Fundamentals of Oriental Medicine Emperors College Douglas Eisenstark L.Ac. [email protected] winter 2010 These are an ever evolving set of notes for the 10 weeks Fundamentals Class at Emperors College. They draw upon my own class with Chris Ting L.Ac at SAMRA University many years ago as well as notes created by previous Emperors teachers: Irene Heller, Yvonne Farrell, Cyndee Overland and Simon Shapiro. There is nothing new about Chinese Medicine, only ways to think and teach it. These notes come from books such as CAM, Maciocia, Scheid/Bensky Formulas and Strategies and the several basics books from Chinese translations. I will do my best to credit and footnote sources yet there cannot help but be omissions. In addition I have benefitted greatly by the on-line discussion groups including the Chinese Herbal Academy and I thank all in these venues and to my students and colleagues to whom I have turned for answers. All mistakes are my own. Fundamentals of Oriental Medicine Eisenstark ECTOM fall 2009 Eisenstark 1

MULTI-PURPOSESECURITYKEYPAD DK-9610 OUTPUT3 ......CONNECTIONTERMINALS!POWERINAC/DC OUTPUT1 OUTPUT2 Powersupplyinput,12VACorDCpoweris possible,nopolaritydiscriminationfortheterminals.!!

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: MULTI-PURPOSESECURITYKEYPAD DK-9610 OUTPUT3 ......CONNECTIONTERMINALS!POWERINAC/DC OUTPUT1 OUTPUT2 Powersupplyinput,12VACorDCpoweris possible,nopolaritydiscriminationfortheterminals.!!

CONNECTION TERMINALS

! POWER IN AC/DC

OUTPUT 1

OUTPUT 2

Power supply input, 12V AC or DC power ispossible, no polarity discrimination for the terminals.

!

!

5 Amp dry relay contacts, with Normally Open(N.O.) and Normally Close (N.C.) terminals. Thisrelay is primarily prepared for door strikeapplication, or for alarm ON-OFF control. For doorstrike connection, use the N.O. Relay contact forFail-secure lock; and the N.C. Relay contact for fail-safe lock. If for alarm ON-OFF control, connect theappropriate pair of these terminals (N.C. or N.O.) tothe remote ARM/DISARM terminals on your alarmsystem; consult the manual for your system. N.O.or N.C. loop is possible. Relay is programmable formomentary or start / stop operation.

Output 2 is prepared for alarm ON-OFF control orfor reporting panic event to an alarm system or toa telephone dialer. The output is programmable formomentary or start / stop operation.

1Amp dry relay contacts, with N.O.and N.C. terminal outputs.

NPN transistor open collector output,switch of the (-) supply. Ic max: 150mA sink, Vcemax: 12V DC.

Version A & B:

Version C:

FOR DOOR STRIKE AND SECURITY CONTROL APPLICATIONS

PRODUCTOUTPUT OUTPUT 1 OUTPUT 2 OUTPUT 3

DK-9610A Super

DK-9610B Super

DK-9610C Super

5 Amp Relay 1 Amp Relay 1 Amp Relay

5 Amp Relay 1 Amp Relay NPN Transistor Open Collector

5 Amp Relay NPN Transistor Open Collector NPN Transistor Open Collector

INTRODUCTIONDK-9610 Super is a self-contained, three output digital access keypad designed for door strike and other accesscontrol applications in office and home security installations.

The DK-9610 Super consists two sets of application software for owner's selection. They are Single User Code andMulti-User Codes for each output. The single user code gives 10,000 combinations and the multi-users code givesover 100 million combinations. All the saved data in the system are nonvolatile in case of power failure.

The DK-9610 Super is weatherproof, which is suitable for both out-door and in-door installations. The DK-9610Super is available with version A, B and C. They have identical specifications except the outputs.

MULTI-PURPOSE SECURITY KEYPADWEATHERPROOF THREE-OUTPUT SYSTEM

1

DK-9610SUPER

DK-9610A

DK - 9 6 1 0 - 0

+

++

12VAC/DC

NO C NCOUTPUT 1

NO C NCOUTPUT 2

BUZZER

RED LED

GREEN LED

N.O. EGRESSDURESS OUTPUTN.C. DOOR SENSINGGROUND ( - )

N.C. TAMPER

OUTPUT 3 (RELAY)

OUTPUT 1 (RELAY)OUTPUT 2 (RELAY)

12V AC/DCPOWER INPUT

DAPJUMPER

TAMPERSWITCH

2

!

!

!

!

!

!

!

OUTPUT 3

-

-

TAMPER N.C.

GROUND (-)-

DOOR N.C.

-

--

NOTE:-

DURESS OUTPUT

-

EGRESS N.O.-

-

GREEN & RED LEDS

Output 3 has identical function as output 2. It isrecommended for alarm ON OFF control or for theauxiliary functional control in your system.

1Amp dry relay contacts, with N.O. andN.C. terminal outputs.

NPN transistor open collector output,switch of the ( ) supply. Ic max: 150mA sink, Vcemax: 12V DC.

Tamper switch Normally Close contact. It is openwhen the keypad is separated from the mounting box.

The ( ) grounding point of the keypad.

This terminal is prepared for connecting a NormallyClosed optional door sensing switch (e.g. MC 01 orMC-02 Magnetic Contact) to the door which iscontrolled by output 1, for initiating the auto re-lockfunction.With the help of the door sensing switch, the keypadreleases the door latch immediately to re lock the doorautomatically after the door is re-closed even the preset operation time is not expired in momentary mode;or you do not require to enter Code 1 again to re-lockthe door when the keypad is in Start / Stop mode.In normal operation without the door sensing switch,an opened door is re-locked after timeout inmomentary mode; or by entering Code 1 again in Start/ Stop mode.

If the door sensing switch is not used, connectthe terminal to Ground ( ).

NPN transistor open collector output, switches of the( ) supply when the Duress Code is entered. Use thisoutput to trigger remote alarm, dialer, indicator etc., incase of duress. Transistor rating -- Ic max: 150mA,Vce max: 12V DC

A Normally Open (N.O.) input terminal refers to ( )ground with the help of a normally open button (e.g.PB 01 Egress Button) to activate the Relay Output 1.Egress button is usually put inside the house near thedoor. Leave this terminal open if it is not used.

Two de-energized LED lamps are available for freeconnections, to indicate alarm or door operationstatus. They are built-in with 1.5K Ohm current limitingresistors.

Version A:

Version B & C:

RED

AMBER(STATUS)

ILLUMINATION

GREEN

F I X I N GSCREWS

#

Page 2: MULTI-PURPOSESECURITYKEYPAD DK-9610 OUTPUT3 ......CONNECTIONTERMINALS!POWERINAC/DC OUTPUT1 OUTPUT2 Powersupplyinput,12VACorDCpoweris possible,nopolaritydiscriminationfortheterminals.!!

THE PACIFIER TONES THE LED INDICATING SIGNALS

KEYBOARD ILLUMINATION LED

THE DAP JUMPER D A P

&The built-in buzzer and the amber LED indicator give the following tones and signals for operation status:

The keyboard illumination LED lights up for 10 seconds when a key button is pressed, which indicates the durationof the allowable time for each digit of continuous code entry. The digit of code entry is invalid beyond the allowabletime when the LED lamp is off.

f the Personal Master Code is forgotten, use the DAP jumper to override the forgotten code permitting direct entryinto programming mode. You are required to apply the following procedures precisely:

1. Disconnect power supply.2. Displace the DAP jumper from OFF to ON position.3. Reconnect power supply (buzzer is activated).4. Put the DAP jumper back to OFF position (this done, the buzzer is de-activated).5. The keypad is in programming mode and ready to receive new programming data.6. Enter the new programming data starting from Section (B) in the Summary Chart shown below.

Set system to Single User Mode, clear all the data previously stored and refreshsystem with the default values

Set system to Multi User Mode, clear all the data previously stored and refreshsystem with the default values

( IRECT CCESS TO ROGRAMMING)I

THE FACTORY-SET DATA

PROGRAMMING OF THE KEYPAD

-- IMPORTANT NOTE

-- SUMMARY CHART

For the owner's convenience in programming at the first time, the factory has put a Master Code 0000 and theDefault Values (listed on page 5) into the keypad. The owner has to put his own unique codes before use. Tocompromise security, in all cases, the owner should program a Personal Master Code to invalidate the factory-setMaster Code.

Enter into Programming Mode by the Factory-set Master Code

A) Use The Factory-set Master Code Entry in Programming

B) Set System to Single User or Multi User Mode & Refresh with The Default Values

-- When star ts for first time

--Installer Programming

0000 *

8900 #

8901 #

Entry of Code Validation Comments

Access Keys Validation Comments

3

STATUS1. In programming mode2. Successful key entry3. Successful code entry4. Unsuccessful code entry5. DAP jumper not replaced6. In standby mode

TONES- - -

- - -

1 Beep2 Beeps5 BeepsContinuous Beeps

LED SIGNALSON1 Flash2 Flashes5 Flashes

1 Flash in 2 seconds intervalContinuous Flashes

4

C) Recording of Personal Master Code User Codes& -- User Programmingi) Programming for Single User

Master Code

User Code 1

User Code 2

User Code 3

4 digits, fixed Personal & Super User Code

with Duress

4 digits, fixed (Suggest for alarm arm-disarm control)

(Suggest for other auxiliary access control)

1 to 999

1 to 999

1 to 999

After 10 successive false codes, the keypad locks during 30seconds

After 10 successive false codes, the Duress output swi tches toground

00 Disappearance of all the above securities

0 #1 #

2 #3 #

404142505152606162

70

71

76

4 digits, fixed

4 digits, fixed

4 to 8 digits Personal & Super User Code

00 to 99 4 to 8 digits 100 with Duress(Suggest for door Strike)

0 to 9 4 to 8 digits 10(Suggest for alarm arm-disarm control)

0 to 9 4 to 8 digits 10(Suggest for other auxiliary access control)

Output 1 in Momentary Mode from 1 to 999 seconds

Output 1 in Start / Stop Mode without accelerated code

Output 1 in Start / Stop Mode with accelerated code

Output 2 in Momentary Mode from 1 to 999 seconds

Output 2 in Start / Stop Mode without accelerated code

Output 2 in Start / Stop Mode with accelerated code

Output 3 in Momentary Mode from 1 to 999 seconds

Output 3 in Start / Stop Mode without accelerated code

Output 3 in Start / Stop Mode with accelerated code

5 to 10 Selectable of after 5 to 10 successive false codes, the keypadlocks during 15 minutes. The keypad can be reset to releaselocking with the Master Code at any time during the locking period

ii) Programming for Multi-Users

Master Code

User Codes in Group 1

User Codes in Group 2

User Codes in Group 3

0 #1 #

2 #

3 #

#########

#

#

72 #

#

D) Configuration of Relay Outputs

E) Personal Safety

-- Installer Programming

-- Installer Programming

Access Keys Entry of Codes Validation Comments

Access Keys Code Duration

Access Keys No. Of False Entry Validation Comments

Code function(Suggest for door strike)

Access Keys User Number Entry of Codes Validation Comments

Validation Comments

Codefunction

Page 3: MULTI-PURPOSESECURITYKEYPAD DK-9610 OUTPUT3 ......CONNECTIONTERMINALS!POWERINAC/DC OUTPUT1 OUTPUT2 Powersupplyinput,12VACorDCpoweris possible,nopolaritydiscriminationfortheterminals.!!

5

F) Exit Programming Mode

The Default Values

* Keypad exits programming mode and returns to normal operation

The keypad consists two sets of software for owner's selection in user code programming. One is "Single UserCode for Each Output" and the other is "Multi-User Codes for Each Output".

The keypad has been set with a Master Code of "0000" and Multi User Mode with the following "Default Values" atthe factory. You do not require to make any operation mode change if your selection is Multi-User Mode. However,You have to refresh the system to

401 --- Output 1 is 1 Second Momentary Mode501 ---

0000

SINGLE USER OR MULTI-USERS SELECTION

Single User Mode if it is your selection.

Output 2 is 1 Second Momentary Mode601 --- Output 3 is 1 Second Momentary Mode70 ----- After 10 Successive False Code, The Keypad Locks During 30 Seconds

The mode of allow only User Code for each output, and it is fixed to 4 digits. This mode isprepared for those people DO NOT like to press the key for code entry to activate the output. They only pressthe 4 digit User Code, then, the specific output is activated. Each output has its own code.

The Single User CodeSingle User Code ONE

#

#

!

!

!

* # ----------

Validation Comments

The Multi-User Codes

Code Entry Limitation for Multi-User Codes

The mode of is prepared for setting up a group of user codes for each output. The User Codes can be4 to 8 digits. To activate the desired output, the user has to press the key to confirm of code entry in theoperation of the Multi-User Code. The following are the number of User Codes available in each group:

User Codes in Group 1 for Output 1 --- 100 UsersUser Codes in Group 2 for Output 2 --- 10 UsersUser Codes in Group 3 for Output 3 --- 10 Users

As the system comes with function and the DURESS CODE is setting up by the system automatically withthe first digit of the User Code "+2". To prevent the other User Codes fall into the Duress Code, or the DuressCodes fall into other User Codes, the first digit of a " " User code "+2" or "-2" is not allowed for the laterUser Code entry in programming. The system will refuse those code entries.

An User Code 56789 is saved in the system, then 36789 and 76789 are not allowed for other UserCodes.

You are required to decide the keypad for Single User or Multi-User Mode in operation. The system can be set forwith the command code " " and stay in that mode until the system is refreshed for other

mode.

Multi-Users

DURESS

Saved

For example:

Single User Mode 8900

MASTER CODE Single User Mode

SET THE SYSTEM TO SINGLE USER MODE

8900 (wait 2-3 seconds until the confirmation beeps are heard)

The Factory Set Master Code

SET THE SYSTEM TO MULTI-USER MODE

REFRESH THE SYSTEM

The system can be set for with the command code " " and stay in that mode until thesystem is refreshed for other mode.

A system was set to It is possible to change it to ; or vice versa. Just refreshthe system with the above operation command codes.

A refreshed keypad will reset itself as a fresh unit with the Default Values.

Make sure all the and are set to after the system is refreshed for SingleUser Mode operation. Otherwise, code entry will not be successful.It is necessary to change the Master Code to 4 digits first (if it was more than 4 digits in Multi Users Mode)before refreshing from Multi User Mode to Single User Mode.The system takes approximate 2 to 3 seconds to refresh itself for new operation mode after the refresh code isentered. DO NOT enter any code during the system is being refreshed until the 2 confirmation beeps are heard.

Multi User Mode 8901

MASTER CODE Multi-User Mode

Single User Mode. Multi-User Mode

All the programmed data that savedpreviously are cleared except the Master Code.IMPORTANT NOTES:1) User Codes Master Code 4 Digits

2)

3)

8901 (wait 2-3 seconds until the confirmation beeps are heard)

-- CHANGE OF OPERATION MODE

q

* #-----------

0000 *8900 #0 3289 #1 8321 #2 6854 #3 9270 #40 1 #51 #62 #72 10 #*

PROGRAM AND USE THE KEYPAD -- OPERATIONOnce the operation mode is selected - Single User or Multi Users, all the three outputs will operate with that mode.

-- Set the following data into the system:

a) Single User Mode Operationb) Change the factory-set Master Code 0000 to a Personal Master Code 3289c) Set User Code 1 in 8321d) Set User Code 2 in 6854e) Set User Code 3 in 9270f ) Set Output 1 in Momentary Mode, 1 secondg) Set Output 2 in Start / Stop Mode without accelerated codeh) Set Output 3 in Start / Stop Mode with accelerated codei ) Set the keypad to lock itself during 15 minutes after 10 successive false codes

1) Re uirement

2) Programming -- Set the above requirement into the keypad:

--------------- Enter to programming mode with the factory-set Master Code

-------------- System has been set for Single User Mode**

---------- 3289 has been saved as the new Personal Master Code Super User Code

---------- 8321 has been saved as User Code 1, with Duress function

---------- 6854 has been saved as User Code 2

---------- 9270 has been saved as User Code 3

--------------- Output 1 has been set in Momentary Mode, 1 second

------------------ Output 2 has been set in Start / Stop Mode without accelerated code

------------------ Output 3 has been set in Start / Stop Mode with accelerated code

------------ The keypad has been set to lock during 15 minutes after 10 successive false codes

------------------------- Keypad exits programming mode. All the data above are saved and ready for use

&

A) SINGLE USER MODE OPERATION -- An Example

6

Page 4: MULTI-PURPOSESECURITYKEYPAD DK-9610 OUTPUT3 ......CONNECTIONTERMINALS!POWERINAC/DC OUTPUT1 OUTPUT2 Powersupplyinput,12VACorDCpoweris possible,nopolaritydiscriminationfortheterminals.!!

NOTE:

c) Duress CodeUser Code 1 of Two units

For example:

NOTE:

a) **Enter the Single User Mode Command Code "8900" may not be necessary if the keypad wasalready in Single User Mode.

b) In case of wrong entry during programming, cancel it with key, or, wait 10 seconds, then re-enter.

The does not need to program. The keypad determines it automatically by increasing thefirst digit of the .

The User Code 1 is "1234", then the Duress Code is "3234"; or the User Code 1 is"8321", then the Duress Code is "0321".

To command the Duress Function, enter the Duress Code

The Duress Code has double actions. It activates the Duress Output and at the same time activates theOutput 1 as like the User Code 1. The Duress Code can always activates or deactivates (in Start / Stopmode) Output 1, but cannot deactivate (reset) the Duress Output. ONLY the User Code 1 can deactivate(reset) the Duress Output.

In this example, Output 3 has been programmed in Start / Stop Mode with Accelerated Code.The Complete Code of Code 3: The Accelerated Code of Code 3:

.

.

#

#

3) Operate The Keypad

a) Press is NOTrequired.

b) Super User Code

d) Accelerated Code First Two Digitsactivate

e) Safety

-- Taking the data programmed above as reference

To command the output 1, 2 & 3, enter the corresponding codes into the keypad.

----------------- Output 1 activates for 1 second

----------------- Output 2 starts (or stops)

----------------- Output 3 starts (or stops)

The Personal Master Code is also a . It allows the owner to use Only One Code tooperate all the 3 outputs. To command output 1, 2 or 3, enter the Personal Master Code and validate

via the key and the corresponding output number.

---------- Output 1 activates for 1 second

---------- Output 2 starts (or stops)

---------- Output 3 star ts (or stops)

----------------- Duress output activates

The is the of the User Code. If the User Code 1, 2 or 3 has beenprogrammed in Start / Stop mode with Accelerated Code, it is possible to the correspondingOutput 1, 2 or 3 with only the First Two Digits of the User Code. Deactivating of the correspondingOutput 1, 2 or 3 always requires the composition of its own Complete User Code.

---------------- Output 3 starts

----------------- Output 3 stops

Try to put some random false codes to the keypad to test its . The keypad considers 4 digits asone code and it generates 5 beeps for each unsuccessful code entry. The keypad locks itself during 15minutes after 10 successive false codes are entered. Normal operation will be resumed after 15minutes expired, or, it can be reset with the Master Code during the locking period.

------------ Locking is reset and keypad resumes normal operation

#

832168549270

3289 #13289 #23289 #3

0321

92 #9270

3289 #

(output switches to ground) & Output 1 activates for 1second

9270 92

7 8

B) MULTI-USER MODE OPERATION -- An Example1) Re uirement

2) Programming

NOTE:

-- Set the following data into the system:

a) Multi-User Mode Operationb) Change the factory-set Master Code 0000 to a Personal Master Code 3289c) Set 1st User Code of Group 1 in 8321d) Set 2nd User Code of Group 1 in 11223e) Set 3rd User Code of Group 1 in 33221f ) Set 1st User Code of Group 2 in 6854g) Set 2nd User Code of Group 2 in 54321h) Set 1st User Code of Group 3 in 9270i ) Set 2nd User Code of Group 3 in 22898j ) Set Output 1 in Momentary Mode, 1 secondk ) Set Output 2 in Start / Stop Mode without accelerated codel ) Set Output 3 in Start / Stop Mode with accelerated codem) Set the keypad to lock itself during 15 minutes after 10 successive false codes

-- Set the above requirement into the keypad:

--------------------------- Enter to programming mode with the factory-set Master Code

-------------------------- System has been set for Multi User Mode**

---------------------- 3289 has been saved as the new Personal Master Code Super UserCode

---------------- 8321 has been saved as the 1st User Code of Group 1 with Duressfunction

-------------- 11223 has been saved as the 2nd User Code of Group 1 with Duressfunction

-------------- 33221 has been saved as the 3rd User Code of Group 1 with Duressfunction

------------------ 6854 has been saved as the 1st User Code of Group 2

---------------- 54321 has been saved as the 2nd User Code of Group 2

------------------ 9270 has been saved as the 1st User Code of Group 3

---------------- 22898 has been saved as the 2nd User Code of Group 3

-------------------------- Output 1 has been set in Momentary Mode, 1 second

------------------------------ Output 2 has been set in Start / Stop Mode without accelerated code

------------------------------ Output 3 has been set in Start / Stop Mode with accelerated code

------------------------ The keypad has been set to lock during 15 minutes after 10successive false codes

------------------------------------- Keypad exits programming mode. All the data above are saved andready for use

a) **Enter the Multi User Mode Command Code "8901" may not be necessary if the keypadwas already in Multi User Mode.

b) In case of wrong entry during programming, cancel it with key, or, wait 10 seconds, thenre-enter.

0000 *8901 #0 3289 #

1 01 8321 #

1 02 11223 #

1 03 33221 #

2 1 6854 #2 2 54321 #3 1 9270 #3 2 22898 #40 1 #51 #62 #72 10 #

*

&

#

q

Page 5: MULTI-PURPOSESECURITYKEYPAD DK-9610 OUTPUT3 ......CONNECTIONTERMINALS!POWERINAC/DC OUTPUT1 OUTPUT2 Powersupplyinput,12VACorDCpoweris possible,nopolaritydiscriminationfortheterminals.!!

9

3) Operate The Keypad

a)

b)

c)

d) Super User Code

e) Duress CodesUser Codes Two units

For example:

NOTE:

f) Accelerated Code First Two Digitsactivate

-- Taking the data programmed above as reference

To command the output 1, enter any one of the User Codes in Group 1 into the keypad and validate viathe key

------------ Output 1 activates for 1 second

---------- Output 1 activates for 1 second

---------- Output 1 activates for 1 second

To command the output 2, enter any one of the User Codes in Group 2 into the keypad and validate viathe key

------------ Output 2 starts (or stops)

---------- Output 2 starts (or stops)

To command the output 3, enter any one of the User Codes in Group 3 into the keypad and validate viathe key

------------Output 3 starts (or stops)

---------- Output 3 starts (or stops)

The Personal Master Code is also a . It allows the owner to use Only One Code tooperate all the 3 outputs. To command output 1, 2 or 3, enter the Personal Master Code and validatevia the key and the corresponding output number.

----------

----------

----------

The do not need to program. The keypad determines it automatically by increasing thefirst digit of the . All the User Codes in Group 1 have Duress Code Function.

8321 032111223 3122333221 53221

To command the Duress Function, enter the Duress Code(s).

------------ Duress output activates

---------- Duress output activates

---------- Duress output activates

The Duress Code(s) has double actions. It activates the Duress Output and at the same time activatesthe Output 1 as like the User Codes of Group 1. The Duress Code(s) can always activates ordeactivates (in Start / Stop mode) Output 1, but cannot deactivate (reset) the Duress Output. ONLY theUser Codes of Group 1 can deactivate (reset) the Duress Output.

The is the of the User code(s). If the User Code(s) of Group 1, 2 or3 has been programmed in Start / Stop mode with Accelerated Code, it is possible to thecorresponding Output 1, 2 or 3 with only the First Two Digits of the User Code(s). Deactivating of thecorresponding Output 1, 2 or 3 always requires the composition of the Complete User Code(s).

#

#

#

#

8321 #11223 #33221 #

6854 #54321 #

9270 #22898 #

3289 #13289 #23289 #3

0321 #

31223 #

53221 #

Output 1 activates for 1 second

Output 2 starts (or stops)

Output 3 starts (or stops)

(output switches to ground) & Output 1 activates for 1second

(output switches to ground) & Output 1 activates for 1second

(output switches to ground) & Output 1 activates for 1second

User Codes of Group 1 The Corresponding Duress Codes

10

In this example, Output 3 has been programmed in Start / Stop Mode with Accelerated Code.The Complete Code of 1st User Code of Group 3: The Accelerated Code is:

2nd User Code of Group 3: The Accelerated Code is:

---------------- Output 3 starts------------ Output 3 stops

---------------- Output 3 starts---------- Output 3 stops

Try to put some random false codes to the keypad to test its . The keypad generates 5 beeps foreach unsuccessful code entry. The keypad locks itself during 15 minutes after 10 successive falsecodes are entered. Normal operation will be resumed after 15 minutes expired, or, it can be reset withthe Master Code during the locking period

------------ Locking is reset and keypad resumes normal operation

----------------- The keypad is in Programming Mode ready to receive new data

---------------------------- All the new data are saved and the keypad is back to normal operation mode

----------------- System in programming mode---------------- System is refreshed for Single User Mode and ready to accept new data after the

confirmation beepsOR

---------------- System is refreshed for Multi User Mode and ready to accept new data after theconfirmation beeps

g) Safety

9270 9222898 22

92 #9270 #22 #22898 #

3289 #

3289 *

*

3289 *8900 #

8901 #

.

C) RE-PROGRAM THE KEYPAD WITH NEW DATA

D) REFRESH THE SYSTEM

It is possible to change the current data at anytime, such as change the User Codes, Door Open timing, etc.

Make the system in first. Enter your Personal Master Code and validate via key.

After the system is in Programming Mode, you can enter the appropriate "Access Keys" number and put inthe new data in the location. Please see the programming "Summary Chart" for details. You can re-programany individual item in the Summary Chart.

It is necessary to exit the programming mode and save the new data after programming via the key

It is possible to change the current operation mode (Single User or Multi-User Mode) by refreshing the systemwith the User Mode Command Code (8900 or 8901) and re-program the keypad with new data.

All the current data in the system will be cleared and save with the DefaultValues once the system is refreshed.

To refresh the system, set system in programming mode and then enter the appropriate

and validate via key.

The system takes approximate 2 to 3 seconds to refresh itself for the new operation mode. DO NOT

enter any data immediately after the validation key is pressed until the 2 confirmation beeps areheard.

After the system is refreshed, it is still in Programming Mode. You can consider it as a new keypad powerup at the first time and program it with new data. Please see the programming "Summary Chart" for details.You can re-program any individual item in the Summary Chart.

1) Programming Mode

2)

3)

NOTE: except the Master Code

1) User Mode

Command Code (8900 or 8901)

NOTE:

2)

*

*

#

#

&

-- IT IS REQUIRED ONLY FOR CHANGING OPERATION MODE

Page 6: MULTI-PURPOSESECURITYKEYPAD DK-9610 OUTPUT3 ......CONNECTIONTERMINALS!POWERINAC/DC OUTPUT1 OUTPUT2 Powersupplyinput,12VACorDCpoweris possible,nopolaritydiscriminationfortheterminals.!!

11

3)

1)

2)

3)

Operation Voltage

Code Combinations A)

Duress Output

Dimensions

Weight

It is necessary to exit the programming mode and save the new data after programming via the key

If you need to delete a user who has left the company or who no longer has authority to enter the protectedarea:

Enter program mode by keying in your Personal Master Code and the key

----------------- The keypad is now in the programming mode

Enter the User Number and the key

If you want to delete User Number 05 from output 1, press

If you want to delete User Number 3 from output 2, press

If you want to delete User Number 2 from output 3, press

Exit the programming mode by pressing the key

: Single User Mode --- 10,000 for each User Code

0g net

Specifications are subject to change for modification without notice

**---------------------------- All the new data are saved and the keypad is back to normal operation mode

: 12V AC/DC Nominal , 10-14VAC or 12-16VDC

: Version ) 15-150mA; Version ) 15-110mA; Version ) 15-80mA

: Single User Mode- User Code 1, 2 & 3 (Fixed to 4 Digits)- Master Code (Fixed to 4 Digits)- Super User Code (4 digits Plus Output Number)- Duress Code (Fixed to 4 Digits)- Accelerated Code (2 Digits)

Multi User Mode- User Codes in Group 1 - 100 Users (4-8 Digits)- User Codes in Group 2 - 10 Users (4-8 Digits)- User Codes in Group 3 - 10 Users (4-8 Digits)- Master Code (4-8 Digits)- Super User Code (4-8 digits Plus Output Number)- Duress Codes (4-8 Digits)- Accelerated Codes (2 Digits)

Multi User Mode ---- 111,110,000 for each User Code

: Output 1 -- 5A / 30VDC Max. N.C. & N.O. Dry ContactsOther Outputs -- 1A / 30VDC Max. N.C. & N.O. Dry Contacts (or NPN open

collector output)

: 100mA Sink / 12VDC Maximum, Open Collector switches to ground (-)

: 10 seconds, auto refresh

: 30 seconds, auto refresh

: 129(H) x 84(W)mm X 41(D)mm, Weatherproof Plastic Case

: 22

E) DELETE USER (MULTI-USER MODE)

*3289 *

#1 05 #

2 3 #3 2 #

*

SPECIFICATIONS!

!

!

!

!

!

!

!

!

!

Current Drain A B C

Operation Codes Available A)

B)

B)

Relay Output Contacts

Digit Entry Allowable Time

Code Entry Allowable Time

TYPICAL APPLICATION

APPENDIX

*Output 1: *Output 2: Output 3:

DRY CONTACT

N.C.

N.O.

TRANSISTOR OPEN COLLECTOR OUTPUT

Door Strike Alarm Control * Auxiliary Alarm Control

* Please consult your alarm control panel manual for the selection of N.C. or N.O. for system ON-OFF control. Forthose Open Collector Outputs at the DK-9610B/C, please consider them as N.O. contacts referring to ground.

A dry contact means that no electricity was connected to it. It is prepared for free connections. Usually the relayoutput contacts provided in a keypad system are dry contacts.

Normally Closed, the contact is closed circuit at normal status. It is open circuit when activated.

Normally Open, the contact is open circuit at normal status. It is closed circuit when activated.

An open collector output is equivalent to a Normally Open (N.O.) contact referring to ground similar to a relaycontact referring to ground. The transistor is normally OFF, and its output switches to ground (-) when activates.The open collector can only provide switching function for small power but it is usually good enough forcontrolling of an alarm system.Output 2 & 3 in DK-9610C, output 3 in DK-9610B, and the Duress Output in all three keypads are opencollector outputs.

!

!

!

!

12

SINCE 1979AEI ADVANCED ELECTRONICS INDUSTRY LTD.

SILENT PANIC OR DIALER (N.O. ZONE)

(-) COMMON GROUNDN.O.COM.N.C.

(-) COMMON GROUNDN.O.COM.N.C.

N.O.COM.N.C.

N.O.COM.N.C.

(OUTPUT 2)

(OUTPUT 3)

GREEN LED (FOR REMOTE STATUS)+

+

+

+

+ +

-

-

AUXILIARYALARM

N.C. TAMPER

RED LED (FOR REMOTE STATUS)

MAIN ALARM

GREEN LED

OUTPUT 3

N.C. TAMPER

RED LED

OUTPUT 1

DUR O/P

OUTPUT 2

GND (-)

(+)

(+)

( )-

DURESS OUTPUT

RED LED

N.C. TAMPER

GREEN LED

N.O. EGRN.C. DR

12VAC/DC

GROUND (-)EGRESS N.O.DOOR N.C.N.O.COM.

POWER INPUTPOWER INPUT (MC-01)

MAGNETICSWITCH

EGRESSBUTTON

(INSIDE HOUSE)

N.C.

12V AC/DCELECTRIC

LATCH(OUTPUT 1)

12V POWERAC/DCDK-9610A

ELECTRIC DOOR STRIKE(OPTIONAL)DOOR OPEN

SENSING SWITCH12V AC/DC

* ALARM ON-OFFCONTROL

* ALARM ON-OFFCONTROL