Market leader in Indiafor protection relays,monitoring relays andalarm annunciators!
Expanding rapidly by
spreading our wingsglobally and continuouslyintroducing new product
categories!
We respondto customer feedback.
Start ing o pe rat io ns in 1965 as amanufacturer of single phasing preventors(phase failure relays), Minilec is today aleading group involved in 100% indigenousproduction, marketing and export of reliableindustrial electronic products for protection,control and monitoring.
Our insistence on quality has resulted incustomer insistence for our products. Ourcontinuous effort to introduce new featuresto enhance product performance, adapt newtechnology to bring in greater sophisticationand evolve new products in anticipation ofmarket needs gives our customers many
reasons to remain in a permanent state ofpleasant surprise
No wonder ourcustomers remain in
a permanent state of
We are Minilec
When we promise,we deliver.
We change with the changing markets;we bring in changes that change the markets.
02
pleasant surprise!
Ind
e
xTHE MINILEC GROUP 03SHAPING THE MARKETS 04
PROGRESS 05
QUALITY FOCUS 06
PRODUCTS 07CUSTOMERS 08
. . . . . .
. . .
. . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . .. . . . . . . . . . . . .
PRODUCT DETAILS
Phase Failure Relays 09 - 16
Monitoring Relays 17 - 23
CBCT 24
Motor / Pump Protection Relays 25 - 30Electronic Timers 31 - 34
Liquid Level Controllers 35 - 38
Power Line Transducers 39 - 46
Automation Products 47 - 49
Twin AC Controller 50
. . . . . . . . . . . . .
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .. . . . . . . . . . . . . . . .
. . . . . . . . . .
. . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
World's only companymanufacturing
a very wide range ofproducts in diverse
Protection, Control &Monitoring areas !
Alarm Annunciators 51-60
Variable Frequency AC Drive 65 - 67
PCB 68
72
. . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . .
. . . . . . . . . . . . . . .
Soft Starters 61 - 64
Agri Sector Product 69 - 71
Pune-the city of Minilec
7/27/2019 Mini Lec
3/72
THE MINILEC GROUPTHE MINILEC GROUPNETWORK & CUSTOMERSUPPORT
Minilec has a strong sales andservice network in the countrywhich, along with an extensivedealer network, ensuresreliable and prompt after-salesservice. We also have a widebase internationally.
03
Sri Lanka
New Zealand
Australia
Spain
Germany
Italy
France
UK
Greece
Philippines
Taiwan
HongkongVietnamOman
Saudi Arabia
Kenya
Egypt
Thailand
Malaysia
Singapore
Indonesia
Bangladesh
PakistanKuwait
BahrainUAE
Colombia
Syria
QatarJordan
U.S.A.
Nepal
Holland
CongoVenezuela
Mexico
Canada
El Salvador
South Africa
Korea
Russia
Guyana
GhanaYemen
Lebanon
Factory & Head Office
Regional Offices
Resident Engineers
China
ORGANISATION
The Minilec Group is a progress-oriented organisation incorporating five group companies. Group
companies work on niche areas to ensure an 'activity focus'. The group is very well-knit and works
together keeping the larger picture in sight.
annunciators, pre-programmed logic controllers, diesel level controllers, motor/pump protection
relays, thermistor-based winding protection relays etc.
Manufacturer of a variety of protection relays
The S-E Asia marketing wing
For export of Minilec products
Minilec (India) Pvt. Ltd.
Minilec Protective Relays Pvt. Ltd.
Minilec Electronics Pvt. Ltd.
Minilec Singapore Pte. Ltd.
Shalaka Electronics Pvt. Ltd.
A world-class manufacturer and exporter of microprocessor-based alarm
Manufacturer of Printed Circuit Board.
7/27/2019 Mini Lec
4/72
04
1965:
Firstto design and manufacture single phasing preventors in India and fulfill an emerging market requirementinnovatively.
SHAPING THE MARKETMinilec's bench-mark developments have shaped the markets since 1965.For instance, in the year 2002, responding to
customer feedback, we introduced multiple options in enclosures of relays, ( in addition to the existing D1-D2 ), P1-P2
and F3 enclosures. This product enhancement gave our customers the much needed flexibility in terms of size and
started a trend. Another interesting product development came anticipating a market need, the MBAS 9400 with front
replaceable windows, which gave us the edge to win a major tender from Indonesian Electricity Authority against
American and Japanese competitors in 1994. This updation in MBAS 9400 has also ensured a continuous flow of
orders from the Malaysian Electricity Authority since 1994.
BENCHMARK DEVELOPMENTS 1965-2007
1982:
First to launch micro-processor based alarm annunciator.(Redesigned as Microwarn 9000 in 1990), this was, and remains the most beautiful alarm annunciator attracting customers across theglobe.
1984:
First to introduce super bright LEDs for facia of alarm annunciators.
1994:First company in our segment to get ISO 9001.
1997:
First company to introduce RS232 communication port to alarm annunciators.
2000:
Millennium Series (P1 & P2 enclosures)products launched
2005:
MBAS 9700 expanded up to 128 channels.
2006:Microcontroller based relaysreplacing existing relays (D1 & D2 series) introduced.
2007:
S2 (Sleek) Series products with microcontroller & SMD technologylaunched.This technology has the powerful advantage of added intelligence. State of art SMD technology & microprocessor based designgives higher reliability, multi purpose functionality, reduced size & more value.
2007-08:
Innovative and upgraded new products with latest technology arepoised to change the face of the emerging market in India and abroad.
1987:
First to launch prodless dry run protection device pump guard.This innovation alone, won usseveral new customers globally.
7/27/2019 Mini Lec
5/72
05
40,000 sq.ft Premiseslocated in clean, green and environment friendly location atPirangoot Industrial Estate near Pune, includes 10,000 sq.ft ofrecent addition.
Innovative designs are made here.
200+ EmployeesHighly qualified engineers, R&D experts, quality controltechnicians and administrative staff; all very well-trained toensure high quality results.
Manufacturing facility to caterever-growing customer demands
Sophisticated R&D laboratory Well-calibrated testing equipments
PROGRESS Every small change or a big expansion that serves the customer betteris progress. To us at Minilec, one more pleasant surprise for ourcustomers is progress.This progress is evident in every area, be it figures of turnover andexports or developments in infrastructure, products and R&D.
INFRASTRUCTURE
7/27/2019 Mini Lec
6/72
06
QUALITY SYSTEMS
Stringent quality checks by carefully selected
vendors, extensive inward inspection and proven
production processes continuously improve
product quality at Minilec. Minilec's Quality
Systems are verified by BVQI to be as per ISO
9001-2008 requirement of international quality
standards.
The products are also thoroughly type tested at
reputed test houses in India, Singapore, Malaysia
and Russia as per the IEC standards.
ACCREDITATIONS
The Models of phase failure
relays and alarm annunciators
c a r r y C E m a r k , C S A
Certification, RoHS and ABS
QUALITY FOCUS
YEARS
WARRANTY!
5YEARSWARRANTY!
5All Minilec alarm
annunciators carry a
5 years' warranty.
'Timely supply ofreliable products
with innovative featuresfor customer satisfaction.'
Quality Policy of Minilec
008
IEC Standards Compatible1) IEC 610002) IEC 60255
7/27/2019 Mini Lec
7/72
07
20 %
10 %
5 %
20%15%
15 %Air Conditioning& Refrigeration
Farm IrrigationWater Supply& Sewerage
Process Industry
10 %
Material Handling
5%
Power Generation,Transmission & Distribution
Telecommunication
Machinery & Equipments
THOROUGH APPROACH TO PRODUCT RELATED EDUCATIONWe update our customers & dealers about our latest product range andbreakthrough technology through various seminars, training sessionsand regular product literature . This ensures optimum utilization of thelatest features and technology used in products.
PRODUCTS
Omnipresence of our productsacross agro and industrial sectors.
WIDEST RANGE
Minilec is the only company
in the world offering thewidest range of products inall three product segmentsviz. protection, control andmonitoring.
Our products cater to everyagro. and industrialsegment and provide forthe needs of small scaleindustries as well ascorporate giants likeSiemens and Reliance.
TREND-SETTING DESIGNSOur product designs today set the
trends for the markets in India.Minilecs quality is a standard thateven competitors aspire for. Ourproducts are approved by leadingindustrial project consultants.Growing demand for our productsworld-wide is a proof of customeracceptance for our productsglobally. Our products are rated as'being the best' on the threecriteria of Quality, ProductFeatures and Delivery Schedules.
PRODUCT CATEGORIES
Phase Failure Relays
Voltage / Current / Frequency /Power Monitoring RelaysMotor/Pump Protection Relays
Level Controllers Timers Alarm Annunciators Power Line Transducers &
Multifuction Meter Pump Automation Products Soft Starters Process & Plant Controllers
Variable Frequency AC DrivePrinted Circuit Boards
SECTOR DIVERSIFICATION
7/27/2019 Mini Lec
8/72
08
T M
Minilecs customers span a wide spectrum of
segments and scale.
Repeat orders from customers for decades is a very
big confirmation of customer delight with our
products.
SIEMENS
CromptonGreaves
li
BLUE STAR
OHPC
CUSTOMERS
Turnover hasshown a steady
increase. Even intimes of marketlows, Minilec has
never found itdifficult to keep agrowing turnover
trend.
Yearly Sales Growth
Turnoverin
INR
x100,0
00
200
400
600
800
1000
1200
1400
1600
1800
20002200
2400
2600
2800
Growing turnover is also an index of productreliability & increasing customer satisfaction.
3000
3200
10.50
10.00
9.50
9.00
8.50
8.00
7.50
7.00
6.50
6.00
5.50
5.00
4.50
4.00
3.50
3.00
2.50
2.00
1.50
1.00
0.50
0.0
Million $
UNDETERRED GROWTH
3400
3600
3800
84-85
8-6
5
8
8 -7
68
88-89
8-0
9
9
9 -1
09
91-92
9 -3
29
9
4
3-9 94-
9595
-96
9 -7
69
9-8
7
9
98-99 -
99
00
0-01
0 01-02
023-003
4-0
0
045-005
-06
06-07
8-8
7
8
07-08
09-10
4000
4200
EXPORTS :
Exports rose steadily in the initial years, and are now
showing a rapid growth fueled by a very encouraging
reception of our products globally. Minilec has traditionally
exported to S.E. Asia, Europe and the Middle-East.
Exports to North and South America are now increasing
substantially.
5.0
5.5
Tu
rnoverin
US$
x100,0
00
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
0.0
05-06
07-08
03-04
00-01
98-99
95-96
93-94
6.0
6.5
7.0
7.5
8.0
09-10
8.5
7/27/2019 Mini Lec
9/72
These relays are suitable for monitoring incoming 3-phase supply from Mains (Electricity distributionline). Being independent of load, they can be used forany HP/KW rating of load.
MODELS
VSP D1, VSP D2, VPG D1, USP D1P1 PFS1, P1 PFS2, P2 PFS1
S2 VMR1, S2 VMR2, S2 VMR3, S2 VMR6, S2 VMR8D1 HLS1, HLV D2, ALV D2, VMR D2, VST D1,D1 VMR1, D2 VMR1, D2 VMR2,S1 VMR7, F3 VSR4
Ordering Instructions
Product Family Name
Model Name
System Supply Voltage
& Frequency
Aux. Supply / Control
supply voltage
09
PHASE FAILURE RELAYS
FEATURES Fixed/adjustable unbalance settings Fixed/adjustable under-
voltage/over-voltage settings
Fixed/adjustable trip delays Built-in or external power supply Resetting Auto / Manual / Remote Output contacts: 1 CO or 2 CO Choice of enclosures (DIN-Rail,
Plug-in) Models with Micro-Controller based
design 2 Line Alpha-Numerac LCD display
(For F3 VSR4 model) Serial Communication (RS 232) Port
(for F3 VSR4 model)
Use of SMD Technology User-friendly LED indications
PROTECTIONS / FUNCTIONS Phase Failure (Phase Loss / Single
Phasing),
Phase sequence reversal,
Voltage Unbalance,
Under Voltage,
Over Voltage
Dry Run
7/27/2019 Mini Lec
10/72
7/27/2019 Mini Lec
11/72
7/27/2019 Mini Lec
12/72
Phase Failure, Unbalance,Phase Sequence, under voltage,Over Voltage, Manual reset,Fixed Unbalance setting,Adjustable UV/OV settings,2 CO output relay
HLV D2
Wherever not specifiedContact Rating :5A @ 230 V AC(resistive)
* CE marked productsavailable on request.
12
Trip Time Delay
On Phase Failure
On UV/OV
Resetting Mode
Weight
Dimensions (mm)
Overall (L x W x D)
Mounting (L x W)
P H A S E F A I L U R E R E L A Y S
Phase Failure with UV / OV Relay
Supply Voltage
System
Auxiliary
Output Contacts
Trip Setting (Volts)
Phase Sequence
Phase Unbalance
3 Ph
AuxSupply
R Y B R B R Y R Y BB
Unbal./
Phase Fail
Td : 2-5 Sec.
UVOV
1613 1714
1815 1613
R
Y
B
N/VOFF ON
DOL STARTER
L1
L2
L3MOTOR
2
14
8
1
13
7
3
15
9
AUX.SUPPLY
4
16
10
5
17
11
6
18
12
HLV D2
Microcontroller design,SMD Technology,Phase Failure, Unbalance,Phase Sequence, under voltage,Over Voltage, Auto reset,Fixed Unbalance setting,Fixed UV/OV settings,2 CO output relay
100-110-120 / 220-230-240 / 380-415-440V AC -25+20%,48-63 Hz, Selectable by Front Knob
Built In (from 3 Phase)
2 CO
Yes
10% (Fixed) 10%
2 - 5 Sec. (Fixed) / RP-Instant
Auto Reset100 gms (Approx.)
90 X 35 X 60
35 mm Rail Mounting
107
107 129
3 Ph
118
Td : 2-5 Sec.
Td : 2-5 Sec.
UV
OV
Unbalance /
Phase fail
R Y B R Y R B Y
RYB
M
20% (Fixed)
For 380-440V ACFor 220-240V ACFor 100-120V AC
UnderVoltage
OverVoltage
For 380-440V ACFor 220-240V AC
For 100-120V AC
Relay contact position shown in Power off' condition
Phase Failure, Unbalance,Phase Sequence, Auto Reset,Fixed Unbalance Setting,1 CO output relay conntacts
110 V (Fixed) or (220-230-240) or (380-415-440) VAC
Phase Failure Relay
S2 VMR2Phase Failure Relay
USP D1
415 VAC 20%, 50 Hz 3%
Built In
1 CO
Yes
60 V 6 V (fixed)
3.5 sec. 1.5 sec.
Auto Reset100 gms (Approx.)
76 x 30.5 x 117.5
68 centre to centre / 35 mm rail Mounting
3.5 secs. 1.5 sec
Less than 2 secs. for OV & 2 - 5 secs for UV
Manual / Remote
430 gms.
76 x 56.5 x 117.5
67 x 46 / 35 mm rail Mounting
110 / 240 / 380 / 415 / 440 V AC 20% 50 / 60 Hz
2 CO
Yes
40 V 6 V (fixed)
80% to 95% (adjustable)
105% to 120% (adjustable)
C US
R
Note: S2 Series - RoHS Product available on request.CE marked HLV D2, ALV D2, VMR D2 available on request.
R
Y
B
USP D1
1 3
3 Ph
12
R Y B R Y R B Y
Td : 2-5 Sec.
R Y B
Phase Fail
7/27/2019 Mini Lec
13/72
Phase Failure, Unbalance,Phase Sequence, under voltage,Over Voltage, Auto Reset,Fixed Unbalance setting,Adjustable UV/OV settings,2 CO output relay
Phase Failure, Unbalance,Phase Sequence, under voltage,Over Voltage Auto Reset,Fixed Unbalance setting,Adjustable UV/OV settings,2 CO output relay
R
Y
B
N/VOFF ON
DOL STARTER
L1
L2
L3MOTOR
2
14
8
1
13
7
3
15
9
AUX.SUPPLY
4
16
10
5
17
11
6
18
12
ALV D2
3 Ph
AuxSupply
R Y B R B R Y R Y BB
Unbal./
Phase Fail
Td : 2-5 Sec.
UVOV
1613 1714
1815 1613
3 Ph
AuxSupply
R Y B R B R Y R Y BB
Unbal./
Phase Fail
Td : 2-5 Sec.
UVOV
1613 1714
1815 1613
ALV D2Phase Failure with UV / OV Relay
13
Phase Failure with UV / OV Relay
S2 VMR6
P H A S E F A I L U R E R E L A Y S
10 V (Fixed) or (220-230-240) or (380-415-440) VAC 20% selectable
Phase Failure, Unbalance,Phase Sequence,Under Voltage, Over Voltage,Auto Reset, Fixed UnbalanceSettings, Adjustable UV/ OVSettings, Neutral Fail, 2 CO
3.5 secs. 1.5 sec
Less than 2 secs.
Auto Reset400 gms.
76x 56.5 x 117.5
67 x 46 / 35 mm rail Mounting
2 CO
Yes
40 V 6 V (fixed)
80% to 95% (adjustable)
105% to 120% (adjustable)
110 / 240 / 380 / 415 / 440 V AC 20% 50 / 60 Hz
R
Y
B
N/VOFF ON
DOL STARTER
L1
L2
L3MOTOR
2
14
8
1
13
7
3
15
9
AUX.SUPPLY
4
16
10
5
17
11
6
18
12
VMR D2
3.5 secs. 1.5 sec
Less than 2 secs.
Auto Reset400 gms.
76x 56.5 x 117.5
67 x 46 / 35 mm rail Mounting
2 CO
Yes
94 V 6 V (fixed)
80% to 95% (adjustable)
105% to 120% (adjustable)
110/220/230/240/380/415/440 V AC 20% 50/60 Hz
VMR D2Phase Failure with UV / OV Relay
Relay contact position shown in 'Power off' condition
Note: Product available on request - P2 PFV1, P2 SMV1
5 sec. 1 sec for UB/SP/UV/OV, Instant for RP,
Less than 2 secs. for NF.
Auto Reset110 gms.
90 x 35 x 60
35 mm rail mounting
2 CO
Yes
94 V 6 V ph- ph (fixed)
75% to 95% of 415 VAC
105% to 125% of 415 VAC
415 V AC 20%
Built-In
ON
OFFN/V
N
B
R
Y
S2 VMR6
107
107 129
3 Ph-N
118
Td : 5 Sec.
Td : 5 Sec.
UV
OV
Unbalance /Phase fail
R Y B N R Y R B Y N
T On
5 Sec.
R Y B N
T On
5 Sec.
110/220/230/240/380/415/440 V AC 20% 50/60 Hz
7/27/2019 Mini Lec
14/72
Wherever not specifiedContact Rating :5A @ 230 V AC(resistive)
14
Supply Voltage
System
Auxiliary
Output Contacts
Trip Setting (Volts)
Phase Sequence
Phase Unbalance
Trip Time Delay
On Phase Sequence
On SP/UV/OV
Resetting Mode
Weight
Dimensions (mm)
Overall (L x W x D)
Mounting (L x W)
P H A S E F A I L U R E R E L A Y S
For 380-440V ACFor 220-240V ACFor 100-120V AC
UnderVoltage
OverVoltage
For 380-440V ACFor 220-240V AC
For 100-120V AC
Note: S2 Series - RoHS Product available on request.
Phase Failure Relay
S2 VMR8
Phase Failure, Phase Sequence,under voltage, Auto Reset,Adjustable trip delay,Adjustable UV setting,1 CO output relaySelectable range of supply
voltage
R
Y
B
2
14
8
1
13
7
3
15
9
N/VOFF ON
DOL STARTER
L1
L2
L3
VST D1
MOTOR
VST D1Phase Failure with Under Voltage
300 gms.
76 x 30.5 x 117.5
68 centre to centre / 35 mm rail Mounting
Auto
240 / 415 / 575 V AC 3 Phase (15% selectable)Built-in
1 CO
Yes
80% of V set
N.A.
N.A.
0.2 - 10 secs. (same for UV & SP)
13
13 15
3 Ph
14
UVPhase fail
R Y B R Y R B Y
Td :0.2-10 Sec.
D1 HL S1Phase Failure with UV / OV Relay
3.5 1.5 secs. [Fixed]
200 gms.
76 x 30.5 x 117.5
68 centre to centre / 35 mm rail Mounting
Auto
100-110-120/220-230-240/380-415-440V AC+20,-25%,48-63 Hz,
Built-in Selectable by Front Knob
2 CO
Yes
75% of system supply (Fixed)
10% (Fixed)
Less than 2 secs.
120% of system supply (Fixed)
Phase Failure, Unbalance,Phase Sequence,under voltage, Over Voltage,Auto reset, Fixed Unbalancesetting, Fixed UV/OV settings,2 CO output relay
113
113 315
3 Ph
214
Td : 3.5 Sec.
UV
OV
Unbalance /Phase fail
R Y B R Y R B Y
Relay contact position shown in Power off' condition
Phase Failure, Unbalance,Phase Sequence,Under Voltage, Over Voltage,Auto Reset, Fixed UnbalanceSettings, Fixed UV/ OVSettings, 2 CO
2 - 5 sec. fixed for UB/SP/UV
150 gms.
110 x 35 x 60
Screw Mounting
Auto Reset
415 V AC 20%Built-In
2 CO
40 V 4 V (10 % 10% of set value-fixed)
85% of 415 V AC (fixed)
Instant for RP/OV
110 % of 415 V AC (fixed)
Yes
ON
OFFN/V
B
R
Y
S2 VMR8
L3 L2 L1
18 1 6 1 5 2 8 2 6 25
L
O
A
D
D1 HLS1
63
63 52
3 Ph
41
Td2-5Sec.
UV
OVR Y B R Y R B Y
T On180Sec.
R Y B
T On
R Y B
T On
Unbalance /Phase fail
7/27/2019 Mini Lec
15/72
Relay contact position shown in 'Power off' condition
Note: Product available on request - P2 PFV1, P2 SMV115
P H A S E F A I L U R E R E L A Y S
Phase Failure, Unbalance,Phase sequence, Under & Overvoltage, Auto Reset,fixed unbalance setting,Adjustable UV/OV settings,fixed trip delay,
2 CO output relay
D1 VMR1Phase Failure with UV / OV Relay
L
O
A
D
DOL STARTER
113
113 315
3 Ph
214
Td : 3.5 Sec.
UV
OV
Unbalance /Phase fail
R Y B R Y R B Y
3.5 secs 1.5 sec.
3.5 secs 1.5 sec.
430 gms.
76 x 30.5 x 117.5
68 centre to centre / 35 mm rail Mounting
Auto
100-120/220-240/380-440 VAC ire20%, 3Ph-3W
Built-in
2 CO
Yes
10% (fixed)
285-425V AC [Variable]165-225V AC [Variable]75-115V AC [Variable]
400-520V AC [Variable]230-290V AC [Variable]
105-140V AC [Variable]
Suitable for 3 Ph-3W system,Microcontroller design,Absolute values of UV/OV settings,Phase Failure, Unbalance, PhaseSequence, under voltage, Over Voltage,Auto/Manual reset, Adjustable settingsfor Unbalance, UV/OV and trip delays,2 CO output relay
D2 VMR 1Phase Failure with UV / OV (3-3W)
100-120 / 220-240 / 380-440V AC -25%+20%, 48-63 Hz
Built In (from 3 Phases)
2 CO
4 % - 20 % [Variable]
285-425V AC [Variable]165-225V AC [Variable]75-115V AC [Variable]
Yes
1 To 10 Sec [Variable)
Auto/ Manual Reset (External NC Push Buttons)
300 gms.
76 X 56.5 X 117.5
67 x 46 / 35 mm rail Mounting
400-520V AC [Variable]230-290V AC [Variable]
105-145V AC [Variable]
Instant
C US
R
1613
1613 1815
3 Ph
1714
Td : 1-10 Sec.
Td : 1-10 Sec.
UV
OV
Unbalance /Phase fail
R Y B R Y R B Y
L
O
A
D
MANUALRESET
PB
R
Y
B
D2 VMR 1
Suitable for 3 Ph-4W system,Microcontroller design,Absolute values of UV/OV settingsPhase Failure, Unbalance, PhaseSequence, under voltage, Over VoltageAuto/Manual reset, Adjustable settings forUnbalance, UV/OV and trip delays,2 CO output relay
D2 VMR 2Phase Failure with UV / OV (3-4W)
100-120 / 220-240 / 380-440V AC -25%+20%, 48-63 Hz
Built In (from 3 Phases)
2 CO
4 % - 20 % [Variable]
165-245V AC [Variable]95-135V AC [Variable]45-65V AC [Variable]
Yes
1 To 10 Sec [Variable)
Auto/ External Manual Reset (External NC Push Buttons)
300 gms.
76 X 56.5 X 117.5
67 x 46 / 35 mm rail Mounting
230-310V AC [Variable]130-170V AC [Variable]
60-80V AC [Variable]
Instant
C US
R
1613
1613 1815
3 Ph N
1714
Td : 1-10 Sec.
Td : 1-10 Sec.
UV
OV
Unbalance /Phase fail
R Y B R Y R B Y
L
O
A
D
MANUALRESETPB
R
Y
B
N
D2 VMR 2
7/27/2019 Mini Lec
16/72
Wherever not specifiedContact Rating :5A @ 230 V AC(resistive)
16
Supply Voltage
System
Auxiliary
Output Contacts
Trip Setting (Volts)
Phase Sequence
Phase Unbalance
Trip Time Delay
On Phase Sequence
On SP/UV/OV
Resetting Mode
Weight
Dimensions (mm)
Overall (L x W x D)
Mounting (L x W)
P H A S E F A I L U R E R E L A Y S
UnderVoltage
OverVoltage
Note: S2 Series - RoHS Product available on request.
Microcontroller design,SMD Technology,Absolute values of UV/OV settings,Phase Failure, Unbalance, PhaseSequence, under voltage, Over VoltageAuto/Manual reset, Adjustable settingsfor Unbalance, UV/OV and trip delays,2 CO output relay
S2 VMR 3Phase Failure with UV / OV Relay
100-120 / 220-240 / 380-440V AC -25%+20%, 48-63 Hz
Built In (from 3 Phases)
2 CO
4 % - 20 % [Variable]
105-145V AC [Variable]
230-290V AC [Variable]400-520V AC [Variable]
Yes
1 To 10 Sec [Variable)
Auto/ Manual Reset [Selectable]
110 gms (Approx.)
90 X 35 X 60
35 mm Rail Mounting
165-225V AC [Variable]285-425V AC [Variable]
75-115V AC [Variable]
Instant
C US
R
Relay position shown in 'Power off' condition
F3 VSR4Voltage Scanner [3 Ph 3 W/ 4 W]
For 380-440V ACFor 220-240V ACFor 100-120V AC
For 380-440V ACFor 220-240V AC
For 100-120V AC
415 V AC + 20%,-30% (3 Ph-3 W or 3 Ph-4 W selectable)
90-270 V AC/DC, 50 Hz/ (60 Hz) 3%
2 CO & RS 232 (optional)
1 - 20 % (Adjustable)
1 - 25V below nominal voltage (for 3 Ph. 4 W)1 - 60V above nominal voltage (for 3 Ph. 3 W)
Yes
1 - 59 secs. or 1-5 mins Selectable
Auto/ Manual Reset [Selectable]
800 gms
96 x 96 x 130
92 x 92 mm
1 - 50V below nominal voltage (for 3 Ph. 4 W)1 - 80V below nominal voltage (for 3 Ph. 3 W)
3.5 1.5 sec.
RS232
NO1C1 NC1 NO2C2 NC2
BYR
SYSTEM SUPPLY
N +VE VEAUX. SUPPLY
90-270 VAC/DC
T1 = POWER ON DELAY T2 = TRIP DELAY
RELAY
C - N O
LED
LINE
RESET RESET RESET RESET
UB>SET R.P.
RESET
OVSET
UVSET
OV UV UB/SP UB/SP UB/SP
B Y R
S.P.
UVT2 T2 T2
T1
OV HYST.
UV HYST.
R
Y
B
107
107 129
3 Ph
118
Td : 1-10 Sec.
Td : 1-10 Sec.
UV
OV
Unbalance /Phase fail
R Y B R Y R B Y
3-Phase 3-Wire or 3-Phase 4-Wire voltagemonitoring & display, Phase Failure, Unbalance,Phase Sequence, under voltage, Over Voltage,Auto / Manual Reset, Adjustable unbalance tripsetting, Adjustable under/over voltage settings,adjustable trip delay, RS232 communication port,
2 CO output relay, True RMS Values
7/27/2019 Mini Lec
17/72
MONITORING RELAYS
Ordering Instructions
Product Family NameModel Name
System Supply Voltage& frequencyAux. Supply/Controlsupply voltageCurrent input (1A or 5A)
FEATURES Fixed/adjustable under/Over trip
settings for parameters. Fixed/adjustable trip delays and Power
On delays Built-in or external power supply Resetting Auto or Manual Output contacts : 1 CO or 2 CO Choice of enclosures (DIN-Rail, Flush) Models with Micro-Controller based
design Use of SMD Technology User-friendly LED indications
These relays are best suitable for monitoringbalanced or unbalanced supplies, either of singlephase, 3-phase 3-wire or 3-phase 4 wire loadspowered by generators, UPS, stabilizers, inverters,
or Mains (by Electricity Boards / Utilities); in AMFpanels, PCCs, distribution boards and for powermonitoring of individual loads / motors / pumps.
MODELS
D1 VCR1, D1 VCR2VCT D2,VCF D2, D2 VCT1, D1 VCT1,S2 VMR 4, S2 VMR 5,D2 EFR1, OCS D1,S2 CMR2, S2 CMR3, S2 CMR4,OFS D1, S2 FMR1,RPT D2, RPF D2, CBCT
17
PROTECTIONS / FUNCTIONS Under/over Voltage, Under/Over Current Under/Over Frequency
Reverse Power Earth Fault/Ground Fault Earth leakage
7/27/2019 Mini Lec
18/72
V O L T A G E M O N I T O R I N G R E L A Y S
18
System Supply
Output Relay Contact
Trip Setting
Under Voltage
Over Voltage
Trip Time Delay
Power on Delay
Reset
Weight
Dimensions (mm)
Overall (L x W x D)
Mounting
Wherever not specifiedContact Rating :5A @ 230 V AC(resistive)
110/240/380/415/440 V AC +20%, 25% 50/60Hz
1613
1613 1815
1714
3 Ph
T on1 to 10sec.
OV SET
UV SET
OV RESET
UV RESET
TD1 to 10sec. TD
D1 VCR 1 D1 VCR 2
2 CO
3-Phase 4-Wire Under& Over voltageAuto/Manual Reset,Adjustable under/overvoltage settings,adjustable trip delay &ON delay,
2 CO output relay
L
O
A
D
N/VON
OFF
R
Y
B
N
2
8
1
7
3
9
4
10
5
11
6
1413 15161718
12
VCF D2
A/M
LINK
75% - 95% (adjustable)
105% -120% (adjustable)
1-10 secs. (adjustable)
1-10 secs. (adjustable)
Auto / Manual
450 gms.
76 x 56.5 x 117.5
67 x 46 / 35 mm railmounting
VCF D2Voltage Monitoring
Relay, 3-4W
2 CO
75% - 95% (adjustable)
105% -120% (adjustable)
1-10 secs. (adjustable)
1-10 secs. (adjustable)
Auto / Manual
450 gms.
76 x 56.5 x 117.5
3-Phase 3-Wire Under& Over voltageAuto/Manual Reset,Adjustable under/overvoltage settings,adjustable trip delay &ON delay,
2 CO output relay
67 x 46 / 35 mm railmounting
VCT D2Voltage Monitoring
Relay, 3-3W
L
O
A
D
N/VON
OFF
2
8
1
7
3
9
4
10
5
11
6
141 3 1 51 61 71 8
12
VCT D2
A/M
LINK
R
Y
B
Single Phase Under &Over voltage, Auto Reset,Adjustable under / overvoltage settings, 2 COoutput relay.
113
113 315
214
1 Ph N
OV SET
UV SET
OV RESET
UV RESET
TD 2 to 5sec. TD
220/230/240 V AC (+20%-30%), 50/60 Hz 3%
2 CO
75 - 95% [Variable] of set value
105 - 120% [Variable] of set value
2- 5 Sec (Fixed) (UV/OV)
Auto Reset
180 gms.
76 x 30.5 x 117.5
68 mm centre to centre / 35 mm railmounting
1 Phase VoltageMonitoring Relay
ON
N/V
OFF
2
14
8
1
13
7
3
15
9
D1 VCR1
L
N
LO
AD
D1 VCR1
Relay contact position shown in 'Power off' condition
1 Phase VoltageMonitoring Relay
220/240 VAC,(+20%,-25%)50/60 Hz3%
2 CO
165 V to 225 V (in step of 15) (2%)
230 V to 290 V (in step of 15) (2%)
3.5 sec. (1.5 sec.)
Auto Reset
180 gms.
76 x 30.5 x 117.5
68 mm centre to centre / 35 mm railmounting
3 min.( 20 sec)
Single Phase Under &Over voltage,Auto Reset,Adjustable under/overvoltage settings,2 CO output relay
ON
2
14
8
1
13
7
3
15
9
N/V
OFF
D1 VCR2
L
N
LOAD
P.ON
DLY= 180 Sec.
Reset
DLY=
180 Sec.
Reset
DLY=
180 Sec.
TRIPDLY2 to 5Sec.
7/27/2019 Mini Lec
19/72
19
V O L T A G E M O N I T O R I N G R E L A Y S
Ph Ph Sensing:
For 380-440V AC 400-520V AC (Variable)
For 220-240V AC 230-290V AC (Variable)
For 100-120V AC 105-145V AC (Variable)
Ph N Sensing:
For 380-440V AC 230-310V AC (Variable)For 220-240V AC 130-170V AC (Variable)
For 100-120V AC 60-80V AC (Variable)
105-145V AC (Variable)
230-290V AC (Variable)
400-520V AC (Variable)
230-310V AC (Variable)130-170V AC (Variable)
60-80V AC (Variable)
Ph Ph Setting:
For 380-440V AC 285-425V AC (Variable)
For 220-240V AC 165-225V AC (Variable)
For 100-120V AC 75-115V AC (Variable)
Ph N Sensing:
For 380-440V AC 165-245V AC (Variable)
For 220-240V AC 95-135V AC (Variable)
For 100-120V AC 45-65V AC (Variable)
75-115V AC (Variable)
165-225V AC (Variable)
285 - 425V AC (Variable)
165-245V AC (Variable)
95-135V AC (Variable)
45-65V AC (Variable)
R
Y
B
3-Phase 3-Wire Under & Overvoltage, Microcontroller baseddesign, SMD TechnologyAuto/Manual Reset, , Adjustableunder/over voltage settings,Absolute values for UV/OV,adjustable trip delay & ON delay,2 CO output relay (or selectable1CO for UV, 1CO for OV)Failsafe-non-failsafe selectable
100-120/220-240/380-440V AC -25%+20%,48-63 Hz
1 CO + 1 CO / 2 CO
1-10 Sec. (Variable)
1-10 Sec (Variable)
Auto / Manual Reset
110 gms (Approx.)
90 X 35 X 60
35 mm Rail Mounting
S2 VMR4Voltage Monitoring
Relay, 3-3W
107
107 129
118
3 Ph
T on1 to 10sec.
OV SET
UV SET
OV RESET
UV RESET
TD1 to 10sec. TD
C US
R
S2 VMR5
3-Phase 4-Wire Under & Overvoltage, Microcontroller baseddesign, SMD Technology, Auto /Manual Reset, Adjustableunder/over voltage settings,Absolute values for UV/OV,adjustable trip delay & ON delay,2 CO output relay (or selectable1CO for UV, 1CO for OV)Failsafe-non-failsafe selectable
100-120/220-240/380-440V AC -25%+20%,48-63 Hz
1 CO + 1 CO / 2 CO
1-10 Sec. (Variable)
1-10 Sec (Variable)
Auto / Manual Reset
110 gms (Approx.)
35 mm Rail Mounting
Voltage MonitoringRelay, 3-4W
C US
R
107
107 129
118
3 Ph N
T on1 to 10sec.
OV SET
UV SET
OV RESET
UV RESET
TD1 to 10sec. TD
R
Y
B
N
OFF
90 X 35 X 60
3-Phase 3-Wire and 3-Phase4-Wire (selectable) Under & Overvoltage, Microcontroller baseddesign, Auto/Manual Reset,Adjustable under/over voltagesettings, Absolute values forUV/OV, adjustable trip delay &ON delay, 2 CO output relay (orselectable 1CO for UV, 1CO for OV)Failsafe-non-failsafe selectable
100-120/220-240/380-440V AC -25%+20%,48-63 Hz
1 CO + 1 CO / 2 CO
1-10 Sec (Variable) UV/OV/NF
1-10 Sec (Variable)
Auto/ Manual Reset
300 gms (Approx.)
76 X 56.5 X 117.5
67 x 46 / 35 mm rail mounting
D2 VCT1Voltage Monitoring
Relay
1613
1613 1815
1714
3 Ph N
T on1 to 10sec.
OV SET
UV SET
OV RESET
UV RESET
TD1 to 10sec. TD
N
L
O
A
D
D2 VCT1
100-120/220-240/380-440 V AC
2 CO
3.5 .5 (UV/OV)1 Sec
Auto Reset
200 gms. (Approx).
76 x 30.5 x 117.5
3-Phase 3-Wire Under& Over Voltage,Auto reset,Adjustable UV/OVsettings,fixed trip delay,2 CO output relay.
D1 VCT1Voltage Monitoring
Relay, 3-3W
165-225 Unit of 220-240 V AC285-425 Unit of 380-440 V AC
75-115 Unit of 100-120 V AC
105-145 Unit of 100-120 V AC230-290 Unit of 220-240 V AC400-520 Unit of 380-440 V AC
LOAD
DOL STARTER
3 Ph
OV SET
UV SET
OV RESET
UV RESET
TD3.5 sec.
TD
113
13 315
214
68 centre to centre / 35 mm railmounting
Relay position shown in Power off condition
3 or 4 Wi r eselectionlink
C US
R
Note: S2 Series - RoHS Product available on request.
7/27/2019 Mini Lec
20/72
20
Supply Voltage
System
Auxiliary
Ext. Input
Output contact
Trip setting
Under Current
Over Current
EF Trip Setting
Wherever not specifiedContact Rating :5A @ 230 V AC(resistive)
Power On Delay
Trip Time Delay
Resetting
Weight
Dimensions (mm)
Overall (L x W x D)
Mounting (L x W)
C U R R E N T M O N I T O R I N G R E L A Y S
1 CO
N.A.
50% -140% (adjustable) of CT sec
1 Amp / 5 Amp (Secondary) CT or 250/500 mA
3.5 secs 1.5 sec (fixed)
1 - 10 secs (adjustable)
Auto
250 gms.
76 x 30.5 x 117.5
68mm centre to centre / 35mm rail Mounting
OCS D11 Phase Over Current Relay
Aux. Supply
OC SetPointOC Reset
T ON2 to 5 sec. Td -
13
13
14
15
1 to 10 sec.
Current Input
2
14
8
1
13
7
3
15
9
OCS D1
N/V
DOL STARTER
OFFON
LO
AD
L
N
AUX.
SUPPLY
Single phase over current Auto reset,Input 1A or 5 A through CT,Adjustable over current trip settings,Adjustable trip delay,1 CO output relay
110-120/220-240/380-440 V Ac12 V DC/24/30 V DC10%
20%,
1 CO + 1 CO
50% - 140% (Variable)
10% - 100% (Variable)
100-120 / 220-240 V AC 20%,24 V DC 10%1 Amp / 5 Amp (Secondary) CT
1-10 Sec. (Adjustable) 1 Sec.
1-10 Sec. (Adjustable) 1 Sec.
Auto / Manual
140 gms
90 X 35 X 60
35 mm Rail Mounting
S2 CMR21 Phase Current Monitoring Relay
Aux. Supply
OC SetPoint
UC SetPoint
OC Reset
UC Reset
AUTO
T ON1 to 10 sec. Td -
RESET
10
10
7
7
11
12
8
9
1 to 10 sec.
Current Input
Single phase under & over currentMicrocontroller based design, SMD technology,Auto/Manual reset, Input 1A or 5 A through CT,Adjustable under / over current trip settings,adjustable trip delay & ON delay,2 CO output relay (or selectable 1CO for UC,1CO for OC)
Failsafe-non-failsafe mode selectable
Relay contact position shown in 'Power off' condition
C US
R
Note: S2 Series - RoHS Product available on request.
7/27/2019 Mini Lec
21/72
21
G R O U N D F A U L T M O N I T O R I N G R E L A Y S
Earth fault/Ground fault monitoring of3 phase systemsManual Reset,Input 1A or 5A through CBCT,Adjustable earth fault trip setting,adjustable trip delay,2 CO relay output
24-30 VDC / 110-240 V AC / DC / 380-440 V AC 20%
1A or 5A (Selectable) CBCT Secondary
1 CO (2 CO) (Pick up on Fault)
N.A.
10% -100% (adjustable) of CT sec
N.A.
0.1-1.0 / 1-10 Sec. (Adjustable)
Manual/ Remote (Selectable)
550gms.
76 x 56.5 x 117.5
67 x 46 / 35 mm rail Mounting
N.A.
D2 EFR1Earth Fault Relay
Td
13
13
15
14
16
16
18
17
Td
*Use either3 x 5A Ext. CTs
or 3 x 1A Ext. CTsor 1 x 5A (or 1A) CBCT
R
N / VOFF ON
M
D2 EFR1
13 14 15 161 718
YB
MOTOR
EXTERNAL5 Amp. CT. CBCT ( ZCT)
Earth fault/Ground fault monitoring of3 phase systems, Microcontroller baseddesign, SMD technology, Manual Reset,Input 1A or 5A through CBCT,Adjustable earth fault trip setting,Adjustable trip delay & ON delay,2 CO relay output
Failsafe-non-failsafe selectable
100-120/220-240/380-440 V AC 20%, 48-63 Hz
2 CO
100-120/220 -240 V AC / 24V DC 20%
10% - 100% of Rated Current Input (Variable)(Input through CT of 1AMP or 5AMP Secondary)
0.1 - 1 Sec.(Adjustable)
1 -10 Sec.(Adjustable)
Manual
140 gms
90 X 35 X 60
35 mm Rail Mounting
S2 CMR3Ground Fault Relay
N.A.
N.A.
C US
R
Earth leakage monitoring of 3 phasesystems, Microcontroller based design,SMD technology, Manual Reset,Input through CBCT,Adjustable trip setting,Adjustable trip delay & ON delay,2 CO relay output
Failsafe-non-failsafe selectable
100-120/220-240/380-440 V AC 20%, 48-63 Hz
2 CO
100-110/240V AC / 24V DC 20%
10% - 100% of Rated Current Input (Variable)(Input through CBCT of 300m A Secondary)
0.1 Sec to 1 Sec.(Adjustable)
1 -10 Sec.(Adjustable)
Manual
140 gms
90 X 35 X 60
35 mm Rail Mounting
S2 CMR4Earth Leakage Relay
N.A.
N.A.
54 6
1110 12
21 3
S2 CMR 4
AUX.SUPPLY
87 9
R
N/V
OFF ON
YB
CBCT (ZCT) With Secondary of 300 mA only
M
C US
R
Relay contact position shown in 'Power off' condition
*Use either3 x 5A Ext. CTs
or 3 x 1A Ext. CTsor 1 x 5A (or 1A) CBCT
Note: S2 Series - RoHS Product available on request.
EXTERNAL5 Amp. CT.
1A or 5A (Selectable) CBCT Secondary 300mA CBCT Secondary
7/27/2019 Mini Lec
22/72
Single phase over frequency,Auto reset,Adjustable over frequency tripsettings,'Adjustable trip delay,1 CO output relay
Wherever not specifiedContact Rating :5A @ 230 V AC(resistive)
22
Single phase under & overfrequency, Microcontroller baseddesign, SMD technology, Autoreset, Adjustable under/overfrequency trip settings,Adjustable trip delay & ON delay,2 CO output relay Failsafe-non-failsafe mode selectable
Supply Voltage
System
Auxiliary
Ext. Input
Output contact
Trip setting
Under Frequency
Over Frequency
Reverse PowerPower On Delay
Trip Time Delay
Resetting
Weight
Dimensions (mm) Overall (L x W x D)
Mounting (L x W)
F R E Q U E N C Y M O N I T O R I N G R E L A Y S
Aux. Supply
OF SetPointOF Reset
T ON
2 to 5 sec. Td -
13
13
14
15
1 to 10 sec.
Freq. Input
Aux. Supply
OF SetPoint
UF SetPoint
Freq. Input
OF Reset
UF Reset
AUTO
T ON
1 to 10 sec. Td
RESET
10
10
7
7
11
12
8
9
1 to 10 sec.
OFS D1 S2 FMR1Over Frequency Relay Frequency Monitoring Relay
1 CO + 1 CO
100-120/220-240/380-440 V AC 20%, 38-72 Hz
40 Hz - 60 Hz (Variable)
50 Hz - 70 Hz (Variable)
1 - 10 Sec.(Adjustable) 1 Sec.
1 - 10 Sec.(Adjustable) 1 Sec.
Auto / Manual
130 gms
90 X 35 X 60
35 mm Rail Mounting
In Built
DOLSTARTER
ON
N/V
OFF
LO
AD
12 / 24 V DC or Built in
1 CO
100-120 / 220-240 / 380-440 V AC 20%
N.A.
50 Hz - 70 Hz
3.5 secs. 1.5 sec (fixed)
1 - 10 secs. (adjustable)
Auto
450 gms.
76 x 30.5 x 117.5
68 centre to centre / 35 mm Rail Mounting
ON
N/V
OFF
LOAD
DOLSTARTER
2
14
8
1
13
7
3
15
9
OFS D1
L
N
Relay contact position shown in 'Power off' condition
C US
R
Note: S2 Series - RoHS Product available on request.
7/27/2019 Mini Lec
23/72
3-phase 3-wire generators reversepower monitoringAuto/Manual reset,Reverse power (current) trip settingsadjustable,ON delay and trip delay adjustable,
2 CO output relay
Single phase or 3-phase 4-wiregenerators reverse power monitoringAuto/Manual reset,Reverse power (current) trip settingsadjustable,ON delay and trip delay adjustable,
2 CO output relay
23
Built-in
5A CT Secondary & B, Neutral
2 CO
100-120 / 220-240 / 380-440 V AC 20%
2% - 20% (adjustable)1 - 10 secs. (adjustable)
1 - 10 secs. (adjustable)
Auto / Manual
460 gms.
76 x 56.5 x 117.5
67 x 46 / 35 mm Rail Mounting
100-120 / 220-240 / 380-440 V AC 20%
Built-in
5A & R,Y, BCT Secondary
2 CO
2% - 20% (adjustable)1 - 10 secs. (adjustable)
1 - 10 secs. (adjustable.)
Auto / Manual
460 gms.
76 x 56.5 x 117.5
67 x 46 / 35 mm Rail Mounting
RPT D2 RPF D2
P O W E R M O N I T O R I N G R E L A Y S
Reverse Power Relay,(3-3W) Reverse Power Relay,( )3-4W
LOAD
G
A/MLINK
RPF D2
R
Y
B
1 2 3 4 5 6
7 8 9
P1
S1 S2
P2
External5 Amp Secondary CT
101112
13 14151617 18
RPT D2
LOAD
16
16
13
13
17
18
14
15
3 Ph
Forward Power
Supply
Reverse Power
RecoveryLevel
Current TrippingLevel
T ON1 to 10 sec.
1 to 10 sec.
Td
Increasing Foward Current
Increasing Reverse Current
ASYN.
MOTOR1ASYN.
MOTOR2
POWERSOURCE
POWERSOURCE
RPT D2 / RPF D2
ASYN.MOTORLOAD
RPT D2 / RPF D2
Relay contact positionshown in 'Power off' condition
7/27/2019 Mini Lec
24/72
24
Introduction & Application
CORE BALANCE CURRENT TRANSFORMERS (CBCT) is a sensor to
sense ear th fault current in conjunction with an EARTH FAULT RELAY
to protect the system when an EARTH FAULT occurs on one or more
phases. The CBCT is mounted externally & load carrying conductors
are passed through CBCT. The CBCT inner diameter is large enough
to pass all the three bus-bars or the three phase cables, unlike ametering CT where only one bus-bar or cable passes through the CT.
As the VECTOR SUM of the three currents at any given time is ZERO,
the resultant magnetic field through the core of the CT is zero. This is
the healthy situation of the system. If required Neutral also can be
passed through CBCT in case of 3 phases, 4 wire system. Ideally
Vector Sum will remain zero in case of fault free systems.
In the event of an Earth Fault occurring in any of the phases, the
current in that phase rises, inducing a resultant magnetic flux in the
CT secondary, energizing the relay & tripping the system.
The current at CBCT secondary will depend on the actual earth fault
current level & hence unbalanced loading does not affect the
functioning of Earth fault relay.
Salient Features
All current ratio's are available to match Minilec EFR / ELR.
Light Weight.
Compact in size.
Cost Effective.
General Specifications
1. System Voltage - up to 440 V AC
2. System Frequency - 50 Hz
3. Operating Temperature - 0 - 60C.
4. Humidity - Up to 95% R.H.
5. Rated Burden - < 3 VA
6. Inner Diameter - 50 / 100 / 120 / 150 / 200 / 220 / 250 / 300 mm
or any other customize size as per the requirement.
7. Outer Diameter - As per the relay requirement (Primary/ Fault &
secondary current) & ID.
8. Mounting - for smaller range clamps can be provided for CBCT
up to 50 mm ID & for higher range ID of CBCT, external
arrangement needs to be done.
Ordering Information
1) CT ratio (Primary & Secondary Current).
2) Inner Diameter.
3) Outer Diameter.
4) Type of CBCT - Resign cast or Tape wound or Moulded.
5) Minilec Relay Model Name.
Core Balance Current Transformers (CBCT)
for Earth fault protection
CORE BALANCE CURRENT TRANSFORMERS (CBCT)
New
7/27/2019 Mini Lec
25/72
These relays are useful for protection of 3-phase AC
induction motors against various hazards. Withtheir unique advantages they eliminate use of athermal/bimetal relay for motor protection. Beingcurrent sensing, they are to be selected according tomotor rating and are available for practically allranges of motors. These relays are ideally suitablefor Air-conditioning Compressor motor protection,as also for motors in machines, conveyors,cranes/hoists and lifts, and for pumps.
MODELS
MPR D2, SPG D2, F3 DRC1,D2 MPR1, D2MPR2, S2 CMR1S2 CTS1, F3 MPR1MBMPR,M-Commander,WTR D1, S2 WTR1
Ordering InstructionsProduct Family NameModel NameSystem Supply Voltage &
frequencyAux. Supply/Control supplyvoltageMotor/Pump rating (HP/KW)& dutyOverload characteristicsrequiredNo. of PTCs & Temp. graph
FEATURES Fixed/adjustable unbalance settings Fixed/adjustable settings for
under/over voltage, current, load
Fixed/adjustable trip delays Resetting Auto or Manual Output contacts : 1 CO or 2 CO Choice of enclosures (DIN-Rail, Flush) Models with Micro-Controller based
design Serial Communication (RS485) port 2 line alpha-numeric LCD display Use of SMD Technology User-friendly LED indications
25
MOTOR / PUMP PROTECTION RELAYS
PROTECTIONS / FUNCTIONS Phase Failure (Phase Loss/Single Phasing), Phase sequence reversal, Voltage Unbalance,
Under Voltage, Over Voltage Overload protection as per motor IDMTL
characteristics No-load/dry running Motor Winding overheating Over-current/Short circuit/locked rotor Earth Fault
7/27/2019 Mini Lec
26/72
7/27/2019 Mini Lec
27/72
7/27/2019 Mini Lec
28/72
CTINPUT
N
M1
M1
B
Y
R
EXTERNAL CBCT OF1Amp / 5Amp OUTPUT
CT MODULE (1A/ 5A / 20A/ 50A)
S1 S2
R
B
YM2
M3
OFF ON
1 2 3 4 5 6 7
8 9 10 11 12 13 14
C1 N01 NC1 C2 N02 NC2
AUX.
SUPPLY 485 O/P PTC I/P
MICROPROCESSOR BASED MOTOR PROTECTION RELAY
Microcontroller based. Sensing voltage, current and temperature. Protectingagainst Phase Failure, Unbalance, Phase sequence, Under/over voltage,overloading, winding over temperature, Over current/Short circuit, lockedrotor, Auto/Manual resetting, Adjustable trip settings for UV/OV, UC/OC, O/L,Locked rotor & earth fault. On delay & start-up delay adjustable, 2x1CO output
relays and serial communication port.
28
AUX.SUPPLY
SYSTEMSUPPLY
ALARM
TRIP
R
Y
B
CON3
CON6
CON1
CTINPUTCON2
CON4
E
T1
T2
T3
T4
NC2NO2
C2
NC1NO1
C1
PTC-1 FOR ALARM
N
M1
M1
B
Y
R
PTC-2 FORTRIP
EXTERNAL CBCT OF1Amp / 5Amp OUTPUT
CT MODULE ( CT1 / CT5 / CT20 / CT50 )
S1 S2
R
B
Y
RS-232OUTPUT
M2
M3
OFF ON
N
L
R
G
B
RELAYOUTPUT
MBMPRComprehensive Motor Protection Relay
F3 MPR1Motor Protection Relay
MBMPR
CT Module
CT Module is speciallydesigned for use withMinilec relays only likeF3 MPR1. MBMPR andM-Commander Available in2 modules, CT20 and CT50.Interconnecting cable(2.5mtrs) is provided with
this module.
Input from R.Y.B. phases and CBCT
CT
Range
CT Module Selection Chart
Settings Trip Level Trip Delay LED Reset Mode
Power ON
Unbal/Ph.Rev 1% - 20%
Under Voltage 75% - 95%
Over Voltage
Over Current/Short Circuit
105% - 120%
OverloadLock Rotor
Earth Fault 30% - 80% 0.5 - 10 Secs. Manual
Winding Overheat
Supply Voltage
System
AuxiliaryOutput
Input
Power Consumption
Trip
Setting
415V AC +20%,-25% 3, 3 Wire, 50 / (60)Hz 3%
90-270V AC / DC1 CO for Trip & 1 CO for Alarm/RS 232 Port (Optional)
Current Sensor - External CTS (CT1/CT5/CT 20/CT50)
8 VA
2/5/10/15/20 Sec. As per IDMTL char. ManualManual200%-500% of Imax 1-10 Secs.
1-20 Secs.4K1 - 5K6 Auto / Manual
300% - 800%of Imax 2-25 Secs.
Multi Attempt
1-10 Secs.
1-10 Secs.
1-10 Secs. Auto / Manual
Auto / Manual
Auto / Manual
Current unbalanceCurrent phase LossUnder Current
(dry run)
20-60% of Imax
30-90% of Imax
1-10 Secs.1-10 Secs.1-10 Secs.
MMuullttii AAtttteemmppttMMuullttii AAtttteemmppttMMuullttii AAtttteemmpptt
} forCDR-M
Display
Dimensions (mm)
Overall (L x W x D)
Panel mounting (L x W)
Approx Weight
16x2 Ch. ( LCD Display)Back lit
166 x 216 x 80
153 x 203
600 gms
MBMPR
Protection Setting Trip Delay Resetting
Over load Trip Setting As perIDMTL Char
pply Voltage
System
Auxiliarytput Relay Contact
rial Communication
220-440 V AC 20%, 45-65Hz
90-270 V AC/DC2 CO
Provision of RS485 Output
splay
mensions (mm.)
Overall (L x W x D)
Mounting (L x W)
prox Weight Unit
16x2 ( LCD Display)Back lit
96 x 96 x 80
Panel Mounting - 92 x 92
400 gms
3 MPR 1
Parameter RangeLCD Display
Mode
2/5/10/15/20 Sec N.A Over Load Manual
Unbalance Trip Setting 20% 60% 1-10 Sec Current Unbalanced Multi Attempt
Phase Faliure N.A 1-10 Sec Current S.P. Manual
Reverse Phasing N.A Instant ManualPhase Reversal
Under Current 30%-90% 1-60 Sec
}Multi Attempt
Under Current
Over Current 300%-800% 2-25 Sec Over CurrentLock Rotor 200%-500% 1-10 Sec ManualRotor Lock
Earth Fault Setting 30%-80% 0.5 - 10 Sec ManualEarth Fault
Over Temp.o o
70 to 180 1-20 Sec Sensor Fail,Motor Temp. High
Auto/Manual
F3 MPR1
Interconnection cable
102 x 35 x 81
90mm Panel Mounting centre to centre
600 gms
For motor currents
(FLA) upto 20 Amp
For motor currents
(FLA) upto 50 Amp
Relay contact positionshown in 'Power off' condition
CT20
CT50
PC Side Software
( CT 20 / CT 50 )
put Current Sensor - External CTS (CT1/CT5/CT 20/CT50)
7/27/2019 Mini Lec
29/72
29
MICROPROCESSOR BASED PUMP AUTOMATION SYSTEM
Motor protection Includes Over voltage protection Single/Reverse phasing protection
Voltage / Current unbalance
Overload trip
Over current protection Dry running protection
Earth fault protection
PTC based winding overheating protection
Pump Management System Features Auto Change over between two pumps
Intelligent resetting facility
On-site programming facility
Password protection for programming Pump On-Off timer programmable for 10
times a day, with advance programming of
7 days
Provision for water level control Run-time compensation
Ideal for Pump Automation & Unmanned
Pumping Stations.
Under/
PARAMETERS SPECIFICATIONS
Supply VoltageSystem 415 V AC +20%,-25% 50/60Hz 3%Auxiliary 90-270 VAC/DC 20%, 50Hz
Output Contacts 4 x 1 CO Relays (for 2 pumps)Current sensor External CT1 / CT5 / CT20 / CT50Reset Auto/ Multi-Attempt / ManualUnbalance 1-20% 6V for Voltage Unbalance
20-60% 5% of current unbalanceOverload As per inverse time characteristicsOver Current / 300% - 800%Short CircuitLocked Rotor 200% - 500%Earth Fault 30% - 80%Winding Overheating As per PTC temperature characteristics
Under Voltage 75% - 95% of system supply (adjustable)Over Voltage 105%-120% of system supply (adjustable)Dry Running 30-90% of Imax
Display 16x2 Ch. (Backlit LCD)
Level Control Upper tank full
Lower tank empty
Weight 800gms
Wherever not specified Contact Rating : 5A @ 230 V AC (resistive)
M-Commander is a micro-processor basedMotor protection and Pump managementsystem, suitable for 2 pumps.Sensing voltage, current and temperature.Protecting against Phase Failure, Unbalance,Phase sequence, Under/over voltage,overloading, dry running, winding overtemperature, Over current/Short circuit,locked rotor, earth fault. Auto/Manualresetting, Adjustable trip settings for UV/OV,UC/OC, O/L, Locked rotor & earth fault.On delay & start-up delay adjustable,2x1CO output relays RTC based time settingsWater level control.
M-COMMANDERPump Management & Protection System
For more detailed specifications, refer table on page No. 26 (MBMPR)
CT Module
For motor current above 50 Amp.customer to use suitable external CT of1 Amp/5 Amp Secondary and CT ModuleCT 1/CT 5 for Minilec relay only like
F3 MPR1, MBMPR & M- COMMANDER
( CT1 / CT 5 )
1 2 5 6
CT-5
B
Y
R
EXTERNAL CBCT OF1Amp / 5Amp OUTPUT
To Unit
S2
EXTERNAL CT OF1Amp / 5Amp OUTPUT
M1
PUMPM1
M2
M3
90 x 35 x 60
35 mm Rail Mounting
400 gms
AUX.SUPPLY
SYSTEMSUPPLY
PUMP-2 PRIMING
PUMP-2
PUMP-1 PRIMING
PUMP-1
CON3
CON6
CTINPUT
CON2
WINDING TEMPSENSOR( PTC- 1) FORPUMP- 1
N
M1
PUMP-1
B
Y
R
M2
WINDING TEMPSENSOR( PTC- 2) FORPUMP- 2
EXTERNAL CBCT OF
1Amp / 5Amp OUTPUT
CT MODULE (CT1 / CT5 / CT20 / CT50)
S1 S2
R
B
Y
OFF ON
OFF ON
M1
M2
M3
M1
M2
M3
CON1
P3
P2
P1
P6
P5
P4
IP1
C
T1
T2
T3
T4
R
Y
B
CON4
E
N
L
NC4NO4
C4
NC3NO3
C3
NC2NO2
C2
NC1N
O1
C1
P2
P1
P3
LOWERTANK
P5
P4
P6
UPPERTANK
PUMP-2
RELAYOUTPUT
INPUT
For Auto operation, Put link across 'ON' push button
M-COMMANDER
Relay contact position shown in 'Power off' condition
7/27/2019 Mini Lec
30/72
WINDING OVER-TEMPERATURE PROTECTION RELAYS
Sensing motor windingtemperature through PTCThermistors.Winding overheating, sensorshort, sensor open faults.Suitable for single,
triple or 6/9/12 PTCs
Sensing motor winding temperaturethrough PTC Thermistors.Winding overheating,sensor short, sensor open faults.Suitable for single,triple or 6/9/12 PTCs
failsafe/Non fail safe
30
Wherever not specifiedContact Rating :5A @ 230 V AC (resistive)
Supply Voltage
Auxiliary
Output Contacts
Trip Setting
Thermistor Sensor Healthy
Thermistor Sensor Trip
Thermistor Sensor Open
Thermistor Sensor Short
Trip time delay
Resetting
Dimensions (mm)
Overall (L x W x D)
Mounting (L x W)Weight
Selection Chart for NRT of PTC Thermistors.
NRT Class Cable Colour
0C of Ins. Code
70 White - Brown
80 White - White
90 Green - Green
100 A Red - Red
110 Brown - Brown
120 E Grey - Grey
130 B Blue - Blue
140 White - Blue
150 F Black - Black
160 Blue - Red
170 H White - Green
180 C White - Red
190 Orange - Black
PTCTHERMISTORCONDITIONAND TRIPSETTINGS
RESISTANCE VS TEMPERATURE O/PRELAYSTATUS
OPENED(RESISTANCE
> 5.6k)
UNHEALTHY(RESISTANCE>4.2k < 5.5k)
Relay ResetZone
(>1.5K39W
7/27/2019 Mini Lec
31/72
Minilec offers timers for various fuctions andapplications,in various enclosures/sizes and withmulti voltage options.
MODELS
ETS D1, ETA D1,ESR D1, ESD D1,D1 ETM1, S2ETM1,
D2 ETR1,S2 ETM2, S2 ETM3
Ordering Instructions
Product Family NameModel Name
Aux. Supply/Controlsupply voltageApplication
FEATURES Single voltage & Multi-voltage Single function and multi-function Wide time range Better repeat Accuracy Models with Micro-Controller based
design Use of SMD Technology (S2 Series
models)
31
ELECTRONIC TIMERS
FUNCTIONS On Delay Interval Delay Cyclic ON/OFF
Multi-Attempt (for Engine Starting) Star-Delta changeover True off Delay
7/27/2019 Mini Lec
32/72
ON DELAY TIMERS
On Delay, time rangeupto 209 hours,2 CO output relay
ETS D1On Delay Timer
On Delay, time range 30 Minutes,Multi-voltage supply,2 CO output relay
ETA D1On Delay Timer (Multivoltage)
32
Supply Voltage
Auxiliary
Output Contacts
Time Range
Operating Modes
Weight
Dimensions (mm)
Overall (L x W x D)
Mounting (L x W)
24-240 V AC / DC
+10%, - 20%
2 CO
0.7 secs. - 30 mins.(4 ranges)
On Delay
160 gms.
76 x 30.5 x 117.5
68 centre to centre / 35 mm Rail Mounting
Wherever not specifiedContact Rating :
5A @ 230 V AC (resistive)
Aux.
Supply
13
14
15
13T Set
Aux.
Supply
13
14
15
13T Set
24/110 / 240 / 380 / 415 V AC 20%,
12 / 24 V DC 20%
2 CO
0.1-10, 1-19, 10-109, 20-209 sec, 1-19, 10-109,20-209 min, 1-19, 10-109, 20- 209 Hrs.
On Delay
175 gms.
76 x 30.5 x 120
68 mm centre to centre / 35 mm Rail Mounting
1 2 3
13 14 15
7 8 9
AUX.
SUPPLY
L
N
Starter/CB
Coil
ETA D1
1 2 3
13 14 15
7 8 9
AUX.
SUPPLY
L
N
Starter/CB
Coil
ETS D1
Relay contact position shown in 'Time Elapsed' condition
ESR D1Engine Start Relay
Multi-attemptengine start relay
12, 24 VDC 10 %
110 / 220/ 230 / 240 VAC 20%
Start attempts - 1 COAlarm on - 1 CO
Start Time - 1 to 10 secs. (via Potentiometer)Pause Time - 2 to 20 secs. (via Potentiometer)Number of attempts - 1 to 10 (via Potentiometer)
175 gms.
76 x 30.5 x 117.5
68 mm centre to centre / 35 mm Rail Mounting
Starter/Solenoid/Load
Start
Failure
Alarm
AUX.
SUPPLY
R1 R2
POWER
SUPPLY
START
RELAY
ON
ALARMRELAY
ON
Ts n
7- 8
1- 2
13-14
1- 3
13-15
PRESET
NUMBER OF
START
Tp
Note: Relay contacts shown
for relay in energizedcondition & alarm relay inde energized condition
Note: ETS D1 old modelavailable on request
7/27/2019 Mini Lec
33/72
ON
N/V
OFF
Aux.Supply
1 2 3
13 14 15
7 8 9
D1 ETM1
L
O
A
D
1 CO + 1 CO
150 gms (Approx.)
90 x 35 x 60
35 mm Rail Mounting
M1 - On delayM2 - Interval
M3 - Cyclic off firstM4 -M5 - Star DeltaM6 - Instant & DelayedM7 - Engine Start Mode
Cyclic on first
0.1-1,1- 10, 6 - 60, 60-600 seconds
0.1- 1, 1-10,10-100 hours
*CE/CSA Not available for 110VAC models
12 VDC 20%24 VAC/DC 20%*100-120/220-240/380-440VAC 20%
12 VDC 20%24 VAC/DC 20%*24-240VAC/DC +10%,-20%*100-120/220-240/380-440VAC 20%
1 CO + 1 CO
200 gms (Approx.)
76 x 30.5 x 117.5
68 mm centre to centre / 35 mm Rail Mounting
0.1-1,1- 10, 6 - 60, 60-600 seconds
M1 - On delayM2 - Interval
M3 - Cyclic off firstM4 - Cyclic on firstM5 - Star DeltaM6 - Instant & DelayedM7 - Eng ine Start Mode
0.1- 1, 1-10,10-100 hours
C US
R
ESD D1Star Delta Timer
Star to DeltaChangeover timer,Time range upto 60seconds,2x1NO output relays
*CE/CSA Not available for 110 V AC & 24-240 VAC/DC Models
C US
R
33
110 / 240 / 380 / 415 V AC
1 NO-Star relay (NO)1 NO-Delta relay (NO)
0.7 60 secs.in 2 diff. ranges
Star Delta Changeover50 / 100 m.secs.
Time
175 gms.
76 x 30.5 x 117.5
68 mm centre to centre / 35 mm Rail Mounting
+10%,20%
S2 ETM1Multi Function Timer
Microcontroller basedMulti-function timer (Ondelay, interval delay,cyclic, star-delta,Engine starting), timerange upto 100 Hrs,
2x1CO output relays
SPECIAL FUNCTION TIMERS
D1 ETM1Multi Function Timer
Relay contact position shown in 'Power off' conditionRelay contact position
shown in 'Time Elapsed condition
Aux.
Supply
1413
1
50/100 msecY- Transfer Time
2
Y
1 2 3
13 14 15
7 8 9
AUX.SUPPLY
ESD D1
Microcontroller based,SMD technologyMulti-function timer (Ondelay, interval delay,cyclic, star-delta, Enginestarting), time range upto100 Hrs,2x1CO output relays
SelectableBy Rotary Switch
SelectableBy Rotary Switch
ON
N/V
OFF
L
O
A
D
Note: S2 Series - RoHS Product available on request.
7/27/2019 Mini Lec
34/72
CYCLIC TIMERS
Microcontroller based,Unequal cyclic and forward-reverse functions, on time andpause time selectable,2x1CO output relays
Microcontroller based,SMD technologyUnequal cyclic and forward-reverse functions,on time and pause timeselectable,
2x1CO output relays
34
Wherever not specifiedContact Rating :5A @ 230 V AC (resistive)
Supply Voltage
Auxiliary
Output Contacts
Time Range
Operating Modes
Weight
Dimensions (mm)
Overall (L x W x D)
Mounting (L x W)
Off Delay timer,Auto reset,Time range upto 200 seconds,2 CO output relay
C US
R
S2 ETM2Cyclic & Forward-Reverse Timer
D2 ETR1Cyclic & Forward-Reverse Timer
Mode 1Unequal
Mode 2Cyclic
POWER
Tset
7 8710 11
7 9710 12
*100-120 / 220-240 / 380-440 V AC 20%,12/24 VDC 20%
1 CO + 1 CO
On Time- 0. 1 Sec.To 100 Hrs.
Pause Time- 0. 1 Sec.To 100 Hrs
Mode 1 Unequal Cyclic Operation
Mode 2 Forward Reverse Cyclic Operation
100 gms (Approx.)
90 x 35 x 60
35 mm Rail Mounting
*CE/CSA mark not available for 110VAC models
*24/110/240/415VAC, 20%,
12/24 VDC 10%
1 CO + 1 CO
On Time - 0. 1 Sec.To 100 Hrs.
Pause Time - 0. 1 Sec.To 100 Hrs
Mode 1 Unequal Cyclic Operation
Mode 2 Forward Reverse Cyclic Operation
200 gms (Approx.)
76 x 56.5 x 117.5
67 x 46 /35 mm Rail Mounting
*CE/CSA mark not available for 110VAC models
110/240 V AC 10%
2 CO
20-200 Sec.
Power On
170 gms. (Approx).
90 x 35 x 60
35 mm Rail Mounting
1 3
L
O
A
D
S2 ETM3
Aux.Supply
Back-upsupply
Aux.Supply
13 14 1 6 17
13 15 1 6 18
13 14
13 15
16 17
16 18
Mode 1Unequal
Mode 2Cyclic
13 14 1 5 1 6 17 18
7 8 9 10 11 12
D2 ETR 1
1 2 3 4 5 6
ON
N/V
OFF
L
O
A
D
Aux.Supply
C US
R
S2 ETM3Off Delay Timer
Relay contact position shown in 'Power off' condition
Note: S2 Series - RoHS Product available on request.
7/27/2019 Mini Lec
35/72
FUNCTIONS Level monitoring of conductive and
non-conductive liquids
One level or two level monitoring
One tank or two tank level
monitoring
These are suitable for conductive liquids like waterand for non-conductive liquids like Diesel/Oil.Models for eitherone level monitoring or two levelmonitoring.
MODELS
WLC D1, Electrodes,P1 LCW1,
S2 WLC1, P2 ALT1,DLC D1 + FRKP 1,FRKP 4
Ordering InstructionsProduct Family Name
Model Name
System Supply Voltage
Aux. Supply/Control
supply voltage
Type of liquid & its
specifications
FEATURES Can be used for potable water, water
with impurities and for diesel/oil Cable size & length no restriction for
water level monitoring Suitable for variety of electrodes Optical sensing for diesel/oil level
monitoring Open collector output (for FRKP4) Choice of enclosures (DIN-Rail, &
Plug-in) Use of SMD Technology (S2 Series
models)
35
LIQUID LEVEL CONTROLLERS
7/27/2019 Mini Lec
36/72
L E V E L C O N T R O L L E R S - C O N D U C T I V E L I Q U I D S
Single tank - 2 level controlrelay, suitable for conductiveliquids, sensitivity adjustment,1CO output relay.Also can be used as moisture
control relay.
WLC D1Water Level Control Relay Two Level Single Tank
Single tank - 2 level controlrelay, suitable for conductiveliquids,1CO output relay
P1 LCW1Water Level Control Relay Two Level Single Tank
36
Auxiliary Supply 24 VAC/DC/100-120/220-240/380-440 V AC 10%, 50 / 60 Hz
Output Contacts 1 CO 1 CO
Input Sensors 3 Electrodes 3 Electrodes
Sensitivity 1K - 200 K (adjustable)W W N.A.Trip Time Delay Less than 1 sec Less than 1 sec
Weight
Unit 300 gms. 125 gms
Sensor (each) 50 gms. 50 gms
Dimensions (mm)
Unit
Overall (L x W x D) 76 x 30.5 x 117.5 50 x 40 x 80
Mounting (L x W) 68 mm centre to centre / 35 mm rail mounting 8 - pin plug-in
Sensor (mm)
Overall 24 (Dia) x 76 (L) 24 (Dia) x 76 (L)
Relay contactApplicable for suction Tank
p1p2
p3
p1p2
p3
p1p2
p3
p1p2
p3
p1p2
p3
Aux Supply
Suction (Source)
Tank Water Level
13
14
15
13
p1p2
p3
p1p2
p3
p1p2
p3
p1p2
p3
p1p2
p3
Aux Supply
Suction (Source)
Tank Water Level
8
6
5
8
24 /110 / 240 / 380 / 415 V AC 10%, 50 / 60 Hz, 12 / 24 V DC
Wherever not specifiedContact Rating :5A @ 230 V AC (resistive)
1
2
3
4 5
6
7
8
Bottomview
AUX. SUPPLY
AC
DC
P3
P2
P1
P1P2
P3
MOTOR
2
14
8
1
13
7
3
15
9
WLC D1
R
Y
B
N/VOFF
ONDOL STARTER
M1
M2
M3
AUX.SUPPLY
P1P2
P3
Link for Autooperation
Moisture control relay connection: Short 1 & 3 terminals. Connect sensor wires at 1 & 2 terminals.
7/27/2019 Mini Lec
37/72
37
S2 WLC1Water Level Control Relay Two Level Single Tank
Single tank 2 level control relay,Sensitivity adjustment,suitable for conductive liquids,1CO output relay
200 gms.
24 V AC / DC / 110 / 240 V AC 10%
Less than 1 sec. (Fixed)
1 CO
90 x 35 x 60
24 (Dia) x 76 (L)
35 MM Rail Mounting
50 gms.
3 Electrodes
1 K To 200 K (adjustable)W W
p1p2
p3
p1p2
p3
p1p2
p3
p1p2
p3
p1p2
p3
Aux Supply
Suction (Source)
Tank Water Level
7
8
9
7
Relay position as per suction logic selection
P2 ALT1Alternating Relay
This is a simple 'Step Relay' to achieve alternatingduty of two pumps or compressors. Operation oftwo pumps or compressors is achieved inalternating sequence as per either pressure switchor level control or thermostat contacts. Product is
available in 11 pin (P2) plug-in enclosure.
Aux Supply 110/115/220/230/240/380/415 V AC
24 V AC/DC 15 %
Frequency 50 Hz / 60 Hz 3%
Power Consumption 5 VA max.
Output Relay Contact 2 NO
Indication
ON Power ON (Green)
RLY Relay ON (Red)
Operations 30 Operation/Min. (max.)
Dimensions (H x W x D) 85 x 35 x 90mm
Mounting 11 pin plug in base mounting
Weight 250 gms. (approx.)
12
3
4
56
7
8
9
1011 PUMP 'A'
CONTACTOR
NC (A) NC (B)
PS1
PS2
PUMP 'B'CONTACTOR
AUX. SUPPLY
PS 2
LEVEL
PS 1
LEVEL
CONTACTOR
PUMP A
CONTACTOR
PUMP B
1 3 5
SUCTION TANK
4 6
S2 WLC1
M1
Aux.Supply
R
M2Y
M3B
P3
P2
P1
Link for Autooperation
7/27/2019 Mini Lec
38/72
One level switch for diesel/oil,optical sensing principle,1 CO output relay
Either high level or low levelswitch (selectable),open collector outputOutput suitable as input to PLCor Controller
38
Auxiliary Supply
Output Contacts
Input Sensors
Sensitivity
Trip Time Delay
Weight
Unit
Sensor (each)
Dimensions (mm)
Unit
Overall (L x W x D)
Mounting (L x W)
Sensor (mm)
Overall
MOTOR
2
14
8
1
13
7
3
15
9
DLC D1
R
Y
B
N/VOFF
DOL STARTER
M1
M2
M3
AUX.SUPPLY
ON
LIQUID TANKSENSOR PROD
3 CORECABLE
13
14
15
13
Aux Supply
Suction
Diseel Fuel Level
L E V E L C O N T R O L L E R S - N O N C O N D U C T I V E L I Q U I D S
Relay position as per logic selection
DLC D1 + FRKP 1Diesel Level Control Relay Single Level
FRKP 4Diesel Level Sensor Switch Single Level
PNP- Break Switching+
-
RED
GREEN
BLACK
200mAMAX.
10 VDCTO
28 VDC
NPN- Make SwitchingRED
GREEN
BLACK
+
-
10 VDCTO
28 VDC
200mAMAX.
10-28 V DC 10%
Open Collector 200 mA @ 24 V DC
Built-in sensor
N. A.
Less than 1 sec
100 gms
18 (Dia) x 75 (L)
10 -120/220-240/380-440 V AC / 24 V DC / AC, 12 V DC0 10%
1 CO
1 (FRK P1)
N. A.
Less than 5 sec
300 gms.
100 gms.
76 x 30.5 x 117.5
68 mm centre to centre / 35 mm rail mounting
18 (Dia) x 75 (L)
AuxSupply
Load ON
Load OFF
NPN-MakeSwitching
DiseelFuelLevel
Load ON
PNP - Break Switching
Load OFF
AuxSupply
DiseelFuelLevel
7/27/2019 Mini Lec
39/72
Power line transucers are suitable for measuringelectrical parameters like AC voltage, current,frequency, PF, KW, KVAR and also for DC signalisolation. They are best suited for MCC and PCCpanels, AMF panels, SCADA systems, PLCs for dataacquisition and metering.
MODELS
D2 PTV1, D2 PTC1, D3 PTF1, D5 PTA1,D5 PTW1, D5 PTW2, D5 PTW3, D1 IST1,D3 IST1, D5 IST1, F3 MFM1, D3 TTT1, D3 RET1,D3 TET1, D5 PTC1, D5 PTV1, D1 PTC3,D1 PTV3, D5 MFT1
Ordering InstructionsProduct Family NameModel Name
System Supply VoltageAux. Supply/Controlsupply voltageCT/PT RatiosPrimary rangeOutput required
FEATURES Fully solidstate electronic design. Rugged to withstand harsh
environments
Load independent outputs Galvanically isolated signals Accuracy class : 0.5% (Optional 0.2%) Self or auxiliary powered. CT burden : less than 0.5 VA
FUNCTIONS Convert high value AC signal to low
value DC signals Inputs voltage, current, frequency,
power factor, power Outputs DC signals single or dual
(optionally 3 or 4 for Isolationtransducers)
39
POWER LINE TRANSDUCERS ANDMULTIFUNCTION METER
7/27/2019 Mini Lec
40/72
VOLTAGE, CURRENT, FREQUENCY TRANSDUCERS
Current transducer,Input AC Current,Output (DC) single or dual,accuracy 0.5%
D2 PTV1AC Voltage Transducer
Frequency transducer,Output (DC) single or dual,accuracy 0.5%
D3 PTF1Line Frequency Transducer
Voltage transducer,Input AC voltage,Output (DC) single or dual,accuracy 0.5%
D2 PTC1AC Current Transducer
Auxiliary Supply 24/48 VDC+/- 20%, 60-300 VAC / DC
Power Consumption
Input Value I in
V in
DC Output (Single / Dual) 0 - 1 mA, 0 - 10 mA, 0 - 20 mA, 4 - 20 mA, 0 - 5 V, 0 - 10 V Other optional on request
No of Signal Output
Response Time
Input / Output isolation
Temperature
Humidity
Dimensions (L x W x D) (mm)Weight
Operations
The input current signal is scaled downthrough Interposing current transformer. Thescaled down signal is fed to a precisionrectifier stage, its output is processed toprovide DC Voltage/ Current outputproportional to input AC Current. The outputsignal is calibrated for RMS value.
The input Voltage signal is scaled downthrough Interposing potential transformer.The scaled down signal is fed to a precisionrectifier stage, its output is processed toprovide DC Voltage/ Current outputproportional to input AC voltage. The outputsignal is calibrated for RMS value.
The input frequency signal isscaled down through Interposingpotential transformer. The scaleddown signal is fed to a precisionfrequency to voltage Converterstage, its output is processed toprovide DC Voltage/ Currentproportional to Line Frequency.
40
Output Load
Resistance (Rout)
For Current Output Max. 10V/I out
(Optional Max. 15V/Iout)
For Voltage Output 10 Kohm (min.)
Output Ripple Less than 0.5% of
span (peak to peak)
Auxiliary Supply Less than 4 VA
Burden
Insulation More than 100 Mohms
Resistance at 500 V DC
Zero Span Optionally provided
AdjustmentTerminals Suitable for 2.5 sq.mm
wires
Enclosure Type ABS Plastic, Ingress
Protection IP40
Common Specifications
24/48 VDC+/- 20%, Self Powered, 60-300 VAC/DC
3.5 VA - AC, 4 VA - DC
63.5 / 110 / 240 / 415 V
Single (Optional Dual Output)
Galvanic0 00 C to + 55 C
Up to 95% Rh non condensing
75 x 83.5 x 117.5575 gms
Freq. Range 45 to 55 Hz/40-60 Hz/55-65 Hz/48-52Hz
3.5 VA - AC, 4 VA - DC
0 -1 A AC / 0 - 5 A AC
N.A.
Single (Optional Dual Output)
Less than 500 miliseconds
Galvanic0 00 C to + 55 C
Up to 95% Rh non condensing
75 x 56.5 x 117.5440 gms
3.5 VA - AC, 4 VA - DC 24/48 VDC +/- 20%
N.A.
110 / 240 / 415 V
Single (Optional Dual Output)
Galvanic0 00 C to + 55 C
Up to 95% Rh non condensing
75 x 56.5 x 117.5440 gms
1 2 3 4 5 6
7 8 9 10 11 12
181716151413
AUX.INPUT
VOLTAGE
D2 PTV1
SUPPLY SUPPLY
AUX.
1 2 3 4 5 6
10 11 12
DC OUTPUTAUX.
SUPPLY
NOMINAL INPUTVOLTAGE
7 8 9
13 1415 16 17 18
19 20 21 22 2324 25 26 27
D3 PTF1
1 2 3 4 5 6
7 8 9 10 11 12
181716151413
DC OUTPUT
INPUTCURRENT
DC OUTPUT
D2 PTC1
Note: Voltage/Current Transducer in case of dual output will come in D3 enclosure (Dimension change)
7/27/2019 Mini Lec
41/72
ower Factor Transducer,put 3-phase voltage & current,
utput Single or Dual (DC),ccuracy 0.5%
D5 PTA1Power Factor Transducer
D5 PTW1Active Power Transducer
Active Power Transducer,Input 3-phase voltage & current,output Single or Dual (DC),Accuracy 0.5%
41
Reactive Power Transducer,Input 3-phase voltage & current,output Single or Dual (DC),Accuracy 0.5%
D5 PTW2Reactive Power Transducer
24/48 VDC+/- 20%, Self Powered, 60-300 VAC / DC
0 - 1 mA, 0 - 10 mA, 0 - 20 mA, 4 - 20 mA, 0 - 5 V, 0 - 10 V
3.5 VA - AC, 4 VA - DC
1 A / 5 A
110 / 415 V
Single (Optional Dual Output)
Galvanic0 00 C to + 55C
Up to 95% Rh non condensing
73 x 150 x 1131200 gms.
3.5 VA - AC, 4 VA - DC
1 A / 5 A
110 / 415 V
Single (Optional Dual Output)
Less than 500 miliseconds
Galvanic0 00 C to + 55 C
Up to 95% Rh non condensing
73 x 150 x 1131200 gms.
3.5 VA - AC, 4 VA - DC
1 A / 5 A
110 / 415 V
Single (Optional Dual Output)
Galvanic0 00 C to + 55 C
Up to 95% Rh non condensing
73 x 150 x 1131200 gms.
POWER TRANSDUCERS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
P1 P2S1 S2P1 P2
S1 S2RYBN
SUPPLY
LOAD
For 3 Phase 4 Wire Network
D5 PTW 1 / D5 PTW 3
AUX.SUPPLY
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
P1 P2S1 S2P1 P2
S1 S2RYBN
SUPPLY
LOAD
For 3 Phase 4 Wire Network
D5 PTW 2
AUX.SUPPLY
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
AUX.SUPPLYP1 P2
S1 S2
P1 P2S1 S2
RYBN
SUPPLY
LOAD
For 3 Phase 3 Wire Network
D5 PTA 1
+ DC o/p
The input Voltage and current signals arescaled down through interposing andcurrent transformers. The scaled downvoltage signal proportional to vcos. Thissignal is divided by the voltage signal to getDC Voltage linearly proportional to PowerFactor. This output is further processed toprovide DC Voltage / Current output signal.
The Transducer is suitable for balancedoad conditions only, when used on 3Phase 3 Wire, 3 Phase 4 Wire electrical
networks.
The input Voltage and current signals are scaled down through interposing potential and current transformer.In case of reactive transducers the voltage signals are 900 phase shifted. The scaled down signals are fed toprecision multipliers working on time division multiplication principle. The multiplier output is processed toprovide DC Voltage / Current output signal proportional to input active / reactive power. For Signal Phasenetwork, only Active Power Transducer is offered. Fro 3 Phase 3 Wire or 3 Phase 4 Wire electrical networksboth Active and Reactive Power Transducers are offered for balanced as well as unbalanced load conditions.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
AUX.SUPPLYP1 P2
S1 S2
P1 P2S1 S2
RYB
SUPPL
Y
LOAD
For 3 Phase 3 Wire Network
D5 PTW 1 / D5 PTW 2 / D5 PTW 3
D5 PTW3ApparentPower Transducer
+ DC o /p
+ DC o/p
+ DC o/p
Apparent Power Transducer,Input 3-phase voltage & current,output Single or Dual (DC),Accuracy 0.5%
3.5 VA - AC, 4 VA - DC
1 A / 5 A
110 / 415 V
Single (Optional Dual Output)
Galvanic0 00 C to + 55 C
Up to 95% Rh non condensing
73 x 150 x 1131200 gms.
7/27/2019 Mini Lec
42/72
Signal Isolation transducer,Input & output DC signals,Single or dual outputs,accuracy 0.5%
Signal Isolation transducer,Input & output DC signals,upto 4 outputs,accuracy 0.5%
42
0-1, 0-5, 0-10, 0-20, 4-20mADC Signals
0-50, 0-60, 0-75, 0-100 mV DC / 0-1, 0-5, 0-10, 0-150, 0-300, 0-600 V DC
0 - 1 mA, 0 - 10 mA, 0 - 20 mA, 4 - 20 mA, 0 - 5 V, 0 - 10 V
ISOLATION TRANSDUCERS
D3 IST1DC Signal Isolation Transducer
D1 IST1DC Signal Isolation Transducer
D5 IST1DC Signal Isolation Transducer
Operations
Loop Powered DC SignalIsolator input & output DCsignal. Single Output.Accuracy 0.2%
4- 20 mA DC
Auxiliary Supply
Power Consumption
Input Value I in
V in
DC Output (Single / Dual)
No of Signal Output
Response Time
Input / Output isolation
Temperature
HumidityDimensions (L x W x D) (mm)
Weight
Resistance Type
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
AUX.SUPPLY
DCOUTPUT2
DCOUTPUT1
+ + DC
OUTPUT4DC
OUTPUT3
+ +
ma or mv or v
D5 IST1ma or mv or v
+
DC signal input
3.5 VA - AC, 4 VA - DC
Single (Optional Dual or 3 or 4)
Galvanic0 00 C to + 55 C
Up to 95% Rh non condensing73 x 150 x 113
1200 gms.
The input signal is filtered and processed to convert into a standard dc voltage. This voltage is fed to a linear optocoupler which
provides the required galvanic isolation. An optical feedback is used for improved linearity, response time and temperature effects.
The output from the linear optocoupler is fur ther processed to provide dc voltage / current output.
The isolator with fast response time (10 mSec) are typically used in feedback control system.
In input dc current is chopped by the chopper to convert it into high frequency ac signal. This signal is fed to an isolating high
frequency transformer. The ac output current from the transformer is rectified and filtered to obtain load independent dc output
current. As the transformation ratio is 1:1 the output current is identical in value to the dc input current.
24/48 VDC+/- 20%, 60-300 VAC / DC
3.5 VA - AC, 4 VA - DC
Single (Optional Dual Output)
Galvanic0 00 C to + 55 C
Up to 95% Rh non condensing73 x 83.5 x 117.5
1200 gms.
N.A.N.A. N.A.
1 2 3 4 5 6
10 11 12
DCO/P
2
AUX.SUPPLY
mA or mV or VDC Signal Input
7 8 9
13 14 1 5 16 17 18
19 20 2122 23 24 25 26 27
DCO/P
1
+
D3 IST1
4 - 20 mA DC Signal.
Single
Galvanic0 00 C to + 55 C
Up to 95% Rh non condensing30 x 80 x 120
150 gms.
Looped Powdered
Less than 100 mSec.
7 8 9
7/27/2019 Mini Lec
43/72
43
0 1 mA DC, 0 5 mA DC, 0 10 mA DC, 0 20 mA DC, 4 20 mA DC, (-)20 0 - (+)20 mA DC, 4 20 mA DC, 500 Ohm (max), 0 5 V DC, 0 - (+)10 V DC, (-)10 0 - (+)10 V DC
Transformer Tap Position transducer,Inputoutput (DC) single or dual,accuracy 0.5%
Resistance
D3 TTT1Transformer Tap Position Transducer
D3 RET1Resistance Transducer
It is a precision grade transducer is used for galvanically isolated measurement of Transformed Tap or Resistance (2 Wire or 3 Wire). It measures the value of
resistance on tap position changers, typically used on high voltage transformers. Each position on the selector has an equal value of resistance so that as the tap
position is increased or decreased the value of resistance increases or decrease respectively. The input is in the form of Resistance and provides a Stable, Ripple-
Free and Optically Isolated DC load independent output in the form of current or voltage. The transducer is fully solid state. Use of latest circuit techniques and quality
components ensure reliable operation over long period.