MLS-ESP-024A Waste Air Ducts%

Embed Size (px)

Citation preview

  • 8/13/2019 MLS-ESP-024A Waste Air Ducts%

    1/8

    PROJECT:

    DOCUMENT TITLE:

    DESCRIPTION

    FIRST ISSUE PELR LLBZ RAAI

    REV.

    A

    R. ARDESTANI

    27/05/2010

    -

    S10 NMO 015

    APPR.

    KINGDOM OF SAUDI ARABIA

    P. LECARPENTIER

    L. BARDEZ

    MLS-ESP-024

    DATE

    SOUTH OF JEDDAH

    AL KHUMRA MAIN LIFT STATION

    PRELIMINARY DESIGN

    DOCUMENT N:

    Tel.: (33-1) 0146.14.71.00 Fax : (33-1) 01.47.24.77.88

    WASTE AIR DUCTS

    27/05/2010

    PREP. CHECK.

    REVISION:

    Parc de l'Ile - 15/27, rue du Port - B.P. 727 - 92007 Nanterre Cedex

    PREPARED:

    CHECKED:

    APPROVED:

    DATE:

    SCALE:

    PROJECT N:

    A

    FILE:MLS-ESP-024A Waste air ducts

  • 8/13/2019 MLS-ESP-024A Waste Air Ducts%

    2/8

    A

    Page 2 / 8

    SUMMARY

    page

    1 - Location / Purpose / Quantity 3

    2 - Environment 4

    3 - Process data 5

    - Field of application 5

    - Sizing data 5

    - Terms of service 5

    4 - Ducts 5

    5 - Balancing volume dampers 6

    6 - Control volume dampers 6

    7 - Louvres 6

    8 - Inspection, maintenance and cleaning of duct network 6

    9 - Drawings 7

    10 - Operating philosophy 8

    11 - Guarantees / Other specifications 8

    - Guarantees 8

    - Other specifications 8

    3,1

    3,2

    MLS-ESP-024

    WASTE AIR DUCTS

    AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN

    27/05/2010

    3,3

    11,2

    11,1

  • 8/13/2019 MLS-ESP-024A Waste Air Ducts%

    3/8

    A

    Page 3 / 8

    1 - Location / Purpose / Quantity

    Localisation Main Lift Station

    Odour treatment building

    Purpose Transfert waste air from polluted chambers to odour

    treatment

    Quantity of equipment

    MLS-ESP-024

    WASTE AIR DUCTS

    AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN

    27/05/2010

  • 8/13/2019 MLS-ESP-024A Waste Air Ducts%

    4/8

    A

    Page 4 / 8

    2 - Environment

    Outdoor

    Indoor, ventilated

    Outdoor, under cover

    Outdoor temperature

    Lower C

    Higher C

    Indoor temperature C

    Relative humidity

    Lower %

    Higher %

    Corosive atmosphere: yes no

    Dusty atmosphere: yes no

    Explosive area: yes no

    Altitude: .. m

    Sandstorm: yes no

    Seaside: yes no

    Presence of hydrogen sulphide: yes no

    Presence of chloride: yes no

    MLS-ESP-024

    WASTE AIR DUCTS

    AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN

    9

    27/05/2010

    47

    5,18

    50

    100

    25

  • 8/13/2019 MLS-ESP-024A Waste Air Ducts%

    5/8

    A

    Page 5 / 8

    3 - Process data

    - Field of application

    Waste air blowing

    - Sizing data

    Static pressure Maximum 2 000 Pa

    - Terms of service

    24 hours/day

    7 days/week

    Automatic control.

    4 - Ducts

    Ducts shall be HDPE or PVC

    Duct air speed (in accordance with INRS recommandations)

    MLS-ESP-024

    WASTE AIR DUCTS

    AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN

    3,1

    3,2

    27/05/2010

    3,3

    Diameter

    mm

    Flow

    m/h

    Flow

    m/s

    Diameter

    mm

    Flow

    m/h

    Flow

    m/s

    Diameter

    mm

    Flow

    m/h

    Flow

    m/s

    DN 100 100 3,8 DN 355 2 200 6,3 DN 710 11 200 8,4

    DN 125 190 4,2 DN 400 3 000 6,5 DN 800 16 000 9,0

    DN 160 320 4,5 DN 450 4 000 7,0 DN 900 21 000 9,4

    DN 200 550 5,0 DN 500 5 200 7,2 DN 1 000 26 000 9,8

    DN 250 1 000 5,5 DN 560 7 000 7,8 DN 1 120 35 000 10,2

    DN 315 1 600 6,0 DN 630 9 000 8,2 DN 1 250 45 000 10,6

  • 8/13/2019 MLS-ESP-024A Waste Air Ducts%

    6/8

    A

    Page 6 / 8

    Construction Ducts are primarily circular section, which ensures a better

    mechanical resistance to pressure or vacuum, and betteraerodynamics profile.

    Ducts will be stiffened in order not to deform under pressure

    or vacuum. Deformation shall be less than 1%

    Installation The materials will be adapted to the location and the possibilities

    of supporting from the concrete structure, ceilings, walls or floor.

    The distance between 2 stands must be such that the duct

    does not suffer any deformation regardless of the type of stands .

    All accessories (dampers, valves, taps, ...) will be supported at

    each end. The ducts should be supported every 2.50 m with

    collars and stainless steel threaded rods.

    Materials used will be stainless steel and plastics.

    Interpose flexible joints between the supports and duct.

    5 - Balancing volume dampers

    Balancing volume dampers shall be provided where flow rates in ducts must be adjusted.

    Dampers shall be made of the same kind of material as that of the ducts, and where it is not applicable

    they shall be made of stainless steel. For every pump sump, a balancing volume damper shall be

    provided on all exhaust ducts. Balancing dampers shall be motorised so that they can be closed when

    not in use and open to their preset position when resuming operation.

    6 - Control volume dampers

    Motorised volume dampers shall be provided on fresh air supply ducts and exhaust air ducts

    so as to extend control range of air flow rate or pressure. Like Variable Speed Drives

    the motorised volume dampers shall be controlled by the PLC

    Each motorised damper shall be bypassed by a manual volume damper of smaller size.

    7 - Louvres

    Louvers shall be sized to meet the maximum air flow requirements. They shall be provided with

    volume dampers where required.

    8 - Inspection, maintenance and cleaning of duct network

    Realization of hatches in sufficient quantity

    MLS-ESP-024

    WASTE AIR DUCTS

    AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN

    27/05/2010

  • 8/13/2019 MLS-ESP-024A Waste Air Ducts%

    7/8

    A

    Page 7 / 8

    Traps will be placed judiciously:

    On straight ducts

    Near the elbowsUpstream and downstream of a damper

    On plenums.

    They will be built with the same material as the ducts and the same thickness.

    9 - Drawings

    MLS-ESP-024

    WASTE AIR DUCTS

    AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN

    27/05/2010

  • 8/13/2019 MLS-ESP-024A Waste Air Ducts%

    8/8

    A

    Page 8 / 8

    10 - Operating philosophy

    Fans are driven by frequency converters. Variable Frequency Drives

    They maintain a low pressure in the plenum: 500 Pa below atmospheric pressure

    11 - Guarantees / Other specifications

    - Guarantees

    The equipment will be guaranteed two years against defects in design, manufacture or

    installation.

    Special guaranty against corrosion (5 years for coating)

    - Other specifications

    The product shall comply with the general requirements.

    On-site installation.

    Ten years spare parts list.

    Manufacturer documentation: dimensional drawings with loads, electric schemes,

    Operating and Maintenance Manual.

    Test reports.

    Certificate of compliance.

    11,1

    11,2

    MLS-ESP-024

    WASTE AIR DUCTS

    AL KHUMRA MAIN LIFT STATION PRELIMINARY DESIGN

    27/05/2010