – commands from manual smoke control for zone pressurize, depressurize, and purge.

• Priority 1 – commands from manual smoke control for individual points.

• For information on the definition and the initial configuration of the Programmable Logic Controllers (PLCs), use the GX-9100 Software Configuration Tool (GX Tool) to examine this program.

• This application can be expanded for a building with more than six stories. For further details, please contact Field Support Services in Milwaukee.

• You must define tag names for all points.

• You must define the hardware location for each object

• You must name each object with a descriptive name that is unique in the system.

• An alarm occurs if the command does not equal the condition for any pressurization or exhaust output. Each Binary Output (BO) for pressurization and exhaust outputs must be configured to have its own feedback (proof sensor) input. The FSCS indicates when command does not equal condition.

For UL compliance:

• If DX Digital Inputs (DIs) are used for smoke control, then DI8 must be jumpered and mapped to the smoke control NAE as a normal state of On. If DI8 is off, a critical alarm must be issued at the FSCS to indicate a binary input fuse failure that must be fixed immediately, because the DI is no longer accurate.

• If DX Analog Outputs (AOs) are used for smoke control, then Analog Output 14 (AO14, voltage) must be wired to Analog Input 8 (AI8, voltage) and the AI must be mapped to the smoke control NAE with a low alarm limit of 20%. If the AI goes below 20%, it indicates the AO has failed because of a blown fuse, which drops the AO to 0V and the AI to 0% (low alarm). The DX is downloaded so that the AO is normally at 5V because its source point is an Analog Constant (ACO) with a default of 50.

Page 13: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

13

• Response time for individual smoke control components to achieve their desired state of operational mode, exclusive of control system response, should not exceed the following time periods: 60 seconds for fan operation at the desired state plus 90 seconds to annunciate; 75 seconds for completion of damper travel plus 90 seconds to annunciate. In the case of fan start after damper close, these times are additive. If the damper must be closed before the fan starts, the total response time could be up to 135 seconds for operation, 75 seconds for damper to close plus 60 seconds for fan to start. Time to annunciate would be added to this time. (Control system response is the time from automatic detection of a smoke condition to the issuing of an appropriate command to the equipment.)

For specific wiring requirements, refer to the Metasys Smoke Control Wiring Technical Bulletin (LIT-1201753).

Page 14: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

14

Smoke Control NAE Design Considerations• The smoke control NAE reports critical alarms based on the alarm condition,

and the alarm can only be cleared by resetting from the Intelligent Fire Controller (IFC) panel or the Firefighter’s Smoke Control Station (FSCS).

• A “Programming In Progress” BV point is required. You must set this point to true any time you are making changes to the Smoke Control system. This turns on the Programming In Progress LED on the FSCS to let a fire fighter know that changes are currently being made, and the system may not be fully functional. The point must be turned off when changes are complete.

• A master reset interlock is required. The interlock is true after you press reset on the Intelligent Fire Controller (IFC) panel.

• Each floor requires a Latched Alarm BV object. The lock alarm logic sets this point to true for the first alarm detected.

• Each floor requires an Alarm Lockout Interlock. The interlock is true if any latched alarms for other floors is true or the master reset interlock is true. Do not include a floors latched alarm in its own Alarm Lockout Interlock.

• Response time for individual smoke control components to achieve their desired state of operational mode, exclusive of control system response, should not exceed the following time periods: 60 seconds for fan operation at the desired state plus 90 seconds to annunciate; 75 seconds for completion of damper travel plus 90 seconds to annunciate. In the case of fan start after damper close, these times are additive. If the damper must be closed before the fan starts, the total response time could be up to 135 seconds for operation, 75 seconds for damper to close plus 60 seconds for fan to start. Time to annunciate would be added to this time. (Control system response is the time from automatic detection of a smoke condition to the issuing of an appropriate command to the equipment.)

For specific wiring requirements, refer to the Metasys Smoke Control Wiring Technical Bulletin (LIT-1201753).

Page 15: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

15

DX-9100 Multi-Story Building Smoke Control Application

Application File LocationThis Metasys system extended architecture smoke control application is located on the Metasys Branch Purchase Package (BPP) CD in the Metasys System Extended Architecture Standard Smoke Control Applications directory.

GX Control LogicThe GX Tool was used to create the logic for this DX smoke control application. This DX smoke control application resides on each DX-9100 controller used for smoke control. Find more information and guidelines for using the GX Tool in the GX-9100 Software Configuration Tool Technical Bulletin (LIT-6364060).

The main GX screen shows the multi-story floor above/floor below smoke control application as user names (Figure 6) or tag names (Figure 7) depending on the view selected.

Figure 6: GX-9100 Graphical Layout (User Names)

Figure 7: GX-9100 Graphical Layout (Tag Names)

Page 16: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

16

Point ListTable 3 and Table 4 show the hardware and software point requirements for the GX configuration.Table 3: Hardware I/O Requirements Input RequirementsHardware Location

Name of Module

Engineer Units

Req? Description

AI1 DA-T F Yes Discharge Air TempAI3 STATIC-P PSI Yes Static PressureAI8 AI-FUSE % Yes AO-AI FUSE CHECKDI8 DI-FUSE ON/OFF Yes DI FUSE CHECK

Output RequirementsHardware Location

Name of Module

Engineer Units

Req? Description

AO1 CLG-VLV % Yes Cooling ValveAO2 INLT-VN OPN/CLO Yes Inlet Vane Control AO14 AO-FUSE % Yes AO FUSE MONITORDO3 SF-SS ON/OFF Yes AHU SUPPLY FAN STA/STDO4 EF-SS ON/OFF Yes AHU EXH FAN STA/STODO5 ODA-DPR % Yes OUTDOOR AIR DAMPERDO6 RA-DPR % Yes RETURN AIR DAMPERDO7 EA-DPR % Yes EXHAUST AIR DAMPERTDO1 ON-DELAY SECONDS Yes TIMER ON DELAY

Table 4: Software I/O Requirements (Part 1 of 2)Module Name of

ModuleEngineer Units

Req? Description

ACO1 DAT-SP F Yes Discharge Air Temp SetpointACO2 STATP-SP PSI Yes Static Pressure SetpointACO8 AOFUSE-O ON/OFF Yes Manual ResetDCO1 PRESSURE OPN/CLO Yes Inlet Vane ControlDOC2 EXHAUST % Yes AO FUSE MONITORDCO4 OCC-

NORMON/OFF Yes AHU SUPPLY FAN STA/ST

DCO6 OAD-AUTO ON/OFF Yes AHU EXH FAN STA/STODCO7 OAD-OVR ON/OFF Yes Outdoor Air DamperDCO8 RAD-AUTO ACT/INA Yes Return Air Damper AutoDCO9 RAD-OVR OPEN Yes Return Air Damper OverrideDCO10 EAD-AUTO ACT/INA Yes Exhaust Air Damper AutoDCO11 EAD-OVR OPEN Yes Exhaust Air Damper OverrideDCO12 SF-AUTO ACT/INA Yes Supply Fan AutoDCO13 SF-OVR OPEN Yes Supply Fan OverrideDCO14 EF-AUTO ACT/INA Yes Exhaust Fan AutoDCO15 EF-OVR ON/OFF Yes Return Air DamperLRS1 SF-CTL ON/OFF Yes Supply Fan Control

Page 17: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

17

GX Configuration ParametersFigure 8 through Figure 10 show the configuration parameters for the control loops, output points, and programmable logic. PID data values shown are default values and must be tuned upon commissioning.

LRS2 EF-CTL ON/OFF Yes Exhaust Fan ControlLRS3 ODADPR-C CLOSE Yes Outdoor Air Damper CloseLRS4 RADPR-C CLOSE Yes Return Air Damper CloseLRS5 EADPR-C CLOSE Yes Exhaust Air Damper CloseLRS6 SF-GO ON/OFF Yes Supply FanLRS7 ALM-MODE ALM/

NORMYes Automatic Smoke Control Return Air

Damper Control

TIMER (TIMER3) - Data-----------------------

User Name :Description :TIMER #1 TYPE 4 TIMER #5 TYPE 0Input Connection #1--> LRS5 Input Connection #5--> Reset Connection #1--> Reset Connection #5--> Time Period #1 30. Time Period #5 10.Time Units #1 0 Time Units #5 0TIMER #2 TYPE 0 TIMER #6 TYPE 0Input Connection #2--> Input Connection #6--> Reset Connection #2--> Reset Connection #6--> Time Period #2 10. Time Period #6 10.Time Units #2 0 Time Units #6 0TIMER #3 TYPE 0 TIMER #7 TYPE 0Input Connection #3--> Input Connection #7--> Reset Connection #3--> Reset Connection #7--> Time Period #3 10. Time Period #7 10.Time Units #3 0 Time Units #7 0TIMER #4 TYPE 0 TIMER #8 TYPE 0Input Connection #4--> Input Connection #8--> Reset Connection #4--> Reset Connection #8--> Time Period #4 10. Time Period #8 10.Time Units #4 0 Time Units #8 0

Figure 8: Timer 3 Data

Table 4: Software I/O Requirements (Part 2 of 2)Module Name of

ModuleEngineer Units

Req? Description

Page 18: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

18

PID (PID1) – Data---------------------

User Name :CLG-CNTLDescription :COOLING CONTROLEna Shutoff: 0=N 0 Maximum WSP -->Shutoff Out Level 0.0000 Local Set Pt.(LSP) 0.0000Ena Startup: 0=N 0 Proport. Band(PB) 30.0000Startup Out Level 100.0000 Reset Action(TI) 0.2000Ena Symm Mode: 0=N 0 Rate Action(TD) 0.0000ExtForce Out Level 0.0000 Standby Bias(BSB) 0.0000Ena PID to P: 0=N 0 Off Mode Bias(BOF) 0.0000Remote Mode: 0=N 0 Symmetry Band(SBC) 5.0000Ena OFF Trans: 0=N 0 Err Deadband(EDB) 0.1000Process Variable --> AI1 Output Bias(OB) 0.0000Remote Setpoint --> ACO1 Out High Lmt(HIL) 100.0000Reference Variable--> Out Low Lmt(LOL) 0.0000Proportional Band --> Dev H.H.Limit(DHH) 10.0000OFF Mode Control --> Dev High Limit(DH) 5.0000Standby Control --> Dev Low Limit(DL) 5.0000Reverse Action --> Dev L.L.Limit(DLL) 10.0000External Forcing --> Minimum WSP(MNWS) -50.0000Output Bias --> Maximum WSP(MXWS) 999.0000Minimum WSP -->

Figure 9: PID1 Data

Page 19: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

19

An alarm is generated:

• if the command to the fan is On and the feedback does not come On within 60 seconds

• if the command to the fan is Off and the feedback does not go Off within 60 seconds

• whenever there is a mismatch between the command and the feedback

PID (PID2) – Data---------------------

User Name :InltVaneDescription :Inlet Vane ControlEna Shutoff: 0=N 0 Maximum WSP -->Shutoff Out Level 0.0000 Local Set Pt.(LSP) 0.0000Ena Startup: 0=N 0 Proport. Band(PB) -60.0000Startup Out Level 100.0000 Reset Action(TI) 0.3000Ena Symm Mode: 0=N 0 Rate Action(TD) 0.0000ExtForce Out Level 0.0000 Standby Bias(BSB) 0.0000Ena PID to P: 0=N 0 Off Mode Bias(BOF) 0.0000Remote Mode: 0=N 0 Symmetry Band(SBC) 5.0000Ena OFF Trans: 0=N 0 Err Deadband(EDB) 0.1000Process Variable --> AI3 Output Bias(OB) 0.0000Remote Setpoint --> ACO2 Out High Lmt(HIL) 100.0000Reference Variable--> Out Low Lmt(LOL) 0.0000Proportional Band --> Dev H.H.Limit(DHH) 10.0000OFF Mode Control --> Dev High Limit(DH) 5.0000Standby Control --> Dev Low Limit(DL) 5.0000Reverse Action --> Dev L.L.Limit(DLL) 10.0000External Forcing --> Minimum WSP(MNWS) -50.0000Output Bias --> Maximum WSP(MXWS) 999.0000Minimum WSP -->

Figure 10: PID2 Data

Page 20: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

20

The PLC1 logic module ladder diagram (Figure 11) logic states:

•If in Pressurize mode (floor above or below is in alarm) or normal Occupied mode, and the FSCS Supply fan switch is in Auto mode (SF-AUTO) or Override mode (SF-OVR), then start the AHU supply fan.

• If in Unoccupied mode, then stop/shutdown the AHU supply fan.

• If AHU supply fan is commanded on, and the FSCS Outdoor Air Damper switch is in Auto mode (OAD-AUTO) or Override mode (OAD-OVR), then start/open the Outdoor Air Damper.

• If in Pressurize mode (floor above or below in alarm) or Exhaust mode (this floor in alarm), then start a pseudo point called alm-mode.

Figure 11: Logic Module Ladder Diagram - PLC1

Page 21: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

21

The PLC2 logic module ladder diagram (Figure 12) logic states:

• If in normal occupied mode and not in alm-mode (not Pressurize or Exhaust), and the FSCS Return Air Damper switch is set to Auto (RAD-AUTO) or Override (RAD-OVR), then start/open Return Air Damper.

• If in Unoccupied mode or alm-mode, then stop/close the Return Air Damper.

• If in normal Occupied mode or in Exhaust mode, and the FSCS Exhaust Air Damper switch is set to Auto (EAD-AUTO) or Override (EAD-OVR), then start/open the Exhaust Air Damper.

• If in Unoccupied mode, then stop/close the Exhaust Air Damper.

• If Exhaust Air Damper is open, and the time delay has completed, and the FSCS Exhaust Fan switch is in Auto mode (EF-AUTO) or Override mode (EF-OVR), then start the Exhaust Fan.

• If the Exhaust Air Damper is not commanded to open, then stop the Exhaust Fan.

Figure 12: Logic Module Ladder Diagram - PLC2

Page 22: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

22

Smoke Control NAE ApplicationApplication File Location

This Metasys system extended architecture smoke control application is located on the Metasys Branch Purchase Package (BPP) CD in the Metasys System Extended Architecture Standard Smoke Control Applications directory.

Metasys System Extended Architecture ObjectsThis smoke control NAE application resides on the smoke control NAE and was created with the System Configuration Tool (SCT) to define the required Control System, Interlock, and Multiple Command objects. The Logic Connector Tool (LCT) is used to create the logic within the Control System object.

The LCT logic and configuration screens are organized into two sections: Multi-Story Building and FSCS. The Multi-Story Building section shows logic and configuration screens for the floor above/floor below pressurization and exhaust logic, lock alarms, latched alarms, and alarm lockout interlock settings for the stairwells, elevators, and each of the six floors. The FSCS section shows the logic and configuration screens for each of the devices the FSCS controls and/or displays status for. These devices include the Zone Switch, Damper 1, Supply Fan 1, Variable Air Volume Modulating Assembly (VMA) 1, Zone Smoke LED, Damper 2, Damper 3, and Exhaust Fan 1 for each of the six floors. In addition, the logic and configuration screens for the stairwell fans, elevator fans, and Fire Fighter Control is provided.

Page 23: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

23

Multi-Story Building Smoke Control

Floor Above/Floor Below Logic The Floor Above/Floor Below main logic (Figure 13) controls the automatic smoke control. It consists of the inputs, two system blocks, and outputs. The inputs (Figure 14) are one interlock for each floor and a master reset interlock. The Lock Alarms block (Figure 15) locks in the first incident. The All Floors Logic block determines which floors to pressurize and depressurize. Outputs (Figure 16) are binary points within a DX. Each floor has a pressurize and depressurize point.

Figure 13: Floor Above/Floor Below Main Logic

Page 24: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

24

The inputs and the Lock Alarms block is shown in Figure 14. Each floor has one smoke alarm interlock. The Lock Alarms block locks in the first incident. The Master Reset Interlock releases the locked alarms. There is an output alarm for each floor. Only the first floor in alarm is set to true. All other floors are set to false.

Figure 14: IFC Alarm Input Points, FSCS Reset Point, and Lock Alarms Block

Page 25: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

25

The Lock Alarms block and All Floors Logic block (Figure 15) show the outputs from the Lock Alarms block feeding into the All Floors Logic block, and the resulting outputs.

Figure 15: Lock Alarms and All Floors Logic Blocks

Page 26: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

26

The outputs from the All Floors Logic block (Figure 16) connect to zone pressurize and depressurize points in the DX. Stairwells and Elevator shafts also have pressurize points in a DX..

Figure 16: All Floors Outputs to DX Controllers

Page 27: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

27

All Floors LogicThe following screens show the expanded All Floors Logic block that includes a system block for each of the six floors (Figure 17), and a stairwell block and elevator block (Figure 18). Each floor logic has an input for that floors smoke alarm, one for the floor above and one for the floor below. Outputs tell the DX to pressurize or depressurize.

Figure 17: All Floors - Floors 1, 2, 3, 4, 5 and 6 Logic

Page 28: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

28

The Stairwell Logic block and Elevator Logic block (Figure 18) both have an input for each floor, and one pressurize output.

The expanded Stairwell Logic block (Figure 19) pressurizes the stairwell if any floor is in smoke alarm or a pull station is active.

Figure 18: All Floors - Stairwell and Elevator Logic

Figure 19: All Floors - Stairwell Pressurization Logic

Page 29: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

29

The expanded Elevator Logic block (Figure 20) pressurizes the elevator shaft if any floor is in smoke alarm or a pull station is active.

Figure 20: All Floors - Elevator Pressurization Logic

Page 30: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

30

Lock Alarms LogicThe Lock Alarms – All Floors system block (Figure 21) has a lock control system block for each floor. Inputs are that floor’s alarms, an Alarm Lockout Interlock that is true if there is an alarm on any other floor, and a Master Reset Interlock. Outputs feed into the All Floors logic and to the Latched Alarm point. The latched alarm point is input into the Alarm Lockout Interlock for all other floors.

Figure 21: Lock Alarms - All Floors

Page 31: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

31

The expanded Floor Lock logic (Figure 22) shows the logic for a single floor. The first latch latches the alarm for that floor until it is reset. The second latch latches the first incident.

Alarm Lockout Interlock LogicThe Master Reset Interlock Definition (Figure 23) releases the locked alarms when commanded by the IFC fire panel Reset button.

The Master Reset Interlock Action Table (Figure 24) sets the Manual Latched Alarm Reset to inactive 60 seconds after the IFC fire panel Reset button is pressed.

Figure 22: Lock Alarms - Single Floor Lockout Logic

Figure 23: Master Reset Interlock Interlock Definition

Figure 24: Master Reset Interlock Action Table

Page 32: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

32

The Alarm Lockout Interlocks for each floor (Figure 25-Figure 30) are displayed below. The Interlock definition includes the Master Reset and the Latch Alarms from all other floors. Do not include the current floor’s Latch Alarm.

The Floor 1 Alarm Lockout Interlock Definition (Figure 25) locks out all floors except for Floor 1, when Floor 1 is in smoke alarm.

The Floor 2 Alarm Lockout Interlock Definition (Figure 26) locks out all floors except for Floor 2, when Floor 2 is in smoke alarm.

Figure 25: Floor 1 Alarm Lockout Interlock Definition

Figure 26: Alarm Lockout Interlock Definition

Page 33: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

33

The Floor 3 Alarm Lockout Interlock Definition (Figure 27) locks out all floors except for Floor 3, when Floor 3 is in smoke alarm.

The Floor 4 Alarm Lockout Interlock Definition (Figure 28) locks out all floors except for Floor 4, when Floor 4 is in smoke alarm.

Figure 27: Floor 3 Alarm Lockout Interlock Definition

Figure 28: Floor 4 Alarm Lockout Interlock Definition

Page 34: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

34

The Floor 5 Alarm Lockout Interlock Definition (Figure 29) locks out all floors except for Floor 5, when Floor 5 is in smoke alarm.

The Floor 6 Alarm Lockout Interlock Definition (Figure 30) locks out all floors except for Floor 6, when Floor 6 is in smoke alarm.

The Pull Station Interlock Definition (Figure 31) sets the zone to be in active alarm. Its only control is to turn on the stairwell and elevator fans.

Figure 29: Floor 5 Alarm Lockout Interlock Definition

Figure 30: Floor 6 Alarm Lockout Interlock Definition

Figure 31: Pull Station Interlock Definition

Page 35: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

35

FSCS ControlThe FSCS Control section contains logic and configuration screens for each of the six floors, the stairwell, the elevator, and Fire Fighter Control. The logic for each floor is the same, with the only difference being the floor name. Floor 2 is used as an example here.

FSCS Zone 2 IFC Zone Interlock DefinitionThe FSCS Zone 2 IFC Zone Interlock Definition (Figure 32) includes the Floor 2 IFC Zones for that floor.

Table 5: IFC Point State Table

FSCS Zone 2 3rd Party Zone Interlock DefinitionThe FSCS Zone 2 3rd Party Zone Interlock Definition (Figure 33) includes a point for an optional, third-party, normally open (N.O.) contact input connection.

BACnet Point State NAE Point StateState 1 - Normal State 1 - NormalState 2 - Active Alarm State 2 - Active AlarmState 3 - Fault State 3 - FaultState 4 - Disable State 4 - Unreliable

Figure 32: Zone 2 IFC Zone Interlock Definition

Figure 33: Zone 2 3rd Party Zone Interlock Definition

Page 36: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

36

FSCS Zone 2 Smoke Interlock DefinitionThe FSCS Zone 2 Smoke Interlock Definition (Figure 34) includes the Zone 2 IFC Zone Interlock and the Zone 2 third-party zone interlock.

FSCS Zone Switch LogicThe FSCS Zone Switch main logic (Figure 35) inputs from the FSCS are Zone Pressurize, Zone Depressurize, Zone Purge, and Firefighter Control switch. Inputs from the DX are Zone Pressurize and Zone Depressurize. Outputs are the Pressurize, Auto, Depressurize, and Purge LEDs on the FSCS panel and the Zone MCO.

The expanded Zone Control system block logic (Figure 36) controls the FSCS Zone LEDs for the zone, depending on the Fire Fighter Control Key setting.

The Purge LED is lit if the pressurize and depressurize points in the DX are true.

The Pressurize LED is lit if the DX pressurize point is true and the depressurize point is false. The Depressurize LED is lit if the DX depressurize point is false and the pressurize point is true.

Figure 34: Zone 2 Smoke Interlock Definition

Figure 35: Zone Control Switch Main Logic

Page 37: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

37

The Auto LED is lit only if the Zone Switch on the FSCS panel is not set to Pressurize, Depressurize, or Purge.

The Pressurize, Depressurize, and Purge settings on the FSCS panel are not functional unless the Fire Fighter Control Key has been turned on. If the Fire Fighter Control Key is off, the FSCS Request is set to 0.

Figure 36: Expanded Zone 2 Control Switch Logic

Page 38: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

38

The Zone 2 MCO Action Table is shown in Figure 37.

Figure 37: Zone 2 Switch MCO Action

Page 39: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

39

The FSCS Zone Switch setting determines the state value (Table 6), which in turn determines the smoke control action. Table 6: FSCS Zone Switch State Value FSCS Zone Switch Position

State Value Smoke Control Action

Pressurize 1 Zone’s Supply Fan On Auto 0 AutoDepressurize 2 Zone’s Exhaust Fan OnPurge 3 Zone’s Supply Fan On

Zone’s Exhaust Fan On

Page 40: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

40

The Zone 2 Pressurize MCO Action Table is shown in Figure 38.

Figure 38: Zone 2 Pressurize MCO Action Table

Page 41: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

41

The Zone 2 Depressurize MCO Action Table is shown in Figure 39.

Figure 39: Zone 2 Depressurize MCO Action Table

Page 42: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

42

FSCS Floor 2 Supply Fan 1 LogicFSCS Floor 2 Supply Fan 1 (Figure 40) inputs from the DX are the Fan Commanded State, Fan Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points.

Figure 40: Supply Fan 1 Main Logic

Page 43: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

43

The FSCS and Fan Trouble Control blocks are shown in Figure 41.

The expanded FSCS Fan block logic is shown in Figure 42.

Figure 41: Supply Fan 1 FSCS and Fan Trouble Control Main Logic

Figure 42: Supply Fan 1 FSCS Logic

Page 44: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

44

The expanded Fan Trouble Control block logic is shown in Figure 43.

The Supply Fan 1 Interlock Definition (Figure 44) sets the values that, when reached, trigger a trouble alarm. The definition includes status and reliability points for the DX AO and BI fuses, supply fan reliability and DX offline status.

Figure 43: Supply Fan 1 Fan Trouble Control Logic

Figure 44: Supply Fan 2-1 Trouble Interlock Definition

Page 45: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

45

The Supply Fan 1 MCO Action is shown in Figure 45. The Supply Fan Auto point is a binary point in the DX to indicate that the fan is under automatic smoke control. When a fire fighter turns the fan on or off, the Supply Fan Auto point is turned off. The Supply Fan Command is a point in the DX to control the fan.

The FSCS Supply Fan toggle switch setting (Table 7) determines the state value, which in turn determines the smoke control action.Table 7: FSCS Supply Fan 1 Switch State ValueFSCS Supply Fan 1 Toggle Switch Position

State Value Smoke Control Action

On 1 Supply Fan 1 OnAuto 0 AutoOff 2 Supply Fan 1 Off

Figure 45: Supply Fan 1 MCO Action

Page 46: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

46

Floor 2 VMA 1 LogicThe VMA main logic (Figure 46) consists of a VMA system control block. Inputs from the DX are the Fan Commanded State, Fan Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points.

Figure 46: VMA Main Logic

Page 47: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

47

The expanded VMA block consists of two system blocks, the FSCS block and the VMA Trouble Control block (Figure 47). The FSCS block controls the LEDs on the FSCS panel and commands the DX. The VMA Trouble Control block sets the Trouble LED on the FSCS.

Figure 47: VMA1 FSCS and VMA 1 Trouble Control Main Logic

Page 48: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

48

The expanded FSCS block (Figure 48) controls the Open, Close, and Auto LEDs of the FSCS. The Open LED is lit only if the FSCS is in Fire Fighter Control and the VMA Interlock is true. The Close LED is lit only if the FSCS is in Fire Fighter Control and the VMA Interlock is false. The Auto LED is lit only if the toggle switch is not in the Open or Close setting. If the Fire Fighter Control Key is Off, FSCS Request is set to 0. If the Fire Fighter Control Key is On, FSCS Request is set to the following values depending on the position of the toggle switch.

Figure 48: VMA 1 Expanded FSCS Logic

Page 49: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

49

The expanded VMA Trouble Control block (Figure 49) controls the FSCS Trouble LED. The Trouble LED is lit if the VMA is in smoke control and the VMA Interlock has not reached its desired set point within 75 seconds or one of the DX fuses has blown. A VMA is in smoke control if either the DX is in pressurize or depressurize mode, or, the Fire Fighter Control Key is on and the FSCS toggle switch is set to Open or Close.

The VMA 1 Close Interlock Definition (Figure 50) sends the VAV close command as a group, in the event there is more than one VAV. If any VAV in the group fails to close its damper, the FSCS VAV Trouble LED turns on.

Figure 49: VMA 1 Expanded Trouble Control Logic

Figure 50: VMA1 Close Interlock Definition

Page 50: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

50

The VMA 1 Open Interlock Definition (Figure 51) sends the VAV open command as a group, in the event there is more than one VAV. If any VAV in the group fails to open its damper, the FSCS VAV Trouble LED turns on.

The VMA 2-1 Trouble Interlock Definition (Figure 52) sets the values that, when reached, trigger a trouble alarm. The definition includes DX offline status and reliability points for the Network Integration Engine (NIE) Monitor and the VMA Open and Close commands.

Figure 51: VMA 1 Open Interlock Definition

Figure 52: Trouble Interlock Definition

Page 51: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

51

The VMA 1 MCO Action is shown in Figure 53. The VAV Auto point is a binary point in the DX to indicate that the VAV is under automatic smoke control. When a fire fighter sets the VMA to open or close, the VAV Auto point is turned off. The VAV Command is a point in the DX to control the VAV.

The FSCS VAV toggle switch setting (Table 8) determines the state value, which in turn determines the smoke control action.Table 8: FSCS VMA 1 Switch State Value FSCS VAV Toggle Switch Position

State Value Smoke Control Action

Open 1 Open VAV DamperAuto 0 AutoClose 2 Close VAV Damper

Figure 53: VMA 1 MCO Action

Page 52: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

52

FSCS Floor 2 Damper 1 LogicFloor 2 Damper 1 (Figure 54) main logic inputs from the DX are the Damper Commanded State, Damper Open Present Value, Damper Close Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the Open and Close toggle switch and the Fire Fighter Control Key. Outputs are the Open, Auto, Close, and Trouble LEDs on the FSCS and an MCO that commands the DX points.

Figure 54: Damper 1 Main Logic

Page 53: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

53

The expanded Damper 1 block (Figure 55) consists of two control systems, the FSCS block, and the Damper Trouble Control block. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Trouble LED on the FSCS..

Figure 55: Damper 1 FSCS and Damper Trouble Control Main Logic

Page 54: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

54

The expanded Damper 1 FSCS block is shown in Figure 56. The Open LED is lit only if the FSCS is in Fire Fighter Control and the damper is open. The Close LED is lit only if the FSCS is in Fire Fighter Control and the damper is closed. The Auto LED is lit only if the toggle switch is not in the Open or Close setting.

If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch:

• Open – 1

• Auto – 0

• Close – 2

Figure 56: Damper 1 Expanded FSCS Logic

Page 55: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

55

The expanded Damper 1 Trouble Control block is shown in Figure 57. The Trouble LED is lit if the damper is in smoke control and the damper has not reached its desired setpoint within 75 seconds or one of the DX fuses has blown. A damper is in smoke control if either the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to Open or Close..

The Damper 2-1 Trouble Interlock Definition (Figure 58) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the NIE Monitor, the exhaust air damper close and open commands, and the DX offline status.

Figure 57: Damper 1 Expanded Trouble Control Logic

Figure 58: Damper 2-1 Trouble Interlock Definition

Page 56: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

56

The Damper 2-1 MCO Action Table is shown in Figure 59. The Damper Auto point is a binary point in the DX to indicate that the exhaust air damper is under automatic smoke control. When a fire fighter sets the exhaust air damper to open or close, the exhaust air damper Auto point is turned off. The Damper Command is a point in the DX to control the exhaust air damper.

The FSCS Damper 1 toggle switch setting (Table 9) determines the state value, which in turn determines the smoke control action.Table 9: FSCS Damper 1 Switch State Value FSCS Damper 1 Toggle Switch Position

State Value Smoke Control Action

Open 1 Open Damper 1Auto 0 AutoClose 2 Close Damper 1

Figure 59: Damper 1 MCO Action

Page 57: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

57

FSCS Floor 2 Damper 2 LogicFSCS Floor 2 Damper 2 main logic is shown in Figure 60. Inputs from the DX are the Damper Commanded State, Damper Open Present Value, Damper Close Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the Open and Close toggle switch and the Fire Fighter Control Key. Outputs are the Open, Auto, Close, and Trouble LEDs on the FSCS and an MCO that commands the DX points.

Figure 60: Damper 2 Main Logic

Page 58: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

58

The expanded Damper block (Figure 61) consists of two control blocks: the FSCS block, and the Damper Trouble Control block. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Trouble LED..

Figure 61: Damper 2 FSCS and Damper Trouble Control Main Logic

Page 59: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

59

The FSCS block expanded logic is shown in Figure 62. The Open LED is lit only if the FSCS is in Fire Fighter Control and the damper is open. The Close LED is lit only if the FSCS is in Fire Fighter Control and the damper is closed. The Auto LED is lit only if the toggle switch is not in the Open or Close setting..

Figure 62: Damper 2 FSCS Logic

Page 60: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

60

The expanded Damper 2 Trouble logic is shown in Figure 63. The Trouble LED is lit if the damper is in smoke control and the damper has not reached its desired setpoint within 75 seconds or one of the DX fuses has blown. A damper is in smoke control if the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to Open or Close.

The Damper 2-2 Trouble Interlock Definition (Figure 64) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the return air damper close and open commands, and the DX offline status.

Figure 63: Damper 2 Trouble Control Logic

Figure 64: Damper 2-2 Trouble Interlock Definition

Page 61: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

61

The Damper 2-2 MCO Action Table is shown in Figure 65. The Damper Auto point is a binary point in the DX to indicate that the return air damper is under automatic smoke control. When a fire fighter sets the return air damper to open or close, the return air damper Auto point is turned off. The Damper Command is a point in the DX to control the return air damper.

The FSCS Damper 2 toggle switch setting (Table 10) determines the state value, which in turn determines the smoke control action.Table 10: FSCS Damper 2 Switch State Value FSCS Damper 2 Toggle Switch Position

State Value Smoke Control Action

Open 1 Open Damper 2Auto 0 AutoClose 2 Close Damper 2

Figure 65: Damper 2 MCO Action

Page 62: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

62

FSCS Floor 2 Zone Smoke LED LogicThe Floor 2 Zone Smoke LED main logic (Figure 66) controls the Zone 2 Smoke LED on the FSCS.

The Zone Smoke expanded logic (Figure 67) has the following logic:

• If the zone is in smoke control, turn the Smoke LED on.

• If the panel status is Off Normal, flash the Smoke LED.

Figure 66: Zone Smoke LED Main Logic

Figure 67: Zone Smoke Logic

Page 63: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

63

The Zone Smoke LED IFC Zone Trouble Interlock Definition (Figure 68) includes points for status and reliability each zone in the list, reliability of the smoke interlock and the status of the IFC Zone Detector Trouble point. Any zone that goes offline or has a status of unreliable will light that zone’s trouble LED.

Figure 68: Zone Smoke LED IFC Zone Trouble Interlock Definition

Page 64: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

64

The Zone Smoke LED IFC Zone Detector Trouble Interlock Definition (Figure 69) includes points for reliability each smoke detector in the list. A smoke detector status that goes to unreliable will light that zone’s smoke LED.

The Zone Smoke LED 3rd Party Zone Trouble Interlock Definition (Figure 70) includes a point for reliability of the 3rd party zone interlock and offline status and reliability of the 3rd party zone. Any zone that goes offline or has a status of unreliable will light that zone’s trouble LED.

Figure 69: Zone Smoke LED IFC Zone Detector Trouble Interlock Definition

Figure 70: Zone Smoke LED 3rd Party Zone Trouble Interlock Definition

Page 65: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

65

FSCS Floor 2 Damper 3 LogicThe Floor 2 Damper 3 main logic is shown in Figure 71. Inputs from the DX are the Damper Commanded State, Damper Open Present Value, Damper Close Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the Open and Close toggle switch and the Fire Fighter Control Key. Outputs are the Open, Auto, Close, and Trouble LEDs on the FSCS, and an MCO that commands the DX points.

Figure 71: Floor 2 Damper 3 Main Logic

Page 66: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

66

The Floor 2 Damper 3 expanded logic (Figure 72) consists of two control blocks. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Trouble LED.

Figure 72: Floor 2 Damper 3 FSCS and Damper Trouble Control Main Logic

Page 67: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

67

The Damper 3 FSCS block logic shown in Figure 73. The Open LED is lit only if the FSCS is in Fire Fighter Control and the damper is open. The Close LED is lit only if the FSCS is in Fire Fighter Control and the damper is closed. The Auto LED is lit only if the toggle switch is not in the Open or Close setting.

If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch:

• Open – 1

• Auto – 0

• Close – 2

Figure 73: Damper 3 FSCS Block Expanded Logic

Page 68: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

68

The expanded Damper Trouble Control block is shown in Figure 74. The damper Trouble LED is lit if the damper is in smoke control and the damper has not reached its desired setpoint within 75 seconds or one of the DX fuses has blown. A damper is in smoke control if the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to Open or Close.

The Damper 2-3 Trouble Interlock Definition (Figure 75) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the NIE Monitor, the outside air damper close and open commands, and the DX offline status.

Figure 74: Damper 3 Damper Trouble Control Logic

Figure 75: Damper 2-3 Trouble Interlock Definition

Page 69: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

69

The Damper 3 MCO Action Table is shown in Figure 76. The Damper Auto point is a binary point in the DX to indicate that the outside air damper is under automatic smoke control. When a fire fighter sets the outside air damper to open or close, the outside air damper Auto point is turned off. The Damper Command is a point in the DX to control the outside air damper

The FSCS Damper 3 toggle switch setting (Table 11) determines the state value, which in turn determines the smoke control action. Table 11: FSCS Damper 3 Switch State Value FSCS Damper 3 Toggle Switch Position

State Value Smoke Control Action

Open 1 Open Damper 3Auto 0 AutoClose 2 Close Damper 3

Figure 76: Damper 3 MCO Action

Page 70: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

70

FSCS Floor 2 Exhaust Fan 1 LogicThe Floor 2 Exhaust Fan 1 main logic is shown in Figure 77. Inputs from the DX are the Fan Commanded State, Fan Present Value, Zone Pressurize Command, and Zone Depressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points.

Figure 77: Exhaust Fan 1 Main Logic

Page 71: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

71

The Exhaust Fan 1 expanded main logic (Figure 78) consists of two control blocks. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Trouble LED.

Figure 78: Exhaust Fan 1 FSCS and Fan Trouble Control Logic

Page 72: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

72

The FSCS block logic is shown in Figure 79. The On LED is lit only if the FSCS is in Fire Fighter Control and the fan is on. The Off LED is lit only if the FSCS is in Fire Fighter Control and the fan is off. The Auto LED is lit only if the toggle switch is not in the On or Off setting.

If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch:

• On – 1

• Auto – 0

• Off – 2

Figure 79: Exhaust Fan 1 FSCS Block Logic

Page 73: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

73

The Fan Trouble Control block logic is shown in Figure 80. The Trouble LED is lit if the fan is in smoke control and the fan has not reached its desired setpoint within 60 seconds or one of the DX fuses has blown. A fan is in smoke control if, the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to On or Off.

The Exhaust Fan 2-1 Trouble Interlock Definition (Figure 81) includes the DX DI Fuse and AO Fuse..

Figure 80: Exhaust FAN 1 Fan Trouble Control Block Logic

Figure 81: Exhaust Fan 2-1 Trouble interlock Definition

Page 74: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

74

The Exhaust Fan 2-1 MCO Action is shown in Figure 82. The Exhaust Fan Auto point is a binary point in the DX to indicate that the Fan is under automatic smoke control. When a fire fighter turns the fan on or off, the Exhaust Fan Auto point is turned off. The Exhaust Fan Command is a point in the DX to control the fan..

The FSCS Exhaust Fan 1 toggle switch setting (Table 12) determines the state value, which in turn determines the smoke control action.Table 12: FSCS Exhaust Fan 1 Switch State Value FSCS Exhaust Fan 1 Toggle Switch Position

State Value Smoke Control Action

On 1 Exhaust Fan 1 On

Auto 0 Auto

Off 2 Exhaust Fan 1 Off

Figure 82: Exhaust Fan 2-1 MCO Action

Page 75: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

75

FSCS Stairwell Fan 1 LogicThe FSCS Stairwell Fan 1 main logic (Figure 83) inputs on the DX are the Fan Commanded State, Fan Present Value, and Stairwell Pressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points..

Figure 83: FSCS Stairwell Fan 1 Main Logic

Page 76: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

76

The FSCS Stairwell Fan 1 expanded logic (Figure 84) consists of two system blocks. The FSCS block controls the LEDs on the FSCS panel and commands the DX. The Fan Trouble Control block sets the Fan Trouble LED..

Figure 84: Stairwell 1 FSCS and Fan Trouble Control Main Logic

Page 77: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

77

The FSCS Stairwell 1 FSCS block logic is shown in Figure 85. The On LED is lit only if the FSCS is in Fire Fighter Control and the fan is on. The Off LED is lit only if the FSCS is in Fire Fighter Control and the fan is off. The Auto LED is lit only if the toggle switch is not in the On or Off setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch:

• On – 1

• Auto – 0

• Off – 2

Figure 85: Stairwell 1 FSCS Logic

Page 78: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

78

The Fan Trouble Control module logic is shown in Figure 86. The Trouble LED is lit if the fan is in smoke control and the fan has not reached its desired setpoint within 60 seconds or one of the DX fuses has blown. A fan is in smoke control if the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to On or Off..

The Stairwell Fan 1 Trouble Interlock Definition (Figure 87) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the stairwell supply fan, the DX offline status, and the stairwell fan failure. The stairwell fan failure alarm is triggered if the stairwell fan fails a weekly test.

Figure 86: Stairwell 1 Fan Trouble Control Logic

Figure 87: Stairwell Fan 1 Trouble Interlock Definition

Page 79: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

79

The Stairwell Fan 1 MCO Action Table is shown in Figure 88. The Stairwell Fan Auto point is a binary point in the DX to indicate that the fan is under automatic smoke control. This MCO controls the stairwell fan during manual smoke control. When a fire fighter turns the FSCS Stairwell Fan switch on or off, the stairwell fan responds accordingly and the Stairwell Fan Auto point is turned off.

Figure 88: Stairwell Fan 1 MCO Action

Page 80: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

80

The Stairwell Auto Pressure MCO Action Table (Figure 89) controls the stairwell fan when it is not in manual smoke control. The MCO turns the stairwell fan on if an automatic smoke control device detects smoke, a pullstation is pulled, or an FSCS floor zone switch is turned on. When a fire fighter turns the FSCS Stairwell Fan on or off, the Stairwell Fan Auto point is turned off.

The FSCS Stairwell Fan 1 switch setting (Table 13) determines the state value, which in turn determines the smoke control action.Table 13: FSCS Stairwell Fan 1 Switch State Value FSCS Stairwell Fan 1 Toggle Switch Position

State Value Smoke Control Action

On 1 Stairwell Fan 1 OnAuto 0 AutoOff 2 Stairwell Fan 1 Off

Figure 89: Stairwell Auto Pressure MCO Action Table

Page 81: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

81

FSCS Elevator Fan LogicThe FSCS Elevator Fan 1 main logic (Figure 90) inputs from the DX are the Fan Commanded State, Fan Present Value, and Stairwell Pressurize Command. Inputs from the FSCS are the On and Off toggle switch and the Fire Fighter Control Key. Outputs are the On, Auto, Off, and Trouble LEDs on the FSCS and an MCO that commands the DX points..

Figure 90: FSCS Elevator Fan 1 Main Logic

Page 82: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

82

The expanded elevator fan logic (Figure 91) consists of two control blocks: the FSCS block (Figure 92) and the Fan Trouble Control block (Figure 93).

Figure 91: FSCS Elevator Fan 1 FSCS and Fan Trouble Control Main Logic

Page 83: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

83

The FSCS logic (Figure 92) controls the elevator LEDs on the FSCS panel and commands the DX. The elevator On LED is lit only if the FSCS is in Fire Fighter Control and the elevator fan is on. The elevator Off LED is lit only if the FSCS is in Fire Fighter Control and the elevator fan is off. The elevator Auto LED is lit only if the toggle switch is not in the On or Off setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values, depending on the position of the toggle switch:

• On – 1

• Auto – 0

• Off – 2

Figure 92: FSCS Elevator Fan 1 FSCS Logic

Page 84: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

84

The Fan Trouble Control logic (Figure 93) sets the elevator fan Trouble LED on the FSCS. The Trouble LED is lit if the fan is in smoke control and the fan has not reached its desired setpoint within 60 seconds or one of the DX fuses has blown. A fan is in smoke control if the DX is in pressurize or depressurize mode, or the Fire Fighter Control Key is on and the FSCS toggle switch is set to On or Off.

The Elevator Fan 1 Trouble Interlock Definition (Figure 94) sets the values that, when reached, trigger a trouble alarm. The definition includes points for status and reliability of the DX AO and BI fuses, reliability of the elevator supply fan, the DX offline status, and the elevator fan failure alarm. The elevator supply fan failure alarm is triggered if the elevator supply fan fails a weekly test.

Figure 93: FSCS Elevator Fan 1 Fan Trouble Control Logic

Figure 94: FSCS Elevator Fan 1 Trouble Interlock Definition

Page 85: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

85

The Elevator Fan 1 MCO Action is shown in Figure 95. The Elevator Fan Auto point is a binary point in the DX to indicate that the fan is under automatic smoke control. When a fire fighter turns the fan on or off, the Elevator Fan Auto point is turned off. The Elevator Fan Command is a point in the DX to control the fan.

The FSCS Elevator Fan 1 toggle switch setting (Table 14) determines the state value, which in turn determines the smoke control action.Table 14: FSCS Elevator Fan 1 Switch State Value FSCS Elevator Fan 1 Switch Position

State Value Smoke Control Action

On 1 Elevator Fan 1 OnAuto 0 AutoOff 2 Elevator Fan 1 Off

Figure 95: FSCS Elevator Fan 1 MCO Action

Page 86: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

86

The FSCS Elevator Fan 1 Auto Pressure MCO Action Table (Figure 96) determines the state value, which in turn determines the smoke control action.

FSCS Firefighter Control LogicThe FSCS Fighter Control main logic (Figure 97) turns the Fire Fighter Control Auto LED on if the Fire Fighter Control Key is off. It turns the Fire Fighter Control LED on if the Fire Fighter Control Key is on. If the Programming in Progress point is on, the logic turns on the Programming Active LED. This point must be turned on any time changes are being made to the LCT application.

Figure 96: FSCS Elevator Auto Pressure MCO Action Table

Figure 97: Fire Fighter Control LED Main Logic

Page 87: Multi-Story Building Smoke Control with FSCS Override

The expanded Fire Fighter Control logic is shown in (Figure 98).

Figure 98: Fire Fighter Control Logic

Page 88: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

88

Using Multiple Smoke Control NAEs or NIEs

Requirements for Larger SitesThere are larger sites where, due to a large number of objects, several smoke control NAEs or NIEs may be required. If this is the case, then one smoke control NAE must be designated as the FSCS smoke control NAE and must connected directly to the FSCS. A Site Director smoke control NAE is used to monitor all smoke control NAEs and smoke control NIEs.

Object LimitsEach device and its programmed points use objects. There is a suggested object limit of, for performance purposes, 5,000 objects per smoke control NAE/NIE. When approaching the object limit it is sometimes necessary to add additional smoke control NAEs or NIEs.

Site Director Smoke Control NAEThe Site Director smoke control NAE provides the ability to monitor and control all devices connected to the smoke control system.

FSCS Smoke Control NAEThe FSCS smoke control NAE connects directly to the FSCS and monitors the Site Director smoke control NAE.

Smoke Control System Connection OverviewThe example multi-story smoke control system (Figure 99) shows the IFC panels, the FSCS panel , the Site Director smoke control NAE, the smoke control FSCS NAE, a smoke control NIE, and various N1 and N2 devices, communicating over Ethernet and fiberoptic connections.

Page 89: Multi-Story Building Smoke Control with FSCS Override

Figure 99: Example Multi-Story Smoke Control System

Page 90: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

90

FSCS AlarmsTable 15 shows the resulting FSCS alarms when any of the devices in the example multi-story smoke control system (Figure 99) go offline.

Monitoring the Site Director Smoke Control NAEThe Site Director smoke control NAE must be monitored by the FSCS smoke control NAE in the event it goes offline. The NAE Site Director Monitor Interlock (Figure 100) is used to monitor the Site Director. If the Site Director smoke control NAE goes offline the FSCS Smoke control NAE detects the offline alarm and sends trouble alarms to the FSCS for any floors, devices, or points being controlled by the Site Director smoke control NAE. .

To monitor the Site Director smoke control NAE:

1. Add a Site Director Monitor point (Figure 101) to the tree in the FSCS folder of the FSCS smoke control NAE

2. Create a folder inside the FSCS folder of the FSCS smoke control NAE for each floor the Site Director smoke control NAE monitors.

3. Inside each newly created floor folder, create a folder for Damper 1, Damper 2, Damper 3, Exhaust Fan 1, Supply Fan 1, VMA 1, and Zone Smoke LED.

Table 15: Example System Offline Device AlarmsOffline Device FSCS AlarmFSCS Smoke Control NAE Offline General Trouble LED + Sonalert Site Director Smoke Control NAE Offline Floors 1,2,3 All Point Trouble LEDs + Sonalert Smoke Control NIE Offline Floors 1,2 All Point Trouble LEDs + SonalertNCM 350 Floor 1 Offline Floor 1 All Point Trouble LEDs + SonalertNCM 350 Floor 2 Offline Floor 2 All Point Trouble LEDs + SonalertFloor 1 DX9100 Offline Floor 1 Damper and Fan Trouble LEDs + SonalertFloor 2 VMA Offline Floor 2 VMA Trouble LED + Sonalert

Figure 100: Site Director Offline Monitor Point Interlock Definition

Page 91: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

91

4. Add a Trouble LED Control interlock point for each device in the device’s respective folder (Figure 102). Include the Action Table for each device (Figure 103).

Figure 101: NAE Connections

Page 92: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

92

Figure 102: Trouble LED Control Interlock Definition

Figure 103: Damper 3-2 Trouble LED Control Action Table

Page 93: Multi-Story Building Smoke Control with FSCS Override

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

93

Monitoring a Smoke Control NIEEach smoke control NIE must be monitored by the Site Director in the event it goes offline. If a smoke control NIE goes offline the Site Director smoke control NAE detects the offline alarm and sends trouble alarms to the FSCS smoke control NAE for any floors, devices, or points being controlled by the smoke control NIE.

To monitor a smoke control NIE:

1. Add an NIE monitor point (Figure 105) to the tree in the FSCS folder of the Site Director smoke control NAE (Figure 104).

Figure 104: NIE Monitor and Trouble Interlocks

Page 94: Multi-Story Building Smoke Control with FSCS Override

Metasys® is a registered trademark of Johnson Controls, Inc.All other marks herein are the marks of their respective owners.

© 2005Johnson Controls, Inc.

Controls Group507 E. Michigan StreetMilwaukee, WI 53202

Published in U.S.A. www.johnsoncontrols.com

Multi-Story Building Smoke Control with FSCS Override - Metasys® System Extended Architecture Application Note

94

2. Add the NIE Monitor point to the Trouble Interlock for the fans, dampers and VMA of every floor the NIE controls (Figure 106).

Figure 105: NIE Monitor Trouble Interlock

Figure 106: NIE Monitor Trouble Interlock