PROJECT:
DOCUMENT TITLE:
DESCRIPTION
FIRST ISSUE PELR LLBZ RAAI
REV.
A
R. ARDESTANI
27/05/2010
-
S10 NMO 015
APPR.
KINGDOM OF SAUDI ARABIA
P. LECARPENTIER
L. BARDEZ
MLS-ESP-024
DATE
SOUTH OF JEDDAH
AL KHUMRA MAIN LIFT STATION
PRELIMINARY DESIGN
DOCUMENT N:
Tel.: (33-1) 0146.14.71.00 Fax : (33-1) 01.47.24.77.88
WASTE AIR DUCTS
27/05/2010
PREP. CHECK.
REVISION:
Parc de l'Ile - 15/27, rue du Port - B.P. 727 - 92007 Nanterre Cedex
PREPARED:
CHECKED:
APPROVED:
DATE:
SCALE:
PROJECT N:
A
FILE:MLS-ESP-024A Waste air ducts
8/13/2019 MLS-ESP-024A Waste Air Ducts%
2/8
A
Page 2 / 8
SUMMARY
page
1 - Location / Purpose / Quantity 3
2 - Environment 4
3 - Process data 5
- Field of application 5
- Sizing data 5
- Terms of service 5
4 - Ducts 5
5 - Balancing volume dampers 6
6 - Control volume dampers 6
7 - Louvres 6
8 - Inspection, maintenance and cleaning of duct network 6
9 - Drawings 7
10 - Operating philosophy 8
11 - Guarantees / Other specifications 8
- Guarantees 8
- Other specifications 8
3,1
3,2
MLS-ESP-024
WASTE AIR DUCTS
AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN
27/05/2010
3,3
11,2
11,1
8/13/2019 MLS-ESP-024A Waste Air Ducts%
3/8
A
Page 3 / 8
1 - Location / Purpose / Quantity
Localisation Main Lift Station
Odour treatment building
Purpose Transfert waste air from polluted chambers to odour
treatment
Quantity of equipment
MLS-ESP-024
WASTE AIR DUCTS
AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN
27/05/2010
8/13/2019 MLS-ESP-024A Waste Air Ducts%
4/8
A
Page 4 / 8
2 - Environment
Outdoor
Indoor, ventilated
Outdoor, under cover
Outdoor temperature
Lower C
Higher C
Indoor temperature C
Relative humidity
Lower %
Higher %
Corosive atmosphere: yes no
Dusty atmosphere: yes no
Explosive area: yes no
Altitude: .. m
Sandstorm: yes no
Seaside: yes no
Presence of hydrogen sulphide: yes no
Presence of chloride: yes no
MLS-ESP-024
WASTE AIR DUCTS
AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN
9
27/05/2010
47
5,18
50
100
25
8/13/2019 MLS-ESP-024A Waste Air Ducts%
5/8
A
Page 5 / 8
3 - Process data
- Field of application
Waste air blowing
- Sizing data
Static pressure Maximum 2 000 Pa
- Terms of service
24 hours/day
7 days/week
Automatic control.
4 - Ducts
Ducts shall be HDPE or PVC
Duct air speed (in accordance with INRS recommandations)
MLS-ESP-024
WASTE AIR DUCTS
AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN
3,1
3,2
27/05/2010
3,3
Diameter
mm
Flow
m/h
Flow
m/s
Diameter
mm
Flow
m/h
Flow
m/s
Diameter
mm
Flow
m/h
Flow
m/s
DN 100 100 3,8 DN 355 2 200 6,3 DN 710 11 200 8,4
DN 125 190 4,2 DN 400 3 000 6,5 DN 800 16 000 9,0
DN 160 320 4,5 DN 450 4 000 7,0 DN 900 21 000 9,4
DN 200 550 5,0 DN 500 5 200 7,2 DN 1 000 26 000 9,8
DN 250 1 000 5,5 DN 560 7 000 7,8 DN 1 120 35 000 10,2
DN 315 1 600 6,0 DN 630 9 000 8,2 DN 1 250 45 000 10,6
8/13/2019 MLS-ESP-024A Waste Air Ducts%
6/8
A
Page 6 / 8
Construction Ducts are primarily circular section, which ensures a better
mechanical resistance to pressure or vacuum, and betteraerodynamics profile.
Ducts will be stiffened in order not to deform under pressure
or vacuum. Deformation shall be less than 1%
Installation The materials will be adapted to the location and the possibilities
of supporting from the concrete structure, ceilings, walls or floor.
The distance between 2 stands must be such that the duct
does not suffer any deformation regardless of the type of stands .
All accessories (dampers, valves, taps, ...) will be supported at
each end. The ducts should be supported every 2.50 m with
collars and stainless steel threaded rods.
Materials used will be stainless steel and plastics.
Interpose flexible joints between the supports and duct.
5 - Balancing volume dampers
Balancing volume dampers shall be provided where flow rates in ducts must be adjusted.
Dampers shall be made of the same kind of material as that of the ducts, and where it is not applicable
they shall be made of stainless steel. For every pump sump, a balancing volume damper shall be
provided on all exhaust ducts. Balancing dampers shall be motorised so that they can be closed when
not in use and open to their preset position when resuming operation.
6 - Control volume dampers
Motorised volume dampers shall be provided on fresh air supply ducts and exhaust air ducts
so as to extend control range of air flow rate or pressure. Like Variable Speed Drives
the motorised volume dampers shall be controlled by the PLC
Each motorised damper shall be bypassed by a manual volume damper of smaller size.
7 - Louvres
Louvers shall be sized to meet the maximum air flow requirements. They shall be provided with
volume dampers where required.
8 - Inspection, maintenance and cleaning of duct network
Realization of hatches in sufficient quantity
MLS-ESP-024
WASTE AIR DUCTS
AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN
27/05/2010
8/13/2019 MLS-ESP-024A Waste Air Ducts%
7/8
A
Page 7 / 8
Traps will be placed judiciously:
On straight ducts
Near the elbowsUpstream and downstream of a damper
On plenums.
They will be built with the same material as the ducts and the same thickness.
9 - Drawings
MLS-ESP-024
WASTE AIR DUCTS
AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN
27/05/2010
8/13/2019 MLS-ESP-024A Waste Air Ducts%
8/8
A
Page 8 / 8
10 - Operating philosophy
Fans are driven by frequency converters. Variable Frequency Drives
They maintain a low pressure in the plenum: 500 Pa below atmospheric pressure
11 - Guarantees / Other specifications
- Guarantees
The equipment will be guaranteed two years against defects in design, manufacture or
installation.
Special guaranty against corrosion (5 years for coating)
- Other specifications
The product shall comply with the general requirements.
On-site installation.
Ten years spare parts list.
Manufacturer documentation: dimensional drawings with loads, electric schemes,
Operating and Maintenance Manual.
Test reports.
Certificate of compliance.
11,1
11,2
MLS-ESP-024
WASTE AIR DUCTS
AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN
27/05/2010