Automation and Drives
Low VoltageControls & Distribution
Introduction
Functions
Layout
Features
Diagnostics
Range
Protection
Applications
May‘2003A&D CD-BD
Microprocessor based Relays
Type 3RB12
Introduction
Automation and Drives
Low VoltageControls & Distribution
Introduction
Functions
Layout
Features
Diagnostics
Range
Protection
Applications
May‘2003A&D CD-BD
Range - 3RB12
3 Control voltages:110-120 V AC220-230 V AC24 V DC
6 Ranges from 1.25A to 820A
3RB12 46 1P… 1.25A to 6.3A
3RB12 46 1P… 6.3A to 25A
3RB12 46 1P… 25A to 100A
3RB12 53 0F… 50A to 205A
3RB12 57 0K… 125A to 500A
3RB12 62 0L… 200A to 820A
Range
Automation and Drives
Low VoltageControls & Distribution
Introduction
Functions
Layout
Features
Diagnostics
Range
Protection
Applications
May‘2003A&D CD-BD
Block diagram of internal construction
Micro-Processor
• Overload• Phase failure• Current unbalance• Thermistor monitoring• Ground fault monitoring• Self monitoring
Status memory
e.g. Overload/Thermistor trip:Output relay 1NO/1NC
e.g. Ground fault trip:Output relay 1NO/1NC
Summation CT
Thermistor connection
Hand/Remote/Auto-RESET
Test function
Set class
Set Ie
Integrated CT's
Motor current
Rectification
A/D-converter
Power supply
Control supply voltage
Self monitoring:Continuous
green LED "Ready"
Overload warning:Flashing
red LED "Overload"
Overload Thermistortrip: Continuous
red LED "Overload"
Ground fault:Continuous
red LED "Ground Fault"
Functions
Functions
Automation and Drives
Low VoltageControls & Distribution
Introduction
Functions
Layout
Features
Diagnostics
Range
Protection
Applications
May‘2003A&D CD-BD
A B
Device test,Hand-Reset
Selection of the trippingclasses: class 5 to 30
Ie setting, only three versions for the ranges from 1.25 A to 100 A
Connection for a thermistorsensor circuit for fullmotor protection
Control supplyvoltage connections
3 LED indicators
1NO+1NC for overloadtripping by currentand/or thermistor
1 NO+1 NC for groundfault tripping
Either Handreset (withTest-/Reset-button), remote or automatic reset
Connection for an external summation CTfor ground fault monitoring
Layout
Layout
Automation and Drives
Low VoltageControls & Distribution
Introduction
Functions
Layout
Features
Diagnostics
Range
Protection
Applications
May‘2003A&D CD-BD
Push-through main conductors ondevices with setting current rangeup to 100 A
The setting current range below 1.25 A is covered by looping the main conductors through the transducer (e.g. 3 loops for the range 0.42 A to 0.62 A)
No extra connection effort
No power loss in contact resistance
No failure / nuisance trip due to loose termination
Features
Features
Push-through technique
Automation and Drives
Low VoltageControls & Distribution
Introduction
Functions
Layout
Features
Diagnostics
Range
Protection
Applications
May‘2003A&D CD-BD
Monitoring of the current for overload, asymmetry and loss of phase by Lock rotor having CT in each of the three phases.
3RB12e110.ppt/10.97
120100
50
20
10
5
21
50
20
10
5
2
10.7 1 2 5 8
100
50
20
10
5
21
50
20
10
5
2
10.7 1 2 5 8
CLASS 30CLASS 25CLASS 20CLASS 15CLASS 10CLASS 5
CLASS 30CLASS 25CLASS 20CLASS 15CLASS 10CLASS 5
t t
x Ie x Ie
120
Tripping curves for 2 poleasymmetrical loading
Tripping curves for 3 polesymmetrical loading
Features
Features
Tripping characteristics
Automation and Drives
Low VoltageControls & Distribution
Introduction
Functions
Layout
Features
Diagnostics
Range
Protection
Applications
May‘2003A&D CD-BD
LED's direct on the unit:
Ready
Overload-trip/Thermistor-trip
Overload warning
Ground fault -trip
Externally with the NO / NC contacts:
Overload-trip / Thermistor-trip
Overload warning
Ground fault-trip
Diagnostics
Features
Display and Signals
Automation and Drives
Low VoltageControls & Distribution
Introduction
Functions
Layout
Features
Diagnostics
Range
Protection
Applications
May‘2003A&D CD-BD
Pressing the Test button:
• By pressing the test/reset button on the unit the current monitoring, thermistor and ground fault protection functions and LEDs can be checked. This test can be carried out during operation. (The contactor does not trip)
• If the Test/Reset button is pressed for more than 5 seconds then the trip functions of the signaling contacts are tested.
• A function test of the unit can be carried out at any time and is simple to effect.
Pressing the Test button:
• By pressing the test/reset button on the unit the current monitoring, thermistor and ground fault protection functions and LEDs can be checked. This test can be carried out during operation. (The contactor does not trip)
• If the Test/Reset button is pressed for more than 5 seconds then the trip functions of the signaling contacts are tested.
• A function test of the unit can be carried out at any time and is simple to effect.
Diagnostics
Diagnostics
Automation and Drives
Low VoltageControls & Distribution
Introduction
Functions
Layout
Features
Diagnostics
Range
Protection
Applications
May‘2003A&D CD-BD
L1L2L3
M3~
Connection of a PTC thermistor sensor circuit:
- The actual temperature in the motor winding is monitored
Needed with:- Motors whose stator is the critical
component- Motors with impeded cooling- Plated motor surface- Motors with long starting and braking
PTB-approval
Open circuit-proof
No additional evaluation unit required
Connection of a PTC thermistor sensor circuit:
- The actual temperature in the motor winding is monitored
Needed with:- Motors whose stator is the critical
component- Motors with impeded cooling- Plated motor surface- Motors with long starting and braking
PTB-approval
Open circuit-proof
No additional evaluation unit required
Protection
Protection Functions
Full motor protection(overload + thermistor protection)
Automation and Drives
Low VoltageControls & Distribution
Introduction
Functions
Layout
Features
Diagnostics
Range
Protection
Applications
May‘2003A&D CD-BD
L1L2L3N
M3~
Internally for motors with 3- wire connection
- ground fault monitoring with fault currents > 30% of the set current Ie
Externally for motors with 3 and 4 wire connections byconnection of a 3UL22 summation CT
- reliable earth fault monitoring with fault currents of 0.3A, 0.5A and 1A
1NO/1NC as separate outputs
- the fault can either be signaled on used to switch off the motor, independent of the overload protection.
Internally for motors with 3- wire connection
- ground fault monitoring with fault currents > 30% of the set current Ie
Externally for motors with 3 and 4 wire connections byconnection of a 3UL22 summation CT
- reliable earth fault monitoring with fault currents of 0.3A, 0.5A and 1A
1NO/1NC as separate outputs
- the fault can either be signaled on used to switch off the motor, independent of the overload protection.
Protection
Protection Functions
Ground fault monitoring
Automation and Drives
Low VoltageControls & Distribution
Introduction
Functions
Layout
Features
Diagnostics
Range
Protection
Applications
May‘2003A&D CD-BD
Applications
Chemical industries.
Paper/Plastics industries.
Steel Plant.
Water supplies.
Gas converting.
Paint plants......
Applications
High demand applications such as