Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
MOVE-MS-03-B-EN
MOUNTING
INSTRUCTION
FOR EI160 SLIDING DOOR
MODEL
MS0671EI160
MOVE-MS-03-B-EN
Content
General conditions ......................................................................................................................... 3
Content of delivery ......................................................................................................................... 3
Types of walls/fixings ..................................................................................................................... 4
Installation ..................................................................................................................................... 5
Tools for mounting ..................................................................................................................... 5
Control of wall opening ............................................................................................................... 5
Distances between wall and frame ............................................................................................. 5
Mounting of counter frame (option) ............................................................................................ 6
Mounting of frame ...................................................................................................................... 6
2. Mounting .................................................................................................................................... 9
2.2 Fixing of frame (option) ........................................................................................................ 9
2.3 Mounting of frame ................................................................................................................ 9
2.4 Mounting of impact list and cover plate .............................................................................. 12
2.5 Mounting of brackets for guide rail ...................................................................................... 12
2.6 Mounting of guide rail ......................................................................................................... 13
2.7 Mounting of rollers .............................................................................................................. 13
2.8 Mounting of door ................................................................................................................ 14
2.9 Mounting of bottom guide rail ............................................................................................. 14
2.10 Mounting of magnet .......................................................................................................... 15
2.11 Mounting of drop plumb .................................................................................................... 16
3. Final mounting ......................................................................................................................... 18
3.1 Adjustment of the door ....................................................................................................... 18
3.2 Maintenance ...................................................................................................................... 18
3.3 Contact............................................................................................................................... 18
MOVE-MS-03-B-EN
General conditions
• It is essential for the fire properties of the fire door, that the door is correctly installed in accordance with these instructions.
• The fire door shall be mounted by qualified personnel.
• The person/company, who mounts the fire door, is responsible for, that the door is mounted correctly.
• The frame must not be filled with concrete.
• Do not change the content or texture of the insulation of the frame. It will impair the fire properties of the fire door.
• Do not mill, cut, drill or do any other machining of the door or frame.
• Do not mount letter slot or peep hole in the door.
• Inflammable flooring, ex. carpet, must not go through the wall opening or underneath the door.
• Door sign or other signs moreover, shall be visible, valid, and must not be covered or painted.
• If door plate or other signs moreover, is damaged or disappears, the door must not be used as a fire door until it is identified as a fire door and the signs are re-established. The identification shall be done by the fire authority.
• The owner of the fire door is responsible for that the door is operational.
• Changes on the door is not allowed, as it will degrade the fire resistance of the door.
Content of delivery
Description Comment
Counter frame, 3 or 4 frame parts incl. connectors Option
Frame with attached sliding rail and connectors Connector for cover attached (option).
Door magnet for use for smoke alarm Option
Counterweight
Support for sliding rail Only for light wall
Sliding rail part B with connectors for cover (option)
Kit with guide rail for floor, incl. fasteners
Door leaf prepared with rollers and handles
Necessary bolts, muster, screws and plugs for installation
Cover for sliding rail Option
MOVE-MS-03-B-EN
Types of walls/fixings
MOVE-MS-03-B-EN
Installation
Tools for mounting
Wedge Level Clamps Power drill/screwdriver/riveter Bolts/screws/plugs etc.
Control of wall opening
Make sure the wall opening is level and perpendicular and in accordance with the order confirmation
Kontroller om gulv og hul er i vater.Control if floor and hole is in level.
Kontroller mål på murhulsåbning.Control measurement of wall opening.
Distances between wall and frame
The distance between the inside of the frame and the wall opening should always be 15±3 mm. See drawing below.
15±3
MOVE-MS-03-B-EN
Mounting of counter frame (option)
Eventuel modkarm skal altid monteres før karmen.
The counter frame is held against the wall with clamps (opposite the side of the wall where the sliding door is to be fitted). Before the final fastening of the counter frame, it has to be checked that the counter frame is in level both horizontal and vertical. The counter frame is prepared with mounting holes and underlying mounting connectors where the counter frame has to be fastened. Drill holes through the mounting holes and fasten the counter frame with the supplied fasteners.
Mounting of frame
Back
Front
MOVE-MS-03-B-EN
Check the wall opening size and the size of the frame are the same.
To make sure the door is covering the wall opening, make sure the distance between the inside of the frame to the wall opening at any place along the opening is 15±3mm. See figure below.
When the door is closed, the distance between the frame and the door should only be enough to make sure the door can run smoothly in the guide rail at the top of the door leaf.
If the requirements are not kept, the wall opening has to be adjusted, so the requirements can be fulfilled. This adjustment is to be agreed with the owner of the door. The company who mounts the door is responsible for this agreement.
DO NOT CHANGE ANYTHING ON THE FIRE DOOR; IT WILL IMPAIR THE FIRE PROPERTIES OF THE DOOR.
15±3
MOVE-MS-03-B-EN
DMAKE SURE THE WALL IS STRONG ENOUGH TO CARRY THE DOOR. IF THAT IS NOT THE CASE THE WALL SHOULD BE REINFORCED OR A SELF-SUPPORTING FRAME SHOULD BE INSTALLED.
MOVE-MS-03-B-EN
2. Mounting
Parts for installation of the sliding door are part of the delivery.
2.2 Fixing of frame (option)
2.3 Mounting of frame
MOVE-MS-03-B-EN
Max
. 10
15±3
1
Inderkarme og karmfalser monteres sætvise.
Hvis døren åbnes mod venstre, startes der med venstre karmside.
Inner frames and frame rebate to be mounted in sets.If the door opens to the left, start with the left side of the frame.
15
Kontroller om gulv og hul er i vater.Control if floor and hole is in level.
Kontroller mål på murhulsåbning.Control measurement of wall opening.
Only use dimensionally stable material for shims/blocking up. NB! Do not use foam for mounting or fixing of the frame. Fix the frame in the wall opening with screws in all the holes in the frame. Before final fixing, the following has to be checked:
• The frame is in plumb and level.
• The frame is placed correct in proportion to the final level of the floor. The distance between final level of floor and frame must not be more than 10 mm.
MOVE-MS-03-B-EN
4
Forkant og bagkant monteres parallelt.Front and rear to be mounted parallel.
230
3
Topkarm monteres. Kontrollér at den er i vater.Top frame to be mounted. Control if it is in level.
25
MOVE-MS-03-B-EN
=
=
½ ½
G
G
325
Alternativt kan beslagene monteres på køreskinnen
inden montage på væg.
As an alternative, the brackets can be pre-mounted
the rails before mounting at the wall.
2.4 Mounting of impact list and cover plate
C C
Anslagsliste monteres.Impact list to be mounted.
E E
Dækliste monteres.Cover plate to be mounted.
2.5 Mounting of brackets for guide rail
MOVE-MS-03-B-EN
124100
2.6 Mounting of guide rail
2.7 Mounting of rollers
MOVE-MS-03-B-EN
2.8 Mounting of door
2.9 Mounting of bottom guide rail
MOVE-MS-03-B-EN
15
61
2.10 Mounting of magnet
MOVE-MS-03-B-EN
2.11 Mounting of drop plumb
MOVE-MS-03-B-EN
Drop plomb
MOVE-MS-03-B-EN
3. Final mounting
NB: Lock cases or any other fixing brackets, which can prevent that the door is not closing totally, may only be used according to agreement with the fire authority. It is the owner of the door, who is responsible for such agreement.
3.1 Adjustment of the door
When the magnet is deactivated or the door is manually closed, it shall close easily and cover the wall opening completely otherwise the door shall be adjusted. Check the door can open and close without any problems. Adjust the height of the roller which is placed at the top of the door leaf, see figure 3.1.1 below. The distance between the final level of the floor and the door leaf cannot be more than 10 mm. When the door is completely closed and cover the entire wall opening, check the door closes tight to the rubber backstop in the frame, see figure 3.1.2. Check the handle does not collide with the frame or wall, when the door is closed.
Figure
3.1.1 Figure 3.1.2
3.2 Maintenance
• There is no demand for regulatory control.
• The owner of the door is responsible for the maintenance and functionality of the fire door.
• The automatically closing device shall be tested at least ones a month (with about 30 days apart).
• The function of the magnet should be tested.
• Steel wire and drop plumb should be checked.
• Electrical installations for the fire door shall be check according to the current legislation.
• If the fire door is damaged, the door must not be used as a fire door until it is identified as a fire door by the fire authority.
• For questions about service and maintenance please contact the service department at Door System.
3.3 Contact
DK: Door System A/S Hovvejen 148 DK-8361 Hasselager Phone: +45 8692 1171 Mail: [email protected]
UK:
Steve Andrews
Area Sales Manager UK
Tel: +44 07940 062747