16
1 Proprietary & Confidential GE Multilin – Sales Training, May 2-5, 2004 MIF II DIGITAL FEEDER PROTECTION “A Comprehensive Protection solution for Feeders at any voltage level” MIFII SR 735/737 F650 F35 F60 SR 750/760 Functionality Price FMII

MIF II DIGITAL FEEDER PROTECTION

  • Upload
    buinhi

  • View
    397

  • Download
    0

Embed Size (px)

Citation preview

Page 1: MIF II DIGITAL FEEDER PROTECTION

1Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

MIF II DIGITAL FEEDER PROTECTION

“A Comprehensive Protection solution for Feeders at any voltage level”

MIFII

SR 735/737

F650 F35

F60

SR 750/760

Functionality

PriceFMII

Page 2: MIF II DIGITAL FEEDER PROTECTION

2Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

CONTENTS

INTRODUCTION: What is MIF II?

APPLICATIONS

FEATURES & BENEFITS

PROTECTION & CONTROL: Block Diagram

PRODUCT ARCHITECTURE: Mechanical, Hardware, Software

SOFTWARE: enerVista MIF II Setup Software

COMMUNICATIONS

ORDER CODE

SUMMARY

Page 3: MIF II DIGITAL FEEDER PROTECTION

3Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

INTRODUCTION

What is the MIF II?

• Supports ModBus communication protocol for integration with other IEDs

• Applicable to Electrical Utilities and industrial systems

• Best value for price• Building block for systems

Protection, control, metering, monitoring, and analysis system

Most Cost Effective Offering for Low and Medium Voltage FeedersMost Cost Effective Offering for Low and Medium Voltage Feeders

Page 4: MIF II DIGITAL FEEDER PROTECTION

4Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

APPLICATIONS

The MIF II can be used for:

• Comprehensive feeder protection for any voltage level

• Backup protection for transformers, busbars, generators and large motors

• Control functions breaker control (open/close) and recloser

Specify MIFII for Low End Feeder and Reclosure ApplicationsSpecify MIFII for Low End Feeder and Reclosure Applications

Page 5: MIF II DIGITAL FEEDER PROTECTION

5Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

FEATURES AND BENEFITS

The MIF II features advantage such as:

• Configurable logic

• Configurable curve

• Flash memory for field upgrades

• Two setting tables

• AC/DC power supply

• HMI with 5 keys and a 2x16

character alphanumeric display

• Isolated front RS232 serial port

State of the Art FeaturesState of the Art Features

Page 6: MIF II DIGITAL FEEDER PROTECTION

6Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

BLOCK DIAGRAMMIF II Protection and Control characteristics:

Combine Overcurrent Protection and Multiple-shot Reclosing in One Compact Relay

Combine Overcurrent Protection and Multiple-shot Reclosing in One Compact Relay

Page 7: MIF II DIGITAL FEEDER PROTECTION

7Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

PROTECTION AND CONTROL

MIF II Protection functions include:

• Configurable breaker failure to open

• Configurable I/O

• 6 outputs: trip, service required, auxiliary

• Sensitive ground protection

• Breaker opening/closing

• Phase/Ground TOC

• Phase/Ground IOC (two levels)

• 4 preconfigured overcurrent curves (ANSI or IEEE)

• Thermal image protection

• 4-shot recloser

• Cold load pickup function

Combine Overcurrent Protection and Multiple-shot Reclosing in One Compact Relay

Combine Overcurrent Protection and Multiple-shot Reclosing in One Compact Relay

Page 8: MIF II DIGITAL FEEDER PROTECTION

8Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

MONITORING AND METERING

The MIF II provides:• 32 Event record

• Analog/Digital oscillography

• Breaker health monitoring through KI2counter

• Per phase current metering for primary or secondary values

Low Priced Scaleable Options – Event Reports, Waveform Capture, Breaker Monitoring

Low Priced Scaleable Options – Event Reports, Waveform Capture, Breaker Monitoring

Page 9: MIF II DIGITAL FEEDER PROTECTION

9Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

TYPICAL WIRING

Page 10: MIF II DIGITAL FEEDER PROTECTION

10Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

User InterfaceDISPLAY & LEDS

KEYPAD

Text 2x16 displayMulticolor programmable LEDs with customizable label panel

ESC/RESET keyUP/DOWN keys for easy navigation ENTER functionMenu key

FRONT PORTElectrically isolated front RS232 communication port

HARDWARE

Easy to Use Man Machine Interface with Communication AccessEasy to Use Man Machine Interface with Communication Access

Page 11: MIF II DIGITAL FEEDER PROTECTION

11Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

DIMENSIONS

Compact Design in a Modular Package for Easy MaintenanceCompact Design in a Modular Package for Easy Maintenance

Page 12: MIF II DIGITAL FEEDER PROTECTION

12Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

enerVista MIF II Setup SoftwareMIIPC Software provides the following functions:

Logic

Metering

Oscillography

Settings

Powerful Configuration Tools That Get the MIF II up and Running in MinutesPowerful Configuration Tools That Get the MIF II up and Running in Minutes

Page 13: MIF II DIGITAL FEEDER PROTECTION

13Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

COMMUNICATIONS

• A front mounted RS232 and a rear RS485 port allow easy user interface via a PC.

• ModBus ® RTU protocol is used for all ports.• The relay supports baud rates from 300 to 19,200

bps. • Up to 32 MIF II relays can be addressed on a

single communications channel. A unique address must be assigned to each relay via a setting when multiple relays are connected.

Access to Information - Serial Communication and ModBus RTU ProtocolAccess to Information - Serial Communication and ModBus RTU Protocol

Page 14: MIF II DIGITAL FEEDER PROTECTION

14Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

***

MIF II ORDER CODE

Page 15: MIF II DIGITAL FEEDER PROTECTION

15Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

Feeder Protection - MIFII

Target Applications/Industries:• Low end three phase over current protection

• Simple re-closure applications

• Backup/auxiliary protection for transformers, generators and motors

• Replacement/upgrade of E/M devices

• Consultants, HQ engineering and end user utilities, OEM

• Simple overcorrect protection applications

Key Values:• Low priced scaleable options – event reports, waveform capture, reclosure, breaker fail

• Reduce troubleshooting and maintenance cost – Event reports, waveform capture

• Design flexibility – Easy to use programming logic

• Asset monitoring – Breaker health, and breaker failure protection

• Access to information – Modbus RTU communications

Sales Strategy:• Specify MIFII for low end feeder and reclosure applications

• Specify 735 for customers that desire draw-out capability

MIFII“M-Family – Cost Effective Digital Protection”

MIFII

SR 735/737

F650 F35

F60

SR 750/760

Functionality

PriceFMII

Most Cost Effective Offering for Low and Medium Voltage FeedersMost Cost Effective Offering for Low and Medium Voltage Feeders

Page 16: MIF II DIGITAL FEEDER PROTECTION

16Proprietary & ConfidentialGE Multilin – Sales Training, May 2-5, 2004

• Reliable feeder protection and control for Electrical Utilities and Industrial applications.

• User-friendly visual software for setting, monitoring, and metering. EnerVistacompatible.

• Password protected HMI for local operation.• Component based architecture for easy

switching of internal boards.• Communications via front RS232, and rear

RS485 ports.

MIF II SUMMARY

Web: www.GEindustrial.com/multilin

Tel: +1 905-294-6222

Fax: +1 905-201-2098

Email: [email protected]

Most Cost Effective Offering for Low and Medium Voltage FeedersMost Cost Effective Offering for Low and Medium Voltage Feeders