Switch module with terminals for rail-mounted installation
Conventional thermal current Ithe
16 A/+40 °C, 11 A/+60 °C
Contact optionscontacts with positive break operation(self-cleaning)1 NC and 1 NO or2 NC or 2 NO
Contact materialAgSnO2
Enclosure materialThermoplastic
ConnectionTerminals 2.5 mm2, fine stranded
Mechanical life106 switching cycles
Storage and transport temperature-55 °C to +70 °C
Dimensions
33.552
57.5
0.5
46
Explosion protectionEx protection type
II 2G Ex de IIC Gb I M2 Ex de I Mb
Class I, Zone 1, AEx de IIC, Ex de IICClass I, Div. 2, Groups A, B, C, D
CertificationPTB 99 ATEX 1043 UUL E184198IECEx PTB 07.0046 UINMETRO 2003EC02CP081U
Ambient temperature-55 °C to +60 °C
Actuating elementCodeno.
0700
7400
0800
0900
1000
1001
1002
1003
1800
1200
1201
1202
1203
6100
Selection chartCodeno.
Pushbutton
Double push button actuator
Emergency stop NOT-AUS
Selector switch 0 + I latching, 2 positions
Selector switch I + II latching, 3 positions
Selector switch I + II momentary-contact, 3 positions
Selector switch I latching, II momentary-contact, 3 positions
Selector switch I momentary-contact, II latching, 3 positions
Mushroom pushbutton, black
Lockable in both positions, DOM lock
Lockable in the depressed position, DOM lock
Lockable in the initial position, DOM lock
Locking-type mushroom pushbutton
Lockable in both positions, RONIS lock
1
2
4
Technical dataProtection class
determined by the actuating element andComEx enclosure, terminals IP 20
Rated insulation voltage690 V
Type of contacts
2 NC
2 NO
1 NC + 1 NO
Complete order no.Switch module without actuating element 07-3321-1 00
Actuating elementStandard 05-0003-00
Increased oil resistance 05-0003-00 BNPlease enter code number.
Weightapprox. 70 g
Mountingon mounting rail TS 35 x 7.5
Shock resistanceDIN EN 60068-2-27: 1995, 30 g 18 ms
Switch module with terminalsfor rail-mounted installation
Rated voltage400 V 400 V 110 V 24 VUtilization categoryAC-12 AC-15 DC-13 DC-13Rated operating currents16 A 10 A 0,5 A 1 A
15
03-0
330-
0192
/B-0
5/11
-BCS
-200
866/
4
Explosion protectionEx protection type
II 2G Ex de IIC Gb I M2 Ex de I Mb
Class I, Zone 1, AEx de IIC, Ex de IICClass I, Div. 2, Groups A, B, C, D
CertificationPTB 97 ATEX 1064 UUL E184198IECEx PTB 10.0014 UINMETRO2003EC02CP096U
Ambient temperature-55 °C to +50 °C+60 °C (AC/DC 12 V to 24 V)
Technical dataProtection class
determined by the actuating element andComEx enclosure, terminals IP 20
Rated insulation voltage300 V
Rated operating voltageAC 12 V to 250 V (Ta < +50 °C)DC 12 V to 60 V (Ta < +50 °C)AC/DC 12 V to 24 V (Ta < +60 °C)
Power consumption< 1 W
LampLEDred, green, yellow, white, blue
Illuminationvery bright, over a visible angle of 180°
Enclosure materialThermoplastic
ConnectionTerminals 2.5 mm2, fine stranded
Electrical life>105 running hours
Storage and transport temperature-55 °C to +70 °C
Weightapprox. 90 g
Dimensions
Lamp module with terminals for rail-mounted installation
∅ 1
9
52 33.5
91
57.546
Colour LED
red
green
yellow
white
blue
1
2
3
4
5
Code no. Colour actuator
red
green
yellow
white
blue
Code no.
3
4
5
6
7
Selection chart
Wiring diagram
Complete order no.Lamp module without actuating element 07-3351-11 0
Actuating elementStandard 05-0003-001 00
Increased oil resistance 05-0003-001 00BN
Please enter code number.
Mountingon mounting rail TS 35 x 7.5(DIN EN 60715)
Shock resistanceDIN EN 60068-2-27: 1995, 30 g 18 ms
1
2
3
4
5
6
7
Lamp module with terminalsfor rail-mounted installation
16
03-0
330-
0192
/A-0
7/10
-BCS
-200
866/
7
Technical dataProtection class
determined by the actuating element andComEx enclosure, terminals IP 20
Rated insulation voltage300 V
Rated operating voltageAC 12 V to 250 V (Ta < +50 °C)DC 12 V to 60 V (Ta < +50 °C)AC/DC 12 V to 24 V (Ta < +60 °C)
Power consumption< 1 W
LampLED: red, green, yellow, white, blue
Illuminationvery bright, over a visible angle of 180°
Contact element
Contacts1 NC or 1 NO as snap switch element
Switching capacityAC-15 1 A/230 VDC-13 0.25 A/24 V
Enclosure materialThermoplastic
Illuminated button with terminals for rail-mounted installation
DimensionsExplosion protectionEx protection type
II 2G Ex de IIC I M2 Ex de I
Class I, Zone 1, AEx de IIC, Ex de IICClass I, Div. 2, Groups A, B, C, D
CertificationPTB 97 ATEX 1064 UUL E184198IECEx PTB 10.0014 UINMETRO 2003 EC 02 CP096 U
Ambient temperature-55 °C to +50 °C+60 °C (AC/DC 12 to 24 V)
Code no.
Selection chart
5
6
7
8
9
Code no. Code no.Colour actuator
red
green
yellow
white
blue
1
2
3
4
5
Colour LED
red
green
yellow
white
blue
7
8
Type of contact
1 NC
1 NO
Complete order no.Illuminated button without actuating element 07-3361-1 0
Actuating element
Standard 05-0003-006 00
Increased oil resistance 05-0003-006 00BN
Please enter code number.
Rated voltage230 V 24 VUtilization categoryAC-15 DC-13Rated operating currents1 A 0,25 A
46 ∅ 1
9
52 33.5
57.5
84
ConnectionTerminals 2.5 mm2, fine stranded
Electrical life>105 running hours
Mechanical life>105 switching cycles
Storage and transport temperature-55 °C to +70 °C
Weightapprox. 110 g
Mountingon mounting rail TS 35 x 7.5(DIN EN 60715)
Shock resistanceDIN EN 60068-2-27: 1995, 30 g 18 ms
Illuminated button with terminalsfor rail-mounted installation
17
03-0
330-
0431
/A-0
7/10
-BCS
-240
908
Explosion protectionEx protection type
II 2G Ex de IIC I M2 Ex de I
Ex de IIC
CertificationPTB 05 ATEX 1064 UIECEx PTB I0.0017 U
Ambient temperature-55 °C to +60 °C
Potentiometer with terminals for rail-mounted installation
Technical dataProtection class
determined by the actuating element andComEx enclosure, terminals IP 20
Rated insulation voltage500 V
Max. rated voltageAC/DC 320 V
Resistance1 kΩ to 10 kΩ
Curve shapelinear
Resistance tolerance 20 %
Rated outputmax. 1 W at Ta < +40 °C
Resistor materialcarbon film on ceramics
Rotationmech. 285° -5°electr. about approx. 250°
Torgue (beginning)0.5 to 1.5 Ncm
Torgue (end stop)> 100 Ncm
Enclosure materialthermoplastic
ConnectionDouble terminals 2 x 2.5 mm2, fine stranded
Mechanical life25000 sinusoidal cycles
Storage and transport temperature-55 °C to +70 °C
Weightapprox. 71 g
Dimensions
52
61
46
57.5
33.5
4
5
6
7
Code no.
Selection chart
Wiring diagram Resistance
1 kΩ
2.2 kΩ
4.7 kΩ
10 kΩ
Notes for installation and inspection:
At rated voltage: < AC 50 V/< DC 120 V(protection low voltage in accordance with DIN VDE 0100 T. 410)potentiometer drive shaft can be operated without actuating element.
At rated voltage: > AC 50 V to max. AC/DC 320 Vpotentiometer drive shaft can only be operated with actuating elementor has to be deenergized.
Other resistances on request.
Complete order no.Potentiometer without actuating element 07-3371-1D 0Please enter code number.
Actuating elementStandard (Skala 1-10) Order no. 05-0003-007600Increased oil resistance (Skala 1-10) Order no. 05-0003-007600BN
1
2
3
4
5
6
7
Potentiometer with terminalsfor rail-mounted installation
200866_7_240908.pmd 12.11.2010, 09:503
18
03-0
330-
0261
/A-0
7/10
-BCS
-202
008/
1
Control switch installation module, 4-pole
DescriptionThis control switch has been designed to solvethe variety of problems encountered in chemicaland petrochemical plants and on explosion-proofed electrical machinery. Four switch contactsas opening and closing elements in differentpermutations permit a variety of functions. Theopener has a positive break operation. The switchactuator offers latched and momentary-contactpositions with different switch positions.
The control switch can be installed quickly anddirectly into double or triple ComEx enclosures,or in combination with other command devicesin control units
Features Contacts with positive break operation
Latched and momentary-contact positions
Technical dataConnection
Terminals 2.5 mm2, fine stranded
Contact materialAgSnO2
Enclosure materialThermoplastic
Installationon TS 35 x 7.5 mounting rail
Switch functionmax. 4 switch contactsdifferent NC/NO contact assemblieslatching and momentary-contact functionswith different switch positions
Contactscontacts with positive break operation(self-cleaning)
Installationable to be installed in double and tripleComEx enclosures in control units
Switch isolatorDIN EN 60947-3 (main motor switch)
P/AC-3/AC-23 AC-3 AC-23230 V 3ph/3kW 1ph/2.2 kW400 V 3ph/5.5 kW 1ph/3 kW
le = AC-23/400 V/10 A
Control switch according to DINEN 60947-5-1 (auxiliary circuit switch)
AC-15 400 V 10 AAC-12 400 V 16 ADC-13 24 V 1 A
Electrical data
Rated insulation voltageUi = 690 VUe = 450 V
Rated impulse strengthUimp = 6 kV
Conditional rated short-circuitcurrent at 400 V
le = 4 kA
Short-circuit current(general-purpose l.v.h.b.c back-up fusefor the protection of cables and circuits)
max. 16 A
Nominal thermal current(+40 °C) Ithe =16 A(+60 °C) Ithe =11 A
Control switch
Explosion protectionEx protection type
II 2G Ex de IIC I M2 Ex de I
Class I, Zone 1, AEx de IIC, Ex de IICClass I, Div. 2, Group A, B, C, D
CertificationPTB 99 ATEX 1043 UUL E184198IECEx PTB 07.0046 UINMETRO 2003 EC02 CP0814
Permissible ambient temperature-55 °C to +60 °C
Dimensions
14
73 25.5
51
73
60
202008_1_2.pmd 12.11.2010, 09:532
19
03-0
330-
0261
/A-0
7/10
-BCS
-202
008/
2
Complete order no. 07-3331-1Please enter code number. Technical data subject to change without notice.
Contact arrangement of switch-isolator
N01 N02
Contact arrangement of control switch Contact arrangement of control switch
Selection chart
A01
A02
A03
A04
H05
C06
C07
E08
E09
L01
Code no. Code no.
Further contact versions are available upon request.
Selection chart
Description Order no.
Black position selector with protective collar, lockable*only for 4-pole switch
0 - I for ComEx enclosure 05-0003-006201für Control unit (flat) 05-0003-006301
I - II for ComEx enclosure 05-0003-006202für Control unit (flat) 05-0003-006302
I - 0 - II for ComEx enclosure 05-0003-006203für Control unit 05-0003-006303
0 - I - II for ComEx enclosure 05-0003-006204für Control unit (flat) 05-0003-006304
0 - I - II - III for ComEx enclosure 05-0003-006205für Control unit (flat) 05-0003-006305
0 - I - II - III - IV for ComEx enclosure 05-0003-006206für Control unit (flat) 05-0003-006306
HAND - 0 - AUTO for ComEx enclosure 05-0003-006209für Control unit (flat) 05-0003-006309
3426 13
M30
x 1
.5
∅ 6
5∅
65
3426 13
Illustration/Dimensions
*In principle, there are 3 boreholes in the protective collar to fit padlocks. If no further details are given on which switching position is to be locked, the boreholes are provided in the switch position 0 (I), other to customer specifications.
For ComEx enclosure
For control unit/ComEx 316L
M30
x 1
.5
Control switch installation module, 4-pole
1
2
3
4
5
6
7
202008_1_2.pmd 12.11.2010, 09:533
03-0
330-
0666
-01/
12-B
CS-3
2017
3
ComExflex Switch module for local control stations and control panels
ComEx flex
Switch module
FeaturesOne module for all fields of application
Large selection of actuating elements
High flexibility thanks to the junction box
Low installation depth
DescriptionThe ComExflex switch module is used in almost all hazardous areas where machine functions are activated by means of a button or a switch.
The ComExflex is flexible and in addition to a large number of actuating elements it offers a junction box to facilitate a safe and convenient installation of the module into a control panel. All contacts in the switch modules are self-cleaning and the opening contacts have positive opening operation.
The conductors are connected by means of terminals on the back of the module which have an increased safety level. The easy installation of the actuating elements without tools ensures conformance to the high IP degree of protection.
Code no.Type of contact
1 N/C + 1 N/O
2 N/O
1
2
4
Explosion protectionEx protection type II 2G Ex de IIC Gb I M2 Ex de I Mb
Certification PTB 99 ATEX 1043 U IECEx PTB 07.0046 U
Ambient temperature -55 °C to +60 °C
ComExflex Switch module
Selection chart
Complete order no.
Switch module without actuating element 07-3323-4 00
2 N/C
Dimensions
Technical DataProtection class determined by the actuating element and control station enclosure, terminals IP 20 (IEC 60529).
Rated 690 V insulation voltage
Rated operating voltage
400 V 400 V 110 V 24 V
Utilization category
AC-12 AC-15 DC-13 DC-13
Rated operating currents
16 A 10 A 0,5 A 1 A
Conventional 16 A/+40 °C, 11 A/+60 °C thermal current Ithe
Contact options contacts with positive-break operation (self-cleaning) 1 N/C and 1 N/O or 2 N/C or 2 N/O
Contact material AgSnO2
Enclosure material thermoplastic
Connection terminals 2.5 mm2, fine-stranded
Mechanical life >106 switching cycles
Storage temperature -55 °C to +70 °C
Weight approx. 110 g
Mounting locked, bayonet lock
Shock resistance DIN EN 60068-2-27: 2010, 30 g 18 msPlease enter code number.
38 68
72
03-0
330-
0670
-01/
12-B
CS-3
2018
7
ComExflex Lamp Module for Local Control Stations and Control Panels
ComEx flex
Lamp Module
FeaturesOne module for all fields of application
Illumination 180°
High flexibility due to junction box
Low installation depth
DescriptionThe ComExflex lamp module indicates command modes by means of a light signal lighting up or going out. It is suitable for use in almost all explosive areas in which a visual indication of a machine’s functional status is required.
The lamp module can be combined with various lamp module actuating elements. A junction box is available to facilitate a safe and convenient installation of the module into a control panel.
The conductors are connected by means of terminals on the back of the module which have an increased safety level. The lamp module actuating elements can be fitted easily without tools, which ensures conformance to the high IP degree of protection.
Explosion protectionEx protection type II 2G Ex de IIC Gb I M2 Ex de I Mb
Certification PTB 97 ATEX 1064 U IECEx PTB 10.0014 U
Ambient temperature -55 °C to +60 °C
ComExflex Lamp Module
Colour LED
red
green
yellow
white
blue
Selection chart
1
2
3
4
5
Code no.Colour
actuator
white
blue
Code no.
3
4
5
6
7
Wiringdiagram
Technical dataProtection class determined by actuating element and control station enclosure, terminals IP 20 (IEC 60529).
Rated 300 V
insulation voltage
Rated AC 12 V to 250 V (Ta < +50 °C) operating voltage DC 12 V to 60 V (Ta < +50 °C) AC/DC 12 V to 24 V (Ta < +60 °C)
Power consumption < 1 W
Lamp LED, red, green, yellow, white, blue
Illumination very bright, over a visible angle of 180°
Enclosure material Thermoplastic
Connection Terminals 2.5 mm2, fine-stranded
Electrical life >105 running hours
Storage and transport- -55 °C to +70 °C temperature
Weight approx. 110 g
Mounting locked, bayonet lock
Shock resistance DIN EN 60068-2-27: 2010, 30 g 18 ms
Dimensions38
9968
72.2
∅19
red
green
yellow
Complete order no. Lamp module 07-3353-41 0 without actuating element
Actuating element Standard 05-0003-001 00
Increased oil resistance 05-0003-001 00BN Please enter code number.
03-0
330-
0667
-01/
12-B
CS-3
2017
4
ComExflex Illuminated button for local control stations and control panels
ComEx flex
Illuminated button
FeaturesOne module for all fields of application
Excellent luminosity
High flexibility thanks to the junction box
Low installation depth
DescriptionThe ComExflex illuminated button is used in almost all hazardous (potentially explosive) areas where machine functions are activated by pressing a button and the corresponding functional status is to be indicated visually.
ComExflex is flexible and in addition to a large number of illuminated button actuators it offers a junction box to facilitate a safe and convenient installation of the module into a control panel. The module contacts are designed as snap-action contact elements.
The conductors are connected by means of terminals on the back of the module which have an increased safety level. The easy installation of the lamp module actuating elements, without tools, ensures conformance to the high IP degree of protection.
Explosion protectionEx protection type II 2G Ex de IIC Gb I M2 Ex de I Mb
Certification PTB 97 ATEX 1064 U IECEx PTB 10.0014 U
Ambient temperature -55 °C to +60 °C
ComExflex Illuminated Button
Dimensions
Complete order no. Illuminated button without actuating element 07-3363-4 0 Actuating element Standard 05-0003-006 00
Increased oil resistance 05-0003-006 00BNPlease enter code number.
Code no.
7
8
Selection chart Colour actuator
red
green
yellow
white
blue
Colour LED
red
green
yellow
white
blue
Type of contacts
1 N/C
1 N/O
Code no.
1
2
3
4
5
Code no.
5
6
7
8
9
Technical DataProtection class determined by the actuating element and control station enclosures, terminals IP 20 (IEC 60529).
Rated 300 V Insulation voltage
Rated AC 12 V to 250 V (Ta < +50 °C) operating voltage DC 12 V to 60 V (Ta < +50 °C) AC/DC 12 V to 24 V (Ta < +60 °C)
Power consumption < 1 W
Lamp LED, red, green, yellow, white, blue
Contacts 1 N/C or 1 N/O as snap switch element AC 15: 1 A, 230 V
Illumination very bright, over a visible angle of 180°
Enclosure material thermoplastic
Type of connection terminals 2.5 mm2, fine-stranded
Service life electrical: >105 running hours mechanical: >105 switching cycles
Storage and transport -55 °C to +70 °C temperature
Weight approx. 110 g
Mounting locked, bayonet lock
Shock resistance DIN EN 60068-2-27: 2010, 30 g 18 ms
3892
68
72 ∅19
03-0
330-
0669
-01/
12-B
CS-3
2018
6
ComExflex Potentiometer for local control stations and control panels
ComEx flex
Potentiometer
FeaturesOne module for all fields of application
High flexibility thanks to the junction box
Low installation depth
DescriptionThe ComExflex potentiometer is used in almost all hazardous (potentially explosive) areas where machine functions are controlled by means of adjustable voltage distributors.
The module can be combined with a potentiometer actuator (scale graduation 0 to 10). A junction box is available as a safe and convenient means of installing the potentiometer in a control panel.
The conductors are connected by means of terminals on the back of the module which have an increased safety level. The easy installation of the potentiometer actuating element without the need for tools,ensures conformance to the high IP degree of protection.
Explosion protectionEx protection type II 2G Ex de IIC Gb I M2 Ex de I Mb
Certification PTB 05 ATEX 1064 U IECEx PTB 10.0017 U
Ambient temperature -55 °C to +60 °C
Technical dataProtection class determined by the actuating element and control station enclosure, terminals IP 20 (IEC 60529).
Rated 500 V insulation voltage
Max. rated voltage AC/DC 320 V
Resistance 1 kΩ to 10 kΩ
Curve shape linear
Resistance tolerance + 20 %
Rated output max. 1 W for Ta < +40 °C
Resistor material carbon film on ceramics
Rotation mech. 285° to 5° electr. approx. 250°
Torque (beginning) 0.5 to 1.5 Ncm
Torque (end stop) > 100 Ncm
Enclosure material Thermoplastic
Connection double terminals 2 x 2.5 mm2, fine-stranded
Mechanical life 25,000 sinusoidal cycles
Storage and transport temperature -55 °C to +70 °C
Weight approx. 110 g
Dimensions
ComExflex Potentiometer
4
5
6
7
Code no.
Selection chart
Wiring diagram
Complete order no. Potentiometer without actuating element 07-3373-4D 0 Please enter code number. Other levels of resistance on request.
Actuating element Complete order no. Standard (Scale 1-10) 05-0003-007600 Increased oil resistance (Scale 1-10) 05-0003-007600BN
Notes for installation and inspection
At rated voltage: < AC 50 V/< DC 120 V (Safety extra low voltage in conformance to DIN VDE 0100 T. 410) The potentiometer drive shaft can be operated without actuating element.
> AC 50 V to max. AC/DC 320 V Potentiometer drive shaft must be operated with an actuating element or it must be deenergized.
Resistance (kΩ)
1
2,2
4,7
10
38 68
72
03-0
330-
0668
-01/
12-B
CS-3
2018
5
ComExflex Junction box for local control stations and control panel
Junction boxBARTEC offers a junction box to facilitate the use of ComExflex in a control console or a control panel. The junction box features a cable gland and can be combined with various function modules.
The junction box allows the connection of a conductor, which can be assembled either to order or by the customer.
ComEx flex
Junction box
DimensionsComExflex Junction box with function modules
38
72
11957
Order no. Junction box05-0042-0050Technical data subject to change without notice.
ComExflex Junction box
Explosion protectionEx protection type II 2G Ex de IIC T6 Gb II 2D Ex tb IIIC T80°C Db IP 66
Certification PTB 11 ATEX 1010 X IECEx PTB 11.0025X
Ambient temperature -55 °C to +40 °C / +50 °C / +60 °C
Approved for Zone 1, 2 and 21, 22
Technical dataProtection class Function module with junction box and actuating element up to IP 66/IP 67
Weight approx. 40 g
Clamping range 4 to 9 mm 5 to 10 mm
Enclosure material/ Thermoplastic/injection moulding -manufacturing process
20
03-0
330-
0192
/B-0
5/11
-BCS
-200
866/
2
Switch module with terminalsfor panel-mounted installation
Conventional thermal current Ithe
16 A/+40 °C, 11 A/+60 °C
Contact optionscontacts with positive break operation(self cleaning)1 NC and 1 NO or2 NC or 2 NO
Contact materialAgSnO2
Enclosure materialThermoplastic
ConnectionTerminals 2.5 mm2, fine stranded
Mechanical life106 switching cycles
Storage temperature-55 °C to +70 °C
Actuating elementCodeno.
0700
7400
0800
0900
1000
1001
1002
1003
7001
7002
7203
1800
1200
1201
1202
1203
6100
7700
7701
7900
Selection chart
Dimensions
Codeno.
46
37
33,5 65
57
Technical dataProtection class
Determined by actuating element andcontrol station enclosure,terminals IP 20 (IEC 60529).
Rated insulation voltage690 V
Switch module for local control stations
1
2
4
Explosion protectionEx protection type
II 2G Ex de IIC Gb I M2 Ex de I Mb
Class I, Zone 1, AEx de IIC, Ex de IICClass I, Div. 2, Groups A, B, C, D
CertificationPTB 99 ATEX 1043 UUL E184198IECEx PTB 07.0046 UINMETRO 2003EC02CP081U
Ambient temperature-55 °C to +60 °C
Type of contact
2 NC
2 NO
1 NC + NO
Complete order no.Switch module without actuating element 07-3323-1 00
Actuating elementStandard 05-0003-00
Increased oil resistance 05-0003-00 BN
Please enter code number.
Pushbutton
Double push button actuator
Emergency stop NOT-AUS
Selector switch 0 + I latching, 2 positions
Selector switch I + II latching, 3 positions
Selector switch I + II momentary-contact, 3 positions
Selector switch I latching, II momentary-contact, 3 positions
Selector switch I momentary-contact, II latching, 3 positions
Selector switch with protective collar 0 + I
Selector switch with protective collar I + 0
Selector switch with protective collar I + 0 + II
Mushroom pushbutton, black
Lockable in both positions, DOM lock
Lockable in the depressed position, DOM lock
Lockable in the initial position, DOM lock
Locking-type mushroom pushbutton
Lockable in both positions, RONIS lock
Key switch, 2 switching positions latching, key retractable 0 + I
Key switch, 2 switching positions momentary contact, not retractable 0 + I
Key switch, 2 switching positions momentary contact, not retractable 0 + I
Weightapprox. 87 g
Mountinglocked, by bayonet lock
Shock resistanceDIN EN 60068-2-27: 1995, 30 g 18 ms
Rated voltage400 V 400 V 110 V 24 VUtilization categoryAC-12 AC-15 DC-13 DC-13Rated operating currents16 A 10 A 0,5 A 1 A
21
03-0
330-
0192
/B-0
5/11
-BCS
-200
866/
5
Lamp module for local control stations
Lamp module with terminalsfor panel-mounted installation
Technical dataProtection class
Determined by actuating element andcontrol station enclosure,terminals IP 20 (IEC 60529).
Rated insulation voltage300 V
Rated operating voltageAC 12 V to 250 V (Ta < +50 °C)DC 12 V to 60 V (Ta < +50 °C)AC/DC 12 V to 24 V (Ta < +60 °C)
Power consumption< 1 W
LampLEDred, green, yellow, white, blue
Illuminationvery bright, over a visible angle of 180°
Enclosure materialThermoplastic
ConnectionTerminals 2.5 mm2, fine stranded
Electrical life> 105 running hours
Storage and transport temperature-55 °C to +70 °C
Weightapprox. 90 g
Mountinglocked, by bayonet lock
Shock resistanceDIN EN 60068-2-27: 1995, 30 g 18 ms
Dimensions
46
37
33.5
65
57
∅ 1
9
97
Colour LED
red
green
yellow
white
blue
1
2
3
4
5
Code no. Colour actuator
red
green
yellow
white
blue
Code no.
3
4
5
6
7
Wiring diagram
X1
X2
Explosion protectionEx protection type
II 2G Ex de IIC Gb I M2 Ex de I Mb
Class I, Zone 1, AEx de IIC, Ex de IICClass I, Div. 2, Groups A, B, C, D
CertificationPTB 97 ATEX 1064 UUL E184198IECEx PTB 10.0014 UINMETRO 2003EC02CP096U
Ambient temperature-55 °C to +50 °C+60 °C (AC/DC 12 to 24 V) Selection chart
1
2
3
4
5
6
7Complete order no.Lamp module without actuating element 07-3353-11 0
Actuating elementStandard 05-0003-001 00
Increased oil resistance 05-0003-001 00BN
Please enter code number.
22
03-0
330-
0295
/A-0
7/10
-BCS
-217
100
Illuminated button with terminalsfor panel-mounted installation
Dimensions
Illuminated button for local control stations
Explosion protectionEx protection type
II 2G Ex de IIC I M2 Ex de I
Class I, Zone 1, AEx de IIC, Ex de IICClass I, Div. 2, Groups A, B, C, D
CertificationPTB 97 ATEX 1064 UUL E184198IECEx PTB 10.0014 UINMETRO 2003 EC02 CP096 U
Ambient temperature-55 °C to +50 °C+60 °C (AC/DC 12 to 24 V)
Technical dataProtection class
determined by actuating element andcontrol station enclosure,terminals IP 20 (IEC 60529).
Rated insulation voltage300 V
Rated operating voltageAC 12 V to 250 V (Ta < +50 °C)DC 12 V to 60 V (Ta < +50 °C)AC/DC 12 V to 24 V (Ta < +60 °C)
Power consumption< 1 W
LampLED: red, green, yellow, white, blue
Illuminationvery bright, over a visible angle of 180°
Contact element
Contacts1 NC or 1 NO as snap switch element
Switching capacityAC-15 1 A/230 VDC-13 0.25 A/24 V
37 65
9033.5
4657
Enclosure materialThermoplastic
ConnectionTerminals 2.5 mm2, fine stranded
Electrical life>105 running hours
Mechanical life>105 switching cycles
Storage and transport temperature-55 °C to +70 °C
Weightapprox. 130 g
Mountinglocked, by bayonet lock
Shock resistanceDIN EN 60068-2-27: 1995, 30 g 18 ms
Rated voltage230 V 24 VUtilization categoryAC-15 DC-13Rated operating current1 A 0.25 A
Code no.
Selection chart
5
6
7
8
9
Code no. Code no.Colour actuator
red
green
yellow
white
blue
1
2
3
4
5
Colour LED
red
green
yellow
white
blue
7
8
Complete order no.Illuminated button without actuating element 07-3363-1 0
Actuating elementStandard 05-0003-006 00
Increased oil resistance 05-0003-006 00BN
Please enter code number.
Type of contact
1 NC
1 NO
23
03-0
330-
0427
/A-0
7/10
-BCS
-240
845
1
2
3
4
5
6
7
Potentiometer for local control stations
Potentiometer with terminalsfor panel-mounted installation
Explosion protectionEx protection type
II 2G Ex de IIC I M2 Ex de I
Ex de IIC
CertificationPTB 05 ATEX 1064 UIECEx PTB I0.0017 U
Ambient temperature-55 °C to +60 °C
Dimensions
37
33.5 65
4657
Technical dataProtection class
determined by actuating element andcontrol station enclosure,terminals IP 20 (IEC 60529).
Rated insulation voltage500 V
Max. rated voltageAC/DC 320 V
Resistance1 kΩ to 10 kΩ
Curve shapelinear
Resistance tolerance 20 %
Power consumptionmax. 1 W at Ta < +40 °C
Resistor materialcarbon film on ceramics
Rotationmech. 285° -5°electr. about approx. 250°
Torgue (beginning)0.5 to 1.5 Ncm
Torgue (end stop)> 100 Ncm
Enclosure materialThermoplastic
ConnectionDouble terminals 2 x 2.5 mm2, fine stranded
Mechanical life25000 sinusoidal cycles
Storage and transport temperature-55 °C to +70 °C
Weightapprox. 88 g
Notes for installation and inspection:
At rated voltage: < AC 50 V/< DC 120 V(protection low voltage in accordance with DIN VDE 0100 T. 410)potentiometer drive shaft can be operated without actuating element.
At rated voltage: > AC 50 V to max. AC/DC 320 Vpotentiometer drive shaft can only be operated with actuating elementor has to be deenergized.
4
5
6
7
Code no.
Selection chart
Wiring diagram Resistance
1 kΩ
2.2 kΩ
4.7 kΩ
10 kΩ
Complete order no.Potentiometer without actuating element 07-3373-1D 0Please enter code number.
Actuating elementStandard (scale 1-10) Order no. 05-0003-007600Increased oil resistance (scale 1-10) Order no. 05-0003-007600BN
Other resistances on request.
24
03-0
330-
0192
/B-0
5/11
-BCS
-200
866/
3
Complete order no.Switch module without actuating element 07-3323-3 03*)
Actuating element Standard 05-0003-00Increased oil resistance 05-0003-00 BN
Please enter code number. *) Standard length 3 m, indicate greater lengths in plain text.
Switch modulewith connection cable for installation on panel (front installation)
Conventional thermal current Ithe
16 A/+40 °C, 11 A/+60 °C
Contact optionscontacts with positive break operation(self cleaning)1 NC and 1 NO or2 NC or 2 NO or1 NC or 1 NO
Contact materialAgSnO2
Enclosure materialThermoplastic
Technical dataProtection class
Determined by actuating element andenclosure, up to IP 67, in conjunctionwith actuating element. PTB 00 ATEX 3114 U.
Rated insulation voltageUi = 690 V (on request)Ui = 400 V (Standard version)
Features Self-cleaning contacts Positive break contacts One-hand fastening
DescriptionAs completely certified equipment, BARTEC modules with connection cable can be directly installed inindustrial control cabinets in hazardous areas. A high IP degree of protection can be maintained due toeasy installation of the actuating elements in the control cabinet. The respective modules can be single-handedly installed to the actuating elements.
Explosion protectionEx protection type
II 2G Ex d IIC T6Class I, Division 2, Groups A, B, C, DClass I, Zone 1, AEx d IICClass I, Division 2, Groups A, B, C, Dfor CanadaClass I, Zone 1, Ex d IIC for Canada
CertificationPTB 00 ATEX 1092 XUL E184198INMETRO 2004EC02CP005X
Ambient temperature-40 °C to +60 °C (-55 °C on request)
Dimensions
35.537
104.5
88
46
Actuating elementCodeno.
Selection chartCodeno.
0700
7400
0800
0900
1000
1001
1002
1003
7001
7002
7203
1800
1200
1201
1202
1203
6100
7700
7701
7900
Type of contact
2 NC
2 NO
1 NC+ 1 NO
1 NC
1 NO
1
2
4
7
8
Pushbutton
Double push button actuator
Emergency stop NOT-AUS
Selector switch 0 + I latching, 2 positions
Selector switch I + II latching, 3 positions
Selector switch I + II momentary-contact, 3 positions
Selector switch I latching, II momentary-contact, 3 positions
Selector switch I momentary-contact, II latching, 3 positions
Selector switch with protective collar 0 + I
Selector switch with protective collar I + 0
Selector switch with protective collar I + 0 + II
Mushroom pushbutton, black
Lockable in both positions, DOM lock
Lockable in the depressed position, DOM lock
Lockable in the initial position, DOM lock
Locking-type mushroom pushbutton
Lockable in both positions, RONIS lock
Key switch, 2 switching positions latching, key retractable 0 + I
Key switch, 2 switching positions momentary contact, not retractable 0 + I
Key switch, 3 switching positions latching, key retractable I + 0 + II
Connectionflexible cord 4 x 1.5 mm² (∅ 9.1 mm)resp. 2 x 1.5 mm², (∅ 7.7 mm)
Mechanical life106 switching cycles
Storage temperature-55 °C to +70 °C
Weightapprox. 160 g without cable
Cable length3 m, indicate greater lengths inplain text
Shock resistanceDIN EN 60068-2-27: 1995, 30 g 18 ms
Rated voltage400 V 400 V 110 V 24 VUtilization categoryAC-12 AC-15 DC-13 DC-13Rated operating currents16 A 10 A 0,5 A 1 A
25
03-0
330-
0192
/B-0
5/11
-BCS
-200
866/
6
Lamp modulewith connection cable for installation on panel (front installation)
Technical dataProtection class
determined by actuating element andenclosure, up to IP 67, in conjunction withactuating element. PTB 00 ATEX 3114 U.
Rated insulation voltage300 V
Rated operating voltageAC 12 V to 250 V (Ta < +50 °C)DC 12 V to 60 V (Ta < +50 °C)AC/DC 12 V to 24 V (Ta < +60 °C)
Power consumption< 1 W
LampLEDred, green, yellow, white, blue
Illuminationvery bright, over a visible angle of 180°
Enclosure materialThermoplastic
Connectionflexible cord 2 x 0.75 mm² (∅ 6.4 mm)
Electrical life>105 running hours
Storage temperature-55 °C to +70 °C
DescriptionAs completely certified equipment, BARTEC modules with connection cable can be directly installed inindustrial control cabinets in hazardous areas. A high IP degree of protection can be maintained due toeasy installation of the actuating elements in the control cabinet. The respective modules can be single-handedly installed to the actuating elements.
Features Long service life Illumination 180° Brilliant colours One-hand fastening
Colour LED
red
green
yellow
white
blue
Selection chart
1
2
3
4
5
Code no. Colour actuator
red
green
yellow
white
blue
Code no.
3
4
5
6
7
Wiring diagram
Complete order no.Lamp module without actuating element 07-3353-31 3*)
Actuating element Standard 05-0003-001 00
Increased oil resistance 05-0003-001 00BN
Please enter code number.
*) Standard length 3 m, indicate greater lengths in plain text.
Explosion protectionEx protection type
II 2G Ex d IIC T6Class I, Division 2, Groups A, B, C, DClass I, Zone 1, AEx d IICClass I, Division 2, Groups A, B, C, Dfor CanadaClass I, Zone 1, Ex de IIC for Canada
CertificationPTB 97 ATEX 1065 XUL E184198INMETRO 2004EC02CP006X
Ambient temperature-40 °C to +50 °C (-55 °C on request)+60 °C (AC/DC 12 to 24 V)
Dimensions
35.537 120
136.5
46
88
ø 19
Weightapprox. 180 g without cable
Mountinglocked, by bayonet lock
Cable length3 m, indicate greater lengths in plain text
Shock resistanceDIN EN 60068-2-27: 1995, 30 g 18 ms
Note
The connection cable for lamp modules mustbe installed in a way which ensures that nocapacitive influence (voltage transmission) ispossible through lines routed in parallel.
1
2
3
4
5
6
7
27
03-0
330-
0426
/A-0
7/10
-BCS
-240
844
4
5
6
7
Code no.
Potentiometerwith connection cable for installation on panel (front installation)
Dimensions
Technical dataProtection class
determined by actuating element andenclosure. Potentiometer up to IP 67in conjunction with actuating element.PTB 00 ATEX 3114 U.
Rated insulation voltageUi = 500 VUi = 400 V (Standard version)
Max. rated operating voltageAC/DC 320 V
Resistance1 kΩ to 10 kΩ
Characteristic curvelinear
Resistance tolerance 20 %
Power consumptionmax. 1 W for Ta < +40 °C
Resistance materialcarbon layer on ceramics
Rotation rangemech. 285° -5°electr. effective approx. 250°
Torque (beginning)0.5 to 1.5 Ncm
Torque (end stop)> 100 Ncm
Enclosure materialThermoplastic
Connectionflexible cable 3 x 0.75 mm²
Mechanical life25000 sinusoidal cycles
Storage temperature-55 °C to +70 °C
88
104.5
3735.5
46
DescriptionAs completely certified equipment, BARTECmodules with connection cable can be directlyinstalled in industrial control cabinets in hazardousareas. A high IP degree of protection can bemaintained due to easy installation of the actuatingelements in the control cabinet. The respectivemodules can be single-handedly installed to theactuating elements.
Selection chart
Wiring diagram
Features High end stop torque High IP degree of protection One-hand fastening
Resistance value
1 kΩ
2.2 kΩ
4.7 kΩ
10 kΩ
Notes for installation and inspection:
At rated voltage: < AC 50 V/< DC 120 V(protection low voltage in accordance with DIN VDE 0100 T. 410)potentiometer drive shaft can be operated without actuating element.
At rated voltage: > AC 50 V to max. AC/DC 320 Vpotentiometer drive shaft can only be operated with actuating elementor has to be deenergized.
Other resistances on request.
Explosion protectionEx protection type
II 2G Ex d IIC T6
CertificationPTB 05 ATEX 1065 X
Ambient temperature-40 °C to +60 °C(-55 °C on request)
Complete order no.Potentiometer without actuating element 07-3373-3D 3*)
Please enter code number.
*) Standard length 3 m, indicate greater lengths in plain text.
Actuating elementStandard (Scale 1-10) 05-0003-007600Increased oil resistance (Scale 1-10) 05-0003-007600BN
Weightapprox. 240 g with 1 m cable
Cable length3 m, indicate greater lengths in plain text
1
2
3
4
5
6
7
Contactos/Contacts:
Comercial/Commercial:
Fernando Mena Costa
e-mail: fcosta@bhb,pt
Tel: (+351) 21 843 64 00
Fax: (+351) 21 843 64 09
Assistência/Service:
Patricia Costa
e-mail: [email protected]
Tel: (+351) 21 843 64 00