28
Alfa Laval Marine & Power MOPX Separation System Parameter List Product No. List No. Printed Book No. 1763107-09 1763141-10 1763145-10 1763147-10 1763143-09 1763208-05 1763210-06 1763212-06 1763214-06 1763216-05 1763220-05 1763221-06 1763222-06 1763223-06 1763224-05 31830-5855-2 Jun 1997 1810108-02 V1

Mopx Parameter List

  • Upload
    eser

  • View
    444

  • Download
    79

Embed Size (px)

DESCRIPTION

sperator

Citation preview

  • Alfa Laval Marine & Power

    MOPX Separation System

    Parameter List

    Product No.

    List No.

    PrintedBook No.

    1763107-091763141-101763145-101763147-101763143-09

    1763208-051763210-061763212-061763214-061763216-05

    1763220-051763221-061763222-061763223-061763224-05

    31830-5855-2

    Jun 19971810108-02 V1

  • Alfa Laval reserve the right to make changes at any time without prior notice.

    Any comments regarding possible errors and omissions or suggestions for improvement of this publication would be gratefully appreciated.

    Copies of this publication can be ordered from your local Alfa Laval company.

    Published by: Alfa Laval Separation ABMarine & Power Oil Treatment DivisionS - 147 80 TumbaSweden

    Copyright Alfa Laval Separation AB 1995. Printed in Sweden.

  • Contents1 Scope 1

    2 Process Parameters 3

    3 Installation Parameters 5

    4 Timer Sequence Parameters 7

    5 Service Mode Parameter 90 9

    5.1 Countdown of Timers P50 P89 9

    5.2 Alarm Log 105.2.1 Examples of Logged

    Alarms 11

    6 Additional Parameter Information 13

    6.1 Process Parameters 13

    6.2 Installation Parameters 18

    6.3 Timer Sequence Parameters 19

    6.3.1 Starting Sequence 19

    6.3.2 Separation Sequence 19

    6.3.3 Sludge Discharge Sequence 20

    6.3.4 Stopping sequence 20

    7 Sequence Diagram 21

    7.1 Purifier mode 21

    7.2 Clarifier mode 221810108-02 V1

  • 1810108-02 V1

  • and observe the, operation,

    ns can result inl injuries.

    P00

    0272

    Alear only foreseeable conditions have e given, therefore, for situations the machine and its tools.

    ion is found in the Safety chapter Study instruction manuals warnings before installationservice and maintenance.

    Not following the instructioserious accidents with fata

    In order to make the information cbeen considered. No warnings ararising from unintended usage of

    A summary of the safety informatunder divider 1.

  • 1 ScopeThis parameter list is valid for the following separation systems

    MOPX 205

    MOPX 207

    MOPX 309

    MOPX 310

    MOPX 213

    Including the EPC-41 control unit with PROM: 31830-5852-1. 1810108-02 V1 1

  • 1 Scope MOPX Parameter List2 1810108-02 V1

  • 2 Process Parameters-r-

    s. ted,

    s.

    -l l

    r The EPC-41 control unit controls the separation process. It can be programmed for diffeent separation systems and different condi-tions within the system, by setting parameterThe process parameters can be easily adjusas often as required, to meet changes in theoperating conditions, e.g. oil temperature, alarm points, time between sludge discharge

    Each separator has its own EPC-41 control unit. Up to three separation systems can beinterconnected via cables between their control units. The separators can work in paralleor series operation. Only two separators canwork in series; the third must work in paralleor act as a stand-by. The first separator in series should always be defined as a purifieand the second as a clarifier.

    NOTE

    P2 is factory set to P (purifier). If you change it to C (clarifier) you get all the factory settings for a clarifier, which is shown in column Factory set value, Clarifier in the tables.

    WARNING

    Disintegration hazard

    If the time between sludge discharges is set too long, sludge accumulation and bowl imbalance may occur. 1810108-02 V1 3

  • 2 Process Parameters MOPX Parameter List1. For more information, seeAdditional Parameter Information on page 13.

    Parameter Description or unit RangeFactory set value Plant

    set valuePurifier Clarifier

    P11 Max. time between sludge discharges

    MinutesP1 = P61Changing of P1 automatically changes P61.

    0 999 30 30 .....

    P21 Purifier/Clarifier mode P = PurifierC = Clarifier

    P or C P .....

    P31 Series configuration 0 = No separator in series12 = The 1st and the 2nd sepa-

    rator work in series13 = The 1st and the 3rd separa-

    tor work in series23 = The 2nd and the 3rd sepa-

    rator work in series

    0, 12, 13, 23 0 0 .....

    P41 Sludge discharge sig-nal from purifier to clarifier

    1 = Every purifier discharge2 = Every 2nd purifier

    discharge3 = Every 3rd purifier discharge4 = Every 4th purifier discharge

    If P3 = 0 then P4 = - - -.

    1 4 - - - - - - .....

    P51 High temperature alarm

    C or F 0 115 C or0 255 F

    0 0 .....

    P61 Low temperature alarm

    C or F 0 115 C or0 255 F

    - - - - - - .....

    P71 Temperature set point C or F 0 110 C or0 240 F

    - - - - - - .....

    P81 P-band % 10 500 - - - - - - .....

    P91 I -time Minutes 0.1 10.0 - - - - - - .....

    P10 toP14

    Not used - - - - - -

    P151 HFO / DO selection of type of oil

    HFO = Heavy Fuel Oildo = diesel oilFor lubricating oil select HFO

    HFO or do HFO HFO .....

    P16 toP19

    Not used - - - - - -4 1810108-02 V1

  • 3 Installation Parametersre

    RangeFactory set value Plant

    set valuePurifier Clarifier

    1.2 2.1 2.1 2.1 2.1

    y is cor-parator.

    50 or 60 50 50 .....

    - - - - - -

    1st linked

    ontrol unitntrol unit

    be linked

    1 8 1 1 .....The installation parameters must be set befothe initial start-up and before process para-meters are set.

    The parameters rarely need to be adjusted again.

    NOTE

    EPC-41 parameter P21 is factory set to 50 Hz. If connected to a 60 Hz supply without changing P21 an alarm will occur. When P21 is set to 60 Hz the alarm will disappear after reset.

    NOTE

    Alfa Laval can not be held responsible for injuries and damage caused by usage of parameters not recommended by Alfa Laval

    Parameter Description or unit

    P20 Separator type 2.1 = MOPX

    P21 Power frequency HzCheck that the frequencrect, see label on the se

    P22 Not used

    P231 EPC-41 address 1 = Single unit or thecontrol unit

    2 = The 2nd linked c3 = The 3rd linked co

    4-8 = Not usedUp to 3 control units cantogether. 1810108-02 V1 5

  • 3 Installation Parameters MOPX Parameter List1. For more information, seeAdditional Parameter Information on page 13.

    P24 toP32

    Not used- - - - - -

    P33 Emergency stop function

    0 = Emergency stop only1 = Mechanical vibration switch

    0 or 1 0 0 .....

    P341 Alarm delay time Seconds 1 30 15 15 .....

    P351 Low temperature alarm delay after MV1 change over

    Seconds 1 999 15 15 .....

    P361 Remote control 0 = No remote control1 = Remote switches2 = Remote computer3 = Not applicable

    10 = No remote control, alarm A4-1 cancelled

    11 = Remote switch, alarm A4-1 cancelled

    12 = Remote computer, alarm A4-1 cancelled

    13 = Not applicable

    0 3, 10 13 0 0 .....

    P371 Heater type 0 = No or common heater with separate controller

    1 = Heatpac EHS-62 controlled by EPC-41

    2 = Heater with control valve, controlled by EPC-41

    0 2 0 0 .....

    P38 Size of Heatpac heater

    kWIf P37 = 1 then P38 is set to 16, otherwise P38 = - - -.

    0, 7, 8, 14, 16, 22, 24, 36, 40, 50, 56, 65, 72

    - - - - - - .....

    P39 Run time of steam control valve

    SecondsIf P37 = 2 then P39 is set to 120, otherwise P39 = - - -.

    0 999 - - - - - - .....

    P401 Temperature reading C = CF = F

    C or F C C .....

    P411 Max. start time for heater

    Minutes 0 999 15 15 .....

    P42 Not used - - - - - -

    P431 Extra alarm function 0 = Alarm indication on display. No action.

    1 = Alarm indication on display. Oil feed off during separation sequence.

    0 or 1 0 0 .....

    P44 toP49

    Not used- - - - - -

    Parameter Description or unit RangeFactory set value Plant

    set valuePurifier Clarifier6 1810108-02 V1

  • 4 Timer Sequence Parameters,

    RangeFactory set value Plant

    setvaluePurifier Clarifier

    quence

    0 999 15 15 .....

    0 999 45 - - - .....

    0 999 30 30 .....

    - - - - - -

    sequence

    - - - - - -

    atically

    0 999 30 30 .....

    - - - - - -

    ge sequence

    0 999 20 20 .....

    - - - - - -

    0 99.9 3.0 3.0 .....

    - - - - - -

    0 999 15 15 .....

    - - - - - -The timer sequence parameters control the operation of the system; i.e. start, separationsludge discharge and stop functions.

    Parameter Description or unit

    Starting se

    P501 Bowl closing water Seconds

    P511 Bowl sealing water Seconds

    P521 Oil feed on during stabilizing period

    Seconds

    P53 to P59

    Not used

    Separation

    P601 Not used

    P611 Time between sludge discharges

    MinutesP61 = P1Changing of P61 automchanges P1.

    P62 toP69

    Not used

    Sludge dischar

    P701 Displacement water. Oil feed off

    Seconds

    P71 Not used

    P721 Sludge discharge Seconds

    P73 toP77

    Not used

    P781 Draining of bowloperating system

    Seconds

    P79 Not used 1810108-02 V1 7

  • 4 Timer Sequence Parameters MOPX Parameter List1. For more information, seeAdditional Parameter Information on page 13.

    Stopping sequence

    P80 Bowl closing water on Seconds 0 999 15 15 .....

    P81 Bowl displ. water Seconds 0 999 90 - - - .....

    P82 Oil feed on Seconds 0 999 - - - 30 .....

    P83 toP85

    Not used - - - - - -

    P86 Separator motor off Seconds 0 999 180 180 .....

    P87 toP89

    Not used - - - - - -

    Parameter Description or unit RangeFactory set value Plant

    setvaluePurifier Clarifier8 1810108-02 V1

  • 5 Service Mode Parameter 90, es

    t

    .

    RangeFactory set value Plant

    setvaluePurifier Clarifier

    O) valuesuntdown

    g self

    0 1 0 0 .....

    - - - - - -

    PS

    42

    G0

    064

    82A

    Timer P61 shows that it is 32 seconds left to next sludge discharge.With aid of the service mode parameters information can be requested and displayedfor instance the countdown of timer sequenccan be displayed while they are running.

    5.1 Countdown of Timers P50 P89

    By setting P90 to 1, the mode selector in position L and then by pushing the alarm resebutton, a countdown of each activated timer(P50 P89) can be displayed during operation.

    1. From 2 to 49 is reserved for Alfa Laval use only

    Parameter Description or unit

    P90 Service mode 0 = No Service mode(F 11=Timer P50 P89 co50 = Alarm log, includin

    resetting alarms

    P91 toP99

    Not used 1810108-02 V1 9

  • 5 Service Mode Parameter 90 MOPX Parameter List

    et

    s

    5.2 Alarm Log

    By setting P90 to 50, the mode selector in position L and then by pushing the alarm resbutton, the 32 latest alarms can be displayed, including self resetting alarms.

    Each logged alarm consists of three consecutive groups of information:

    1. The accumulated alarm log time, which shows how long the EPC has been in operation since an alarm.

    If the interval between two alarms is greater than 999.5 hours ( 41 days) the whole alarm log will be reset to 0.

    2. The alarm is indicated in the same way awhen it occurred, except for the alarms starting with an E:

    alarm code starting with an A.

    LED and an alarm code, for instance High or low oil temperature.

    LED indications only.

    alarm code starting with an E (eventswith no alarm released)

    There is only one event for EPC-41, which is a self resetting function; E2 = low pressure

    3. The actual value of parameter P1 (maximum time between sludge discharges).10 1810108-02 V1

  • MOPX Parameter List 5 Service Mode Parameter 90

    I

    0008

    81A

    I00

    110

    3AI0

    008

    91A

    I000

    901A

    I000

    912

    AI0

    008

    91A

    I00

    0921

    AS

    0001

    21A

    I001

    151

    AI0

    008

    91A

    I001

    001A5.2.1 Examples of Logged Alarms

    The capital H indicates that this is the latest alarm which has been logged. TheEPC had been in operation 48 hours and20 29 minutes since this alarm. Every tenth minute is displayed, but several alarms can be logged within this period.

    The alarm was a Power failure.

    P1 (maximum time between sludge discharges) was set to 30 minutes.

    Between these two alarms 10 hours and 0 9 minutes had elapsed (58.2 48.2).

    This event occurred 58 hours and 20 29 minutes ago.

    The event was a Low pressure.

    P1 indicated 30 minutes.

    106 operating hours and 30 39 minutes ago the first logged alarm occurred.

    The alarm was a Low temperature. (Which is indicated by the LED and the figures on the display).

    P1 indicated 30 minutes.

    This indicates the end of the log.1810108-02 V1 11

  • 5 Service Mode Parameter 90 MOPX Parameter List12 1810108-02 V1

  • 6 Additional Parameter Informationly

    ,

    t s

    6.1 Process ParametersP1 Max time between sludge discharge

    Long intervals between sludge discharges can cause the sludge to accumulate and solidify. The sludge may then break up at sludge discharge and create imbalance in the bowl.

    As many factors influence the sludge discharge interval, the choice of interval must be based on experience.When the bowl is opened for routine cleaning, the sludge space should be inspected and, if necessary, the interval between discharges changed accordingly.

    Clean sludge space: the interval may be prolonged. Clean sludge space means that no noticeable amount of solidified sludge remains in the sludge space.Dirty sludge space: the interval must be shortened. Dirty sludge space means that some solidified sludge has accumulated in the sludge space.

    The only way to get a clean sludge space is to make appropriate adjustment of the interval based on regular inspection.

    N.B. Alfa Laval assumes no responsibility for the actual choice of discharge interval times, as these depend entireon local feed characteristics.

    Fuel oil cleaningConditions may change completely when bunkers are changed. Thereforegreat care must be given to the discharge interval setting for each newbunker. In case the current discharge interval exceeds the recommended initial value, the interval setting has tobe reduced according to table on nexpage, when a new, unknown bunker ito be separated.

    Use of unstable fuel or mixing of incompatible fuel oils may cause precipitation of sludge and overloadingof the separator.

    WARNING

    Disintegration hazard

    If the interval between sludge discharges is too long, there is risk of heavy side breakdown.

    WARNING

    Disintegration hazard

    Each new bunker requires review of the discharge time setting.1810108-02 V1 13

  • 6 Additional Parameter Information MOPX Parameter List

    t n

    s

    for

    P3

    ischarge Time to first bowl inspection

    hours 1 week

    hours 1 week

    5 hour 2 days

    ystem

    Time to first bowl inspection

    1 week

    After one batch

    2 daysLubricating oil cleaningThe interval between discharges musbe shortened if the separator has beeout of service for 24 hours or longer while the diesel engine has been running.In order to have a reasonable startingpoint the table below shows recommended initial discharge intervals and operating time to first inspection.

    P2 Purifier/clarifier modeThe MOPX separator can be defined aa clarifier or as a purifier. It can operateas a single separator or in parallel or series. This is defined by the parameters P2, P3 and P23. See P3 the relationship between these parameters.If a separator operates in series whenthe mode is changed the parameters have to be changed accordingly.

    Type of oil Initial d

    Distillate (1.5 - 6 cSt /40 C) 4

    Marine Diesel Oil (max. 13 cSt / 40 C) 2

    Intermediate / Heavy Fuel Oil 0.

    Main lubricating oil s

    Initial discharge

    Recommended interval for cross head engines

    1 hour

    Stuffing box oil 5 minutes

    Recommended interval for trunk piston engines

    0.5 hour14 1810108-02 V1

  • MOPX Parameter List 6 Additional Parameter Information

    in

    r r.

    in

    s d in

    inked control unit Third linked control unit

    -

    P 0 2 (2nd linked control unit)

    P2 = PP3 = 0P23= 3 (3rd linked control

    unit)

    C (Clarifier)122

    P2 = PP3 = 0 P23= 3This separator works as a stand-by unit; i.e. in parallel operation or not used.

    P0 2

    separator works as a -by unit.

    P2 = CP3 = 13P23= 3

    P23 (2 and 3 in series)2

    P2 = CP3 = 23P23= 3P3 Series configurationUp to three EPC-41 control units can be linked together. Only two of the three connected separators can work series. The first separator in series should always be defined as a purifieand the second separator as a clarifieThe relationship between the parameters P2, P3 and P23 is shownthe following table.

    N.B. The 1st linked control unit must alwayshave the power on (the separator doenot need to be operating) when the 2nand the 3rd separators are operating series.

    Type of operation First linked control unit Second l

    Single operation: P2 = P (Purifier)P3 = 0 (No separator in

    series)P23= 1 (Single unit)

    -

    Parallel operation: P2 = P P3 = 0 P23= 1 (1st linked

    control unit)

    P2 =P3 =P23=

    Series operation 1st and 2nd separator:

    P2 = PP3 = 12 (1 and 2 in

    series)P23= 1

    P2 =P3 =P23=

    Series operation 1st and 3rd separator:

    P2 = PP3 = 13 (1 and 3 in

    series)P23= 1

    P2 =P3 =P23=This stand

    Series operation 2nd and 3rd separator:

    P2 = PP3 = 0 P23= 1This separator works as a stand-by unit.

    P2 =P3 =P23=1810108-02 V1 15

  • 6 Additional Parameter Information MOPX Parameter List

    P4 Sludge discharge signals from purifier to clarifierThe number of sludge discharges initiated by the first separator (purifier) before a discharge signal is sent to the second separator to start its sludge discharge sequence. P4 should be set in the purifier controller.

    P5 High temperature alarmP5 should be set sufficiently above the temperature set point P7. 5 10 C (10 20 F) higher than P7 is recommended.If P5 = 0 (monitoring temperature sensor (Pt 100) not connected)then P6 = P7 = - - -.

    P5, P6 and P7 can be set both for heavy fuel oil (HFO) and for diesel oil (DO), see P15. If both oils are to be used, the following must be done:

    1. Set P5, P6 and P7 for HFO (P15 is factory set to HFO).

    2. Change P15 to do.

    3. Go back to P5 and set P5, P6 and P7 for DO.

    If only diesel oil is to be used for the installation, the following must be done:

    1. Set P5 greater than 0.

    2. Change P15 to do.

    3. Go back to P5 and set P5, P6 and P7 for DO.

    P6 Low temperature alarmShould be set sufficiently below the temperature set point P7. 5 10 C (10 20 F) lower than P7 is recommended.

    P7 Temperature set pointTo be set according to plant application. See also P5 and P6.

    P8 P-band (Proportional band)If P37 = 0 then P8 = - - -.If P37 = 1 or 2 then P8 is automaticallypreset to 40%.

    P9 I-time (Integral time)If P37 = 0 then P9 = - - -.If P37=1 or 2 then P9 is automaticallypreset to 1.2 minutes.16 1810108-02 V1

  • MOPX Parameter List 6 Additional Parameter Information

    .

    ps t

    P

    000

    041A

    Constant amplitude

    P00

    0051

    A

    How to set P8 and P9:If the temperature varies with regularlyrepeated oscillation, setting of the proportional band and integral time isnecessary.

    Increasing the value of parameterP8 (proportional band width) will result in a slower and more stablecontrol action.

    Increasing the value of parameterP9 (integral time) also results in slower response from the EPC-41

    We recommend that you follow these guidelines:

    1. Set P9 = 10 minutes.

    2. Decrease P-band (P8) band in steuntil the process reaches the poinwhere it starts to oscillate with a constant amplitude. Test the stability after each step by introducing a step-change of load or set point.

    3. When you have discovered the point where the process oscillateswith a constant amplitude note thefollowing figures:

    4. Calculation of optimal parameter settings.

    The settings above give a rather goodresult but may be adjusted accordingto individual characteristics in differentloops.

    A = The value of P-band (P8).B = The time for one full period in

    seconds.

    P-band I-timeP8 = 2.2 A P9 = 0.8 B1810108-02 V1 17

  • 6 Additional Parameter Information MOPX Parameter List

    s .

    ng

    t.d P15 HFO / DO selection of oil typeTo prevent false alarm (A7-10) when cleaning diesel oil the type of oil must be specified.Once P5, P6 and P7 are set for HFO or DO they automatically follow the selection of P15.If P15 = HFO and P5 is set > 0 then P5 for DO is automatically reset to 50 C (120 F).If P15 = do then P53 =P70 = 0.See P5 for the relationship between P5, P6, P7 and P15.

    6.2 Installation ParametersP23 EPC-41 address

    If the separator works as single unit the EPC-41 address shall always be 1. When using more than one separator in the same system (parallel or series) each interconnected EPC-41 control unit must be identified. The EPC-41 address shows in which order the control units are linked.See also P3 for the relationship between the parameters.

    P34 Alarm delay timeActivation of most alarm functions can be delayed up to 30 seconds, except for

    emergency / vibration alarm

    high temperature alarm,which have a fixed delay time of 2 seconds.

    If operating two separators in series, P34 for the clarifier separator must be 3 seconds longer.

    P35 Low temperature alarm delay after MV1 change overWhen the oil feed change over valve changes position the flow rate and thuthe oil temperature may be influencedBy delaying the temperature alarm, a false alarm is avoided as the oil temperature has time to stabilize.P35 should be set according to plant application. If a delay time above 120seconds is necessary, check the heatisystem and the installation layout.

    P36 Remote controlRemote control can be applied in formof:

    external switches

    external computers

    P37 Heater typeThe EPC-41 control unit is designed for control of:

    Heatpac EHS-62 (P37 =1)

    Heater with heating media controlvalve (P37=2)

    N.B. If a different type of heater is installed(P37 = 0), only a start/stop signal is available from the EPC-41 control uniIf a steam heating system is connecteto the EPC-41 and if the system is equipped with an optional shut-off valve, and provided P37= 0 or 2, the valve is opened when the heater is started.

    The valve is shut:

    when the heater is stopped

    at high temperature alarm

    at power failure

    at EPC stand-by mode18 1810108-02 V1

  • MOPX Parameter List 6 Additional Parameter Information

    r

    ter

    P40 Temperature readingDegrees Celsius (C) or Fahrenheit (F) temperature readings available.P5, P6 and P7 have to be set according to C or F.

    P41 Max. start time for heaterSets the maximum allowed start time for the heater. Minimum temperature limit (P6) must be reached within this time.

    P43 Extra alarm functionExtra alarm functions can be connected. By setting P43 to 1 the oil feed to the separator will be stopped when the extra alarm occur.

    6.3 Timer Sequence Parameters

    6.3.1 Starting Sequence

    P50 Bowl closing waterFor proper closing of the separator bowl during start-up sequence. If more than 60 seconds is required, it may indicate a malfunction.

    P51 Sealing waterSealing water is used in the bowl to prevent oil from discharging through the water outlet in a purifier. The amount of sealing water in the bowl is balanced by the gravity disc. During the starting sequence, sufficient water must be admitted to the empty bowl to establish an adequate water seal.Insufficient water will lead to a broken water seal. If a broken water seal occurs during the starting sequence the time setting can be increased. P51 should be set according to experience.

    Recommended values:MOPX 213: 45 sec.MOPX 205, 207, 309 & 310: 30 sec.

    N.B. If more than 100 secs is required for MOPX 205, or 140 seconds for the MOPX 207, 309, 310 & 213 this indicates a malfunction.

    N.B. Before increasing the sealing water, make sure that the appropriate gravitydisc is fitted to the separator bowl.

    N.B. This function is blocked in the clarifiermode (P2 = C, and P51 = - - -).

    P52 Oil feed on during stabilizing periodOil admitted to separator bowl during astabilizing period.If more than 30 seconds is needed fothe purifier and 60 seconds for the clarifier it may indicate a malfunction.

    6.3.2 Separation Sequence

    P61 Time between sludge dischargesThe same as P1 (setting one paramewill set both to the same value).Bowl closing water is supplied for 2 seconds every 15 minutes.

    N.B. In series operation the time sequencefor the clarifier must be longer than forthe purifier, in order to synchronize sludge discharges initiated from the purifier.1810108-02 V1 19

  • 6 Additional Parameter Information MOPX Parameter List6.3.3 Sludge Discharge Sequence

    P70 Displacement waterFilling of displacement water to the bowl eliminates the risk of oil loss at the next sludge discharge.If more than 40 seconds are required, this indicates a malfunction.

    N.B. If P2 = C (clarifier mode), then P70 starts but the valve is not activated(i.e. no displacement water added).

    P72 Sludge dischargeSludge discharge initiated by MV15 admitting water to the separator bowl.If more than 4 seconds are required, this indicates a malfunction.

    P78 Draining of bowl operating system.Stabilizing period to allow water to drain from the opening chamber.Should be set according to experience.

    6.3.4 Stopping sequence

    P80 Bowl closing water onTo be set for proper closing of the bowl (on until P86)

    P81 Bowl displacement water onPurifier mode only; the bowl is filled up in order to prevent vibration. MOPX 213 is 90 secs, and for smaller sizes 45 secs is recommended

    P82 Oil feed onClarifier mode only; the bowl is filled up in order to prevent vibration.

    P86 Separator motor offThe separator motor is automatically switched off. Restarting is blocked for 3 minutes. 20 1810108-02 V1

  • 7 Sequence Diagramd as a 7.1 Purifier mode

    The duration of the monitoring functions and output signals when the separator is operatepurifier is illustrated in the diagram.

    1. Emergency Stop (XS2) is normally connected to terminal X8:4. If the optional vibration switch (XS1) is installed it is connected to terminal X8:4 and the Emergency Stop (XS2) is connected to the system power supply.

    2. With optional sensor TT1 installed P50 will not start if the temperature is too low or too high.3. During P61 intermittently 1second every 5 minutes.

    ValveRelay,Sensor

    Terminal Activated functionStandby Starting

    sequenceSeparationsequence

    Sludge discharge sequence

    Stopping sequence

    OFF P50 P51 P52 P61 P70 P72 P78 P80 P81 P86 OFF

    15 s 45 s 30 s 30 min 20 s 3 s 15 s 15 s 90 s 180 s

    Mon. functions

    PS42 X7:4 Low oil pressure

    PS41 X7:3High oil pressure

    - X7:1Extra alarm

    XS1 X8:4 Vibrations1

    XS2 X8:4 Emergency stop1

    - X9:3 Heater fault

    TT1 X11:1-3 High oil temperature2

    TT1 X11:1-3 Low oil temperature2

    PS42 7:4 Switch function

    Output signals

    X1: 1,2 Motor starter

    XS1 X2: 3,4Blocking vibration switch

    MV1 X4: 4 Oil to separator

    MV10A X5: 1 Closed drain valve

    MV10 X5: 2 Displ./Sealing. water

    MV15 X5: 3 Bowl opening water

    MV16 X5: 4 Bowl closing water3 1810108-02 V1 21

  • 7 Sequence Diagram MOPX Parameter List

    d as a 7.2 Clarifier mode

    The duration of the monitoring functions and output signals when the separator is operateclarifier is illustrated in the diagram.

    1. Emergency Stop (XS2) is normally connected to terminal X8:4. If optional vibration switch (XS1) is installed it is connected to terminal X8:4 and the Emergency Stop (XS2) is connected to the system power supply.If the emergency stop button is pushed while the EPC is in stand-by mode the separator motor is stopped.

    2. With optional sensor TT1 installed P50 will not start if the temperature is too low or too high.3. During P61 intermittently 1second every 5 minutes.

    ValveRelay,Sensor

    Terminal Activated functionStandby Starting

    sequenceSeparationsequence

    Sludge discharge sequence

    Stopping sequence

    OFF P50 P52 P61 P70 P72 P78 P80 P82 P86 OFF

    15 s 30 s 30 min 20 s 3 s 15 s 15 s 30 s 180 s

    Mon. functions

    PS42 X7:4 Low oil pressure

    PS41 X7:3High oil pressure

    - X7:1Extra alarm

    XS1 X8:4 Vibrations1

    XS2 X8:4 Emergency stop1

    - X9:3 Heater fault

    TT1 X11:1-3 High oil temperature2

    TT1 X11:1-3 Low oil temperature2

    PS42 7:4 Switch function

    Output signals

    X1: 1,2 Motor starter

    XS1 X2: 3,4Blocking vibration switch

    MV1 X4: 4 Oil to separator

    MV10A X5: 1 Closed drain valve

    MV10 X5: 2 Displ./Sealing. water

    MV15 X5: 3 Bowl opening water

    MV16 X5: 4 Bowl closing water322 1810108-02 V1

    MOPX Separation SystemParameter List1 Scope 12 Process Parameters 33 Installation Parameters 54 Timer Sequence Parameters 75 Service Mode Parameter 90 96 Additional Parameter Information 137 Sequence Diagram 211 ScopeThis parameter list is valid for the following sep...MOPX 205MOPX 207MOPX 309MOPX 310MOPX 213

    Including the EPC-41 control unit with PROM:31830...

    2 Process ParametersThe EPC-41 control unit controls the separation pr...Each separator has its own EPC41 control unit. Up...NOTEP2 is factory set to P (purifier). If you change i...

    WARNINGDisintegration hazardIf the time between sludge discharges is set too l...

    3 Installation ParametersNOTEEPC-41 parameter P21 is factory set to 50 Hz. If c...The installation parameters must be set before the...The parameters rarely need to be adjusted again.

    NOTEAlfa Laval can not be held responsible for injurie...

    4 Timer Sequence ParametersThe timer sequence parameters control the operatio...

    5 Service Mode Parameter 90With aid of the service mode parameters informatio...5.1 Countdown of Timers P50 P89By setting P90 to 1, the mode selector in position...

    5.2 Alarm LogBy setting P90 to 50, the mode selector in positio...Each logged alarm consists of three consecutive gr...1. The accumulated alarm log time, which shows how...If the interval between two alarms is greater than...2. The alarm is indicated in the same way as when ... alarm code starting with an A. LED and an alarm code, for instance High or low... LED indications only. alarm code starting with an E (events with no ...There is only one event for EPC-41, which is a sel...

    3. The actual value of parameter P1 (maximum time ...

    5.2.1 Examples of Logged AlarmsThe capital H indicates that this is the latest ...The alarm was a Power failure.P1 (maximum time between sludge discharges) was se...Between these two alarms 10 hours and 0 9 minute...This event occurred 58 hours and 20 29 minutes a...The event was a Low pressure.P1 indicated 30 minutes.106 operating hours and 30 39 minutes ago the fi...The alarm was a Low temperature. (Which is indic...P1 indicated 30 minutes.This indicates the end of the log.

    6 Additional Parameter Information6.1 Process ParametersP1 Max time between sludge dischargeLong intervals between sludge discharges can cause...

    WARNINGDisintegration hazardIf the interval between sludge discharges is too l...As many factors influence the sludge discharge int...When the bowl is opened for routine cleaning, the ...Clean sludge space: the interval may be prolonged....Dirty sludge space: the interval must be shortened...The only way to get a clean sludge space is to mak...N.B. Alfa Laval assumes no responsibility for the ...Fuel oil cleaningConditions may change completely when bunkers are ...Use of unstable fuel or mixing of incompatible fue...

    WARNINGDisintegration hazardEach new bunker requires review of the discharge t...Lubricating oil cleaningThe interval between discharges must be shortened ...In order to have a reasonable starting point the t...P2 Purifier/clarifier modeThe MOPX separator can be defined as a clarifier o...If a separator operates in series when the mode is...

    P3 Series configurationUp to three EPC41 control units can be linked tog...N.B. The 1st linked control unit must always have ...

    P4 Sludge discharge signals from purifier to clari...The number of sludge discharges initiated by the f...

    P5 High temperature alarmP5 should be set sufficiently above the temperatur...5 10 C (10 20 F) higher than P7 is recommend...If P5 = 0 (monitoring temperature sensor (Pt 100) ...then P6 = P7 = - - -.P5, P6 and P7 can be set both for heavy fuel oil (...

    1. Set P5, P6 and P7 for HFO (P15 is factory set...2. Change P15 to do.3. Go back to P5 and set P5, P6 and P7 for DO.If only diesel oil is to be used for the installat...

    1. Set P5 greater than 0.2. Change P15 to do.3. Go back to P5 and set P5, P6 and P7 for DO.P6 Low temperature alarmShould be set sufficiently below the temperature s...5 10 C (10 20 F) lower than P7 is recommende...

    P7 Temperature set pointTo be set according to plant application. See also...

    P8 P-band (Proportional band)If P37 = 0 then P8 = - - -.If P37 = 1 or 2 then P8 is automatically preset to...

    P9 I-time (Integral time)If P37 = 0 then P9 = - - -.If P37=1 or 2 then P9 is automatically preset to 1...

    How to set P8 and P9:If the temperature varies with regularly repeated ...Increasing the value of parameter P8 (proportional...Increasing the value of parameter P9 (integral tim...

    We recommend that you follow these guidelines:

    1. Set P9 = 10 minutes.2. Decrease P-band (P8) band in steps until the pr...3. When you have discovered the point where the pr...A =The value of P-band (P8).B =The time for one full period in seconds.

    4. Calculation of optimal parameter settings.P-bandI-timeP8 = 2.2 AP9 = 0.8 BThe settings above give a rather good result but m...P15 HFO / DO selection of oil typeTo prevent false alarm (A7-10) when cleaning diese...Once P5, P6 and P7 are set for HFOor DO they automatically follow the selection of P...If P15 = HFO and P5 is set > 0 then P5 for DO is...If P15 = do then P53 =P70 = 0.See P5 for the relationship between P5, P6, P7 and...

    6.2 Installation ParametersP23 EPC-41 addressIf the separator works as single unit the EPC-41 a...See also P3 for the relationship between the param...

    P34 Alarm delay timeActivation of most alarm functions can be delayed ...emergency / vibration alarmhigh temperature alarm,

    which have a fixed delay time of 2 seconds.If operating two separators in series, P34 for the...

    P35 Low temperature alarm delay after MV1 change o...When the oil feed change over valve changes positi...P35 should be set according to plant application. ...

    P36 Remote controlRemote control can be applied in form of:external switchesexternal computers

    P37 Heater typeThe EPC-41 control unit is designed for control of...Heatpac EHS-62 (P37 =1)Heater with heating media control valve (P37=2)

    N.B. If a different type of heater is installed (P...If a steam heating system is connected to the EPC-...The valve is shut:when the heater is stoppedat high temperature alarmat power failureat EPC stand-by mode

    P40 Temperature readingDegrees Celsius (C) or Fahrenheit (F) temperatur...P5, P6 and P7 have to be set according to C or F...

    P41 Max. start time for heaterSets the maximum allowed start time for the heater...

    P43 Extra alarm functionExtra alarm functions can be connected. By setting...

    6.3 Timer Sequence Parameters6.3.1 Starting SequenceP50 Bowl closing waterFor proper closing of the separator bowl during st...

    P51 Sealing waterSealing water is used in the bowl to prevent oil f...establish an adequate water seal.Insufficient water will lead to a broken water sea...Recommended values:MOPX 213: 45 sec.MOPX 205, 207, 309 & 310: 30 sec.N.B. If more than 100 secs is required for MOPX 20...N.B. Before increasing the sealing water, make sur...N.B. This function is blocked in the clarifier mod...

    P52 Oil feed on during stabilizing periodOil admitted to separator bowl during a stabilizin...If more than 30 seconds is needed for the purifier...

    6.3.2 Separation SequenceP61 Time between sludge dischargesThe same as P1 (setting one parameter will set bot...Bowl closing water is supplied for 2 seconds every...N.B. In series operation the time sequence for the...

    6.3.3 Sludge Discharge SequenceP70 Displacement waterFilling of displacement water to the bowl eliminat...If more than 40 seconds are required, this indicat...N.B. If P2 = C (clarifier mode), then P70 starts b...

    P72 Sludge dischargeSludge discharge initiated by MV15 admitting water...If more than 4 seconds are required, this indicate...

    P78 Draining of bowl operating system.Stabilizing period to allow water to drain from th...Should be set according to experience.

    6.3.4 Stopping sequenceP80 Bowl closing water onTo be set for proper closing of the bowl (on until...

    P81 Bowl displacement water onPurifier mode only; the bowl is filled up in order...

    P82 Oil feed onClarifier mode only; the bowl is filled up in orde...

    P86 Separator motor offThe separator motor is automatically switched off....Restarting is blocked for 3 minutes.

    7 Sequence Diagram7.1 Purifier modeThe duration of the monitoring functions and outpu...

    7.2 Clarifier modeThe duration of the monitoring functions and outpu...