Upload
catalincc
View
293
Download
1
Embed Size (px)
Citation preview
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 1/44
Version: P132 -308 -420/-421/-425/-426/-427 -632 ffIndex: BRelease: 09 / 2011
Technical Data Sheet
This document does not replace the technical Manual
MiCOM P132
Feeder Management and
Bay Control
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 2/44
[One-Box Solutions for Protection and Control] MiCOM P132 2
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Application and ScopeThe unit's protections functions provide selectiveshort-circuit protection, ground fault protectionand overload protection in medium- and high-voltage systems.
The systems can be operated as solidly-, low-
impedance or resonant-grounded or isolated.The multitude of protection functions enables theuser to cover a wide range of applications in theprotection of cable and lines, transformers andmotors.
For easy adaptation to varying system operationconditions four independent parameter subsetsare provided.
Alternatively the MiCOM P132 is optionally
deliverable with VT inputs only to be applied asover-/under frequency/voltage protection unit.
The optional control functions are designed forthe control of up to three electrically operatedswitchgear units located in the bay of a MV- or anon-complex HV- Station.
ANSI IEC 61850
Function
group
Function
only
VT´s
only
CT´s
CT s
an d
VT´s
50 P/Q/NDtpPhs-/DtpEft-/
DtpNgsPTCOxDTOC
Definite-time o/c protection, four stages, phase-
selective• •
51 P/Q/NItpPhs-/ItpEft-/
ItpNgsPTCOx
IDMT1/
IDMT2
Inverse-time o/c protection, single-stage, phase-
selective• •
67DtpPhs-/ DtpResRDIRx
SCDD Short circuit direction detection•
50 / 27
PSOF1 SOTF Switch onto fault protection • •
85 PSCH1 PSIG Protective signaling • •
79 RREC1 ARC Auto-reclosure control (3-pole) • •
25 RSYN1 ASC Automatic synchronism check ( • )
67W/YN PSDE1 GFDSS Ground fault direction determination ( wattmetric ) •
PTEF1 TGFD Transient ground fault direction dtermination ( • )1)
37/48/49/
49LR/50S/66
MotPMRI1/
MotPMSS1/
MotPTTR1/ ZMOT1
MP Motorprotection • •
49 ThmPTTR1 THERM Thermal overload protection • •
Coolant temperature measuring (using MEASI) ( • ) ( • )
46 UbpNgsPTOCx I2> Unbalance protection • •
27/59/47
P/Q/N
VtpPhs-/VtpNgs-/
VtpPss-
/VtpRefPTyVx
U<>Over/Undervoltage protection
• •
81 FrqPTyFx f<> Over- / Underfrequenceprotection • •
32/ 37
PdpAct-/
PdpRealPDyPxP<>
Directional power protection•
50/62BF RBRFx CBF Circuit breaker failure protection • •
XCBR1 CBM Circuit breaker monitoring • •
30/74 AlmGGIO1 MCMON Measuring circuit monitoring • • •
LIMIT Limit value monitoring • •
PHAR1 MAIN Inrushstabilizing • •
LGC PloGGIOx LOGIC Programmable logic • • •
LLN0.SGCB PSS Parameter subset selection • • •
Mmuxxx Measuring • • •
Analog inputs and outputs ( • ) ( • ) ( • )
26 RtdGGIO1 MEASI RTD input ( •
) ( •
) ( •
)IdcGGIO1 Measuring data input 20 mA, one settable input value ( • ) ( • ) ( • )
MEASOMeasuring data output 20 mA, two settable output
values( • ) ( • ) ( • )
PTRCx/ RDRE1 FT_RC Fault recording • • •
52 XCBRx, XSWIx, CS BM Control and monitoring of up to 3 switchgear units ( • ) ( • ) ( • )
CtlGGIO2 BEF_1 Single-pole commands ( • ) ( • ) ( • )
CtlGGIO1 MEL_1 Single-pole signals ( • ) ( • ) ( • )
LGC V_LOG Interlocking logic ( • ) ( • ) ( • )
16S KOMMx 2 Communication interfaces serial, RS 422/485 or FO ( • ) ( • ) ( • )
CLK IRIGB Time synchronisation IRIG-B ( • ) ( • ) ( • )
16E IEC Communication interface Ethenet ( • ) ( • ) ( • )
16E GosGGIOx GOOSE IEC 61850 ( •
) ( •
) ( •
)
16S FKT_T 6 Function keys ( • )1)
( • )1)
( • )1)
• = STANDARD; ( • ) = ORDER OPTION; ( · )1) = Not for P132 in 24 TE
Functional overview P132
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 3/44
[One-Box Solutions for Protection and Control] MiCOM P132 3
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
The MiCOM P132 provides over 80 predefinedbay types for simple efficient configuration ofSwitchgear control functions.
External auxiliary devices are largely obviatedthrough the integration of binary inputs andpower outputs that are independent of auxiliaryvoltages, by the direct connection option forcurrent and voltage transformers and by thecomprehensive interlocking capability.
This simplifies handling of the protection andcontrol technology for HV- or MV- Feeder fromplanning to put into operation.
The MiCOM P132 provides an extensive numberof functions which can select individually forinclusion in the unit's configuration or cancelthem as desired. By means of a straight-forwardconfiguration procedure, the user can adapt thedevice flexibly to the scope of protection requiredin each particular application. Due to the
powerful, freely configurable logic of the device,special applications can be accommodated.
Following global functions are available in theMiCOM P132:
• Parameter subset selection (4 subsets)
• Measured operating data to support the userduring commissioning, testing and operation
• Operating data recording (time-tagged signal)
• Overload data acquisition1)
• Overload recording (time-tagged signal) )
• Ground fault data acquisition
• Ground fault recording (time-tagged signal)
• Measured fault data
• Fault data acquisition
• Fault recording (time-tagged signal)(logging together with fault value recording ofthe three phase currents, the residual current,the three phase-to-ground voltages and the
neutral displacement voltage).
Setting tool MiCOM S1 Studio
Scheme signaling
50/27
SOTF
67
SCDD
46
I2>
50/ 51 P/Q/N
DTOC
51 P/Q/N
IDMT_1
85
PSIG
27/59 P/Q/N
V<>
LGC
LOGIC
LIMIT
25
ASC
LGC
ILOCK
I
V
Vref
SIG_1CMD_1
26
MEASI
conventionalserial
Feeder Management and
Bay Control Unit MiCOM P1321)
16S
COMM1
16S
COMM2
16E
IEC
CBM
50/62BF
CBF
52
DEV
77
InterMiCOM
CLK
IRIGB
32/37
P<>
51 P/Q/N
IDMT_2
49
THERM
MEASO
TGFD
67 W/YN
GFDSS
30/74
MCMONMCMON
79
ARC
37/48/49/50S/66
MP
81
f<>
Further
options
Always
available
Optional
VT´s fitted
Optional Control /
Monitoring of up to
3 switchgear units
Communication
to SCADA / substation control / RTU / modem ...
via RS485 or Fiber optics
using IEC 60870-5-101, -103, Modbus, DNP3, Courier
resp.
via RJ45 or Fiber optics using IEC 61850
Self
Monitoring
Recording and
Data
Acquisition
Metering
Overload rec.
Ground flt. rec.
Fault rec.
Function diagram
1) Function diagram for P132 with CT inputs and P132 with CT and VT inputs in 40TE resp. In 84TE case
Function overview for P132 with VT inputs only resp. In 24TE case please see table "functions overview "
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 4/44
[One-Box Solutions for Protection and Control] MiCOM P132 4
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
DesignThe MiCOM P132 is of modular design. The
pluggable modules are housed in a robustaluminum case and electrically connected via ananalog and a digital bus printed circuit board.
The MICOM P132 has the following inputs and
outputs: • 4 current-measuring inputs
• 4 or 5 voltage-measuring inputs
• 4 binary inputs and 8 output relays
As further option one control board with 6 binarysignal inputs (optical couplers) and 6 outputrelays for the control of 3 switchgear units (2-polecontacts).
Furthermore up to 36 additional binary signalinputs (optical couplers) with freely configurablefunction assignment for individual control or
protection signals and up to 18 additional outputrelays with freely configurable functionassignment for individual control or protectionapplications can be configured.
Alternatively up to 16 high break output relaysapplicable for DC circuits with max. breakingcapability of 2500 W inductive (L/R = 40 ms) or10 A at 250 VDC are configurable.
The nominal currents or the nominal voltages,respectively, of the measuring inputs can be setwith the help of function parameters.
The nominal currents or the nominal voltages,
respectively, of the measuring inputs can be setwith the help of function parameters.
The nominal voltage range of the standard opticalcoupler inputs is 24 to 250 V DC without internal
switching. Optional there are also other rangeswith higher pick-up thresholds possible.
The auxiliary voltage input for the power supply isa wide-range design as well. The nominal voltageranges are 48 to 250 V DC and 100 to 230 V AC.
An additional version is available for the lowernominal voltage range of 24 V DC.
All output relays are suitable for both signals and
commands.
The optional resistance temperature detector(RTD) inputs are lead compensated andbalanced. The optional 0 to 20 mA input providesopen-circuit and overload monitoring, zerosuppression defined by a setting, plus the optionof linearizing the input variable via 20 adjustableinterpolation points.
Two freely selected measured signals (cyclicallyupdated measured operating data and storedmeasured fault data) can be output as a load-independent direct current via the two optional 0
to 20 mA outputs. The characteristics are definedvia 3 adjustable interpolation points allowing aminimum output current (4 mA, for example) forreceiver-side open-circuit monitoring, knee-point
definition for fine scaling and a limitation to lowernominal currents (10 mA, for example). Wheresufficient output relays are available, a freelyselected measured variable can be output inBCD-coded form via contacts.
Control and display
• Local control panel with LC-display
• 6 function keys (available for 40TE and 84TE)
• 23 LED’s, 18 configurable(Red/Green/Yellow)(24TE: 10 unicoloured LED’s, 5 configurable ).
• PC interface
• Communication interfaces (optional)
• IRIG-B signal input (optional)
• Protection communication interfaceInterMiCOM (optional)
24TE, 40TE and 84TE Mounting case options
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 5/44
[One-Box Solutions for Protection and Control] MiCOM P132 5
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Function keys(available in 40T and 84T case)
The MiCOM P132 has six freely configurablefunction keys. A single function can be assignedto each function key. So circuit breakers andfunctions can be switched on or off and recorded
information can be reseted directly via functionkey.
Instead of a single function, a menu jump listswith up to 16 elements can be assigned. Settingparameters, event counters and/or event recordscan be selected into a menu list. Repeatedpressing of the relevant function key will thensequentially trigger the element of the selectedmenu jump list.
For each function key, the user can define anoperating mode suitable to the assignedfunctionality. To guard against inadvertent or
unauthorized use each function key is protectedwith a password.
Detachable HMI(available in 40T and 84T case)
For remote mounting in switch gears theMiCOM P132 can be equipped with a detachable
HMI. This design has the advantage of acomfortable device handling even in switch gearswith protection arrangements difficult to access.
Detachable HMI mounted a MV switchgear
The design of the protection device MiCOM P132
allows a connection or disconnection to thedetachable HMI at any time. The HMI hardwaremodule will be completely and automaticallyrecognized.
The visualisation of the device status is done viathe display of the HMI and via 4 LED`s at thebasic device.
Even if the detachable HMI is lacking all devicefunctions are completely warranted. With aconnected HMI the PC-interface of the devicecannot be enabled.
To connect the basic device and the detachableHMI standardised cable (Ethernet cable, max.length 10 m) can be used. One connection cableof three meter length is included in theMiCOM P132 scope of delivery.
Basic device with detachable HMI
Information interfaces(optional)
Information exchange is done via the local controlpanel, the PC interface and 2 optionalcommunication interfaces.
The first communication interface has settableprotocols conforming to IEC 60870-5-103,
IEC 60870-5-101, DNP 3.0, Modbus and Courier
(COMM1) or provides alternatively protocolconforming to IEC 61850 (IEC). It’s intended forintegration in substation control systems.
The 2nd communication interface (COMM2)conforms to IEC 60870-5-103 and is intended forremote setting access only.
Clock synchronization can be achieved using oneof the protocols or using the IRIG-B signal input.
Additionally, the optional InterMiCOM interface(COMM 3) allows a direct transfer of any digitalstatus information between two devices.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 6/44
[One-Box Solutions for Protection and Control] MiCOM P132 6
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Main functions
Main functions are autonomous function groupsand can be individually configured or disabled tosuit a particular application. Function groups thatare not required and have been disabled by theuser are masked completely (except for the
configuration parameter) and functional supportis withdrawn from such groups.
This concept permits an extensive scope offunctions and universal application of the devicein a single design version, while at the same timeproviding for a clear and straight-forward settingprocedure and adaptation to the protection andcontrol task under consideration.
Overcurrent protection
For the overcurrent protection stages the threephase currents, residual current and negative-
sequence current determined from the filteredfundamental wave of the three phase currents areevaluated in separate, single stage measuringsystems.
For the residual current stage the use of theresidual current measured directly or calculatedfrom the three phase currents is offered forselection. The residual and negative-sequencecurrents stages affect the general starting signal.This effect can be suppressed if desired.
Additionally, the operate values of all overcurrentstages can be set as dynamic parameters. For asettable hold time, switching to the dynamicoperate values can be done via an externalsignal. Once the hold time has elapsed, the staticoperate values are reinstated.
Definite time overcurrent protection
Definite-time overcurrent protection is providedfor the three phase currents and the negative-sequence current with three timer stages and forthe residual current with four timer stages. Forthe fourth residual current stage - with extendedsetting range - the calculated residual current isalways used.
Starting of the phase current stage I> and thenegative-sequence current stage Ineg> can bestabilized under inrush conditions if desired. Thephase current stages I>> and I>>> and thenegative-sequence current stages Ineg>> andIneg>>> are never affected by this stabilizationprocedure.
Intermittent starting of the residual current stageIN> can be accumulated over time by means of asettable hold time. If the accumulated startingtimes reach the trip limit value (which is alsoadjustable by setting) then a trip with selective
signaling ensues.
Inverse time overcurrent protection
For the inverse-time overcurrent protectionstages the three phase currents, residual currentand negative-sequence current are evaluated inseparate, single stage measuring systems.
For the individual measuring systems, the usercan select from a multitude of trippingcharacteristics.
Starting of the phase current stage and thenegative-sequence current stage can bestabilized under inrush conditions if desired.
Intermittent starting of the phase, negative-sequence or residual current stage can beaccumulated on the basis of the set trippingcharacteristic by means of a settable hold time.Tripping is also performed in accordance with therelevant tripping characteristic.
No Tripping time characteristic
k= 0.01 … 10.00) A B C R
0 Definite Time
per IEC 255-3
1 Normally inverse 0,14000 0.02000
2 Very inverse 13.50000 1.00000
3 Extremely inverse 80.00000 2.00000
4 Long time inverse 120.00000 1.00000
per ANSI / IEEE C37.112 Trip
Release
5 Moderately inverse 0.05150 0.02000 0.11400 4.85000
6 Very inverse 19.61000 2.00000 0.49100 21.60000
7 Extremly inverse 28.20000 2.00000 0.12170 29.10000
per ANSI Trip
Release
8 Normally inverse 8.93410 2.09380 0.17966 9.00000
9 Short time inverse 0.26630 1.29690 0.03393 0.50000
10 Long time inverse 5.61430 1.00000 2.18592 15.75000
not per standard
11 RI-type inverse
not per standard
12 RXIDG-type inverse
Constants and formulae (t in s)
kt =
1I
I
Akt
B
B
−⎟⎟ ⎠
⎞⎜⎜⎝
⎛ ⋅=
⎟⎟⎟⎟⎟
⎠
⎞
⎜⎜⎜⎜⎜
⎝
⎛
−
−⎟⎟ ⎠
⎞⎜⎜⎝
⎛ ⋅= C
1I
I
Akt
B
B
1I
I
Rkt
B
B
r
−⎟⎟ ⎠
⎞⎜⎜⎝
⎛ ⋅=
⎟⎟ ⎠
⎞⎜⎜⎝
⎛ −
⋅=
BI
I
236.0339.0
1kt
⎟⎟ ⎠
⎞⎜⎜⎝
⎛ ⋅−⋅=
BI
Iln35.18.5kt
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 7/44
[One-Box Solutions for Protection and Control] MiCOM P132 7
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Short-Circuit Direction Determination
Due to the short-circuit direction determinationfunction, the MiCOM P132 can be used as a
directional time-overcurrent protection device.For the individual overcurrent timer stages theuser may select whether the stage shall be
forward-directional, backward-directional or non-directional. Direction determination is performedin separate measuring systems for the phasecurrent and residual current timer stages,respectively.
In the direction-measuring system for the phasecurrent timer stages, the phase-to-phase voltageopposite to the selected phase current is used fordirection determination as a function of the typeof fault, and an optimum characteristic angle isemployed (see table “Directional characteristicsin short-circuit direction determination ”). A
voltage memory is integrated to provide therequired voltage data for direction determinationin the event of 3-pole faults with a large 3-phasevoltage drop.
In the direction measuring system for the residualcurrent timer stages, direction is determinedusing the internally computed neutraldisplacement voltage; the characteristic angle isadjustable taking account of the various neutral-point treatments in the system. The directionmeasuring system for the residual current timerstages is not enabled until a set value for neutraldisplacement voltage is exceeded. The user may
select whether the triggering pre-orientation for anon-enabled direction measuring system forresidual current timer stages shall be blocked inthe event of phase current starting.
Meas.-
systemStarting
Characteristic
angle1)
I
meas
U
meas
P
bzw.
N
P A I1 VBC=VBN-VCN +45°
B I2 VCA =VCN-V AN +45°
C I3 V AB=V AN-VBN +45°
A-B I1 VBC=VBN-VCN +60°
B-c I3 V AB=V AN-VBN +30°
C-A I3 V AB=V AN-VBN +60°
A-B-C I3 V AB=V AN-VBN +45°
G GF IN VNG=
1/3(V AN+VBN+VCN )
-90°…+90°
(adjustable)
1) for phase sequence A - B - C
Variables selected for measurement
Protective Signaling
Protective signaling can be used in conjunctionwith short-circuit direction determination. For thispurpose the protection devices must be suitablyconnected by pilot wires or the optionalprotection interface InterMiCOM on both ends ofthe line section to be protected. The user may
select whether teleprotection will be controlled bythe direction measuring system of the phasecurrent timer stages only, by the directionmeasuring system of the residual current timerstages only, or by the direction measuringsystems of the phase current and residual currenttimer stages. For protection devices on the infeedside of radial networks, teleprotection can also becontrolled without the short-circuit directiondetermination function.
Protection Interface InterMiCOM
(Optional)InterMiCOM allows high performance permissiveand blocking type unit protection to beconfigured, plus transfer of any digital statusinformation between line ends. Intertripping issupported too, with channel health monitoringand cyclic redundancy checks (CRC) on thereceived data for maximum message security.
InterMiCOM provides eight end-end signal bits,assignable to any function within a MiCOMrelay’s programmable logic.
Default failsafe states can be set in case of
channel outage.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 8/44
[One-Box Solutions for Protection and Control] MiCOM P132 8
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Switch on to Fault Protection
Closing of a circuit breaker might inadvertentlylead to a short-circuit fault due to a feedergrounding connection not yet removed, forexample.
The manual close command is monitored for a
settable period of time. During this period, anundelayed trip command may be issuedautomatically on initialisation of the generalstarting (depending on the chosen operatingmode).
Auto-Reclosing Control
The auto-reclosing control (ARC) operates inthree-phase mode. ARC cycles with one high-speed reclosing (HSR) and multiple (up to nine)subsequent time-delay reclosing (TDR) may beconfigured by the user. Reclosing cycles withoutprior HSR are possible. For special applications,tripping prior to an HSR or TDR can be delayed.HSR and TDR reclosings are counted andsignaled separately. A test HSR can be triggeredvia any of the unit's interfaces.
Automatic Synchronism Check(Optional)
This function can be used in conjunction withautomatic or manual (re)closure or closecommand of the control functions. In non-radial
networks this ensures that reclosure or closecommand will proceed only if the synchronismconditions are met.
For the control functions a second mode with adecoupled operation of the automaticsynchronism check and close command isavailable.
Over-/Underfrequency Protection
Over-/underfrequency protection has four stages.Each of these can be operated in one of thefollowing modes:
• Over-/underfrequency monitoring
• Over-/underfrequency monitoring combinedwith differential frequency gradientmonitoring (df/dt) for system decouplingapplications
• Over-/underfrequency monitoring combinedwith medium frequency gradient monitoring
( Δf/ Δt) for load shedding applications
Over-/Undervoltage Protection
The over-/undervoltage-time protection functionevaluates the fundamental wave of the phasevoltages, reference voltage and of the neutraldisplacement voltage as well as the positive-sequence voltage and negative-sequence voltage
obtained from the fundamental wave of the threephase-to-ground voltages.
Two definite-time-delay overvoltage stages eachare provided for evaluation of the neutraldisplacement voltage and negative-sequencevoltage.
Two additional definite-time-delay undervoltagestages each are provided for evaluation of thephase voltages and the positive-sequencevoltage. As an option, a minimum current levelcan be specified to enable the undervoltagestages.
Evaluation of the phase voltages can beperformed using either the phase-to-phasevoltages or the phase-to-ground voltages asdesired. For evaluating the neutral displacementvoltage, the user may choose between theneutral displacement voltage formed internallyfrom the three phase-to-ground voltages and theneutral displacement voltage formed externally(from the open delta winding of the voltagetransformer, for example) via the fourth voltagemeasuring input.
Directional Power ProtectionThe directional power protection monitorsexceeding the active and reactive power limit, apower drop and the reversal of direction atasymmetrically operated lines.
Evaluation of the power is performed using thefundamental wave of the phase currents and ofthe phase-to-ground voltages.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 9/44
[One-Box Solutions for Protection and Control] MiCOM P132 9
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Circuit Breaker Failure Protection
With the trip command, two timer stages arestarted for circuit breaker action monitoring. If thecurrent is still in excess of a set current thresholdafter the first timer stage has elapsed, a furthertrip command is issued. This could be used to
trigger a second trip coil, for example.Should the protection criterion continue to bemet after the second timer stage has elapsed, atrip command is issued to a higher-levelprotection system.
If a 'circuit breaker failure' signal is received viaan appropriately configured binary input while thegeneral starting condition persists, a CBF tripsignal is issued.
Circuit Breaker Monitoring
This function provides the user with severalcriteria for the assessment of circuit breakerwear:
• Calculated number of remaining operationsbased on the CB wear curve
• Mechanical operations count
• Interrupted currents sum (linear and squared)
• Accumulated current-time integrals of trips
For each of these criteria, a signaling thresholdcan be set by the user.
Circuit breaker wear curve
100000
10
100
1000
10000
0,1 1 10 100
Tripped current [kA]
If the CBM function is blocked, the accumulatedvalues and counts are frozen so that they remainunchanged by secondary protection testing.
To connect the basic device and the detachableHMI standardised cable (Ethernet cable, max.length 10 m) can be used. One connection cableof three meter length is included in theMiCOM P132 scope of delivery.
The settings of the accumulated values andcounts can be adjusted to allow for prior CBwear, CB servicing etc.
Ground-Fault Direction Determination
For the determination of the ground-fault
direction in isolated or Peterson-coilcompensated power systems several provenmethods are provided:
• Steady-state power or admittance evaluationmethods - complemented by signalingschemes and tripping logic
• Transient signal method (optional)
Ground Fault Direction DeterminationUsing Steady-State Values
The ground fault direction is determined by
evaluating the neutral displacement voltage andthe residual current (from a core balance orwindow-type current transformer). The directional
characteristic (cos ϕ or sin ϕ circuit) can be set tosuit the neutral-point treatment (resonant-
grounded or isolated-neutral). In the cos ϕ mode(for a resonant-grounded network), the adjustablesector angle also has an effect so that faultydirection decisions (resulting, for instance, fromthe phase angle error of the CT and VT) can besuppressed effectively. Operate sensitivity andsector angle can be set separately for the forwardand backward direction, respectively.
Either steady-state power or steady-stateadmittance can be selected for evaluation.
Alternatively, an evaluation based on current onlycan be performed. In this case, only themagnitude of the filtered neutral current is usedas ground fault criterion.
Both procedures operate with either the filteredfundamental wave or the fifth harmoniccomponent in accordance with the chosensetting.
Transient Ground Fault DirectionDetermination(Optional)
The ground fault direction is determined byevaluating the neutral displacement voltagecalculated from the three phase-to-groundvoltages and the neutral current on the basis ofthe transient ground fault measuring procedure.The direction decision is latched. The user mayselect either manual or automatic resetting after aset time delay.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 10/44
[One-Box Solutions for Protection and Control] MiCOM P132 1
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Motor Protection
For the protection of directly switched h.v.induction motors with thermally critical rotor, thefollowing specially matched protection functionsare provided:
• Recognition of operating mode
• Rotor overload protection using a thermalmotor replica
• Motor operation hours run counter (controlfunctionality)
• Choice of reciprocally quadratic orlogarithmic tripping characteristic
• Inclusion of heat dispersion processes in therotor after several startups
• Separate cooling periods for rotating andstopped motors
• Startup repetition monitoring with reclosureblocking (see Figure 4)
• Control logic for heavy starting andprotection of locked rotor
• Loss of load protection
m
[%]
100
80
40
20
321
t
t
60
t
t
Overload Memory
Permissible number of StartupsBlocking
Three successive startups
Motor Start-Up Supervision
Using the optional resistance temperaturedetector inputs direct monitoring of thetemperature of the stator windings and thebearings can be realized.
Unbalance Protection
The negative-sequence current is determinedfrom the filtered fundamental wave of the threephase currents. The evaluation of the negative-sequence current is performed in two time-overcurrent stages with definite-time delay.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 11/44
[One-Box Solutions for Protection and Control] MiCOM P132 11
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Thermal Overload Protection
Using this function, thermal overload protectionfor lines, transformers and stator windings of h.v.motors can be realized. The highest of the threephase currents serves to track a first-orderthermal replica according to IEC 255-8. The
tripping time is determined by the set thermaltime constant τ of the protected object and the
set tripping level Δϑtrip and depends on the
accumulated thermal load Δϑ0:
t = ln.
I
Iref
2
- 0
I
Iref
2
- Trip
The temperature ot the cooling medium can be
taken into account in the thermical replica usingthe optional resistance temperature inputs or the0 to 20 mA input.
The user has a choice of using a thermal replicaon the basis of either relative or absolutetemperature.
A warning signal can be issued in accordance
with the set warning level Δϑwarning. As an
alternative method of generating a warning, thecyclically updated measured operating value ofthe predicted time remaining before tripping ismonitored to check whether it is falling below aset threshold.
Limit Monitoring
The phase currents, the phase-to-groundvoltages and the phase-to-phase voltages aremonitored. For 3-phase sets, the highest and thelowest value is determined. Also the neutraldisplacement and the reference voltage, thetemperatures of the resistance temperaturedetectors and the value of the linearised 0 to 20mA input are monitored. The evaluations uses anoperate value and time delay set by the user.Thereby, all values can be monitored forexceeding an upper limit or falling below a lowerlimit.
Limit value monitoring is not a fast protectionfunction and is intended to be used formonitoring and signaling purposes e.g. limittemperature monitoring.
Temperature detection of a motor for Limit monitoring and Thermal overload protection
RTD PhaseL1 L2 L3
RTD
Ambient temperature/Cooling temperature
Bearing
Prime Sensor
Backup Sensor
RTD
RTD
R T D
R T D
R T D
R T D
R T D
R T D
R T D
Stator R T D
Stator
Rotor
R T D
R T D
Bearing
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 12/44
[One-Box Solutions for Protection and Control] MiCOM P132 12
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Programmable Logic
User-configurable logic enables the user to setup logic operations on binary signals within aframework of Boolean equations. By means of astraightforward configuration procedure, any ofthe signals of the protection device can be linked
by logic 'OR' or 'AND' operations with thepossibility of additional negation operations.
The output signal of an equation can be fed into afurther, higher-order equation as an input signalthus leading to a set of interlinked Booleanequations.
The output signal of each equation is fed to aseparate timer stage with two timer elementseach and a choice of operating modes. Thus theoutput signal of each equation can be assigned afreely configurable time characteristic.
The two output signals of each equation can be
configured to each available input signal. Theuser-configurable logic function is then able toinfluence the individual functions without externalwiring (block, reset, trigger, for example).
Via non-storable continuous signals, monostabletrigger signals and bistable storedsetting/resetting signals, the Boolean equationscan be controlled externally via any of thedevice's interfaces.
Programmable logic
Output
signalsFunction groups
Spec. application
(programmable)
LOGIC
HMI
INP
F_KEY
PC
COMM1
COMM2
COMM3
GOOSE
Fixed device logic
DTOC, IDMT
ARC, THERM, ...
Input
signals
HMI
OUTP
LED
PC
COMM1
COMM2
COMM3
GOOSE
Measured Data Input(Optional)
The optional analog I/O module provides a 0 to20 mA input for the acquisition of externallymeasured variables such as transducer outputs.The external input characteristics can be
linearized via adjustable interpolation points. Thisfeature also provides for an adaptation of therange to, for example, 4 to 20 mA or 0 to 10 mA.
The RTD module is equipped with 9 resistancetemperature detectors for direct temperatureacquisition. Depending on the set operatingmode, all the RTD's operate in parallel or theRTD's can be subdivided into regular inputs andreserve inputs which take over when thecorresponding regular inputs fail.
The measured variables acquired by the analogdata input function are monitored for exceeding
or falling below set limits. Furthermore, they areused by thermal overload protection function forthe acquisition of the coolant temperature.
Measured Data Output
The protection device provides the options ofoperating data output and fault data output. Theuser can select an output in BCD-coded formthrough relay contacts or an output in analogform as load-independent current (0 to 20 mA).For an output in BCD-coded form, an appropriatenumber of free output relays need to be available.
For the current output, a special analog I/Omodule is required.
Measuring-Circuit Monitoring
Measuring-circuit monitoring includes themonitoring of the phase currents and phase-to-phase voltages.
Phase current monitoring is based on theprinciple of maximum allowable magnitudeunbalance, whereby the arithmetic differencebetween the maximum and minimum phasecurrents - as referred to the maximum phase
current - is compared to the set operate value.Even with an economy-type CT connection (CT’sin only two phases) it is possible to monitor thephase currents given appropriate settings.
Phase-to-phase voltage monitoring is based on aplausibility check involving the phase currents. Ifa low current threshold setting is exceeded by atleast one phase current, the three phase-to-phase voltages are monitored for a set minimumlevel. In addition to magnitude monitoring, phasesequence monitoring of the phase-to-phasevoltages may be activated.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 13/44
[One-Box Solutions for Protection and Control] MiCOM P132 13
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Control Functions(optional)
The optional control functions of theMiCOM P132 are designed for the control of upto three electrically operated switchgear unitsequipped with electrical check-back signaling.
For this task, the MiCOM P132 is fitted with theoptional binary I/O module X (6I/6O) for thecontrol of switchgear units. This module providesbinary inputs for the acquisition of switchingpositions and output relays for switchingcommands.
For the control of switchgear units either thebinary inputs or the optional communicationinterface or the function keys of the local controlpanel can be used.
Up to 12 single-pole operating signals can beacquired and processed in accordance with their
significance for the substation (circuit breakerreadiness, for example). For the setting of thedebounce and chattering times, threeindependent setting groups are available. Thesecan be assigned to the switching positionsignaling inputs and single-pole operatingsignals.
The MICOM P132 issues switching command
outputs with the integration of switchingreadiness and permissibility tests; subsequentlythe MiCOM P132 monitors the intermediate
position times of the switchgear units. If aswitchgear malfunction is detected, this fact will
be indicated (e.g. by an appropriately configuredLED indicator).
Before a switching command output is executed,the interlocking logic of the MiCOM P132 will
check whether the new switchgear unit statecorresponds to a permissible bay or substationtopology. The interlocking logic is set out foreach bay in the default setting as bay interlockwith and without station interlock. By means of astraight-forward parameter setting procedure, theinterlocking equations can be adapted to theprevailing bay and substation topology. The
presentation and functioning of the interlockingsystem correspond to those of the programmablelogic.
For integration of the MiCOM P132 into anintegrated control system, the equations for thebay interlock with station interlock form the basisof interlock checking.
Without integration into the substation controlsystem or with integration using IEC 61850, thebay interlock without station interlock is used ininterlock checking; external ring feeders orsignals received via IEC 61850 may be includedin the interlocking logic.
If the bay or station topology (as applicable) ispermissible then the switching command isissued. If a non-permissible state would resultfrom the switching operation then the switchingcommand is rejected and a signal to this effect isissued.
If the bay type does not require all binary outputsthen the remaining outputs are available for freeconfiguration.
In addition to the switching command output, atriggering of binary outputs by continuouscommands is possible.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 14/44
[One-Box Solutions for Protection and Control] MiCOM P132 14
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Global Functions
Functions operating globally allow the adaptationof the unit's interfaces to the protected powersystem, offer support during commissioning andtesting and provide continuously updatedinformation on the operation, as well as valuable
analysis results following events in the protectedsystem.
Clock Synchronization
The device incorporates an internal clock with aresolution of 1ms. All events are time-taggedbased on this clock, entered in the recordingmemory according to their significance andsignaled via the communication interface. Alternatively two external synchronization signalscan be employed. Using one of thecommunication protocols Modbus, DNP3,IEC 60870-5-103, IEC 60870-5-101 or IEC 61850,
the device will be synchronized by a timetelegram from a higher-level substation controlsystem. Alternatively, it can be synchronized viathe IRIG-B signal input. The user can select aprimary and a backup source for synchronization.The internal clock will then be adjustedaccordingly and operate with an accuracy of±10 ms if synchronized via protocol and ±1ms if
synchronized via IRIG-B signal.
Parameter Subset Selection
The function parameters for setting the protection
functions are, to a large extent, stored in fourindependent parameter subsets. Switchingbetween these subsets is readily achieved viaany of the device's interfaces.
Operating Data Recording
For the continuous recording of processes insystem operation or of events, a non-volatile ringmemory is provided. The relevant signals, eachfully tagged with date and time at signal start andsignal end, are entered in chronologicalsequence. Included are control actions such asthe enabling or disabling of functions as well as
local control triggering for testing and resetting.The onset and end of events in the network, asfar as these represent a deviation from normaloperation (overload, ground fault or short-circuit,for example) are recorded.
Overload Data Acquisition
Overload situations in the network represent adeviation from normal system operation and canbe permitted for a brief period only. The overloadprotection functions enabled in the devicerecognize overload situations in the system and
provide for acquisition of overload data such asthe magnitude of the overload current, therelative heating during the overload situation andits duration.
Overload Recording
While an overload condition persists in thenetwork, the relevant signals, each fully taggedwith date and time at signal start and signal end,are entered into a non-volatile memory inchronological sequence. The measured overloaddata, fully tagged with the date and time ofacquisition, are also entered. Up to eightoverload situations can be recorded. If more thaneight overload situations occur without interimmemory clearance then the oldest overloadrecording is overwritten.
Ground Fault Data Acquisition
While a ground fault in a network with isolatedneutral or resonant grounding represents asystem fault, it is usually nevertheless possible, inthe first instance, to continue system operationwithout restrictions. The ground faultdetermination functions enabled in the protection
device recognize ground faults in the system andprovide for the acquisition of the associatedground fault data such as the magnitude of theneutral displacement voltage and the ground faultduration.
Ground Fault Recording
While a ground fault condition persists in thepower system, the relevant signals, each fullytagged with date and time at signal start andsignal end, are entered into a non-volatilememory in chronological sequence. Themeasured ground fault data, fully tagged with the
date and time of acquisition, are also entered. Upto eight ground faults can be recorded. If morethan eight ground faults occur without interimmemory clearance then the oldest ground faultrecording is overwritten.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 15/44
[One-Box Solutions for Protection and Control] MiCOM P132 15
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Fault Data Acquisition
A short-circuit within the network is described asa fault.
The short-circuit protection functions enabled inthe devices recognize short-circuits within thesystem and trigger acquisition of the associated
measured fault data such as the magnitude of theshort-circuit current and the fault duration.
As acquisition time, either the end of the fault orthe start of the trip command can be specified bythe user.
Triggering via an external signal is also possible.The acquisition of the measured fault data isperformed in the measuring loop selected by theprotective device and provides impedances andreactances as well as current, voltage and anglevalues.
The fault distance is determined from the
measured short-circuit reactance and is read outwith reference to the set 100% value of theprotected line section.
The fault location is output either with eachgeneral starting or only with a general startingaccompanied by a trip (according to the user'schoice).
Fault Recording
While a fault condition persists in the powersystem, the relevant signals, each fully tagged
with date and time at signal start and signal end,are entered into a non-volatile memory inchronological sequence.
The measured fault data, fully tagged with thedate and time of acquisition, are also entered.Furthermore, the sampled values of all analoginput variables such as phase currents andneutral current, phase-to-ground voltages andneutral displacement voltage are recorded duringa fault.
Up to eight faults can be recorded. If more thaneight faults occur without interim memoryclearance then the oldest fault recording isoverwritten.
Self-Monitoring
Comprehensive self-monitoring procedureswithin the devices ensure that internal hardwareor software errors are detected and do not causemalfunctions of the device.
As the auxiliary voltage is turned on, a functional
test is carried out. Cyclic selfmonitoring tests arerun during operation.
If test results deviate from the default value thenthe corresponding signal is entered into the non-volatile monitoring signal memory.
The result of the fault diagnosis determineswhether a blocking of the protection and controlunit will occur or whether a warning only isissued.
Password protection
For variable configuration requirements thedevices are provided with a settable default –
password.
If required the function keys available with thetext HMI can be provided with settable barriers(password for each of the keys).
Access barriers protect the enter mode or thefunction keys in order to guard againstinadvertent or unauthorized changing ofparameter settings or triggering of controlfunctions.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 16/44
[One-Box Solutions for Protection and Control] MiCOM P132 16
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Local Control
All data required for operation of theMiCOM P132 are entered from the integratedlocal control panel, and the data important forsystem management are read out there as well.The following tasks can be handled via the local
control panel:• Switchgear control
• Readout and modification of settings
• Readout of cyclically updated measuredoperating data and state signals
• Readout of operating data logs and ofmonitoring signal logs
• Readout of event logs (after overloadsituations or short-circuits in the powersystem)
• Resetting of the unit and triggering of further
control functions designed to support testingand commissioning tasks
The MiCOM P132 local control panel (HMI)comprises the local control elements andfunctions described below.
Operation
(1) The integrated local control panel has agraphical back-lit LCD Display with 4 x 20resp. 16 x 21 alphanumeric characters.
23 resp. 17 LED indicators are provided for signal
display. A separate adhesive label is provided foruser-defined labeling of these LED indicatorsaccording to the chosen configuration.
(2) 5 LED indicators are permanently assigned tosignals.
(3) The remaining 18 LED indicators are availablefor free assignment by the user and can beconfigured for the colors red, green or yellow.Furthermore different operation and flashingmodes are available.
Menu tree
(4) By pressing the navigation keys
, , and guided by the LCDdisplay, the user moves within a plain textmenu. All setting parameters and measuredvariables as well as all local control functionsare arranged in this menu which isstandardized for all devices of the system.Changes to the settings can be prepared and
confirmed by means of the Enter Key
G which also serves to trigger local controlfunctions.In the event of erroneous entries, exit from theenter mode with rejection of the entries ispossible at any time by means of the
Clear Key
C When the edit mode is not
activated, pressing the Clear Key has theeffect of resetting the indications.
Pressing the Read Key provides directaccess to a preselected point in the menu.
Function keys
(5) 6 Function keys (F1…F6) are available for freeassignment to any logical binary input orcontrol function. This facilitates control, e.g. ofmanual trip and close commands.
Type label and PC interface
(6) An upper cover identifying the product name.The cover may be raised to provide access tothe product model number and ratings.
(7) A lower cover concealing the RS232 serial
interface to connect a personal computer.
(8) To guard the lower cover against unauthorized
opening it is provided a facility for fitting asecurity lead seal.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 17/44
[One-Box Solutions for Protection and Control] MiCOM P132 17
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Display panels
Display panels are automatically displayed forcertain operation conditions of the system.Priority increases from normal operation tooperation under overload or ground faultconditions and finally operation following a short
circuit in the system. The protection device thusprovides the measured value data relevant for theprevailing conditions.
The configuration of the local control panelallows the installation of measured value“panels” on the LCD display.
Devices with the optional control functions haveadditionally a control panel display to show theactive switchgear status and for local control viafunction keys.
C
Local control with text HMI
+
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 18/44
[One-Box Solutions for Protection and Control] MiCOM P132 18
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Mechanical Design
The device is supplied in two case designs.
• Surface-mounting case
• Flush-mounting case
Both case types with optional Detachable HMI.With both case versions, connection is viathreaded terminal ends with the option of eitherpin or ring-terminal connection.
Two 40T flush-mounting cases can be combinedto form a complete 19" mounting rack.
Below figure shows the modular hardwarestructure of the device.
The plug-in modules may be combined to suit theindividual requirements. The components fitted inan individual unit can be determined from thetype identification label on the front panel of theunit.
The identification of the modules fitted in thedevice is carried out by the device itself. Duringeach startup of the device, the number and typeof fitted modules are established by interrogationvia the digital bus, the admissibility of the set offitted components is checked and appropriateconfiguration parameters - in accordance withthe fitted set of modules - are released forapplication. The device identification valuesadditionally read out by the device provideinformation on the type, variant and designversion of each individual module.
Transformer Module T
The transformer module converts the measuredcurrent and voltage variables to the internalprocessing levels and provides for electricalisolation. Alternatively a NCIT module for aconnection to non-conventional instrument
transformer is provided.
Processor Module P
The processor module performs theanalog/digital conversion of the measuredvariables as well as all digital processing tasks.
Power Supply Module V
The power supply module ensures the electricalisolation of the device as well as providing thepower supply. Depending on the chosen designversion, optical coupler inputs and output relays
are provided in addition.
Local Control Module L
The local control module encompasses all controland display elements as well as a PC interface forrunning the operating program S1. The localcontrol module is located behind the front paneland connected to the processor module via aribbon cable.
Bus Modules B
Bus modules are printed circuit boards (PCBs)without any active components. They provide the
electrical connection between the other modules.Two types of bus modules are used, namely theanalog and the digital bus PCB.
MiCOM
TRIP
ALARM
OUT OFSERVICE
HEALTHY
EDIT MODE
GGC
GG
G
G
G
O I L/R
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 19/44
[One-Box Solutions for Protection and Control] MiCOM P132 19
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Transient Ground Fault Evaluation
Module N(Option)
The optional transient ground fault moduleevaluates the measured variables according tothe transient ground fault evaluation scheme.
Binary I/O Modules X(Option)
The binary I/O modules are equipped with opticalcouplers for binary signal input as well as outputrelays for the output of signals and commands orcombinations of these.
Analog Modules Y(Option)
The optional RTD module is fitted with 9resistance temperature detector inputs. Theoptional analog module is fitted with a resistancetemperature detector input, a 20 mA input andtwo 20 mA outputs. One output relay each isassigned to the two 20 mA outputs. Additionallyfour optical coupler inputs are available.
Communication Module A(Option)
The optional communication modules provideone or two serial communication interfaces forthe integration of the protection and control unitinto a substation control system and for remote
access respectively a protection communicationinterface for the transfer of digital informationbetween two protection devices. Thecommunication module with serialcommunication interface(s) is plugged into theprocessor module.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 20/44
[One-Box Solutions for Protection and Control] MiCOM P132 2
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Technical Data
CE Marking
This product complies with the essential requirements of the
following European directives:
Electromagnetic Compatibility Directive (EMC) 2004/108/ECLow Voltage Directive (LVD) 2006/95/EC
General Data
Design
Surface-mounting case suitable for wall installa-tion or flush-mounting case for 19" cabinets andfor control panels
Installation Position
Vertical ± 30°
Degree of Protection
Per DIN VDE 0470 and EN 60529 or IEC 529.
IP 52; IP 20 for the rear connection area of theflush-mounting case.
Weight
Case 40T: approx. 7 kgCase 84T: approx. 11 kg
Dimensions
See Dimensions
Terminal Connection Diagrams
See Locations and Connections
Terminals
PC Interface X6)
Connector DIN 41652 connector,Type D-Sub, 9-pin.
Communication Interfaces COMM1 to COMM3
Optical plastic fibers (X7, X8 and X31, X32):F-SMA-interface per IEC 60874-2 per plastic fiber
orBFOC-(ST
® )-interface 2.5 per IEC 60874-10-1 per glass
fiberor
Leads (X9, X10, X33):Threaded terminal ends M2 for wire crosssections up to 1.5 mm
2
or (Only for InterMiCOM)RS 232 (X34):DIN 41652 connector,Type D-Sub, 9 pin.
Communication Interface IEC 61850
Optical plastic fibers (X7, X8):BFOC-(ST
® )-interface 2.5 per IEC 60874-10-1 per glass
fiberor
optical plastic fibers (X13):SC-interface per IEC60874-14-4 per glass fiber
andLeads (X12):RJ45 connector per ISO/IEC 8877
IRIG-B Interface X11)
BNC plug
Current-Measuring Inputs conventional)
Threaded terminals for pin-terminal connection:Threaded terminal ends M5,self-centering with wire protection for
conductor cross sections of ≤ 4 mm2
orThreaded terminals M4 for ring-terminal connection
Current/Voltage-Measuring Inputs NCIT)
DIN 41652 connector and socket,Type D-Sub, 9 pin.
Other Inputs and OutputsThreaded terminals for pin-terminal connection:
Threaded terminal ends M3,self-centering with wire protection forconductor cross sections of 0.2 to 2.5 mm
2
orThreaded terminals M4 for ring-terminal connection
Creepage Distances and Clearances
Per EN 61010-1 and IEC 664-1Pollution degree 3,working voltage 250 V,overvoltage category III,
impulse test voltage 5 kV
Environmental Conditions
Ambient Temperature Range
Recommended temperature range:
-5°C to +55°C or +23°F to +131°FLimit temperature range:
-25°C to +70°C or -13°F to +158°F
Ambient Humidity Range
75 % relative humidity (annual mean),
up to 56 days at ≤ 95% relative humidity and 40 °C,condensation not permissible
Solar Radiation
Avoid exposure of the front panel to direct solar radiation.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 21/44
[One-Box Solutions for Protection and Control] MiCOM P132 21
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Tests
Type Test
Tests according to EN 60255-6 or IEC 255-6
Environmental tests
Temperature stabilitiy test
Per IEC 60068-2-1-25 °C or -13 °F storage (96 hours)-40 °C or -40 °F operation (96 hours)
Per IEC 60068-2-2+85 °C or 185 °F storage (96 hours)+85 °C or 185 °F operation (96 hours)
Per IEC 60068-2-14Change of temperature, 5 cycles,1°C / min rate of change
Ambient humidity range test
Per IEC 60068-2-3
56 days at ≤ 93 % relative humidity and 40 °C,Per IEC 60068-2-30
Damp heat, cyclic (12 + 12 hours)
93 % relative humidity, + 25 …+ 55 °C
Corrosive environment tests
Industrial corrosive environment/
poor environmental control, mixed gas flow test.
Per IEC 60068-2-60: 1995, Part 2, Test Ke, Method (class) 321 days at 75% relative humidity and +30°Cexposure to elevated concentr. of H
2
S, NO2
, Cl2
and SO2
EMC
Interference Suppression
Per EN 55022 or IEC CISPR 22, Class A
1 MHz Burst Disturbance Test
Per IEC 255 Part 22-1 or IEC 60255-22-1, Class III,
Common-mode test voltage: 2.5 kV,Differential test voltage: 1.0 kV,
Test duration: > 2 s, Source impedance: 200 Ω
Immunity to Electrostatic Discharge
Per EN 60255-22-2 or IEC 60255-22-2, Level 3,
Contact discharge, single discharges: > 10,Holding time: > 5 s, Test voltage: 6 kV,
Test generator: 50 to 100 MΩ, 150 pF / 330 Ω
Immunity to Radiated Electromagnetic Energy
Per EN 61000-4-3 and ENV 50204, Level 3, Antenna distance to tested device:
> 1 m on all sides,Test field strength, frequ. band 80 to 1000 MHz:
10 V/m,Test using AM: 1 kHz / 80%,Single test at 900 MHz: AM 200 Hz / 100%
Electrical Fast Transient or Burst Requirements
Per IEC 60255-22-4, Test severity Level 4,Rise time of one pulse: 5 ns,Impulse duration (50% value): 50 ns,
Amplitude: 4 kV / 2 kV, resp.,Burst duration: 15 ms, Burst period: 300 ms,
Burst frequency: 2.5 kHz, Source impedance: 50 Ω
Surge Immunity Test
Per EN 61000-4-5 or IEC 61000-4-5, Level 4,
Testing of power supply circuits,asymmetrically/ symmetrically operated lines,Open-circuit voltage front time/time to half-value:
1.2 / 50 µs,
Short-circuit current front time/time to half-value:8 / 20 µs,
Amplitude: 4 / 2 kV, Pulse frequency: > 5/min,
Source impedance: 12 / 42 Ω
Immunity to Conducted Disturbances Induced by Radio
Frequency Fields
Per EN 61000-4-6 or IEC 61000-4-6, Level 3,
Disturbing test voltage: 10 V
Power Frequency Magnetic Field Immunity
Per EN 61000-4-8 or IEC 61000-4-8 , Level 4,Frequency: 50 Hz, Test field strength: 30 A/m
Alternating Component Ripple) in DC Auxiliary Energizing
Quantity
Per IEC 255-11, 12 %
Insulation
Voltage Test
Per IEC 255-5 or EN 61010, 2 kV AC, 60 sFor the voltage test of the power supply inputs, direct voltage(2.8 kV DC) must be used. The PC interface and the NCITinputs must not be subjected to the voltage test.
Impulse Voltage Withstand Test
Per IEC 255-5,Front time: 1.2 µs, Time to half-value: 50 µs,
Peak value: 5 kV, Source impedance: 500 Ω
Mechanical Robustness
Vibration Test
Per EN 60255-21-1 or IEC 255-21-1, Test severity class 1,
Frequency range in operation:10 to 60 Hz, 0.035 mm, 60 to 150 Hz, 0.5 g,
Frequency range during transport: 10 to 150 Hz, 1 g
Shock Response and Withstand Test, Bump Test
Per EN 60255-21-2 or IEC 255-21-2, Test severity class 1,
Acceleration: 5 g/15 g, Pulse duration: 11 ms
Seismic Test
Per EN 60255-21-3 or IEC 255-21-3, Test procedure A,
Class 1,Frequency range:
5 to 8 Hz, 3.5 mm / 1.5 mm8 to 35 Hz, 10/5 m/s2, 3 x 1 cycle
Vibration test 1)
Per DIN EN 60255-21-1 or IEC 255-21-1, Test severity class 2:Frequency range in operation:
10...60 Hz, 0.075 mm, 60...150 Hz, 1.0 g,Frequency range during transport: 10...150 Hz, 2 g
Shock response and withstand test, bump test 1)
Per DIN EN 60255-21-2 or IEC 255-21-2,acceleration and pulse duration:
Shock Response test to verify full operability(during operation): test severity class 2, 10 g für 11 ms,
Shock Response test to verify endurance(during transport): test severity class 1, 15 g für 11 ms
Shock bump test to verify permanent shock(during transport): test severity class 1, 10 g für 16 ms
Seismic test 1)
Per DIN EN 60255-21-3 or IEC 255-21-3,test procedure A, Class 2 frequency range:
5...8 Hz, 7.5 mm / 3.5 mm,8...35 Hz, 20 / 10 m/s2 3 × 1 cycle
Routine Test
Tests per EN 60255-6 or IEC 255-6
Voltage Test
Per IEC 255-5, 2.2 kV AC, 1 sFor the voltage test of the power supply inputs, direct voltage(2.8 kV DC) must be used. The PC interface inputs must notbe subjected to the voltage test.
Additional Thermal Test
100% controlled thermal endurance test, inputs loaded
1) Enhanced mechanical robustness for the following case variants:Flush mounted case, version 2 (with angle brackets and frame)Surface mounted case
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 22/44
[One-Box Solutions for Protection and Control] MiCOM P132 22
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Ratings
Measurement Inputs
Nominal frequency f nom: 50 and 60 Hz (settable)
Operating range: 0.95 to 1.05 f nom
Over-/Underfrequency Protection: 40...70 Hz
Current
Conventional inputs:Nominal current Inom: 1 and 5 A (settable)Nominal consumption per phase: < 0.1 VA at I nom
Load rating:continuous 4 I nom
for 10 s: 30 I nom
for 1 s; 100 I nom
Nominal surge current: 250 I nom
Voltage
Conventional inputs:Nominal voltage V nom: 50 to 130 V AC (settable)
Nominal consumption per phase:< 0.3 VA at V nom = 130 V AC
Load rating: continuous 150 V AC
Binary Signal Inputs
Max. permissible voltage: 300 V DC
Switching threshold (as per order option)Standard variant: 18V (VA, nom: 24 ... 250 V DC):
Switching threshold range 14 V ... 19 V DCSpecial variant with switching thresholds from58 ... 72 % of the nominal supply voltage (V A, nom )(definitively "low" at V A < 58 % of the nominal supply voltage,definitively "high" at V A > 72 % of the nominal supply voltage):
"Special variant 73 V": nominal supply voltage 110 V DC"Special variant 90 V": nominal supply voltage 127 V DC"Special variant 146 V": nominal supply voltage 220 V DC"Special variant 155 V": nominal supply voltage 250 V DC
Power Consumption as per order option):Standard variant:
V A = 19...110V DC : 0,5 W +/-30%
V A > 110V DC : V A ∗ 5 mA +/- 30 %Special variants:
V A > switching threshold: V A ∗ 5mA +/-30 %Binary Count InputMaximum frequency of 20 Hz with pulse/interpulse ratio of 1:1
Output Relays
Rated voltage: 250 V DC, 250 V ACContinuous current:
Output relays of binary I/O module X (6I/6O) for control ofswitchgear units: 8 AOutput relays of other modules: 5 A
Short-duration current: 30 A for 0.5 sMaking capacity: 1000 W (VA) at L/R = 40 ms
Breaking capacity:0.2 A at 220 V DC and L/R = 40 ms
4 A at 230 V AC and cos ϕ = 0.4
Binary modules X (4H; 6I6H)with High-break contacts applicable to DC circuits onlyRated voltage: 250 VDCContinuous current: 10 AShort-duration current:
250 A for 0.03 s30 A for 3 s
Making capacity: 30 ABreaking capacity:
7500 W resistive or 30 A at 250 VDCmaximum values: 30 A and 300 VDC2500 W inductive (L/R = 40 ms) or 10 A at 250 VDCmaximum values: 10 A and 300 VDC
Analog Inputs and Outputs
Direct Current InputInput current: 0 to 26 mA
Value range: 0.00 to 1.20 I DC,nom ( I DC,nom = 20 mA)Maximum permissible continuous current: 50 mAMaximum permissible input voltage: 17 V
Input load: 100 Ω Open-circuit monitoring: 0 to 10 mA (adjustable)Overload monitoring: > 24.8 mAZero suppression: 0.000 to 0.200 I DC,nom (adjustable)
Resistance Temperature detector:For analog module only Pt100 permitted,for RTD module Pt100, Ni100 or Ni120 permitted
Value range: -40 to +215°C(Equivalent to -40 to +419°F)
3-wire configuration: max. 20 Ω per conductor.Open and short-circuited input permitted.Open-circuit monitoring:
Θ > +215°C (or Θ > +419°F) and Θ < -40°C (or Θ < -40°F)
Direct Current OutputOutput current: 0 to 20 mA
Maximum permissible load: 500 Ω Maximum output voltage: 15 V
Power Supply
Nominal Auxiliary VoltageV A,nom: 48 to 250 V DC and 100 to 230 V AC or
V A,nom: 24 V DC (depends on ordering)
Operating Rangefor direct voltage: 0.8 to 1.1 V A,nom
with a residual ripple of up to 12 % of V A,nom
for alternating voltage: 0.9 to 1.1 V A,nom
Nominal Consumptionat V A = 220 V DC and maximum number of modules fitted:
in case 40TE:Initial position approx.: 12.6 W
Active position approx.: 34.1 Win case 84TE:
Initial position approx.: 14.5 W Active position approx.: 42.3 W
Start-Up Peak Current< 3 A, duration 0.25 ms
Stored-Energy Time
≥ 50 ms for interruption of V A ≥ 220 V DC
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 23/44
[One-Box Solutions for Protection and Control] MiCOM P132 23
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
PC Interface
Transmission rate: 300 to 115,200 baud (settable)
Communication Interface COMM1 to COMM3
Communication interface COMM1:
Protocol can be switched between
IEC 60870-5-103, IEC 870-5-101, Modbus, DNP 3.0, CourierTransmission speed: 300 to 64000 bit/s (settable)
Communication interface COMM2:
Protocol per IEC 60870-5-103Transmission speed: 300 to 57600 bit/s (settable)
Protection interface COMM3:
InterMiCOM, asynchronous, full duplexTransmission speed: 600 to 19200 bit/s (settable)
Wire Leads
Per RS 485 or RS 422, 2kV-isolation,Distance to be bridged:
peer-to-peer link: max. 1200 mmulti-endpoint link: max. 100 m
Plastic Fiber Connection
Optical wavelength: typ. 660 nmOptical output: min. -7.5 dBmOptical sensitivity: min. -20 dBmOptical input: max. -5 dBmDistance to be bridged: max. 45 m 1)
Glass Fiber Connection G 50/125
Optical wavelength: typ. 820 nmOptical output: min. -19.8 dBmOptical sensitivity: min. -24 dBmOptical input: max. -10 dBmDistance to be bridged: max. 400 m 1)
Glass Fiber Connection G 62,5/125
Optical wavelength: typ. 820 nmOptical output: min. -16 dBmOptical sensitivity: min. -24 dBmOptical input: max. -10 dBm
Distance to be bridged: max. 1400 m 1)
Communication Interface IEC
61850
Ethernet based communication per IEC 61850
Wire Leads
RJ45, 1.5kV-isolation,Transmission rate: 10 resp.100 Mbit/sDistance to be bridged: max. 100 m
Optical Fiber 100 Mbit/s)
ST- or SC-interfaceOptical wavelength: typ. 1300 nmFor glass fiber G50/125
Optical output: min. –23.5 dBmOptical sensitivity: min. -31 dBmOptical input: max. -14 dBm
For glass fiber G62.5/125Optical output: min. -20 dBmOptical sensitivity: min. -31 dBmOptical input: max. -14 dBm
IRIG-B Interface
Format B122, Amplitude modulated,1 kHz carrier signal, BCD time-of-year code
1) Distance to be bridged for optical outputs and inputs thatare equal on both ends, taking into account a systemreserve of 3 dB and typical fiber attenuation.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 24/44
[One-Box Solutions for Protection and Control] MiCOM P132 24
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Typical Characteristic DataMain Function
Minimum output pulse for a trip command: 0.1 to 10 s(settable)Output pulse for a close command: 0.1 to 10 s (settable)
Definite-Time and Inverse-Time Overcurrent Protection
Operate time inclusive of output relay (measured variable from
0 to 2-fold operate value):≤ 40 ms, approx. 30 ms
Reset time (measured variable from 2-fold operate value to 0):
≤ 40 ms, approx. 30 msStarting resetting ratio: ca. 0.95
Short-Circuit Direction Determination
Nominal acceptance angle for forward decision: ±90 °
Resetting ratio forward/backward recognition: ≤ 7 °Base point release for phase currents: 0.1 I nom
Base point release for phase-to-phase voltages:0.002 V nom at V nom = 100 V
Base point release for residual current: 0.01 I nom
Base point release for neutral displacement voltage:
0.015 to 0.6 V nom / √3 (adjustable)
Over-/Undervoltage Protection
Operate time inclusive of output relay (measured variable fromnominal value to 1.2-fold operate value or measured variablefrom nominal value to 0.8-fold operate value):
≤ 40 ms, approx. 30 msReset time (measured variable from 1.2-fold operate value tonominal value or measured variable from 0.8-fold operatevalue to nominal value):
≤ 45 ms, approx. 30 msStarting resetting ratio: settable hysteresis 1...10%
Directional Power Protection
Operate time inclusive of output relay (measured variable fromnominal value to 1.2-fold operate value or measured variablefrom nominal value to 0.8-fold operate value):
≤ 60 ms, approx. 50 msReset time (measured variable from 1.2-fold operate value to
nominal value or measured variable from 0.8-fold operatevalue to nominal value):
≤ 40 ms, approx. 30 msResetting ratio for P>, Q>: settable hysteresis 0.05...0.95
P<, Q<: settable hysteresis 1.05...20
Deviations of the Operate Values‘Reference Conditions’
Sinusoidal signals with nominal frequency f nom ,
total harmonic distortion ≤ 2 %, ambient temperature 20 °Cand nominal auxiliary voltage V A,nom
‘Deviation’
Deviation relative to the setting under reference conditions
Measuring-circuit monitoring
Operate values : ± 3 %
Overcurrent-Time Protection
Operate values: ± 5 %
Short-circuit direction determination
Operate values: ± 10 °
Motor and Thermal Overload Protection
Reaction time: ± 7.5 % at I/Iref =6
Over-/Underfrequency Protection
Operate values f<>: +/- 30 mHz ( f nom = 50 Hz)
+/- 40 mHz ( f nom = 60 Hz)
Operate values df/dt: +/- 0,1 Hz/s ( f nom = 50 or 60 Hz)
Over-/Undervoltage Protection
Operate values V<>, Vref<>, Vpos<>: ± 1 %(setting 0.6…1.4 V nom )
Operate values VNG>, Vneg>: ± 1 %(setting > 0.3 V nom )
Unbalance Protection
Operate values: ± 5 %
Directional Power Protection
Operate values P<>, Q<>: ± 5 %
GF Direction Determination
Operate values: VNG>, IN,act , IN,reac, IN> ± 3 %
Sector Angle: 1 °
Deviations of the Timer Stages‘Reference Conditions’
Sinusoidal signals with nominal frequency f nom ,total harmonic distortion ≤ 2 %, ambient temperature 20 °Cand nominal auxiliary voltage V A,nom
‘Deviation’
Deviation relative to the setting under reference conditions
Definite-Time Stages
± 1% + 20...40 ms
Inverse-Time Stages
± 5 % + 10 to 25 ms (measured variable greater than 2 I ref )
for IEC characteristic extremely inverse and for thermaloverload protection:± 7.5 % + 10 to 20 ms
Deviations in Measured Data Acquisition‘Reference Conditions’
Sinusoidal signals with nominal frequency f nom ,
total harmonic distortion ≤ 2 %, ambient temperature 20 °Cand nominal auxiliary voltage V A,nom
‘Deviation’
Deviation relative to the setting under reference conditions
Operating Data
Currents / measuring inputs: ± 1 % Voltages / measuring input: ± 0.5 %Currents / internally calculated : ± 2 %
Voltages / internally calculated : ± 2 % Active and reactive power / energy:
approx. ± 2 % of meas. value for cos ϕ = ± 0.7
approx. ± 5 % of meas. value for cos ϕ = ± 0.3Load angle: ± 1 °Frequency: ± 10 mHz
Fault Data
Short-circuit current and voltage: ± 3 %Short-circuit impedance, reactance and Fault location: ± 5 %
Internal Clock
With free running internal clock: < 1 min / monthWith external synchronization
via protocol, synch. interval ≤ 1 min: ± 10 ms
via IRIG-B signal input: ± 1 ms
Resolution in measured Data AcquisitionTime Resolution
20 sampled values per period
Phase Currents
Dynamic range: 100 I nom resp. 25 I nom
Amplitude resolutionat I nom = 1 A: 6.1 mA r.m.s. resp. 1.5 mA r.m.s.
at I nom = 5 A: 30.5 mA r.m.s. resp. 7.6 mA r.m.s.
Residual Current
Dynamic range: 16 I nom resp. 2 I nom
Amplitude resolutionat I nom = 1 A: 0.98 mA r.m.s. resp. 0.12 mA r.m.s.
at I nom = 5 A: 4.9 mA r.m.s. resp. 0.61 mA r.m.s.
Voltage
Dynamic range: 150 V Amplitude resolution: 9.2 mV r.m.s.
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 25/44
[One-Box Solutions for Protection and Control] MiCOM P132 25
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Address List
Function Parameters
Global Functions
PC link PC):
Command blocking: No/Yes
Sig./meas.val.block.: No/Yes
Commun ication link CO MM1):
Command block. USER: No/YesSig./meas.block.USER: No/Yes
Communication Link CO MM2):
Command block. USER: No/YesSig./meas.block.USER: No/Yes
Binary and analog output OUTP):
Outp.rel.block USER: No/Yes
Main function MAIN):
Device on-line: No (= off) /Yes (= on)Test mode USER: No/YesNominal frequ. fnom: 50 Hz/60 HzPhase sequence: A – B - C/A – C - BTime tag:
1stEgde.,OpMem sorted1stEgde.,OpMem unsortafter debounce time
Inom C.T. prim.: 1..10000 AIN,nom C.T. prim.: 1....10000 A
Vnom V.T. prim.: 0.1....1000.0 kV VNG,nom V.T. prim.: 0.1....1000.0 kV Vref,nom V.T. prim.: 0.1...1000.0 kVInom prim.NCIT: 50...4000 AIN,nom prim. NCIT: 10...800 A
Vnom prim. NCIT:0.1...1000,0 kVPh. err. VAG,1 NCIT: -5.0…5.0°Ph. err. VBG,1 NCIT: -5.0…5.0°Ph. err. VCG,1 NCIT: -5.0…5.0°Ph. err. VAG,2 NCIT: -5.0…5.0°
Ph. e. VBG/Vref,2 NCIT: -5.0…5.0°Ph. err. VCG,2 NCIT: -5.0…5.0°Channel select NCIT:
No channelChannel 1 onChannel 2 on
Inom device: 1.0 A/5.0 AIN,nom device: 1.0 A/5.0 A
Vnom V.T. sec.: 50...130 V VNG,nom V.T. sec.: 50...130 V Vref,nom V.T. sec.: 30...130 VConn. meas. circ. IP: Standard/OppositeConn. meas. circ. IN: Standard/OppositeMeas. value rel. IP: 0.000...0.200 InomMeas. value rel. IN: 0.000...0.200 IN,nomMeas. value rel. V: 0.000...0.200 Vnom
Meas. val. rel. VNG: 0.000...0.200 VNE,nomMeas. val. rel. Vref: 0,000...0,200 Vref,nomOp. mode energy cnt.: Procedure 1/ Procedure 2Settl. t. IP,max,del: 0.1...60.0 minFct.assign. block. 1: see selection tableFct.assign. block. 2: see selection tableFct.assig.trip cmd.1: see selection tableFct.assig.trip cmd.2: see selection tableFct. assign. fault: see selection tableTrip cmd.block. USER: No/YesMin.dur. trip cmd. 1: 0.10...10.00 sMin.dur. trip cmd. 2: 0.10...10.00 sLatching trip cmd. 1: No/YestCB,close : 0.000…1.000 sLatching trip cmd. 2: No/YesClose cmd.pulse time 0.10...10.00 s
Sig. asg. CB open: see selection tableSig. asg. CB closed: see selection tablevalid for y = ‚1‘ to ‚8‘
Debounce time gr. y: 0.00...2.54 sChatt.mon. time gr. y: 0.0...25.4 s
Change of state gr. y: 0...254Cmd. dur.long cmd.: 1...254 sCmd. dur. short cmd.: 1...254 sElectrial Control: Remote/LocalDelay Man.Op.Superv.: 0...255 sW. ext. cmd. termin.: No/YesInp.asg. ctrl.enabl. Without functionInp.asg.interl.deact: see selection tableInp.asg. L/R key sw.: see selection table
Auto-assignment I/O: No/YesInp.assign. tripping: see selection tableProt.trip>CB tripped:
Without functionGen. trip command 1Gen. trip command 2Gen.trip command 1/2
Inp. asg. CB trip: see selection tableInp.asg.CB tr.en.ext: see selection tableInp.asg. CB trip ext: see selection tableInp.asg. mult.sig. 1: see selection tableInp.asg. mult.sig. 2: see selection table
Parameter subset selection PSS):
Control via USER: No/YesParam.subs.sel. USER:
Parameter subset 1Parameter subset 2Parameter subset 3Parameter subset 4
Keep time: 0.000...65.000 s / Blocked
Selfmonitoring SFMON):
Fct. assign. warning: see selection table
Fault data acquisition FT_DA):
Line length: 0.01...500.00 kmLine reactance:
0.10...200.00 Ω for Inom = 1.0 A
0.02...40.00 Ω for Inom = 5.0 A Angle kG: -180...180 ° Abs. value kG: 0.00...8.00Start data acquisit.: End of fault/Trigg., trip, GS endOutput fault locat.:
On general startingOn gen.start.w.trip
Fault recording FT_RC):
Fct. assig. trigger: see selection tableI>: 0.01...40.00 Inom / BlockedPre-fault time: 1...50 periodsPost-fault time: 1...50 periodsMax. recording time: 5...750 periods
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 26/44
[One-Box Solutions for Protection and Control] MiCOM P132 26
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Main Functions
Main function MAIN):
Syst.IN enabled USER: No/Yes
Definite-time overcurrent protection DTOC):
General enable USER: No/Yes
Inverse-time overcurrent protection IDMT1 resp. IDMT2):
General enable USER: No/Yes
Shortcircuit direction determination SCDD):
General enable USER: No/Yes
Switch on to fault protection SOTF):
General enable USER: No/YesOperating mode:
Trip by I>Trip by I>>Trip b< I>>>Trip by gen. start.
Manual close timer: 0.00...10.00 s
Protective signaling PSIG):
General enable USER: No/Yes
Autoreclosing control ARC):
General enable USER: No/Yes
Sig.asg.trip t.GFDSS:Starting LSStarting Y(N)>Starting LS/Y(N)>
Fct.assign. tLOGIC: see selection table
Automatic synchronism check ASC):
General enable USER: No/YesTransm.cycle,meas.v.: 0...10 s
Ground fault direction determination using
steady-state values (GFDSS):General enable USER: No/YesOperating mode:
Steady-state powerSteady-state currentSteady-state admitt.
Transient ground fault direction
determination (TGFD):General enable USER: No/Yes
Motor protection MP):
General enable USER: No/YesHours_Run >: 1…65.000 h
Thermal overload protection THERM):
General enable USER: No/YesRelative replica: No/Yes
Absolute replica: No/Yes
Unbalance protection I2>):
General enable USER: No/Yes
Over-/undervoltage protection V<>):
General enable USER: No/Yes
Over-/ underfrequency protection f<>):
General enable USER: No/YesSelection meas. volt:
Voltage A-G Voltage B-G Voltage C-G Voltage A-B Voltage B-C
Voltage C-AEvaluation time: 3...6 Periods
Undervolt. block. V<: 0.20...1.00 Vnom(/ √3)
Directional power protection P<>):
General enable USER: No/Yes
Circuit breaker failure protection CBF):
General enable USER: No/YesStart with man. Trip: No/YesFct.assign. CBaux: see selection tableI<: 0.05...20.00 Inomt1 3p: 0.00...100.00 s / Blockedt2: 0.00...100.00 s / BlockedMin.dur. trip cmd. t1: 0.10...10.00 sMin.dur. trip cmd. t2: 0.10...10.00 sLatching trip cmd. t1: No/YesLatching trip cmd. t2: No/Yes
Delay/starting trig.: 0.00...100.00 s / BlockedDelay/fault beh. CB: 0.00...100.00 s / BlockedDelay/CB sync. superv: 0.00...100.00 s / Blocked
Circuit breaker monitoring CBM)
General enable USER: No/YesBlocking USER: No/YesSig.asg. trip cmd.: see selection tableOperating mode:
with trip cmd. onlywith CB sig.EXT onlyCB sig.EXT or trip
Inom,CB: 1...65000 APerm. CB op. Inom,CB: 1...65000Med.curr. Itrip,CB: 1...65000 A / BlockedPerm. CB op. Imed,CB: 1...65000 / Blocked
Max.curr. Itrip,CB: 1...65000 APerm. CB op. Imax,CB: 1...65000No. CB operations >: 1...65000Remain No. CB op. <: 1...65000
ΣItrip>: 1...65000 Inom,CB
ΣItrip**2>: 1...65000 Inom,CB**2
ΣI*t>: 1...4000 kAsCorr. acqu.time trip 0.000…0.200 sCorr.acqu.t. CB sig. -0.200…0.200 s
Measuring circuit monitoring MCMO N):
General enable USER: No/YesOp. mode Idiff>:
WithoutIA,ICIA, IB, IC
Idiff>: 0.25...0.50 IP,max
Vmin<: 0.40...0.90 Vnom / BlockedOperate delay: 0.50...10.00 s / BlockedPhase sequ. monitor.: No/YesFF,Vref enabled USER: No/YesOper. delay FF, Vref: 00.00...10.00 s
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 27/44
[One-Box Solutions for Protection and Control] MiCOM P132 27
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Limit value monitoring LIMIT):
General enable USER: No/YesI>: 0.10... 2.40 Inom/ BlockedI>>: 0.10...2.40 Inom/ BlockedtI>: 1...1000 s / BlockedtI>>: 1...1000 s / BlockedI<: 0.10... 2.40 Inom/ BlockedI<<: 0.10... 2.40 Inom/ Blocked
tI<: 1...1000 s / BlockedtI<<: 1...1000 s / Blocked
VPG>: 0.10... 2.50 Vnom/ √3 / Blocked
VPG>>: 0.10... 2.50 Vnom/ √3 / BlockedtVPG>: 1...1000 s / BlockedtVPG>>: 1...1000 s / Blocked
VPG<: 0.10... 2.50 Vnom/ √3 / Blocked
VPG<<: 0.10... 2.50 Vnom/ √3 / BlockedtVPG<: 1...1000 s / BlockedtVPG<<: 1...1000 s / Blocked
VPP>: 0.10... 1.50 Vnom / Blocked VPP>>: 0.10... 1.50 Vnom / BlockedtVPP>: 1...1000 s / BlockedtVPP>>: 1...1000 s / Blocked
VPP<: 0.10... 1.50 Vnom / Blocked VPP<<: 0.10... 1.50 Vnom / Blocked
tVPP<: 1...1000 s / BlockedtVPP<<: 1...1000 s / Blocked
VNG>: 0.010... 1.000 Vnom / Blocked VNG>>: 0.010... 1.000 Vnom / BlockedtVNG>: 1...1000 s / BlockedtVNG>>: 1...1000 s / Blocked
Vref>: 0.10...2.50 Vnom/ Blocked Vref>>: 0.10...2.50 Vnom/ BlockedtVref>: 1...1000 s / BlockedtVref>>: 1...1000 s / Blocked
Vref<: 0.10...2.50 Vnom/ Blocked Vref<<: 0.10...2.50 Vnom/ BlockedtVref<: 1...1000 s / BlockedtVref<<: 1...1000 s / BlockedIDC,lin>: 0.100...1.100 IDC,nomIDC,lin>>: 0.100...1.100 IDC,nom
tIDC,lin>: 0.00...20.00 stIDC,lin>>: 0.00...20.00 sIDC,lin<: 0.100...1.100 IDC,nomIDC,lin<<: 0.100...1.100 IDC,nomtIDC,lin<: 0.00...20.00 stIDC,lin<<: 0.00...20.00 sT>: -20...200°CT>>: -20...200°CtT>: 0...1000 s / BlockedtT>>: 0...1000 s / BlockedT<: -20...200°CT<<: -20...200°CtT<: 0...1000 s / BlockedtT<<: 0...1000 s / Blockedvalid for y = ‚1‘ to ‚9‘
Ty>: -20...200°C
Ty>>: -20...200°CtTy>: 0...1000 s / BlockedtTy>>: 0...1000 s / BlockedTy<: -20...200°CTy<<: -20...200°CtTy<: 0...1000 s / BlockedtTy<<: 0...1000 s / Blocked
Logic LOGIC):
General enable USER: No/Yesvalid for y = ‚1‘ to ‚8‘
Set 1 USER: No/Yesvalid for y = = ‚1‘ to ‚32‘
Fct.assignm. outp. y: see selection tableOp. mode t output y:
Without timer stage
Oper./releas.delayOper.del./puls.dur.Op./rel.delay,retrigOp.del./puls.dur.,rtMinimum time
Time t1 output y: 0.00...600.00 sTime t2 output y: 0.00...600.00 sSig.assig. outp. y: see selection tableSig.assig.outp. y(t): see selection table
Signaling SIG_1):
valid for y = ‚S001‘ to ‚S040‘ Designat. signal y: see selection tableOper. mode sig. y:
Without functionStart/end signalTransient signal
Gr.asg. debounc. y:Group 1 ... Group 8
Min. sig. dur. y: 0...254 s
Commands CMD_1):
valid for y = ‚C001‘ to ‚C026‘ Design. command y: see selection tableOper. mode cmd. y:
Long commandShort commandPersistent command
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 28/44
[One-Box Solutions for Protection and Control] MiCOM P132 28
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Parameter Subset
valid for parameter subsets x = 1 to 4
Measured Data Input MEASI):
BackupTempSensor:NoneGroup 1 - 2Group 1 - 2/3
Main function MAIN):
Neutrl-pt threat. PSx:Low-imped. groundingIsolated/res.ground.
Hld time dyn.par. PSx: 0.00...100.00 s / BlockedBl.tim.st. IN,neg PSx:
WithoutFor single-ph. startFor multi-ph. start.
Gen. start. mode PSx: W/o start. IN, Ineg/With start. IN, InegOp. rush restr. PSx:
WithoutNot phase-selectivePhase-selective
Rush I(2*fn)/I(fn) PSx: 10...35 %I> lift rush restr. PSx: 5.0...20.0 Inom / Blocked
Phase reversal I PSx: No swap; A-B/ B-C/ C-A swappedSuppr.start. sig. PSx: 0.0...100.0 stGS PSx: 0.00...100.00 s / Blocked
Definite-time overcurrent protection DTOC):
Enable PSx: No/YesI>: 0.1...40.0 Inom / BlockedI> dynamic: 0.1...40.0 Inom / BlockedI>>: 0.1...40.0 Inom / BlockedI>> dynamic: 0.1...40.0 Inom / BlockedI>>>: 0.1...40.0 Inom / BlockedI>>> dynamic: 0.1...40.0 Inom / BlockedtI>: 0.00...100.00 s / BlockedtI>>: 0.00...100.00 s / BlockedtI>>>: 0.00...100.00 s / BlockedIneg> PSx: 0.1...25.0 Inom / BlockedIneg> dynamic PSx: 0.1...25.0 Inom / BlockedIneg>> PSx: 0.1...25.0 Inom / BlockedIneg>> dynamic PSx: 0.1...25.0 Inom / BlockedIneg>>> PSx: 0.1...25.0 Inom / BlockedIneg>>> dynamic PSx: 0.1...25.0 Inom / BlockedtIneg> PSx: 0.00...100.00 s / BlockedtIneg>> PSx: 0.00...100.00 s / BlockedtIneg>>> PSx: 0.00...100.00 s / BlockedEvaluation IN> PSx: calculated/MeasuredEvaluation IN>> PSx: calculated/MeasuredEvaluation IN>> PSx: calculated/MeasuredIN>: 0.002...8.000 Inom / BlockedIN> dynamic: 0.020...8.000 Inom / BlockedIN>>: 0.002...8.000 Inom / BlockedIN>> dynamic: 0.020...8.000 Inom / BlockedIN>>>: 0.002...8.000 Inom / BlockedIN>>> dynamic: 0.020...8.000 Inom / BlockedIN>>>>: 0.01...40.00 Inom / BlockedIN>>>> dynamic: 0.01...40.00 Inom / BlockedtIN>: 0.00...100.00 s / BlockedtIN>>: 0.00...100.00 s / BlockedtIN>>>: 0.00...100.00 s / BlockedtIN>>>>: 0.00...100.00 s / BlockedPuls.prol.IN>,interm: 0.00...10.00 stIN>,interm.: 0.00...100.00 s / BlockedHold-time tIN>,intm.: 0.0...600.0 sMode Timer start : With starting, With direction
Inverse-time overcurrent protection IDMT1 resp. IDMT2):
Enable PSx: No/YesIref,P PSx: 0.10...4.00 Inom / BlockedIref,P dynamic PSx: 0.10...4.00 Inom / BlockedCharacteristic P PSx:
Definite TimeIEC Standard InverseIEC Very Inverse
IEC Extr. InverseIEC Long Time Inv.IEEE Moderately Inv.IEEE Very InverseIEEE Extremely Inv.
ANSI Normally Inv. ANSI Short Time Inv. ANSI Long Time Inv.RI-Type InverseRXIDG-Type Inverse
Factor KI,P PSx 1.00...10.00Factor kt,P PSx: 0.05...10.00Min. trip t. P PSx: 0.00...10.00 sHold time P PSx: 0.00...600.00 sRelease P PSx: Without delay/Delayed as per char.Evaluation IN PSx: calculated/Measured
valid for y = ‚neg‘ or ‚N‘:Iref,y PSx: 0.01...0.80 Inom / BlockedIref,y dynamic PSx: 0.01...0.80 Inom / BlockedCharacteristic y PSx:
Definite TimeIEC Standard InverseIEC Very InverseIEC Extr. InverseIEC Long Time Inv.IEEE Moderately Inv.IEEE Very InverseIEEE Extremely Inv.
ANSI Normally Inv. ANSI Short Time Inv. ANSI Long Time Inv.RI-Type Inverse
RXIDG-Type InverseFactor KI,y 1.00…10.00Factor kt,y PSx: 0.05...10.00Min. trip t. y PSx: 0.00...10.00 sHold time y PSx: 0.00...600.00 sRelease y PSx:
Without delay/Delayed as per char.Mode Timer start PSx With starting/ With direction
Short-circuit direction determination SCDD):
Enable PSx: No/YesTrip bias: No/Yesvalid values for:
Direction tI>:Direction tI>>:Direction tI>>>:Direction tIref,P>:
Direction tIN>:Direction tIN>>:Direction tIN>>>:Direction tIref,N>:
Forward directionalBackward directionalNon-directional
Charact. angle G: -90... -45...90 °Evaluation IN Calculated, Measured
VNG>: 0.015... 0.100...0.600 Vnom/ √3Evaluation VNG Calculated, MeasuredBlock. bias G: No/YesOper.val. Vmemory: 0.01...1.00 Vnom
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 29/44
[One-Box Solutions for Protection and Control] MiCOM P132 29
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Protective signaling PSIG):
Enable PSx: No/YesTripping time: 0.00...10.00 sRelease time send: 0.00...10.00 sDC loop op. mode: Transm.rel.break con/Transm.rel.makecon.Direction dependence:
Without
Phase curr. systemResidual curr.systemPhase/resid.c.system
Autoreclosing control ARC):
Enable PSx: No/YesCB clos.pos.sig. PSx: Without/WithOperating mode PSx:
HSR/TDR permittedTDR only permittedTest HSR only permit
Operative time PSx: 0.00...10.00 sHSR trip.time GS PSx: 0.00...10.00 s / BlockedHSR trip.time I> PSx: 0.00...10.00 s / BlockedHSR trip.time I>>PSx: 0.00...10.00 s / BlockedHSRtrip.time I>>>PSx: 0.00...10.00 s / BlockedHSR trip.time IN>PSx: 0.00...10.00 s / Blocked
HSRtrip.time IN>>PSx: 0.00...10.00 s / BlockedHSRtrip.t. IN>>> PSx: 0.00...10.00 s / BlockedHSRtrip.t. IrefP>PSx: 0.00...10.00 s / BlockedHSRtrip.t.IrefN>PSx: 0.00...10.00 s / BlockedHSRtrip.t. Iref,neg> PSx: 0.00...10.00 s / BlockedHSR trip t.GFDSS PSx: 0.00...10.00 s / BlockedHSRtrip.t. LOGIC PSx: 0.00...10.00 s / BlockedHSR block.f. I>>>PSx: No/YesHSR dead time PSx: 0.15...600.00 sNo. permit. TDR PSx: 0...9TDR trip.time GS PSx: 0.00...10.00 s / BlockedTDR trip.time I> PSx: 0.00...10.00 s / BlockedTDR trip.time I>>PSx: 0.00...10.00 s / BlockedTDRtrip.time I>>>PSx: 0.00...10.00 s / BlockedTDR trip.time IN>PSx: 0.00...10.00 s / BlockedTDRtrip.time IN>>PSx: 0.00...10.00 s / Blocked
TDRtrip.t. IN>>> PSx: 0.00...10.00 s / BlockedTDRtrip.t. IrefP>PSx: 0.00...10.00 s / BlockedTDRtrip.t.IrefN>PSx: 0.00...10.00 s / BlockedTDRtrip.t. Iref,neg> PSx: 0.00...10.00 s / BlockedTDR trip t.GFDSS PSx: 0.00...10.00 s / BlockedTDRtrip.t. LOGIC PSx: 0.00...10.00 s / BlockedTDR dead time PSx: 0.15...600.00 sTDR block.f. I>>>PSx: No/YesReclaim time PSx: 1...600 sBlocking time PSx: 0...600 s
Automatic synchonism check ASC):
Enable PSx: No/YesCB assignment PSx: see selection tableSystem integrat. PSx:
Autom.synchron.check Autom.synchron.control
Active for HSR PSx: No/Yes Active for TDR PSx: No/YesClos.rej.w.block PSx: No/YesOperative time PSx: 0.0...6000.0 sOperating mode PSx:
Voltage-checkedSync.-checked
Volt./sync.-checkedOp.mode volt.chk.PSx:
Vref but not V V but not VrefNot V and not VrefNot V or not Vref
AR with tCB PSx No, Yes
V> volt.check PSx: 0.10...0.80 Vnom(/ √3)
V< volt. check PSx: 0.10...0.80 Vnom(/ √3)tmin volt. check PSx: 0.00...10.00 sMeasurement loop PSx:
Loop A-G/ B-G/ C-G/ A-B/ B-C/ C-A
V> sync. check PSx: 0.40...1.20 Vnom(/ √3)
Delta Vmax PSx: 0.02...0.40 VnomDelta f max PSx: 0.03...1.00 HzDelta phi max PSx: 5...100 °Phi offset PSx: -180...180 °tmin sync. check PSx: 0.00...10.00 s
Ground fault direction determination using
steady-state values (GFDSS):Enable PSx: No/Yes
Op.m.GF pow./adm PSx:cos phi circuit/sin phi circuitEvaluation VNG PSx: Calculated/MeasuredMeas. direction PSx: Standard/Opposite
VNG> PSx: 0.02...1.00 Vnom(/ √3)tVNG> PSx: 0.02...10.00 sf/fnom (pow.meas.) PSx: 1/5f/fnom (curr.meas.) PSx: 1/5IN,act>/reac> LS PSx: 0.003...1.000 IN,nomSector angle LS PSx: 80...89 °Operate delay LS: 0.00...100.00 s / BlockedRelease delay LS: 0.00...10.00 sIN,act>/reac> BS: 0.003...1.000 IN,nomSector angle BS: 80...89 °Operate delay BS PSx: 0.00...100.00 s / BlockedRelease delay BS PSx: 0.00...10.00 s
IN> PSx: 0.003...1.000 IN,nomOperate delay IN PSx: 0.00...100.00 s / BlockedRelease delay IN PSx: 0.00...10.00 sG(N)> / B(N)> LS PSx: 0.01...1.00 YN,nomG(N)> / B(N)> BS PSx: 0.01...1.00 YN,nomY(N)> PSx: 0.01...2.00 YN,nomCorrection angle: -30...+30°Operate delay Y(N)> PSx: 0.00...100.00 sRelease delay Y(N)> PSx: 0.00...10.00 s
Transient ground fault direction
determination (TGFD):Enable PSx: No/YesEvaluation VNG PSx: Sum (VA-B-C-G) /MeasuredMeasurem. direc. PSx: Standard/Opposite
VNG> PSx: 0.15...0.50 Vnom(/3)Operate delay PSx: 0.05...1.60 s
IN,p> PSx: 0.10...0.50 InomBuffer time PSx: 0...1200 s / Blocked
Motor protection MP):
Enable PSx: No/YesIref: 0.10...4.00 InomFactor kP: 1.05...1.50Istup>: 1.8...3.0 IreftIstup>: 0.1...1.9 sCharacter. type P: Reciprocal squared/logarithmict6Iref: 1.0...100.0 sTau after start-up: 1...60 sTau machine running: 1...1000 minTau machine stopped: 1...1000 minPermiss.No.start-ups:
2/1 (cold/warm) / 3/2 (cold/warm)
RC permitted, Θ<: 22...60 % / BlockedOperating mode: Without THERM/With THERMStart-up time t,stup: 2.0...100.0 sBlocking time tE: 2.0...100.0 sI<: 0.2...0.9 Iref / BlockedtI<: 0.1...20.0 s
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 30/44
[One-Box Solutions for Protection and Control] MiCOM P132 3
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Thermal overload protection THERM):
Enable PSx: No/YesSel. backup th. PSx: see selection tableIref PSx: 0.10...4.00 InomStart.fact OL_RC PSx: 1.05...1.50Tim.const.1,>Ibl PSx: 1.0...1000.0 minTim.const.2,<Ibl PSx: 1.0...1000.0 minMax.perm.obj.tmp. PSx: 0...300 °C
O/T f.Iref pers. PSx: 0...300 K (abs. replica only)Max. perm.cool.temp. PSx: 0...70 °C (rel. replica only)Select.meas.input PSx: see selection tableWarning temp. PSx: 0...300 °C (abs. replica only)Default CTA PSx: -40...70 °CBl. f. CTA fault PSx: No/YesRel. O/T warning PSx: 50...200 % (rel. replica only)Rel. O/T trip PSx: 50...200 % (rel. replica only)Hysteresis trip PSx: 2...30 %Warning pre-trip PSx: 0.0...1000.0 min / BlockedFunct.f.CTA fail PSx:
Default temp. valueLast meas. temperat.Blocking
Unbalance protection (I2>):Enable PSx: No/Yes
Ineg> PSx: 0.10...0.80 Inom / BlockedIneg>> PSx: 0.10...0.80 Inom / BlockedtIneg> PSx: 0.00...100.00 s / BlockedtIneg>> PSx: 0.00...100.00 s / BlockedOver-/undervoltage protection (V<>):Enable PSx: No/YesOperating mode PSx: Delta/StarI enable V< PSx: 0.04....1.00 InomOp.mode V< mon. PSx : without/with
Evaluation VNG PSx: Calculated/Measured
V> PSx: 0.20...1.50 Vnom(/ √3) / Blocked
V>> PSx: 0.20...1.50 Vnom(/ √3) / BlockedtV> PSx: 0.00...100.00 s / BlockedtV> 3-pole PSx: 0.00...100.00 s / BlockedtV>> PSx: 0.00...100.00 s / Blocked
V< PSx: 0.20...1.50 Vnom(/ √3) / Blocked
V<< PSx: 0.20...1.50 Vnom(/ √3) / BlockedtV< PSx: 0.00...100.00 s / BlockedtV< 3-pole PSx: 0.00...100.00 s / BlockedtV<< PSx: 0.00...100.00 s / Blocked
Vpos> PSx: 0.20...1.50 Vnom/ √3 / Blocked
Vpos>> PSx: 0.20...1.50 Vnom/ √3 / BlockedtVpos> PSx: 0.00...100.00 s / BlockedtVpos>> PSx: 0.00...100.00 s / Blocked
Vpos< PSx: 0.20...1.50 Vnom/ √3 / Blocked
Vpos<< PSx: 0.20...1.50 Vnom/ √3 / BlockedtVpos< PSx: 0.00...100.00 s / BlockedtVpos<< PSx: 0.00...100.00 s / Blocked
Vneg> PSx: 0.20...1.50 Vnom/ √3 / Blocked
Vneg>> PSx: 0.20...1.50 Vnom/ √3 / BlockedtVneg> PSx: 0.00...100.00 s / BlockedtVneg>> PSx: 0.00...100.00 s / Blocked
VNG> PSx: 0.02...1.00 Vnom(/ √3) / Blocked VNG>> PSx: 0.02...1.00 Vnom(/ √3) / BlockedtVNG> PSx: 0.00...100.00 s / BlockedtVNG>> PSx: 0.00...100.00 s / Blocked
Vref> PSx: 0.20...1.50 Vnom/ √3 / BlockedtTransient PSx: 0.00...100.00 s / Blocked
Vref>> PSx: 0.20...1.50 Vnom/ √3 / BlockedHyst. V<> meas. PSx: 1...10 %tVref> PSx: 0.00...100.00 s / BlockedHyst. V<> deduc. PSx: 1...10 %tVref>> PSx: 0.00...100.00 s / Blocked
Vref< PSx: 0.20...1.50 Vnom/ √3 / Blocked
Vref<< PSx: 0.20...1.50 Vnom/ √3 / BlockedtVref< PSx: 0.00...100.00 s / BlockedtVref<< PSx: 0.00...100.00 s / Blocked
Directional power protection P<>):
Enabled PSx: No/Yesvalid for y = ‚>‘ and ‚>>‘ and ‚<‘ and ‚<<‘:
Py PSx: 0.010...0.500 Snom / BlockedOperate delay Py PSx: 0.00...100.00 s / BlockedRelease delay Py PSx: 0.00...100.00 sDirection Py PSx:
Forward directional
Backward directionalNon-directionalDiseng. ratio Py PSx: 0.05...0.95Qy PSx: 0.010...0.500 Snom /BlockedOperate delay Qy PSx: 0.00...100.00 s / Block.Release delay Qy PSx: 0.00...10.00 sDirection Qy PSx:
Forward directionalBackward directionalNon-directional
Diseng. ratio Qy> PSx: 0.05tTransient pulse PSx: 0.00...100.00 s
Over-/ underfrequency protection f<>):
Enable PSx: No/Yesvalid for y = ‚1‘ to ‚4‘ Oper. mode fy PSx:
ff with df/dtf w. Delta f/Delta t
fy PSx: 40.00...70.00 Hz / Blockedtfy PSx: 0.00...10.00 s / Blockeddfy/dt PSx: 0.1...10.0 Hz/s / BlockedDelta fy PSx: 0.01...5.00 Hz / BlockedDelta ty PSx: 0.04...3.00 s
Control
Main function MAIN):
BI active USER: No/YesInp.asg. fct.block.1: see selection tableInp.asg. fct.block.2: see selection tableOp. delay fct. block: 0...60 sPerm.No.mot.drive op: 1...20Mon.time mot.drives: 1...20 minCool.time mot.drives: 0...10 minMon.time motor relay: 0.01...2.00 s
External device DEV01 to DEV03):
Designat. ext. dev.: see selection tableDEV-Name User: Configurable (4 Char. max)Op.time switch. dev.: 0...254 sLatching time: 0.00...25.4 sGr. assign.debounce: Group 1...Group 8Interm. pos. suppr.: No/YesStat.ind.interm.pos.: No/YesOper.mode cmd:
Long command/ Short command/ Time controlInp.asg. sw.tr. plug: see selection tableInp.asg.el.ctrl.open: see selection table
Inp.asg.el.ctr.close: see selection tableInp. asg. end Open: see selection tableInp. asg. end Close: see selection tableOpen w/o stat.interl: No/YesClose w/o stat. int.: No/YesFct.assig.BIwSI open: see selection tableFct.assig.BIwSI clos: see selection tableFct.asg.BI w/o SI op: see selection tableFct.asg.BI w/o SI cl: see selection table
Interlocking logic ILOCK):
valid for y = ‚1‘ to ‚32‘ ‘ Fct.assignm. outp. y: see selection table
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 31/44
[One-Box Solutions for Protection and Control] MiCOM P132 31
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Operation
Measured Operating DataProtection Communication interface InterMiCOM COMM 3):
No. tel.errors p.u.: 0...100 %No.t.err. max,stored: 0...100 %Loopback result:
Not measuredPassedFailed
Loopback receive:0...255 / not measured
Measured Data Input MEASI):
Current IDC: 0.00...24.00 mACurrent IDC p.u.: 0.00...1.20 IDC,nomCurr. IDC,lin. p.u.: 0.00...1.20 IDC,nomScaled value IDC,lin: -32000...32000Temperature T: -40.0...215.0 °CTemperature Tmax : -40.0...215.0 °CTemperature p.u. T: -0.40...2.15 100 °Cvalid for y = ‚1‘ to ‚9‘
Temperature Ty: -40.0...215.0 °CTemp. Ty max.: -40.0...215.0 °CTemperature p.u. Ty: -0.40...2.15 100°C
Measured Data Output MEASO):
Current A-1: 0.00...20.00 mACurrent A-2: 0.00...20.00 mA
Main Function MAIN):
Date: 01.01.1997...31.12.2096 dd.mm.yyTime: 00:00:00...23:59:59 hh:mm:ssTime switching: Standard time/Daylight saving timeFrequency f: 40.00...70.00 HzCurr. IP,min prim.: 0...25000 AIP,maxprim, demand: 0...25000 AIP,maxprim,demand st: 0...25000 ACurr. IP,min prim.: 0...25000 ACurrent A prim.: 0...25000 ACurrent B prim.: 0...25000 A
Current C prim.: 0...25000 ACurrent Σ (IP) prim.: 0...100 ACurrent IN prim.: 0...2500 A
Volt. VPG,max prim.: 0.0...2500.0 kV Volt. VPG,min prim.: 0.0...2500.0 kV Voltage A-G prim.: 0.0...2500.0 kV Voltage B-G prim.: 0.0...2500.0 kV Voltage C-G prim.: 0.0...2500.0 kV
Volt. Σ(VPG)/3 prim.: 0.0...2500.0 kV Voltage VNG prim.: 0.0...2500.0 kV Voltage Vref prim.: 0.0...3000.0 kV Volt. VPP,max prim.: 0.0...2500.0 kV Volt. VPP,min prim.: 0.0...2500.0 kV Voltage A-B prim.: 0.0...2500.0 kV Voltage B-C prim.: 0.0...2500.0 kV Voltage C-A prim.: 0.0... 2500.0 kV
Appar.power S prim.: -1399.9...1400.0 MVA Active power P prim.: -999.9...1000.0 MWReac. power Q prim.: -999.9...1000.0 Mvar
Act.energy outp.prim: 0.00...6.553.500,00 MWh Act.energy inp. prim: 0.00... 6.553.500,00 MWhReact.en. outp. prim: 0.00... 6.553.500,00 Mvar hReact. en. inp. prim: 0.000... 6.553.500,00 Mvar hFrequency f p.u.: 0.200...4.000 fnomCurrent IP,max p.u.: 0.000...25.000 InomIP,maxp.u.,demand st: 0.000...25.000 InomIP,max p.u.,demand: 0.000...25.000 InomCurrent A p.u.: 0.000...25.000 InomCurrent B p.u.: 0.000...25.000 InomCurrent C p.u.: 0.000...25.000 Inom
Current Σ (IP) p.u.: 0.000...25.000 InomCurrent IN unfilt.: 0.000...16.000 IN,nom
Current IN p.u.: 0.000...16.000 IN,nomCurrrent Ipos p.u.: 0.000...25.000 InomCurrrent Ineg p.u.: 0.000...25.000 Inom
Voltage VPG,max p.u.: 0.000...25.000 Vnom
Voltage VPG,min p.u.: 0.000...25.000 Vnom Voltage A-G p.u.: 0.000...25.000 Vnom Voltage B-G p.u.: 0.000...25.000 Vnom Voltage C-G p.u.: 0.000...25.000 Vnom
Volt. Σ(VPG)/ √3 p.u.: 0.000...12.000 Vnom Voltage VNG p.u.: 0.000...25.000 VNG,nom Voltage Vref p.u.: 0.000...3.000 Vnom Voltage VPP,max p.u.: 0.000...25.000 Vnom Voltage VPP,min p.u.: 0.000...25.000 Vnom
Voltage A-B p.u.: 0.000...25.000 Vnom Voltage B-C p.u.: 0.000...25.000 Vnom Voltage C-A p.u.: 0.000...25.000 Vnom Voltage Vpos p.u.: 0.000...25.000 Vnom Voltage Vneg p.u.: 0.000...25.000 Vnom Appar. power S p.u.: -10.700...10.700 Snom Active power P p.u.: -7,500...7.500 SnomReac. power Q p.u.: -7.500...7.500 Snom
Active power factor: -1.000...1.000Load angle phi A: -180...180 °Load angle phi B: -180...180 °Load angle phi C: -180...180 °
Angle phi N: -180...180 °
Angle Σ VPG vs. IN: -180...180 °
Phase rel.,IN vs ΣIP:Equal phase / Reverse phase
Current ΣI unfilt. 0.000...25.000 Inom
Ground fault direction determination using
steady-state values (GFDSS):Current IN,act p.u.: 0.000...30.000 IN,nomCurr. IN,reac p.u.: 0.000...30.000 IN,nomCurr. IN filt. p.u.: 0.000...20.00 mA
Admitt. Y(N) p.u.: 0.000... 5.000 YN,nomConduct. G(N) p.u.: -5.000... 5.000 YN,nomSuscept. B(N) p.u.: -5.000... 5.000 YN,nom
Motor Protection MP):
Therm.repl.buffer MP: 0...100 %St-ups still permitt: 0...3Therm. repl. MP p.u.:0.00...1.00 100%St-ups st. perm.p.u.: 0.00...0.30 factor 10
Thermal overload protection THERM):
Status THERM replica: -25000...25000 %Current I, therm prim: 0…25000AObject temperature: -40...300 °CCoolant temperature: -40...200 °CPre-trip time left: 0.0...1000.0 minTherm. replica p.u.: -2.50...2.50 100 %Current I, therm p. u.: 0…2.4 IBObject temp. p.u.: -0.40...3.00 100 °CCoolant temp.p.u.: -0.40...0.20 100 °CTemp. offset replica: -25000...25000 %
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 32/44
[One-Box Solutions for Protection and Control] MiCOM P132 32
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Dimensional drawings
Surface-mounted case 24 T
Surface-mounted case 40 T
139.6
168.8
186.4
257.1
TRIP
ALARM
OUT OF SERVICE
HEALTHY
EDIT MODE
Mi
Pa
CO
ra
M
me
P1
te
32
rs
213.4
242.6
260.2
257.1
TRIP
ALARM
OUTOFSERVICE
HEALTHY
EDIT MODE
Mi
Pa
CO
ra
M
me
P1
te
32
rs
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 33/44
[One-Box Solutions for Protection and Control] MiCOM P132 33
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Dimensional drawings
Surface-mounted case 84 T
Flush-mounted case 24T with panel cutout, version 1 (without angle brackets)
227.9
253.6
129.2
77.5
5.0
5.0
103.8
139.6
TRIP
ALARM
OUT OF SERVICE
HEALTHY
EDIT MODE
Mi
Pa
CO
ra
M
me
P1
te
32
rs
434.8
464.0
481.6
257.1
TRIP
ALARM
OUTOF SERVICE
HEALTHY
EDITMODE
Mi
Pa
CO
ra
M
me
P1
te
32
rs
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 34/44
[One-Box Solutions for Protection and Control] MiCOM P132 34
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Dimensional drawings
Flush-mounted case 40T with panel cutout, version 1 (without angle brackets)
Flush-mounted case 84T with panel cutout, version 1 (without angle brackets)
227.9
253.6
213.4
203.0
155.4
5.0
5.0
181.3
TRIP
ALARM
OUTOF SERVICE
HEALTHY
EDITMODE
Mi
Pa
CO
ra
M
me
P1
te
32
rs
227.9
253.6
434.8
284.9
259.0
5.0
5.0
25.9
410.0
TRIP
ALARM
OUTOFSERVICE
HEALTHY
EDITMODE
Mi
Pa
CO
ra
M
me
P1
te
32
rs
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 35/44
[One-Box Solutions for Protection and Control] MiCOM P132 35
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Dimensional drawings
Flush-mounted case 24T with panel cutout, Version 2 (with angle brackets and frame)
Flush-mounted case 40T with panel cutout, Version 2 (with angle brackets and frame)
227.9
253.6
139.6
168.8
186.4
6.4
150.7
168.8
TRIP
ALARM
OUT OF SERVICE
HEALTHY
EDIT MODE
Mi
Pa
CO
ra
M
me
P1
te
32
rs
227.9
253.6
6.4
224.5
242.6
213.4
242.6
260.2
TRIP
ALARM
OUT OFSERVICE
HEALTHY
EDIT MODE
Mi
Pa
CO
ra
M
me
P1
te
32
rs
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 36/44
[One-Box Solutions for Protection and Control] MiCOM P132 36
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Dimensional drawings
Flush-mounted case 84T with panel cutout, Version 2 (with angle brackets and frame)
227.9
253.6
1 7 7 . 5
1 0 1 . 6
6.4
445.9
464.0
1 0 1 . 6
1 8 6 . 5
434.8
464.0
481.6
TRIP
ALARM
OUT OF SERVICE
HEALTHY
EDITMODE
Mi
Pa
CO
ra
M
me
P1
te
32
rs
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 37/44
[One-Box Solutions for Protection and Control] MiCOM P132 37
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Detachable HMI with panel cutout
Front view 40T case for connection of a detachable HMI
Dimensional drawings
Front view 84T case for connection of a detachable HMI
TRIP
ALARM
OUT OFSERVICE
HEALTHY
WARNING:Connectionforremotecontrolpanel only.Not fornetworkconnection!
TRIP
ALARM
OUTOFSERVICE
HEALTHY
WARNING:Connectionforremotecontrolpanel only.Not fornetworkconnection!
206.0 20.7
46.3
1 7 7 . 5
197.5
3.0
181.3
1 4 8 . 0
1 6 8 . 0
1 0 7 . 3
192.5
Aus-Kommando
Warnung
Block./Störung
Betrieb
Änderungsmod.
MiPa
COra
Mme
P1te
32rs
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 38/44
[One-Box Solutions for Protection and Control] MiCOM P132 38
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
X_1
1
2
3
4
5
6
7
8
9
X_1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Ring
Type X
High-break
contacts
Pin
X_3
1
2
3
4
5
6
7
8
9
X_2
1
2
3
4
5
6
7
8
9
K_01
4H
K_02
K_04
K_03
+
+
+
+
Binary
module
X_1
1
2
3
4
5
6
7
8
9
X_1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Ring
Output relays
Pin
X_3
1
2
3
4
5
6
7
8
9
X_2
1
2
3
4
5
6
7
8
9
K_01
K_02
K_03
K_04
K_05
K_06
1)
1)
1)
1)
Type X 6O
Binary
module
Binary
module
Type X6I / 3O
X_1
1
2
3
4
5
6
7
8
9
X_1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Ring Pin
X_3
1
2
3
4
5
6
7
8
9
X_2
1
2
3
4
5
6
7
8
9
Signal-
inputs
U_01
U_02
U_03
U_04
U_05
U_06
Output relays
K_01
K_02
K_03
Vin
Vin
Vin
Vin
Vin
Vin
X_1
1
2
3
4
5
6
7
8
9
X_1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Ring
K_01
K_02
K_03
K_04
K_05
K_06
K_07
K_08
Power supply
Type V
U100
Power supply
module
Signal inputs
U_01
U_02
U_03
U_04
Output relays
Pin
X_3
1
2
3
4
5
6
7
8
9
X_2
1
2
3
4
5
6
7
8
9Vin
Vin
Vin
Vin
PE
Vaux
4I / 8O
+-
X041
13
14
15
16
17
18
11
12
1
2
3
4
5
6
7
8
Ring
Type T
Pin
X042
1
2
3
4
5
6
7
8
Current measuring
inputs
VA
VB
VC
VNG
VRef
IA
IB
IC
IN
T1
T2
T3
T4
Voltage measuring
inputs
4J / 4/5V
Transformer
module
T5
T6
T7
T90
T15
X041
1
2
3
4
5
6
7
8
Option:
Connection of the modules
’_’ is used as a wildcard for the location (slot number)
1) Binary module X (6O) optional with 4 static outputs, in parallel with closer contact K_02.2, K_03.1, K_04, K_05
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 39/44
[One-Box Solutions for Protection and Control] MiCOM P132 39
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
X8
TX
Type A
IEC 61850
optical fiber link ST
Per order
COMM2
wire link
or
optical fiber link SC
X//Y
RS 485
D2[R]
X10
1
2
3
4
5 D1[T]
U20
U17X/Y
U18X/Y
X7
RX
Communication
module ETH / CH2
X12
1
U26
X/Y
U25X//Y
X13
RX
TX
and wire link
RJ45
X11
1
X8
1
Type A
Channel 1
optical fiber link
Per order
##
IRIG-B
time synchronization
Channel 2
wire link only
or wire link
X//Y
RS 485
D2[R]
X10
1
2
3
4
5 D1[T]
U20
X//Y
RS 485
D2[R]
X9
1
2
3
4
5 D1[T]
U19
U17X//Y
U18X//Y
X7
1
U21
Communication
module CH1 / CH2
X_3
1
2
3
4
5
6
X_2
1
2
3
4
5
6
7
8
9
X_11
2
3
4
5
6
7
8
9
X_11
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Ring
Analog
module
U_01
U_02
U_03
U_04
Pin
Type Y4I
Signal and measuring
inputs
Measuring outputs
K_01
U_080..20 mA
valid
K_02
U_090..20 mA
valid
U
# U
#
U_05
U_06
U
#
U
#
0..20 mA
PT100
Vin
Vin
Vin
Vin
X_1
1
2
3
4
5
6
7
8
9
X_1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Ring
Binary
module
Signal inputs
Pin
X_3
1
2
3
4
5
6
7
8
9
X_2
1
2
3
4
5
6
7
8
9
Type X24I
U_17
U_18
U_19
U_20
U_21
U_22
U_23
U_24
U_01
U_02
U_03
U_04
U_05
U_06
U_07
U_08
U_09
U_10
U_11
U_12
U_13
U_14
U_15
U_16
Vin
Vin
Vin
X_11
2
3
4
5
6
7
8
9
X_11
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Ring
Type X
Pin
X_3
X_2
1
2
3
4
5
6
7
8
9
6I / 6H
Binary
module
19
20
21
22
23
24
25
26
27
_
1
2
3
4
5
6
7
8
9
High-break
contacts
K_01
K_02
K_03
K_04
K_05
K_06
U_01
U_02
U_03
U_04
U_05
U_06
UE
UE
UE
UE
UE
UE
Signal inputs
+
+
+
+
+
+
X_11
2
3
4
5
6
7
8
9
X_11
2
3
4
5
6
7
8
9
10
11
12
13
14
15
15
17
18
19
20
21
22
23
24
25
26
27
Output relays
X_3
1
2
3
4
5
6
7
8
9
X_2
1
2
3
4
5
6
7
8
9
K_01
K_02
K_03
K_04
K_05
K_06
Signal inputs
U_01
U_02
U_03
U_04
U_05
U_06
Ring Pin
Vin
Vin
Vin
Vin
Vin
Vin
Binary
module
Type X6I / 6O
Connection of the modules
X_11
2
3
4
5
6
7
8
9
Type YRTD
module
Temperature
measuring inputs
Pin
X_3
1
2
3
4
5
6
7
8
9
X_2
1
2
3
4
5
6
7
8
9
U81
U82
U83
U84
U85
U86
U87
U88
U89
9T
U
# U
# U
#
U
# U
# U
#
U
# U
# U
#
T1
T2
T3
T4
T5
T6
T7
T8
T9
X_11
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Ring
X32
1
Type A
COMM3optical fiber link
Per order
or wire link
or wire link
X//Y
RS 485
D2[R]
X33
1
2
3
4
5 D1[T]
U24
U22X//Y
U23X//Y
X31
1
Communication
module CH3
U27
D1[T]
D2[R]
RS 232
E2[G]
X//Y
M5[DCD]
+UB
X34
1
2
3
4
5
7
E
X_1
1
2
3
4
5
6
7
8
9
X_1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Ring
K_01
K_02
K_03
K_04K_05K_06K_07
K_08
Binary
module
U_01
U_02
U_03
U_04
U_05
U_06
Output relaysPin
X_3
1
2
3
4
5
6
7
8
9
X_2
1
2
3
4
5
6
7
8
9
Type X6I / 8O
Signal inputs
Vin
Vin
Vin
Vin
Vin
Vin
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 40/44
[One-Box Solutions for Protection and Control] MiCOM P132 4
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Connection Examples
Voltage and Current Transformer
Optional Control Function
I >
L1
L2
L3
I >I >
I >
U
V
W
N
e
n
1I 1
1I 2
1I 3
1IE
P 132( Detail)
X 042 :
X 041 :
X 091 :
X 091 :
2
4
1
3
1
5
8
4
7
3
6
2
1
5
4
3
6
2
( Detail)
UE
UE
UE
UE
OPEN
X 061 :
X 061 :
X 061 :
X 061 :
5
6
3
4
1
2
CLOSE
X 063 :
X 063 :
X 063 :
X 063 :
X 063 :
X 063 :
X 063 :
X 063 :
X 063 :
1
2
7
6
5
4
3
8
9
Dashed lines: recommended for GFDSS only(GFDSS: ground fault direction determination using steady-state values)
Gen. trip command 1
Power supply
Power supply
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 41/44
[One-Box Solutions for Protection and Control] MiCOM P132 41
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Feeder Management and Bay Control P132 P 1 3 2 9 0 308 4xx 632 47x 46x 9x x 9x x 8xx
Basic device:
Basic device 24TE, pin-terminal connection, 1 -420
Basic device 24TE, CT/VT ring-, I/O pin-terminal connection, 2 -421
Basic device 40TE, pin-terminal connection, 3 -425
Basic device 40TE, CT/VT ring-, I/O pin-terminal connection, 5 -426
Basic device 84TE, ring-terminal connection, 8 -427
basic complement with 4 binary inputs, 8 output relays
and 6 function keys16)
Mounting option and display:
Surface-mounted, local control panel with text display 3
Flush-mounted, local control panel with text display 4
Surface-mounted, with detachable HMI16) 7
Flush-mounted, with detachable HMI16)
9
Current transformer:
Without11)
0
Inom = 1 A / 5 A (T1...T4) 2)
9
Voltage transformer:
Without11)
0
Vnom = 50 ... 130 V (4-pole) 4
Vnom = 50 ... 130 V (5-pole) for automatic synchronism control20)
5
Additional binary I/O options16)
:
Without 0
With 1 binary module (add. 6 binary inputs and 8 output relays) 1
With 2 binary modules (add. 12 binary inputs and 16 output relays) 2
With 1 binary module (add. 6 binary inputs and 6 output relays (2-pole)) 5
for the control of up to 3 additional switchgear units
With 1 binary module (add. 6 binary inputs and 6 output relays (2-pole)) 6
and 1 binary module (add. 6 binary inputs and 6 output relays (2-pole))
for the control of up to 3 switchgear units
With 1 binary module (add. 6 binary inputs and 8 output relays) 8
and 1 binary module (add. 6 binary inputs and 6 output relays (2-pole)) for the control of up to 3 switchgear units
Power supply and additional binary I/O options:
VA,nom = 24 VDC 3
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC 4
VA,nom = 24 VDC and 6 output relays, 4 with thyristor 6
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC 7
and 6 output relays, 4 with thyristor
VA,nom = 24 VDC and 6 output relays 8
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC and 6 output relays 9
VA,nom = 24 VDC and 6 binary inputs and 3 output relays A
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC B
and 6 binary inputs and 3 output relays
VA,nom = 24 VDC and 4 high break contacts C
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC and 4 high break contactsD
Further add options
16):
Without 0
With TGF (transient ground fault direction determination) module3) 10)
1
With analog module 2
With TGF and analog module 3) 10)
3
With binary module (add. 24 binary inputs) 4
With TGF and binary module (add. 24 binary inputs)3) 10)
5
With RTD module 3) 20)
7
With RTD and analog module3) 20)
8
With RTD module and binary module (add. 24 binary inputs)3) 20) 9
Ordering information MiCOM P132
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 42/44
[One-Box Solutions for Protection and Control] MiCOM P132 42
P132_TechnicalDataSheet_EN_32_B.doc Schneider Electric Energy P132 -308 -420/-421/-425/-426/-427 -632 ff
Feeder Management and Bay Control P132 P 1 3 2 9 0 308 4xx 632 47x 46x 9x x 9x x 8xx
Binary modules with single pole high break contacts for control
19):
Without high break contact characteristic Without order extension No.
With 1 module with high break contacts (1-pole) -471
With 2 modules with high break contacts (1-pole) -472
Switching threshold on binary inputs:
>18 V (standard variant) Without order extension No.
>90 V (60...70% of VA,nom = 125...150 V)8) -461
>155 V (60...70% of VA,nom = 220...250 V)8) -462
>73 V (67% of VA,nom = 110 V)8) -463
>73 V (67% of VA,nom = 110 V)8) -463
>146 V (67% of VA,nom = 220 V)8) -464
With communication / information interface:
Without Without order extension No.
Protocol can be switched between: -92
IEC 60870-5-101/-103, Modbus, DNP3, Courier
and IRIG-B input for clock synchronization
and 2nd interface (RS485, IEC 60870-5-103)
For connection to wire, RS485, isolated 1
For connection to plastic fiber, FSMA connector 2
For connection to glass fiber, ST connector 4
Protocol IEC61850 -94
For connection to 100 MHz Ethernet, glass fiber SC and wire RJ45 6
and 2nd interface (RS485, IEC 60870-5-103)
For connection to 100 MHz Ethernet, glass fiber ST and wire RJ45 7
and 2nd interface (RS485, IEC 60870-5-103)
With guidance / protection interface
16):
Without Without order extension No.
Protocol InterMiCOM -95
For connection to wire, RS485, isolated 1
For connection to plastic fiber, FSMA connector 2
For connection to glass fiber, ST connector 4
For connection to wire, RS232, isolated 5
Language:
English (German) 4)
Without order extension No.
Px40 English (English) 4)
Not yet available - on request -800
German (English) 4) -801
French (English) 4)
Not yet available - on request -802
Spanish (English) 4) Not yet available - on request -803
Polish (English) 4)
Not yet available - on request -804
Russian (English) 4) 7) Not yet available - on request -805
2) Switching via parameter, default setting is underlined!
3) This option is excluded if the InterMiCOM (-95x) is ordered
4) Second included language in brackets
7) Hardware option, supports Cyrillic letters instead of special West. European characters
8) Standard variant recommended if higher pickup threshold not explicitly required by the application
10) Transient ground fault option for variants with current and voltage transformers only
11) Option without current transformers and without voltage transformers not possible
16) Options for basic device 24 TE not possible
20) Option without current transformers not possible
Ordering information MiCOM P132
19) Depend on the selected numbers of binary modules (6 binary inputs and 6 output relays); Use of High break ouputs: 1-pole only
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 43/44
7/24/2019 MiCOM P132_TechnicalDataSheet
http://slidepdf.com/reader/full/micom-p132technicaldatasheet 44/44
© 2
0 1 1 S c h n e i d e r E l e c t r i c .
A l l r i g h t s r e s e r
e v e d